ML071210185: Difference between revisions

From kanterella
Jump to navigation Jump to search
(Created page by program invented by StriderTol)
(Created page by program invented by StriderTol)
Line 2: Line 2:
| number = ML071210185
| number = ML071210185
| issue date = 04/26/2007
| issue date = 04/26/2007
| title = Kewaunee - Supplement to License Amendment Request 230, Emergency Diesel Generator Short-Time Load Testing.
| title = Supplement to License Amendment Request 230, Emergency Diesel Generator Short-Time Load Testing.
| author name = Bischof G T
| author name = Bischof G
| author affiliation = Dominion, Dominion Energy Kewaunee, Inc
| author affiliation = Dominion, Dominion Energy Kewaunee, Inc
| addressee name =  
| addressee name =  
Line 20: Line 20:
{{#Wiki_filter:Dominion Energy Kewaunee, Inc. F0; D o mi nion5000 Dominion Boulevard, Glen Allen, VA 23060 April 26, 2007 U. S. Nuclear Regulatory Commission Serial No. 07-00080 Attention:
{{#Wiki_filter:Dominion Energy Kewaunee, Inc. F0; D o mi nion5000 Dominion Boulevard, Glen Allen, VA 23060 April 26, 2007 U. S. Nuclear Regulatory Commission Serial No. 07-00080 Attention:
Document Control Desk KPS/LIC/GOR:
Document Control Desk KPS/LIC/GOR:
RO Washington, DC 20555 Docket No. 50-305 License No. DPR-43 DOMINION ENERGY KEWAUNEE, INC.KEWAUNEE POWER STATION SUPPLEMENT TO LICENSE AMENDMENT REQUEST 230. "EMERGENCY DIESEL GENERATOR SHORT-TIME LOAD TESTING" Pursuant to 10 CFR 50.90, Dominion Energy Kewaunee, Inc. (DEK) submitted a request for approval of a proposed amendment to the Kewaunee Power Station (KPS)Technical Specifications (TS) (reference 1). The proposed amendment would modify KPS Technical Specification 4.6.a.5 to permit performance of the emergency diesel generator (EDG) short-time load test at a reduced load. Subsequently, the Nuclear Regulatory Commission (NRC) transmitted a request for additional information (RAI)regarding the proposed amendment (reference  
RO Washington, DC 20555 Docket No. 50-305 License No. DPR-43 DOMINION ENERGY KEWAUNEE, INC.KEWAUNEE POWER STATION SUPPLEMENT TO LICENSE AMENDMENT REQUEST 230. "EMERGENCY DIESEL GENERATOR SHORT-TIME LOAD TESTING" Pursuant to 10 CFR 50.90, Dominion Energy Kewaunee, Inc. (DEK) submitted a request for approval of a proposed amendment to the Kewaunee Power Station (KPS)Technical Specifications (TS) (reference 1). The proposed amendment would modify KPS Technical Specification 4.6.a.5 to permit performance of the emergency diesel generator (EDG) short-time load test at a reduced load. Subsequently, the Nuclear Regulatory Commission (NRC) transmitted a request for additional information (RAI)regarding the proposed amendment (reference
: 2) which DEK responded to (reference 3).Based on DEK's response to the NRC RAIs, a teleconference was held on April 25, 2007, between the NRC staff and DEK staff concerning the power factor value listed in the proposed TS. During this teleconference, DEK committed to change the power factor value contained in the proposed TS to bound the calculated power factors listed in KPS "Calculation C-042-001, Revision 6, Addendum C, "Safeguards Diesel Generator Loading" (attachment 2 of reference 3).Attachment 1 contains the revised marked-up TS pages changing the specified power factor from < 0.9 to < 0.89. Attachment 2 contains the proposed revision to the affected TS pages.This proposed change to the amendment request does not change the conclusions of the no significant hazards determination in reference 1.If you have any questions or require additional information, please contact Mr. Craig Sly at (804) 273-2784.
: 2) which DEK responded to (reference 3).Based on DEK's response to the NRC RAIs, a teleconference was held on April 25, 2007, between the NRC staff and DEK staff concerning the power factor value listed in the proposed TS. During this teleconference, DEK committed to change the power factor value contained in the proposed TS to bound the calculated power factors listed in KPS "Calculation C-042-001, Revision 6, Addendum C, "Safeguards Diesel Generator Loading" (attachment 2 of reference 3).Attachment 1 contains the revised marked-up TS pages changing the specified power factor from < 0.9 to < 0.89. Attachment 2 contains the proposed revision to the affected TS pages.This proposed change to the amendment request does not change the conclusions of the no significant hazards determination in reference 1.If you have any questions or require additional information, please contact Mr. Craig Sly at (804) 273-2784.
A complete copy of this submittal has been transmitted to the State of Wisconsin as required by 10 CFR 50.91 (b)(1).Very truly yours, Gerald T. Bishof Vice President  
A complete copy of this submittal has been transmitted to the State of Wisconsin as required by 10 CFR 50.91 (b)(1).Very truly yours, Gerald T. Bishof Vice President  
Line 35: Line 35:
Serial No. 07-0008C LAR 230 Supplemental Response Page 3 of 4 cc: Regional Administrator, Region III U.S. Nuclear Regulatory Commission 2443 Warrenville Road Suite 210 Lisle, IL 60532-4352 Ms. M. H. Chernoff U.S. Nuclear Regulatory Commission Mail Stop O-8-G9A Washington, D. C. 20555 Mr. S. C. Burton NRC Senior Resident Inspector Kewaunee Power Station Public Service Commission of Wisconsin Electric Division P. 0. Box 7854 Madison, WI 53707 Serial No. 07-0008C LAR 230 Supplemental Response Page 4 of 4 COMMONWEALTH OF VIRGINIA )))COUNTY OF HENRICO The foregoing document was acknowledged before me, in and for the County and Commonwealth aforesaid, today by Gerald T. Bischof, who is Vice President  
Serial No. 07-0008C LAR 230 Supplemental Response Page 3 of 4 cc: Regional Administrator, Region III U.S. Nuclear Regulatory Commission 2443 Warrenville Road Suite 210 Lisle, IL 60532-4352 Ms. M. H. Chernoff U.S. Nuclear Regulatory Commission Mail Stop O-8-G9A Washington, D. C. 20555 Mr. S. C. Burton NRC Senior Resident Inspector Kewaunee Power Station Public Service Commission of Wisconsin Electric Division P. 0. Box 7854 Madison, WI 53707 Serial No. 07-0008C LAR 230 Supplemental Response Page 4 of 4 COMMONWEALTH OF VIRGINIA )))COUNTY OF HENRICO The foregoing document was acknowledged before me, in and for the County and Commonwealth aforesaid, today by Gerald T. Bischof, who is Vice President  
-Nuclear Engineering of Dominion Energy Kewaunee, Inc. He has affirmed before me that he is duly authorized to execute and file the foregoing document in behalf of that Company, and that the statements in the document are true to the best of his knowledge and belief.Acknowledged before me this c?4 (a" day of&4~Ajl~y ,2007.My Commission Expires: b.6A Noay~~blic (SEAL)
-Nuclear Engineering of Dominion Energy Kewaunee, Inc. He has affirmed before me that he is duly authorized to execute and file the foregoing document in behalf of that Company, and that the statements in the document are true to the best of his knowledge and belief.Acknowledged before me this c?4 (a" day of&4~Ajl~y ,2007.My Commission Expires: b.6A Noay~~blic (SEAL)
Serial No. 07-0008C ATTACHMENT 1 SUPPLEMENT TO KEWAUNEE LICENSE AMENDMENT REQUEST 230 EMERGENCY DIESEL GENERATOR SHORT-TIME LOAD TESTING MARKED-UP TS PAGES TS 4.6-1 TS 4.6-2 KEWAUNEE POWER STATION DOMINION ENERGY KEWAUNEE, INC.  
Serial No. 07-0008C ATTACHMENT 1 SUPPLEMENT TO KEWAUNEE LICENSE AMENDMENT REQUEST 230 EMERGENCY DIESEL GENERATOR SHORT-TIME LOAD TESTING MARKED-UP TS PAGES TS 4.6-1 TS 4.6-2 KEWAUNEE POWER STATION DOMINION ENERGY KEWAUNEE, INC.
 
4.6 PERIODIC TESTING OF EMERGENCY POWER SYSTEM AI:PLICABILITY Applies to periodic testing and surveillance requirements of the emergency power system.01J.ECI.VE To verify that the emergency power sources and equipment are OPERABLE.SPECIFICATION The following tests and surveillance shall be performed:
===4.6 PERIODIC===
TESTING OF EMERGENCY POWER SYSTEM AI:PLICABILITY Applies to periodic testing and surveillance requirements of the emergency power system.01J.ECI.VE To verify that the emergency power sources and equipment are OPERABLE.SPECIFICATION The following tests and surveillance shall be performed:
: a. Diesel Generators
: a. Diesel Generators
: 1. Manually-initiated start of each diesel generator, and assumption of load by the diesel generator.
: 1. Manually-initiated start of each diesel generator, and assumption of load by the diesel generator.
This test shall be conducted monthly, loading the diesel generator to at least 2600 KW (nominal) for a period of at least 1 hour.2. Automatic start of each diesel generator, load shedding, and restoration to operation of particular vital equipment, all initiated by a simulated loss of all normal a-c station service power supplies together with a simulated safety injection signal.This test will be conducted at each REFUELING interval to assure that each diesel generator will start and assume required loads to the extent possible within 1 minute, and operate for > 5 minutes while loaded with the emergency loads.3. Each diesel generator shall be inspected at each major REFUELING outage.4. Diesel generator load rejection test in accordance with IEEE 387-1977, Section 6.4.5, shall be performed at least once per 18 months.LAR 230 TS 4.6-1  
This test shall be conducted monthly, loading the diesel generator to at least 2600 KW (nominal) for a period of at least 1 hour.2. Automatic start of each diesel generator, load shedding, and restoration to operation of particular vital equipment, all initiated by a simulated loss of all normal a-c station service power supplies together with a simulated safety injection signal.This test will be conducted at each REFUELING interval to assure that each diesel generator will start and assume required loads to the extent possible within 1 minute, and operate for > 5 minutes while loaded with the emergency loads.3. Each diesel generator shall be inspected at each major REFUELING outage.4. Diesel generator load rejection test in accordance with IEEE 387-1977, Section 6.4.5, shall be performed at least once per 18 months.LAR 230 TS 4.6-1
: 5. Each diesel generator shall be o edjoeaded at ' pnwg.r fntn, .f g A C) ,tras hoi irs every operating oyrlo: Nota 1 MonmntarV trqn.iant.
: 5. Each diesel generator shall be o edjoeaded at ' pnwg.r fntn, .f g A C) ,tras hoi irs every operating oyrlo: Nota 1 MonmntarV trqn.iant.
ai it.-ida tho In-d qnd ,ipowr factnr rh- not invlida~ta thi.s tapct Note 2 Thi; 5Sijr'aillanrp ghnll not nnrmlly b h-in the O)PFEEATIN(Q or HOT STANI'RYV MOI'F I-inwpvpr this Si grvyillanc, may bh performed to ree-,tnhlicqh C)PFIRARII ITY ,nrnvidd an , s ssment dz.terminaos thn qafoty nf thp plant isq m;intninard nr .nhnnno.d C-rdit may hbe tqkn fnr imnPklannd Pvpnt-, that .qtikfy thi.s .iirvo.ilbnoo Note. 3 If ,pnrfnrmeod with the diop.l ganerator .ynchrnnized with nff.ita ,nwor it .qhnlL.ho prformed at a ponw.r fartor < 0 AQ -inweov.r if grid nonditionnc do nnt ,pormit tho ,ow.r farctor limit i* not regi firmd to hb mpt. I Indlr this rondition the ,onwr factor shgil ho maint.ined ao nlos o tn tho limit a-, ,rgatinrahp_
ai it.-ida tho In-d qnd ,ipowr factnr rh- not invlida~ta thi.s tapct Note 2 Thi; 5Sijr'aillanrp ghnll not nnrmlly b h-in the O)PFEEATIN(Q or HOT STANI'RYV MOI'F I-inwpvpr this Si grvyillanc, may bh performed to ree-,tnhlicqh C)PFIRARII ITY ,nrnvidd an , s ssment dz.terminaos thn qafoty nf thp plant isq m;intninard nr .nhnnno.d C-rdit may hbe tqkn fnr imnPklannd Pvpnt-, that .qtikfy thi.s .iirvo.ilbnoo Note. 3 If ,pnrfnrmeod with the diop.l ganerator .ynchrnnized with nff.ita ,nwor it .qhnlL.ho prformed at a ponw.r fartor < 0 AQ -inweov.r if grid nonditionnc do nnt ,pormit tho ,ow.r farctor limit i* not regi firmd to hb mpt. I Indlr this rondition the ,onwr factor shgil ho maint.ined ao nlos o tn tho limit a-, ,rgatinrahp_
Line 48: Line 46:
the specific gravity and height of electrolyte in every cell and the temperature of every fifth cell.3. All measurements shall be recorded and compared with previous data to detect signs of deterioration.
the specific gravity and height of electrolyte in every cell and the temperature of every fifth cell.3. All measurements shall be recorded and compared with previous data to detect signs of deterioration.
: 4. The batteries shall be subjected to a load test during the first REFUELING and once every 5 years thereafter.
: 4. The batteries shall be subjected to a load test during the first REFUELING and once every 5 years thereafter.
Battery voltage shall be monitored as a function of time to establish that the battery performs as expected during heavy discharge and that all electrical connections are tight.LAR 230 TS 4.6-2 Serial No. 07-0008C ATTACHMENT 2 SUPPLEMENT TO KEWAUNEE LICENSE AMENDMENT REQUEST 230 EMERGENCY DIESEL GENERATOR SHORT-TIME LOAD TESTING AFFECTED TS PAGES TS 4.6-1 TS 4.6-2 KEWAUNEE POWER STATION DOMINION ENERGY KEWAUNEE, INC.  
Battery voltage shall be monitored as a function of time to establish that the battery performs as expected during heavy discharge and that all electrical connections are tight.LAR 230 TS 4.6-2 Serial No. 07-0008C ATTACHMENT 2 SUPPLEMENT TO KEWAUNEE LICENSE AMENDMENT REQUEST 230 EMERGENCY DIESEL GENERATOR SHORT-TIME LOAD TESTING AFFECTED TS PAGES TS 4.6-1 TS 4.6-2 KEWAUNEE POWER STATION DOMINION ENERGY KEWAUNEE, INC.
 
4.6 PERIODIC TESTING OF EMERGENCY POWER SYSTEM APPLICABILITY Applies to periodic testing and surveillance requirements of the emergency power system..JECILVE To verify that the emergency power sources and equipment are OPERABLE.SPECIFICATION The following tests and surveillance shall be performed:
===4.6 PERIODIC===
TESTING OF EMERGENCY POWER SYSTEM APPLICABILITY Applies to periodic testing and surveillance requirements of the emergency power system..JECILVE To verify that the emergency power sources and equipment are OPERABLE.SPECIFICATION The following tests and surveillance shall be performed:
: a. Diesel Generators
: a. Diesel Generators
: 1. Manually-initiated start of each diesel generator, and assumption of load by the diesel generator.
: 1. Manually-initiated start of each diesel generator, and assumption of load by the diesel generator.
This test shall be conducted monthly, loading the diesel generator to at least 2600 KW (nominal) for a period of at least 1 hour.2. Automatic start of each diesel generator, load shedding, and restoration to operation of particular vital equipment, all initiated by a simulated loss of all normal a-c station service power supplies together with a simulated safety injection signal.This test will be conducted at each REFUELING interval to assure that each diesel generator will start and assume required loads to the extent possible within 1 minute, and operate for > 5 minutes while loaded with the emergency loads.3. Each diesel generator shall be inspected at each major REFUELING outage.4. Diesel generator load rejection test in accordance with IEEE 387-1977, Section 6.4.5, shall be performed at least once per 18 months.TS 4.6-1  
This test shall be conducted monthly, loading the diesel generator to at least 2600 KW (nominal) for a period of at least 1 hour.2. Automatic start of each diesel generator, load shedding, and restoration to operation of particular vital equipment, all initiated by a simulated loss of all normal a-c station service power supplies together with a simulated safety injection signal.This test will be conducted at each REFUELING interval to assure that each diesel generator will start and assume required loads to the extent possible within 1 minute, and operate for > 5 minutes while loaded with the emergency loads.3. Each diesel generator shall be inspected at each major REFUELING outage.4. Diesel generator load rejection test in accordance with IEEE 387-1977, Section 6.4.5, shall be performed at least once per 18 months.TS 4.6-1
: 5. Each diesel generator shall be operated for > 24 hours every operating cycle: Note 1 Momentary transients outside the load and power factor ranges do not invalidate this test.Note 2 This Surveillance shall not normally be performed in the OPERATING or HOT STANDBY MODE. However, this Surveillance may be performed to reestablish OPERABILITY provided an assessment determines the safety of the plant is maintained or enhanced.
: 5. Each diesel generator shall be operated for > 24 hours every operating cycle: Note 1 Momentary transients outside the load and power factor ranges do not invalidate this test.Note 2 This Surveillance shall not normally be performed in the OPERATING or HOT STANDBY MODE. However, this Surveillance may be performed to reestablish OPERABILITY provided an assessment determines the safety of the plant is maintained or enhanced.
Credit may be taken for unplanned events that satisfy this surveillance requirement.
Credit may be taken for unplanned events that satisfy this surveillance requirement.

Revision as of 01:23, 13 July 2019

Supplement to License Amendment Request 230, Emergency Diesel Generator Short-Time Load Testing.
ML071210185
Person / Time
Site: Kewaunee Dominion icon.png
Issue date: 04/26/2007
From: Gerald Bichof
Dominion, Dominion Energy Kewaunee
To:
Document Control Desk, NRC/NRR/ADRO
References
07-0008C, LAR 230
Download: ML071210185 (10)


Text

Dominion Energy Kewaunee, Inc. F0; D o mi nion5000 Dominion Boulevard, Glen Allen, VA 23060 April 26, 2007 U. S. Nuclear Regulatory Commission Serial No. 07-00080 Attention:

Document Control Desk KPS/LIC/GOR:

RO Washington, DC 20555 Docket No. 50-305 License No. DPR-43 DOMINION ENERGY KEWAUNEE, INC.KEWAUNEE POWER STATION SUPPLEMENT TO LICENSE AMENDMENT REQUEST 230. "EMERGENCY DIESEL GENERATOR SHORT-TIME LOAD TESTING" Pursuant to 10 CFR 50.90, Dominion Energy Kewaunee, Inc. (DEK) submitted a request for approval of a proposed amendment to the Kewaunee Power Station (KPS)Technical Specifications (TS) (reference 1). The proposed amendment would modify KPS Technical Specification 4.6.a.5 to permit performance of the emergency diesel generator (EDG) short-time load test at a reduced load. Subsequently, the Nuclear Regulatory Commission (NRC) transmitted a request for additional information (RAI)regarding the proposed amendment (reference

2) which DEK responded to (reference 3).Based on DEK's response to the NRC RAIs, a teleconference was held on April 25, 2007, between the NRC staff and DEK staff concerning the power factor value listed in the proposed TS. During this teleconference, DEK committed to change the power factor value contained in the proposed TS to bound the calculated power factors listed in KPS "Calculation C-042-001, Revision 6, Addendum C, "Safeguards Diesel Generator Loading" (attachment 2 of reference 3).Attachment 1 contains the revised marked-up TS pages changing the specified power factor from < 0.9 to < 0.89. Attachment 2 contains the proposed revision to the affected TS pages.This proposed change to the amendment request does not change the conclusions of the no significant hazards determination in reference 1.If you have any questions or require additional information, please contact Mr. Craig Sly at (804) 273-2784.

A complete copy of this submittal has been transmitted to the State of Wisconsin as required by 10 CFR 50.91 (b)(1).Very truly yours, Gerald T. Bishof Vice President

-Nuclear Engineering

,4oo!

Serial No. 07-0008C LAR 230 Supplemental Response Page 2 of 4 Commitments made by this letter: None

References:

1. Letter from Gerald T. Bischof (DEK) to Document Control Desk, "License Amendment Request 230 -Emergency Diesel Generator Short-Time Load Testing," dated January 10, 2007 (ADAMS Accession No. ML070120088).
2. Letter from R. F. Kuntz (NRC) to D. A. Christian (DEK), "Kewaunee Power Station -Request for Additional Information Related to Emergency Diesel Generator Short-Time Load Testing (TAC No. MD3995)," dated March 8, 2007 (ADAMS Accession No. ML070600485).
3. Letter from Gerald T. Bischof (DEK) to Document Control Desk, "Response to NRC Request for Additional Information Regarding License Amendment Request 230 -Emergency Diesel Generator Short-Time Load Testing," dated April 5, 2007 (ADAMS Accession No. ML071020080).

Attachments:

1. Marked-up TS Pages.2. Affected TS Pages.

Serial No. 07-0008C LAR 230 Supplemental Response Page 3 of 4 cc: Regional Administrator, Region III U.S. Nuclear Regulatory Commission 2443 Warrenville Road Suite 210 Lisle, IL 60532-4352 Ms. M. H. Chernoff U.S. Nuclear Regulatory Commission Mail Stop O-8-G9A Washington, D. C. 20555 Mr. S. C. Burton NRC Senior Resident Inspector Kewaunee Power Station Public Service Commission of Wisconsin Electric Division P. 0. Box 7854 Madison, WI 53707 Serial No. 07-0008C LAR 230 Supplemental Response Page 4 of 4 COMMONWEALTH OF VIRGINIA )))COUNTY OF HENRICO The foregoing document was acknowledged before me, in and for the County and Commonwealth aforesaid, today by Gerald T. Bischof, who is Vice President

-Nuclear Engineering of Dominion Energy Kewaunee, Inc. He has affirmed before me that he is duly authorized to execute and file the foregoing document in behalf of that Company, and that the statements in the document are true to the best of his knowledge and belief.Acknowledged before me this c?4 (a" day of&4~Ajl~y ,2007.My Commission Expires: b.6A Noay~~blic (SEAL)

Serial No. 07-0008C ATTACHMENT 1 SUPPLEMENT TO KEWAUNEE LICENSE AMENDMENT REQUEST 230 EMERGENCY DIESEL GENERATOR SHORT-TIME LOAD TESTING MARKED-UP TS PAGES TS 4.6-1 TS 4.6-2 KEWAUNEE POWER STATION DOMINION ENERGY KEWAUNEE, INC.

4.6 PERIODIC TESTING OF EMERGENCY POWER SYSTEM AI:PLICABILITY Applies to periodic testing and surveillance requirements of the emergency power system.01J.ECI.VE To verify that the emergency power sources and equipment are OPERABLE.SPECIFICATION The following tests and surveillance shall be performed:

a. Diesel Generators
1. Manually-initiated start of each diesel generator, and assumption of load by the diesel generator.

This test shall be conducted monthly, loading the diesel generator to at least 2600 KW (nominal) for a period of at least 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br />.2. Automatic start of each diesel generator, load shedding, and restoration to operation of particular vital equipment, all initiated by a simulated loss of all normal a-c station service power supplies together with a simulated safety injection signal.This test will be conducted at each REFUELING interval to assure that each diesel generator will start and assume required loads to the extent possible within 1 minute, and operate for > 5 minutes while loaded with the emergency loads.3. Each diesel generator shall be inspected at each major REFUELING outage.4. Diesel generator load rejection test in accordance with IEEE 387-1977, Section 6.4.5, shall be performed at least once per 18 months.LAR 230 TS 4.6-1

5. Each diesel generator shall be o edjoeaded at ' pnwg.r fntn, .f g A C) ,tras hoi irs every operating oyrlo: Nota 1 MonmntarV trqn.iant.

ai it.-ida tho In-d qnd ,ipowr factnr rh- not invlida~ta thi.s tapct Note 2 Thi; 5Sijr'aillanrp ghnll not nnrmlly b h-in the O)PFEEATIN(Q or HOT STANI'RYV MOI'F I-inwpvpr this Si grvyillanc, may bh performed to ree-,tnhlicqh C)PFIRARII ITY ,nrnvidd an , s ssment dz.terminaos thn qafoty nf thp plant isq m;intninard nr .nhnnno.d C-rdit may hbe tqkn fnr imnPklannd Pvpnt-, that .qtikfy thi.s .iirvo.ilbnoo Note. 3 If ,pnrfnrmeod with the diop.l ganerator .ynchrnnized with nff.ita ,nwor it .qhnlL.ho prformed at a ponw.r fartor < 0 AQ -inweov.r if grid nonditionnc do nnt ,pormit tho ,ow.r farctor limit i* not regi firmd to hb mpt. I Indlr this rondition the ,onwr factor shgil ho maint.ined ao nlos o tn tho limit a-, ,rgatinrahp_

A For > 2 hoi ing lowiedo e-9$j4AVIA on ------ KW R- Fnr the remining hmirr nf tha test loaided ..... K d -4...70n.(nnminalfo

^2,,, hour e.... opxuer&t,, , cyole.6. Safeguard bus undervoltage and safeguard bus second level undervoltage relays shall be calibrated at least once per operating cycle.b. Station Batteries 1. The voltage of each cell shall be measured to the nearest hundredth volt each month. An equalizing charge shall be applied if the lowest cell in the battery falls< 2.13 volts. The temperature and specific gravity of a pilot cell in each battery shall be measured.2. The following additional measurements shall be made quarterly:

the specific gravity and height of electrolyte in every cell and the temperature of every fifth cell.3. All measurements shall be recorded and compared with previous data to detect signs of deterioration.

4. The batteries shall be subjected to a load test during the first REFUELING and once every 5 years thereafter.

Battery voltage shall be monitored as a function of time to establish that the battery performs as expected during heavy discharge and that all electrical connections are tight.LAR 230 TS 4.6-2 Serial No. 07-0008C ATTACHMENT 2 SUPPLEMENT TO KEWAUNEE LICENSE AMENDMENT REQUEST 230 EMERGENCY DIESEL GENERATOR SHORT-TIME LOAD TESTING AFFECTED TS PAGES TS 4.6-1 TS 4.6-2 KEWAUNEE POWER STATION DOMINION ENERGY KEWAUNEE, INC.

4.6 PERIODIC TESTING OF EMERGENCY POWER SYSTEM APPLICABILITY Applies to periodic testing and surveillance requirements of the emergency power system..JECILVE To verify that the emergency power sources and equipment are OPERABLE.SPECIFICATION The following tests and surveillance shall be performed:

a. Diesel Generators
1. Manually-initiated start of each diesel generator, and assumption of load by the diesel generator.

This test shall be conducted monthly, loading the diesel generator to at least 2600 KW (nominal) for a period of at least 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br />.2. Automatic start of each diesel generator, load shedding, and restoration to operation of particular vital equipment, all initiated by a simulated loss of all normal a-c station service power supplies together with a simulated safety injection signal.This test will be conducted at each REFUELING interval to assure that each diesel generator will start and assume required loads to the extent possible within 1 minute, and operate for > 5 minutes while loaded with the emergency loads.3. Each diesel generator shall be inspected at each major REFUELING outage.4. Diesel generator load rejection test in accordance with IEEE 387-1977, Section 6.4.5, shall be performed at least once per 18 months.TS 4.6-1

5. Each diesel generator shall be operated for > 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> every operating cycle: Note 1 Momentary transients outside the load and power factor ranges do not invalidate this test.Note 2 This Surveillance shall not normally be performed in the OPERATING or HOT STANDBY MODE. However, this Surveillance may be performed to reestablish OPERABILITY provided an assessment determines the safety of the plant is maintained or enhanced.

Credit may be taken for unplanned events that satisfy this surveillance requirement.

Note 3 If performed with the diesel generator synchronized with offsite power, it shall be performed at a power factor < 0.89. However, if grid conditions do not permit, the power factor limit is not required to be met. Under this condition the power factor shall be maintained as close to the limit as practicable.

A. For > 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> loaded to 2860 KW (nominal) and, B. For the remaining hours of the test loaded to 2700 KW (nominal).

6. Safeguard bus undervoltage and safeguard bus second level undervoltage relays shall be calibrated at least once per operating cycle.b. Station Batteries 1. The voltage of each cell shall be measured to the nearest hundredth volt each month. An equalizing charge shall be applied if the lowest cell in the battery falls< 2.13 volts. The temperature and specific gravity of a pilot cell in each battery shall be measured.2. The following additional measurements shall be made quarterly:

the specific gravity and height of electrolyte in every cell and the temperature of every fifth cell.3. All measurements shall be recorded and compared with previous data to detect signs of deterioration.

4. The batteries shall be subjected to a load test during the first REFUELING and once every 5 years thereafter.'

Battery voltage shall be monitored as a function of time to establish that the battery performs as expected during heavy discharge and that all electrical connections are tight.TS 4.6-2