ML13088A133

From kanterella
Jump to navigation Jump to search
IR 05000369-13-007 and 05000370-13-007; 01/28 - 02/01/2013 and 02/11 - 15/2013; McGuire Nuclear Station Units 1 and 2; Fire Protection (Triennial)
ML13088A133
Person / Time
Site: Mcguire, McGuire  Duke Energy icon.png
Issue date: 03/27/2013
From: Mark King
NRC/RGN-II/DRS/EB2
To: Capps S
Duke Energy Corp
References
IR-13-007
Download: ML13088A133 (33)


See also: IR 05000369/2013007

Text

UNITED STATES

NUCLEAR REGULATORY COMMISSION

REGION II

245 PEACHTREE CENTER AVENUE NE, SUITE 1200

ATLANTA, GEORGIA 30303-1257

March 27. 2012

EA-13-050

Mr. Steven D. Capps

Site Vice President

Duke Energy Corporation

McGuire Nuclear Station

MG01VP/12700 Hagers Ferry Road

Huntersville, NC 28078

SUBJECT: MCGUIRE NUCLEAR STATION - NRC TRIENNIAL FIRE PROTECTION

INSPECTION REPORT 05000369/2013007 & 05000370/2013007 AND

EXERCISE OF ENFORCEMENT DISCRETION

Dear Mr. Capps:

On February 15, 2013, the U.S. Nuclear Regulatory Commission (NRC) completed an

inspection at your McGuire Nuclear Station Units 1 and 2. The enclosed inspection report

documents the inspection results which were discussed on February 15, 2013, with you and

other members of your staff.

The inspection examined activities conducted under your license as they relate to safety and

compliance with the Commissions rules and regulations and with the conditions of your license.

The inspectors reviewed selected procedures and records, observed activities, and interviewed

personnel.

The enclosed report documents one NRC-identified finding of very low safety significance

(Green) that was determined to involve a violation of NRC requirements. The NRC is treating

this violation as a non-cited violation (NCV) consistent with Section 2.3.2 of the NRC

Enforcement Policy. If you contest the violation or significance of this NCV, you should provide

a response within 30 days of the date of this inspection report, with the basis for your denial, to

the Nuclear Regulatory Commission, ATTN.: Document Control Desk, Washington DC 20555-

001; with copies to the Regional Administrator Region II; the Director, Office of Enforcement,

United States Nuclear Regulatory Commission, Washington, DC 20555-0001; and the NRC

Resident Inspector at the McGuire Nuclear Station.

The enclosed report also documents one noncompliance for which the NRC is exercising

enforcement discretion in accordance with Section 9.1 of the NRC Enforcement Policy,

Enforcement Discretion for Certain Fire Protection Issues (10 CFR 50.48). The noncompliance

is associated with your implementation of the requirements and standards of 10 CFR 50,

Appendix R, Fire Protection Program for Nuclear Power Facilities Operating Prior to January 1,

1979. The non-compliance was identified by the licensee, and is a violation of

NRC requirements. The inspectors have screened the violation and determined that it

warranted enforcement discretion per the Interim Enforcement Policy Regarding Enforcement

S. Capps 2

Discretion for Certain Fire Protection Issues, and Section 11.05(b) of Inspection Manual Chapter 0305 Operating Reactor Assessment Program..

You are not required to respond to this letter. In accordance with 10 CFR 2.390 of the NRC's

"Rules of Practice," a copy of this letter, its enclosure, and your response, if any, will be

available electronically for public inspection in the NRC Public Document Room or from the

Publicly Available Records (PARS) component of NRC's document system (ADAMS). ADAMS

is accessible from the NRC Website at http://www.nrc.gov/reading-rm/adams.html (the

Public Electronic Reading Room).

Sincerely,

/RA/

Michael F. King, Chief

Engineering Branch 2

Division of Reactor Safety

Docket Nos.: 50-369 & 370

License Nos.: NPF-9, NPF-17

Enclosure: Inspection Report 05000369/2013007

and 05000370/2013007 w/Attachment:

Supplemental Information

cc: (See page 3)

_________________________ XG SUNSI REVIEW COMPLETE G FORM 665 ATTACHED

OFFICE RII:DRS RII:DRS RII:DRS RII:DRS RII:DRP

SIGNATURE /RA/ /RA/ /RA/ /RA/ /RA/

NAME JONES BRAXTON DYMEK MONTGOMERY BARTLEY

DATE 3/21/2013 3/20/2013 3/21/2013 3/20/2013 3/22/2013

E-MAIL COPY? YES NO YES NO YES NO YES NO YES NO YES NO YES NO

S. Capps 3

cc: Alicia Richardson

Charles J. Morris III Licensing Administrative Assistant

Plant Manager General Office

McGuire Nuclear Station Duke Energy Corporation

Duke Energy Corporation Electronic Mail Distribution

Electronic Mail Distribution

Lara S. Nichols

Jeffrey J. Nolin Deputy General Counsel

Design Engineering Manager Duke Energy Corporation

McGuire Nuclear Station Electronic Mail Distribution

Duke Energy Corporation

Electronic Mail Distribution David A. Cummings

Associate General Counsel

H. Duncan Brewer General Office

Organizational Effectiveness Manager Duke Energy Corporation

McGuire Nuclear Station Electronic Mail Distribution

Duke Energy Corporation

Electronic Mail Distribution Beth J. Horsley

Wholesale Customer Relations

Kenneth L. Ashe Duke Energy Corporation

Regulatory Compliance Manager Electronic Mail Distribution

McGuire Nuclear Station

Duke Energy Corporation David A. Repka

Electronic Mail Distribution Winston Strawn LLP

Electronic Mail Distribution

Kay L. Crane

Senior Licensing Specialist Senior Resident Inspector

McGuire Nuclear Station U.S. Nuclear Regulatory Commission

Duke Energy Corporation William B. McGuire Nuclear Station

Electronic Mail Distribution 12700 Hagers Ferry Rd

Huntersville, NC 28078

Joseph Michael Frisco, Jr.

Vice President, Nuclear Design Engineering County Manager of Mecklenburg County

General Office 720 East Fourth Street

Duke Energy Corporation Charlotte, NC 28202

Electronic Mail Distribution

W. Lee Cox, III

M. Christopher Nolan Section Chief

Director - Regulatory Affairs Radiation Protection Section

General Office N.C. Department of Environmental

Duke Energy Corporation Commerce & Natural Resources

Electronic Mail Distribution Electronic Mail Distribution

David A. Cummings (acting)

Fleet Regulatory Compliance & Licensing

Manager

General Office

Duke Energy Corporation

Electronic Mail Distribution

Letter to Steven D. Capps from Michael F. King dated March 27, 2013.

SUBJECT: MCGUIRE NUCLEAR STATION - NRC TRIENNIAL FIRE PROTECTION

INSPECTION REPORT 05000369/2013007 & 05000370/2013007 AND

EXERCISE OF ENFORCEMENT DISCRETION

Distribution:

RIDSNRRDIRS

PUBLIC

RidsNrrPMMcGuire Resource

U.S. NUCLEAR REGULATORY COMMISSION

REGION II

Docket Nos.: 50-369 & 370

License Nos.: NPF-9, NPF-17

Report Nos.: 05000369/2013007, 05000370/2013007

Licensee: Duke Energy Carolinas, LLC

Facility: McGuire Nuclear Station, Units 1 and 2

Location: Huntersville, NC 28078

Dates: January 28 - February 1, 2013 (Week 1)

February 11 - 15, 2013 (Week 2)

Inspectors: D. Jones, Senior Reactor Engineer (Lead Inspector)

P. Braxton, Reactor Inspector

J. Dymek, Reactor Inspector

J. Montgomery, Reactor Inspector

Approved by: Michael F. King, Chief

Engineering Branch 2

Division of Reactor Safety

Enclosure

SUMMARY OF FINDINGS

IR 05000369/2013007 and 05000370/2013007; 01/28 - 02/01/2013 and 02/11 - 15/2013;

McGuire Nuclear Station Units 1 and 2; Fire Protection (Triennial).

This report covers an announced two-week period of inspection by a triennial fire protection

team composed of four regional inspectors. One Green non-cited violation (NCV) was

identified. The significance of most findings is indicated by their color (Green, White, Yellow,

Red) using Inspection Manual Chapter (IMC) 0609, Significance Determination Process,

(SDP) dated 06/02/11. Findings for which the SDP does not apply may be Green or be

assigned a severity level after U.S. Nuclear Regulatory Commission (NRC) management

review. Cross-cutting aspects are determined using IMC 0310, Components Within The Cross-

Cutting Areas, dated 10/28/11. The NRC's program for overseeing the safe operation of

commercial nuclear power reactors is described in NUREG-1649, Reactor Oversight Process,

Revision 4, dated December 2006.

A. NRC-Identified and Self-Revealing Findings

Cornerstone: Mitigating Systems

Green. An NRC identified Green non-cited violation of McGuires Selected Licensing

Commitment 16.9.5, Fire Rated Assemblies was identified for the licensees inadequate

implementation of modifications that resulted in nonfunctional fire doors.

The licensee has entered the finding into the corrective action program as PIP M-13-

01454, declared the doors as nonfunctional and implemented fire watches for the fire

areas of concern.

The licensees inadequate implementation of fire door modifications that resulted in the

failure to meet the requirements of Selected Licensee Commitment 16.9.5, Fire Rated

Assemblies, was a performance deficiency. The performance deficiency was more than

minor because it adversely affected the Mitigating Systems cornerstone attribute of

Protection Against External Events. Specifically, the welding modifications performed on

nine fire doors adversely affected their capability to provide the required 3-hours of fire

resistance. In accordance with NRC IMC 0609 Appendix F, Part 1; Fire Protection

Significance Determination Process Phase 1 Worksheet the inspectors determined the

finding to be of very low safety significance (Green) because the fire doors would still

provide a minimum of 20 minutes fire endurance protection A cross-cutting aspect was

not assigned because the performance deficiency does not reflect current licensee

performance. (Section 1R05.02)

B. Licensee Identified Violations

None

Enclosure

REPORT DETAILS

1. REACTOR SAFETY

Cornerstones: Initiating Events, Mitigating Systems, Barrier Integrity

1R05 Fire Protection

This report presents the results of a triennial fire protection inspection of the McGuire

Nuclear Station Units 1 and 2. The inspection was conducted in accordance with NRC

Inspection Procedure (IP) 71111.05T, Fire Protection (Triennial), issued October 28,

2011. The objective of the inspection was to review a minimum sample of four risk-

significant fire areas to verify implementation of the fire protection program (FPP) and to

verify site specific implementation of at least one B.5.b mitigating strategy as well as the

storage, maintenance, and testing of B.5.b mitigating equipment. The four fire areas

(FAs) were selected after reviewing risk information analyzed by a Senior Reactor

Analyst from Region II, as well as previous inspection results, plant walk downs of fire

areas, relational characteristics of ignition sources to targets, and location of equipment

needed to achieve and maintain safe shutdown (SSD) of the reactor. In selecting the

B.5.b mitigating strategy sample, the team reviewed licensee submittal letters, safety

evaluation reports, licensee commitments, B.5.b implementing procedures, and previous

NRC inspection reports. The IP specifies a minimum sample size of three fire areas and

one B.5.b implementing strategy for addressing large fires and explosions. This

inspection fulfilled the requirements of the procedure. The specific FAs chosen for

review were:

1. FA 5, Unit 1 Train A Diesel Generator Room (Elevation 733.0)

2. FA 16-18, Unit 2 Train A Switchgear & Penetration Room (ETB) (Elevation

750.0)

3. FA 20, Unit 2 Cable Room (Elevation 750.0)

4. FA Turbine Building 1, 7KV Switchgear Room, (Elevation 760.0)

The team evaluated the licensees FPP against applicable requirements, including

McGuire Unit 1 and 2 Operating License Condition 2.C.4, Fire Protection; Title 10 of

the Code of Federal Regulations (10 CFR) Part 50, Appendix R, Sections III.G., J., L.

and O; 10 CFR 50.48; commitments to Appendix A of Branch Technical Position (BTP)

Auxiliary and Power Conversion Systems Branch (APCSB) 9.5-1; McGuire Units 1 and 2

Updated Final Safety Analysis Report (UFSAR); related NRC safety evaluation reports

(SERs); Technical Specifications and Selected Licensee Commitments (SLC). The

review of the B.5.b mitigating strategies was based on the McGuire B.5.b submittal

letters, related NRC SERs, licensee commitments, B.5.b implementing procedures, and

previous NRC inspection reports. The team evaluated all areas of this inspection, as

documented below, against these requirements. Specific licensing bases documents

reviewed are listed in the Attachment.

Enclosure

4

.01 Protection of Safe Shutdown Capabilities

a. Inspection Scope

For the selected FAs, the inspectors performed physical walk-downs to observe: (1) the

material condition of fire protection systems and equipment; (2) the storage of

permanent and transient combustibles; (3) the proximity of fire hazards to cables relied

upon for SSD; and (4) the licensees implementation of procedures and processes for

limiting fire hazards, housekeeping practices, and compensatory measures for

inoperable or degraded fire protection systems and credited fire barriers. The specific

documents reviewed are listed in the Attachment.

Methodology

The team evaluated the potential for fires, the combustible fire load characteristics, and

the potential fire severity exposure for the selected FAs. The team reviewed Design

Basis Document (DBD) MCS-1465-00-00-0008; the UFSAR applicable SERs; and plant

administrative procedures that (1) established and implemented controls and practices to

prevent fires and (2) controlled ignition sources and the storage of permanent and

transient combustible materials. These evaluations were performed to ensure that the

objectives established by the NRC approved FPP were satisfied and to ensure that the

licensee had properly characterized in-situ combustible fire loads and limited transient

fire hazards in a manner consistent with the plant administrative and FPP procedures.

For each of the selected FAs the team reviewed the fire hazards analysis, SSD analyses

and supporting drawings and documentation to verify whether the shutdown

methodology had properly identified and protected the components necessary to achieve

and maintain SSD conditions for equipment in the FAs selected for review.

Operational Implementation

The inspectors reviewed applicable sections of abnormal and emergency procedures, to

verify that the shutdown methodology properly identified the systems and components

necessary to achieve and maintain SSD conditions. The inspectors performed a walk-

through of abnormal procedure steps to verify implementation and human factors

adequacy of the procedures. The inspectors verified that licensee personnel credited for

procedure implementation had procedures available, were trained on implementation,

and were available in the event a fire occurred. The inspectors also reviewed selected

operator actions to verify that the operators could reasonably be expected to perform the

specific actions within the time required to maintain plant parameters within specified

limits.

b. Findings

No findings were identified.

Enclosure

5

.02 Passive Fire Protection

a. Inspection Scope

For the selected FAs, the inspectors verified the adequacy of fire barrier walls, ceilings,

floors, mechanical and electrical penetration seals, fire doors, and fire dampers. The

inspectors walked down accessible portions of the selected FAs to observe material

condition of the passive barriers and to identify degradation or nonconformances. The

inspectors compared the installed configurations to the approved construction details

and supporting fire endurance test data to assure that the respective fire barriers met the

requirements of 10CFR50, Appendix R, Section III.G and Appendix A to BTP APCSB

9.5-1. In addition, the inspectors reviewed licensing bases documentation to verify that

passive fire protection features met license commitments. A sample of completed

surveillance and maintenance procedures for selected fire doors, fire dampers, and

penetration seals were reviewed to ensure that these passive fire barriers were being

properly inspected and maintained. Specific barriers reviewed are listed in the

Attachment.

b. Findings

Introduction: An NRC identified Green non-cited violation (NCV) of McGuire Nuclear

Station Unit 1 and Unit 2 Selected Licensing Commitment 16.9.5, Fire Rated

Assemblies, was identified for the licensees inadequate implementation of modifications

that resulted in nonfunctional fire doors.

Description: The team identified nine fire doors, associated with risk significant areas

such as the control room and battery rooms, that had been modified in the 1980s and

90s by the licensee. Seven of the fire doors (705B, 706B, 925B, 925C, 925D, 926, 928)

were modified with welded angle brackets to permanently prevent the doors from being

opened. The other two fire doors (PD5 and PD6) were modified by welding metal

brackets to the doors that supported an I beam that was used to provide an additional

security barrier. These modifications were performed in 1985 and 1995 under

modification packages MG-11709 and MGMM-6884. The doors were procured as three-

hour assemblies as required by the licensees commitment in SER Supplement 2, Part

2,Section IV.3.A, dated March 1, 1979, which states, in part, that fire doors of proper

fire rating have been provided.

All nine doors were labeled by Underwriters Laboratory (UL) meaning that the

manufacturer received certification of the doors through specified testing. Field

modifications beyond the scope of prescriptive allowances by the labeling agency or

manufacturer typically result in the decertification of the fire door. Metal plates and

brackets found welded to the outer skin of the doors and door frames could create

localized thermal stresses under actual fire conditions which would result in warping,

twisting or tearing of the doors as they attempt to expand. These failure mechanisms

would potentially allow the passage of excessive smoke and heat. The inspectors

determined that the licensees modification packages were inadequate because they (1)

lacked a detailed discussion on the effects of welding a fire rated assembly, and (2) did

not include an evaluation or concurrence from the manufacturer or UL. Additionally, the

team noted that NFPA (National Fire Protection Association) 80, Fire Doors and Other

Opening Protectives required that when fire doors are no longer used for ingress and

egress, that the opening shall be filled with construction equivalent to that of a wall. This

Enclosure

6

requirement was based upon the fact that as long as a door is used for ingress and

egress, the storage of combustible materials in close proximity was not possible. Once

the door was permanently secured, combustible materials could be placed on either side

thus allowing a pathway for fires to communicate between fire zones. For these

reasons, the inspectors concluded that the licensee lacked reasonable assurance that

the three-hour ratings of the doors were maintained. The licensee entered the finding

into the corrective action program as PIP (Problem Identification Report) M-13-01454,

declared the doors as nonfunctional and implemented fire watches for the fire areas of

concern.

Analysis: The licensees inadequate implementation of fire door modifications that

resulted in the failure to meet the requirements of Selected Licensee Commitment

16.9.5, Fire Rated Assemblies, was a performance deficiency. The performance

deficiency was more than minor because it adversely affected the Mitigating Systems

cornerstone attribute of Protection Against External Events and adversely affected the

cornerstone objective to ensure the availability, reliability and capability of systems that

respond to initiating events to prevent undesirable consequences. Specifically, the

welding modifications performed on nine fire doors adversely affected their capability to

provide the required 3-hours of fire resistance. In accordance with NRC IMC 0609

Appendix F, Part 1, Fire Protection SDP Phase 1 Worksheet, the inspectors

determined the finding to be of very low safety significance (Green) because the fire

doors would still provide a minimum of 20 minutes fire endurance protection; and the

fixed fire ignition sources, and combustible or flammable materials, were positioned such

that the degraded fire doors would not have been subject to direct flame impingement.

A cross-cutting aspect was not assigned because the performance deficiency does not

reflect current licensee performance.

Enforcement: McGuire Nuclear Station Unit 1 and Unit 2 Operating License Condition

2.C. (4), Fire Protection Program states in part that, Duke Energy shall implement and

maintain in effect all provisions of the approved fire protection program as described in

the UFSAR for the facility and as approved in the NRC SER (NUREG-0422) and

associated supplements. SER Supplement 2, Part 2,Section IV.3.A dated March 1,

1979 stated, in part, that fire doors of proper fire rating have been provided. SLC

16.9.5, Fire Rated Assemblies, states, in part, that fire doors in a fire rated assembly

shall be operable at all times. For an inoperable fire door, SLC 16.9.5 required, in part,

that (1) a continuous fire watch be established; or (2) verify fire detectors on at least one

side of the door and establish a fire watch patrol; or (3) complete an evaluation as

permitted by NRC RIS (Regulatory Issues Summary) 2005-07 to institute required

action(s).

Contrary to the above, since 1995, nine fire doors in rated fire assemblies were

inoperable and the licensee failed to implement the required actions described above.

Specifically, the doors are inoperable because the licensee performed welding

modifications that resulted in a lack of reasonable assurance that the fire doors

maintained their UL qualification. Because this finding is of very low safety significance

and because it was entered into the licensees corrective action program as PIP M-13-

01454, this violation is being treated as an NCV, consistent with Section 2.3.2 of the

NRC Enforcement Policy. NCV 05000369 and 05000370/2013007-01, Modifications

Result in Nonfunctional Fire Doors.

Enclosure

7

.03 Active Fire Suppression

a. Inspection Scope

For the selected FAs, the inspectors performed in-plant observations to verify the

material condition and operational lineup of the fire water intake structure; the electric

motor driven fire pumps; the fire protection water supply distribution piping including

sprinklers, manual fire hose, and standpipe systems; and installed fire extinguishers.

The inspectors reviewed engineering drawings and specifications to verify that the as-

built configuration of fire suppression equipment was adequately maintained. Internal

standpipe and hose stations, and heat and smoke detection systems were reviewed

against specifications, drawings and engineering calculations to verify that the fire

detection and suppression methods were appropriate for the types of fire hazards that

existed in the FAs. The inspectors also verified that the suppression equipment met

applicable NFPA Standard(s). The inspectors reviewed completed surveillance testing

and maintenance procedures to verify that the equipment was adequately maintained.

The inspectors reviewed fire fighting pre-plans to verify that the strategies were

adequate. The inspectors observed the fire brigade staging and dress out areas to

assess the condition of fire fighting and smoke control equipment. In addition, the

inspectors verified the capabilities of the fire brigade by reviewing staffing, qualification

and training records. The Letters of Agreement with off-site emergency responders

were reviewed to verify the availability of additional resources to combat fires. Fire hose

stations and permanently installed fire extinguishers that were inspected are listed in the

attachment.

b. Findings

No findings were identified.

.04 Protection from Damage from Fire Suppression Activities

a. Inspection Scope

The inspectors evaluated whether manual water-based fire fighting activities or heat and

smoke migration from fires within the selected FAs could adversely affect equipment

credited for SSD, inhibit access to alternate shutdown equipment, or adversely affect

local operator actions required for SSD. The inspectors reviewed McGuire Nuclear

Station evaluations addressing concerns identified in Information Notice 1998-31, Fire

Protection System Design Deficiencies and Common Mode Flooding of Emergency Core

Cooling System Rooms at Washington Nuclear Project Unit 2. Fire Strategies (pre-fire

plans); fire brigade training procedures; heating, ventilating and air conditioning (HVAC)

drawings; and abnormal procedures for fires were also reviewed to verify that inter-area

migration of water or the ventilation of heat and smoke were addressed and would not

adversely affect SSD equipment or the performance of operator manual actions.

b. Findings

No findings were identified.

Enclosure

8

.05 Alternative Shutdown Capability

a. Inspection Scope

Methodology

The licensee credited an alternative shutdown capability for a postulated fire in FA 20

(Unit 2 Cable Room). The inspectors reviewed UFSAR Section 9.5.1, the McGuire FPP,

and corresponding abnormal procedures to ensure that appropriate controls provided

reasonable assurance that alternative shutdown equipment remained operable,

available, and accessible when required. In cases where local operator manual actions

(OMA) were credited in lieu of cable protection of SSD components, the inspectors

performed a walk-through of the procedures to verify that the OMAs were feasible. The

inspectors reviewed applicable process and instrumentation diagrams to gain an

understanding of credited equipments flow path and function. The inspectors reviewed

applicable licensee calculations to ensure the alternative shutdown methodology

properly identified systems and components to achieve and maintain safe-shutdown for

the FAs selected for review. Reviews also included verification that alternative shutdown

could be accomplished with or without offsite power.

The team reviewed procedures, work orders and completed surveillances to verify that

the alternative shutdown transfer capability was periodically tested. Additionally, the

team reviewed electrical schematics and one line diagrams to ensure that the transfer of

safe shutdown control functions to the alternate shutdown facility included sufficient

instrumentation to safely shutdown the reactor. This review also included verification that

shutdown from outside the MCR could be performed both with and without the

availability of offsite power.

Operational Implementation

The inspectors reviewed procedure AP-24, Loss of Plant Control Due to Fire or

Sabotage, to verify the adequacy of this procedure to mitigate a fire in the Unit 2 Cable

Room. The inspectors reviewed selected training materials for licensed and non-

licensed operators to verify that training reinforced the shutdown methodology that is

utilized in the FPP and abnormal procedures for FA 20. The inspectors also reviewed

shift turnover logs and shift manning to verify that personnel required for SSD using

alternative shutdown systems and procedures were available onsite, exclusive of those

assigned as fire brigade members.

The inspectors performed a walk-through of procedure steps with operations personnel

to assess the implementation and human factors adequacy of the procedures and

shutdown strategy to evaluate the ambient conditions, difficulty and operator

familiarization associated with each OMA. The inspectors reviewed the systems and

components credited for use during this shutdown method to verify that they would

remain free from fire damage. The inspectors reviewed selected operator actions to

verify that the operators could reasonably be expected to perform the specific actions

within the time required to maintain plant parameters within specified limits.

b. Findings

No findings were identified.

Enclosure

9

.06 Circuit Analyses

a. Inspection Scope

The team reviewed the licensees Appendix R design basis documentation, calculations,

drawings, wiring diagrams, and applicable McGuire circuit breaker coordination curves

for selected safe shutdown components to verify that fire damage to electrical circuits

associated with the post-fire safe shutdown capability would not adversely affect

achieving safe shutdown.

b. Findings

No findings were identified.

.07 Communications

a. Inspection Scope

The team reviewed the adequacy of the communication system to support plant

personnel in the performance of alternative safe shutdown functions and fire brigade

duties. The team verified that portable radios and fixed emergency communications

systems were available, adequate, and operable for the performance of the designated

activities. The team reviewed that the electrical power supplies and cable routing for the

wall mounted phone system would allow them to remain functional following a fire in the

selected fire areas. Additionally the team verified that a fire would not affect

communication equipment such as antennas, repeaters and transmitters.

b. Findings

No findings were identified.

.08 Emergency Lighting

a. Inspection Scope

The inspectors reviewed maintenance and design aspects of the fixed 8-hour battery

pack emergency lighting units (ELUs) required by the licensees approved FPP and 10

CFR 50 Appendix R,Section III.J. The inspectors performed plant walkdowns of the

post-fire SSD procedures for the selected FAs to observe the placement and coverage

area of the ELUs throughout the selected FAs. The inspectors also evaluated the

adequacy of the ELUs to illuminate access and egress pathways, and any equipment

requiring local operation and/or instrumentation monitoring for post-fire SSD. The

inspectors reviewed preventive maintenance procedures and completed surveillance

tests to verify that adequate surveillance testing was in place. Additionally, the

inspectors reviewed completed 8-hour discharge test records to verify the adequacy of

the licensees three year battery replacement schedule. The team validated that the

emergency lighting system was scoped into the licensees Maintenance Rule Program.

b. Findings

No findings were identified.

Enclosure

10

09. Cold Shutdown Repairs

a. Inspection Scope

The inspectors reviewed the McGuire FPP and abnormal procedures to verify that the

licensee identified repairs needed to reach and maintain cold shutdown and had

dedicated repair procedures, equipment, and materials to accomplish these repairs after

a fire event, assuming no offsite power was available. The inspectors verified that the

fire damage repair procedures were current, adequate, and that repair parts and

equipment were being stored and maintained onsite. The inspectors viewed the

containers where cold shutdown fire damage repair equipment and tools were stored to

examine the material condition of the tools and equipment. The inspectors reviewed

licensee inventory records to verify that repair parts and equipment were maintained in

accordance with the applicable attachments in electrical preventive maintenance

procedures. The inspectors reviewed the inventory inspection work order records and

compared them to the equipment and tool lists to verify that all required replacement

parts and equipment were being accounted for and were available for use.

b. Findings

No findings were identified.

.10 Compensatory Measures

a. Inspection Scope

The team reviewed the administrative controls for out-of-service, degraded and/or

inoperable fire protection features (e.g. detection and suppression systems and passive

fire barriers) as well as hot work from cutting, welding and grinding activities. The

inspectors also reviewed the operator compensatory actions log (dated January 29,

2013) and the fire protection system impairment log (dated February 13, 2013) to identify

and verify the adequacy of FPP interim compensatory measures. The team observed

performance of a fire protection roving fire watch activity in the Unit 2 Cable Spreading

Room (FA 20) and Unit 2 Train A Switchgear Room & Penetration Room (FA 16-18) and

compared hourly watch sign-in sheets against badge access transaction reports for

credited access doors used for egress through the fire areas. Fire watch personnel were

interviewed for familiarity with job requirements.

b. Findings

No findings were identified.

.11 Review and Documentation of Fire Protection Program Changes

a. Inspection scope

The inspectors reviewed six modifications associated with the FPP to verify that changes

were in accordance with the fire protection license condition and had no adverse affect

on the ability to achieve SSD.

Enclosure

11

b. Findings

No findings were identified

.12 Control of Combustibles and Ignition Sources

a. Inspection Scope

The inspectors conducted walkdowns of numerous plant areas that were important to

reactor safety, including the selected FAs, to verify the licensees implementation of fire

protection requirements as described in procedures NSD 313, Control of Transient Fire

Loads; NSD 314, Hot Work Authorization and Portable Heater Control; and NSD 316,

Fire Protection Impairment and Surveillance. The inspectors verified that the licensee

had properly evaluated transient fire hazards, controlled hot-work activities, and

maintained general housekeeping consistent with administrative control procedures and

the fire hazards analysis. For the selected FAs, the inspectors evaluated the potential

for fires and explosions, and potential fire severity. There were no hot work activities

ongoing during the inspection so direct observations of hot work related activities could

not be performed.

b. Findings

No findings were identified.

.13 B.5.b Inspection Activities

a. Inspection Scope

The team reviewed procedures to verify the adequacy of procedural guidance for the

manual depressurization of the steam generators and use of portable pump strategy.

The team performed walkdowns to verify the feasibility of implementing the guidance

provided in the procedures; and to verify that the apparatus required by the procedure,

to include communication equipment, was adequately staged. The team reviewed

records to verify that personnel were appropriately trained; and to verify that appropriate

preventive maintenance was performed on a recurring bases. The team reviewed a

calculation to verify that the minimum required flow for the strategy was achievable.

b. Findings

No findings were identified.

4. OTHER ACTIVITIES

4OA2 Identification and Resolution of Problems

a. Inspection Scope

The inspectors reviewed recent independent audits and evaluations to verify that the

licensee was performing appropriate assessments of the FPP. In addition, a sample of

fire protection nonconformances were reviewed to verify that deficiencies were identified,

Enclosure

12

entered into, and resolved by the licensees corrective action program. The problem

identification reports (PIP) were reviewed with regard to the adequacy of the evaluation,

appropriateness of the proposed corrective actions, and the timeliness of implementing

the corrective actions.

b. Findings

No findings were identified.

4OA3 Follow-Up of Events and Notices of Enforcement Discretion

.01 (Closed) Licensee Event Report (LER) 05000369/2012-001-00: Appendix R Non-

Compliance Could Have Potentially Affected Cold Shutdown (EA-13-050)

a. Inspection Scope

On May 17, 2012, the licensee submitted an LER documenting the identification of

circuits that, if impacted by fire, could result in damage of the steam generator (SG)

power operated relief valve (PORV) block valves. This potential cable damage could

also result in valve damage. This inadequacy could prevent operators from achieving

and maintaining cold shutdown (CSD) of the plant in the case of a postulated fire. The

inspectors performed a detailed review of the information related to the LER. The

inspectors reviewed documents, performed walk-downs, and discussed the LER with

plant personnel to gain an understanding of the operation of SG PORV block valves

during a postulated fire event. The inspectors assessed the licensees compensatory

measures and corrective actions to determine if they were adequate.

The following finding was identified by the licensee and is a violation of NRC

requirements. This finding has been screened and determined to warrant enforcement

discretion per the Interim Enforcement Policy Regarding Enforcement Discretion for

Certain Fire Protection Issues (10 CFR 50.48).

b. Findings

Introduction: A licensee-identified non-compliance with the Units 1 & 2 McGuire

Operating License Conditions 2.C.(4), Fire Protection Program, was identified for the

failure to provide fire protection features capable of limiting fire damage such that

systems necessary to achieve and maintain cold shutdown could be repaired within 72

hours. Specifically, the licensee discovered that a postulated fire could cause damage

to SG PORV block valves, and the valves would be unable to be repaired within 72

hours.

Description: During circuit analysis review in support of the NFPA 805 transition, the

licensee discovered that a fire in the Units 1 & 2 Train A Switchgear and Penetration

Rooms (FAs 15-17 and 16-18) could cause hot shorts that would result in the spurious

operation of the block valves for the SG PORVs. In addition to causing spurious valve

operation, these shorts could potentially bypass the valves limit/torque switches. These

switches provide the valves signal to stop, bypassing these switches would possibly

result in motor burnout, gear box damage, and internal valve damage. This failure

mechanism is discussed in NRC Information Notice (IN) 92-18, Potential for Loss of

Remote Shutdown Capability During a Control Room Fire.

Enclosure

13

To achieve and maintain hot standby after a fire event, the SG PORVs or block valves

are required to remain closed to prevent an uncontrolled cooldown of the reactor coolant

system (RCS). The inspectors determined that the SG PORVs would be available and

able to perform their hot standby function for a fire in FAs 15-17 and 16-18.

For cold shutdown, operators modulate the SG PORVs to accomplish a controlled plant

cooldown. This evolution requires the block valves to be open. The hot shorts

described above could result in the inability to, remotely or locally, open the valves.

Because these valves are unisolable, they would not be repaired in a timely manner to

support requirements for achieving cold shutdown conditions during fire events.

The licensee determined that these conditions were caused by a latent Appendix R

design deficiency in the electrical circuits for the Unit 1 and Unit 2 SG PORV block

valves. Upon discovery, the licensee implemented compensatory measures, in the form

of roving fire watches for the affected areas.

Analysis: Failure to provide features that are capable of limiting fire damage such that

systems necessary to achieve and maintain cold shutdown within 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br />, in

accordance with the NRC approved FPP, was a performance deficiency. This finding is

more than minor because it is associated with the reactor safety mitigating system

cornerstone attribute of protection against external events (i.e., fire), and affects the

cornerstone objective of ensuring the availability, reliability, and capability of systems

that respond to initiating events to prevent undesirable consequences. Using the

guidance of IMC 0609, Appendix F, Fire Protection Significance Determination Process

the inspectors determined that this finding was in the cold shutdown category. The

inspectors concluded that the finding was of very low safety significance (Green)

because the noncompliance only affected the ability to reach and maintain cold

shutdown conditions.

Because this issue relates to fire protection, and this non-compliance was identified

during the licensees transition to NFPA 805, this issue is being dispositioned in

accordance with Section 9.1, Enforcement Discretion for Certain Fire Protection Issues

(10 CFR 50.48) of the NRC Enforcement Policy. The inspectors determined that a

cross-cutting aspect was not applicable to this non-compliance and that it met the criteria

for enforcement discretion in accordance with Section 9.1 of the NRC Enforcement

Policy.

Enforcement: McGuire Operating License condition 2.C.(4) for Units 1 & 2, state, in part,

that Duke Energy Carolinas, LLC shall implement and maintain in effect all provisions of

the approved fire protection program as approved in the NRC SER (NUREG - 0422)

Supplement 5, dated April 1981. SER Supplement 5 stated, in part, that, in a letter

dated January 9, 1981, the licensee committed to meet the requirements of 10 CFR 50,

Appendix R,Section III.G. 10 CFR 50, Appendix R, Section III.G.1 stated, in part, that

fire protection features shall be provided for structures, systems, and components

important to safe shutdown. These features shall be capable of limiting fire damage so

that systems necessary to achieve and maintain cold shutdown from either the control

room or emergency control station(s) can be repaired within 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br />.

Contrary to the above, from initial plant operation through March 22, 2012, the licensee

failed to implement all provisions of the McGuire approved FPP in that features were not

Enclosure

14

provided that were capable of limiting fire damage such that systems necessary to

achieve and maintain cold shutdown could be repaired within 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br />. Specifically, the

licensee discovered that since initial plant operation, for fires in FA 16-18 and 15-17,

circuits for the SG PORV block valves were not adequately protected, and as a result,

postulated spurious actuation of the valves could cause valve damage. These valves

would be unable to be repaired within 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br />. The licensee entered this finding into

the corrective action program (CR 12-02194) and the licensee has taken appropriate

compensatory measures.

Because the licensee committed to adopt NFPA 805 and change their fire protection

licensing bases to comply with 10 CFR 50.48(c), the NRC is exercising enforcement and

reactor oversight process (ROP) discretion for this issue in accordance with the NRC

Enforcement Policy, Section 9.1, Enforcement Discretion for Certain Fire Protection

Issues (10 CFR 50.48) and Inspection Manual Chapter 0305. Specifically, this issue

was identified and will be addressed during the licensees transition to NFPA 805, was

entered into the licensees corrective action program, immediate corrective action and

compensatory measures were taken, was not likely to have been previously identified by

routine licensee efforts, was not willful, and it was not associated with a finding of high

safety significance (i.e., Red). (EA-13-050)

4OA5 Other Activities

.01 (Closed) Unresolved Item (URI) 2003-07-04: Requirements Relative to the Number of

Spurious Operations that Must be Postulated

a. Inspection Scope

The 2003 Triennial Fire Protection Inspection documented an URI associated with the

licensees procedural guidance associated with mitigating a postulated main control

room fire (FA 24) that adversely affected a single pressurizer PORV and the associated

pressurizer PORV block valve.

Additionally, during the 2006 Triennial Fire Protection Inspection the URI was updated to

include concerns with a postulated fire in the motor driven auxiliary feedwater (MDAFW)

pump room (FA 2). The issue was associated with the spurious closure of the auxiliary

feedwater (AFW) air-operated control valves (1CA36AB and 1CA64AB) during a

postulated fire event that would isolate the flow path to the D and A steam generators

(SG).

The team performed an in-office and on-site review of NRC inspection reports

(05000369 & 370/2003007 and 05000369 & 3702006/008), applicable regulatory

requirements, fire protection licensing documents, design bases documents, drawings,

operating procedures, and NFPA- 805 transition documentation. Additionally, the NRC

regional inspectors interviewed numerous licensee personnel to determine if a more

than minor performance deficiency existed for the URI.

b. Findings

No findings were identified.

Enclosure

15

URI 2003-07 is closed based on the following discussions:

In 2003, the NRC opened URI 2003-007-04 that documented an issue for a postulated

fire in the main control room (FA 24) that could result in the spurious opening of a single

pressurizer PORV (2NC34A) and its associated isolation valve (2NC33A). The spurious

opening of both valves would result in a breach of the RCS pressure boundary with the

possibility of pressurizer level going outside of the indicating range. For this fire

scenario, procedures directed operators to close the pressurizer PORV isolation valve

within 10 minutes. The NRCs concern was that the licensees procedures provided no

follow-up actions, such as de-energizing the PORV isolation valve, to ensure that it

would not spuriously reopen. The 2013 inspection team determined that, for a control

room fire, procedure AP-45, Plant Fire provided appropriate instructions to isolate all of

the PORVs by closing the associated block valves within 10 minutes. Procedure AP 45

directed the performance of procedure AP-24, Loss of Plant Control Due to Fire or

Sabotage which directed electrical realignments that closed all of the pressurizer

PORVs, and aligned control to the Standby Shutdown Facility. The team determined

that the proceduralized actions were consistent with the licensees fire protection

requirements and commitments. Additionally, the team noted that the licensees

proceduralized actions were consistent with current regulatory guidance. Specifically,

Regulatory Guide 1.189, Fire Protection for Nuclear Power Plants, Section 5.4.1, which

states, in part, The licensee should consider one spurious actuation or signal to occur

before control of the plant is achieved through the alternative or dedicated shutdown

system for fires in areas that require alternative or dedicated shutdown.

In 2006, the triennial fire protection inspection team updated URI 2003-007-04 by

documenting an issue for a postulated fire in the Unit 1 motor driven auxiliary feedwater

pump room (FA 2). The report discussed multiple fire-induced cable short circuits that

could adversely affect AFW air-operated valves (1CA-36AB or 1CA-64AB). The

inspectors concern was that two simultaneous proper polarity direct current short

circuits could cause either valve to close, thus isolating AFW flow from the turbine driven

AFW pump to either the D or A SG. The 2013 inspection team determined that fire

damage to the cables would cause a loss of power to the associated solenoid valves.

This loss of power would result in valves 1CA-36AB or 1CA-64AB failing to an open

position which is the required position. Therefore, a fire-induced short on the affected

cables will not adversely impact SSD.

4OA6 Meetings, Including Exit

On February 15, 2012, the inspection team leader presented the preliminary inspection

results to Mr. S. Capps and other members of the licensees staff. The licensee

acknowledged the results. The inspectors verified that no proprietary information was

retained by the inspectors or documented in this report.

Enclosure

SUPPLEMENTAL INFORMATION

KEY POINTS OF CONTACT

Licensee personnel

J. Bryant, Regulatory Affairs Lead

G. Carpenter, Fire Protection Engineer

D. Houser, Emergency lighting Engineer

J. Lukowski, Appendix R/NFPA 805 Engineer

S. Manning, B.5.b Supervisor

D. Miller, Fire Suppression Engineer

N. Sayles, Communications

P. Thompson, Operations

B. Weaver, PRA Engineer

NRC personnel

M. King, Chief, Engineering Branch 2, Division of Reactor Safety, Region II

J. Zeiler, Senior Resident Inspector, McGuire Nuclear Station

LIST OF ITEMS OPENED, CLOSED, AND DISCUSSED

Opened and Closed

05000369&370/2013007-01 NCV Modifications Result in Nonfunctional Fire

Doors (Section 1R05.02)

Closed

05000369/2012-001-00 LER Appendix R Non-Compliance Could Have

Potentially Affected Cold Shutdown

Modifications Result in Nonfunctional Fire

Doors (Section 4OA3.01)

05000370/2003-07-04 URI Requirements Relative to the Number of

Spurious Operations that Must be Postulated

(Section 4OA5.01)

Discussed

None

Attachment

LIST OF DOCUMENTS REVIEWED

LIST OF FIRE BARRIER FEATURES INSPECTED

(Refer Report Section 1R05.02 and 1R05.03)

Fire Damper Identification Description

1-733-42.2-5 FA 9-11 to

Fire Door Identification Description

701C FA 9-11 to Stairwell

705B (Welded) FA 13 to Battery Room

716B (Welded) FA 13 to Battery Room

801B FA 20 to Stairwell

801J FA 20 to FA 19

804 FA 16-18 to FA 16-18

925B (Welded) FA 24 to Stairwell

925C (Welded) FA 24 to Stairwell

925D (Welded) FA 24 to FA 25

926 (Welded) FA 22 to FA 24

928 (Welded) FA 23 to FA 24

PD5 (Welded) FA 22 to MG Set Room

PD6 (Welded) FA 23 to MG Set Room

1XCDDFRA (Roll-Up) FA 5 to FA 6

Fire Barrier Penetration Seal Identification Description

1-733-410.2 FA 9-11 to 2A

1-750-158.0-2 FA 16-18 to FA 10-12

2-750-131.0-1 FA 20 to FA 13

1-736-5.1-9 FA 5 to FA 15-17

1-736-5.2-2 FA 5 to FA 15-17

1-736-8.1-1 FA 5 to FA 6

Wall, Ceiling, Floor Identifications Description

Unit 1 Diesel Generator Rooms 1A & 1B FA 5

1ETB/733 Electrical Penetration Room FA 9-11

2ETA/750 Electrical Penetration Room FA 16-18

Service Building Cable Spreading Room FA 20

Unit 1 Turbine Building Switchgear Room FA U1 TB

Fire Extinguishers Inspected Description

9069 FA 5

9071 FA 5

9072 FA 5

9075 FA 5

9412 FA 9-11

9414 FA 9-11

9415 FA 9-11

9826 FA 9-11

9440 FA 16-18

9441 FA 16-18

9842 FA 16-18

Attachment

3

9843 FA 16-18

9845 FA 16-18

9438 FA 20

9439 FA 20

Fire Hose Stations Inspected Description

1RF 891 FA 5

1RF 892 FA 5

1RF 893 FA 5

1RF 894 FA 5

1RF 889 FA 9-11

1RF 890 FA 9-11

1RF 895 FA 9-11

1RF 967 FA 16-18

1RF 968 FA 16-18

1RF 969 FA 16-18

1RF 970 FA 16-18

1RF 971 FA 20

1RF 972 FA 20

LIST OF COMPONENTS REVIEWED

(Refer to Report Sections 1RO5.05- and 1RO5-.06)

Components Sampled

2NV VA0842AC, Standby Makeup Pump Suction Isolation

2NV VA0849AC, Standby Makeup Pump Containment Outside Isolation

2CA PU0002, Auxiliary Feedwater Pump 2B

2ETB Switchgear

2EVDD 125Vdc

1CA-42B, Feed to SG

Attachment

LIST OF DOCUMENTS REVIEWED

Audits and Self Assessment Reports

10-22, Audit- McGuire Triennial Fire Protection Program

10-13, Audit McGuire Triennial Fire Protection Program

12-013, Audit - McGuire Fire Protection

NRC Triennial 2013 Assessment

2011 MNS Fire Brigade Health Report

Cable Wiring Diagrams

Cable Block Diagram for 2CA PU0002

Cable Block Diagram for 2NV VA0842AC

Cable Block Diagram for 2NV VA0849AC

Cable Block Diagram for Radio Equipment

Cable Block Diagram for 2CA VA0064AB

Cable Block Diagram for 2CA VA0036AB

Cable Block Diagram for 1CA VA0064AB

Cable Block Diagram for 1CA VA0036AB

Cable Block Diagram for 1CA VA 0162C

Cable Block Diagram for 2CA VA 0162C

Cable Block Diagram for 1CA VA 0161C

Cable Block Diagram for 2CA VA 0161C

CALCULATIONS

MCC-1205.06-00-0046, Rim Pull Requirements for Time Critical Valves, Rev. 4

MCC-1223.20-00-0016, B.5.b Portable Pump Requirements, Rev. 3

MCC 1381.05-00-0335, Appendix R Coordination Study, Rev 1

MCC-1435.00.00-0059, NFPA 805-App R Safe Shutdown Deterministic Analysis, Rev. 2

MCC-1435.00-00-0022, Fire Prot. Manual Action Feasibility and Reliability Demonstration,

Rev. 0

MCC-1435.00-00-0023, NFPA 805 Transition Expert Panel Report for Addressing Potential

McGuire Multiple Spurious Operations, Rev. 1

MCC 1435.00-00-0027, NFPA Transition Licensing Action Review

MCC-1435.00-00-0059-00, NFPA 805 Appendix R Safe Shutdown Deterministic Analysis

MCC-1435.03-00-0013, Fire Protection Code Deviations, 8/29/2012

MCC-1435.00-00-0026, NFPA-805 Transition Existing Engineering Equivalency Evaluations,

11/23/2010

MCC-1435.00-00-0027, NFPA 805 Transition Licensing Action Review, 8/31/2010

MCC-1435.00-00-0031, NFPA 12A Code Conformance Review, Turbine Drive Auxiliary Feed

Pump Room, 5/25/2010

MCC-1435.00-00-0033, NFPA 20 Code Conformance Review, 5/25/2010

MCS-1435.00-00-0003, Design Specification for Mechanical and Electrical Penetration Fire

Flood and Pressure Seals, Rev.6

MCC-1535.00-00-0115, Risk Evaluation of McGuire Fire Issues

MCC-1535.00-00-0160, Fire PRA Evaluation of Steam Generator PORV Block Cables in Fire

Areas 16-18 and 15-17, Rev. 0

MCS-1184.00-1 Specification for McGuire 1-2 Rolling Doors, 6/29/1972

MCS-1465.00-00-0008, Design Basis Specification for Fire Protection, Rev. 13

MCS-1465.00-00.0008, Design Basis Specification for Fire Protection, Rev. 14

MCS-1465.00-00-0022, Design Basis Specification for the Appendix R Safe Shutdown Analysis,

Rev. 13

Attachment

5

MCS-1465.00-00-0022, Design Basis Specification for the Appendix R Safe Shutdown Analysis,

Rev. 14

EDM-101, Engineering Calculations/Analyses, Rev. 17

EDM-601, Engineering Change Manual, Rev. 19

Completed Procedures/ Surveillances/ Work Orders

WO 01784420-01, PM 1ECPPARX1, Perform Inspection Unit 1 RX PA System, dated 10/18/08

WO 01956849-01, PM 1ECPPARX1, Perform Inspection Unit 1 RX PA System, dated 9/28/11

WO 01909654-01, PM 1ECPPAUnit 1, Perform Inspection Unit 1 PA System, dated 12/1/10

WO 01813353-01, PM 1ECPPAUnit 1, Perform Inspection Unit 1 PA System, dated 2/25/09

WO 01840421-01, PM 2ECPPARX2, Perform Inspection Unit 2 RX PA System, dated 10/11/09

WO 01924533-01, PM 2ECPPARX2, Perform Inspection Unit 2 RX PA System, dated 10/30/12

WO 01909654-01, PM 2ECPPAUnit 2, Perform Inspection Unit 2 PA System, dated 2/2/11

WO 01909654-01, PM 2ECPPAUnit 2, Perform Inspection Unit 2 PA System, dated 7/1/09

WO 01080119, Fire Hose and Fire Hydrant Inspection, February 08, 2013

WO 02051614, Roll-up Fire Door Test, January 28, 2013

WO 02076651, Test Fire Zone 37H and 50H, January 28, 2013

WO 02076651, Test Fire Zone 70H, January 29, 2013

WO 01960534-02, SSS Emergency lighting Battery Discharge Test, dated 6/30/11

WO 02052333-01, PT 2ELDLPXXX1: Test Emergency Lighting Unit 2, dated 1/22/13

WO 01981680-01, PT 2ELDLPXXX1: Test Emergency Lighting Unit 2, dated 10/17/11

WO 01882848-01, PT 2ELDLPXXX1: Test Emergency Lighting Unit 2, dated 1/20/10

WO 01760001-25, MD100745 Addition of Emergency Lighting (Batts 35-48) dated 3/3/08

WO 01859190-01, PT 1ELDLPXXX1: Emergency Lighting Unit 1 & SSF, dated 8/27/09

WO 02032676-01, PM 2CF-151 Lube Stem, dated 10/12/12

WO 02032677-01, PM 2CF-153 Lube Stem, dated 10/8/12

WO 02016208-01, SG Tempering Flow Check Valve Testing, dated 9/15/12

PT/0/A/4200/002, Standby Shutdown Facility Operability Test, dated 12/13/12

PT/0/A/4200/002, Standby Shutdown Facility Operability Test, dated 1/12/13

PT/1/A/4200/041, Unit 1 SSF System Integrated Test, dated 4/11/07

PT/2/A/4200/041, Unit 2 SSF System Integrated Test, dated 8/25/06

PT/1/A/4200/041, Unit 1 SSF System Integrated Test, dated 6/22/98

PT/0/A/4400/010 A, Main Fire Pump A, 4/16/2012

PT/0/A/4600/112, Exterior/Interior Fire Equipment Inspection, 1/04/2013

PT/0/A/4400/022, Godwin Portable Pump Quarterly, dated 12/14/12

PT/0/A/4600/112, Exterior/Interior Fire Equipment Inspection, dated 1/07/13

Design Basis Documents

MCS-1223.SS-00-001, Design Basis Specification for the Standby Shutdown System, Rev. 29

MCS-0115.00-EPC-0001, Design Basis Spec. for the 4.16KV Essential Auxiliary Power, Rev. 13

MCS-1465.00-00-0022, Design Basis Spec. for Appendix R Safe Shutdown Analysis, Rev. 13

MCS-1465.00-00-008, Design Basis Specification for Fire Protection, Rev. 14

DRAWINGS

MCCD-1702-02.00, One Line Diagram 4160V Essential Auxiliary Power System, Rev. 13

MCCE-215-00.24, Elementary Diagram 4160 V Switchgear 2ETB Unit #6, Auxiliary Feedwater

Pump Motor #2B - Part 1, Rev. 13

MCCE-215-00.24-01, Elementary Diagram 4160 V Switchgear 2ETB Unit #6 , Auxiliary

Feedwater Pump Motor #2B - Part 3, Rev. 7

Attachment

6

MCCE-215-00.24-03, Elementary Diagram 4160 V Switchgear 2ETB Unit #6 , Auxiliary

Feedwater Pump Motor #2B - Part 4, Rev. 1

MCCE-215-00.24-02, Elementary Diagram 4160 V Switchgear 2ETB Unit #6 , Auxiliary

Feedwater Pump Motor #2B - Part 2, Rev. 5

MCEE-212-00.29-01, Elementary Diagram Standby Shutdown Facility Transfer Scheme, Rev. 5

MC-1315-01.04-100, Diesel Generator Building Unit 1- Fire, Flood, & HVAC Boundaries

General Arrangement, Elevation 736+6, Rev. 7

MC-1315-01.04-101, Diesel Generator Building Unit 1- Fire, Flood, & HVAC Boundaries

General Arrangement, Elevation 736+6, Rev. 0

MC-1203-02.0A, Diesel Generator Building Unit 1- General Arrangement Floor Plan, Elevation

764+8, Rev. 29

MC-1204-4-A, Auxiliary Building Unit 1 & 2 Gen. Arrangement, Floor Elevation 750+0, Rev. 23

MC-1204-5-A, Auxiliary Building Unit 1 & 2 General Arrangement, Switchgear Room Plans,

Floor Elevation 750+0 , Rev. 22

MC-1315-01.05-005, Auxiliary Building - Fire, Flood, & HVAC Boundaries General

Arrangement, Switchgear Room Plans, Elevation 750+0, Rev. 2

MC-1315-01.05-105, Auxiliary Building Unit 2- Fire, Flood, & HVAC Boundaries General

Arrangement, Elevation 750+0, Rev. 1

MCEE-0147-32.00, Elementary Diagram Auxiliary Feedwater System (CA), DC Motor Operated

Valve 1CA0161C, Rev. 4

MC-1831-01.01, Communications Plant Telephone & Intercom System, Rev. 0

MC-1831-02.01, Communications Telephone & PA Systems Telephone Directory, Rev. 0

MC-1908-07.00, Electrical Equipment Layout Auxiliary Building Mounting Details, Rev. 8

MC-1888-01.00, Auxiliary Building Unit 1 Station Grounding Plan, Elevation 767 +0, Rev. 55

MC-1831-11.00, Communications PA & Telephone Systems Roof Plan, Rev. 15

MC-1831-07.00, Communications- PA & Telephone Systems Auxiliary Building Elevation

733+0, Reactor Building Elevation 738+ 3, Turbine Building Elevation 739+0, Rev. 34

MC-1831-01.00, Comm. Plant Telephone & Intercom Systems Details & Sections, Rev. 13

MC-1831-09.00, Communications PA & telephone Systems Auxiliary Building Elevation 733+0

& 767 + 0, Reactor Building Elevation 767+0, Turbine Building Elevation 760+6, Rev. 63

MC-1705-02.00, One Line Diagram 125VDC-240/120VAC Auxiliary Control Power, Rev. 141

MCFD-1554-01.00, Flow Diagram of Chemical and Volume Control System (NV), Rev. 9

MCFD-1554-01.01, Flow Diagram of Chemical and Volume Control System (NV), Rev. 10

MCFD-1554-01.02, Flow Diagram of Chemical and Volume Control System (NV), Rev. 12

MCFD-1554-01.03, Flow Diagram of Chemical and Volume Control System (NV), Rev. 3

MCFD-1554-02.00, Flow Diagram of Chemical and Volume Control System (NV), Rev. 17

MCFD-1554-02.01, Flow Diagram of Chemical and Volume Control System (NV), Rev. 6

MCFD-1554-03.00, Flow Diagram of Chemical and Volume Control System (NV), Rev. 16

MCFD-1554-03.01, Flow Diagram of Chemical and Volume Control System (NV), Rev. 23

MCFD-1554-04.00, Flow Diagram of Chemical and Volume Control System (NV), Rev. 9

MCFD-1554-05.00, Flow Diagram of Chemical and Volume Control System (NV), Rev. 20

MCFD-1574-01.00, Flow Diagram of Nuclear Service Water System (RN), Rev. 20

MCFD-1574-01.01, Flow Diagram of Nuclear Service Water System (RN), Rev. 27

MCFD-1574-02.00, Flow Diagram of Nuclear Service Water System (RN), Rev. 29

MCFD-1574-02.01, Flow Diagram of Nuclear Service Water System (RN), Rev. 10

MCFD-1574-03.00, Flow Diagram of Nuclear Service Water System (RN), Rev. 32

MCFD-1574-03.01, Flow Diagram of Nuclear Service Water System (RN), Rev. 10

MCFD-1574-04.00, Flow Diagram of Nuclear Service Water System (RN), Rev. 17

MCFD-1574-05.00, Flow Diagram of Nuclear Service Water System (RN), Rev. 4

MCFD-1592-01.00, Flow Diagram of Auxiliary Feedwater System (CA), Rev. 7

MCFD-1592-01.01, Flow Diagram of Auxiliary Feedwater System (CA), Rev. 24

MCFD-1592-01.02, Flow Diagram of Auxiliary Feedwater System (CA), Rev. 8

Attachment

7

MCFD-1592-02.00, Flow Diagram of Auxiliary Feedwater System (CA), Rev. 5

MCFD-1593-01.00, Flow Diagram of Main Steam System (SV), Main Steam Vent to

Atmosphere (SM), Rev. 19

MCFD-1593-01.01, Flow Diagram of Main Steam System (SV), Main Steam Vent to

Atmosphere (SM), Rev. 18

MCFD-1593-01.03, Flow Diagram of Main Steam System (SV), Main Steam Vent to

Atmosphere (SM), Rev. 17

MCFD-2554-01.00, Flow Diagram of Chemical and Volume Control System (NV), Rev. 10

MCFD-2554-01.01, Flow Diagram of Chemical and Volume Control System (NV), Rev. 10

MCFD-2554-01.02, Flow Diagram of Chemical and Volume Control System (NV), Rev. 11

MCFD-2554-01.03, Flow Diagram of Chemical and Volume Control System (NV), Rev. 3

MCFD-2554-02.00, Flow Diagram of Chemical and Volume Control System (NV), Rev. 19

MCFD-2554-02.01, Flow Diagram of Chemical and Volume Control System (NV), Rev. 6

MCFD-2554-03.00, Flow Diagram of Chemical and Volume Control System (NV), Rev. 17

MCFD-2554-03.01, Flow Diagram of Chemical and Volume Control System (NV), Rev. 25

MCFD-2554-04.00, Flow Diagram of Chemical and Volume Control System (NV), Rev. 6

MCFD-2554-05.00, Flow Diagram of Chemical and Volume Control System (NV), Rev. 11

MCFD-2574-01.01, Flow Diagram of Nuclear Service Water System (RN), Rev. 30

MCFD-2574-02.00, Flow Diagram of Nuclear Service Water System (RN), Rev. 26

MCFD-2574-02.01, Flow Diagram of Nuclear Service Water System (RN), Rev. 10

MCFD-2574-03.00, Flow Diagram of Nuclear Service Water System (RN), Rev. 17

MCFD-2574-03.01, Flow Diagram of Nuclear Service Water System (RN), Rev. 9

MCFD-2574-04.00, Flow Diagram of Nuclear Service Water System (RN), Rev. 27

MCFD-2574-05.00, Flow Diagram of Nuclear Service Water System (RN), Rev. 5

MCFD-2592-01.00, Flow Diagram of Auxiliary Feedwater System (CA), Rev. 10

MCFD-2592-01.01, Flow Diagram of Auxiliary Feedwater System (CA), Rev. 22

MCFD-2592-02.00, Flow Diagram of Auxiliary Feedwater System (CA), Rev. 4

MCFD-2593-01.00, Flow Diagram of Main Steam System (SV), Main Steam Vent to

Atmosphere (SM), Rev. 18

MCFD-2593-01.01, Flow Diagram of Main Steam System (SV), Main Steam Vent to

Atmosphere (SM), Rev. 21

MCFD-2593-01.03, Flow Diagram of Main Steam System (SV), Main Steam Vent to

Atmosphere (SM), Rev. 17

MCCD-1703-06.10, One Line Diagram 600 VAC Essential Motor Control Center 1EMXH1,

Rev. 3

MCCD-2700-00.00, Unit 2 Configuration One Line Diagram Unit Essential Power System,

Rev. 5

MC-1705-01.00, One Line Diagram 125 VDC/120 VAC Vital Instrument & Control Pwr. Sys.,

Rev. 100

MCCD-1700-00.00, One Line Diagram, Unit One Configuration Essential Power System,

Rev. 5

MCEE-0147-11.00, Elementary Diagram Aux. Feedwater System AFWP 1B Isolation Valve

1CA0042B, Rev. 2

MCEE-270-05.16, Elementary Diagram Main Steam Vent to Atmosphere System (SV) MS 2D

Atmos Dump Pwr Oper Relief Isol Vlv. 2SV25, Rev. 1

MCEE-270-05.15, Elementary Diagram Main Steam Vent to Atmosphere System (SV) MS 2C

Atmos Dump Pwr Oper Relief Isol Vlv. 2SV26, Rev. 1

MCEE-270-05.13, Elementary Diagram Main Steam Vent to Atmosphere System (SV) MS 2A

Atmos Dump Pwr Oper Relief Isol Vlv. 2SV27, Rev. 1

MCEE-270-05.14, Elementary Diagram Main Steam Vent to Atmosphere System (SV) MS 2B

Atmos Dump Pwr Oper Relief Isol Vlv. 2SV28, Rev. 2

MCID-1499-CA.08, Instrument Detail T.D. Aux. FWP Disch. To Steam Gen. Valve Control,

Rev. 2

Attachment

8

MC-1384-07.14-01, Fire Plan Auxiliary Building Elevation 733.0 and 736.0, Rev.13

MC-1384-07.14-02, Fire Plan Auxiliary Building Elevation 733.0 and 736.0, Rev.14

MC-1384-07.15-01, Fire Plan Auxiliary Building Elevation 750.0, Rev.14

MC-1384-07.15-02, Fire Plan Auxiliary Building Elevation 750.0, Rev.13

MC-1418-06.43-01, Piping Layout System RF Plan Elevation 750.0, Rev.10

MC-1762-01.00-03, Location Diagram Fire Detector System Elevation 733 and 739, Rev. 15

MC-1762-01.00-03, Location Diagram Fire Detector System Elevation 750 Rev. 15

MCFD-1599-01.00, Flow Diagram of the Fire Protection System, Rev. 17

MCFD-1599-01.01, Flow Diagram of the Fire Protection System, Rev. 17

MCFD-1599-02.00, Flow Diagram of the Fire Protection System, Rev. 23

MCFD-1599-02.01, Flow Diagram of the Fire Protection System, Rev. 11

MCFD-1599-02.02, Flow Diagram of the Fire Protection System, Rev. 11

MCFD-1599-02.03, Flow Diagram of the Fire Protection System, Rev. 7

MCFD-1599-03.00, Flow Diagram of the Fire Protection System, Rev. 11

MCFD-1599-03.01, Flow Diagram of the Fire Protection System, Rev. 6

MCFD-1599-04.00, Flow Diagram of the Fire Protection System, Rev. 3

MCFD-1599-05.00, Flow Diagram of the Fire Protection System, Rev. 1

MCFD-2599-04.00, Flow Diagram of the Fire Protection System, Rev. 2

MCFD-1591-01.00, Flow Diagram of Feedwater System, Rev. 4

MCFD-1591-01.01, Flow Diagram of Feedwater System, Rev. 22

Engineering Changes (EC)

104730, OWST Project Piping/Pumps/Valves & Controls Replacement, 8/26/2011

103857, Install Anti-Hammer Circuit for Valve 1NV842AC, 4/10/2012

103930, Change Activator on 2NV-142B, 10/10/2012

98743, Disable Auto-Open Function 1CA161C, 10/12/2011

103255, Fire Alarm Control Panel Installation, 2/22/2012

95850, Edwards System Technology Fire Detection Installation, 9/21/2011

103857, Install an Anti-Hammer Circuit for Valve 1NV 842AC

98743, MD-101869 - DISABL Auto Open Function 1CA-161C / 1CA-162C Mod

103930, Change Actuator on 2NV-142B from NA2 to NA1E

104730, OWTS Project Piping/Pumps/Valves and Controls Replacement

Fire Protection Pre-Plans and Fire Drill Critiques

PT/0/B/4600/121, Fire Drill, 1ETA SWGR Air Handling Room, C shift, 1/29/2011

PT/0/B/4600/121, Fire Drill, 1ETA SWGR Air Handling Room, D shift, 2/10/2011

PT/0/B/4600/121, Fire Drill, 1ETA SWGR Air Handling Room, A shift, 2/15/2011

PT/0/B/4600/121, Fire Drill, 1ETA SWGR Air Handling Room, B shift, 4/11/2011

PT/0/B/4600/121, Fire Drill, 1ETA SWGR Air Handling Room, E shift, 8/17/2011

PT/0/B/4600/121, Fire Drill, 2CSR, B shift, 7/28/2012

PT/0/B/4600/121, Fire Drill, 2CSR, C shift, 8/12/2012

PT/0/B/4600/121, Fire Drill, 2CSR, A shift, 8/31/2012

PT/0/B/4600/121, Fire Drill, 2CSR, D shift, 11/07/2012

PT/0/B/4600/121, Fire Drill, 2CSR, E shift, 12/26/2012

MFDS-005.006, Unit 1 DG Rooms, Rev. 0

MFDS-009.011, 1ETB / 733 Elec. Pen. Room, Rev. 0

MFDS-016.018, 2ETA / 750 Elec. Pen. Room, Rev. 0

MFDS-019.020, Unit 2 750 Aux. Cable Room 801C, Rev. 0

McGuire Nuclear Station Fire Strategy, Aux. Diesel Generator 1A, Rev. 0

McGuire Nuclear Station Fire Strategy, Unit 1 733 Electrical Penetration Room, Rev. 0

McGuire Nuclear Station Fire Strategy, Unit 2 750 Electrical Penetration Room, Rev. 0

Attachment

9

McGuire Nuclear Station Fire Strategy, Unit 2 Aux Cable Room 801C, Rev.1

Procedures

AP/2/A/5500/07, Loss of Electrical Power, Enclosure 30, Rev. 30

AP/2/A/5500/07, Loss of Electrical Power, Enclosure 30-Shifting 2ETB Power from Alternate

(SATB) to Normal (2ATD), Rev. 30

AP/1/A/5500/07, Loss of Electrical Power, Rev. 31

AP/1/A/5500/11, Pressurizer Pressure Anomalies, Rev. 11

AP/2/A/5500/11, Pressurizer Pressure Anomalies, Rev. 12

AP/1/A/5500/24, Loss of Plant Control Due to Fire or Sabotage, Rev.24

AP/1/A/5500/24, Loss of Plant Control Due to Fire or Sabotage, Rev.29

AP/2/A/5500/24, Loss of Plant Control Due to Fire or Sabotage, Rev. 30

AP/0/A/5500/45, Plant Fire, Rev. 5

AP/0/A/5500/45, Plant Fire, Rev. 13

AP/0/A/5500/45, Plant Fire, Rev. 14

IP/0/A/3090/023, Fire Damage Control, Rev. 4E

OP/O/A/6350/001, Normal Power Checklist, Rev. 54

OP/2/A/6350/005, AC Electrical Operation other Than Normal Lineup, Rev. 36

OP/0/A/6350/008, Operation of Station Breakers, Rev. 67

OP/0/A/6100/020, Operational Guidelines Following a Fire in Auxiliary Building or Vital Area,

Rev. 27

OP/0/A/6100/21, Shutdown Outside the Control room following a Fire, Rev. 19

PT/0/B/4350/022, Periodic Inspection of Plant PA System, Rev. 7

PT/1/A/4200/041, Unit 2 SSF System Integration Test, Rev. 4

PT/2/A/4200/041, Unit 2 SSF System Integration Test, Rev. 4

RP/0/A/5700/025, Fire Brigade Response, Rev. 19

RP/0/B/4600/121, Fire Drill, Rev. 05

EDM-101, Engineering Calculations/Analysis, Rev.17

EDM-601, Engineering Change Manual, Rev.19

MP/0/A/7650/122, Inspection of Fire Hose Stations and Hydrant Houses, Rev.10

NGD-FB-05, Initial Fire Brigade Training: Fire Hose, Nozzles, Appliances and Streams, 7/3/06

NSD 112, Fire Brigade Organization, Training and Responsibilities, 9/11/12

NSD 301, Nuclear Station Modifications, 9/30/97

NSD 313, Control of Transient Fire Loads for McGuire, 12/31/12

NSD 314, Hot Work Authorization and Portable Heater Control for McGuire, 12/31/12

NSD 316, Fire Protection Impairment and Surveillance for McGuire, 12/31/12

NDS 320, Fire Protection Program Change Review Form, 11/15/2011

OP/1/A/6400/002A, Fire Protection System, Rev. 139

OP/0/A/6400/002B, Halon Fire Protection System, Rev. 17

OP/0/A/6400/002C, Fire Detection System, Rev. 60

OP/0/A/4600/016B, Halon Fire Detectors Monthly Test, Rev. 20

OP-MC-JPM-SSRFY:019, Manually Initiate Diesel Generator Halon, Rev.13/01-09-02

PT/0/A/4250/004, Fire Barrier Inspection, Rev. 33

PT/0/A/4600/032D, Fire Detection System Operational Tests for Aux. Bldg 733 and 750, Rev.3

PT/0/A/4600/112, Exterior/Interior Fire Equipment Inspection, Rev. 8

PT/0/A/4700/043, SLC Fire Hose Station Valve Operability Test, Rev.5

PT/0/A/4700/049, SLC Fire Hose Inspection, Rev.4

PT/0/B/4600/118, Fire Brigade Qualification Verification, Rev.3

PT/1/A/4400/001N, Halon 1301 System Periodic Test, Rev. 38

PT/0/A/4400/017, Fire Pump A & B Operability Test, Rev. 21

PT/0/A/4400/017, Fire Pump C Operability Test, Rev.17

Attachment

10

PT/0/4600/127, B.5.b Equipment Inventory, Rev. 0

Evaluations by Station Management in the TSC, Volume 2, Book 2 of 3, Rev. 1

Miscellaneous Documents

AR3010, Organization Chart and Access Report, 1/29/2013

Aurora Pump Factory Acceptance Test for Pump D36271A, 6/26/1973

Aurora Pump Factory Acceptance Test for Pump D36271B, 6/26/1973

Aurora Pump Factory Acceptance Test for Pump D36271C, 6/26/1973

Badge Access Transaction Report for Roving Fire Watch 287547, 2/13/2013

Badge Access Transaction Report for Roving Fire Watch 325000, 2/13/2013

ETQS2400.0 Attachment 6.6, Training ILT Class Attendance Sheet, 12/22/2012

Fire Protection System Impairment Log, 2/13/2013

Kinnear AKBAR Rolling Fire Door Model FH-A Service Manual

Letter of Agreement between Duke Energy Company and Cornelius VFD, 4/13/2010

Letter of Agreement between Duke Energy Company and Huntersville FD, 7/28/2010

MG-11709, Nuclear Station Modification Safety Evaluation for Fire Door Modification, 5/13/1985

MGMM-6884, Screening Form for 10CFR50.59 for Fire Door Modification, 4/10/1995

NRC Triennial Fire Protection Inspection Report 05000369/2009007 and 05000370/2009007,

June 25, 2009

NRC Triennial Fire Protection Inspection Report 05000369/2006008 and 05000370/2006008,

January 29, 2007

NRC Triennial Fire Protection Inspection Report 50-369/03-07 and 50-370/03-07, July 03, 2003

OBED 05-039881, Internal Flooding/Spray Down Event of Safety Related Equipment, 8/11/2005

Penetration Seal Data Sheet for Penetration Seal Number 750-158.0-2, 8/23/1999

Purchase Order A27426, Duke Power Company and W. Fred Casey & Co for Furnish and

Delivery of Rolling Doors, 9/27/1972

Summary Report, Three Hour Qualification of Whittaker Electronics Resources Appendix R and

SI 2400 Silicone Dioxide Insulated Fire Cable, December 1994

Summary Test Report for Appendix R Fire Test, ER 98-033, October 29, 1998

ST2122, Multiple Assigned Job Status Report, 1/29/2013

Underwriters Laboratory Online Certifications Directory, VUFZ.EX1394, 10/31/1996

Underwriters Laboratory Fire Door Certificate C28916, September 11, 1973

Underwriters Laboratory Standard 10B, Fire Test of Door Assemblies

Engineering Support Document, Emergency Communications System, Rev. 1A

IMP-MC-2012-00946, Fire Hemyc Wrap, Cable not Meeting the 1-Hour Fire Resistance Criteria

Impairment and Compensatory Measures Form [Selected Fire Areas], dated 01/13/13

NFPA 12A- 1977, Standard on Halon 1301 Extinguishing Systems

NFPA 13-1978, Standard for the Installation of Sprinkler Systems

NFPA 14-1976 Standard for the Installation of Standpipes and Hose Systems

NFPA 15-1977, Standard for Water Spray Fixed Systems for Fire Protection

NFPA 20-1978, Standard for the Installation of Centrifugal Fire Pumps

NFPA 24-1977, Standard for the Installation of Private Service Mains and their Appurtenances

NFPA 72E-1974, Standard on Automatic Fire Detection

NFPA 80-1977, Fire Doors and Windows

NFPA 80-2007, Fire Doors and Other Opening Protectives

NFPA 80-2013, Fire Doors and Other Opening Protectives

Technical Manuals and Vendor Information

Data Sheet Motorola Digital Two- Way Portable Radios-Mototrbo XPR 6550/XPR 6350, dated

1/11

Data Sheet Clear Command Helmet Communication System-dated 3/07

Attachment

11

Data Sheet Motorola Digital Two- Way Portable Radios-Mototrbo XPR 4550/XPR 4580, dated

1/11

Data Sheet C & D Technologies Tel Series Valve Regulated Lead Acid Battery, dated 04/12

Licensing Documents

Selected Licensing Commitment, 16.9.7, Standby Shutdown System

NUREG-0422, Safety Evaluation Report Related to the Operation of McGuire Nuclear Station

Units 1 and 2, March 1978

NUREG-0422, Supplement 2, Safety Evaluation Report Related to the Operation of McGuire

Nuclear Station Units 1 and 2, March 1979NUREG-0422, Supplement 3, Safety Evaluation

Report Related to the Operation of McGuire Nuclear Station Units 1 and 2, May 1980

NUREG-0422, Supplement 4, Safety Evaluation Report Related to the Operation of McGuire

Nuclear Station Units 1 and 2, January 1981

NUREG-0422, Supplement 5 with Corrections, Safety Evaluation Report Related to the

Operation of McGuire Nuclear Station Units 1 and 2, November 1993

NUREG-0422, Supplement 6, Safety Evaluation Report Related to the Operation of McGuire

Nuclear Station Units 1 and 2, February 1983

Selected Licensee Commitment 16.9.7- Standby Shutdown System

Letter dated January 5, 1983 regarding responses to several concerns in the draft Safety

Evaluation Report for the McGuire Standby Shutdown System

Letter dated September 10, 1984 regarding the Standby Shutdown System at McGuire and

Catawba Nuclear Station

Letter dated December 14, 1982 regarding the McGuire Standby Shutdown System

Letter dated August 2, 1984 regarding Fire Protection for Redundant Safe Shutdown Equipment

Letter dated September 12, 1984 regarding meeting at Region II office to discuss the Standby

Shutdown Facility for McGuire Units 1 and 2, Catawba Unit 1 and Oconee SSF

Letter dated May 15, 1989 regarding Fire Protection Deviations for McGuire Unit 1 and 2

McGuire Nuclear Station, Unit 1 - Request for Deviation from Fire Protection Program

Incorporating Requirements of Appendix R to Part 50 of Title 10 of the Code of Federal

Regulations, January 13, 2003

NRC Letter dated April 16, 1984 regarding Issuance of Amendment No. 31

LIST OF PROBLEM IDENTIFICATION REPORTS (PIP) REVIEWED DURING INSPECTION

M-09-05990, Documentation of Noncompliances with the Appendix R Program Identified as Part

of the Reconstitution Project

M-03-02311, Evaluate May 2003 Fire Protection Inspection Items

M-06-04539, NRC Response (September 26, 2006) to McGuire Letter of Intent to Adopt

10CFR50, Section 50.48 (c)

M-12-01086, Swap of 1EMXH-1 to Alternate (SSF) Power Source, along with Associated SSF

Controls, is not Periodically Tested

M-09-05990, Documentation of Noncompliances with the Appendix R Program Identified as Part

of the Reconstitution Project

M-02-01708, It has Been Discovered that Pressurizer Ambient Heat Losses are Greater than

Calculated in OSC-3144, Impacting SSF ASW System Operability (T.S. 3.10.1) and T.S.

3.4.9 (Pressurizer)

M-05-04859, CNS PIP M-05-6055 on Appendix R Manual Action Rule NRC Public Meeting

M-12-01020, Review Noncompliances Identified as a Result of the Appendix R Reconstitution

and NFPA-805 Transition Work for Reportability

M-12-02194, Evaluation Identified an Appendix R Noncompliance which has the Potential to

Adversely Affect the Ability to Achieve and Maintain a Cold Shutdown on Unit 2

M-02-03265, Columbia Generating Station Water Spill Event

Attachment

12

M-06-04727, Fire Nozzle 1RF841 is not Rated for Use on Electrical Fires

M-10-02460, Manual Halon System Release Located Within Fire Hazard Area

M-10-04408, Portable Fire Extinguisher Code Deviations

M-10-04416, TDAFW Pump Room Halon System Code Deviations

M-10-04632, Fire Service Main and Appurtenances Code Deviations

M-10-07639, Unit 2 CSR Water Based Suppression Adverse Effects

M-12-01098, NDS 313-1, Transient Fire Load Approval Forms are not Retained

M-12-02351, Duct Fire Detector Test Sampling Methodology to Include DP

M-1208218, Concrete Hatch Plugs are a Degraded Fire BarrierM-13-00011, Shift Fire Brigade

Member not Recorded in LMS

M-12-01086, Swap of 1EMXH-1 to Alternate Power Source

M-12-04539, Issues Noted During Annual #1 and #2 Hale Pump Testing

M-13-00880, PIP Evaluate Failed Emergency Lights for Maintenance Rule Functional Failure

List of PROBLEM IDENTIFICATION REPORTS (PIP) Generated as a Result of this

Inspection

M-13-00359, Relay House Fire protection Power light was not Illuminated

M-13-00909, Penetration Seal 2-750-131.0-1, 0.25 Gap in Cable Spreading Room Floor

M-13-00912, Evaluate 1ETB SWGR Room MI Cable (two) with Tape as not Impacting 3 Hour

Rating

M-13-00950, Task for Radio Battery Swaps was Removed from the Operations WCC Routine

Task List

M-13-00951, Discrepancy in the Nomenclature used on the Radios used at the Plant

M-13-00980, Evaluate Maint. Rule Functional Failure Criteria for Emergency Lighting

M-13-00925, MCC-1223.20-00.0016 Contains the Computer Model Output Data but does not

Contain the Computer Model Input Data

M-13-01021, Fire Strategy for 1A D/G Requires More Detail for Manual Halon Actuation

M-13-00124, Incomplete Documentation of Fire Brigade Members for July 4, 2010 Day Shift

M-13-01154, Electrically Rated Fire Hose Nozzle are Required to be provided at Locations

where Electrical Equipment or Cabling is Located

M-13-01407, Inspection of Repair Kits Identified Electrical Tape was out of Date

M-13-00414, WO 02032676 was Closed without Performing Functional

M-13-00415, WO 02032678 was Closed without Performing Required Scope as Directed

M-13-00416, WO 02032679 was Closed without Performing Required Scope as Directed

M-13-00451, App. R DBD Says Wiring and Cabling used for Repairs must be Pre-fitted with

Lugs

M-13-01454, Fire Doors Modified Without Proper Evaluations

M-13-01510, Fire Pre-plan Backlog Observations

M-13-01511, Fire Evaluation Screening Form Might Need to be Improved

M-13-01513, Evaluate if MRFF Criteria for Particular Systems/Components are Adequate to

Detect Adverse Trends

M-13-01514, App R Related conclusions and Basis is not Contained in a Controlled Document

Attachment

13

LIST OF ACRONYMS AND ABBREVIATIONS

APCSB Auxiliary and Power Conversion Systems Branch

AR Action Request

BTP Branch Technical Position

CAP Corrective Action Program

CFR Code of Federal Regulations

DC Direct Current

DSP Dedicated Shutdown Procedure

ELS Emergency Lighting System

FA Fire Area

FHA Fire Hazards Analysis

FPM Fire Protection manual

FPP Fire Protection Program

FZ Fire Zone

HVAC Heating, Ventilation, and Air Condition

IMC Inspection Manual Chapter

IP NRC Inspection Procedure

LER Licensee Event Report

NUREG an explanatory document published by the NRC

NCR Nuclear Condition Report

NCV Non Cited Violation

NFPA National Fire Protection Association

NRC United States Nuclear Regulatory Commission

OMA Operator Manual Actions

P&IDs Piping and Instrumentation Diagrams

PIP Problem Identification Report

PORV Power Operated Relief Valve

Rev Revision

SCBA Self-Contained Breathing Apparatus

SDP Significance Determination Process

SER Safety Evaluation Report

SLC Selected Licensee Commitments

SSC Systems, Structures and Components

SSD Safe Shutdown

UFSAR Updated Final Safety Analysis Report

Attachment