ATTACHMENT 2TOAEP:NRC:0896K PROPOSEDREVISEDTECHNICAL SPECIFICATION PAGES9f20400i889ff28PDRADOCK050003f5PDC

>~

34.8ELECTRICAL POWERSYSTEMS34,8,1A.C.SOURCESOPERATING LIMITINGCONDITION FOROPERATION 3.8.1.1Asaminimum,thefollowing A,C.electrical powersourcesshallbeOPERABLE:

a.Twophysically independent circuitsbetweentheoffsitetrans-missionnetworkandtheonsiteClass1Edistribution system,andb.Twoseparateandindependent dieselgenerators, eachwith:1.Aseparatedayfueltankcontaining aminimumof70gallonsoffuel,2.Aseparatefuelstoragesystemscontaining aminimumindicated volumeof46,000gallonsoffuel,and3.Aseparatefueltransferpump.APPLICABILITY:

MODES1,2,3and4.ACTION:a.WithanoffsitecircuitoftheaboverequiredA.C.electrical powersourcesinoperable, demonstrate theOPERABILITY oftheremaining A.C.offsitesourcebyperforming Surveillance Requirement 4.8.1.1.1.a within1hourandatleastonceper8hoursthereafter; andSurveillance Requirement 4.8.1.1.2.a.4 within24hours;restoreatleasttwooffsitecircuitsandtwodieselgenerators toOPERABLEstatuswithin72hoursorbeinatleastHOTSTANDBYwithinthenext6hoursandinCOLDSHUTDOWNwithinthefollowing 30hours.b.Withadieselgenerator oftheaboverequiredA.CDelectrical powersourcesinoperable, demonstrate theOPERABILITY oftheA.C.offsitesourcesbyperforming Surveillance Requirement 4.8.1.1.1.a within1hourandatleastonceper8hoursthereafter; andifthedieselgenerator becameinoperable

'duetoanycauseotherthanpreplanned preventive maintenance ortesting,demonstrate theOPERABILITY oftheremaining OPERABLEdieselgenerator byperforming Surveillance Requirement 4.8,1,1.2.a.4 within24hours;restoredieselgenerators toOPERABLEstatuswithin72hoursorbeinatleastHOTSTANDBYwithinthenext6hoursandinCOLDSHUTDOWNwithinthefollowing 30hours.Atthenumberoffailuresfortheinoperable dieselindicated inTable4.8-1performtheAdditional Reliability Actionsprescribed inTable4.8-1.+TanksareseparatebetweendieselsbutsharedbetweenUnits1and2.COOKNUCLEARPLANT-UNIT13/48-1AMENDMENT NO,

~~

ELECTRICAL POWERSYSTEMSSHUTDOWNLIMITINGCONDITION FOROPERATION 3.8.1.2Asaminimum,thefollowing A.C.electrical powersourcesshallbeOPERABLE:

a.Onecircuitbetweentheoffsitetransmission networkandtheonsiteClass1Edistribution system,andb.Onedieselgenerator with:1.Adayfueltankcontaining aminimumof70gallonsoffuel,2.Afuelstoragesystemcontaining aminimumindicated volumeof46,000gallonsoffuel,and3.Afueltransferpump.APPLICABILITY:

MODES5and6.ACTION:WithlessthantheaboveminimumrequiredA.C.electrical power'ources

OPERABLE, suspendalloperations involving COREALTERATIONS positivereactivity changes*untiltheminimumrequiredA.C.electrical powersourcesarerestoredtoOPERABLEstatus.SURVEILLANCE REUIREMENTS 4.8.1.2TheaboverequiredA.C.electrical powersourcesshallbedemonstrated OPERABLEbytheperformance ofeachoftheSurveillance Requirements of4'.1.1.1and4.8.1.1.2 exceptforrequirement 4.8.1.1.2.a.5.
  • Forpurposesofthisspecification, additionofwaterfromtheRWSTdoesnotconstitute apositivereactivity additionprovidedtheboronconcentration intheRWSTisgreaterthantheminimumrequiredbySpecification 3.1.2.7.b.2.

COOKNUCLEARPLANT-UNIT13/48-9AMENDMENT NO.

s ELECTRICAL POWERSYSTEMSContinued BASESRemovalofaccumulated waterasrequiredby4.8.1.1.2.b,2 isperformed bydrawingthecontentsoffthebottomofthetankuntilacceptable resultsareobtainedforeitheratapetestorawaterandsedimenttest.Anacceptable resultforthewaterandsedimentcontentisa'easured valuelessthan0.05percentvolume.Thesamplespecified in4.8.1.1.2.c.4 issentoffsitefortesting.Aseriousattemptwillbemadetomeetthe31-daylimitontheoffsitetests;however,ifforsomereasonthislimitisnotmet(e.g.,ifthesampleislostorbrokenoriftheresultsarenotreceivedin31days),thedieselgenerators shouldnotbeconsidered inoperable.

Ifthesmapleislost,broken,orfailstheoffsitetestsandthenewoilhasalreadybeenputintothestoragetank,theoffsitetestswillbeperformed onasampletakenfromthestoragetank.Iftheresultsonthesubsequent storagetanksamplearenotwithinspecified limits,thedieselgenerators shouldbeconsidered OPERABLEandtheout-of-spec properties shouldbereturnedtowithinspecification assoonaspossible.

Ifthemonthlystoragetanksampletakeninaccordance withSpecification 4.8.1.1.2.d failstheparticulate contamination test,thedieselgenerators shouldbeconsidered OPERABLEandthecontamination levelshouldberestoredtobelow10mg/literassoonaspossible.

Theprecision leak-detection testdescribed inSurveillance Requirement 4.8.1,1.2.f.2 shouldbeperformed asdescribed inNFPA(National FireProtection Association)

-329.AsNFPA-329isrevised,theprecision leak-detection testmaybemodifiedtoincorporate changestothetestasdescribed intherevisions toNFPA-329.

Theminimumrequireddieselfueloilvolumeis43,240gallons.Thisvolumeisconsistent withoperation ofonedieselgenerator continuously for7daysatratedload,asrecommended inRegulatory Guide1.137,entitled"FuelOilSystemforStandbyDieselGenerators."

TheTechnical Specifications requireaminimumof46,000gallonsoffuel.The46,000gallonsisanindicated volume,Thisamountincludesmarginforcharacteristics suchaslocationofthetankdischarge pipesandslopeofthetanks.COOKNUCLEARPLANT-UNIT1B3/48-2AMENDMENT NO.

34'ELECTRICAL POWERSYSTEMS34.8.1A.C.SOURCESOPERATING LIMITINGCONDITION FOROPERATION 3.8.1.1Asaminimum,thefollowing A.C.electrical powersourcesshallbeOPERABLE:

a.Twophysically independent circuitsbetweentheoffsitetrans-missionnetworkandtheonsiteClass1Edistribution system,andb.Twoseparateandindependent dieselgenerators, eachwith:Aseparatedayfueltankcontaining aminimumof70gallonsoffuel,2.Aseparatefuelstoragesystem+containing aminimumindicated volumeof46,000gallonsoffuel,and3.Aseparatefueltransferpump.APPLICABILITY:

MODES1,2,3and4.ACTION:a.b.WithanoffsitecircuitoftheaboverequiredA.C.electrical powersourcesinoperable, demonstrate theOPERABILITY oftheremaining A.C.offsitesourcebyperforming, Surveillance Requirement 4.8.1,1.1.a within1hourandatleastonceper8hoursthereafter; andSurveillance Requirement 4.8.1.1.2,a.4 within24hours;restoreatleasttwooffsitecircuitsandtwodieselgenerators toOPERABLEstatuswithin72hoursorbeinatleastHOTSTANDBYwithinthenext6hoursandinCOLDSHUTDOWNwithinthefollowing 30hours.IWithadieselgenerator oftheaboverequiredA.C.electrical powersourcesinoperable, demonstrate theOPERABILITY oftheA.C.offsitesourcesbyperforming Surveillance Requirement 4.8.1.1.1.a within1hourandatleastonceper8hoursthereafter; andifthedieselgenerator becameinoperable duetoanycauseotherthanpreplanned preventive maintenance oxtesting,demonstrate theOPERABILITY oftheremaining OPERABLEdieselgenerator byperforming Surveillance Requirement 4.8.1.1.2.a.4 within24hours;restoredieselgenerators toOPERABLEstatuswithin72hoursorbeinatleastHOTSTANDBYwithinthenext6hoursandinCOLDSHUTDOWNwithinthefollowing 30hours.Atthenumberoffailuresfortheinoperable dieselindicated inTable4.8-1performtheAdditional Reliability Actionsprescribed inTable4.8-1.*TanksareseparatebetweendieselsbutsharedbetweenUnits1and2.COOKNUCLEARPLANT-UNIT23/48-1AMENDMENT NO~

ELECTRICAL POWERSYSTEMSSHUTDOWNLIMITINGCONDITION FOROPERATION 3.8.1.2Asaminimum,thefollowing A.C.electrical powersourcesshallbeOPERABLE:

'.Onecircuitbetweentheoffsitetransmission networkandtheonsiteClass1Edistribution system,andb.Onedieselgenerator with:1.Adayfueltankcontaining aminimumof70gallonsoffuel,2.Afuelstoragesystemcontaining aminimumindicated volumeof46,000gallonsoffuel,and3.Afueltransferpump.APPLICABILITY:

MODES5and6.ACTION:WithlessthantheaboveminimumrequiredA,C,electrical powersourcesOPERABLE, suspendalloperations involving COREALTERATIONS orpositivereactivity changes*untiltheminimumrequiredA.C.electrical powersourcesarerestoredtoOPERABLEstatus.SURVEILLANCE REUIREMENTS 4.8.1,2TheaboverequiredA.C.electrical powersourcesshallbedemonstrated OPERABLEbytheperformance ofeachoftheSurveillance Requirements of4.8.1.1.1 and4.8.1.1.2 exceptforrequirement 4.8.1.1.2,a,5.

  • Forpurposesofthisspecification, additionofwaterfromtheRWSTdoesnotconstitute apositivereactivity additionprovidedtheboronconcentration intheRWSTisgreaterthantheminimumrequiredbySpecification 3.1.2.7.b.2.

COOKNUCLEARPLANT-UNIT23/48-9AMENDMENT NO.

ELECTRICAL POWERSYSTEMSContinued BASESRemovalofaccumulated waterasrequiredby4.8.1,1.2.b.2 isperformed bydrawingthecontentsoffthebottomofthetankuntilacceptable resultsareobtainedforeitheratapetestorawaterandsedimenttest.Anacceptable resultforthewaterandsedimentcontentisameasuredvaluelessthan0.05percentvolume.Thesamplespecified in4.8.1.1.2.c.4 issentoffsitefortesting.Aseriousattemptwillbemadetomeetthe31-daylimitontheoffsitetests;however,ifforsomereasonthislimitisnotmet(e.g.,ifthesampleislostorbrokenoriftheresultsarenotreceivedin31days),thedieselgenerators shouldnotbeconsidered inoperable.

Ifthesmapleislost,broken,orfailstheoffsitetestsandthenewoilhasalreadybeenputintothestoragetank,theoffsitetestswillbeperformed onasampletakenfromthestoragetank.Iftheresultsonthesubsequent storage'ank samplearenotwithinspecified limits,thedieselgenerators shouldbeconsidered OPERABLEandtheout-of-spec properties shouldbereturnedtowithinspecification assoonaspossible.

Ifthemonthlystoragetanksampletakeninaccordance withSpecification 4.8.1.1.2.d failstheparticulate contamination test,thedieselgenerators shouldbeconsidered OPERABLEandthecontamination levelshouldberestoredtobelow10mg/literassoonaspossible.

Theprecision leak-detection testdescribed inSurveillance Requirement 4.8.1,1.2.f.2 shouldbeperformed asdescribed inNFPA(National FireProtection Association)

-329.AsNFPA-329isrevised,theprecision leak-detection testmaybemodifiedtoincorporate changestothetestasdescribed intherevisions toNFPA-329.

Theminimumrequireddieselfueloilvolumeis43,240gallons.Thisvolumeisconsistent withoperation ofonedieselgenerator continuously for7daysatratedload,asrecommended inRegulatory Guide1.137,entitled"FuelOilSystemforStandbyDieselGenerators."

TheTechnical Specifications requireaminimumof46,000gallonsoffuel.The46,000gallonsisanindicated volume.Thisamountincludesmarginforcharacteristics suchaslocationofthetankdischarge pipesandslopeofthetanks.COOKNUCLEARPLANT-UNIT2B3/48-2AMENDMENT NO.

Nhr,(~h