05000247/FIN-2015007-02
From kanterella
Jump to navigation
Jump to search
Finding | |
|---|---|
| Title | Inadequate design verification that adequate voltages would be available to all Class 1E motors, MOVs, static loads, and MCC control circuits and contactors at the minimum DVR dropout setting |
| Description | The team identified a finding of very low safety significance (Green) involving a non-cited violation of 10 CFR Part 50, Appendix B, Criterion III, Design Control, because Entergy did not verify the adequacy of their electrical design. Specifically, Entergy failed to verify, in design basis calculations and/or periodic testing, that adequate voltages would be available to all Class 1E motors, motor-operated valves (MOVs), static loads, and motor control center (MCC) control circuits and contactors powered from the 480 volt distribution system with the voltage at the 480 volt safety-related switchgear operating at the minimum degraded voltage dropout setting including tolerances. After identification, Entergy entered the issues into the corrective action program and performed several additional evaluations to verify adequate voltage to Class 1E motors, MOVs, static loads, and MCC control circuits. The performance deficiency was determined to be more than minor in accordance with IMC 0612, Power Reactor Inspection Reports, Appendix B, and Appendix E, example 3j, because the engineering calculation error resulted in a condition where there was a reasonable doubt on the operability of a system. In addition, the performance deficiency was associated with the design control attribute of the Mitigating Systems Cornerstone and adversely affected the cornerstone objective of ensuring the availability, reliability, and capability of systems that respond to initiating events to prevent undesirable consequences. The team evaluated the finding in accordance with IMC 0609, Appendix A, The Significance Determination Process for Findings at Power, Exhibit 2 Mitigating Systems Screening Questions. The finding was determined to be of very low safety significance because it was a design deficiency confirmed not to result in a loss of operability. The finding has a cross-cutting aspect in the area of Problem Identification and Resolution, Operating Experience, because Entergy did not systematically and effectively collect, evaluate, and implement relevant internal and external operating experience in a timely matter. Specifically, Entergy did not systematically and effectively evaluate NRC Regulatory Issue Summary 2011-12, Revision 1, Adequacy of Station Electric Distribution System Voltages. |
| Site: | Indian Point |
|---|---|
| Report | IR 05000247/2015007 Section 1R21 |
| Date counted | Sep 30, 2015 (2015Q3) |
| Type: | NCV: Green |
| cornerstone | Mitigating Systems |
| Identified by: | NRC identified |
| Inspection Procedure: | IP 71111.21 |
| Inspectors (proximate) | D Werkheiser G Nicely J Ayala J Brand J Schoppy M Orr M Yeminy P Krohn |
| Violation of: | 10 CFR 50 Appendix B Criterion III, Design Control |
| CCA | P.5, Operating Experience |
| INPO aspect | CL.1 |
| ' | |
Finding - Indian Point - IR 05000247/2015007 | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Finding List (Indian Point) @ 2015Q3
Self-Identified List (Indian Point)
| ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||