d % UNITED STATES i
c y . j ij NUCLE AR REGULATORY COMMISSION W A$mNO TON. D. C. 20655 s . . .... .f .
SAFETY EVALUATION REPORT BY THE OFFICE OF SPECIAL PRORCTS EMPLOYEE CONCERN EttMENT REPORT CO 10107 I "BACKFILL WITH 1632"
+
TENhESSEE VALLEY AUTHORITY SEQUOYAk NUCLEAR F0WER PLANT UNITS 1 & 2 DOCKET NOS. 50-327 AND 50-328 i
!. Subfect ;
l i
! Categcry: Construction (20000) i
' Subcategory: Soils (10100) i Elerent: Eacktill with 1032 (C0 10107) ;
The basis for Element Report C010107-SQN (Rev. 2) dated 10-15-86 is Sequoyah l Employee Co.mcern JAN 56-CC2 which states:
' r
- Excavation for DAW building foundation revealed red elay, various size rocks, etc. that were usea as a backfill material for the storage yard. ,
if building founcation is constructed without removing backfilled [
material, an uneven settlement of building could occur." j II. Sumery of Issue ;
Tha Sequoyah (SON) Lry Active Waste (DAW) building was being constructed on \
J unsuitable backfill r:aterial that could result in uneven settlement. l r
(
i 4 111. Evaluation ;
1 TVA said that the decision was made that to remove the existing material and [
j
]
backfill with 1032-crushtd stone prior to building the foundation. This work [
j was perforced by TVA ano as the building was classified as non-QA, the mater- [
s ial was randomly inspected by engir.eers, not QC inspectors. The concerned j l individual was contacted by TVA, and the evaluation report indicates that he was satisfied with the corrective actions taken, i 1 j
!Y. Conclusien I FSAk Secticn 3.2, "Seismic Classification of Strur.tures, Systens and Compo-
) i nents," incicates that the building is not classified as a Seismic Category I i structure. The building is catecerized as non-seismic ano does not recuire l j
r t.c le a r g r a :e c u e l l t,, c.s:uram s (rer.(A). Becaust of the classificaticn of tne builc;q. tr.s stai: :.oncl.. C tra? trere is no need to assess the .