ATTACHMENT 1TOAEP:NRC:0896U EXISTINGTECHNICAL SPECIFICATION PAGESMARKEDTOREFLECTPROPOSEDCHANGES9503080170 950228PDRADOCK05000315PPDR ELECTRICAL POWERSYSTEMSSURVEILLANCE REOUIREMENTS Continued 2.Thepilotcellspecificgravity,corrected to77F,andfullelectrolyte level(fluidat.thebottomofthemaximumlevelindication mark),isgreaterthanorequalto1.200,3.Thepilotcellvoltageisgreaterthanorequalto2.13.volts,and.Theoverallbatteryvoltageisgreaterthanorequalto250volts.b.Atleastonceper92daysbyverifying that:1.Thevoltageofeachconnected cellisgreaterthanorequalto2.13voltsunderfloatcharge.2.Thespecificgravity,corrected to77F,andfullelectrolyte 0level(fluidatthebottomofthemaximumlevelindication mark),ofeachconnected cellisgreaterthanorequalto1.200andhasnotdecreased morethan0.03fromthevalueobservedduringtheprevioustest,and3.Theelectrolyte levelofeachconnected cellisbetveenthetopofthe'minimumlevelindication markandthebottomofthemaximumlevelindication mark.c.Atleastonceper18monthsbyverifying that:1.Thecells,cellplatesandbatte~racksshownovisualindication ofphysicaldamageorabnormaldeterioration, 2.Thecell-to-cell andterminalconnections areclean,tight,freeofcorrosion andcoatedvithanti-corrosion
- material, 3.Thebatterychargervillsupplyatleast140amperesatgreaterthanorequalto250voltsforatleast4hours.d.Atleastonceper18months,performabattery'ervice testduringshutdown(MODES5or6),byverifying thatthebatterycapacityisadequatetosupplyandmaintainiOPERABLEstatustheactualorsimulated emergency loadsfortheThebatteryterminalvoltageshallbemaintained greatethanorequalto210voltsthroughout thistest.designdutycyclewhichisbasedonthecomposite loadprofile.Thecomposite loadprofileenvelopes boththeLOCA/LOOP andStationBlackoutprofilesandprovidesthebasisforthetimeslistedinTable4.8-2.Thebatterychargerwillbedisconnected throughout thetes~COOKNUCLEARPLANT-UNIT13/48-13AMENDMENT No.fg155 ELECTRICAL POWERSYSTEMSSURVEILLANCE REUIREMENTS Continued e.ths-,perforat-a-'l~attery-t5sc shutdown(MOOESo,verifying thatthebatter15atleast80Xofthemanufacturer
'rormancedischarge testshalbe-pe1nplaceofservicetest%tleastonceper60months,conductaperformance testofbatterycapacityduringshutdown(MODES5or6),byverifying thatthcbatterycapacityisatleast80%ofthemanufacturer's rating.Whenthistestisperformed inplaceofabatteryservicetest,amodifiedperformance testshallbeconducted.
Annualperformance testsofbatterycapacityshallbegiventoanybatterythatshowssignsofdegradation orhasreached85%oftheservicelifeexpectedfortheapplication, Degradation isindicated wheuthcbatterycapacitydropsmorethan10%fromitscapacityonthepreviousperformance test,orisbelow90%ofthemanufacturer's rating.Ifthebatteryhasreached85%ofservicelife,deliversacapacityof100%orgreaterofthemanufacturer's ratedcapacity, andhasshownnosignsofdegradation, performance testingattwoyearintervals isacceptable untilthebatteryshowssignsofdegradation~
D.CCOOK-UNIT13/48-14AMENOMENT NO'25 TABLE4.8-2BATTERYEMERGENCY LOAOSA~BI<<Ld1.ChannelIIIstaticinverter2.ChannelIVstaticinverterMinimumTime4P'hrs4fhrs$j(+p.$8.&feedpumpturbine+oiipumpControlroomemergency lightingHainturbinebackupoilpumpIsolation valvecontrolAllcontrolcircuits1hr4Phrs(dthrs4Phrs4jfhrs~LBII<<Ld1.ChannelIstaticinverter2.ChannelIIstaticinverter3.BOPstaticinverter"
~<ctdP<
4.'I'eedpumpturbinerggoi1pumpg~~87HC%6~44 5.Generator)seal oilpump6.i'n8urbine emergency oilpump7.Isolation valves8.Annunciators9.Allcontrolcircuits'ffhrs+ghrsgghrs1hr4P'rsIghrs4.Phrsgghrsditj(brspowersourcestotheinverters shallbeturnedoffatthestartofthetestandmaybeturnedonattheendofthespecified timeinterval.
Inverters maybeleftinthisoperating modeforthedurationofthedischarge test.D.C.COOK-UNIT13/48-15AMENDMENT NO.125 ELECTRICAL POWERSYSTEMSSURVEILLANCE REUIREMENTS Continued 3.Thepilotcellvoltageisgreaterthanorequalto2.13volts,and4.Theoverallbatteryvoltageisgreaterthanorequalto250volts.b.Atleastonceper92daysbyverifying that:1.Thevoltageofeachconnected cellisgreaterthanorequalto2.13voltsunderfloatcharge.2.Thespecificgravity,corrected to77Fand,fullelectrolyte olevel(fluidatthebottomofthemaximumlevelindication mark),ofeachconnected cellisgreaterthanorequalto1.200andhasnotdecreased morethan0.03fromthevalueobservedduringtheprevioustest,and3.Theelectrolyte levelofeachconnected cellisbetweenthetopoftheminimumlevelindication markandthebotto'mofthemaximumlevelindication mark.c~Atleastonceper18monthsbyverifying that:1.Thecells,cellplatesandbatteryracksshownovisualindication ofphysicaldamageorabnormaldeterioration.
2.Thecell-to-cell andterminalconnections areclean,tight,freeofcorrosion andcoatedwithanti-corrosion material.
3.Thebatterychargervillsupplyatleast10amperesatgreaterthanorequalto250voltsforatleast4hours.d.Atleastonceper18monthsperformabatteryservicetest,duringshutdown(MODES5or6),byverifying thatthebatterycapacityisadequatetosupplyandmaintaininOPERABLEstatustheactualorsimulated emergency loadsforthetimesspecified ofTable4,8-3withthebatterychargerdisconnected.
Thebatteryterminalvoltageshallbemaintained greaterthanorequalto210voltsthroughout thebatteryservicetest.e~AHENDMENT NO.P),155duringshut5or6),byveriebatterycapacityisatleast80%octurer'srating.This~performance etestshallbeperformeofthe~-WH~W7-~&7COOKNUCLEARPLANT-UNIT13/48-18
Atleastouceper60months,conductaperformance testofbatterycapacityduringshutdown(MODES5or6),byveri%ging thatthebatterycapacityisatleast80%ofthcmanufacturer's rating.Whenthistestisperformed inplaceofabatteryservicetest,amodifiedperformance testshallbeconducted.
Annualpcrformancc testsofbatterycapacityshallbegiventoanybatterythatshowssignsofdegradation orhasreached85%ofthcservicelifeexpectedfortheapplication.
Degradation isindicated whenthebatterycapacitydropsmorethan10%fromitscapacityonthepreviousperformance test,orisbelow90%ofthemanufacturer's rating.Ifthebatteryhasreached85%ofservicelife,deliversacapacityof100%orgreaterofthemanufacturer's ratedcapacity, andhasshownnosignsofdegradation, performance testingattwoyearintervals isacceptable untilthebatteryshowssignsofdegradation.
TABLE4.8-3BATTERYEMERGENCY LOADS"H"BatterLoadsAuxiliary feedwater turbinecontrolbusFMO-211valveFMO-221valveFMO-231valveFMO-241valveTDTVvalyeMinimumTime4hours+~bouc'4~($c}.pg,~(s+)h<uc<ggars*Valves2..3.willbeoperatedthroughthefollowing sequence:
Beginning oftest:openvalvesFiveminutesafterthebeginning hetes't:closethevalves.~~Tenminutesafter+Aeginningofthetest:reopenthevalves.4.Fourhouafterthebeginning ofthetest:closethevalves.Endof"thetest.D.C.COOK-UNIT13/48-19AMEHDMEHT NO.125I
3/4.8ELECTRICAL POMERSYSTEMSBASESTheOPERABILITY oftheA.C.andD.C.powersourcesandassociated distribution systemsduringoperation ensuresthatsufficient powerwillbeavailable tosupplythesafetyrelatedequipment requiredfor1)thesafeshutdownofthefacilityand2)themitigation andcontrolofaccident'conditions withinthefacility.
Theminimumspecified independent andredundant A.C.andD.C.powersourcesanddistribution systemssatisfytherequirements ofGeneralDesignCriteria17ofAppendix"A"to10CFR50.TheACTIONrequirements specified forthelevelsofdegradation ofthepowersourcesproviderestriction uponcontinued facilityoperation commensurate withthelevelofdegradation.
TheOPERABILITY ofthepowersourcesareconsistent withtheinitialcondition assumptions oftheaccidentanalysesandarebaseduponmaintaining atleastoneofeachoftheonsiteA.C.andD.C.powersourcesandassociated distribution systemsOPERABLEduringaccidentconditions coincident withanassumedlossofoffsitepowerandsinglefailureoftheotheronsiteA.C.source.TheOPERABILITY oftheminimumspecified A.C.andD.C.powersourcesandassociated distribution systemsduringshutdownandrefueling ensuresthat1)thefacilitycanbemaintained intheshutdownorrefueling condition forextendedtimeperiodsand2)sufficient instrumentation andcontrolcapability isavailable formonitoring andmaintaining thefacilitystatus.ThetrainNstationbatterysystemprovidesanindependent 250voltDCpowersupplyforpowerandcontroloftheturbinedrivenauxiliary feedwater pumptrain.Thelimitingconditions ofoperation forthetrainNbatteryareconsistent withtherequirements oftheauxiliary feedwater system.Thesurveillance requirements forthetrainNbatterysystemareconsistent withtherequirements oftheABandCDstationbatteries.
ThetrainNbatteryloadsarederivedfromequipment intheturbinedrivenauxiliary feedwater pumptrainandbattery.sizingisconsistent withthefunctional requirements ofthesecomponents.
Simulated loadsforbatterytestsareloadsequivalent tomeasuredactualloads.~TheABandCDstationbatterysystemsprovideareliablesourceofcontinuous powerforsupplyandcontrolofplantloadssuchasswitchgear 6annunciator controlcircuits, staticinverters, valvecontrolcenters,emergency lightingandmotorcontrolcenters.Thedesigndutycyclesofthesebatteries arecomposite loadprofilesresulting fromthecombination ofthethreehourLossOfCoolantAccident/Loss OfOffsitePowerbatteryloadprofilesandthefourhourStationBlackoutbatteryloadprofiles.
DC.COOK-UNIT1B3/48-1Amendment No.86002OO0S00I8 ECOSVSSSURVEILLANCE UXREMSCotuedI2.Thepilotcellspecificgravj.ty, corrected to77F,andfull'lectrolyte level(fluidatthebottomofthemaximumlevelindication mark),isgreaterthanorequalto1.200,3.Thepilotcellvoltageisgxeaterthanorequalto2.13volts,and4..Theoverallbatteryvoltageisgreaterthanorequalto250volts.b.Atleaseonceper92daysbyveri.fying"Chat:
I1.Thevoltageofeachconnected cellisgreaterthanorequalto2.13voltsunderfloatcharge.2.3;Thespecificgravity,corrected to77F,andfull'*e3.:ectrolyte level(fluidatthebottomofthemaximumlevelindication mark),ofeachconnected cellisgreaterthan'requalto1.200andhasnotdecreased morethan0.03fromthevalueobservedduringtheprevioustest,andTheelectrolyte levelofeachconnected cellisbetveenthetop.oftheminimumlevelindication markandthebottomofthemaximumlevelindication mark.c~Atleastonceper18monthsbyverifying that:1.Thecells,.cellplatesandbatteryracksshov'novisualindication ofphysicaldamageorabnormaldeterioration, 2.3.Thecell-to-cell andterminalconnections areclean,tight,freeofcox'rosion andcoatedvithanti-corrosion
- material, Thebatterychargervillsupplyatleast140amperesatgreaterthanorequalto250voltsforatleast4'hours.*
d.Atleast:onceper18months,performabatteryservicetestduringshutdovn(MODES5or6),byverifying thatthebatCexycapacityisadequatetosupplyandmaintain.
inOPERABLEstatustheactu'alorsimulated emergency loadsforCheebattexyterminalvoltageshallbemainCained greaterChanorequalto210voltsthroughout thistest.*>designdarycyclewhichisbasedonthecomposite loadprofite.Thecomposite loadprofileenvelopes boththeLOCA/LOOP andStationBlackoutprofilesandprovidesthebasisforthetimeslistedinTable4.8-2.Thebatterychargerwillbedisconnected throughout thetest.~eprovisions ofSpecification
4.0. 9areapplicable
tothe2-CDbatteryandcharger.COOKNUCLEARPLANT-UNXT23/48-13AMENDMENT NO.~,~166
ELECTRICAL POWERSYSTEMSSURVEILLANCE REUIREMEHTS Continued
'e.1shutdo5or6),byverifying thatthebestyisatleast80Koftettjrer'sperformance discharge tests0laceofthebatteryservicetAtleastonceper60months,conductaperformance testofbatterycapacityduringshutdown(MODES5or6),byverifying thatthebatterycapacityisatleast80%ofthemanufacturer's rating.-Whcnthistestisperformed inplaceofabatteryservicetest,amodifiedperformance testshallbeconducted.
Annualpcrformancc testsofbatterycapacityshallbcgiventoanybatterythatshowssignsofdegradation orhasreached85%oftheservicelifeexpectedfortheapplication.
Degradation isindicated whenthcbatterycapacitydropsmorethan10%fromitscapacityonthepreviousperformance test,orisbelow90%ofthemanufacturer's rating.Ifthebatteryhasreached85%ofservicelife,deliversacapacityof100%orgreaterofthemanufacturer's ratedcapacity, andhasshownnosignsofdegradation, performance testingattwoyearintervals isacceptable untilthebatteryshowssignsofdegradation~'
~yCD.CCOOK-UNIT23/48-14AMENOMENT NO.U2
TABLE4.8-2BATTERYEMERGENCY LOADSABBatterLoads1.ChannelIIIstaticinverter2.ChannelIVstaticinverterMinimumTime4P'rs4P'hrsSP'.Bopstaticinverter" gP.&peedpumpturbineffoiIpumpControlroamemergency lighting@$fPj.MainturbineAemergency oilpumpr7g.Isolation valvecentralSP.A11controlcircuits0Shrs1hri'rsIghrsiAP'rs4/hrsCDBatteLoads1.ChannelIstaticinverter2.ChannelIIstaticinverter3.eedpumpturbineoilpumpRa<~&C4.Generosealoslpump5.'ainturbind<emergency oilpump6.Isolation valves7.Annunciators 8.AllcontrolcircuitsgP'r's+ghrs1hr+PhrslPhrs4Phrs4jfhrs+Phrs~~ACpowersourcestotheinverters shallbeturnedoffatthestartofthetestandmaybeturnedonattheendofthespecified timeinterval.
Inverters maybeleftinthisoperating modeforthedurationofthedischarge test.0.C.COOK-UNIT23/48-15AMEHDMEHT HO.M2
0'LECTRICAL POWERSYSTEMSSURVEILLANCE UIEUBKNTS Continued 3.Thepilotcellvoltageisgreaterthanorequalto2.13volts,and4.Theoverallbatteryvoltageisgreatertluurorequalto250volts.b.Atleastonceper92daysbyverifying that:1.Thevoltageofeachconnected cellisgreaterthanorequalto2.13voltsunderfloatcharge.2.Thespecificgravity,corrected to77Fandfullelectrolyte level(fluidatthebottomofthemaximumlevelindication mark),ofeachconnected cellisgreaterthanorequalto1.200andhasnotdecreased morethan0.03fromthevalueobservedduringtheprevioustest,and3.Theelectrolyte levelofeachconnected cellisbetveenthetopoftheminimumlevelindication markandthebottomofthemaximumlevelindication mark.c.-Atleastonceper18monthsbyverifying that:1.Thecells,cellplatesandbatteryracksshovnovisualindication ofphysicaldamageorabnormaldeterioration.
2.3.Thecell-to-cell andterminalconnections areclean,tight,freeofcorrosion andcoatedwithanti-corrosion material.
Thebatterychargervillsupplyatlea'st10amperesat.greaterthanore'qualto250voltsforatleast4hours.d.Atleastonceper18monthsperformabatteryservicetest,duringshutdown(MODES5or6),byverifying thatthebatterycapacityisadequatetosupplyandmaintaininOPERABLEstatustheactualorsimulated emergency loadsforthetimesspecified ofTable4.8-3withthebatterychargerdisconnected.
Thebatteryterminalvoltageshallbemaintained greaterthanorequalto210voltsthroughout thebatteryservicetest.e.AlKMDMWfN0.PP,139duringsuDES5or6),byverifebatterycapacityisatleast8acturer's rating.Thisperforgetestshallbepelaceofthe~eS~~1~7-f'~gCCOOKNUCLEARPMT-UNIT23/48-18 Atleastonceper60months,conductaperformance testoFbatterycapacityduringshutdown~(MODES5or6),byverifying thatthebatterycapacityisatleast80%ofthemanufacturer's rating.Whenthistestisperformed inplaceofabatteryservicetest,amodifiedperformance testshallbeconducted.
Annualperformance testsofbatterycapacityshallbegiventoanybatterythatshowssignsofdegradation orhasreached85%oftheservicelifeexpectedfortheapplication.
Degradation isindicated whenthebatterycapacitydropsmorethan10%fromitscapacityonthepreviousperformance test,orlsbelow90%ofthemanufacturer's rating.Ifthcbatteryhasreached85%ofservicelife,deHversacapacityof100%orgreaterofthemanufacturer's ratedcapacity, andhasshownnosignsofdegradation, performance testingattwoyearintervals isacceptable untilthebatteryshowssignsofdegradation.
TABLE4.8-3BATTERYEMERGENCY LOADS"H"BatterLoadsAuxiliary feedwater turbinecontrolbusFMO-211valveFMO-221valveFMO-231valveFMO-241valveTDTVvalveMinimumTime4hours4.~h~urZ4~haut('x$~4ovf(f'~kopcJ"Valves2.3.~iiwillbeoperatedthroughthefollowing sequence:
Beginning oftest:openvalvesFiveminutesafterthebegi~intheteW:closethevalves.w~PQP'0Tenminutesafter4ebeginning ofthetest:reopenthevalves.4.Fourursafterthebeginning ofthetest:closethevalves.Endofthetest.0.C.COOK"UNIT23/48-19,.AMEHDMEHT HO.~2'normnnn
3/4.8ELECTRICAL POWERSYSTEHSBASESTheOPERABILITY oftheA.C.andD.C.powersourcesandassociated distribution systemsduringoperation ensuresthatsufficient powerwillbeavailable tosupplythesafetyrelatedequipment requiredfor1)thesafeshutdownofthefacilityand2)themitigation andcontrolofaccidentconditions withinthefacility.
Theminimumspecified independent andredundant A.C.andD,C.powersourcesanddistribution systemssatisfytherequirements ofGeneralDesignCriteria17ofAppendix"A"to10CFR50.TheACTIONrequirements specified forthelevelsofdegradation ofthepowersourcesproviderestriction uponcontinued facilityoperation commensurate withthelevelofdegradation.
TheOPERABILITY ofthepowersourcesareconsistent withtheinitialcondition assumptions oftheaccidentanalysesandarebaseduponmaintaining atleastoneredundant setofonsiteA.C.andD.C.powersourcesandassociated distribution systemsOPERABLEduringaccidentconditions coincident withanassumedlossofoffsitepowerandsinglefailureoftheotheronsiteA.C.source.TheOPERABILITY oftheminimumspecified A.C.andD.C.powersourcesandassociated distribution systemsduringshutdownandrefueling ensuresthat1)thefacilitycanbemaintained intheshutdownorrefueling condition forextendedtimeperiodsand2)sufficient instrumentation andcontrolcapability isavailable formonitoring andmaintaining thefacilitystatus.ThetrainNstationbatterysystemprovidesanindependent 250voltDCpowersupplyforpowerandcontroloftheturbinedrivenauxiliary feedwater'ump train.Thelimitingconditions ofoperation forthetrainNbatteryareconsistent withtherequirements oftheauxiliary feedwater system.Thesurveillance requirements forthetrainNbatterysystemareconsistent withtherequirements oftheABandCDstationbatteries.
ThetrainNbatteryloadsarederivedfromequipment intheturbinedrivenauxiliary feedwater pumptrainandbatterysizingisconsistent withthefunctional requirements ofthesecomponents.
Simulated loadsforbatterytestsareloadsequivalent tomeasuredactualloads.~TheABandCDstationbatterysystemsprovideareliablesourceofcontinuous
.powerforsupplyandcontrolofplantloadssuchasswitchgear 6annunciator controlcircuits, staticinverters, valvecontrolcenters,emergency lightingandmotorcontrolcenters.Thedesigndutycyclesofthesebatteries arecomposite loadprofilesresulting fromthecombination ofthethreehourLossOfCoolantAccident/Loss OfOffsitePowerbatteryloadprofilesandthefourhourStationBlackoutbatteryloadprofiles~D.C.COOK-UNIT2B3/48-1Amendment No.72 ATTACHMENT 2TOAEP:NRC:0896U PROPOSEDREVISEDTECHNICAL SPECIFICATION PAGES 4'>"~~P 3/4.0LIMITINGCONDITION FOROPERATION ANDSURVEILLANCE REQUIREMENTS 3/4.8ELECTRICAL POWERSYSTEMSD..DISTRIBTIN-PERATINGLIMITINGCONDITION FOROPERATION 3.8.2.3Thefollowing D.C.bustrainsshallbeenergized andOPERABLEwithtiebreakersbetweenbustrainsopen:TRAINABconsisting of250-voltD.C.busAB,250-voltD.C.batterybankNo.1AB,andafullcapacitycharger,andTRAINCDconsisting of250-voltD.C.busCD,250-voltD.C.batterybankNo.1CD,andafullcapacitycharger.~*'ACTIONMODES1,2,3and4.Withone250-voltD.C.businoperable, restoretheinoperable bustoOPERABLEstatuswithin2hoursorbeinatleastHOTSTANDBYwithinthenext6hoursandinCOLDSHUTDOWNwithinthefollowing 30hours.b.Withone250-voltD.C.batteryand/oritschargerinoperable, restoretheinoperable batteryand/orchargertoOPERABLEstatuswithin2hoursorbeinatleastHOTSTANDBYwithinthenext6hoursandinCOLDSHUTDOWNwithinthefollowing 30hours.SURVEILLANCE REUIREMENTS 4.8.2.3.1 4.8.2.3.2 EachD.C.bustrainshallbedetermined OPERABLEandenergized withtiebreakersopenatleastonceper7daysbyverifying correctbreakeralignment andindicated poweravailability.
Each250-voltbatterybankandchargershallbedemonstrated OPERABLEAtleastonceper7daysbyverifying that:Theelectrolyte levelofeachpilotcellisbetweentheminimumandmaximumlevelindication marks,Thepilotcellspecificgravity,corrected to77'F,andfullelectrolyte level(fluidatthebottomofthemaximumlevelindication mark),isgreaterthanorequalto1.200,Thepilotcellvoltageisgreaterthanorequalto2.13volts,andTheoverallbatteryvoltageisgreaterthanorequalto250volts.COOKNUCLEARPLANT-UNIT 1Page3/48-12AMENDMENT
~
3/4,0LIMITINGCONDITION FOROPERATION ANDSURVEILLANCE REQUIREMENTS 3/4.8ELECTRICAL POWERSYSTEMSSURVEILLANCE REUIREMENTS Continued Atleastonceper92daysbyverifying that:1.Thevoltageofeachconnected cellisgreaterthanorequalto2.13voltsunderfloatcharge.Thespecificgravity,corrected to77'F,andfullelectrolyte level(fluidatthebottomofthemaximumlevelindication mark),ofeachconnected cellisgreaterthanorequalto1.200andhasnotdecreased morethan0.03fromthevalueobservedduringtheprevioustest,andTheelectrolyte levelofeachconnected cellisbetweenthetopoftheminimumlevelindication markandthebottomofthemaximumlevelindication mark.Atleastonceper18monthsbyverifying that:1.Thecells,cellplatesandbatteryracksshownovisualindication ofphysicaldamageorabnormaldeterioration, 2.Thecell-towell andterminalconnections areclean,tight,freeofcorrosion andcoatedwithantiworrosion
- material, Thebatterychargerwillsupplyatleast140amperesatgreaterthanorequalto250voltsforatleast4hours.Atleastonceper18months,performabatteryservicetestduringshutdown(MODES5or6),byverifying thatthebatterycapacityisadequatetosupplyandmaintaininOPERABLEstatustheactualorsimulated emergency loadsforthedesigndutycyclewhichisbasedonthecomposite loadprofile.Thecomposite loadprofileenvelopes boththeLOCA/LOOP andStationBlackoutprofilesandprovidesthatbasisforthetimeslistedinTable4.8-2.Thebatterychargerwillbedisconnected throughout thetest.Thebatteryterminalvoltageshallbemaintained greaterthanorequalto210voltsthroughout thistest.e.Atleastonceper60months,conductaperformance testofbatterycapacityduringshutdown(MODES5or6),byverifying thatthebatterycapacityisatleast80%ofthemanufacturer's rating.Whenthistestisperformed inplaceofabatteryservicetest,amodifledperformance testshallbeconducted.
Annualperformance testsofbatterycapacityshallbegiventoanybatterythatshowssignsofdegradation orhasreached85%oftheservicelifeexpectedfortheapplication.
Degradation isindicated whenthebatterycapacitydropsmorethan10%fromitscapacityonthepreviousperformance test,orisbelow90%ofthemanufacturer's rating.Ifthebatteryhasreached85%ofservicelife,deliversacapacityof100%orgreaterofthemanufacturer's ratedcapacity, andhasshownnosignsofdegradation, performance testingattwoyearintervals isacceptable untilthebatteryshowssignsofdegradation.
COOKNUCLEARPLANT-UNIT 1Page3/48-13AMENDMENT 42$,4' 3/4.0LIMITINGCONDITION FOROPERATION ANDSURVEILLANCE REQUIREMENTS 3/4.8ELECTRICAL POWERSYSTEMSTABLE4.8-2BATI'ERYEMERENYLOADABBatteLoadsMinimumTime2.6.ChannelIIIstaticinverterChannelIVstaticinverterEastfeedpumpturbineemergency oilpumpControlroomemergency lightingMainturbinebackupoilpumpIsolation valvecontrolAllcontrolcircuits1hr1hrDBattead2.4,5.9.ChannelIstaticinverterChannelIIstaticinverterBOPstaticinverterWestfeedpumpturbineemergency oilpumpGenerator hydrogenemergency sealoilpumpMainturbineemergency oilpumpIsolation valvesAnnunciators AllcontrolcircuitsACpowersourcestotheinverters shallbeturnedoffatthestartofthetestandmaybeturnedonattheendofthespecified timeinterval.
Inverters maybeleftinthisoperating modeforthedurationofthedischarge test.COOKNUCLEARPLANT-UNIT 1Page3/48-14AMENDMENT
~
0 3/4.0LIMITINGCONDITION FOROPERATION ANDSURVEILLANCE REQUIREMENTS 3/4.8ELECTRICAL POWERSYSTEMSD.C.DISTRIBUTION
-SHUTDOWN.LIMITINNDITIONFORPERATION3.8.2.4Asaminimum,thefollowing D.C.electrical equipment andbusshallbeenergized andOPERABLE:
1-250-voltD.C.bus,and1-250-voltbatterybankandchargerassociated withtheaboveD.C.bus.APPLICABILITY:
MODES5and6.~ATION:Withlessthantheabovecomplement ofD.C.equipment andbusOPERABLE, establish CONTAINMENT INTEGRITY within8hours.SURVEILLANCE REUIREMENT4.8.2.4.1 4.8.2.4.2 Theaboverequired250-voltD.C.busshallbedetermined OPERABLEandenergized atleastonceper7daysbyverifying correctbreakeralignment andindicated poweravailability.
Theaboverequired250-voltbatterybankandchargershallbedemonstrated OPERABLEperSurveillance Requirement 4.8.2.3.2.
COOKNUCLEARPLANT-UNIT 1Page3/48-15AMENDMENT 4%
3/4.0LIMITINGCONDITION FOROPERATION ANDSURVEILLANCE REQUIREMENTS 3/4.8ELECTRICAL POWERSYSTEMSDC.DITRIBUTION
-OPERATING
-TRAINNBALI'ERYSYSTEIMITINGCONDITION FOROPERATION 3.8.2.5Thefollowing D.C.bustrainshallbeenergized andOPERABLE:
TRAINNconsisting of250-voltD.C.busN,250-voltD.C.batterybankN,andafullcapacitycharger.WiththeTrainNbatterysysteminoperable, declaretheturbinedrivenAuxiliary Feedwater Pumpinoperable andfollowtheACTIONstatement ofSpecification 3.7.1.2.SRVEILLANCE REUIREMENTS 4.8.2.5.1 TheD.C.bustrainNshallbedetermined OPERABLEandenergized atleastonceper7daysbyverifying correctbreakeralignment andindicated poweravailability.
4.8.2.5.2 IThe250-voltbatterybankandchargershallbedemonstrated OPERABLE:
Atleastonceper7daysbyverifying that:Theelectrolyte levelofeachpilotcellisbetweentheminimumandmaximumlevelindication marks,2..Thepilotcellspecificgravity,corrected to77'Fandfullelectrolyte level(fluidatbottomofthemaximumlevelindication mark),isgreaterthanorequalto1.200,3.Thepilotcellvoltageisgreaterthanorequalto2.13volts,and4.Theoverallbatteryvoltageisgreaterthanorequalto250volts.Atleastonceper92daysbyverifying that:1.Thevoltageofeachconnected cellisgreaterthanorequalto2.13voltsunderfloatcharge.Thespecificgravity,corrected to77'Fandfullelectrolyte level(fluidatthebottomofthemaximumlevelindicationmark),
ofeachconnected cellisgreaterthanorequalto1.200andhasnotdecreased morethan0.03fromthevalueobservedduringtheprevioustest,and3.-Theelectrolyte levelofeachconnected cellisbetweenthetopoftheminimumlevelindication markandthebottomofthemaximumlevelindication mark.COOKNUCLEARPLANT-UNIT 1Page3/48-16 3/4.0LIMITINGCONDITION FOROPERATION ANDSURVEILLANCE REQUIREMENTS 3/4.8ELECTRICAL POWERSYSTEMSSURVEILLANCE REUIREMENTS ontinuedAtleastonceper18monthsbyverifying that:1~Thecells,cellplatesandbatteryracksshownovisualindication ofphysicaldamageorabnormaldeterioration.
2.Thecell-to-cell andterminalconnections areclean,tight,freeofcorrosion andcoatedwithantieorrosion material.
3.Thebatterychargerwillsupplyatleast10amperesatgreaterthanorequalto250voltsforatleast4hours.Atleastonceper18monthsperformabatteryservicetest,duringshutdown(MODES5or6),byverifying thatthebatterycapacityisadequatetosupplyandmaintaininOPERABLEstatustheactualorsimulated emergency loadsforthetimesspecified ofTable4.8-3withthebatterychargerdisconnected.
Thebatteryterminalvoltageshallbemaintained greaterthanorequalto210voltsthroughout thebatteryservicetest.Atleastonceper60months,conductaperformance testofbatterycapacityduringshutdown(MODES5or6),byverifying thatthebatterycapacityisatleast80%ofthemanufacturer's rating.Whentinstestisperformed inplaceofabatteryservicetest,amodifiedperformance testshallbeconducted.
Annualperformance testsofbatterycapacityshallbegiventoanybatterythatshowssignsofdegradation orhasreached85%oftheservicelifeexpectedfortheapplication.
Degradation isindicated whenthebatterycapacitydropsmorethan10%fromitscapacityonthepreviousperformance test,orisbelow90%ofthemanufacturer's rating.Ifthebatteryhasreached85%ofservicelife,deliversacapacityof100%orgreaterofthemanufacturer's ratedcapacity, andhasshownnosignsofdegradation, performance testingattwoyearintervals isacceptable untilthebatteryshowssignsofdegradation.
COOKNUCLEARPLANT-UNIT 1Page3/48-17AMENDEIENT 4K,455 3/4.0LIMITINGCONDITION FOROPERATION ANDSURVEILLANCE REQUIREMENTS 3/4.8ELECTRICAL POWERSYSTEMSTABLE4.-BATTERYEMERGENCY LOADS"N"BatteadsAuxiliary feedwater turbinecontrolbusFMO-211valveFMO-221valveFMO-231valveFMO-241valveTDTVvalveMinimumTime4hours4hours4hours4hours4hours4hoursCOOKNUCLEARPLANT-UNIT 1Page3/48-18AMENDMENT AS
3/4.0LIMITINGCONDITION FOROPERATION ANDSURVEILLANCE REQUIREMENTS 3/4.8ELECTRICAL POWERSYSTEMS/4.Alternative ACPowerSurcesLIMITINCNDITIONFOROPERATIN3.8.3.1Thesteadystatebusvoltageforthemanualalternate reservesourceshallbegreaterthanorequalto90%ofthenominalbusvoltage.~ACTINSURVEILLAN EREIREMENTSAPPLICABILITY:
Wheneverthemanualalternate reservesource(69kV)isconnected tomorethantwobuses.Withbusvoltagelessthan90%nominal,adjustloadontheremaining busestomaintainsteadystatebusvoltagegreaterthanorequalto90%limit.4.8.3.1Noadditional surveillance requirements otherthanthoserequiredbySPecifications 4.8.1.1.1 and4.8.1.2.SharedwithD.C.CookUnit2.COOKNUCLEARPLANT-UNIT 1Page3/48-19
3/4BASES3/4.8ELECTRICAL POWERSYSTEMSTheOPERABILITY oftheA.C.andD.Cpowersourcesandassociated distribution systemsduringoperation ensuresthatsufficient powerwillbeavailable tosupplythesafetyrelatedequipment requiredfor1)thesafeshutdownofthefacilityand2)themitigation andcontrolofaccidentconditions withinthefacility.
Theminimumspecified independent andredundant A.C.andD.C.powersourcesanddistribution systemssatisfytherequirements ofGeneralDesignCriteria17ofAppendix"A"to10CFR50.TheACTIONrequirements specified forthelevelsofdegradation ofthepowersourcesproviderestriction uponcontinued facilityoperation commensurate withthelevelofdegradation.
TheOPERABILITY ofthepowersourcesareconsistent withtheinitialcondition assumptions oftheaccidentanalysesandarebaseduponmaintaining atleastoneofeachoftheonsiteA.C.andD.C.powersourcesandassociated distribution systemsOPERABLEduringaccidentconditions coincident withanassumedlossofoffsitepowerandsinglefailureoftheotheronsiteA.C.source.TheOPERABILITY oftheminimumspecified A.C.andD.C.powersourcesandassociated distribution systemsduringshutdownandrefueling ensuresthat1)thefacilitycanbemaintained intheshutdownorrefueling condition forextendedtimeperiodsand2)sufficient instrumentation andcontrolcapability isavailable formonitoring andmaintaining thefacilitystatus.TheABandCDstationbatterysystemsprovideareliablesourceofcontinuous powerforsupplyandcontrolofplantloadssuchasswitchgear andannunciator controlcircuits, staticinverters, valvecontrolcenters,emergency lightingandmotorcontrolcenters.Thedesigndutycyclesofthesebatteries arecomposite loadprofilesresulting fromthecombination ofthethreehourLossOfCoolantAccident/Loss OfOffsitePowerbatteryloadprofilesandthefourhourStationBlackoutbatteryloadproliies.
ThetrainNstationbatterysystemprovidesanindependent 250voltDCpowersupplyforpowerandcontroloftheturbinedrivenauxiliary feedwater pumptrain.Thelimitingconditions ofoperation forthetrainNbatteryareconsistent withtherequirements oftheauxiliary feedwater system.Thesurveillance requirements forthetrainNbatterysystemareconsistent withtherequirements oftheABandCDstationbatteries.
ThetrainNbatteryloadsarederivedfromequipment intheturbinedrivenauxiliary feedwater pumptrainandbatterysizingisconsistent withthefunctional requirements ofthesecomponents.
Simulated loadsforbatterytestsareloadsequivalent tomeasuredactualloads.COOKNUCLEARPLANT-UNIT 1PageB3/48-1AMENDMENT 86 3/4BASES3/4.8ELECTRICAL POWERSYSTEMSRemoval.ofaccumulated waterasrequiredby4.8.1.1.2.b.2 isperformed bydrawingthecontentsoffthebottomofthetankuntilacceptable resultsareobtainedforeitheratapetestorawaterandsedimenttest.Anacceptable
.resultforthewaterandsedimentcontentisameasuredvaluelessthan0.05percentvolume.Thesamplespecified in4.8.1.1.2.c.4 issentoffsitefortesting.Aseriousattemptwillbemadetomeetthe31-daylimitontheoffsitetests;however,ifforsomereasonthislimitisnotmet(e.g.,ifthesampleislostorbrokenoriftheresultsarenotreceivedin31days),thedieselgenerators shouldnotbeconsidered inoperable.
Ifthesampleislost,broken,orfailstheoffsitetestsandthenewoilhasalreadybeenputintothestoragetank,theoffsitetestswillbeperformed onasampletakenfromthestoragetank.Iftheresultsonthesubsequent storagetanksamplearenotwithinspecified limits,thedieselgenerators shouldbeconsidered OPERABLEandtheout-of-spec properties shouldbereturnedtowithinspecification assoonaspossible.
Ifthemonthlystoragetanksampletakeninaccordance withSpecification 4.8.1.1.2.d failstheparticulate contamination test,thedieselgenerators shouldbeconsidered OPERABLEandthecontamination levelshouldberestoredtobelow10mg/literassoonaspossible.
Theprecision leak-detection testdescribed inSurveillance Requirement 4.8.1.1.2.f.2 shouldbeperformed asdescribed inNFPA(National FireProtection Association)
-329.AsNFPA-329isrevised,theprecision leak-detection testmaybemodifiedtoincorporate changestothetestasdescribed intherevisions toNFPA-329, Theminimumrequireddieselfueloilvolumeis43,240gallons.Thisvolumeisconsistent withoperation ofonedieselgenerator continuously for7daysatratedload,asrecommended inRegulatory Guide1.137,entitled"FuelOilSystemforStandbyDieselGenerators."
TheTechnical SpeciIications requireaminimumof46,000gallonsoffuel.The46,000gallonsisanindicated volume.Thisamountincludesmarginforcharacteristics suchaslocationofthetankdischarge pipesandslopeofthetanks.COOKNUCLEARPLANT-UNIT 1PageB3/48-2AMENDMENT
~,145 3/4.0LIMITINGCONDITION FOROPERATION ANDSURVEILLANCE REQUIREMENTS 3/4.8ELECTRICAL POWERSYSTEMSCDISTRIBN-PERATINLIMITINNDITIONFRPERATIN3.8.2.3Thefollowing D.C.bustrainsshallbeenergized andOPERABLEwithtiebreakersbetweenbustrainsopen:TIGONABconsisting of250-voltD.C.busAB,250-voltD.C.batterybankNo.2AB,andafullcapacitycharger,andTI4QNCDconsisting of250-voltD.C.busCD,250-voltD.C.batterybankNo.2CD,andafullcapacitycharger.~*~TI(~Na.Withone250-voltD.C.businoperable, restoretheinoperable bustoOPERABLEstatuswithin2hoursorbeinatleastHOTSTANDBYwithinthenext6hoursandinCOLDSHUTDOWNwithinthefollowing 30hours.b.Withone250-voltD.C.batteryand/oritschargerinoperable, restoretheinoperable batteryand/orchargertoOPERABLEstatuswithin2hoursorbeinatleastHOTSTANDBYwithinthenext6hoursandinCOLDSHUTDOWNwithinthefollowing 30hours.SURVEILLAN EREUIREMENT4.8.2.3.1 4.8.2.3.2 EachD.C.bustrainshallbedetermined OPERABLEandenergized withtiebreakersopenatleastonceper7daysbyverifying correctbreakeralignment andindicated poweravailability.
Each250-voltbatterybankandchargershallbedemonstrated OPERABLEAtleastonceper7daysbyverifying that:Theelectrolyte levelofeachpilotcellisbetweentheminimumandmaximumlevelindication marks,2,4,Thepilotcellspecificgravity,corrected to77'F,andfullelectrolyte level(fluidatthebottomofthemaximumlevelindication mark),isgreaterthanorequalto1.200,Thepilotcellvoltageisgreaterthanorequalto2.13volts,andTheoverallbatteryvoltageisgreaterthanorequalto250volts.COOKNUCLEARPLANT-UNIT 2Page3/48-12
3/4.0LIMITINGCONDITION FOROPERATION ANDSURVEILLANCE REQUIREMENTS 3/4.8ELECTRICAL POWERSYSTEMSVEILLAEREEMENTntinuedb.Atleastonceper92daysbyverifying that:1.Thevoltageofeachconnected cellisgreaterthanorequalto2.13voltsunderfloatcharge.2.Thespecificgravity,corrected to77'F,andfullelectrolyte level(fiuidatthebottomofthemaximumlevelindication mark),ofeachconnected cellisgreaterthanorequalto1.200andhasnotdecreased morethan0.03fromthevalueobservedduringtheprevioustest,and3.Theelectrolyte levelofeachconnected cellisbetweenthetopoftheminimumlevelindication markandthebottomofthemaximumlevelindication mark.C.Atleastonceper18monthsbyverifying that:1.Thecells,cellplatesandbatteryracksshownovisualindication ofphysicaldamageorabnormaldeterioration, 2.Thecell-to-cell andterminalconnections areclean,tight,freeofcorrosion andcoatedwithantimrrosion
- material, 3.Thebatterychargerwillsupplyatleast140amperesatgreaterthanorequalto250voltsforatleast4hours.d.Atleastonceper18months,performabatteryservicetestduringshutdown(MODES5or6),byverifying thatthebatterycapacityisadequatetosupplyandmaintaininOPERABLEstatustheactualorsimulated emergency loadsforthedesigndutycyclewhichisbasedonthecomposite loadprofile.Thecomposite loadprofileenvelopes boththeLOCA/LOOP andStationBlackoutprofilesandprovidesthatbasisforthetimeslistedinTable4.8-2.Thebatterychargerwillbedisconnected throughout thetest.Thebatteryterminalvoltageshallbemaintained greaterthanorequalto210voltsthroughout thistest.e.Atleastonceper60months,conductaperformance testofbatterycapacityduringshutdown(MODES5or6),byverifying thatthebatterycapacityisatleast80%ofthemanufacturer's rating.Whenthistestisperformed inplaceofabatteryservicetest,amodifiedperformance testshallbeconducted.
Annualperformance testsofbatterycapacityshallbegiventoanybatterythatshowssignsofdegradation orhasreached85%oftheservicelifeexpectedfortheapplication.
Degradation isindicated whenthebatterycapacitydropsmorethan10%&omitscapacityonthepreviousperformance test,orisbelow90%ofthemanufacturer's rating.Ifthebatteryhasreached85%ofservicelife,deliversacapacityof100%orgreaterofthemanufacturer's ratedcapacity, andhasshownnosignsofdegradation, performance testingattwoyearintervals isacceptable untilthebatteryshowssignsofdegradation.
Theprovisions ofSpecification
4.0. 9areapplicable
tothe2NDbatteryandcharger.COOKNUCLEARPLANT-UNIT 2Page3/48-13AMENDMENT 444,439,446
3/4.0LIMITINGCONDITION FOROPERATION ANDSURVEILLANCE REQUIREMENTS 3/4.8ELECTRICAL POWERSYSTEMS~TABLE4AITERYEMER ENYLADABBatteLoadsinimumTime3.4,5.6.7.ChannelIIIstaticinverterChannelIVstaticinverterBOPstaticinverterEastfeedpumpturbineemergency oilpumpControlroomemergency lightingMainturbineeastemergency oilpumpIsolation valvecontrolAllcontrolcircuitsIhrDBatteadsl.ChannelIstaticinverter2.Channel11staticinverterWestfeedpumpturbineemergency oilpump4.Generator hydrogenemergency sealair-oilpump5.Mainturbinewestemergency oilpump7.Isolation valvesAnnunciators AllcontrolcircuitsACpowersourcestotheinverters shallbeturnedoffatthestartofthetestandmaybeturnedonattheendofthespecified timeinterval.
Inverters maybeleftinthisoperating modeforthedurationofthedischarge test.COOKNUCLEARPLANT-UNIT 2Page3/48-14
lt3/4.0LIMITINGCONDITION FOROPERATION ANDSURVEILLANCE REQUIREMENTS 3/4.8ELECTRICAL POWERSYSTEMSDCDISTRIBN-WNLIMlTING NDITINFPERATIN3.8,2.4Asaminimum,thefollowing D.C.electrical equipment andbusshallbeenergized andOPERABLE:
1-250-voltD.C.bus,and1-250-voltbatterybankandchargerassociated withtheaboveD.C.bus.~ATION:Withlessthantheabovecomplement ofD.C.equipment andbusOPERABLE, establish CONTAINMENT INTEGRITY within8hours.URVEILLANCE REREMENTS4.8.2.4.1 4.8.2.4.2 Theaboverequired250-voltD.C.busshallbedetermined OPERABLEandenergized atleastonceper7daysbyverifying correctbreakeralignment andindicated poweravailability.
Theaboverequired250-voltbatterybankandchargershallbedemonstrated OPERABLEperSurveillance Requirement 4.8.2.3.2.
Theprovisions ofSpecification
4.0. 9areapplicable
totheSurveillance Requirements 4.8.2.3.2.c.3 and4.8.2.3.2.d forthe2-CDbatteryandcharger.COOKNUCLEARPLANT-UNIT 2Page3/48-15 3/4.0LIMITINGCONDITION FOROPERATION ANDSURVEILLANCE REQUIREMENTS 3/4.8ELECTRICAL POWERSYSTEMSD..DlTRIBIN-OPERATING
-TRAINNBALI'ERYSYSTEM,LIMITINCODITINFOROPERATION 3.8.2.5Thefollowing D.C.bustrainshallbeenergized andOPERABLE:
TRAINNconsisting of250-voltD.C.busN,250-voltD.C.batterybankN,andafullcapacitycharger.APPLICABILITY:
MODES1,2and3.ACTIONWiththeTrainNbatterysysteminoperable, declaretheturbinedrivenAuxiliary Feedwater Pumpinoperable andfollowtheACTIONstatement ofSpecification 3.7.1.2.SURVEILLANCE REUIREMENTS 4.8.2.5.1 4.8.2.5.2 TheD.C.bustrainNshallbedetermined OPERABLEandenergized atleastonceper7daysbyverifying correctbreakeralignment andindicated poweravailability.
The250-voltbatterybankandchargershallbedemonstrated OPERABLE:
Atleastonceper7daysbyverifying that:Theelectrolyte levelofeachpilotcellisbetweentheminimumandmaximumlevelindication marks,Thepilotcellspecificgravity,corrected to77'Fandfullelectrolyte level(fluidatbottomofthemaximumlevelindication mark),isgreaterthanorequalto1.200,3.4,Thepilotcellvoltageisgreaterthanorequalto2.13volts,andTheoverallbatteryvoltageisgreaterthanorequalto250volts.Atleastonceper92daysbyverifying that:Thevoltageofeachconnected cellisgreaterthanorequalto2.13voltsunderfioatcharge.Thespecificgravity,corrected to77'Fandfullelectrolyte level(fluidatthebottomofthemaximumlevelindication mark),ofeachconnected cellisgreaterthanorequalto1.200andhasnotdecreased morethan0.03fromthevalueobservedduringtheprevioustest,andTheelectrolyte levelofeachconnected cellisbetweenthetopoftheminimumlevelindication markandthebottomofthemaximumlevelindication mark.COOKNUCLEARPLANT-UNIT 2Page3/48-16AMENDMENT 448
3/4.0LIMITINGCONDITION FOROPERATION ANDSURVEILLANCE REQUIREMENTS 3/4.8ELECTRICAL POWERSYSTEMSSRVEILLANCE REIREMENTSCntinuedC.Atleastonceper18monthsbyverifying that:1.Thecells,cellplatesandbatteryracksshownovisualindication ofphysicaldamageorabnormaldeterioration.
Thecell-towell andterminalconnections areclean,tight,freeofcorrosion andcoatedwithanti-corrosion material.
3.Thebatterychargerwillsupplyatleast10amperesatgreaterthanorequalto250voltsforatleast4hours.Atleastonceper18monthsperformabatteryservicetest,duringshutdown(MODES5or6),byverifying thatthebatterycapacityisadequatetosupplyandmaintaininOPERABLEstatustheactualorsimulated emergency loadsforthetimesspecified ofTable4.8-3withthebatterychargerdisconnected.
Thebatteryterminalvoltageshallbemaintained greaterthanorequalto210voltsthroughout thebatteryservicetest.e.Atleastonceper60months,conductaperformance testofbatterycapacityduringshutdown(MODES5or6),byverifying thatthebatterycapacityisatleast80%ofthemanufacturer's rating.Whenthistestisperformed inplaceofabatteryservicetest,amodifiedperformance testshallbeconducted.
Annualperformance testsofbatterycapacityshallbegiventoanybatterythat'shows signsofdegradation orhasreached85%oftheservicelifeexpectedfortheapplication.
Degradation isindicated whenthebatterycapacitydropsmorethan10%fromitscapacityonthepreviousperformance test,orisbelow90%ofthemanufacturer's rating.Ifthebatteryhasreached85%ofservicelife,deliversacapacityof100%orgreaterofthemanufacturer's ratedcapacity, andhasshownnosignsofdegradation, performance testingattwoyearintervals isacceptable untilthebatteryshowssignsofdegradation.
COOKNUCLEARPLANT-UNIT 2Page3/48-17AMENDMENT 4R,439 3/4.0LIMITINGCONDITION FOROPERATION ANDSURVEILLANCE REQUIREMENTS 3/4.8ELECTRICAL POWERSYSTEMST~ABLE4BATTERYEMERENYLOADS"N"BatteadAuxiliary feedwater turbinecontrolbusFMO-211valveFMO-221valveFMO-231valveFMO-241valveTDTVvalveinimumTime4hours4hours4hours4hours4hours4hoursCOOKNUCLEARPLANT-UNIT 2Page3/48-18AMENDMENT 443 3/4.0LIMITINGCONDITION FOROPERATION ANDSURVEILLANCE REQUIREMENTS 3/4.8ELECTRICAL POWERSYSTEMS/4.1ernaivePwSuLIMITINNDITINFORPERATION3.8.3.1Thesteadystatebusvoltageforthemanualalternate reservesourceshallbegreaterthanorequalto90%ofthenominalbusvoltage.~*":"'""'l""'0'uses.
Withbusvoltagelessthan90%nominal,adjustloadontheremaining busestomaintainsteadystatebusvoltagegreaterthanorequalto90%limit.RVEILLNEREEMENT4.8.3.1Noadditional surveillance requirements otherthanthoserequiredbySpecifications 4.8.1.1.1 and4.8.1.2.SharedwithCookNuclearPlantUnitI.COOKNUCLEARPLANT-UNIT 2Page3/48-19
3/4BASES3/4.8ELECTRICAL POWERSYSTEMSTheOPERABILITY oftheA.C.andD.Cpowersourcesandassociated distribution systemsduringoperation ensuresthatsufficient powerwillbeavailable tosupplythesafetyrelatedequipment requiredfor1)thesafeshutdownofthefacilityand2)themitigation andcontrolofaccidentconditions withinthefacility.
Theminimumspecified independent andredundant A.C.andD.C.powersourcesanddistribution systemssatisfytherequirements ofGeneralDesignCriteria17ofAppendix"A"to10CFR50.TheACTIONrequirements specified forthelevelsofdegradation ofthepowersourcesproviderestriction uponcontinued facilityoperation commensurate withthelevelofdegradation.
TheOPERABILITY ofthepowersourcesareconsistent withtheinitialcondition assumptions oftheaccidentanalysesandarebaseduponmaintaining atleastoneofeachoftheonsiteA.C.andD.C.powersourcesandassociated distribution systemsOPERABLEduringaccidentconditions coincident withanassumedlossofoffsitepowerandsinglefailureoftheotheronsiteA.C.source.TheOPERABILITY oftheminimumspecified A.C.andD.C.powersourcesandassociated distribution systemsduringshutdownandrefueling ensuresthat1)thefacilitycanbemaintained intheshutdownorrefueling condition forextendedtimeperiodsand2)sufficient instrumentation andcontrolcapability isavailable formonitoring andmaintaining thefacilitystatus.TheABandCDstationbatterysystemsprovideareliablesourceofcontinuous powerforsupplyandcontrolofplantloadssuchasswitchgear andannunciator controlcircuits, staticinverters, valvecontrolcenters,emergency lightingandmotorcontrolcenters.Thedesigndutycyclesofthesebatteries arecomposite loadprofilesresulting fromthecombination ofthethreehourLossOfCoolantAccident/Loss OfOffsitePowerbatteryloadprofilesandthefourhourStationBlackoutbatteryloadprofiles.
ThetrainNstationbatterysystemprovidesanindependent 250voltDCpowersupplyforpowerandcontroloftheturbinedrivenauxiliary feedwater pumptrain.Thelimitingconditions ofoperation forthetrainNbatteryareconsistent withtherequirements oftheauxiliary feedwater system.Thesurveillance requirements forthetrainNbatterysystemareconsistent withtherequirements oftheABandCDstationbatteries.
ThetrainNbatteryloadsarederivedfromequipment intheturbinedrivenauxiliary feedwater pumptrainandbatterysizingisconsistent withthefunctional requirements ofthesecomponents.
Simulated loadsforbatterytestsareloadsequivalent tomeasuredactualloads.COOKNUCLEARPLANT-UNIT 2PageB3/48-1AMENDMENT
&
3/4BASES3/4.8ELECTRICAL POWERSYSTEMS.Removalofaccumulated waterasrequiredby4.8.1.1.2.b.2 isperformed bydrawingthecontentsoffthebottomofthetankuntilacceptable resultsareobtainedforeitheratapetestorawaterandsedimenttest.Anacceptable resultforthewaterandsedimentcontentisameasuredvaluelessthan0.05percentvolume.Thesamplespecified in4.8.1.1.2.c.4 issentoffsitefortesting.Aseriousattemptwillbemadetomeetthe31-daylimitontheoffsitetests;however,ifforsomereasonthislimitisnotmet(e.g.,ifthesampleislostorbrokenoriftheresultsarenotreceivedin31days),thedieselgenerators shouldnotbeconsidered inoperable.
Ifthesampleislost,broken,orfailstheoffsitetestsandthenewoilhasalreadybeenputintothestoragetank,theoffsitetestswillbeperformed onasampletakenfromthestoragetank.Iftheresultsonthesubsequent'torage tanksamplearenotwithinspecified limits,thedieselgenerators shouldbeconsidered OPERABLEandtheout-of-spec properties shouldbereturnedtowithinspecification assoonaspossible.
Ifthemonthlystoragetanksampletakeninaccordance withSpecification 4.8.1.1.2.d failstheparticulate contamination test,thedieselgenerators shouldbeconsidered OPERABLEandthecontamination levelshouldberestoredtobelow10mg/literassoonaspossible.
Theprecision leak-detection testdescribed inSurveillance Requirement 4.8.1.1.2.f.2 shouldbeperformed asdescribed inNFPA(National FireProtection Association)
-329.AsNFPA-329isrevised,theprecision leak-detection testmaybemodifiedtoincorporate changestothetestasdescribed intherevisions toNFPA-329.
Theminimumrequireddieselfueloilvolumeis43,240gallons.Thisvolumeisconsistent withoperation, ofonedieselgenerator continuously for7daysatratedload,asrecommended inRegulatory Guide1.137,entitled"FuelOilSysteinforStandbyDieselGenerators."
TheTechnical'Specifications requireaminimumof46,000gallonsoffuel.The46,000gallonsisanindicated volume.Thisamountincludesmarginforcharacteristics suchaslocationofthetankdischarge pipesandslopeofthetanks.COOKNUCLEARPLANT-UNIT 2PageB3/48-2AMENDMENT 448,132