text

- - _ - _ _ _ _ - _ _ . _ _ - .

Omaha Pub!!c Power District 444 South 16th Street Mall Omaha, Nebraska 68102-2247 January 14, 1993 402/636-2000 LIC-93-001 U. S. Nuclear Regulatory Commission ATTN: Document Control Desk Mail Station Pl-137 Washington, DC 20555

References:

1. Docket No. 50-285.
2. , dated Letter 7,1975, January from OPPD Abnormal(W. C. Jones)

Occurrence Reportto50-285/75-AEC (E. M. Howard)1 (FC 75A).

3. Letter from OPPD (W. C. Jones) to NRC (E. M. Howard), dated May 5, 1977, LER 50-285/77-9 (FC-266-77).
4. Letter from 0 PPD (S. C. Stevens) to NRC (K. V. Seyfrit), dated
5. November Fort Calhoun7, 1980, LER Station 80-027 (FC-Il48-80)

Technical Specificat ion 3.1, Table 3-2, item 10.

Gentlemen:

SUBJECT:

Surveillance Test Requirements for the AC Sequencer Timing Relays Prior to 1977, Omaha Public Power District AC sequencer timing relays on a quarterly (basis as required by ReferenceA5.0 PPD) tcsted the number of failures of these electromechanical devices occurred during the mid-1970's (References 2, 3 and 4). In Licensee Event Report 77-09, OPPD committed to perform monthly testing as a corrective action.

In May 1990, OPPD completed modification MR-fC-83-074 which replaced the original relays with more reliable solid state relays. Since the new relays were installed, the setpoints have not varied and there have been no failures.

Therefore, the monthly testing frequency is no longer warranted. Accordingly, OPPD is revising the referenced commitment to test the relays quarterly as required by Reference 5.

If you should have any questions, please contact me.

Sincerely, 4V.

W. G. Gates A b Vice President WGG/grc c: LeBoeuf, Lamb, Leiby & MacRae J. L. Milhoan, NRC Regional Administrator, Region IV R. P. Mullikin, NRC Senior Resident inspector S. D. Bloom, NRC Project Manager 21000 9301250023 9aoi14 PDR U ADOCK 05000285 am PDR \\0 twqggewcm f  ;

- _ _ _