ML20206G529

From kanterella
Jump to navigation Jump to search
SER Supporting Employee Concern Element Rept OP 301112, Sys 31 Not Operated Properly
ML20206G529
Person / Time
Site: Sequoyah  
Issue date: 11/04/1988
From:
NRC OFFICE OF SPECIAL PROJECTS
To:
Shared Package
ML20206G037 List: ... further results
References
NUDOCS 8811220307
Download: ML20206G529 (1)


Text

'%

'1 n ar,

[o

'c, UNITFD STATES NUCLEAR REGULATORY COMMISSION i s*

. [+' ?i w Asm NcTON. D. C. 20S$5

!(-%/l SAFETY EVALVAT10N REPORT BY ThE OFFICE OF SPECIAL PROJECTS D6LOYTE CONCERf1 ELEMENT REPORT OP 30112, "SYSTEM 31 NOT OPERATED PROPERLY" TENNESSEE VALLEY AUTHORITY SEQUDYAH NUCLEAR POWER PLANT UNITS 1 & 1 00fKETNOS.50-3E7AND50-328 1.

Subject Category: Operation (30000)

Subcategery. Machanical Equipment ReliabilityiDesign (30100)

Element: System 31 Not Cperated Properly (30112)

The Basis for Element Report 3U112-SON, Rev.1, dated October 14, 1986 is l

Watt:, bar employee concern IN-86-064-001-Four (4) air flow switches on the

~

4 5. ; 5 board room air handlers do not function Aux. Bldg., Units 1 & 2, El:-9.

.,2" & 786'.

These switches have been removed and recalibrated and results have alv.ays been within acceptabls tolerance; however, they remain inoperatie.

(Name/cetails known to QTC and release of this information would jeopercize CI's confidentiality.) CI has no further information. Nuclear Power Concern.

11.

Suu. cry of Issue Inoperability of fluid Cor.ponents Inc. (FCI) flow switches on 480 volt board room air handling units (AHUs) with slow response probes.

111. Evaluation i

TVA interviewed the engineers in instrurent maintenance for systems 30 and 31 (ventilation ano air conditiening). The engineers seid that Dryer diaphram type flow switches are used cr the 480 volt board room AhUs and in most 4

applications at Sequoyah.

An ECIS listing of the FCI slow probes indicated that the proces are used on the emergency gas treattuent system (EGTS) and EGTS room coolerf.. A review of mair,tenance requests written on these instruments i

did not indicate probleu similar to Watts 0&r's.

IV. Conclusion The NRC statt found the TVA investigation of the concern to be adequate, and the resolution of the encern as cescribed in Eletent Report 30112 is

]

acceptatie for restart, i

8811220307 sgg3g4 hDR ADOCK 0500o327 PDC