i SAFETY EVALUATION REPORT BY THE OFFICE OF SPECIAL PROJECTS EMPLOYEE CONCERN ELEMENT REPORT OP 30204, "GROUND DETECTOR P10BLEM" TENNESSEE VALLEY AUTHORITY l

SEQUOYAH NUCLEAR POWER PLANT UNITS 1 & 2 1

DOCKET NOS. 50-327 AND 50-328 4

1 1.

Ebfect Category:

Oner4tions (30000) i Subca tegory:

Cable and Contuit (30200)

Elerent:

GroundbetectorProblem(30204) i 1

The basis for Element Report 302.0? - SQN, Rev. I datec September 30,1986, is the following erployee concern SQN-86-013-001 which states.

p t

"Changing out the Sy!vania bulas in various group detector causes t.

resistance change which shows a ground between all three phases on the boarc when the test button is pushed. This false ground signal l

i otershadows an actual ground on the board, since the bulb lights up trighter than the other bulbs indicating a ground although an actal j

ground cay be on one of the other phases."

y II. Summary of Issue 1

i Ccncern 50M-60-013-001 references the potential of replacement bulbs in i

t various grcuna fault detectors giving false indications.

III. Eva'uation

[

The evaluator conducted interviews with various singineering, raintenance, and cperations personnel and rev ewed schematic ciagrims of the grouno detection

(

i circuits.

The concern was substantiated that both partial and full false i

grounc fault indicetions on the ground detectors have vccurred in the past.

l TVA has committee to have plastic tags placed near the ground detector bulbs en the unit anc shutdown beards stating "Replace Grcund lights as a set of tnree SYL 1%0V Bulbs Cnly" and "Verify all Greund Lights good prior to

{

m rcorr; 'ur gr:sta cr E" b,

f r

SS11220309 SS11C)4 L

PDR ADOCK 05000327 I

p PDC

(

a

.g.

IV. Conclusion The fiRC staff believes that the TVA investigation of the concern was adequate, and their resolutien of the cor.cern as described in Element Report OP 30?O4 is acceptable for rcstart.