| title = Oconee, Unit 2 - EOC 24 Refueling Outage Inservice Inspection Report, Fourth Ten-Year Inservice Inspection Interval
| title = EOC 24 Refueling Outage Inservice Inspection Report, Fourth Ten-Year Inservice Inspection Interval
| author name = Baxter D
| author name = Baxter D
| author affiliation = Duke Energy Carolinas, LLC
| author affiliation = Duke Energy Carolinas, LLC

Revision as of 13:48, 30 January 2019

EOC 24 Refueling Outage Inservice Inspection Report, Fourth Ten-Year Inservice Inspection Interval
ML102430529
Person / Time
Site: Oconee Duke Energy icon.png
Issue date: 08/27/2010
From: Baxter D
Duke Energy Carolinas
To:
Document Control Desk, Office of Nuclear Reactor Regulation
References
IWA-6230, IWA-6240
Download: ML102430529 (186)


Text

DAVE BAXTER Vice President rakEnergy Oconee Nuclear Station Duke Energy ONO] VP / 7800 Rochester Highway Seneca, SC 29672 864-873-4460 864-873-4208 fax dave. baxter@duke-energy.

com August 27, 2010 U.S. Nuclear Regulatory Commission Document Control Desk Washington, DC 20555

Subject:

Duke Energy Carolinas, LLC Oconee.Nuclear Stati on, Unit 2 Docket No. 50-270 Unit 2 EOC,24 Refdeli9gi utage Inservice Inspection Report-Fourth Ten-Year Inservice Inspection Interval Please find attached a copy of the Inservice Inspection Report for Oconee Unit 2 End of Cycle 24 Refueling Outage. This report is submitted pursuant to Section Xl of the ASME Boiler and Pressure Vessel Code, 1998 Edition, with 2000 addenda, Subsubarticles IWA 6230 and IWA-6240.This report does not include activities specific to the Steam Generator Tube Inservice Inspection.

An additional summary report which documents the Steam Generator Tube Inservice Inspection of the Unit 2 EOC-24 Refueling Outage will be transmitted separately.

If there are any questions you may contact Corey Gray at (864) 873-6325.Sincerely, Dave Baxter, Site Vice-President Oconee Nuclear Station Attachment Nf-71 www. duke-energy.

com U. S. Nuclear Regulatory Commission August 27, 2010 Page 2 xc wo/attachment:

Luis Reyes Region II Administrator U.S. Nuclear Regulatory Commission Marquis One Tower 245 Peachtree Center Ave., NE, Suite 1200 Atlanta, Ga 30303-1257 John Stang Project Manager U. S. Nuclear Regulatory Commission Office of Nuclear Reactor Regulation Washington, D.C. 20555 Andy Sabisch NRC Senior Resident Inspector Oconee Nuclear Station INSERVICE INSPECTION REPORT DUKE ENERGY CAROLINAS OCONEE NUCLEAR STATION UNIT 2 TWENTY-Fourth REFUELING OUTAGE Duke VEnergy Owner's Report For INSERVICE INSPECTIONS OCONEE UNIT 2 2010 REFUELING OUTAGE EOC24 (OUTAGE 4)Plant Location:

7800 Rochester Highway, Seneca, South Carolina 29672 NRC Docket No. 50-270 Commercial Service Date: September 9, 1974 Document Completion Date Owner: Duke Energy Carolinas 526 South Church St.Charlotte, N. C. 28201-1006 Revision 0 Prepared By: Reviewed By:.. Approved By: Date "7-_-_o Date 7" 20 -/Date 7 2/..

FORM NIS-1 OWNER'S DATA REPORT FOR INSERVICE INSPECTIONS As required by the Provisions of the ASME Code Rules 1. Owner: Duke Energy Carolinas, 526 S. Church St.. Charlotte, NC 28201-1006 (Name and Address of Owner)2. Plant: Oconee Nuclear Station, 7800 Rochester Highway, Seneca, SC 29672 (Name and Address of Plant)3. Plant Unit: 2 4. Owner Certificate of Authorization (if required)

N/A 5. Commercial Service Date: September 9, 1974 6. National Board Number for Unit N/A 7. Components Inspected:

Component or Appurtenance Manufacturer Installer Manufacturer Installer Serial No.State or Province No.National Board No.See Section 1.1 in the Attached Report r Note: Supplemental sheets in the form of lists, sketches, or drawings may be used provided (1) size is 81/2 in. x 11 in., (2) information in items 1 through 6 on this data report is included on each sheet, and (3) each sheet is numbered and the number of sheets is recorded at the top of this form.Total number of pages contained in this report 177

.FORM NIS-1 (Back)8. Examination Dates December 12, 20008 to May 30, 2010 0 9. Inspection Period Identification:

10. Inspection Interval Identification:
11. Applicable Edition of Section XI 12. Date/Revision of Inspection Plan: Second Period Fourth Interval 1998 Addenda 2000 January 26, 2008 / Revision 1 13. Abstract of Examinations and Tests. Include a list of examinations and tests and a statement concerning status of work required for the Inspection Plan. See Sections 2.0, 3.0 and 6.0 14. Abstract of Results of Examination and Tests.15. Abstract of Corrective Measures.See Sections 4.0 and 6.0 See Subsection 4.3 We certify that a) the statements made in this report are correct b) the examinations and tests meet the Inspection Plan as required by the ASME Code,Section XI, and c) corrective measures taken conform to the rules of the ASME Code,Section XI.Certificate of Authorization No. (if applicable)

NA Expiration Date NA Date 7/2Z/2 Signed Duke Energy Carolinas.

Owner By CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of -Ty"7-N /f vif.,eod employed by HSB Global Standards have inspected the components described in this Owner's Report during the period iz-/z-O8 to 6-So -3 o , and state that to the best of my knowledge and belief, the Owner has performed examinations and tests and taken corrective measures described in the Owner's Report in accordance with the Inspection Plan and as required by the ASME Code,Section XI.By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations, test, and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection Commissions SCa5"e AJ/1W,6C_

/J National Board, State, Province, and Endorsements Inspector's Signature Date 7--3 /0 HSB Global Standards 200 Ashford Center North Suite 205 Atlanta, GA. 30338-4860 (800) 417-3721 www.hsbct.com DISTRIBUTION LIST 1. Duke Energy Carolinas Nuclear Technical Services Division Section XI Inspection Program Section 2. NRC Document Control Desk 3. HSB Global Standards (AIA)c/o ANII at Oconee Note: The following personnel are to be notified via e-mail after the Inservice Inspection Report has been stored in the Nuclear Electronic Document Library: GO Nuclear Assurance c/o Bruce Nardoci Inspection Services (ISI Coordinator)

TABLE OF CONTENTS Section Title Revision 1.0 General Information 0 2.0 Fourth Ten Year Inspection Status 0 3.0 Final Inservice Inspection Plan 0 4.0 Results of Inspections Performed 0 5.0 Owners Report for Repair/Replacement Activities 0 6.0 Pressure Testing 0 I, 1

1.0 General

Information This report describes the Inservice Inspection of Duke's Oconee Nuclear Station, Unit 2, during Outage 4/EOC 24. This is the second outage in the second inspection period of the Fourth Ten-Year Interval.

ASME Section XI, 1998 Edition with the 2000 Addenda, was the governing Code for selection and performance of the ISI examinations.

Included in this report are: the inspection status for each examination category, the final inservice inspection plan, the inspection results for each item examined, and corrective actions taken when reportable conditions were found. In addition, there is an Owner's Report for Repair/Replacement Activities Section, which includes completed NIS-2 documentation of repair/replacement activities.

1.1 Identification

Numbers Manufacturer Item Manufacturer or Installer State or National or Installer Serial No. Province No. Board No.Reactor Vessel Babcock & Wilcox 620-0004-51-52 N/A N-1 05 Reactor Vessel Babcock & Wilcox 068S-02 N/A 209 Head (replaced head)Steam Generator A Babcock & Wilcox 006K03 N/A 207 Steam Generator B Babcock & Wilcox 006K04 N/A 208 Pressurizer Babcock & Wilcox 620-0004-59 N/A N-1 06 Main Steam Duke Power NA NA NA System Auxiliary Steam Duke Power NA NA NA System Feedwater System Duke Power NA NA NA Emergency Duke Power NA NA NA Feedwater System Steam Generator Duke Power NA NA NA Flush System Condensate Duke Power NA NA NA System EOC 24 Refueling Outage Report Oconee Unit 2 Section 1 Page 1 of 4 Revision 0 July 14, 2010 Manufacturer Item Manufacturer or Installer State or National or Installer Serial No. Province No. Board No.Vents and Exhaust Duke Power NA NA NA System Condenser Duke Power NA NA NA Circulating Water High Pressure Duke Power NA NA NA Service Water System Low Pressure Duke Power NA NA NA Service Water System Reactor Coolant Duke Power NA NA NA System High Pressure Duke Power NA NA NA Injection System Low Pressure Duke Power NA NA NA Injection System Reactor Building Duke Power NA NA NA Spray System Component Duke Power NA NA NA Cooling System Spent Fuel Cooling Duke Power NA NA NA System Vents -Reactor Duke Power NA NA NA Building Components Drains -Reactor Duke Power NA NA NA Building Components EOC 24 Refueling Outage Report Oconee Unit 2 Section 1 Page 2 of 4 Revision 0 July 14, 2010

1.2 Reference

Documents The following reference documents apply to the inservice inspections performed during this report period. A copy may be obtained by contacting the ISI Plan Manager at Duke's Corporate Office in Charlotte, North Carolina.Code Case N-460 (Alternative Examination Coverage for Class 1 and Class 2 Welds,Section XI, Division I) Applicable to items in this report where less than 100% coverage of the required weld examination volume was achieved.Code Case N-504-2 (Alternative Rules for Repair of Class 1, 2, and 3 Austenitic Stainless Steel Piping). Applicable to items that receive a weld overlay. During 2EOC-24 outage there were welds that received weld overlay and the PSI exams were performed per Code Case N-504-2.Code Case N-609 (Alternate Requirements to Stress-Based Selection Criteria for Category B-J Welds,Section XI, Division 1.)Code Case N-624 (Alternative to the requirements of IWB-2420(a), IWC-2420(a), IWD-2420(a), and IWF-2420(a).)

This will allow the sequence of component examinations that were established during the first inspection interval to be modified, provided that the percentage requirements are still met.Code Case N-663 (Alternative Requirements for Classes 1 and 2 Surface Examinations,Section XI, Division, I)Code Case N-685 (Lighting Requirements for Surface Examinations)

Code Case N-695 (Qualification Requirements for Dissimilar Metal Piping Welds,Section XI, Division I)Code Case N-722 (Additional Examinations for PWR Pressure retaining Welds in Class 1 Components Fabricated with Alloy 600/82/182 MaterialsSection XI, Division 1) 1 OCFR Part 50, Federal Register, Final Rule that was issued September 10, 2008 mandates the use of this code case. (Effective Date is October 10, 2008)Duke Power Company Problem Investigation Process Report 0-10-0755.

This PIP was written to track the evaluation process and resolution of indications that are not service induced that were found during ISI on Class 1, 2, or 3 supports.Duke Power Company Problem Investigation Process Report 0-10-0757.

This PIP was written to track the evaluation process and resolution of service induced indications found during ISI on Class 1, 2, or 3 supports.EOC 24 Refueling Outage Report Page 3 of 4 Oconee Unit 2 Revision 0 Section 1 July 14, 2010 Duke Power Company Problem Investigation Process Report 0-10-02605.

This PIP was written to track the evaluation process and resolution for limited coverage on UT examinations of welds that were inspected during EOC-24 for Unit 2. This will include processing relief request if it is determined that greater than ninety percent of coverage cannot be achieved.

The welds with limited coverage are listed in Section 4.4 of this report.PIP 0-09-00530 was written to document the work orders that had work completed during the 2EOC-23 report period but the documentation was not completed in time for the NIS-2 forms to be incorporated into 2EOC-23 report.PIP 0-09-0848 was written to incorporate Code Case N-609 into the Fourth Interval ISI Plan. This code case is instrumental in removing stress welds from the inspection plan.PIP G-08-0185 was written to incorporate Code Case N-663 into the Fourth Interval ISI Plan. This code case is instrumental in removing surface exams from the inspection plan.Plan Addenda ONS2-079, ONS2-089, ONS2-091, ONS2-092, and ONS2-096 are instrumental to making changes to the Unit 2 Fourth Interval ISI Plan, which are reflected in the totals shown in the tables in Section 2.Request for Relief 03-006 (Allows Duke an Alternative for the Snubber Examinations required in IWF-5000 for the 4 th interval.)

Request for Relief 07-ON-001 (Allows Duke an Alternative for Section XI inspection requirements to support the application of Structural Weld Overlays on Nozzle to SE Welds. (Summary Numbers 01.Q1.1)EOC 24 Refueling Outage Report Oconee Unit 2 Section 1 Page 4 of 4 Revision 0 July 14, 2010 2

2.0 Fourth

Ten Year Interval Inspection Status The completion status of inspections required by the 1998 ASME Code Section XI, with the 2000 Addenda, is summarized in this section. The requirements are listed by the ASME Section XI Examination Category as defined in Table IWB-2500-1 for Class 1 Inspections, Table IWC-2500-1 for Class 2 Inspections, and IWF-2500-1 for Class.1 and 2 Component Supports.

Appendix Q, Augmented, and Elective inspections are also included.Class I Inspections Examination Inspections Inspections Percentage (1)Category Description Required Completed Completed Deferral Allowed B-A Pressure Retaining Welds 6 Welds .5 Weld 8% Partial in Reactor Vessel B-B Pressure Retaining Welds 10 Welds 6 Welds 60% No in Vessels Other than Reactor Vessel B-D Full Penetration Welds of 54 27 50% Partial Nozzles in Vessels Inspections Inspections Inspection Program B B-F Pressure Retaining 2 Welds 1 Welds 50% Partial Dissimilar Metal Welds _-B-G-1 Pressure Retaining Bolting 128 Items 83.66 Items 65% Yes Greater than 2 Inches in Diameter B-G-2 Pressure Retaining Bolting 20 Items 15 Items 75% No 2 Inches and Less in Diameter B-J Pressure Retaining Welds (2) 139 Welds 91 Welds 65% No in Piping II___II_B-K Welded Attachments for 11 7 64% No Vessels, Piping, Pumps and Valves (1) Deferral of inspection to the end of the interval as allowed by ASME Section XI Table IWB-2500-1.

(2)Totals changed from 160 in EOC-23 to 139 in EOC-24 due to welds being deleted and from adopting Code Case N-609. See Plan Addenda ONS2-079, ONS2-092, and PIP G-09-0848 for details on the changes.EOC 24 Refueling Outage Report Oconee Unit 2 Section 2 Page 1 of 4 Revision 0 July 14, 2010 Class 1 Inspections (Continued)

Examination Inspections Inspections Percentage (1)Category Description Required Completed Completed Deferral Allowed B-L-1 Pressure Retaining Welds 1 Weld 1 Weld 100% Yes in Pump Casings B-L-2 Pump Casings 1 Casing 0 Casing 0% Yes B-M-1 Pressure Retaining 1 Valve Body 1 Valve Body 100% Yes Welds in Valve Bodies Weld Weld B-M-2 Valve Bodies 3 Valves 1 Valves 33% Yes B-N-1 Interior of Reactor Vessel 3 Inspections 2 Inspection 67% No B-N-2 Welded Core Support 1 Inspection 0 Inspections 0% Yes Structures and Interior Attachments to Reactor Vessels B-N-3 Removable Core Support 1 Inspection 0 Inspections 0% Yes Structures B-0 Pressure Retaining Welds 12 Housing 8 Housing 67% Yes in Control Rod Housings Welds Welds B-P All Pressure Retaining Components REFERENCE SECTION 6.0 OF THIS REPORT B-Q Steam Generator Tubing N/A N/A N/A N/A F-A Class 1 Component 37 Supports 24 Supports 65% No F1.10 & F1.40 Supports (Except items. Snubbers)F-A Class 1 Component (2)F1.50 items. Supports, Snubbers Weld Overlay per Section XI Appendix Q (1)Deferral of inspection to the end of the interval as allowed by ASME Section XI Table IWB-2500-1.

(2) Inspected under Selected License Commitment 16.9.18 per Relief Request 03-006.EOC 24 Refueling Outage Report Oconee Unit 2 Section 2 Page 2 of 4 Revision 0 July 14, 2010 Class 2 Inspections Examination Inspections Inspections Percentage Category Description Required Completed Completed C-A Pressure Retaining Welds 11 Welds 7 Welds 64%in Pressu(e Vessels C-B Pressure Retaining Nozzle 4 Welds 3 Welds 75%Welds in Vessels C-C Integral Attachments for (2) 41 25 61%Vessels, Piping, Pumps Attachments Attachments and Valves C-D Pressure Retaining Bolting 2 Items 1 Items 50%Greater Than 2 Inches in Diameter C-F-1 Pressure Retaining Welds (3) 160 Welds 95 Welds 59%in Austenitic Stainless Steel or High Alloy Piping C-F-2 Pressure Retaining Welds 65 Welds 43 Welds 66%in Carbon or Low Alloy (4)Steel Piping C-G Pressure Retaining Welds N/A N/A N/A in Pumps and Valves C-H All Pressure Retaining Components REFERENCE SECTION 6.0 OF THIS REPORT F-A Class 2 Component 141 Supports 89 Supports 63%F1.20 & F1.40 Supports (Except (5)items. Snubbers)F-A Class 2 Component (1)F1.50 items Supports, Snubbers (1) Inspected under Selected License Commitment 16.9.18 per Relief Request 03-006.(2) Totals changed from 38 in EOC-23 to 41 in EOC-24 due to supports being added. See Plan Addenda ONS2-089 for details on the changes.(3) Totals changed from 164 in EOC-23 to 160 in EOC-24 due to adopting Code Case N-663. See Plan Addenda ONS2-091, and PIP G-08-00185 for details on the changes.(4) Totals changed from 66 in EOC-23 to 65 in EOC-24 due to adopting Code Case N-663. See Plan Addenda ONS2-091, and PIP G-08-00185 for details on the changes.(5) Totals changed from 137 in EOC-23 to 141 in EOC-24 due to adding supports to schedules.

See Plan Addenda ONS2-089, and ONS2-096 for details on the changes.EOC 24 Refueling Outage Report Oconee Unit 2 Section 2 Page 3 of 4 Revision 0 July 14, 2010 Augmented/Elective Inspections Summary Percentage Complete Number Description 02.B4.30 Head with Nozzles and Partial Penetration Welds, Bare None scheduled for EOC 24 Metal Visual per Code Case N-729-1 02.B4.40 Head with nozzles and Partial Penetration Welds, None scheduled for EOC 24 Volumetric/Surface exam per Code Case N-729-1 02.B1 5.80 Reactor Vessel Bottom Head Bare Metal Visual per 100% of EOC 24 Requirements Code Case N-722 02.B15.210 Hot Leg Full Penetration Weld, Bare Metal Visual per 100% of EOC 24 Requirements Code Case N-722 02.B15.215 Cold Leg Full Penetration Weld, Bare Metal Visual per 100% of EOC 24 Requirements Code Case N-722 02.G1.1 Reactor Coolant Pump Flywheel 100% of EOC 24 Requirements 02.G2.1 HPI Nozzle Safe End Examinations 100% of EOC 24 Requirements 02.G3.1 Pressurizer Surge Line Examinations None scheduled for EOC 24 02.G4.1 Thermal Stress Piping (NRC Bulletin 88-08) 100% of EOC 24 Requirements 02.G12.1 UT Examination per MRP-139 100% of EOC 24 Requirements 02.G12.2 UT Examination per MRP-139 100% of EOC 24 Requirements 02.G14.1 VT MRP-139 100% of EOC-24 Requirements 02.G16.1 UT Examination per MRP-146 100% of EOC-24 Requirements 02.H2.1 Class 1 RTE Mounting Bosses None scheduled for EOC 24 02.H3.1 Main Feedwater Piping in the East and West 100% of EOC 24 Requirements Penetration Rooms per QA-513J (ER-ONS-04-03) 02.H4.1 Main Feedwater and Main Steam Piping Supports and 100% of EOC 24 Requirements Attachment Welds per QA-513J (ER-ONS-04-05) 02.H5.1 East Penetration Main Feedwater piping welds and 100% of EOC 24 Requirements attachments 02.H6.1 Main Feedwater rupture restraint attachment welds None scheduled for EOC 24 EOC 24 Refueling Outage Report Oconee Unit 2 Section 2 Page 4 of 4 Revision 0 July 14, 2010 3

3.0 Final

Inservice Inspection Plan The final Inservice Inspection Plan shown in this section lists all ASME Section XI Class 1, Class 2, Class 3, Appendix Q, Augmented, and Elective examinations credited for this report period.EOC 24 Refueling Outage Report Oconee Unit 2 Section 3 Page 1 of 1 Revision 0 July 14, 2010 ScheduleWorks DUKE ENERGY NUCLEAR TECHNICAL SERVICES Inservice Inspection Database Management System Plan Report Oconee 2, 4th Interval, Outage 4 (EQ C-24)This report includes all changes through addendum ONS2-107 Summary Num Component ID ISO/DWG Numbers Procedure Insp Req Material Sched Class I System Description Comments Thick/NPS Cal Blocks Componenet ID 2 Category Aug 02.B135.210.0001 Dissimilar 2RC-278-66 Class 1 50 2RC-278 OM 1201-1469 OM 1201-1472 NDE-68 VT-2 CS-Inconel 0.250 / 1.000 Pipe to Safe End 1 inch HL SB-166 Pressure Tap SE to CS Nozzle weld and SS pipe weld. This weld is located on piping that branches off of "A" Hot Leg.(Examine the Nozzle to Safe-End weld and the Safe-End to Pipe weld.)Per the requirements of 10 CFR 50.55a (g) (6) (ii) (E), all licensees of PWRs shall augment their ISI program implementing ASME Code Case N-722 subject to the conditions specified in paragraphs (g) (6) (ii) (E) 2 through 4.Bare Metal Visual Inspection by VT-2 qualified inspector per the requirements of applicable item numbers listed in Table 1 of Code Case N-722.Personnel performing the visual examination shall be qualified as VT-2 visual examiners and shall have completed a minimum of four hours of additional training in detection of borated water leakage from alloy 600/82/182 components and the resulting boric acid corrosion of adjacent ferritic steel components.

Procedure NDE 68, Acceptance Criteria is "no evidence of borated water leakage." This B15.210 item is to be examined each refueling outage.For additional information, contact Chris Cruz from the Materials and NDE Services Section, Nuclear Technical Services Division.Printed 07/14/10 Ick8302 v. 06/18/09 SDQA Cat "C" Oconee 2 7/14/2010 2:17:26 PM Page 1 of 79 This report includes all changes through addendum ONS2-107 Oconee 2, 4th Interval, outage 4 (EOC-24)Summary Num Component ID ISO/DWG Numbers Procedure Insp Req Material Sched Thick/NPS Cal Blocks Componenet ID 2 Class I System Description Comments Category Aug 02.B15.210.0002 2RC-278-70V Class 1 50 2RC-278 NDE-68 VT-2 CS-Inconel 0.250/ 1.000 OM 1201-1469 Dissimilar OM 120-1472 Pipe to Safe End 1 inch HL SB-166 Pressure Tap SE to CS Nozzle weld and SS pipe weld. This weld is located on piping that branches off of "A" Hot Leg..(Examine the Nozzle to Safe-End weld and the Safe-End to Pipe weld.)Per the requirements of 10 CFR 50.55a (g) (6) (ii) (E), all licensees of PWRs shall augment their ISI program implementing ASME Code Case N-722 subject to the conditions specified in paragraphs (g) (6) (ii) (E) 2 through 4.Bare Metal Visual Inspection by VT-2 qualified inspector per the requirements of applicable item numbers listed in Table 1 of Code Case N-722.Personnel performing the visual examination shall be qualified as VT-2 visual examiners and shall have completed a minimum of four hours of additional training in detection of borated water leakage from alloy 600/82/182 components and the resulting boric acid corrosion of adjacent ferritic steel components.

Procedure NDE 68, Acceptance Criteria is "no evidence of borated water leakage." This B15.210 item is to be examined each refueling outage.For additional information, contact Chris Cruz from the Materials and NDE Services Section, Nuclear Technical Services Division.02.B15.210.0003 2RC-277-50 Class 1 50 2RC-277 NDE-68 VT-2 CS-Inconel 0.250 /1.000 OM 1201-1469 Dissimilar OM 120-1472 Pipe to Safe End 1 inch HL SB-166 Pressure Tap SE to CS Nozzle weld and SS pipe weld. This weld is located on piping that branches off of "B" Hot Leg.(Examine the Nozzle to Safe-End weld and the Safe-End to Pipe weld.)Per the requirements of 10 CFR 50.55a (g) (6) (ii) (E), all licensees of PWRs shall augment their ISI program implementing ASME Code Case N-722 subject to the conditions specified in paragraphs (g) (6) (ii) (E) 2 through 4.Bare Metal Visual Inspection by VT-2 qualified inspector per the requirements of applicable item numbers listed in Table 1 of Code Case N-722.Personnel performing the visual examination shall be qualified as VT-2 visual examiners and shall have completed a minimum of four hours of additional training in detection of borated water leakage from alloy 600/82/182 components and the resulting boric acid corrosion of adjacent ferritic steel components.

Procedure NDE 68, Acceptance Criteria is "no evidence of borated water leakage." This B15.210 item is to~be examined each refueling outage.For additional information, contact Chris Cruz from the Materials and NDE Services Section, Nuclear Technical Services Division.Printed 07/14/10 Ick8302 v. 06/18/09 SDOA Cat "C" Oconee 2 7/14/2010 2:17:26 PM Page 2 of 79 This report includes all changes through addendum ONS2-107 Oconee 2, 4th Interval, outage 4 (EOC-24)Summary Num Component ID ISO/DWG Numbers Procedure Insp Req Material Sched Thick/NPS Cal Blocks Componenet ID 2 Class I System Description Comments Category Aug 02.B15.210.0004 2RC-277-71V Class 1 50 2RC-277 NDE-68 VT-2 CS-Inconel 0.250 /1.000 OM 1201-1469 Dissimilar OM 120-1472 Pipe to Safe End 1 inch HL SB-1 66 Pressure Tap SE to CS Nozzle weld and SS pipe weld: This weld is located on piping that branches off of "B" Hot Leg.(Examine the Nozzle to Safe-End weld and the Safe-End to Pipe weld.)Per the requirements of 10 CFR 50.55a (g) (6) (ii) (E), all licensees of PWRs shall augment their ISI program implementing ASME Code Case N-722 subject to the conditions specified in paragraphs (g) (6) (ii) (E) 2 through 4.Bare Metal Visual Inspection by VT-2 qualified inspector per the requirements of applicable item numbers listed in Table 1 of Code Case N-722.Personnel performing the visual examination shall be qualified as VT-2 visual examiners and shall have completed a minimum of four hours of additional training in detection of borated water leakage from alloy 600/82/182 components and the resulting boric acid corrosion of adjacent ferritic steel components.

Procedure NDE 68, Acceptance Criteria is "no evidence of borated water leakage." This B15.210 item is to be examined each refueling outage.For additional information, contact Chris Cruz from the Materials and NDE Services Section, Nuclear Technical Services Division.02.B15,210.0005 2RC-278-23 Class 1 50 2RC-278 NDE-68 VT-2 CS-Inconel 0.250 /1.000 OM 1201-1469 Dissimilar OM 120-1472 Pipe to Safe End.075 inch ID HL SB-167 Flowmeter Nozzle SE to CS Nozzle weld and SS pipe weld. (Examine the Nozzle to Safe-End weld and the Safe-End to Pipe weld.) This weld is located on piping that branches off of "A" Hot Leg.Per the requirements, of 10 CFR 50.55a (g) (6) (ii) (E), all licensees of PWRs shall augment their ISI program implementing ASME Code Case N-722 subject to the conditions specified in paragraphs (g) (6) (ii) (E) 2 through 4.Bare Metal Visual Inspection by VT-2 qualified inspector per the requirements of applicable item numbers listed in Table 1 of Code Case N-722.Personnel performing the visual examination shall be qualified as VT-2 visual examiners and shall have completed a minimum of four hours of additional training in detection of borated water leakage from alloy 600/82/182 components and the resulting boric acid corrosion of adjacent ferritic steel components.

Procedure NDE 68, Acceptance Criteria is "no evidence of borated water leakage." This B15.210 item is to be examined each refueling outage.For additional information, contact Chris Cruz from the Materials and NDE Services Section, Nuclear Technical Services Division.Printed 07/14/10 Ick8302 v. 06/18/09 SDQA Cat "C" PvOconee 2 7/14/2010 2:17:26 PM Page 3 of 79 This report includes all changes tnrough addendum ONS2-107 Oconee 2, 4th Interval, outage 4 (EOC-24)Summary Num Component ID ISO/DWG Numbers Procedure Insp Req Material Sched Thick/NPS Cal Blocks Componenet ID 2 Class / System Description Comments Category Aug 02.B15.210.0006 2RC-278-69 Class 1 50 2RC-278 NDE-68 VT-2 CS-Inconel 0.250 /1.000 OM 1201-1469 Dissimilar OM 120-1472 Pipe to Safe End.075 inch ID HL SB-167-Flowmetef N'zzle SE to CS Nozzle weld and SS pipe weld. (Examine the Nozzle to Safe-End weld and the Safe-End to Pipe weld.) This weld is located on piping that branches off of "A" Hot Leg.Per the requirements of 10 CFR 50.55a (g) (6) (ii) (E), all licensees of PWRs shall augment their ISI program implementing ASME Code Case N-722 subject to the conditions specified in paragraphs (g) (6) (ii) (E) 2 through 4.Bare Metal Visual Inspection by VT-2 qualified inspector per the requirements of applicable item numbers listed in Table 1 of Code Case N-722.Personnel performing the visual examination shall be qualified as VT-2 visual examiners and shall have completed a minimum of four hours of additional training in detection of borated water leakage from alloy 600/82/182 components and the resulting boric acid corrosion of adjacent ferritic steel components.

Procedure NDE 68, Acceptance Criteria is "no evidence of borated water leakage." This B15.210 item is to be examined each refueling outage.For additional information, contact Chris Cruz from the Materials and NDE Services Section, Nuclear Technical Services Division.02.B15.210.0007 2RC-277-24 Class 1 50 2RC-277 NDE-68 VT-2 CS-Inconel 0.250 / 1.000 OM 1201-1469 Dissimilar

\ OM 120-1472 Pipe to Safe End.075 inch ID HL SB-167 Flowmeter Nozzle SE to CS Nozzle weld and SS pipe weld. (Examine the Nozzle to Safe-End weld and the Safe-End to Pipe weld.) This weld is located on piping that branches off of "B" Hot Leg.Per the requirements of 10 CFR 50.55a (g) (6) (ii) (E), all licensees of PWRs shall augment their ISI program implementing ASME Code Case N-722 subject to the conditions specified in paragraphs (g) (6) (ii) (E) 2 through 4.Bare Metal Visual Inspection by VT-2 qualified inspector per the requirements of applicable item numbers listed in Table 1 of Code Case N-722.Personnel performing the visual examination shall be qualified as VT-2 visual examiners and shall have completed a minimum of four hours of additional training in detection of borated water leakage from alloy 600/82/182 components and the resulting boric acid corrosion of adjacent ferritic steel components.

Procedure NDE 68, Acceptance Criteria is "no evidence of borated water leakage." This B15.210 item is to be examined each refueling outage.For additional information, contact Chris Cruz from the Materials and NDE Services Section, Nuclear Technical Services Division.Printed 07/14/10 Ick8302 v. 06/18/09 SDQA Cat "C" Oconee 27/14/2010 2:17:26 PM Page 4 of 79 This report includes all change rough addendum ONS2-107 Oconee 2, 4th Interval, outage 4 (EOC-24)Summary Num Component ID ISO/DWG Numbers Procedure lns'p Req Material Sched ThickINPS Cal Blocks Componenet ID 2 Class / System Description Comments Category Aug 02.B15.210.0008 2RC-277-70 Class 1 50 2RC-277 NDE-68 VT-2 CS-Inconel 0.250 /1.000 OM 1201-1469 Dissimilar OM 120-1472 Pipe to Safe End.075 inch ID HL SB-167 Flowmeter Nozzle SE to CS Nozzle weld and SS pipe weld. (Examine the Nozzle to Safe-End weld and the Safe-End to Pipe weld.) This weld is located on piping that branches off of "B" Hot Leg.Per the requirements of 10 CFR 50.55a (g) (6) (ii) (E), all licensees of PWRs shall augment their ISI program implementing ASME Code Case N-722 subject to the conditions specified in paragraphs (g) (6) (ii) (E) 2 through 4.Bare Metal Visual Inspection by VT-2 qualified inspector per the requirements of applicable item numbers listed in Table 1 of Code Case N-722.Personnel performing the visual examination shall be qualified as VT-2 visual examiners and shall have completed a minimum of four hours of additional training in detection of borated water leakage from alloy 600/82/182 components and the resulting boric acid corrosion of adjacent ferritic steel components.

Procedure NDE 68, Acceptance Criteria is "no evidence of borated water leakage." This B15.210 item is to be examined each refueling outage.For additional information, contact Chris Cruz from the Materials and NDE Services Section, Nuclear Technical Services Division.02.B15.210.0009 2-PHA-13 Class 1 50 ISI-OCN2-005 NDE-68 VT-2 CS-Inconel 2.875 / 9.000 OM 1201-1469 Dissimilar OM 1201-1472 Pipe to Pipe RTE Mounting Boss SB-166 to 690 Drywell Weld on 2A Hotleg (X-Axis)Hot Leg (Piece 7) to RTE Mounting Boss (piece 12).Per the requirements of 10 CFR 50.55a (g) (6) (ii) (E), all licensees of PWRs shall augment their ISI program implementing ASME Code Case N-722 subject to the conditions specified in paragraphs (g) (6) (ii) (E) 2 through 4.Bare Metal Visual Inspection by VT-2 qualified inspector per the requirements of applicable item numbers listed in Table 1 of Code Case N-722.Personnel performing the visual examination shall be qualified as VT-2 visual examiners and shall have completed a minimum of four hours of additional training in detection of borated water leakage from alloy 600/82/182 components and the resulting boric acid corrosion of adjacent ferritic steel components.

Procedure NDE 68, Acceptance Criteria is "no evidence of borate d water leakage." This B15.210 item is to be examined each refueling outage.For additional information, contact Chris Cruz from the Materials and NDE Services Section, Nuclear Technical Services Division.Printed 07/14/10 Ick8302 v. 06/18/09 SDQA Cat "C" Oconee 2 7/14/2010 2:17:26 PM Page 5 of 79 This report includes all changesTrough addendum ONS2-107 Oconee 2, 4th Interval, outage 4 (EOC-24)Summary Num Component ID ISO/DWG Numbers Procedure Insp Req Material Sched Thick/NPS Cal Blocks Componenet ID 2 Class I System Description Comments Category Aug 02.B15.210.0010 2-PHA-14 Class 1 50 ISI-OCN2-005 NDE-68 VT-2 CS-Inconel 2.875 / 9.000 OM 1201-1469 Dissimilar OM 1201-1472 Pipe to Pipe RTE Mounting Boss SB-166 to 690 Drywell WVeld on 2A Hotleg ( Y-Z Axis)Hot Leg (piece 7) to RTE Mounting Boss (piece 12).Per the requirements of 10 CFR 50.55a (g) (6) (ii) (E), all licensees of PWRs shall augment their ISI program implementing ASME .Code Case N-722 subject to the conditions specified in paragraphs (g) (6) (ii) (E) 2 through 4.Bare Metal Visual Inspection by VT-2 qualified inspector per the requirements of applicable item numbers listed in Table 1 of Code Case N-722.Personnel performing the visual examination shall be qualified as VT-2 visual examiners and shall have completed a minimum of four hours of additional training in detection of borated water leakage from alloy 600/82/182 components and the resulting boric acid corrosion of adjacent ferritic steel components.

Procedure NDE 68, Acceptance Criteria is "no evidence of borated water leakage." This B15.210 item is to be examined each refueling outage.For additional information, contact Chris Cruz from the Materials and NDE Services Section, Nuclear Technical Services Division.02.B15.210.0011 2-PHA-15 Class 1 50 ISI-OCN2-005 NDE-68 VT-2 CS-Inconel 2.875 I 9.000 OM 1201-1469 Dissimilar OM 1201-1472 Pipe to Pipe RTE Mounting Boss SB-166 to 690 Drywell Weld on 2A Hotleg (Z-W Axis)Hot Leg (Piece 7) to RTE Mounting Boss (piece 12).Per the requirements of 10 CFR 50.55a (g) (6) (ii) (E), all licensees of PWRs shall augment their ISI program implementing ASME Code Case N-722 subject to the conditions specified in paragraphs (g) (6) (ii) (E) 2 through 4.Bare Metal Visual Inspection by VT-2 qualified inspector per the requirements of applicable item numbers listed in Table 1 of Code Case N-722.Personnel performing the visual examination shall be qualified as VT-2 visual examiners and shall have completed a minimum of four hours of additional training in detection of borated water leakage from alloy 600/82/182 components and the resulting boric acid corrosion of adjacent ferritic steel components.

Procedure NDE 68, Acceptance Criteria is "no evidence of borated water leakage." This B15.210 item is to be examined each refueling outage.For additional information, contact Chris Cruz from the Materials and NDE Services Section, Nuclear Technical Services Division.Printed 07/14/10 Ick8302 v. 06118/09 SDQA Cat "C" Oconee 2 7/14/2010 2:17:26 PM Page 6 of 79 This report includes all changes~rough addendum ONS2-107 Oconee 2, 4th Interval, outage 4 (EOC-24)Summary Num Component ID ISO/DWG Numbers Procedure Insp Req Material Sched Thick/NPS Cal Blocks Componenet ID 2 Class I System Description Comments Category Aug 02.B15.210.0012 2-PHB-13 Class 1 50 ISI-OCN2-006 NDE-68 VT-2 CS-Inconel 2.875 / 9.000 OM 1201-1469 Dissimilar OM 1201-1472 Pipe to Pipe RTE Mounting Boss SB-166 to 690 Drywell Weld on 2B Hotleg ( X Axis) -Hot Leg (Piece 7) to RTE Mounting Boss (piece 12).Per the requirements of 10 CFR 50.55a (g) (6) (ii) (E), all licensees of PWRs shall augment their ISI program implementing ASME Code Case N-722 subject to the conditions specified in paragraphs (g) (6) (ii) (E) 2 through 4.Bare Metal Visual Inspection by VT-2 qualified inspector per the requirements of applicable item numbers listed in Table 1 of Code Case N-722.Personnel performing the visual examination shall be qualified as VT-2 visual examiners and shall have completed a minimum of four hours of additional training in detection of borated water leakage from alloy 600/82/182 components and the resulting boric acid corrosion of adjacent ferritic steel components.

Procedure NDE 68, Acceptance Criteria is "no evidence of borated water leakage." This B15.210 item is to be examined each refueling outage.For additional information, contact Chris Cruz from the Materials and NDE Services Section, Nuclear Technical Services Division.02.B15.210.0013 2-PHB-14 Class 1 50 ISI-OCN2-006 NDE-68 VT-2 CS-Inconel 2.875 / 9.000 OM 1201-1469 Dissimilar OM 1201-1472 Pipe to Pipe RTE Mounting Boss SB-166 to 690 Drywell Weld on 2B Hotleg (Y-Z Axis)Hot Leg (Piece 7) to RTE Mounting Boss (piece 12).Per the requirements of 10 CFR 50.55a (g) (6) (ii) (E), all licensees of PWRs shall augment their ISI program implementing ASME Code Case N-722 subject to the conditions specified in paragraphs (g) (6) (ii) (E) 2 through 4.Bare Metal Visual Inspection by VT-2 qualified inspector per the requirements of applicable item numbers listed in Table 1 of Code Case N-722.Personnel performing the visual examination shall be qualified as VT-2 visual examiners and shall have completed a minimum of four hours of additional training in detection of borated water leakage from alloy 600/82/182 components and the resulting boric acid corrosion of adjacent ferritic steel components.

Procedure NDE 68, Acceptance Criteria is "no evidence of borated water leakage." This B15.210 item is to be examined each refueling outage.For additional information, contact Chris Cruz from the Materials and NDE Services Section, Nuclear Technical Services Division.Printed 07/14/10 Ick8302 v. 06/18/09 SDQA Cat "C" Oconee 2 7/14/2010 2:17:26 PM Page 7 of 79 This report includes all change rough addendum ONS2-107 Oconee 2, 4th Interval, outage 4 (EOC-24)Summary Num Component ID ISO/DWG Numbers Procedure Insp Req Material Sched Thick/NPS Cal Blocks Componenet ID 2 Class I System Description Comments Category Aug 02.B15.210.0014 2-PHB-15 Class 1 50 1S8-OCN2-006 NDE-68 VT-2 CS-Inconel 2.875 / 9.000 OM 1201-1469 Dissimilar OM 1201-1472 Pipe to Pipe RTE Mounting Boss SB-166 to 690 Drywell Weld on 2B Hotleg (Z-W Axis)Hot Leg (Piece 7) to RTE Mounting Boss (piece 12).Per the requirements of 10.CFR 50.55a (g) (6) (ii) (E), all licensees of PWRs shall augment their ISI program implementing ASME Code Case N-722 subject to the conditions specified in paragraphs (g) (6) (ii) (E) 2 through 4.Bare Metal Visual Inspection by VT-2 qualified inspector per the requirements of applicable item numbers listed in Table 1 of Code Case N-722.Personnel performing the visual examination shall be qualified as VT-2 visual examiners and shall have completed a minimum of four hours of additional training in detection of borated water leakage from alloy 600/82/182 components and the resulting boric acid corrosion of adjacent ferritic steel components.

Procedure NDE 68, Acceptance Criteria is "no evidence of borated water leakage." This B15.210 item is to be examined each refueling outage.For additional information, contact Chris Cruz from the Materials and NDE Services Section, Nuclear Technical Services Division.02.B15.210.0015 2SGA-HL-CON-36 Class 1 50 OM-1201-0103.001 NDE-68 VT-2 CS-Inconel 0-ISIN4-100A-2.1 Dissimilar OM-1201-1472.001 RTE Hot Leg Thermal Well Steam Generator A Hot Leg Connection

  1. 36 on drawing OM 1201-0103.001 and Mark # 10 on drawing OM-1201-1472.001.

Abandoned RTE Thermal Well Connection.

Per the requirements of 10 CFR 50.55a (g) (6) (ii) (E), all licensees of PWRs shall augment their ISI program implementing ASME Code Case N-722 subject to the conditions specified in paragraphs (g) (6) (ii) (E) 2 through 4.Bare Metal Visual Inspection by VT-2 qualified inspector per the requirements of applicable item numbers listed in Table 1 of Code Case N-722.Personnel performing the visual examination shall be qualified as VT-2 visual examiners and shall have completed a minimum of four hours of additional training in detection of borated water leakage from alloy 600/82/182 components and the resulting boric acid corrosion of adjacent ferritic steel components.

Procedure NDE 68, Acceptance Criteria is "no evidence of borated water leakage." ThisB15.210 item is to be examined each refueling outage.For additional information, contact Chris Cruz from the Materials and NDE Services Section, Nuclear Technical Services Division.Printed 07/14/10 Ick8302 v. 06/18/09 SDQA Cat "C" Oconee 2 7/14/2010 2:17:26 PM Page 8 of 79 This report includes all change rough addendum ONS2-107 Oconee 2, 4th Interval, outage 4 (EOC-24)Summary Num Component ID ISOIDWG Numbers Procedure Insp Req Material Sched Thick/NPS Cal Blocks ID 2 Class I System Description Comments Category Aug 02.B15.210.0016 2SGB-HL-CON-27 Class 1 50 OM-1201-0103.001 NDE-68 VT-2 CS-Inconel 0-ISIN4-100A-2.1 Dissimilar OM-1201-1472.001 RTE Hot Leg Thermal Well Steam Generator B Hot Leg Connection

  1. 27 on drawing OM 1201-0103.001 and Mark # 10 on drawing OM-1201-1472.001 Abandoned RTE Thermal Well Connection Per the requirements of 10 CFR 50.55a (g) (6) (ii) (E), all licensees of PWRs shall augment their ISI program implementing ASME Code Case N-722 subject to the conditions specified in paragraphs (g) (6) (ii) (E) 2 through 4.Bare Metal Visual Inspection by VT-2 qualified inspector per the requirements of applicable item numbers listed in Table 1 of Code Case N-722.Personnel performing the visual examination shall be qualified as VT-2 visual examiners and shall have completed a minimum of four hours of additional training in detection of borated water leakage from alloy 600/82/182 components and the resulting boric acid corrosion of adjacent ferritic steel components.

Procedure NDE 68, Acceptance Criteria is "no evidence of borated water leakage." This B15.210 item is to be examined each refueling outage.For additional information, contact Chris Cruz from the Materials and NDE Services Section, Nuclear Technical Services Division.02.B15.215.0003 2-PIB1-11 Class 1 50 ISI-OCN2-009 NDE-68 VT-2 CS-Inconel 0.672 / 3.500 B&W146635E Dissimilar Stress Weld Nozzle to Safe End Reactor Coolant Pump 2B1 Suction Piping. Nozzle Pc. 87 to Safe End Pc. 88.Per the requirements of 10 CFR 50.55a (g) (6) (ii) (E), all licensees of PWRs shall augment their ISI program implementing ASME Code Case N-722 subject to the conditions specified in paragraphs (g) (6) (ii) (E) 2 through 4.Bare Metal Visual Inspection by VT-2 qualified inspector per the requirements of applicable item numbers listed in Table 1 of Code Case N-722.Personnel performing the visual examination shall be qualified as VT-2 visual examiners and shall have completed a minimum of four hours of additional training in detection of borated water leakage from alloy 600/82/182 components and the resulting boric acid corrosion of adjacent ferritic steel components.

Procedure NDE 68, Acceptance Criteria is "no evidence of borated water leakage." This item is to be examined once per interval.For additional information, contact Chris Cruz from the Materials and NDE Services Section, Nuclear Technical Services Division.Printed 07/14/10 Ick8302 v. 06/18/09 SDQA Cat "C" Oconee 2 7/14/2010 2:17:26 PM Page 9 of 79 This report includes all changesrough addendum ONS2-107 Oconee 2, 4th Interval, outage 4 (EOC-24)Summary Num Component ID ISO/DWG Numbers Procedure Insp Req Material Sched Thick/NPS Cal Blocks Componenet ID 2 Class I System Description Comments Category Aug 02.B15.215.0004 2-51A-35-15A Class 1 51A 2-51A-35 (1) NDE-68 VT-2 SS-Inconel 0.375 /2.500 O-ISIN4-100A-2.1 Dissimilar Stress Weld Elbow to Pipe Reactor Coolant Pump 2B1 Suction Piping. Nozzle Pc. 87 and Safe End Pc. 88 to elbow weld.Per the requirements of 10 CFR 50.55a (g) (6) (ii) (E), all licensees of PWRs shall augment their ISI program implementing ASME Code Case N-722 subject to the conditions specified in paragraphs (g) (6) (ii) (E) 2 through 4.Bare Metal Visual Inspection by VT-2 qualified inspector per the requirements of applicable item numbers listed in Table 1 of Code Case N-722.Personnel performing the visual examination shall be qualified as VT-2 visual examiners and shall have completed a minimum of four hours of additional training in detection of borated water leakage from alloy 600/82/182 components and the resulting boric acid corrosion of adjacent ferritic steel components.

Procedure NDE 68, Acceptance Criteria is "no evidence of borated water leakage." This item is to be examined once per interval.For additional information, contact Chris Cruz from the Materials and NDE Services Section, Nuclear Technical Services Division.02.B15.215.0007 2-PIB1-7 Class 1 50 ISI-OCN2-009 NDE-68 VT-2 SS-CS 2.330 / 33.500 OM-1 201-966 Dissimilar Stress Weld Pipe to Safe End Reactor Coolant Pump 2B1 Suction Piping. Pipe Pc. 56 to Safe End Pc. 55.Per the requirements of 10 CFR 50.55a (g) (6) (ii) (E), all licensees of PWRs shall augment their ISI program implementing ASME Code Case N-722 subject to the conditions specified in paragraphs (g) (6) (ii) (E) 2 through 4.Bare Metal Visual Inspection by VT-2 qualified inspector per the requirements of applicable item numbers listed in Table 1 of Code Case N-722.Personnel performing the visual examination shall be qualified as VT-2 visual examiners and shall have completed a minimum of four hours of additional training in detection of borated water leakage from alloy 600/82/182 components and the resulting boric acid corrosion of adjacent ferritic steel components.

Procedure NDE 68, Acceptance Criteria is "no evidence of borated water leakage." This item is to be examined once per interval.For additional information, contact Chris Cruz from the Materials and NDE Services Section, Nuclear Technical Services Division.Printed 07/14/10 Ick8302 v. 06/18/09 SDQA Cat "C'" Oconee 2 7/14/2010 2: 17:26 PM Page 10 of 79 This report includes all changesqhrough addendum ONS2-107 Oconee 2, 4th Interval, outage 4 (EOC-24)Summary Num Component ID ISO/DWG Numbers Procedure Insp Req Material Sched Thick/NPS Cal Blocks Componenet ID 2 Class / System Description Comments Category Aug-02.815.215.0008 2-PIB2-7 Class 1 50 ISI-OCN2-010 NDE-68 VT-2 SS-CS 2.330 / 33.500 OM-1201-966 Dissimilar Stress Weld Pipe to Safe End Reactor Coolant Pump 282 Suction Piping. Pipe Pc. 56 to Safe End Pc. 55.Per the requirements of 10 CFR 50.55a (g) (6) (ii) (E), all licensees-of PWRs shall augment their ISI program implementing ASME Code Case N-722 subject to the conditions specified in paragraphs (g) (6) (ii) (E) 2 through 4.Bare Metal Visual Inspection by VT-2 qualified inspector per the requirements of applicable item numbers listed in Table 1 of Code Case N-722.Personnel performing the visual examination shall be qualified as VT-2 visual examiners and shall have completed a minimum of four hours of additional training in detection of borated water leakage from alloy 600/82/182 components and the resulting boric acid corrosion of adjacent ferritic steel components.

" Procedure NDE 68, Acceptance Criteria is "no evidence of borated water leakage." This item is to be examined.once per interval.For additional information, contact Chris Cruz from the Materials and NDE Services Section, Nuclear Technical Services Division.02.815.215.0011 2-PDBI-2 Class 1 50 ISI-OCN2-013 NDE-68 VT-2 SS-CS 2.330 / 33.500 OM-1201-966 Dissimilar Stress Weld Safe End to Elbow Reactor Coolant Pump 281 Discharge Piping. Safe End Pc. 49 to Elbow Pc. 53.Per the requirements of 10 CFR 50.55a (g) (6) (ii) (E), all licensees of PWRs shall augment their ISI program implementing ASME Code Case N-722 subject to the conditions specified in paragraphs (g) (6) (ii) (E) 2 through 4.Bare Metal Visual Inspection by VT-2 qualified inspector per the requirements of applicable item numbers listed in Table 1 of Code Case N-722.Personnel performing the visual examination shall be qualified as VT-2 visual examiners and shall have completed a minimum of four hours of additional training in detection of borated water leakage from alloy 600/82/182 components and the resulting boric acid corrosion of adjacent ferritic steel components.

Procedure NDE 68, Acceptance Criteria is "no evidence of borated water leakage." This item is to be examined once per interval.For additional inf6rmation, contact Chris Cruz from the Materials and NDE Services Section, Nuclear Technical Services Division.Printed 07/14/10 Ick8302 v. 06/18/09 SDQA Cat "C" Oconee 2 7/14/2010 2:17:26 PM Page 11 of 79 This report includes all change rough addendum ONS2-107 Oconee 2, 4th interval, outage 4 (EOC-24)Summary Num Component ID ISO/DWG Numbers Class / System Procedure Insp Req Material Sched Thick/NPS Description Comments Cal Blocks Componenet ID 2 Category Aug 02.1B15.215.0012 Dissimilar Stress Weld 2-PDB2-2 Class 1 50 ISI-OCN2-014 OM-1201-966 NDE-68 VT-2 SS-CS 2.330 / 33.500 Safe End to Elbow Reactor Coolant Pump 2B2 Discharge Piping. Safe End Pc. 49 to Elbow Pc. 53.Per the requirements of 10 CFR 50.55a (g) (6) (ii) (E), all licensees of PWRs shall augment their ISI program implementing ASME Code Case N-722 subject to the conditions specified in paragraphs (g) (6) (ii) (E) 2 through 4.Bare Metal Visual Inspection by VT-2 qualified inspector per the requirements of applicable item numbers listed in Table 1 of Code Case N-722.Personnel performing the visual examination shall be qualified as VT-2 visual examiners and shall have completed a minimum of four hours of additional training in detection of borated water leakage from alloy 600/82/182 components and the resulting boric acid corrosion of adjacent ferritic steel components.

Procedure NDE 68, Acceptance Criteria is "no evidence of borated water leakage." This item is to be examined once per interval.

-.For additional information, contact Chris Cruz from the Materials and NDE Services Section, Nuclear Technical Services Division.02.B15.215.0020 2-PIB2-11 Class 1 50 ISI-B&Y Dissimilar Stress Weld OCN2-010 N146823E NDE-68 VT-2 CS-lnconel 0.816 / 3.500 Nozzle to Safe End Reactor Coolant Pump 2B2 Suction Piping. Nozzle Pc. 64 to Safe End Pc. 65.Per the requirements of 10 CFR 50.55a (g) (6) (ii) (E), all licensees of PWRs shall augment their ISI program implementing ASME Code Case N-722 subject to the conditions specified in paragraphs (g) (6) (ii) (E) 2 through 4.Bare Metal Visual Inspection by VT-2 qualified inspector per the requirements of applicable item numbers listed in Table 1 of Code Case N-722.Personnel performing the visual examination shall be qualified as VT-2 visual examiners and shall have completed a minimum of four hours of additional training in detection of borated water leakage from alloy 600/82/182 components and the resulting boric acid corrosion of adjacent ferritic steel components.

Procedure NDE 68, Acceptance Criteria is "no evidence of borated water leakage." This item is to be examined once per interval.For additional information, contact Chris Cruz from the Materials and NDE Services Section, Nuclear Technical Services Division.This exam was moved from EOC25 to EOC-24 per request from Jay Eaton at Oconee. Chris Cruz was in agreement with the schedule being changed. See Plan Addenda ONS2-102. (See PIP 0-10-2864)

Printed 07/14/10 Ick8302 v. 06/18/09 SDQA Cat "C" Oconee 2 7/14/2010 2:17:26 PM Page 12 of 79 This report includes all changes through addendum ONS2-107 Oconee 2, 4th Interval, outage 4 (EOC-24)Summary Num Component ID ISO/DWG Numbers Procedure Insp Req Material Sched Thick/NPS Cal Blocks Componenet ID 2 Class I System Description Comments Category Aug 02.B15.215.0021 2-50-7-8 Class 1 50 2-50-7 (2) NDE-68 VT-2 SS-Inconel 0.281 / 1.500 0-ISIN4-10OA-2.1 Dissimilar Elbow to Nozzle Reactor Coolant Pump 2B2 Suction Drain Piping.Per the requirements of 10 CFR 50.55a (g) (6) (ii) (E), all licensees of PWRs shall augment their ISI program implementing ASME Code Case N-722 subject to the conditions specified in paragraphs (g) (6) (ii) (E) 2 through 4.Bare Metal Visual Inspection by VT-2 qualified inspector per the requirements of applicable item numbers listed in Table 1 of Code Case N-722.Personnel performing the visual.examination shall be qualified as VT-2 visual examiners and shall have completed a minimum of four hours of additional training in detection of borated water leakage from alloy 600/82/182 components and the resulting boric acid corrosion of adjacent ferritic steel components.

Procedure NDE 68, Acceptance Criteria is "no evidence of borated water leakage." This item is to be examined once per interval.For additional information, contact Chris Cruz from the Materials and NDE Services Section, Nuclear Technical Services Division.This exam was 'rhoved from EOC25 to EOC-24 per request from Jay Eaton at Oconee. Chris Cruz was in agreement with thee schedule being changed. See Plan Addenda ONS2-102. (See PIP 0-10-2864) 02.B15.215.0026 2-PIB1-12 Class 1 50 ISI-OCN2-009 NDE-68 VT-2 CS-Inconel 2.250 / 8.750 OM-1 201-1521 Dissimilar Nozzle to Pipe RTE Mounting Boss Pc.58 to Pipe Pc.56 located on Pump 2B1 Suction Piping.Per the requirements of 10 CFR 50.55a (g) (6) (ii) (E), all licensees of PWRs shall augment their ISI program implementing ASME Code Case N-722 subject to the conditions specified in paragraphs (g) (6) (ii) (E) 2 through 4.Bare Metal Visual Inspection by VT-2 qualified inspector per the requirements of applicable item numbers listed in Table 1 of Code Case N-722.Personnel performing the visual examination shall be qualified as VT-2 visual examiners and shall have completed a minimum of four hours of additional training in detection of borated water leakage from alloy 600/82/182 components and the resulting boric acid corrosion of adjacent ferritic steel components.

Procedure NDE 68, Acceptance Criteria is "no evidence of borated water leakage." This item is to be examined once per interval.For additional information, contact Chris Cruz from the Materials and NDE Services Section, Nuclear Technical Services Division.This exam was moved from EOC26 to EOC-25 per request from Max Hipps at Oconee. Chris Cruz was in agreement with the schedule being changed. See Plan addenda ONS2-101.This exam was moved from EOC25 to EOC-24 per request from Jay Eaton at Oconee. Chris Cruz was in agreement with the schedule being changed. See Plan Addenda ONS2-102. (See PIP 0-10-2864)

Printed 07/14/10 Ick8302 v. 06/18/09 SDQA Cat "C'" Oconee 2 7/14/2010 2:17:26 PM Page 13 of 79 This report includes all changes through addendum ONS2-107 Oconee 2, 4th Interval, outage 4 (EOC-24)Summary Num- Component ID ISO/DWG Numbers Procedure Insp Req Material Sched Thick/NPS Cal Blocks Componenet ID 2 Class I System Description Comments Category Aug 02.B15.215.0027 2-PIB2-12 Class 1 50 ISI-OCN2-010 NDE-68 VT-2 CS-lnconel 2.250 / 8.750 OM-1201-1521 Dissimilar Nozzle to Pipe RTE Mounting Boss Pc.58 to Pipe Pc.56 located on Pump 2B2 Suction Piping.Per the requirements of 10 CFR 50.55a (g) (6) (ii) (E), all licensees of PWRs shall augment their ISI program implementing ASME Code Case N-722 subject to the conditions specified in paragraphs (g) (6) (ii) (E) 2 through 4.Bare Metal Visual Inspection by VT-2 qualified inspector per the requirements of applicable item numbers listed in Table 1 of Code Case N-722.Personnel performing the visual examination shall be qualified as VT-2 visual examiners and shall have completed a minimum of four hours of additional training in detection of borated water leakage from alloy 600/82/182 components and the resulting boric acid corrosion of adjacent ferritic steel components.

Procedure NDE 68, Acceptance Criteria is "no evidence of borated water leakage." This item is to be examined once per interval.For additional information, contact Chris Cruz from the Materials and NDE Services Section, Nuclear Technical Services Division.This exam was moved from EOC26 to EOC-25 per request from Max Hipps at Oconee. Chris Cruz was in agreement with the schedule being changed. See Plan addenda ONS2-101.This exam was moved from EOC25 to EOC-24 per request from Jay Eaton at Oconee. Chris Cruz was in agreement with the schedule being changed. See Plan Addenda ONS2-102. (See PIP 0-10-2864) 02.B15.80.0001 2-RPV-BMI-NOZZLES Class 1 50 NDE-68 VT-2 CS/Alloy 690 0.000 / 0.000 O-ISIN4-100A-2.1 Dissimilar RPV Bottom Head BMI Nozzles Per the requirements of 10 CFR 50.55a(g)(6)(ii)(E), all licensees of PWRs shall augment their ISI program implementing ASME Code Case N-722 subject to the conditions specified in paragraphs (g) (6) (ii) (E) 2 through 4.Bare Metal Visual Inspection by VT-2 qualified inspector of the BMI Nozzles per the requirements of Code Case N-722. (Item Number B15.80).B1 5.80 items, bare metal visual examinations are on the reactor vessel bottom head, bottom mounted instrument nozzles and alloy 600 transition weld between the alloy 600 tube and the stainless steel tube.B1 5.80 items are to be examined every other refueling outage from the start date.Personnel performing the visual examination shall be qualified as VT-2 visual examiners and shall have completed a minimum of four hours of additional training in detection of borated water leakage from alloy 600/82/182 components and the resulting boric acid corrosion of adjacent ferritic steel components.

Procedure NDE 68, Acceptance Criteria is "no evidence of borated water leakage." Procedure NDE-68 in conjunction with MP/O/A/1 150/030 should be used to perform the Bare Metal Visual inspection.

For additional information, contact Chris Cruz from the Materials and NDE Services Section, Nuclear Technical Services Division.Printed 07/14/10 Ick8302 v. 06/18/09 SDQA Cat "C" Oconee,2 7/14/2010 2:17:26 PM Page 14 of 79 This report includes all changestrough addendum ONS2-107 Oconee 2, 4th Interval, outage 4 (EOC-24)Summary Num Category Aug 02.G1.1.0001 Component ID ISO/DWG Numbers Class I System Procedure Insp Req Material Sched Description Comments Thick/NPS Cal Blocks Componenet ID 2 2-RCP-2A1 Class 1 50 OM-201 D-038 O-ISIN4-100A-2.1 NDE-900 UT CS 9.500 / 72.000 Component GO1.001.001, GO1.001.001, RCP 2A1 Flywheel.

Reference Section 7 of the ISI Plan, General Requirements.

--(GO1.001.001A)Whenever maintenance or repair activities necessitate flywheel removal, a surface examination of exposed surfaces and a complete volumetric examination shall be performed if the interval measured from the previous such inspection is greater than 6 2/3 years.02.G1.1.0005 2-RCP-2A2 Class 1 50 OM-201 D-038 0-ISIN4-1 OOA-2.1 NDE-900 UT CS 9.500 / 72.000 Component GO1.001.002, GO1.001.002, RCP 2A2 Flywheel.

Reference Section 7 of the ISI Plan, General Requirements.

-- (GO1.001.002A)

Whenever maintenance or repair activities necessitate flywheel removal, a surface examination of exposed surfaces and a complete volumetric examination shall be performed if the interval measured from the previous such inspection is greater than 6 2/3 years.02.G1.1.0006 2-RCP-2B1 Class 1 50 OM-201 D-038 0-ISIN4-100A-2.1 NDE-900 UT CS 9.500 / 72.000 Component GO1.001.003, GO1.001.003, RCP 2B1 Flywheel.

Reference Section 7 of the ISI Plan, General Requirements.

-- (GO1.001.003A)

Whenever maintenance or repair activities necessitate flywheel removal, a surface examination of exposed surfaces and a complete volumetric examination shall be performed if the interval measured from the previous such inspection is greater than 6 2/3 years.02.G1.1.0007 2-RCP-282 Class 1 50 OM-201 D-038 0-ISIN4-100A-2.1 NDE-900 UT CS 9.500 / 72.000 Component G01 .001.004, GO1.001.004?

RCP 2B2 Flywheel.

Reference Section 7 of the ISI Plan, General Requirements.

-- (GO1.001.004A)

Whenever maintenance or repair activities necessitate flywheel removal, a surface examination of exposed surfaces and a complete volumetric examination shall be performed if the interval measured from the previous such inspection is greater than 6 2/3 years.02.G12.1.0005 Circumferential Dissimilar 2-PDB2-11 Class 1 50 ISI-OCN2-014 B&W146629E O-ISIN4-100A-2.1 PDI-UT-10 UT SS-CS 0.750 / 3.500 40416 Component G12.001.00' Nozzle to Safe End 2B2 HPI Nozzle Pc.46 to Safe End Pc.47. Augmented Inspection Per MRP-139. Contact Jody Shuping for additional information on this examination.

Examination schedule cannot exceed 5 years between examinations.

Printed 07/14/10 Ick8302 v. 06/18/09 SDQA Cat "C" Oconee 2 7/14/2010 2:17:26 PM Page 15 of 79 This report includes all changes through addendum ONS2-107 Oconee 2, 4th Interval, outage 4 (EOC-24)Summary Num Component ID ISO/DWG Numbers Procedure Insp Req Material Sched ThicklNPS Class I System Description Comments Cal Blocks Componenet ID 2 Category Aug 02.G12.2.0001 Circumferential Terminal End Dissimilar 2-RPV-WR53 Class 1 50 ISI-OCN2-001 OM-1201-1528 54-1SI-823 UT SS-CS 1.688 / 15.625 8034675 G12.002.00' Nozzle to Safe End RV A-Side Core Flood Nozzle Pc. 17 to Safe End Pc. 89. W-Axis.Procedure to be used will be determined after a Vendor has been selected to perform the Automated UT examination.

Augmented Inspection Per MRP-1 39. Contact Jody Shuping for additional information on this examination.

Examination schedule cannot exceed 6 years between examinations.

02.G12.2.0002 Circumferential Terminal End Dissimilar 2-RPV-WR53A Class 1 50 ISI-OCN2-001 54-ISI-823 UT SS-CS 1.688 / 15.625 8034675 G12.002.00; OM-1201-1528 Nozzle to Safe End RV B-Side Core Flood Nozzle Pc. 17 to Safe End Pc. 89. Y-Axis.Procedure to be used will be determined after a Vendor has been selected to perform the Automated UT examination.

Augmented Inspection Per MRP-139. Contact Jody.Shuping for additional information on this examination.

Examination schedule cannot exceed 6 years between examinations.

02.G12.2.0005 Circumferential Dissimilar Stress Weld 2-PIA1-7 Class 1 50 ISI-OCN2-007 OM-1201-966 EPRI-DMW-UT PA-1 SS-CS 3.000 / 33.500 40350 40397 G12.002.00,1 Pipe to Safe End Reactor Coolant Pump 2A1 Suction Piping. Pipe Pc. 56 to Safe End Pc. 55: Augmented Inspection Per MRP-1 39. Contact Jody Shuping for additional information on this examination.

Examination schedule cannot exceed 6 years between examinations.

Printed 07/14/10 Ick8302 v. 06/18/09 SDQA Cat "C" Oconee 2 7/14/2010 2:17:26 PM Page 16 of 79 This report includes all change~srough addendum ONS2-107 Oconee 2, 4th Interval, outage 4 (EOC-24)Summary Num Category Aug 02.G12.2.0006 Component ID ISO/DWG Numbers Class I System Procedure Insp Req Material Sched Description Comments Thick/NPS Cal Blocks Componenet ID 2 2-PIA2-7 Class 1 50 lSl-OCN2-008 OM-1201-966 EPRI-DMW-UT PA-1 SS-CS 2.330 / 33.500 40350 40397 G12.002.00(Circumferential Dissimilar Stress Weld Pipe to Safe End Reactor Coolant Pump 2A2 Suction Piping. Pipe Pc, 56 to Safe End Pc. 55.Augmented Inspection Per MRP-1 39. Contact Jody Shuping for additional information on this examination.

Examination schedule cannot exceed 6 years between examinations.

02.G12.2.0007 Circumferential Dissimilar Stress Weld 2-PIB1-7 Class 1 50 ISI-OCN2-009 OM-1201-966 EPRI-DMW-UT PA-1 SS-CS 2.330 / 33.500 40350 40397 G12.002.00, Pipe to Safe End Reactor Coolant Pump 211 Suction Piping. Pipe Pc. 56 to Safe End Pc. 55.Augmented Inspection Per MRP-1 39. Contact Jody Shuping for additional information on this examination.

Examination schedule cannot exceed 6 years between examinations.

02.G12.2.0008 Circumferential Dissimilar.

Stress Weld 2-PIIB2-7 Class 1 50 ISI-OCN2-010 OM-1 201-966 EPRI-DMW-UT PA-1 SS-CS 2.330/ 33.500 40350 40397 G12.002.00O Pipe to Safe End Reactor Coolant Pump 2B2 Suction Piping. Pipe Pc. 56 to Safe End Pc. 55.Augmented Inspection Per MRP-139. Contact Jody Shuping for additional information on this examination.

Examination schedule cannot exceed 6 years between examinations.

Printed 07/14/10 Ick8302 v. 06118109 SDQA Cat "C" Oconee 2 7/14/2010 2:17:26 PM Page 17 of 79 Thisreport includes all change~sro~ugh addendum ONS2-107 Oconee 2, 4th Interval, outage 4 (EOC-24)Summary Num Component ID ISOIDWG Numbers Class I System Procedure Insp Req Material Sched Description Comments Thick/NPS Cal Blocks Componenet ID 2 Category Aug 02.G12.2.0009 Circumferential Dissimilar Stress Weld 2-PDA1-2 Class 1 50 ISI-OCN2-011 OM-1201-966 EPRI-DMW-UT PA-1 SS-CS 2.330 / 33.500 40350 40397 G12.002.00, Safe End to Elbow Reactor Coolant Pump 2A1 Discharge Piping. Safe End Pc. 49 to Elbow Pc. 53.Augmented Inspection Per MRP-139. Contact Jody Shuping for additional information on this examination.

Examination schedule cannot exceed 6 years between examinations.

02.G12.2.0010 2-PDA2-2 Class 1 50 ISI-OCN2-012 OM-1201-966 EPRI-DMW-UT PA-1 SS-CS 2.330/ 33.500 40350 40397 G12.002.01(Circumferential Dissimilar Stress Weld Safe End to Elbow Reactor Coolant Pump 2A2 Discharge Piping. Safe End Pc. 49 to Elbow Pc. 53.Augmented Inspection Per MRP-1 39. Contact Jody Shuping for additional information on this examination.

Examination schedule cannot exceed 6 years between examinations.

02.G12.2.0011 Circumferential Dissimilar Stress Weld 2-PDB 1-2 Class 1 50 ISI-OCN2-013 OM-1201-966 EPRI-DMW-UT PA-1 SS-CS 2.330/ 33.500 40350 40397 G12.002.01' Safe End to Elbow Reactor Coolant Pump 281 Discharge Piping. Safe End Pc. 49 to Elbow Pc. 53.Augmented Inspection Per MRP-1 39. Contact Jody Shuping for additional information on this examination.

Examination schedule cannot exceed 6 years between examinations.

SDQA Cat "C" Oconee 2 7/14/2010 2:17:26 PM Page 18 of 79 Printed 07/14/10 Ick8302 v. 06/18/09 This report includes all chang rough addendum ONS2-107 Oconee 2, 4th Interval, outage 4 (EOC-24)Summary Num Component ID ISO/DWG Numbers Procedure Insp Req Material Sched ThickINPS Cal Blocks Componenet ID 2 Class / System Description Comments Category Aug -_02.G12.2.0012 2-PDB2-2 Class 1 50 ISI-OCN2-014 EPRI-DMW-UT SS-CS 2.330 / 33.500 40350 G12.002.01; OM-1201-966 PA-1 40397 Circumferential Dissimilar Stress Weld Safe End to Elbow Reactor Coolant Pump 2B2 Discharge Piping. Safe End Pc. 49 to Elbow Pc. 53.Augmented Inspection Per MRP-139. Contact Jody Shuping for additional information on this examination.

Examination schedule cannot exceed 6 years between examinations.

02.G14.1.0001 2-PZR-THERM Class 1 50 NDE-68 VT-2 CS-Inconel 0.250 / 1.000 G14.001.00" Circumferential OM 1201-1135 Dissimilar OM 100-1189 Nozzle to Elbow 1.5 inch Thermowell located on the Pressurizer.

Augmented Inspection Per Oconee Response to BL-2004-01.

Contact Jody Shuping for additional information on this examination.

Bare Metal Visual Examinations are to be performed each refueling outage by a VT-2 qualified inspector.

Acceptance criteria is"no evidence of borated water leakage." 02.G16.1.0001 2-50-7-8 Class 1 50 2-50-7 (2) NDE-995 UT SS-Inconel 0.281 / 1.900 50202 O-ISIN4-100A-2.1 Component Dissimilar ISI-OCN2-010 Elbow to Nozzle Reactor Coolant Pump 2B2, Suction Piping (J-Leg), Safe End Pc. 65 to Elbow.Augmented Inspection by ultrasonic examination to identify thermal fatigue cracking on the inside surface of RCS drain line piping downstream of the RCS connection on 2B2 cold leg. This examination is for weld 2-50-7-8.

See Figure 1 in procedure NDE-995 for details on the areas to be examined for this weld.NRC Commitment for MRP-146 requires an ultrasonic examination to identify thermal fatigue cracking on the inside surface of RCS drain line piping downstream of the RCS connection.

Examination includes both welds (located at each end of the elbow)and the elbow base metal. Procedure NDE-995 shall be used to perform the UT examination.

For additional information, contact Dave Peltola from the Oconee Civil Engineering Section.The welds/areas for G16.1 items are to-be examined once every ten years from the start date (Unit 2 EOC-24). The examinations should be performed during refueling outage. See QA-513-J form with tracking number ER-ONS-08-09 for more details.Printed 07/14/10 Ick8302 v. 06/18/09 SDQA Cat "C" Oconee 2 7/14/2010 2:17:26 PM Page 19 of 79 This report includes all chang rough addendum ONS2-107 Oconee 2, 4th Interval, outage 4 (EOC-24)Summary Num Component ID ISO/DWG Numbers Procedure Insp Req Material Sched Thick/NPS Cal Blocks Componenet ID 2 Class / System Description Comments Category Aug 02.G16.1.0002 2-50-7-9 Class 1 50 2-50-7 (2) NDE-995 UT SS 0.281 /1.900 50202 O-ISIN4-100A-2.1 Component Elbow to Pipe Drain Line Piping that branches off of Reactor Coolant Pump 2B2 Suction Piping (J-Leg). On weld iso 2-50-7(2) examine weld #9.Augmented Inspection by ultrasonic examination to identify thermal fatigue cracking on the inside surface of RCS drain line piping downstream of the RCS connection on 2B2 cold leg. This examination is for weld 2-50-7-9.

See Figure 1 in procedure NDE-995 for details on the areas to be examined for this weld.D NRC Commitment for MRP-146 requires an ultrasonic examination to identify thermal fatigue cracking on the inside surface of RCS drain line piping downstream of the RCS connection.

Examination includes both welds (located at each end of the elbow)and the elbow base metal. Procedure NDE-995 shall be used to perform the UT examination.

For additional information, contact Dave Peltola from the Oconee Civil Engineering Section.The welds/areas for G16.1 items are to be examined once every ten years from the start date (Unit 2 EOC-24). The examinations should be performed during refueling outage. See QA-513-J form with tracking number ER-ONS-08-09 for more details.02.G16.1.0003 2-50-7-ELBOW Class 1 50 2-50-7 (2) NDE-995 UT SS 0.281 /1.900 50202 O-ISTN4-1 OOA-2.1 Component Dissimilar Elbow Base Metal Drain Line Piping that branches off of Reactor Coolant Pump 282 Suction Piping (J-Leg) .On weld iso 2-50-7(2) examine the elbow base metal on the elbow associated with welds 8 and 9.Augmented Inspection by ultrasonic examination to identify thermal fatigue cracking on the inside surface of RCS drain line piping downstream of the RCS connection on 282 cold leg. This examination is for the elbow base metal on the elbow associated with welds 8 and 9. See Figure 5 in procedure NDE-995 for details on the areas to be examined for this elbow.J[NRC Commitment for MRP-146 requires an ultrasonic examination to identify thermal fatigue cracking on the inside surface of RCS drain line piping downstream of the RCS connection.

Examination includes both welds (located at each end of the elbow)and the elbow base metal. Procedure NDE-995 shall be used to perform the UT examination.

For additional information, contact Dave Peltola from the Oconee Civil Engineering Section.The welds/areas for G16.1 items are to be examined once every ten years from the start date (Unit 2 EOC-24). The examinations should be performed during refueling outage. See QA-513-J form with tracking number ER-ONS-08-09 for more details.Printed 07/14/10 Ick8302 v. 06/18/09 SDQA Cat "C" Oconee 2 7/14/2010 2:17:26 PIM Page 20 of 79 This report includes all changesthrough addendum ONS2-107.Oconee 2, 4th Interval, outage 4 (EOC-24)Summary Num 2 Component ID ISO/DWG Numbers Class I System Procedure Insp Req Material Sched Thick/NPS Description Comments Cal Blocks Componenet

[0 2 Category Aug 02.G2.1.0001 2-PDB1-46 Class 1 50 ISI-OCN2-013 B&W146629E NDE-680 UT CS 2.500 / 3.500 40410 40350 G02.001.005C 0-ISIN4-100A-2.1 2B1 HPI Nozzle Pc.46. Perform UT on the nozzle inside radius (knuckle area). Reference Section 7 of the ISI Plan, General Requirements.

This schedule cannot be changed without Engineering approval.02.G2.1.0002 2-PDA2-46 Class 1 50 ISI-OCN2-012 B&W146629E NDE-680 UT CS 2.500 / 3.500 40410 40350 G02.001.005E 0-ISIN4-100A-2.1 2A2 Make-Up Nozzle Pc.46. Perform UT on the nozzle inside radius (knuckle area). Reference Section 7 of the ISI Plan, General Requirments.

This schedule cannot be changed without Engineering approval.02.G2.1.0003 2-PDA1-46 Class 1 50 ISI-OCN2-011 B&W146629E NDE-680 UT CS 2.500 / 3.500 .40410 40350 G02.001.005i 0-ISIN4-100A-2.1 2A1 Make-Up Nozzle Pc.46. Perform UT on the nozzle inside radius (knuckle area). Reference Section 7 of the ISI Plan, General Requirements.

This schedule cannot be changed without Engineering approval.02.G2.1.0004 2-PDB2-46 Class 1 50 ISI-OCN2-014 B&W146629E NDE-680 UT CS-2.500 / 3.500 40410 40350 G02.001.005E O-ISIN4-100A-2.1 2B2 HPI Nozzle Pc.46. Perform UT on the nozzle inside radius (knuckle area). Reference Section 7 of the ISI Plan, General Requirements.

This schedule cannot be changed without Engineering approval.02.G2.1.0005 Circumferential Dissimilar 2-PDAl-11 Class 1 50 ISI-OCN2-011 B&W146629E 0-ISIN4-10OA-2.1 PDI-UT-10 UT SS-CS 0.750 / 3.500 40416 G02.001.006, Nozzle to Safe End 2A1 Make-Up Nozzle Pc.46 to Safe End Pc.47. Perform UT on the nozzle to safe end weld. Reference Section 7 of the tSI Plan, General Requirements.

This schedule cannot be changed without Engineering approval.This weld was cut out and welded back in EOC-20. The new weld is also listed as weld 29 on rev .11 of iso 2RC-204.Printed 07/14/10 Ick8302 v. 06/18/09 SDQA Cat "C" Oconee 2 7/14/2010 2:17:26 PM Page 21 of 79 This report includes all change~strough addendum ONS2-107 Oconee 2, 4th Interval, outage 4 (EOC-24)0 Summary Num Component ID ISO/DWG Numbers Class I System Procedure Insp Req Material Sched Thick/NPS Description Comments Cal Blocks Componenet ID 2 Category Aug 02.G2.1.0006 Circumferential Dissimilar 2-PDA2-11 Class 1 50 ISI-OCN2-012 B&W146629E 0-IS 1N4-100A-2.1 PDI-UT-10 UT SS-CS 0.750 / 3.500 40416 G02.001.006E Nozzle to Safe End 2A2 Make-Up Nozzle Pc.46 to Safe End Pc.47. Perform UT on the nozzle to safe end weld. Reference Section 7 of the ISI Plan, General Requirements.

This schedule cannot be changed without Engineering approval..

This weld was cut out and welded back in EOC-20. The new weld is also listed as weld 22 on rev .10 of iso 2RC-203.02.G2.1.0007 Circumferential Dissimilar 2-PDB2-11 Class 1 50 ISI-OCN2-014 B&W146629E 0-ISlN4-100A-2.1 PDI-UT-10 UT SS-CS 0.750 / 3.500 40416 G02.001.006E Nozzle to Safe End 2B2 HPI Nozzle Pc.46 to Safe End Pc.47. Perform UT on the nozzle to safe end weld. Reference Section 7 of the ISI Plan, General Requirements.

This schedule cannot be changed without Engineering approval.02.G2.1.0008 Circumferential Dissimilar 2-PDB1-11 Class 1 50 ISI-OCN2-013 B&W146629E 0-ISIN4-100A-2.1 PDI-UT-10 UT SS-CS 0.750 / 3.500 40416 G02.001.006C Nozzle to Safe End 2B1 HPI Nozzle Pc.46 to'Safe End Pc.47. Perform UT on the nozzle to safe end weld.This weld was cut out and welded back in EOC-20.. The new weld is also listed as weld 16 on rev .8 of iso 2RC-202.Reference Section 7 of the ISI Plan, General Requirements.

This schedule cannot be changed without Engineering approval.02.G2.1.0009 2-PDB1-47 Class 1 50-ISI-OCN2-013 B&W146629E 0-ISIN4-10OA-2.1 PDI-UT-10 UT SS 0.750/3.500 40416 G02.001.007C Safe End Pc.47 adjoining HPI Nozzle 281. Perform UT on the Safe End base metal (between the nozzle to safe end weld and the safe end to pipe weld). Reference Section 7 of the ISI Plan, General Requirements.

This schedule cannot be changed without Engineering approval.Printed 07/14/10 lck8302 v. 06/18/09 SDQA Cat "C" Oconee 2 7/14/2010 2:17:26 PM Page 22 of 79 This report includes all changeshrough addendum ONS2-107 Oconee 2, 4th Interval, outage 4 (EOC-24)Summary Num Category Aug 02.G2.1.0010 Component ID ISO/DWG Numbers Class I System Procedure Insp Req Material Sched Thick/NPS Description Comments Cal Blocks Componenet ID 2 2-PDB2-47 Class 1 50 ISI-OCN2-014 B&W146629E 0-ISIN4-10OA-2.1 PDI-UT-10 UT SS 0.750 / 3.500 40416 G02.001.007E Safe End Pc.47 adjoining HPI Nozzle 282. Perform UT on the Safe End base metal (between the nozzle to safe end weld and the safe end to pipe weld). Reference Section 7 of the ISI Plan, General Requirements.

This schedule cannot be changed without Engineering approval.02.G2A1.0011 2-PDA1-47 Class 1 50 ISI B&0-1-OCN2-011 W146629E ISIN4-100A-2.1 PDI-UT-10 UT SS 0.750 / 3.500 40416 G02.001.007/

Safe End Pc.47 adjoining Make-Up Nozzle 2A1. Perform UT on the Safe End base metal (between the nozzle to safe end weld and the safe end to pipe weld). Reference Section 7 of the iSI Plan, General Requirements.

This schedule cannot be changed without Engineering approval.02.G2.1.0012 2-PDA2-47 Class 1 50 ISI-OCN2-012 B&W146629E 0-ISIN4-100A-2.1 PDI-UT-10 UT SS 0.750 / 3.500 40416 G02.001.007E Safe End Pc.47 adjoining Make-Up Nozzle 2A2. Perform UT on the Safe End base metal (between the nozzle to safe end weld and the safe end to pipe weld). Reference Section 7 of the ISI Plan, General Requirements.

This schedule cannot be changed without Engineering approval.02.G2.1.0013 Circumferential 2RC-204-37 Class 1 50 2RC-204 B&W146629E O-ISIN4-100A-2.1 NDE-995 UT SS 0.375 / 2.500 Component 40378 G02.001 .008i Safe End to Pipe Make-Up Nozzle 2A1. Perform UT on weld 2RC-204-31 and adjoining base metal out to weld 2RC-204-20 (at valve 2HP-127).Weld 2RC-204-18 was cut out and replaced with weld 2RC-204-28 during EOC-20.Weld 2RC-204-28 was cut out and replaced with weld 2RC-204-37 during EOC-23.Reference Section 7 of the ISI Plan, General Requirements.

This schedule cannot be changed without Engineering approval.Note: The inspection performed for this G02 item number will satisfy the requirements for G04.001 .029(02.G4.1.0024).

Printed 07/14/10 lck8302 v. 06/18/09 SDQA Cdt "C" Oconee 2 7/14/2010 2:17:26 PM Page 23 of 79

  • This report includes all change~s rough addendum ONS2-107 Oconee 2, 4th Interval, outage 4 (EOC-24)Summary Num Component ID ISO/DWG Numbers Procedure Insp Req Material Sched Thick/NPS Cal Blocks Componenet ID 2 Class I System Description Comments Category Aug 02.G2.1.0014 2RC-202-17 Class 1 50 2RC-202 NDE-995 UT SS 0.375 / 2.500 Component G02.001.008C B&W146629E 40378 Circumferential O-ISIN4-100A-2.1 Safe End to Pipe HPI Nozzle 2B1. Perform UT on weld 2RC-202-17 and adjoining base metal out to weld,2RC-202-19 (at valve 2HP-153).Reference Section 7 of the ISI Plan, General Requirements.

Weld 2RC-202-1 was cut out and replaced with weld 2RC-202-17 during EOC-20.This schedule cannot be changed without Engineering approval Note: The inspection performed for this G02 item number will satisfy the requirements for G04.001.001.

02.G2.1.0015 2RC-203-32 Class 1 50 2RC-203 NDE-995 UT SS 0.375 / 2.500 Component.

G02.001.008E B&W146629E 40378 Circumferential 0-ISIN4-100A-2.1 Safe End to Pipe Make-Up Nozzle 2A2. Perform UT on weld 2RC-203-31 and adjoining base metal out to weld 2RC-203-3 (at valve 2HP-126).Reference Section 7 of the ISI Plan, General Requirements.

This schedule cannot be changed without Engineering approval.Weld 2RC-203-2 was cut out and replaced with weld 2RC-203-21 during EOC-20.Weld 2RC-203-21 was cut out and replaced with weld 2RC-203-32 during EOC-23.'Note: The inspection performed for this G02 item number will satisfy the requirements for G04.001.027(Summary Number 02.G4.1.0022).

02.G2.1.0016 2RC-205-1 Class. 1 50 2RC-205 NDE-995 UT SS 0.375 / 2.500 Component G02.001.0081 B&W146629E 40378 Circumferential 0-ISIN4-100A-2.1 Safe End to Pipe HPI Nozzle 282. Perform UT on weld 2RC-205-1 and adjoining base metal out to weld 2RC-205-3 (at valve 2HP-152).Reference Section 7 of the ISI Plan, General Requirements.

This schedule cannot be changed without Engineeringapproval.

Note: The inspection performed for this G02item number will satisfy the requirements for G04.001.004.

Printed 07/14/10 lck8302 v. 06/18/09 SDQA Cat "C" Oconee 2 7/14/2010 2:17:26 PM Page 24 of 79 This report includes all changestrough addendum ONS2-107 Oconee 2, 4th Interval, outage 4 (EOC-24)Summary Num Component ID ISO/DWG Numbers Procedure Insp Req Material Sched Thick/NPS Cal Blocks Componenet ID 2 Class I System Description Comments )Category Aug 02.G2.1.0017 2RC-203-3 Class 1 50 2RC-203 NDE-995 UT SS 0.375 / 2.500 Component G02.001.01OE B&W146629E 40378 Circumferential 0-ISIN4-10OA-2.1 Pipe to Valve Make-Up Nozzle 2A2. Perform UT on weld 2RC-203-3 at valve 2HP-126. Reference Section 7 of the ISI Plan, General Requirements.-

This schedule cannot be changed without Engineering approval.Note: The inspection performed for this G02 item number will satisfy the requirements for G04.001.028.

02.G2.1.0018 2RC-202-19 Class 1 50 2RC-202 NDE-995 UT SS 0.375 / 2.500 Component G02.001.010C B&W146629E 40378 Circumferential 0-ISIN4-100A-2.1 Pipe to Valve HPI Nozzle 2B1. Perform UT on weld 2RC-202-19 at valve 2HP-153. Reference Section 7 of the ISI Plan, General Requirements.

This schedule cannot be chan'ged without Engineering approval.Weld 2RC-202-3 was cut out and replaced with weld 2RC-202-19 during EOC-20.Note: The inspection performed for this G02 item number will satisfy the requirements for G04.001.003.

02.G2.1.0019 2RC-204-20 Class 1 50 2RC-204 NDE-995 UT SS 0.375 / 2.500 Component G02.001.0101 B&W146629E 40378 Circumferential 0-ISIN4-100A-2.1 Pipe to Valve Make-Up Nozzle 2A1. Perform UT on weld 2RC-204-20 at valve 2HP-127. Reference Section 7 of the ISI Plan, General Requirements.

This schedule cannot be changed without Engineering approval.Note: The inspection performed for this G02 item number will satisfy the requirements for G04.001 .030.02.G2.1.0020 2RC-205-3 Class 1 50 2RC-205 NDE-995 UT SS 0.375 / 2.500 Component G02.001.010E B&W146629E 40378 Circumferential 0-ISIN4-100A-2.1 Pipe to Valve HPI Nozzle 2B2. Perform UT on weld 2RC-205-3 at valve 2HP-1 52. Reference Section 7 of the ISI Plan, General Requirements.

This schedule cannot be changed without Engineering approval.Note: The inspection performed for this G02 item number will satisfy the requirements for G04.001.006.

Printed 07/14/10 Ick8302 v. 06/18/09 SDQA Cat "C" Oconee 2 7/14/2010 2:17:26 PM Page 25 of 79 This report includes all changes through addendum ONS2-107 Oconee 2, 4th Interval, outage 4 (EOC-24)Summary Num Component ID ISO/DWG Numbers Class I System Procedure Insp Req Material Sched Description Comments Thick/NPS Cal Blocks Componenet ID 2 Category Aug 02.G2.1.0021 Circumferential 2A2 THERM-SLEEVE Class 1 50 ISI OCN2-012 B&W146629E 0-ISIN4-100A-2.1 NDE-105 RT SS 0.750 / 3.500 G02.001.011F Make-Up Nozzle 2A2. Perform RT between the nozzle to safe end and safe end to pipe weld in the thermal sleeve expansion area as described in Procedure NDE-105. Reference Section 7 of the ISI Plan, General Requirements.

This schedule cannot be changed without Engineering approval.02.G2.1.0022 Circumferential 2B1 THERM-SLEEVE Class 1 50 SI OCN2-013 B&W146629E 0-ISIN4-100A-2.1 NDE-105 RT SS 0.750 / 3.500 G02.001.011C HPI Nozzle 2131. Perform RI between the nozzle to safe end and safe end to pipe weld in the thermal sleeve expansion area as described in Procedure NIJE-lOS.

Reference Section 7 of the ISI Plan, General Requirements.

This schedule cannot be changed without Engineering approval.

______02.G2.1.0023 Circumferential

.-2A1 THERM-SLEEVE Class 1 50 ISI OCN2-011 B&W146629E 0-ISIN4-100A-2.1 NDE-105 RT SS 0.750 / 3.500 G02.001.011/

Make-Up Nozzle 2A1. Perform RT between the nozzle to safe end and safe end to pipe weld in the thermal sleeve expansion area as described in Procedure NDE-105. Reference Section 7 of the ISI Plan, General Requirements.

This schedule cannot be changed without Engineering approval.02.G2.1.0024 Circumferential 2B2 THERM-SLEEVE Class 1 50 ISI OCN2-014 B&W146629E 0-ISIN4-100A-2.1 NDE-105 RT SS 0.750 / 3.500 G02.001.011E HPI Nozzle 2B32. Perform RT between the nozzle to safe end and safe end to pipe weld in the thermal sleeve expansion area as described in Procedure NDE-105. Reference Section 7 of the ISI Plan, General Requirements.

This schedule cannot be changed without Engineering approval.02.G4.1.0001 Circumferential 2RC-202-17 Class 1 51A 2RC-202 0-ISIN4-10OA-2.1 NDE-995 UT SS 0.375 / 2.500 Component 40378 G04.001.00' Pipe to Safe End Inspect 100% of weld &V of base material (axial & circumferential).

This weld was listed previously as 2-51A-39-90C until iso 2-51A-39 was redrawn. Reference Section 7 of the ISI Plan, General Requirements.

Weld 2RC-202-1 was cut out and replaced with weld 2RC-202-17 during EOC-20.Note: The inspection performed for G02.001.008C will satisfy the requirements for this G04 inspection.

Printed 07/14/10 Ick8302 v. 06/18/09 SDQA Cat "C" Oconee 2 7/14/2010 2:17:26 PM Page 26 of 79 S This report includes all changestrough addendum ONS2-107 Oconee 2, 4th Interval, outage 4 (EOC-24)Summary Num Component ID ISO/DWG Numbers Class / System Procedure Insp Req Material Sched Description Comments Thick/NPS Cal Blocks Componenet ID 2 Category Aug 02.G4.1.0002 2RC-202-19 Class 1 51A 2RC-202 NDE-995 UT SS 0.375 /2.500 Component G04.001.00" 0-ISIN4-101A-2.4 40378 Circumferential Pipe to Valve 2HP-153 Inspect 100% of weld &1" of base material (axial & circumferential).

This weld was listed previously as 2-51A-39-91 until iso 2-51A-39 was redrawn. Reference Section 7 of the ISI Plan, General Requirements.

Weld 2RC-202-3 was cut out and replaced with weld 2RC-202-19 during EOC-20.Note: The inspection performed for G02.001.010C will satisfy the requirements for this G04 inspection.

02.G4.1.0003 2RC-205-1 Class 1 51A 2RC-205 0-ISIN4-100A-2.1 NDE-995 UT SS 0.375 / 2.500 Component 40378 G04.001 .00z Circumferential Pipe to Safe-End Inspect 100% of weld &1" of base material (axial & circumferential).

This weld was listed previously as 2-51A-39-92A until iso 2-51A-39 was redrawn. Reference Section 7 of the ISI Plan, General Requirements.

Note: The inspection performed for G02.001.008D will satisfy the requirements for this G04 inspection.

02.G4.1.0004 Circumferential 2RC-205-3 Class 1 51A 2RC-205 0-ISIN4-101A-2.4 NDE-995 UT SS 0.375 / 2.500 Component 40378 G04.001.0OE Pipe to Valve 2HP-152 Inspect 100% of weld &1" of base material (axial & circumferential).

This weld was listed previously as 2-51A-39-93 until iso 2-51A-39 was redrawn. Reference Section 7 of the ISI Plan, General Requirements.

Note: The inspection performed for G02.001 .010OD will satisfy the requirements for this G04 inspection.

02.G4.1.0005 Circumferential 2HP-218-18 Class 1 51A 2HP-218 0-ISIN4-101A-2.4 NDE-995 UT SS 0.375 / 2.500 Component 40378 G04.001.00; I Elbow to Pipe Inspect 100% of weld &1" of base material (axial & circumferential).

This weld was listed previously as 2-51A-27-73 until iso 2-51A-27 (2) was redrawn.Reference Section 7 of the ISI Plan, General Requirements.

Hanger 51A-0-1 479A-H 1 3B' needs to be moved in order to perform the examination for 02.G4.1.0005.

Printed 07/14/10 Ick8302 v. 06/18/09 SDQA Cat "C" Oconee 2 7/14/2010 2:17:26 PM Page 27 of 79 This report includes all change rough addendum ONS2-107 Oconee 2, 4th Interval, outage 4 (EOC-24)Summary Num Category Aug 02.G4.1.0006 Circumferential Component ID ISO/DWG Numbers Procedure Insp Req Material Sched Class /System Description Comments Thick/NPS Cal Blocks Componenet ID 2 2HP-214-13 Class 1 51A 2HP-214 0-ISIN4-101A-2.4 NDE-995 UT SS 0.375 / 2.500 Component 40378 G04.001.01(Pipe to Elbow Inspect 100% of weld &1" of base material (axial & circumferential).

This weld was listed. previously~as 2-51A-27-108 until iso 2-51A-27 (3) was redrawn. Reference Section 7 of the ISI Plan, General Requirements.

02.G4.1.0007 Circumferential I 2HP-214-15 Class 1 51A 2HP-214 0-ISIN4-101A-2.4 NDE-995 UT SS 0.375 / 2.500 Componient 40378 G04.001.01' Pipe to Valve 2HP-488 Inspect 100% of weld & 1" of base material (axial & circumferential).

This weld was originally 2-51A-27-110.

It was cut out during outage 15 and replaced as 2HP-214-15.

Reference Section 7 of the ISI Plan, General Requirements.

02.G4.1.0008 Circumferential 2RC-202-4 Class 1 51A 2RC-202 0-ISIN4-101A-2.4 NDE-12 RT SS 0.375 / 2.500 G04.001.01, Valve 2HP-488 to Valve 2HP-153 Use Procedure NDE-995 to perform a circumferential scan of the weld and half of an inch of base metal on each side of the weld as access permits.Use procedure NDE-1 2 to perform RT on 100% of the weld and a quarter of an inch of base metal on each side of the weld.See PIP # 0-99-02157 and PIP # 0-01-04673 for examination methods and area of coverage for this item number.02.G4.1.0008 Circumferential 2RC-202-4 Class 1 51A 2RC-202 0-ISIN4-101A-2.4 NDE-995 UT SS 0.375 / 2.500 Component 40378 G04.001 .01" Valve 2HP-488 to Valve 2HP-153 Use Procedure NDE-995 to perform a circumferential scan of the weld and half of an inch of base metal on each side of the weld as access permits.Use procedure NDE-12 to perform RT on 100% of the weld and a quarter of an inch of base metal on each side of the weld.See PIP # 0-99-02157 and PIP # 0-01-04673 for examination methods and area of coverage for this item number.Printed 07/14/10 Ick8302 v. 06/18/09 SDQA Cat "C" Oconee 2 7/14/2010 2:17:26 PM Page 28 of 79 0 This report includes all changeqrough addendum.

ONS2-107 Oconee 2, 4th Interval, outage 4 (EOC-24)Summary Num Component ID ISO/DWG Numbers Class I System Procedure Insp Req Material Sched ThickINPS Description Comments Cal Blocks Componenet ID 2 Category Aug 02.G4.1.0009 Circumferential 2RC-203-4 Class 1 51A 2RC-203 0-ISIN4-101A-2.4 NDE-12 RT SS 0.375 / 2.500 G04.001.01O Valve 2HP-486 to Valve 2HP-126 Use Procedure NDE-995 to perform a circumferential scan of the weld and half of an inch of base metal on each side of the weld as access permits.Use procedure NDE-12 to perform RT on 100% of the weld and a quarter of an inch of base metal on each side of the weld.See PIP # 0-99-02157 and PIP # 0-01-04673 for examination methods and area of coverage for this item number.02.G4.1.0009 Circumferential 2RC-203-4 Class 1 51A 2RC-203 0-ISIN4-101A-2.4 NDE-995 UT SS 0.375 / 2.500 Component 40378 G04.001.01, Valve 2HP-486 to Valve 2HP-126 Use Procedure NDE-995 to perform a circumferential scan of the weld and half of an inch of base metal on each side of the weld as access permits.Use procedure NDE-1 2 to perform RI on 100% of the weld and a quarter of an inch of base metal on each side of the weld.See PIP # 0-99-02157 and PIP # 0-01 -04673 for examination methods and area of coverage for this item number.02.G4.1.0010 Circumferential 2RC-204-4 Class 1 51A 2RC-204 0-ISIN4-101A-2.4 NDE-12 RT SS 0.375 / 2.500 G04.001.01!

Valve 2HP-487 to Valve 2HP-127 Use Procedure NDE-995 to perform a circumferential scan of the weld and half of an inch of base metal on each side of the weld as access permits.Use procedure NDE-12 to perform RT on 100% of the weld and a quarter of an inch of base metal on each side of the weld.See PIP # 0-99-02157 and PIP # 0-01-04673 for examination methods and area of coverage for this item-number.

02.G4.1.0010 Circumferential 2RC-204-4 Class 1 51A 2RC-204 O-ISIN4-101A-2.4 NDE-995 UT SS 0.375 / 2.500 Component 40378 G04.001.01!

Valve 2HP-487 to Valve 2HP-127*Use Procedure NDE-995 to perform a circumferential scan of the weld and half of an inch of base metal on each side of the weld as access permits.Use procedure NDE-12 to perform RT on 100% of the weld and-a quarter of an inch of base metal on each side-of the weld.See PIP # 0-99-02157 and PIP # 0-01-04673 for examination methods and area of coverage for this item number.Printed 07/14/10 Ick8302 v. 06/18/09 SDQA Cat "C" Oconee 2 7/14/2010 2:17:26 PM Page 29 of 79 S This report includes all changes through addendum ONS2-107 Oconee 2, 4th Interval, outage 4 (EOC-24)Summary Num Component ID ISO/DWG Numbers Class I System Procedure Insp Req Material Sched Thick/NPS Description Comments Cal Blocks Componenet ID 2 Category Aug 02.G4.1.0011 Circumferential 2RC-205-4 Class 1 51A 2RC-205 0-ISIN4-101A-2.4 NDE-12 RT SS 0.375 / 2.500 G04.001.01(Valve 2HP-489 to Valve 2HP-152 Use Procedure NDE-995 to perform a circumferential scan of the weld and half of an inch of base metal on each side of the weld as access permits.Use procedure NDE-12 to perform RT on 100% of the weld and a quarter of an inch of base metal on each side of the weld.See PIP # 0-99-02157 and PIP # 0-01-04673 for examination methods and area of coverage for this item number.02.G4.1.0011 Circumferential 2RC-205-4 Class 1 51A 2RC-205 0-ISIN4-101A-2.4 NDE-995 UT. SS 0.375 / 2.500 Component 40378 G04.001.01(Valve 2HP-489 to Valve 2HP-152 Use Procedure NDE-995 to perform a circumferential scan of theweld and half of an inch of base metal on each side of the weld as access permits.Use procedure NDE-12 to perform RT on 100% of the weld and a quarter of an inch of base metal on each side of the weld.See PIP # 0-99-02157 and PIP # 0-01-04673 for examination methods and area of coverage for this item number.02.G4.1.0012 Circumferential 2HP-214-14 Class 1 51A 2HP-214 0-ISIN4-101A-2.4 NDE-995 UT SS 0.375 /2.500 Component 40378 G04.001.01; Elbow to Pipe Inspect 100% of weld & 1 " of base material (axial & circumferential).

This weld was listed previously as 2-5 1A-27-109 until iso 2-51A-27 (3) was redrawn. Reference Section 7 of the ISI Plan, General Requirements..

________02.G4.1.0013 Circumferential 2HP-216-7 Class 1 51A 2HP-216 O-ISIN4-1 01 A-2.4 NDE-995 UT SS 0.375 / 2.500 Component 40378 G04.001.011 Pipe to Elbow Inspect 100%of weld & 1" of base material (axial & circumferential).

This weld was listed previously as 2-51A-30-51 until iso 2-51A-30 was redrawn. Reference Section 7 of the ISI Plan, General Requirements.

Printed 07/14/10 Ick8302 v. 06/18/09 1 SDQA Cat "C" Oconee 2 7/14/2010 2:17:26 PM Page 30 of 79 O This report includes all changes through addendum ONS2-107 Oconee 2, 4th Interval, outage 4 (EOC-24)Summary Num Component 10 ISOIDWG Numbers Class I System Procedure lnsp Req Material Sched Description Comments Thick/NPS Cal Blocks Componenet 1D 2 Category Aug 02.G4.1.0014 Circumferential 2HP-216-8 Class 1 51A 2HP-216 O-ISIN4-101A-2.4 NDE-995 UT SS 0.375 / 2.500 Component 40378 G04.001 .01 ýElbow to Pipe Inspect 100% of weld & 1" of base material (axial & circumferential).

This weld was listed previously as 2-51A-30-52 until iso 2 51A-30 was redrawn. Reference Section 7 of the ISI Plan, General Requirements.

02.G4.1.0015 Circumferential 2HP-216-9 Class 1 51A 2HP-216 O-ISIN4-101A-2.4 NDE-995 UT SS 0.375 / 2.500 Component 40378 G04.001 .02(Pipe to Valve 2HP-486 Inspect 100% of weld & 1" of base material (axial & circumferential).

This weld was listed previously as 2-51A-30-54 until iso 2-51A-30 was redrawn. Reference Section 7 of the ISI Plan, General Requirements.

02.G4.1.0016 Circumferential 2HP-217-10 Class 1 51A 2HP-217 O-ISIN4-101A-2.4 NDE-995 UT SS 0.375 / 2.500 Component 40378 G04.001.02' J, Pipe to Elbow Inspect 100% of weld & 1" of base material (axial & circumferential).

This weld vxas listed previously as 2-51A-30-28,until iso 2-51A-30 was redrawn. Reference Section 7 of the ISI Plan, General Requirements.

02.G4.1.0017 Circumferential 2HP-217-11 Class 1. 51A 2HP-217 O-ISIN4-101A-2.4 NDE-995 UT SS 0.375 / 2.500 Component 40378 G04.001.02, Elbow to Pipe Inspect 100% of weld & 1" of base material (axial & circumferential).

This weld was listed previously as 2-51A-30-29 until iso 2-51A-30 was redrawn. Reference Section 7 of the ISI Plan, General Requirements.

Printed 07/14/10 Ick8302 v. 06/18/09 SDQA Cat "C" Oconee 2 7/14/2010 2:17:26 PM Page 31 of 79 0 This report includes all changes through addendum ONS2-107 Oconee 2, 4th Interval, outage 4 (EOC-24)0 Summary Num Component ID ISOIDWG Numbers Class I System Procedure Insp Req Material Sched Thick/NPS Description Comments Cal Blocks Componenet ID 2 Category Aug 02.G4.1.0018 Circumferential 2HP-217-12 Class 1 51A 2HP-217 O-ISIN4-101A-2.4 NDE-995 UT SS 0.375 / 2.500 Component 40378 G04.001.02, Pipe to Valve 2HP-487 Inspect 100% of weld & 1" of base material (axial & circumferential).

This weld was listed previously as 2-51A-30-31 until iso 2-51A-30 was redrawn. Reference Section 7 of the ISI Plan, General Requirements.

02.G4.1.0019 Circumferential 2HP-218-20 Class 1 51A 2HP-218 0-ISIN4-101A-2.4 NDE-995 UT SS 0.375 / 2.500 Component 40378 G04.001.021 Pipe to Elbow Inspect 100% of weld & 1 " of base material (axial & circumferential).

This weld was listed previously-as 2-51A-27-79 until iso 2-51A-27 (2) was redrawn. Reference Section 7 of the I51 Plan, General Requirements.

02.G4.1.0020 Circumferential 2HP-218-21 Class 1 51A 2HP-218 0-ISIN4-101A-2.4 NDE-995 UT SS 0.375 / 2.500 Component 40378 G04.001.02!

Elbow to Pipe Inspect 100% of weld & 1' of base material (axial & circumferential).

This weld was listed previously as 2-51A-27-80 until iso 2-51A-27 (2) was redrawn. Reference Section 7 of the ISI Plan, General Requirements.

02.G4.1.0021 Circumferential 2HP-218-22 Class 1 51A 2HP-218 O-ISIN4-101A-2.4 NDE-995 UT SS 0.375 / 2.500 Component 40378 G04.001.02E Pipe to Valve 2HP-489 Inspect 100% of weld & 1" of base material (axial & circumferential).

Reference Section 7 of the ISI Plan, General Requirements.

Printed 07/14/10 Ick8302 v. 06/18/09 SDQA Cat "C" Oconee 2 7/14/2010 2:17:26 PM Page 32 of 79 0 S This report includes all changes through addendum ONS2-107 Oconee 2, 4th Interval, outage 4 (EOC-24)Summary Num Component ID ISO/DWG Numbers Procedure Insp Req Material Sched Thick/NPS Cal Blocks Componenet ID 2 Class I System Description Comments Category Aug 02.G4.1.0022 2RC-203-32 Class 1 50 2RC-203 NDE-995 UT SS 0.375 /2.500 Component G04-001.02-B&W146629E 40378 Circumferential O-ISIN4-100A-2.1 Safe End to Pipe Inspect 100% of weld & 1" of base material (axial & circumferential):

Reference Section 7 of the ISI Plan, General Requirements.

Weld 2RC-203-2 was cut out and replaced with weld 2RC-203-21 during EOC-20.Weld 2RC-203-21 was cut out and replaced with weld 2RC-203-32 during EOC-23.Note: The inspection performed for G02.001.008B(02.G2.1.0015) will satisfy the requirements for this G4 (02.G4.1.0022) inspection.

O2.G4.1.0023 2RC-203-3 Class 1 50 2RC-203 NDE-995 UT SS 0.375 / 2.500 Component G04.001.02ý B&W146629E 40378 Circumferential O-ISIN4-100A-2.1 Pipe to Valve 2HP-126 Inspect 100% of weld & 1" of base material (axial & circumferential).

Reference Section 7 of the ISI Plan, General Requirements.

________ ___ .. ...Note: The inspection performed for G02.001.0101B will satisfy the requirements for this.G04 inspection.

02.G4.1.0024 2RC-204-37 Class 1 50 2RC-204 NDE-995 UT SS 0.375 /2.500 Component G04.001.02, B&W146629E 40378 Circumferential O-ISIN4-100A-2.1 Safe End to Pipe Inspect 100% of weld & 1" of base material (axial & circumferential).

Reference Section 7 of the ISI Plan, General Requirements.

Weld 2RC-204-18 was cut out and replaced with weld 2.RC-204-28 during EOC-20.Weld 2RC-204-28 was cut out and replaced with weld 2RC-204-37 during EOC-23 per Revison 15 of iso 2RC-204.Note: The inspection performed for G02.001.0608A(Summary Number 02.G2.1.0013) will satisfy the requirements for this G4 inspection.

Printed 07/14/10 Ick8302 v. 06/18/09 SDQA Cat "C" Oconee 2 7/14/2010 2:17:26 PM Page 33 of 79 This report includes all changes through addendum ONS2-107 Oconee 2, 4th Interval, outage 4 (EOC-24)Summary Num Component ID ISO/DWG Numbers Class / System Procedure Insp Req Material Sched Description Comments Thick/NPS Cal Blocks Componenet ID 2 Category Aug 02.G4.1.0025 Circumferential 2RC-204-20 Class 1 50 2RC-204 B&W146629E O-ISIN4-100A-2.1 NDE-995 UT SS 0.375 / 2.500 Component 40378 G04.001.03(Pipe to Valve 2HP-127 Inspect 100% of weld & 1" of base material (axial & circumferential).

Reference Section 7 of the ISI Plan, General Requirements.

Inspect this weld at the same time item number G02.001.010A is inspected.

Note: The inspection performed for the G02 item number will be sufficient to meet the requirements for the G04 inspection.

Category B-B 02.12.11.0002 Circumferential 2-PZR-WP28 Class 1 50 ISI-OCN2-002 OM-1201-456 PDI-UT-7 UT CS 4.750 / 84.000 B02.011 .00, 50470A Head to Htr. Belt Shell / Forging Pressurizer Lower Head Pc. 6 to Heater Belt Shell Pc. 4 and Lower Heater Belt Forging Pc. 40.Cal block 50470 to be used with Procedure PDI-UT-7 for sizing purposes.02.B2.11.0002 Circumferential 2-PZR-WP28 Class 1 50 ISI-OCN2-002 OM-1201-456 NDE-640 UT CS 4.750 / 84.000 40394 40338 B02.01 1.00, Head to Htr. Belt Shell / Forging Pressurizer Lower Head Pc. 6 to Heater Belt Shell Pc. 4 and Lower Heater Belt Forging Pc. 40.Cal block 50470 to be used with Procedure PDI-UT-7 for sizing purposes.02.B2.111.0002 Circumferential 2-PZR-WP28 Class 1 50 ISI-OCN2-002 OM-1201-456 NDE-820 UT CS 4.750 / 84.000 40394 40338 B02.011.00, Head to Htr. Belt Shell / Forging Pressurizer Lower Head Pc. 6 to Heater Belt Shell Pc. 4 and Lower Heater Belt Forging Pc. 40.Cal block 50470 to be used with Procedure PDI-UT-7 for sizing purposes.Printed 07/14/10 Ick8302 v. 06/18/09 SDQA Cat "C" P0Oconee 2 7/14/2010 2:17:26 PM Page 34 of 79 This report includes all changes through addendum ONS2-107 Oconee 2, 4th Interval, outage 4 (EOC-24)Summary Num Category B-B 02.132.12.0002 Longitudinal Component ID lSO/DWG Numbers Class I System Procedure Insp Req Material Sched Thick/NPS Description Comments Cal Blocks Componenet ID 2 2-PZR-WP7-1 Class 1 50 ISI-OCN2-002 OM-1201-456 NDE-820 UT CS 6.188 / 0.000 40338 40394 B02.012.00, Htr. Belt Shell to Htr. Belt Forging Pressurizer Heater Belt Shell Pc. 4.to Lower,/ Upper Heater Belt Forging Pc. 40 / 41. Y-Z Quadrant.Inspect only one foot of the longitudinal weld, starting from the centerline of the adjacent circumferential weld (2-PZR-WP28).

02.B2.12.0002 2-PZR-WP7-1 Class 1 50 ISI-OCN2-002 OM-1201-456 Longitudinal NDE-640 UT CS 6.188 / 0.000 40338 40394 B02.012.00, Htr. Belt Shell to Htr. Belt Forging Pressurizer Heater Belt Shell Pc. 4 to Lower / Upper Heater Belt Forging Pc. 40 / 41. Y-Z Quadrant.Inspect only one foot of the longitudinal weld, starting from the centerline of the adjacent circumferential weld (2-PZR-WP28).

Category B-B 02.B3.110.0002 Circumferential 2-PZR-WP34 Class 1 50 ISI-OCN2-002 OM-1201-456 B&W149769E NDE-820 UT CS 4.750 / 7.750 40394 B03.1 10.00;Nozzle to Head Pressurizer Spray Nozzle Pc. 9 to Upper Head Pc. 5.02.B3.110.0002 Circumferential 2-PZR-WP34 Class 1 50 ISI-OCN2-002 OM-1 201-456 B&W149769E NDE-640 UT CS 4.750 / 7.750 40394 B03.1 10.00, Nozzle to Head Pressurizer Spray Nozzle Pc. 9 to Upper Head Pc. 5.02.B3.110.0003 Circumferential 2-PZR-WP33-3 Class 1 50 ISI-OCN2-002 OM-1 201-456 B&W149770E NDE-640 UT CS 4.750 / 6.875 40394 B03.110.00" Nozzle to Head Pressurizer Relief Nozzle Pc. 31 to Upper Head Pc. 5. Z-W Quadrant.Printed 07/14/10 Ick8302 v. 06/18/09 SDQA Cat "C" Oconee 2 7/14/2010 2:1726 PM Page 35 of 79 0 This report includes all changes through addendum ONS2-107--, Oconee 2, 4th Interval, outage 4 (EOC-24)Summary Num Category B-D 02.B3.110.0003 Circumferential Component ID ISOIDWG Numbers Class / System 2-PZR-WP33-3 Class 1 50- ISI-OCN2-002 OM-1201-456 B&W149770E Procedure Insp Req Material Sched Description Comments NDE-820 UT CS Thick/NPS Cal Blocks Componenet ID 2 4.750 / 6.875 40394 B03.110.00' Nozzle to Head Pressurizer Relief Nozzle Pc. 31lto Upper Head Pc. 5. Z-W Quadrant.02.B3.110.0005 Circumferential 2-PZR-WP33-1 Class 1 50 ISI-OCN2-002 OM-1201-456 B&W149770E NDE-640 UT CS 4.750 / 6.875 40394 B03.1 10.00!Nozzle to Head Pressurizer Relief Nozzle Pc. 31 to Upper Head Pc. 5. W-X Quadrant.02.B3.110.0005 Circumferential 2-PZR-WP33-1 Class 1 50 ISI-OCN2-002 OM-1201-456 B&W149770E NDE-820 UT CS 4.750 / 6.875 40394 B03.1 10.00!Nozzle to-Head Pressurizer Relief Nozzle Pc., 31 to Upper Head Pc. 5. W-X Quadrant.02.B3.120.0002 2-PZR-WP34 Class 1 50 ISI-OCN2-002 NDE-3620 UT CS 2.125 /7.750 40394 B03.120.00, B&W149768E Nozzle to Head Pressurizer Spray Nozzle Pc. 9 to Upper Head Pc. 5. (Inside Radius Section)02.B3.120.0003 2-PZR-WP33-3 Class 1 50 ISI-OCN2-002 B&W149770E NDE-3620 UT CS 2.310 / 6.875 40394 B03.120.00' Nozzle to Head Pressurizer Relief Nozzle Pc. 31 to Upper Head Pc. 5. Z-W Quadrant: (Inside Radius Section)02.B3.120.0004 2-PZR-WP33-2 Class 1 50 ISI-OCN2-002 B&W149770E NDE-3620 UT CS 2.310 / 6.875 40394 B03.120.00i Nozzle to Head Pressurizer Relief Nozzle Pc. 31 to Upper Head Pc. 5. X-Y Quadrant. (Inside Radius Section)SDQA Cat "C" ,, Oconee 2 7/14/2010 2:17:26 PM Page 36 of 79 Printed 07/14/10 Ick8302 _v. 06/18/09 This report includes all changes through addendum ONS2-107 Oconee 2, 4th Interval, outage 4 (EOC-24)Summary Num Component ID ISO/DWG Numbers Class I System Procedure Insp Req Material Sched Description Comments Thick/NPS Cal Blocks Componenet ID 2 Category B-D 02.83.120.0005 2-PZR-WP33-1 Class 1 50 ISI-OCN2-002 B&W149770E NDE-3620 UT CS 2.310 / 6.875 40394 B03.120.00!

Nozzle to Head Pressurizer Relief Nozzle Pc. 31 to Upper Head Pc. 5. W-X Qradrant. (Inside Radius Section)Category B-F 02.B5.10.0001 Circumferential Terminal End Dissimilar 2-RPV-WR53 Class 1 50 ISI-OCN2-001 54-ISI-823 UT SS-CS 1.688 /15.625 8034675 B05.010.001, B05.010.0011 OM-1201-1528 I Nozzle to Safe End RV A-Side Core Flood Nozzle Pc. 17 to Safe End Pc. 89. W-Axis. (B05.010.001)

The automated UT performed from the ID of the Reactor Vessel on this weld will be substituted for this surface exam. -- (B05.010.001A)

Procedures must be qualified through PDI.A vendor that is PDI qualified for remote automated UT examinations will have to be contracted to perform this inspection.

A UT performed in 2EOC-24 (contracted by Areva) for augmented exams (G12.2 items) also met the Code Requirements for B5.10 items of the 1998 Edition thru the 2000 Addenda of the Section XI Code. We will take credit for the UT exam in the 2EOC-24 outage. We will determine if Code Case N-663 can be used to cover the surface exam that is scheduled in 2EOC-26. If Code Case N-663 cannot be used for the B5.10 item surface exams, we will have to perform a UT from the ID during the 10 year Reactor Vessel Exam scheduled during 2EOC-26. The vendor for the Reactor Vessel exams will have to be qualifed to detect surface flaws from the ID by UT method. See Third Interval Relief Request ONS-001 and ONS-002 for details on the UT performed in lieu of the surface exam.i Printed 07/14/10 Ick8302 v. 06/18/09 SDQA Cat "C" Oconee 2 7/14/2010 2:17:26 PM Page 37 of 79 0 S This report includes all changes through addendum ONS2-107 Oconee 2, 4th Interval, outage 4 (EOC-24)Summary Num Category B-F 02.B5.10.0002 Component ID ISO/DWG Numbers Class I System Procedure Insp Req Material Sched Description Comments Thick/NPS Cal Blocks Componenet ID 2 2-RPV-WR53A Class 1 50 ISI-OCN2-001 54-1SI-823 UT SS-CS 1.688 / 15.625 8034675 B05.010.002, B05.010.002/

Circumferential Terminal End Dissimilar OM-1201-1528 Nozzle to Safe End RV B-Side Core Flood Nozzle Pc. 17 to Safe End Pc. 89. Y-Axis. (B05.010.002)

The automated UT performed from the ID of the Reactor Vessel on this weld will be substituted for this surface exam. -- (B05.010.002A)Procedures must be qualified through PDI.A vendor that is PDI qualified for remote automated UT examinations will have to be contracted to perform this inspection.

A UT performed in 2EOC-24 (contracted by Areva) for augmented exams (G12.2 items) also met the Code Requirements for B5.10 items of the 1998 Edition thru the 2000 Addenda of the Section XI Code. We will-take credit for the UT exam in the 2EGC-" 24 outage. We will determine if Code Case N-663 can be used to cover the surface exam that is scheduled in 2EOC-26. If Code Case N-663 cannot be used for the B5.10 item surface exams, we will have to perform a UT from the ID during the 10 year Reactor Vessel Exam scheduled during 2EOC-26. The vendor for the Reactor Vessel exams will have to be qualifed to detect surface flaws from the ID by UT method. See Third Interval Relief Request ONS-001 and ONS-002 for details on the UT performed in lieu of the surface exam: Category B-G-1 02.B6.60.0001 2-PZR-MW-STU DS Class 1 50 B&W149775E OM 1201-858 2-PZR-MW-NUTS Class 1 50 OM-1201-1135 G-ISIN4-100A-2.1 OM 1201-858 PDI-UT-5 UT CS 0.000 / 2.750 40425 B06.060.00' Pressurizer Manway Studs Pc. 67. 12 Studs, Stud Length = 14.875".02.B6.80.0001 NDE-62 VT-1 CS 0.000 / 2.750 B06.080.00' Pressurizer Manway Nuts Pc. 68. Examination includes bushings and washers.Category 8-G-2 02.B7.30.0005 2-SGA-UHHC-STUDS Class 1 50 OM-201.S-0001 OM-201.S-0171 OM-201 .S-0252 NDE-62 VT-1 SS 0.000 / 1.250 B07.030.00!

Steam Generator 2A Upper Head Handhole (primary)

Cover Studs and Nuts.(8 studs and nuts)Examine all studs and nuts.Stud Length = 10.94 inches.SDQA Cat "C" Printed 07/14/10 Ick8302 v. 06/18/09 Oconee 2 7/14/2010 2:17:26 PM Page 38 of 79 This report includes all changes through addendum ONS2-107 Oconee 2, 4th Interval, outage 4 (EOC-24)Summary Num Component ID ISO/DWG Numbers Class / System Procedure Insp Req Material Sched Description Comments Thick/NPS Cal Blocks Componenet ID 2 Category B-G-2 02.B7.30.0006 2-SGB-UHHC-STUDS Class 1 50 OM-201.S-0001 NDE-62 VT-1 SS 0.000 / 1.250 B07.030.OOE OM-201.S-0171 OM-201 .S-0252 Steam Generator 2B Upper Head Handhole (primary)

Cover Studs and Nuts.(8 studs and nuts)Examine all studs and nuts.Stud Length = 10.94 inches.02.B7.70.0005 2-53A-LP1-STUDS Class 1 53A OM-245-2054.001 0-ISIN4-102A-2.1 NDE-62 VT-1 SS 0.000 / V.000 B07.070.00]

Decay Heat Suction 12" Valve 2LP-1 Bolting. Inspect one of the following valves: 2LP-1 or 2LP-2. Examine all studs and nuts.Category B-J 02.B9.11.0006 Circumferential 2-PDA1-2 Class 1 50 ISI-OCN2-011 NDE PT SS-CS 2.330 / 33.500 B09.011.006, B09.011.006/

OM-1201-966 Dissimilar Stress Weld Safe End to Elbow Reactor Coolant Pump 2A1 Discharge Piping. Safe End Pc. 49 to Elbow Pc. 53.Code Case N-624.02.B9.11.0006 Circumferential Dissimilar Stress Weld 2-PDAI-2 Class 1 50 ISI-OCN2-011 OM-1201-966 EPRI-DMW-UT PA-1 SS-CS 2.330 / 33.500 40350 40397 B09.011.006, B09.011.006i Safe End to Elbow Reactor Coolant Pump 2A1 Discharge Piping. Safe End Pc. 49 to Elbow Pc. 53.Code Case N-624.Printed 07/14/10 lck8302 v. 06/18/09 SDQA Cat "C" Prite 0714101ck30 v.061 /09SDA Ct C"Oconee 27/14/2010 2:17.26 PM Page 39of 79 S This report includes all changes through addendum ONS2-107 Oconee 2, 4th Interval, outage 4 (EOC-24)Summary Num Component ID ISO/DWG Numbers Class I System Procedure Insp Req Material Sched Description Comments Thick/NPS Cal Blocks Componenet ID 2 Category B-J 02.B9.11.0007 Circumferential Dissimilar Stress Weld 2-PDA2-2 Class 1 50 ISI-OCN2-012 OM-1201-966 NDE-35 PT SS-CS 2.330 / 33.500 B09.011.007, B09.011.007/

Safe End to Elbow Reactor Coolant Pump 2A2 Discharge Piping. Safe End Pc. 49 to Elbow Pc. 53.02.B9.11.0007 2-PDA2-2 Class 1 50 ISI-OCN2-012 OM-1201-966 EPRI-DMW-UT PA-1 SS-CS 2.330 / 33.500 40350 40397 B09.011.007, B09.011.0071 Circumferential Dissimilar Stress Weld Safe End to Elbow Reactor Coolant Pump 2A2 Discharge Piping. Safe End Pc. 49 to Elbow Pc. 53.02.B9.11.0008 2-PDB1-2 Class 1 50 ISI-OCN2-013 NDE-35 , PT SS-CS 2.330 / 33.500 Circumferential OM-1201-966 Dissimilar Stress Weld Safe End to Elbow Reactor Coolant Pump 281 Discharge Piping. Safe End Pc. 49 to Elbow Pc. 53.Code Case N-624 02.19.11.0008 2-PDB1-2 B09.011.008, B09.011.008/

B09.011.008, B09.011.008/

Class 1 50 ISI-OCN2-013 OM-1201-966 EPRI-DMW-UT PA-1 SS-CS 2.330 / 33.500 40350 40397 Circumferential Dissimilar Stress Weld Safe End to Elbow Reactor Coolant Pump 2B1 Discharge Piping. Safe End Pc. 49 to Elbow Pc. 53.Code Case N-624 Printed 07/14/10 Ick8302 v, 06/18/09 SDQA Cat "C" Oconee 2 7/14/2010 2:17:26 PM Page 40 of 79

  • This report includes all changes through addendum ONS2-107 Oconee 2, 4th Interval, outage 4 (EOC-24)Summary Num Category B-J 02.B9.11.0009 Component ID ISO/DWG Numbers Class I System Procedure Insp Req Material Sched Thick/NPS Description Comments Cal Blocks Componenet ID 2 2-P1DB2-2 Class I )50 ISI-OCN2-014 OM-1201-966 NDE-35 PT SS-CS 2.330 / 33.500 B09.011.009, B09.01 1.009/Circumferential Dissimilar Stress Weld Safe End to Elbow Reactor Coolant Pump 2B32 Discharge Piping. Safe End Pc. 49 to Elbow Pc. 53.02.B9.11.0009 Circumferential Dissimilar Stress Weld 2-PDB2-2 Class 1 50 ISI-OCN2-014 OM-1 201-966 EPRI-DMW-UT PA-1 SS-CS 2.330 / 33.500 40350 40397 B09.011.009, B09.011.009/

Safe End to Elbow Reactor Coolant Pump 282 Discharge Piping. Safe End Pc. 49 to Elbow Pc. 53.02.B9.11.0012 Circumferential Dissimilar Stress Weld 2-PIAl1;7 Class 1 50 ISI-OCN2-007 NDE-35 PT SS-CS 3.000 / 33.500 B09.011.012, B09.011.012/

OM-1201-966 Pipe to Safe End Reactor Coolant Pump 2A1 Suction Piping. Pipe Pc. 56 to Safe End Pc. 55.02.B9.11.0012 Circumferential Dissimilar Stress Weld 2-PIAl-7 Class 1 50 ISI-OCN2-007 OM-1201-966 EPRI-DMW-UT PA-1 SS-CS 3.000 / 33.500 40350 40397 B09.011.012, B09.011.012/

Pipe to Safe End Reactor Coolant Pump 2A1 Suction Piping. Pipe Pc. 56 to Safe End Pc. 55.Printed 07/14/10 lck8302 v. 06/18/09 SDQA Cat "C" Oconee 2 7/14/2010 2:17:26 PM Page 41 of 79 This report includes all changes through addendum ONS2-107 Oconee 2, 4th Interval, outage 4 (EOC-24)Summary Num Component 10 ISO/DWG Numbers Class I System Procedure Insp Req Material Sched Description Comments ThicklNPS Cal Blocks Componenet ID 2 Category B-J 02.B9.11.0013 Circumferential Dissimilar Stress Weld 2-PIA2-7 Class 1 50 ISI-OCN2-008 NDE-35 PT SS-CS 2.330 / 33.500 B09.011.013, B09.011.013/

OM-1201-966 Pipe to Safe End Reactor Coolant Pump 2A2 Suction Piping. Pipe Pc. 56 to Safe End Pc. 55. Code Case N-624.02.B9.11.0013 Circumferential Dissimilar Stress Weld 2-PIA2-7 Class 1 50 ISI-OCN2-008 GM-1i201-966 EPRI-DMW-UT PA-1 SS-CS 2.330 / 33.500 40350 40397 B099.011.013, B09.011.013/

Pipe to Safe End Reactor Coolant Pump 2A2 Suction Piping. Pipe Pc. 56 to Safe End Pc. 55. Code Case N-624.02.B9.11.0014 Circumferential Dissimilar Stress Weld 2-PIB1-7 Class 1 50 ISI-OCN2-009 NDE-35 PT SS-CS 2.330 / 33.500 B09.011.014, B09.011.014/

OM-1201-966 Pipe to Safe End Reactor Coolant Pump 2B1 Suction Piping. Pipe Pc. 56 to Safe End Pc. 55.02.B9.11.0014 2-PIB1-7 Class 1 50 ISI-OCN2-009 EPRI-DMW-UT SS-CS 2.330 I 33.500 40350 OM-1201-966 PA-1 40397 Circumferential Dissimilar Stress Weld B09.011.014, B09.011.0141 Pipe to Safe End Reactor Coolant Pump 2B1 Suction Piping. Pipe Pc. 56 to Safe End Pc. 55.Printed 07/14/10 Ick8302 v. 06/18/09 SDQA Cat "C" Oconee 2 7/14/2010 217:26 PM Page 42 of 79 0 This report includes all changes through addendum ONS2-107 Oconee 2, 4th Interval, outage 4 (EOC-24)Summary Num Component ID ISOIDWG Numbers Class I System Procedure Insp Req Material Sched Description Comments Thick/NPS Cal Blocks Componenet ID 2 Category B-J 02.B9.11.0015 2-PIB2-7 Class 1 50 ISI-OCN2-010 NDE-35 PT SS-CS 2.330/ 33.500 Circumferential OM-1201-966 Dissimilar Stress Weld Pipe to Safe End Reactor Coolant Pump 2B2 Suction Piping. Pipe Pc. 56,to Safe End Pc. 55.02.B9.11.0015 2-PIB2-7 B09.011-015, B09.011.015/

Class 1 50 ISI-OCN2-010 OM-1201-966 EPRI-DMW-UT PA-1 SS-CS 2.330 / 33.500 40350 40397 B09.011.015, B09.011.015/

Circumferential Dissimilar Stress Weld Pipe to Safe End Reactor Coolant Pump 2B2 Suction Piping. Pipe Pc. 56 to" Safe End Pc. 55.02.B9.11.0020 Circumferential Terminal End 2RC-279-88V Class 1 50 ISI-OCN2-005 2RC-279 0-ISIN4-10OA-2.1 NDE-25 MT CS 3.500 / 36.000 B09.011.020,-

B09.011.020/

Nozzle to Pipe Sream Generator 2A Inlet Nozzle to Hot Leg.Weld 88V is listed on weld iso 2RC-27b but drawing ISi-OCN2-005 is listed as the iso to show where the weld is located on the 2A Hot Leg Piping Loop.02.B9.11.0020 Circumferential Terminal End 2RC-279-88V Class 1 50 ISI-OCN2-005 2RC-279 O-1SIN4-100A-2.1 NDE-600 UT CS 3.500 / 36.000 Component B09.011.020, B09.011.020/

Nozzle to Pipe Sream Generator 2A Inlet Nozzle to Hot Leg.Weld 88V is listed on weld iso 2RC-279 but drawing ISI-OCN2-005 is listed as the iso to show where the weld is located on the 2A Hot Leg Piping Loop.Printed 07/14/10 Ick8302 v. 06/18/09 SDQA Cat "C" Oconee 2 7/14/2010 2:17:26 PM Page 43 of 79 This report includes all changes through addendum ONS2-107 Oconee 2, 4th Interval, outage 4 (EOC-24)Summary Num Component ID ISOIDWG Numbers Procedure Insp Req Material Sched Thick/NPS Cal Blocks Componenet ID 2 Class I System Description Comments Category B-J 02.B9.11.0046 2-PIA1-8 Class 1 50 ISI-OCN2-007 PDI-UT-2 UT SS 2.330 / 33.500 Component B09.011.046, OM-1201-966 40397 B09.011.046, 50214 Circumferential Terminal End Stress Weld Casing to Safe End Reactor Coolant Pump 2A1 Suction Piping. RCP 2A1 Casing to Safe End Pc. 55. Procedure NDE-600 uses the component for calibration.

Procedure PDI-UT-2 may be used in lieu of procedure NDE-600. If PDI-UT-2 is used, then the calibration block listed shall be used. Procedure NDE-830 and Cal Block 50386 are to be used only for a supplemental UT performed from the pump side. The supplemental exam is being performed as requested by Jim McArdle which will be used to justify limited coverage from the code exam (performed using NDE-600 or PDI-UT-2).

Code N-663 allows us to exclude the surface exam from the Fourth Interval ISI Plan. See PIP G-08-00185 (CA # 7) for details on the exclusion of surface exams.02.B9.11.0046 2-PIA1-8 Class 1 50 ISI-OCN2-007 NDE-830 UT SS 2.330/ 33.500 Component B09.011.046, OM-1201-966 40397 B09.011.046/

50214 Circumferential Terminal End Stress Weld Casing to Safe End Reactor Coolant Pump 2A1 Suction Piping. RCP 2A1 Casing to Safe End Pc. 55. Procedure NDE-600 uses the component for calibration.

Procedure PDI-UT-2 may be used in lieu of procedure NDE-600. If PDI-UT-2 is used, then the calibration block listed shall be used. Procedure NDE-830 and Cal Block 50386 are to be used only for a supplemental UT performed from the pump side. The supplemental exam is being performed as requested by Jim McArdle which will be used to justify limited coverage from the code exam (performed using NDE-600 or PDI-UT-2).

Code N-663 allows us to exclude the surface exam from the Fourth Interval ISI Plan. See PIP G-08-00185 (CA # 7) for details on the exclusion of surface exams.Printed 07/14/10 Ick8302 v. 06/18/09 SDQA Cat "C" Oconee 2 7/14/2010 2:17:26 PM Page 44 of 79 This report includes all changes through addendum ONS2-107 Oconee 2, 4th Interval, outage 4 (EOC-24)Summary Num Component ID ISO/DWG Numbers Procedure Insp Req Material Sched Thick/NPS Cal Blocks Componenet ID 2 Class I System Description Comments Category B-J 02.B9.11.0053 2-PDA2-1 Class 1 50 ISI-OCN2-012 NDE-830 UT SS 2.330 /33.500 Component B09.011.053, OM-1201-966 40397 B09.011.053/

50214 Circumferential Terminal End Stress Weld Casing to Safe End Reactor Coolant Pump 2A2 Discharge Piping. RCP 2A2 Casing to Safe End Pc. 49. Procedure NDE-600 uses the component for calibration.

Procedure PDI-UT-2 may be used in lieu of procedure NDE-600. If PDI-UT-2 is used, then the calibration block listed shall be used. Procedure NDE-830 and Cal Block 50386 are to be used only for a supplemental UT performed from the pump side. The supplemental exam is being performed as requested by Jim McArdle which will be used to justify limited coverage from the code exam (performed using NDE-600 or PDI-UT-2).

Code N-663 allows us to exclude the surface exam from the Fourth Interval ISI Plan. See PIP G-08-00185 (CA # 7) for details on the exclusiorn of surface exams.02.B9.11.0053 2-PDA2-1 Class 1 50 ISI-OCN2-012 NDE-600 UT SS 2.330 /33.500 Component B09.011.053, OM-1201-966 40397 B09.011.053/

50214 Circumferential Terminal End Stress Weld Casing to Safe End Reactor Coolant Pump 2A2 Discharge Piping. RCP 2A2 Casing to Safe End Pc. 49. Procedure NDE-600 uses the component for calibration.

Procedure PDI-UT-2 may be used in lieu of procedure NDE-600. If PDI-UT-2 is used, then the calibration block listed shall be used. Procedure NDE-830 and Cal Block 50386 are to be used only for a supplemental UT performed from the pump side. The supplemental exam is being performed as requested by Jim McArdle which will be used to justify limited coverage from the code exam (performed using NDE-600 or PDI-UT-2).

Code N-663 allows us to exclude the surface exam from the Fourth Interval IS Plan. See PIP G-08-00185 (CA # 7) for details on the exclusion of surface exams.Printed 07/14/10 Ick8302 v.06/18/09 SDQA Cat "C" Oconee 2 7/14/2010 2:17:26 PM Page 45 of 79 This report includes all changes through addendum ONS2-107 Oconee 2, 4th Interval, outage 4 (EOC-24)Summary Num Component ID ISO/DWG Numbers Procedure Insp Req Material Sched Thick/NPS Cal Blocks Componenet ID 2 Class I System Description Comments Category B-J 02.B9.11.0063 2-PDB2-1 Class 1 50 ISI-OCN2-014 NDE-830 UT SS 2.330/ 33.500 Component B09.011.063, OM-1201-966 40397 B09.011.063/

50214 Circumferential Terminal End Stress Weld Casing to Pipe Safe End Reactor Coolant Pump 212 Discharge Piping. RCP 282 Casing to Safe End Pc. 49. Procedure NDE-600 uses the component for calibration.

Procedure PDI-UT-2 may be used in lieu of procedure NDE-600. If PDI-UT-2 is used, then the calibration block listed shall be used. Procedure NDE-830 and Cal Block 50386 are to be used only for a supplemental UT performed from the pump side. The supplemental exam is being performed as requested by Jim McArdle which will be used to justify limited coverage from the code exam (performed using NDE-600 or PDI-UT-2).

Code N-663 allows us to exclude the surface exam from the Fourth Interval ISI Plan. See PIP G-08-00185 (CA # 7) for details on the exclusion of surface exams.02.B9.11.0063 2-PDB2-1 Class 1 50 ISI-OCN2-014 NDE-600 UT SS .2.330 / 33.500 Component B09.011.063, OM-1201-966 40397 B09.011.063/

50214 Circumferential Terminal End Stress Weld Casing to Pipe Safe End Reactor Coolant Pump 282 Discharge Piping. RCP 2B2 Casing to Safe End Pc. 49. Procedure NDE-600 uses the component for calibration.

Procedure PDI-UT-2 may be used in lieu of procedure NDE-600. If PDI-UT-2 is used, then the calibration block listed shall be used. Procedure NDE-830 and Cal Block 50386 are to be used only for a supplemental UT performed from the pump side. The supplemental exam is being performed as requested by Jim McArdle which will be used to justify limited coverage from the code exam (performed using NDE-600 or PDI-UT-2).

Code N-663 allows us to exclude the surface exam from the Fourth Interval ISI Plan. See PIP G-08-00185 (CA # 7) for details on the exclusion of surface exams.Printed 07/14/10 Ick8302 v. 06/18/09 SDQA Cat "C" Oconee 2 7/14/2010 2:17:26 PM Page 46 of 79 This report includes all changes through addendum ONS2-107 Oconee 2, 4th Interval, outage 4 (EOC-24)Summary Num Component ID ISO/DWG Numbers Class I System Procedure Insp Req Material Sched Description Comments Thick/NPS Cal Blocks Componenet ID 2 Category B-J 02.B9.111.0068 2-53A-10-8 Class 1 53A 2-53A-10 0-ISIN4-102A-2.1 PDI-UT-2 UT SS 1.125/12.000 Component PDI-UT-2-0 PDI-UT-2A-0 B09.011.202, B09.011.202/

Circumferential Pipe to Elbow Procedure NDE-600 uses the component for calibration.

Procedure PDI-UT-2 may be used in lieu of procedure NDE-600, If PDI-UT-2 is used, then the calibration block listed shall be used.Code N-663 allows us to exclude the surface exam from the Fourth Interval ISI Plan. See PIP G-08-00185 (CA # 7) for details on the exclusion of surface exams.02.B9.11.0074 Circumferential 2-53A-8-60 Class 1 53A 2-53A-8(2) 0-ISIN4-102A-2.3 NDE-600 UT SS 1.250 / 14.000 Component PDI-UT-2-0 B09.011.210, B09.011.210/

Elbow to Tee Procedure NDE-600 uses the component for calibration.

Procedure PDI-UT-2 may be used in lieu of procedure NDE-600. If PDI-UT-2 is used, then the calibration block listed shall be used.Code N-663 allows us to exclude the surface exam from the Fourth Interval ISI Plan. See PIP G-08-00185 (CA # 7) for details on the exclusion of surface exams.02.B9.21.0007 2-PDB2-11.

Class 1 50 ISI-OCN2-014 NDE-35 PT SS-CS 0.750 / 3.500 B09.021.00, Circumferential B&W146829E Dissimilar Stress Weld Nozzle to Safe End Reactor Coolant Pump 282 Discharge Piping. Nozzle Pc. 46 to Safe End Pc. 47.02.B9.21.0033 2RC-202-17 Class 1 51A 2RC-202 O-ISIN4-1 OOA-2.1 NDE-35 PT SS 0.375 / 2.500 B09.021.11(Circumferential Stress Weld Safe End to Pipe Weld 2RC-202-1 was cut out and replaced with weld 2RC-202-17 during EOC-20.Inspect with Item Number G02.001.008C.

Printed 07/14/10 Ick8302 v. 06/18/09 SDQA Cat "C" Oconee 2 7/14/2010 2:17:26 PM Page 47 of 79 This report includes all changes through addendum ONS2-107 Oconee 2, 4th Interval, outage 4 (EOC-24)Summary Num Component ID ISO/DWG Numbers Class I System Procedure Insp Req Material Sched Thick/NPS Description Comments Cal Blocks Componenet ID 2 Category B-J 02.B9.21.0038 2RC-203-4 Class 1 51A 2RC-203 NDE-35 PT SS 0.375/ 2.500 109.021.11!

Circumferential 0-ISIN4-101A-2.4 Stress Weld Valve 2HP-486 to Valve 2HP-126 02.B9.21.0039 2RC-204-37 Class 1 51A 2RC-204 NDE-35 PT SS 0.375 /2.500 B09.021.11(Circumferential 0-ISIN4-100A-2.1 Stress Weld Safe End to Pipe This weld was listed previously as 2-51A-39-44 until iso 2-51A-39 was redrawn as 2RC-204 and was given the new weld number of 2RC-204-1.

Revision 4 to iso 2RC-204 deleted weld 1 and reassigned weld number 18 to the same weld.Weld 2RC-204-18 was cut out.and replaced with weld 2RC-204-28 during EOC-20.Weld 2RC-204-28 was cut out and replaced with weld 2RC-204-37 during EOC-23 per Revison 15 of Iso 2RC-204.Inspect with Item Number G02.001.008A(Summary Number 02.G2.1.0013).

02.B9.21.0042 2RC-205-1 Class 1 51A 2RC-205 NDE-35 PT SS 0.375/2.500 B09.021.11, Circumferential 0-ISIN4-100A-2.1 Stress Weld Safe End to Pipe This weld was listed previously as 2-51A-39-92A until iso 2-51A-39 was redrawn.Inspect with Item Number G02.001.008D.

02.B9.21.0043 2RC-205-3 Class 1 51A 2RC-205 NDE-35 PT SS 0.375/2.500 B09.021.12(Circumferential 0-ISIN4-101A-2.4 Stress Weld Pipe to Valve 2HP-152 This weld was-listed previously as 2-51A-39-93 until iso 2-51A-39 was redrawn.Inspect with Item Number G02.001.010D.

02.89.21.0044 2RC-205-4 Class 1 51A 2RC-205 0-ISIN4-1 01A-2.4 Circumferential Stress Weld NDE-35 PT SS Valve 2HP-489 to Valve 2HP-152 0.375 / 2.500 B09.021.12' Printed 07/14/10 Ick8302 v. 06/18/09 SDQA Cat "C" Oconee 2 7/14/2010 2:17:26 PM Page 48 of 79 This report includes all changes through addendum ONS2-107 Oconee 2, 4th Interval, outage 4 (EOC-24)Summary Num Component ID ISO/DWG Numbers Class I System Procedure Insp Req Material Sched Description Comments Thick/NPS Cal Blocks Componenet ID 2 Category B-J 02.B9.21.0048 Circumferential 2-51A-30-11 Class 1 51A 2-51A-30 0-151N4-1O1A-2.4 NDE-35 PT SS 0.375 / 2.500 B09.021.12!

Pipe to Pipe 02.B9.21.0066 Circumferential 2HP-216-4 Class 1 51A 2HP-216 0-ISIN4-101A-2.4 NDE-35 PT SS 0.375 / 2.500 B09.021.14' Flange to Pipe This weld was listed previously as 2-51A-30-44 until iso 2-51A-30 was redrawn.02.B9.21.0067 Circumferential 2HP-216-8 Class 1 51A 2HP-216 0-ISIN4-101A-2.4 NDE-35 PT SS 0.375 / 2.500 B09.021.14z Elbow to Pipe This weld was listed previously as 2-51A-30-52 until iso 2-51A-30 was redrawn.02,19.32.0003 Branch Stress Weld 2-PDBl-10 Class 1 50 ISI-OCN2-013 OM-1201-966 OM-1201-969 NDE-25 MT CS 2.250 / 12.000 B09.032.00" Nozzle to Pipe Reactor Coolant Pump 2831 Discharge Piping. HPI1 Nozzle Pc. 46 to Pipe Pc. 44.NPS of Branch Piping is 2.5 inches.02.B9.32.0005 Branch Stress Weld 2-PDB2-1 0 Class 1 50 ISI-OCN2-014 OM-1201-966 OM-1201-969 NDE-25 MT CS 2.250 / 12.000 B09.032.00,'

Nozzle to Pipe B2 Discharge HPI Nozzle.HPI Nozzle Pc. 46 to Pipe Pc. 44. The NPS of the branch piping is 2.5 Inches.Printed 07/14/10 Ick8302 v. 06/18/09 SDQA Cat "C" Oconee 2 7/14/2010 2:17:26 PM Page 49 of 79 This report includes all changes through addendum ONS2-107 Oconee 2, 4th Interval, outage 4 (EOC-24)Summary Num Category B-J 02.B9.32.0007 Component ID ISO/DWG Numbers Class I System Procedure Insp Req Material Sched Description Comments NDE-25 MT CS Thick/NPS Cal Blocks 2.250 / 12.000 Componenet ID 2 2-PIA2-10 Class 1 50 Branch Stress Weld ISI-OCN2-008 OM-1201-966 B&W146623E B09.032.00; Nozzle to Pipe Reactor Coolant Pump 2A2 Suction Piping. Drain Nozzle Pc. 64 to Pipe Pc. 63.NPS of Branch Piping is 1.5 inches.02.B9.40.0005 Socket 2RC-271-7 Class 1 50 2RC-271 O-ISIN4-1 OOA-2.2 NDE-35 PT SS 0.281 / 1.500 B09.040.00!

Elbow to Pipe This weld was listed previously as 2-50-129-7 until iso 2-50-129 was deleted and all welds were tranferred to iso 2RC-271.02.B9.40.0008 2-50-7-102 Class 1 50 2-50-7 (1)0-ISIN4-100A-2.1 NDE-35 PT SS 0:281 / 1.500 B09.040.00l Socket Pipe to Elbow Category B-K 02.B1310.20.0008 2-53A-0-1 478A-Hl1A Class 1 53A 0-14920-2(5)

Spring Hgr 0-ISIN4-102A-2.3 2-53-1 3/sht. 1 NDE-35 PT NA 2.000 /14.000 B1 0.020.03;Calculation No. OSC-1318.Inspect with F01 .0120.031.

Category B-M-1I 02.B112.30.0001 Circumferential 2-51A-HP-126 Class 1 53A OM-245-1910 0-ISIN4-101A-2.4 NDE-35 PT SS 0.000 / 2.500 B12.030.00' Body to Bonnet Extension Valve 2HP-126 Body to Bonnet Extension Weld. Inspect one of the following valves: 2HP-126, 2HP-127, 2HP-152, or 2HP-153.Printed 07/14/10 Ick8302 v. 06/18/09 SDQA Cat "C" Oconee 2 7/14/2010 2:17:26 PM Page 50 of 79 This report includes all changes through addendum ONS2-107 Oconee 2, 4th Interval, outage 4 (EOC-24)Summary Num Component ID ISOIDWG Numbers Class I System Procedure Insp Req Material Sched Description Comments Thick/NPS Cal Blocks Componenet ID 2 Category C-C 02.C3.20.0004 Constant Support 2-01A-0-1481B-H 1 B Class 2 01A 2-01-08/sht.1 0-ISIN4-122A-2.1 NDE-25 MT CS 2.000 / 36.000 C03.020.00i Calculation No. OSC-1315.

Inspect with F01.022.002.

02.C3.20.0016 Spring Hgr 2-51A-435B-DKB-1411 Class 2 51A 0-2AB-25102-02 O-ISIN4-101A-2.3 NDE-35 PT SS 0.226 / 6.000 C03.020.03, Calculation No. OSC-481. Inspect with F01.022.042.

02.C3.20.0029 Spring Hgr 02.C3.20.0034 Rigid Support 2-54A-3-0-435B-H25 Class 2 54A 2-54-1/sht.1 0-ISIN4-103A-2.1 NDE-35 PT SS 0.216 / 8.000 C03.020.05" Calculation No. OSC-494. Inspect with F01 .022.061.2-54A-3-0-1439C-H5 Class 2 54A 2-54-03/sht.1 0-ISIN4-103A-2.1 NDE-35 PT SS-CS 1.000 / 8.000 C03.020.05(Calculation No. OSC-496. Inspect with F01.020.096.

Category C-F-I 02.C5.11.0009 2LP-150-39 Class 2 53A 2LP-150 0-ISIN4-102A-2.3 PDI-UT-2 UT SS 1.125 / 10.000 Component PDI-UT-2-0 PDI-UT-2A-O C05.011.009, C05.011.009, Circumferential Pipe to Elbow Procedure NDE-600 uses the component for calibration.

Procedure PDI-UT-2 may be used in lieu of procedure NDE-600. If PDI-UT-2 is used, then the calibration block listed shall be used. This weld was listed previously as 2-53A-9-39 until iso 2-53A-9 was redrawn.Code N-663 allows us to exclude the surface exam from the Fourth Interval ISI Plan. See PIP G-08-00185 (CA # 7) for details on the exclusion of surface exams.SDQA Cat "C" Oconee 2 7/14/2010 2:17:26 PM Page 51 of 79 Printed 07/14/10 Ick8302 v. 06/18/09 This report includes all changesrough addendum ONS2-107 Oconee 2, 4th Interval, outage 4 (EOC-24)Summary Num Component ID ISO/DWG Numbers Class I System Procedure Insp Req Material Sched ThickfNPS Description Comments Ca" Blocks Componenet ID 2 Category C-F-I 02.C5.1 1.0010 2LP-150-40 Class 2 53A 2LP-150 O-ISIN4-102A-2.3 PDI-UT-2 UT SS 1.125/10.000 Component PDI-UT-2-O PDI-UT-2A-O C05011.010, C05.011.010/

Circumferential Pipe to Elbow Procedure NDE-600 uses the component for calibration.

Procedure PDI-UT-2 may be used in lieu of procedure NDE-600. If PDI-UT-2 is used, then the calibration block listed shall be used. This weld was listed previously as 2-53A-9-40 until iso 2-53A-9 was redrawn.Code N-663 allows us to exclude the surface exam from the Fourth Interval ISI Plan. See PIP G-08-00185 (CA# 7) for details on the exclusion of surface exams.02.C5.11.0013 2LP-148-89 Class 2 53A 2LP-148 O-ISIN4-102A-2.2 Circumferential 02.C5.11.0014 2LP-148-92 Class 2 53A, 2LP-148, O-lSIN4-102A-2.2 PDI-UT-2 UT SS 160 1.125/10.000 Component PDI-UT-2-O PDI-UT-2A-O C05.011.013, C05.011.0131 Pipe to Reducer Procedure NDE-600 uses the component for calibration.

Procedure PDI-UT-2 may be used in lieu of procedure NDE-600. If PDI-UT-2 is'used, then the calibration block listed shall be used.Code N-663 allows us to exclude the surface exam from the Fourth Interval ISI Plan. See PIP G-08-00185 (CA # 7) for details on the exclusion of surface exams.PDI-UT-2 UT SS 160 1.125 / 10.000 Component PDI-UT-2-O PDI-UT-2A-O C05.011.014, C05.011.014i Circumferential Pipe to Elbow Procedure NDE-600 uses the component for calibration.

Procedure PDI-UT-2 may be used in lieu of procedure NDE-600. If PDI-UT-2 is used, then the calibration block listed shall be used.Code N-663 allows us to exclude the surface exam from the Fourth Interval ISI Plan. See PIP G-08-00185 (CA # 7) for details on the exclusion of surface exams.Printed 07/14/10 Ick8302 v. 06/18/09 SDQA Cat "C" Oconee 2 7/14/2010 2:17:26 PM Page 52 of 79 This report includes all changes through addendum ONS2-107 Oconee 2, 4th Interval, outage 4 (EOC-24)Summary Num Component ID ISOIDWG Numbers Class I System Procedure Insp Req Material Sched Description Comments Thick/NPS Cal Blocks Componenet ID 2 Category C-F-1 02.C5.11.0037 2LP-215-2 Class 2-- 53A 2LP-215 O-ISIN4-102A-2.3 PDI-UT-2 UT SS 1.000 /10.000 Component PDI-UT-2-0 PDI-UT-2A-O C05.011.037, C05.011.037, Circumferential Pipe to Tee Procedure NDE-600 uses the component for calibration.

Procedure PDI-UT-2 may be used in lieu of procedure NDE-600. If PDI-UT-2 is used, then the calibration block listed shall be used.Code N-663 allows us to exclude the surface exam from the Fourth Interval ISI Plan. See PIP G-08-00185 (CA # 7) for details on the exclusion of surface exams.02.C5.11.0038 2LP-215-27 Class2 53A 2LP-215 0-ISIN4-102A-2.3 PDI-UT-2 UT SS 1.000 / 10.000 Component PDI-UT-2-0 PDI-UT-2A-O C05.011.038, C05.011.038f Circumferential Pipe to Valve 2LP-177 Procedure NDE-600 uses the component for calibration.

Procedure PDI-UT-2 may be used in lieu of procedure NDE-600. If PDI-UT-2 is used, then the calibration block listed shall be used.Code N-663 allows us to exclude the surface exam from the Fourth Interval ISI Plan. See PIP G-08-00185 (CA # 7) for details on the exclusion of surface exams.02.C5.11.0039 2LP-215-3 Class 2 53A 2LP-215 0-ISlN4-102A-2.3 PDI-UT-2 UT SS 1.000 / 10.000 Component PDI-UT-2-0 PDI-UT-2A-O C05.011.039, C05.011.0391 Circumferential Tee to Pipe Procedure NDE-600 uses the component for calibration.

Procedure PDI-UT-2 may be used in lieu of procedure NDE-600. If PDI-UT-2 is used, then the calibration block listed shall be used.Code N-663 allows us to exclude the surface exam from the Fourth Interval IS Plan. See PIP G-08-00185 (CA # 7) for details on the exclusion of surface exams.Printed 07/14/10 Ick8302 v. 06/18/09 SDQA Cat "C" Oconee 2 7/14/2010 2:17:26 PM Page 53 of 79 This report includes all changeshrough addendum ONS2-107 Oconee 2, 4th Interval, outage 4 (EOC-24).Summary Num Component ID ISOIDWG Numbers Crass I System Procedure Insp Req Material Sched Description Comments Thick/NPS Cal Blocks Componenet ID 2 Category C-F-I 02.C5.11.0040 2LP-215-5 Class 2 53A 2LP-215 0-ISIN4-102A-2.3 NDE-600 UT SS 1.000/10.000 Component PDI-UT-2-0 PDI-UT-2A-O C05.011.040, C05.011.040, Circumferential Pipe to Elbow Procedure NDE-600 uses the component for calibration.

Procedure PDI-UT-2 may be used in lieu of procedure NDE-600. If PDI-UT-2 is used, then the calibration block listed shall be used.Code N-663 allows us to exclude the surface exam from the Fourth Interval ISI Plan. See PIP G-08-00185 (CA # 7) for details on the exclusion of surface exams.02.C5.11.0041 2LP-215-6 Class 2 53A 2LP-215 NDE-600 UT SS 0-ISIN4-102A-2.3 1.000 / 10.000 Component PDI-UT-2-0 PDI-UT-2A-O C05.011.041, C05.011.041, Circumferential Elbow to Pipe Procedure NDE-600 uses the component for calibration.

Procedure PDI-UI-2 may be used in lieu of procedure NDE-600. If PDI-UT-2 is used, then the calibration block listed shall be used.Code N-663 allows us to exclude the surface exam from the Fourth Interval ISI Plan. See PIP G-08-00185 (CA # 7) for details on the exclusion of surface exams.02.C5.11.0042 2LP-215-9 Class 2 53A 2LP-215 0-ISIN4-102A-2.3 PDI-UT-2 UT SS 1.000 /10.000 Component PDI-UT-2-0 PDI-UT-2A-O C05.011.042, C05.011.042, Circumferential Tee to Pipe Procedure NDE-600 uses the component for calibration.

Procedure PDI-UT-2 may be used in lieu of procedure NDE-600. If PDI-UT-2 is used, then the calibration block listed shall be used.Code N-663 allows us to exclude the surface exam from the Fourth Interval ISI Plan. See PIP G-08-00185 (CA # 7) for details on the exclusion of surface exams.Printed 07/14/10 Ick8302 v. 06/18/09 SDQA Cat "C" Oconee 2 7/14/2010 2:17:26 PM Page 54 of 79 This report includes all changes through addendum ONS2-107 Oconee 2, 4th Interval, outage 4 (EOC-24)0 Summary Num ComponentlD, ISO/DWGNumbers Class I System Procedure Insp Req Material Sched Description Comments Thick/NPS Cal Blocks Componenet ID 2 Category C-F-I 02.C5.11.0043 2LP-216-1 Class 2 53A 2LP-216 NDE-600 UT SS 1.000 / 10.000 Component C05.011.043, 0-ISIN4-102A-2.3 PDI-UT-2-0 C05.011.043, PDI-UT-2A-0 Circumferential Pipe to Elbow Procedure NDE-600 uses the component for calibration.

Procedure PDI-UT-2 may be used in lieu of procedure NDE-600. If PDI-UT-2 is used, then the calibration block listed shall be used.Code N-663 allows us to exclude the surface exam from the Fourth Interval ISI Plan. See PIP G-08-00185 (CA # 7) for details on the exclusion of surface exams.02.C5.11.0044 2 LP:216-10 Class 2 53A 2LP-216 0-ISIN4-102A-2.3 PDI-UT-2 UT SS 1.000 / 10.000 Component PDI-UT-2-0 PDI-UT-2A-O C05.011.044, C05:011.044/

Circumferential Elbow to Pipe Procedure NDE-600 uses the component for calibration.

Procedure PDI-UT-2 may be used in lieu of procedure NDE-600. If PDI-UT-2 is used, then the calibration block listed shall be used.Code N-663 allows us to exclude the surface exam from the Fourth Interval ISI Plan. See PIP G-08-00185 (CA # 7) for details on the exclusion of surface exams.02.C5.11.0045 2LP-216-14 Class 2 53A 2LP-216 0-ISIN4-102A-2.3 PDI-UT-2 UT SS 1.000/10.000 Component PDI-UT-2-0 PDI-UT-2A-0 C05.011.045, C05.011.045, Circumferential Pipe to Elbow Procedure NDE-600 uses the component for calibration.

Procedure PDI-UT-2 may be used in lieu of procedure NDE-600. If PDI-UT-2 is used, then the calibration block listed shall be used.Code N-663 allows us to exclude the surface exam from the Fourth Interval ISI Plan. See PIP G-08-00185 (CA # 7) for details on the exclusion of surface exams.Printed 07/14/10 Ick8302 v. 06/18/09 SDQA Cat "C" Oconee 2 7/14/2010 2:17:26 PM Page 55 of 79 This report includes all changes through addendum ONS2-107 Oconee 2, 4th Interval, outage 4 (EOC-24)Summary Num Component ID ISO/DWG Numbers Class I System Procedure Insp Req Material Sched Thick/NPS Description Comments Cal Blocks Componenet ID 2 Category C-F-I 02.C5.11.0046 2LP-216-15 Class 2 53A 2LP-216 0-ISIN4-102A-2.3 PDI-UT-2 UT SS 1.000 /10.000 Component PDI-UT-2-0 PDI-UT-2A-0 C05.011.046, C05.011.046?

Circumferential Elbow to Pipe Procedure NDE-600 uses the component for calibration.

Procedure PDI-UT-2 may be used in lieu of procedure NDE-600. If PDI-UT-2 is used, then the calibration block listed shall be used.Code N-663 allows us to exclude the surface exam from the Fourth Interval ISI Plan. See PIP G-08-00185 (CA # 7) for details on the exclusion of surface exams.02.C5.11.0070 2LPS-724-1 Class 2 14B 2LPS-724 0-ISIN4-124B-2.2 PDI-UT-2 UT SS 0.432 / 6.000 Component PDI-UT-2-0 PDI-UT-2A-0 C05.011.070, C05.011.070?

Circumferential Pipe to Elbow Procedure NDE-600 uses the component for calibration.

Procedure PIJI-UT-2 may be used in lieu of procedure NDE-600. If PDI-UT-2 is used, then the calibration block listed shall be used.Code N-663 allows us to exclude the surface exam from the Fourth Interval ISI Plan. See PIP G'08-00185 (CA # 7) for details on the exclusion of surface exams.02.C5.11.0075 2LPS-724-17 Class 2 14B 2LPS-724 0-ISIN4-124B-2.2 PDI-UT-2 UT SS 0.432 / 6.000 Component PDI-UT-2-0 PDI-UT-2A-0 C05.011.075, C05.011.075/

Circumferential Elbow to Pipe Procedure NDE-600 uses the component for calibration.

Procedure PDI-UT-2 may be used in lieu of procedure NDE-600. If PDI-UT-2 is used, then the calibration block listed shall be used.Code N-663 allows us to exclude the surface exam from the Fourth Interval ISI Plan. See PIP G-08-00185 (CA # 7) for details on the exclusion of surface exams.Printed 07/14/10 Ick8302 v. 06/18/09 SDQA Cat "C" Oconee 2 7/14/2010 2:17:26 PM Page 56 of 79 This report includes all changes through addendum ONS2-107 Oconee 2, 4th Interval, outage 4 (EOC-24)Summary Num Component ID ISO/DWG Numbers Class / System Procedure Insp Req Material Sched Description Comments Thick/NPS Cal Blocks Componenet ID 2 Category C-F-I 02.C5.11.0077 2LPS-724-2 Class 2 14B 2LPS-724 0-ISIN4-124B-2.2 PDI-UT-2 UT SS 0.432 / 6.000 Component PDI-UT-2-0 PDI-UT-2A-O C05.011.077, C05.011.077, Circumferential Elbow to Elbow.Procedure NDE-600 uses the component for calibration.

Procedure PDI-UT-2 may be used in lieu of procedure NDE-600. If PDI-UT-2 is used, then the calibration block listed shall be used.Code N-663 allows us to exclude the surface exam from the Fourth Interval ISI Plan. See PIP G-08-00185 (CA # 7) for details on the exclusion of surface exams.02.C5.21.0033 2HP-222-106AA Class 2 51A 2HP-222 0-ISIN4-101A-2.4 PDI-UT-2 UT SS 0.674 / 4.000 Component PDI-UT-2-0 PDI-UT-2A-O C05.021.041, C05.021.041, Circumferential Elbow to Tee Procedure NDE-600 uses the component for calibration.

Procedure PDI-UT-2 may be used in lieu of procedure NDE-600. If PDI-UT-2 is used, then the calibration block listed.shall be used. This weld was listed previously as 2-51A-28-106AA until iso 2-51A-28(2) was deleted and this weld was transferred to iso 2HP-222.Code N-663 allows us to exclude the surface exam from the Fourth Interval ISI Plan. See PIP G-08-00185 (CA # 7) for details on the exclusion of surface exams.02.C5.21.0034 2HP-222-106C Class 2 51A 2HP-222 0-ISIN4-101A-2.4 PDI-UT-2 UT SS 0.674 / 4.000 Component PDI-UT-2-0 PDI-UT-2A-0 C05.021.042, C05.021.042, Circumferential Tee to Pipe Procedure NDE-600 uses the component for calibration.

Procedure PDI-UT-2 may be used in lieu of procedure NDE-600. If PDI-UT-2 is used, then the calibration block listed shall be used. This weld was listed previously as 2-51A-28-106C until iso 2-51A-28(2) was deleted and this weld was transferred to iso 2HP-222.Code N-663 allows us to exclude the surface exam from the Fourth Interval ISI Plan. See PIP G-08-00185 (CA # 7) for details on the exclusion of surface exams.Printed 07/14/10 Ick8302 v. 06/18/09 SDQA Cat "C" Oconee 2 7/14/2010 2:17:26 PM Page 57 of 79 0 This report includes all changes hrough addendum ONS2-107 Oconee 2, 4th Interval, outage 4 (EOC-24)Summary Num Component ID ISO/DWG Numbers Class / System Procedure Insp Req Material Sched Description Comments Thick/NPS Cal Blocks Componenet ID 2 Category C-F-I 02.C5.21.0035 2HP-341-V1 Class 2 51A 2HP-341 0-ISIN4-101A-2.4 PDI-UT-2 UT SS 0.375 / 2.500 Component PDI-UT-2-0 PDI-UT-2A-0 C05.021.043, C05.021.043, Circumferential Valve 2HP-120 to Pipe Procedure NDE-600 uses the component for calibration.

Procedure PDI-UT-2 may be used in lieu of procedure NDE-600. If PDI-UT-2 is used, then the calibration block listed shall be used. This weld used to be listed as 2-51A-28-80A and was shown on isometric 2-51A-28 (2). This weld is a vendor weld joining valve 2HP-120.Code N-663 allows us to exclude the surface exam from the Fourth Interval ISI Plan. See PIP G-08-00185 (CA # 7) for details on the exclusion of surface exams.02.C5.21.0036 2-51A-28-65 Class 2 51A 2-51A-28 (3)0-ISIN4-101A-2.4 PDI-UT-2 UT SS 0.531 / 4.000 Component PDI-UT-2-0 PDI-UT-2A-0 C05.021.044, C05.021.044, Circumferential Pipe to Tee Procedure NDE-600 uses the component for calibration.

Procedure PDI-UT-2 may be used in lieu of procedure NDE-600. If PDI-UT-2 is used, then the calibration block listed shall be used.Code N-663 allows us to exclude the surface exam from the Fourth Interval iSI Plan. See PIP G-08-00185 (CA # 7) for details on the exclusion of surface exams.02.C5.21.0051 2-51A-17-97 Class 2 51A 2-51A-17 (2)0-ISIN4-101A-2.2 PDI-UT-2 UT SS 0.375 / 2.500 Component PDI-UT-2-0 PDI-UT-2A-0 C05.021.061, C05.021.0611 Circumferential Pipe to Elbow Procedure NDE-600 uses the component for calibration.

Procedure PDI-UT-2 may be used in lieu of procedure NDE-600. If PDI-UT-2 is used, then the calibration block listed shall be used.Code N-663 allows us to exclude the surface exam from the Fourth Interval ISI Plan. See PIP G-08-00185 (CA # 7) for details on the exclusion of surface exams.Printed 07/14/10 Ick8302 v. 06/18/09 SDQA Cat "C" Oconee 2 7/14/2010 2:17:26 PM Page 58 of 79 This report includes all changestrough addendum ONS2-107 Oconee 2, 4th Interval, outage 4 (EOC-24)Summary Num Component ID ISO/DWG Numbers Class I System Procedure

.Insp Req Material Sched Description Comments Thick/NPS Cal Blocks Componenet ID 2 Category C-F-1 02.C5.21.0053 2-51A-17-98B Class 2 51A 2-51A-17 (2)0-ISIN4-101A-2.2 PDI-UT-2 UT SS 0:375 / 2.500 Component PDI-UT-2-0 PDI-UT-2A-O C05.021.063, C05.021.063/

Circumferential Elbow to Pipe Procedure NDE-600 uses the component for calibration.

Procedure PDI-UT-2 may be used in lieu of procedure NDE-600. If PDI-UT-2 is used, then the calibration block listed shall be used.Code N-663 allows 'us to exclude the surface exam from the Fourth Interval ISI Plan. See PIP G-08-00185 (CA # 7) for details on the exclusion of surface exams.02.C5.21.0054 2-51A-17-98D Class 2 51A 2-51A-17 (2)0-ISIN4-101A-2.2 PDI-UT-2 UT SS 0.375 / 2.500 Component PDI-UT-2-0 PDI-UT-2A-0 C05.021.064, C05.021.064, Circumferential Elbow to Pipe Procedure NDE-600 uses the component for calibration.

Procedure PDI-UT-2 may be used in lieu of procedure NDE-600. If PDI-UT-2 is used, then the calibration block listed shall be used.Code N-663 allows us to exclude the surface exam from the Fourth Interval ISI Plan. See PIP G-08-00185 (CA # 7) for details on the exclusion of surface exams., 02.C5.2,1.0489 Circumferential 2-51A-17-96 Class 2 51A 2-51A-17 (2)0-ISIN4-101A-2.2 PDI-UT-2 UT SS 0.375 7 2.500 PDI-UT-2-0 PDI-UT-2A-0 C05.021 Elbow to Pipe Code N-663 allows us to exclude the surface exam from the Fourth Interval ISI Plan. See PIP G-08-00185 (CA # 7) for details on the exclusion of surface exams.Printed 07/14/10 Ick8302 v. 06/18/09 SDQA Cat "C" Oconee 2 7/14/2010 2:17:26 PM Page 59 of 79 0 This report includes all changes 9 rough addendum ONS2-107 Oconee 2, 4th Interval, outage 4 (EOC-24)Summary Num Category C-F-2 02.C5.51.0005 ComponentlD.

ISO/DWGNumbers Class I System 2MS-123-27 Class 2 01A 2MS-123 0-ISIN4-122A-2.1 Procedure Insp Req Material Sched Description Comments Thick/NPS Cal Blocks Componenet ID 2 PDI-UT-1 UT CS 0.875 / 26.000 Component PDI-UT-1 -0 PDI-UT-iA-C C05.051.005, C05.051.005/

Circumferential Pipe to Elbow Procedure NDE-600 uses the component for calibration.

Procedure PDI-UT-1 may be used in lieu of procedure NDE-600. If PDI-UT-1 is used, then the calibration block listed shall be used. This weld was listed previously as 2-01A-5-27 on iso 2-01A-5 (4)until it was transferred to iso 2MS-123.Code N-663 allows us to exclude the surface exam from the Fourth Interval ISI Plan. See PIP G-08-00185 (CA # 7) for details on the exclusion of surface exams.02.C5.51.0006 2MS-103-9 Class 2 01A 2MS-103 O-ISIN4-122A-2.1 PDI-UT-1 UT CS 0.906 / 8.000 Component PDI-UT-1-0 PDI-UT-1A-O C05.051.006, C05.051.006, Circumferential Pipe to Valve 2MS-2 Procedure NDE-600 uses the component for calibration.

Procedure PDI-UT-1 may be used in lieu of procedure NDE-600. If PDI-UT-1 is used, then the calibration block listed shall be used.Code N-663 allows us to exclude the surface exam from the Fourth Interval ISI Plan. See PIP G-08-00185 (CA # 7) for details on the exclusion of surface exams.02.C5.51.0014 2FDW-210-21 Class 2 03A 2FDW-210 O-)SIN4-121D-2.1 PDI-UT-1 UT CS 0.432 / 6.000 Component PDI-UT-1-C PDI-UT-iA-C C05.051.014, C05.051.014/

Circumferential Pipe to Elbow Procedure NDE-600 uses the component for calibration.

Procedure PDI-UT-1 may be used in lieu of procedure NDE-600. If PDI-UT-1 is used, then the calibration block listed shall be used. This weld was 'originally identified as 2-03A-10-21 until iso was changed from 2-03A-10 to 2FDW-210.Code N-663 allows us to exclude the surface exam from the Fourth Interval ISI Plan. See PIP G-08-00185 (CA # 7) for details on the exclusion of surface exams.Printed 07/14/10 Ick8302 v. 06/18/09 SDQA Cat "C" Oconee 2 7/14/2010 2:17:26 PM Page 60 of 79 S This report includes all changesqrough addendum ONS2-107 Oconee 2, 4th Interval, outage 4 (EOC-24)0 Summary Num Component ID ISO/DWG Numbers Class / System Procedure Insp Req Material Sched Thick/NPS Description Comments Cal Blocks Componenet ID 2 Category C-F-2 02.C5.51.0018 2-03A-67-7 Class 2 03A 2-03A-67 O-ISIN4-121 D-2.1 NDE-600 UT CS 0.562 / 6.000 Component PDI-UT-1-0 PDI-UT-1A-O C05.051.018, C05.051.018, Circumferential Pipe to Elbow Procedure NDE-600 uses the component for calibration.

Procedure PDI-UT-1 may be used in lieu of procedure NDE-600. If PDI-UT-1 is used, then the calibration block listed shall be used.Code N-663 allows us to exclude the surface exam from the Fourth Interval ISI Plan. See PIP G-08-00185 (CA # 7) for details on the exclusion of surface exams.02.C5.51.0022 2FDW-226-37 Class 2 03 2FDW-226 O-ISIN4-121 B-2.3 PDI-UT-1 UT CS 1-.031 / 20.000 Component PDI-UT-1-0 PDI-UT-1A-C C05.051.022, C05.051.022/

Circumferential Elbow to Pipe Procedure NDE-600 uses the component for calibration.

Procedure PDI-UT-1 may be used in lieu of procedure NDE-600. If PDI-UT-1 is used, then the calibration block listed shall be used. This weld used to be listed as 2-03-18-37 and was shown on isometric 2-03-18 (2).Code N-663 allows us to'exclude the surface exam from the Fourth Interval ISI Plan. See PIP G-08-00185 (CA # 7) for details on the exclusion of surface exams.02.C5.51.0035 2LPS-606-2 Class 2 14B 2LPS-606 O-ISIN4-124B-2.2 PDI-UT-1 UT CS 0.500 / 8.000 Component PDI-UT-1-0 PDI-UT-1A-O C05.051.035, C05.051.035i Circumferential Pipe to Elbow Procedure NDE-600 uses the component for calibration.

Procedure PDI-UT-1 may be used in lieu of procedure NDE-600. If PDI-UT-1 is used, then the calibration block listed shall be used. This weld was listed previously as 2-14B-51-2 until iso 2-14B-51 was redrawn.Code N-663 allows us to exclude the surface exam from the Fourth Interval ISI Plan. See PIP G-08-00185 (CA # 7) for details on the exclusion of surface exams.Printed 07/14/10 Ick8302 v. 06/18/09 SDQA Cat "C" Oconee 2 7/14/2010 2:17:26 PM Page 61 of 79_9 This report includes all changeqsrough addendum ONS2-107 Oconee 2, 4th Interval, outage 4 (EOC-24)Summary Num Component ID " ISO/DWG Numbers Class I System Procedure Insp Req Material Sched Description Comments Thick/NPS Cal Blocks Componenet ID 2 Category C-F-2 02.C5.51.0036 2LPS-606-3 Class 2 14B 2LPS-606 0-ISIN4-124B-2.2 PDI-UT-1 UT CS 0.500 / 8.000 Component PDI-UT-1-0 PDI-UT-1A-0 C05.051.036, C05.051.036?

Circumferential Elbow to Pipe Procedure NDE-600 uses the component for calibration.

Procedure PDI-UT-1 may be used in lieu of procedure NDE-600. If PDI-UT-1 is used, then the calibration block listed shall be used. This weld was listed previously as 2-14B-51-3 until iso 2-143-51 was redrawn.Code N-663 allows us to exclude the surface exam from the Fourth Interval ISI Plan. See PIP G-08-00185 (CA # 7) for details on the exclusion of surface exams.02.C5.51.0038 2LPS-606-82 Class 2 14B 2LPS-606 O-ISIN4-124B8-2.2 PDI-UT-1 UT CS°0.500 / 8.000 Component PDI-UT-1 -0 PDI-UT-1A-0 C05.051.038, C05.051.038/

Circumferential Elbow to Tee Procedure NDE-600 uses the component for calibration.

Procedure PDI-UT-1 may be used in lieu of procedure NDE-600. If PDI-UT-1 is used, then the calibration block listed shall be used. This weld was listed previously as 2-14B-51-82 until iso 2-14B-51 was redrawn.Code N-663 allows us to exclude the surface exam from the Fourth Interval ISI Plan. See PIP G-08-00185 (CA # 7) for details on the exclusion of surface exams.02.C5.51.0042 2FDW-226-36 Class 2 03 2FDW-226 O-ISIN4-121 B-2.3 PDI-UT-1 UT CS 1.031 / 20.000 Component PDI-UT-1 -0 PDI-UT-1A-0 C05.051.042, C05.051.042?

Circumferential Pipe to Elbow Procedure NDE-600 uses the component for calibration.

Procedure PDI-UT-1 may be used in lieu of procedure NDE-600. If PDI-UT-1 is used, then the calibration block listed shall be used. This weld used to be listed as 2-03-18-36 and was shown on isometric 2-03-18 (2).Code N-663 allows us to exclude the surface exam from the Fourth Interval /SI Plan. See PIP G-08-00185 (CA # 7) for details on the exclusion of surface exams.Printed 07/14/10 Ick8302 v. 06/18/09 SDQA Cat "C" Oconee 2 7114/2010 2:17:26 PM Page 62 of 79 0 This report includes all change~s"rough addendum ONS2-107 Oconee 2, 4th Interval, outage 4 (EOC-24)0 Summary Num Component ID ISOIDWG Numbers Class I System Procedure Insp Req Material Sched Thick/NPS Description Comments Cal Blocks Componenet ID 2 Category C-F-2 02.C5.51.0053 2-03-18-44AA Class 2 03 2-03-18 (2)0-ISIN4-121 B-2.3 PDI-UT-1 UT CS 1.219/24.000 Component PDI-UT-1-0 PDI-UT-1A-O C05.051.053, C05.051.0531 Circumferential Pipe to Valve 2FDW-37 Procedure NDE-600 uses the component for calibration.

Procedure PDI-UT-1 may be used in lieu of procedure NDE-600. If PDI-UT-1 is used, then the calibration block listed shall be used.Code N-663 allows us to exclude the surface exam from the Fourth Interval ISI Plan. See PIP G-08-00185 (CA # 7) for details on the exclusion of surface exams.02.C5.61.0004 Circumferential 2-14-238-24 Class 2 03A 2-14-238 NDE-12 RT SS-CS 0.674 / 4.000 C05,061.004,.C05.061.004i 0-ISIN4-121 D-2.1 OM 245-1856 Reducer to Valve 2CCW-269 (Cast SS)Cast Stainless Steel Valve Body Code N-663 allows us to exclude the surface exam from the Fourth Interval ISI Plan. See PIP G-08-00185 (CA # 7) for details on the exclusion of surface exams.Category D-A 02.D1.20.0004 Hyd Snubber 2-03-0-1401A-R7 Class 3 03 2-03-01/sht.1 0-ISIN4-121 B-2.3 NDE-65 VT-1 NA'1.000 / 24.000 D01.020.01 (Calculation No. 0S0-454. Inspect with F01 .032.012.02.D1.20.0009 Rigid Support 2-03A-0-1400A-MDH-1101 Class 3 03A 0-2TB-203A12-01 0-ISIN4-121D-2.1 NDE-65 VT-I NA 0.500 / 6.000 D01.020.01!

Calculation No. OSC-1 213. Inspect with F01 .030.027.02.D1.20.0027 Rigid Restraint 2-57-0-1481A-H4 Class 3 57 0-2RB-25701-01

-,O-ISIN4-107A-2.1 NDE-65 VT-1 NA 1.000 / 12.000 D01.020.07,'

Calculation No. OSC-1332-06.

Inspect with F01.031.071.

Printed 07/14/10 Ick8302 v. 06/18/09 SDQA C-at "'C" Pconee 2 7/14/2010 2:17:26 PM Page 63 of 79 This report includes all change rough addendum ONS2-107 Oconee 2, 4th Interval, outage 4 (EOC-24)0 Summary Num Category ELC 02.H3,1.0007 Circumferential Component ID ISO/DWG Numbers Class I System Procedure Insp Req Material Sched Description Comments Thick/NPS Cal Blocks Componenet ID 2 2-03-18-25 Class 3 03 2-03-18 (1)O-ISIN4-121 B-2.3 NDE-946 UT CS 1.219 / 24.000 H03.001.00; Pipe to Elbow Procedure NDE-600 should be used for angle beam inspection and Procedure NDE-946 should be used for thickness measurements on this weld.PDI-UT -1 may be used in lieu of NDE-600 with cal block PDI-UT-1-O.

Inspection results should be forwarded to Timothy D. Brown of the Oconee Design Basis Group.02.H3.1.0008 Circumferential 2-03-18-25G Class 3 03 2-03-18 (1)O-ISIN4-121 B-2.3 NDE-946 UT CS 1.219 / 24.000 H03.001.001 Elbow to Pipe ,Weld 2-03-18-25 is a Pipe to elbow weld located on iso 2-03-18(1).

Weld 2-03-18-25G is a Grinnell Subassembly (elbow to pipe) weld located on the opposite end of the elbow from weld 1-03-18-25 Procedure NDE-600 should be used for angle beam inspection and Procedure NDE-946 should be used for thickness measurements on this weld.PDI-UT 11 may be used in lieu of NDE-600 with cal block PDI-UT-1-O.

Inspection results should be forwarded to Timothy D. Brown of the Oconee Design Basis Group.02.H3.1.0009 2-03-18-43A Class 2 03 2-03-18 (2)O-ISIN4-121 B-2.3 NDE-946 UT CS 1.219 / 24.000 H03.0011.00, Circumferential Pipe to Elbow Procedure NDE-600 should be used for angle beam inspection and Procedure NDE-946 should'be used for thickness measurements on this weld.Inspection results should be forwarded to Timothy D. Brown of the Oconee Design Basis Group.02.H3.1.0010 Circumferential 2-FWD60-A Class 2 03 2-03-,18 (2)O-ISIN4-121 B-2.3 NDE-946 UT CS 1.219 / 24.000 H03.001.01(Elbow to Pipe Weld 2-03-18-43AA is a Pipe to elbow weld located on iso 2-03-18(2).

Weld 2-FWD60-A is a Grinnell Subassembly (elbow to pipe) weld located on the opposite end of the elbow from weld 1-03-18-43AA.

Procedure NDE-600 should be used for angle beam inspection and Procedure NDE-946 should be used for thickness measurements on this weld.Inspection results should be forwarded to Timothy D. Brown of the Oconee Design Basis Group.Printed 07/14/10,lck8302

v. 06/18/09, SDQA Cat "C" Oconee 2 7/14/2010 2:17:26 PM Page 64 of 79 This report includes all changestrough addendum ONS2-107 Oconee 2, 4th Interval, outage 4 (EOC-24)rs Procedure lnsp Req Material Sched Thick/NPS Description Comments 0 Summary Num Category ELC 02.H3.1.0011 Circumferential Component ID ISO/DWG Numbe Class I System 2-03-18-43AA Class 2 03 2-03-18 (2)O-ISIN4-121 B-2.3 Cal Blocks Componenet ID 2 NDE-946 UT CS 1.219 / 24.000 H03.001.01' Pipe to Elbow Procedure NDE-600 should be used for angle beam inspection and Procedure NDE-946 should be used for thickness measurements on this weld.Inspection results should be forwarded to Timothy D. Brown of the Oconee Design Basis Group.02.H4.1.0002 Rigid Support 2-03-0-1439B-H54 Class 3 03 2-01-03/sht.1 O-ISIN4-121 B-2.3 NDE-66 VT-3 NA 0.000 / 24.000 H04:001.00, Calculation No. OSC-454.Inspect with item number F01 .030.020.02.H4.1.0008 Hyd Snubber 2-03-0-1401A-R7 Class 3 03 2-03-01/sht.1 O-ISIN4-121 B-2.3 NDE-25 MT CS 1.000 / 24.000 H04.001.008, H04.001.008; Calculation No. OSC-454. Inspect with D01.020.010 and F01.032.012

-- (H04.001.008A)

Perform a Surface exam on the attachment welds.Note: Magnetic Particle examinations (with the use of procedure NDE-25) may be performed on carbon steel material in lieu of or in conjunction with liquid penetrant examinations.

02.H4.1.0008 Hyd Snubber 2-03-0-1401A-R7 Class 3 03 2-03-01/sht.1 O-ISIN4-121 B-2.3 NDE-66 VT-3 CS 1.000 / 24.000 H04.001.008, H04.001.008/

Calculation No. OSC-454. Inspect with D01.020.010 and F01.032.012

-- (H04.001.008A)

Perform a Surface exam on the attachment welds.Note: Magnetic Particle examinations (with the use of procedure NDE-25) may be performed on carbon steel material in lieu of or in conjunction with liquid penetrant examinations.

Printed 07/14/10 Ick8302 v. 06/18/09 SDQA Cat "C" Oconee 2 7/14/2010 2:17:26 PM Page 65 of 79 This report includes all changesfrough addendum ONS2-107 Oconee 2, 4th Interval, outage 4 (EOC-24)Summary Num Component ID ISO/DWG Numbers Class I System Procedure Insp Req Material Sched Description Comments Thick/NPS Cal Blocks Componenet ID 2 Category ELC 02.H4.1-.0032 Mech Snubber 2-01A-0-1401B-R6 Class 2 01A 2-01-01/sht.2 NDE-25 MT CS 1.000 / 36.000 H04.001.032, H04.001.032i O-ISIN4-122A-2.1 Calculation No. OSC-440.-- (H04.001.032A)

Perform a Surface exam on the attachment welds.Note: Magnetic Particle examinations (with the use of procedure NDE-25) may be performed on carbon steel material in lieu of or in conjunction with liquid penetrant examinations.

02.H4,1-.0032 2-01A-0-1401 B-R6 Class 2 01A 2-01-01/sht.2 NDE-66 VT-3 CS 1.000 / 36.000 H04.001.032, H04.001.032, Mech Snubber 0-ISIN4-122A-2.1 Calculation No. OSC-440.(H04.001.032A)

Perform a Surface exam on the attachment welds.Note: Magnetic Particle examinations (with the use of procedure NDE-25) may be performed on carbon steel material in lieu of or in conjunction with liquid penetrant examinations.

02.1H4A1.0033 2-O1A-0-1401B-H1O Class 2 01A 2-01-01/sht.2 NDE-66 VT-3 NA 0.000 I 36.000 H04.001.03' Spring Hgr 0-ISIN4-122A-2.1 Calculation No. OSC-440.02.H4.1.0034 2-01A-0-1401B-R15 Class 2 01A 2-01-01/sht.2 0-ISIN4-122A-2.1 NDE-66 VT-3 NA 0.000 / 24.000 H04.001.03' Mech Snubber 02.H4.1.0035 Rigid Support Calculation No. OSC-440.2-01A-OM-200-30-MS-1 Class 2 01A 2-01-01/sht.1 0-ISIN4-122B-2.1 NDE-66 VT-3 NA 0.000 / 28.000 H04.001.03!

Calculation No. OSC-440.Printed 07/14/10 Ick8302 v. 06/18/09 SDQA Cat "C" Oconee 2 7/14/2010 2:17:26 PM Page 66 of 79 This report includes all changeshrough addendum ONS2-107 , Oconee 2, 4th Interval, outage 4 (EOC-24)0 Summary Num Component ID ISO/DWG Numbers Procedure Insp Req Material Sched Thick/NPS Class I System Description Comments Cal Blocks Componenet ID 2 Category ELC 02.H4.1.0036 Rigid Support 2-O1A-OM-200-30-MS-2 Class 2 01A 2-01-01/sht.1 0-ISIN4-122B-2.1 NDE-66 VT-3 NA 0.000 / 28.000 H04.001.03(Calculation No. OSC-440.02.H4.1.0037 Rigid Support 2-01A-0-1441-H16 Class 2 01A 2-01-01/sht.1 0-ISIN4-122A-2.1 NDE-66 VT-3 NA 0.000 / 36.000 H04.001.03; Calculation No. OSC-440.When examining this support, drawing 0-2157B (Section U-U) will also be needed to complete this exam.02.H4.1.0038 Hyd Snubber 2-01A-0-j1441-R9-1 Class 2 01A 2-01-01/sht.1 NDE-25 MT CS 0.562 / 36.000 H04.001.038, H04.001.038, 0-ISIN4-122A-2.1 Calculation No. OSC-440.-- (H04.001.038A)

Perform a Surface exam on the attachment welds.Note: Magnetic Particle examinations (with the use of procedure NDE-25) may be performed on carbon steel material in lieu of or in conjunction with liquid penetrant examinations.

02.H4.1.0038 Hyd Snubber 2-01A-0-1441-R9-1 Class 2 01A 2-01-01/sht.1 NDE-66 VT-3 CS 0.562 1 36.000 H04.001.038, H04.001.038/

0-ISIN4-122A-2.1 Calculation No. 05C-440.--(H04.001 .038A) Perform a Surface exam on the attachment welds.Note:-Magnetic Particle examinations (with the use of procedure NDE-25) may be performed on carbon steel material in lieu of or in conjunction with liquid penetrant examinations.

02.H4.1.0039 Rigid Support 2-01A-0-1441-H17 Class 2 01A 2-01-01/sht.1 0-ISIN4-122A-2.1 NDE-66 VT-3 NA 0.000 / 36.000 H04.001.03.

Calculation No. OSC-440.When examining this support, drawing 0-2157B (Section U-U) will also be needed to complete this exam.Printed 07/14/10 lck8302 v. 06/18/09 .SDQA Cat "C" Oconee 2 7/14/2010 2:17:26 PM Page 67 of 79 0 This report includes all changestrough addendum ONS2-107 Oconee 2, 4th Interval, outage 4 (EOC-24)0 Summary Num Category ELC Component ID ISOIDWG.Numbers Class I System Procedure Insp Req Material Sched Description Comments ThickINPS Cal Blocks Componenet ID 2 I 02.H4.1.0040 Spring Hgr 2-01A-0-1401[B-H18 Class 2 01A 2-01-01/sht.1 0-ISIN4-122A-2.1 NDE-66 VT-3 NA 0.000 / 8.000 H04.001.04(Calculation No. OSC-440.02.H4.1.0050 Hyd Snubber 2-01A-0-1441-R9-2 Class 2 01A 2-01-01/sht.1 NDE-25 MT CS 0.562 / 36.000 H04.001.050, H04.001.050i 0-ISIN4-122A-2.1 Calculation No. OSC-440. 1,-- (H04.001.050A)

Perform a Surface exam on the attachment welds.Note: Magnetic Particle examinations (with the use of procedure NDE-25) may be performed on carbon steel material in lieu of or in conjunction with liquid penetrant examinations.

02.H4.1.0050 Hyd Snubber 2-01A-0-1441-R9-2 Class2 01A 2-01-01/sht.1 NDE-66 VT-3 CS 0.562 / 36.000 H04.001.050, H04.001.050?

0-ISIN4-122A-2.1 Calculation No. 05C-440.-- (H04.001 .050A) Perform a Surface exam on the attachment welds.Note: Magnetic Particle examinations (with the use of procedure NDE-25) may be performed on carbon steel material in lieu of or in conjunction with liquid penetrant examinations.

02.H4.1.0051 Hyd Snubber 2-01A-0-1441-R9-3 Class2 01A 2-01-01/sht.1 NDE-25 MT .CS 0.562 / 36.000 H04.001.051, H04.001.051/

0-ISIN4-122A-2.1 Calculation No. OSC-440.-- (H04.001.051A)

Perform a Surface exam on the attachment welds.Note: Magnetic Particle examinations (with the use of procedure NDE-25) may be performed on carbon steel material in lieu of or in conjunction with liquid penetrant examinations.

Printed 07/14/10 lck8302 v. 06/18/09 SDQA Cat "C" Oconee 2 7/14/2010 2:17:26 PM Page 68 of 79 0 This report includes all changeshrough addendum ONS2-107 Oconee 2, 4th Interval, outage 4 (EOC-24)0 Summary Num Category ELC Component ID ISO/DWG Numbers Class I System Procedure Insp Req Material Sched Description Comments ThickINPS Cal Blocks Componenet ID 2 02.H4.1.0051 Hyd Snubber 2-01A-0-1441-R9-3 Class 2 01A 2-01-01/sht.1 NDE-66 VT-3 CS 0.562 / 36.000 H04.001.051, H04.001.051, 0-ISIN4-122A-2.1 Calculation No. OSC-440.--(H04.001 .051A) Perform a Surface exam on the attachment welds.Note: Magnetic Particle examinations (with the use of procedure NDE-25) may be performed on carbon steel material in lieu of or in conjunction with liquid penetrant examinations.

02.H4.1.0052 Hyd Snubber 2-O1A-0-1441-R9-4 Class 2 01A 2-01-01/sht.1 0-ISIN4-122A-2.1 NDE-25 MT CS 0.562 / 36.000 H04.001.05, Calculation No. OSC-440.Perform a Surface exam on the attachment welds.Note: Either a magnetic particle examinations or a liquid penetrant examination or a combination of the 2 methods may be performed on carbon steel material to meet the surface examination requirements for this item.02.H4.1.0052 Hyd Snubber 2-01A-0-1441-R9-4 Class 2 01A 2-01-01/sht.1 0-ISIN4-122A-2.1 NDE-66 VT-3 CS 0.562 / 36.000 H04.001.05, Calculation No. OSC-440.Perform a Surface exam on the attachment welds.Note: Either a magnetic particle examinations or a liquid penetrant examination or a combination of the 2 methods may be performed on carbon steel material to meet the surface examination requirements for this item.02.H5.1.0001 Spring Hgr 2-01A-0-1441-H1 Class 2 01A 2-01-01/sht.1 NDE-25 MT CS 0.500 / 36.000 H05.001.00" 0-ISIN4-122A-2.1 Calculation No. OSC-440. Perform MT examination on the attachment weld to the elbow.Printed 07/14/10 lck8302 v. 06/18/09 SDQA Cat "C" Oconee 2 7/14/2010 2:17:26 PM Page 69 of 79 This report includes all change~s~rough addendum ONS2-107 Oconee 2, 4th Interval, outage 4 (EOC-24)I Summary Num Component ID ISO/DWG Numbers Class I System Procedure Insp Req Material Sched Description Comments Thick/NPS Cal Blocks Componenet ID 2 Category ELC 02.H5.1.0002 2-MS9A-A Class2 01A 2MS-103 0-ISlN4-122A-2.1 NDE-600 UT CS 1.164 /36.000 Component PDI UT 1-0 PDI-UT-1A-O H05.001.00, Circumferential 2MS-9A Elbow to Pipe Subassembly 2MS-9A. Procedure NDE-600 uses the component for calibration.

Procedure PDI-UT-1 may be used in lieu of NDE-600. If PDI-UT-1 is used, then the calibration block listed shall be used. NDE-946 is\to be used for thickness measurements.

Inspection results should be forwarded to Timothy D Brown of the Oconee Design Basis Group.02.H5.1.0002 2-MS9A-A Class 2 01A 2MS-1l O-ISIN 03 4-122A-2.1 NDE-946 UT CS 1.164 / 36.000 Component PDI UT 1- 0 PDI-UT-1A-O H05.001.00, Circumferential 2MS-9A Elbow to Pipe Subassembly 2MS-9A. Procedure NDE-600 uses the component for calibration.

Procedure PDI-UT-1 may be used in lieu of NDE-600. If PDI-UT-1 is used, then the calibration block listed shall be used. NDE-946 is to be used for thickness measurements.

Inspection results should be forwarded to Timothy D Brown of the Oconee Design Basis Group.02.H5.11.0003 2MS-103-39 Class 2 01A 2MS-103 0-ISIN4-122A-2.1 NDE-946 UT CS 1.164/36.000 Component PDI UT 1- 0 PDI-UT-L1A-0 H05.001.00, Circumferential Elbow to Elbow Procedure NDE-600 uses the component for calibration.

Procedure PDI-UT-1 may be used in lieu of NDE-600. If PDI-UT-1 is used, then the calibration block listed shall be used. NDE-946 is to be used for thickness measurements.

Inspection results should be forwarded to Timothy D Brown of the Oconee Design Basis Group.02.H5.1.0003 2MS-103-39 Class 2 01A 2MS-103 0-ISIN4-122A-2.1 NDE-600 UT CS 1.164 / 36.000 Component PDI UT 1- 0 PDI-UT-1A-O H05.001.00" Circumferential Elbow to Elbow Procedure NDE-600 uses the component for calibration.

Procedure PDI-UT-1 may be used in lieu of NDE-600. If PDI-UT-1 is used, then the calibration block listed shall be used. NDE-946 is to be used for thickness measurements.

Inspection results should be forwarded to Timothy D Brown of the Oconee Design Basis Group.Printed 07/14/10 Ick8302 v. 06/18/09 SDQA Cat "C" Oconee 2 7/14/2010 2:17:26 PM Page 70 of 79 This report includes all changeosrough addendum ONS2-107 Oconee 2, 4th Interval, outage 4 (EOC-24)s Summary Num Component ID ISO/DWG Numbers Class / System Category ELC 02.H5.1.0004 2-MS10A-A Class 2 01A 2MS-103 0-ISIN4-122A-2.1 Procedure Insp Req Material Sched Description Comments Thick/NPS Cal Blocks Componenet ID 2 NDE-946 UT CS 1.164 / 36.000 Component PD1 UT 1- 0 PDI-UT-1A-O H05.001.00i Circumferential 2MS-10A Pipe to Elbow Subassembly 2MS-10A. Procedure NDE-600 uses the component for calibration.

Procedure PDI-UT-1 may be used in lieu of NDE-600. If PDI-UT-1 is used, then the calibration block listed shall be used. NDE-946 is to be used for thickness measurements.

Inspection results should be forwarded to Timothy 0 Brown of the Oconee Design Basis Group.02.H5.1.0004 2-MS 10A-A Class 2 01A 2MS-103 0-ISIN4-122A-2.1 NDE-600 UT CS 1.164 / 36.000 Component PDI UT 1- 0 PDI-UT-1A-O H05.001.00' Circumferential 2MS-10A Pipe to Elbow Subassembly 2MS-10A. Procedure NDE-600 uses the component for calibration.

Procedure PDI-UT-1.may be used in lieu of NDE-600. If PDI-UT-1 is used, then the calibration block listed shall be used. NDE-946 is to be used for thickness measurements.

Inspection results should be forwarded to Timothy D Brown of the Oconee Design Basis Group.Category F-A 02.F1.11.0001-Rigid Restraint 2-51A-0-1479A-H 1OA Class 1 51A 0-2RB-25315-04 0-ISIN4-101A-2.4 NDE-66 VT-3 NA 0.000 / 2.500 F01.011.01' Calculation No. OSC-1324-06.

HPI East Coolant Loop.021F1. 11.0008 Rigid Restraint 2-53A-0-1480A-H26C Class 1 53A 0-2RB-25314-02 O-ISIN4-1 OOA-2.2 NDE-66 VT-3 NA 0.250 / 1.500 F01.01 1.03ýCalculation No. 05C-1324-06.

was inspected as aF1701.01.

in 3rd.02.F1.12.0008 Spring Hgr 2-53A-0-1478A-H1A Class 1 53A 0-1492D-2(S) 0-ISIN4-102A-2.3 2-53-13/sht.

1 NDE-66 VT-3 NA 2.000 / 14.000 F01 .012.03" 0-1478A Printed 07/14/10 Ick8302 v. 06/18/09 SDQA Cat "C" Oconee 2 7/14/2010

-2:17:26 PM Page 71 of 79 This report includes all changestrough addendum ONS2-107 Oconee 2, 4th Interval, outage 4 (EOC-24)S Summary Num Category F-A 02.F1.20.0014 Rigid Support Component ID ISO/DWG Numbers Class I System 2-51A-3-0-437B-DE048 Class 2 51A 0-2AB-25101-04 O-ISIN4-101A-2.1 Procedure Insp Req Material Description Comments Sched Thick/NPS Cal Blocks Componenet ID 2 NDE-66 VT-3 NA 0.000 / 4.000 F01.020.04, Calculation No. OSC-479.02.F1.20.0025 Rigid Support 2-51A-0-1439C-H166 Class 2 51A 2-51-18/sht.1 0-ISIN4-101A-2.4

  • NDE-66 VT-3 NA 0.000 / 4.000 F01.020.05" Calculation No. OSC-1023.02.F1.20.0035 Rigid Support 2-53B-0-435B-DE015 Class 2 53B 0-2AB-25301-01 0-ISIN4-102A-2.1 NDE-66 VT-3 NA 0.000 / 14.000 F01.020.07" Calculation No. OSC-487..02.F1.20.0040 Rigid Support 2-53B-2-0-435B-R69 Class 2 53B 0-2AB-25301-04 0-ISIN4-102A-2.2 NDE-66 VT-3 NA 0.000 / 8.000 F01.020.07i Calculation No. OSC-487.02.F1.20.0042 Rigid Support 2-53B-1-0-1439C-DE067 Class 2 53B 0-2AB-25302-01 0-ISIN4-102A-2.2 NDE-66 VT-3 NA 0.000 / 10.000 F01.020.08(Calculation No. OSC-493.02.F1.20.0054 Rigid Support 02.F1.20.0056 Rigid Support 2-54A-3-0-1439C-H5 Class 2 54A 2-54-03/sht.1 0-ISIN4-103A-2.1 1.000 / 8.000 NDE-66 VT-3 NA F01.020.09(Calculation No. OSC-496. Inspect with C03.020.056.

2-54A-3-0-435B-R10 Class 2 54A 2-54-1/sht.1 0-ISIN4-103A-2.1 NDE-66 VT-3 NA 0.000 / 8.000 F101.020.091 Calculation No. OSC-494.Printed 07/14/10 Ick8302 v. 06/18/09 SDQA.Cat "C" Oconee 2 7/14/2010 2:17:26 PM Page 72 of 79 This report includes all changes 9 rough addendum ONS2-107 Oconee 2, 4th Interval, outage 4 (EOC-24)Summary Num Component ID ISOIDWG Numbers Class I System Procedure Insp Req Material Description Comments Sched Thick/NPS Cal Blocks Componenet ID 2 Category F-A 02.F1 21.0011 Rigid Restraint 2-14-1478F-H6091 Class 2 14 0-2RB-203A13-03 O-ISIN4-121 D-2.1 NDE-66 VT-3 NA 0.000 / 6.000 F01.021.02ý Calculation No. OSC-1224-17.

02.F1 21.0016 Rigid Restraint 2-51A-0-1478A-H13C Class 2 51A 2-51-12/sht.5 0-ISIN4-101A-2.1 NDE-66 VT-3 NA 0.750 / 2.500 F01.021.04, Calculation No. OSC-1660-06.

HPI System.02.F1.21.0021 Rigid Restraint 2-51A-2-0-438C-SP115 Class 2 51A 2-51-18/sht.5 0-ISIN4-101A-2.4 NDE-66 VT-3 NA 0.000 / 4.000 F01.021.04, Calculation No. OSC-1023.HPI System.02.F1`.21.0023 Rigid Restraint 2-51B-436J-DE013 Class 2 51B 0-2AB-25102-01 0-ISIN4-101A-2.2 NDE-66 VT-3 NA 0.000 / 3.000 F0t1.021.05' Calculation No. OSC-481.When examining this support, which is part of a gang hanger, the examination boundary should be extended back to the building structure.

Support sketch 2-GH-QR-7374-01 will also be needed to complete this exam.-02.F1.21.0030 Rigid Restraint 2-53B-5-0-1436A-R5 Class 2 53B 0-2AB-25302-03 0-ISIN4-102A-2.2 NDE-66 VT-3 NA 0.000 / 10.000 F01.021.06z Calculation No. OSC-493.02.F1.21.0038 Rigid Restraint 2-56-438B-DE002 Class 2 56 4-56-02/sht.5 0-ISIN4-104A-1.1 NDE-66 VT-3 NA 0.000 / 8.000 F01.021.08, Calculation No. OS-421.When examining this support, which is part of a gang hanger, the examination boundary should be extended back to the building structure.

Support sketch 2-GH-TRB-7576-02 will also be needed to complete this exam.Printed 07/14/10 lck8302 v. 06/18/09 SDQA Cat "C" Oconee 2 7/14/2010 2:17:26 PM Page 73 of 79 0 This report includes all changes-rough addendum ONS2-107 Oconee 2, 4th Interval, outage 4 (EOC-24)Summary Num Category F-A 02.F1.21.0039 Rigid Restraint 02.F1.22.0002 Constant Support 02.F1.22.0008 Constant Support Component ID ISO/DWG Numbers Class I System -Procedure Insp Req Material Sched Thick/NPS Description Comments Cal Blocks Componenet ID 2 2-56-0-1478A-H1 1 Class 2 56 0-2RB-25310-01 O-ISIN4-104A-1 NDE-66 VT-3 NA 0.375 / 8.000 F01.021.08 Calculation No. OSC-1321-07.

2-01A-0-1481 B-H11B Class 2 01A 2-01-08/sht.1 0-ISIN4-122A-2.1 NDE-66 VT-3 NA 2.000 / 36.000 F01.022.00, Calculation No. OSC-1 315. Inspect with C03.020.004.

2-01A-0-1480A-H lA Class 2 01A 2-01-09/sht.1 0-ISIN4-122A-2.1 NDE-66 VT-3 NA 1.500 / 26.000 F01.022.00M Calculation No. 05C-1 315.02.F1.22.0013 Spring Hgr 2-51A-435B-DKB-1411 Class 2 51A 0-2AB-25102-02 0-ISIN4-101A-2.3 NDE-66 VT-3 NA 0.226 / 6.000 E01.022.04, Calculation No. 05C-481. Inspect with C03.020.034.

02.F1.22.0023 Spring Hgr 2-53B-5-0-1439A-H56 Class 2 53B 0-2AB-25305-01 0-ISIN4-102A-2.2 NDE-66 VT-3 NA 0.000 / 10.000 F01.022.05-Calculation No. OSC-491.02.F1.22.0025 Spring Hgr 2-54A-3-0-435B-H25 Class 2 54A 2-54-1/sht.1 0-ISIN4-103A-2.1 NDE-66 VT-3 NA 0.216 / 8.000 F01.022.06" Calculation No. OSC-494. Inspect with C03.020.051.

Printed 07/14/10 Ick8302 v. 06/18/09 SDQA Cat "C" Oconee 2 7/14/2010 2:17:26 PM Page 74 of 79 This report includes all change~s Prrough addendum ONS2-107 Oconee 2, 4th Interval, outage 4 (EOC-24)Summary Num Component ID ISO/DWG Numbers Class / System Procedure Insp Req Material Sched Description Comments Thick/NPS Cal Blocks Componenet ID 2 Category F-A 02.F1.30.0013 Rigid Support 2-03-0-1439B-H54 Class 3 03 2-01-03/sht.1 O-ISIN4-121 B-2.3 NDE-66 VT-3 NA 0.000 / 24.000 F01.030.02(Calculation No. OSC-454.Inspect with item number H04.001 .002.02.F1.30.0014 Rigid Support 2-03A-1-0-1401B-SR8 Class 3 03A 2-03A-05/sht.5 O-ISIN4-121 D-2.1 NDE-66 VT-3 NA 0.000 /6.000 F01.030.02' Calculation No. OSC-447.02.F1.30.0020 I Rigid Support 02.F1.30.0035 Rigid Support 2-03A-0-1400A-MDH-1 101 Class 3 03A 0-2TB-203A12-01 O-ISIN4-121 D-2.1 NDE-66 VT-3 NA 0.500 /6.000.F01.030.02-Calculation No. OSC-1213.

Inspect with D01.020.015.

2-14B-0-437B-JEJ-1 705 Class 3 14B 0-2AB-21405-02 O-ISIN4-124B-1.1 NDE-66 VT-3 NA 0.000/12.000 F01.030.07, Calculation No. OSC-473.02.F1.31.0002 Rigid Restraint 2-03A-1-0-1401A-SR28 Class 3 03A 2-03A-06/sht.1 O-ISIN4-121 D-2.1 NDE-66 VT-3 NA 0.000 / 6.000 F01.031.01' Calculation No. OSC-459.02.F1.31.0004 Rigid Restraint 2-03A-1-0-1401B-SR4 Class 3 03A 2-03A-05/sht.5 O-ISIN4-121 D-2.1 NDE-66 VT-3 NA 0.000 / 6.000 F01.031.01' Calculation No. OSC-447.Printed 07/14/10 Ick8302 v. 06/18/09 SDQA Cat "C" Oconee 2 7/14/2010 2:17:26 PM Page 75 of 79 This report includes all changes-rough addendum ONS2-107 Oconee 2, 4th Interval, outage 4 (EOC-24)Summary Num Component ID ISO/DWG Numbers Procedure Insp Req Material Sched Thick/NPS Cal Blocks Componenet ID 2 Class / System Description Comments Category F-A 02.F1.31.0015 2-07A-1400A-H4089 Class 3 07A 0-2TB-20701-06 NDE-66 VT-3 NA 0.000 /8.000 F01.031.03; Rigid Restraint O-ISIN4-121A-2.8 9------- Calculation No. OSC-467.02.F1.31.0025 2-14B-1-0-1439-H13 Class 3 14B 4-14-04/sht.3 NDE-66 VT-3 NA 0.000 / 8.000 F01.031.06, Rigid Restraint O-ISIN4-124B-2.2 Calculation No. OSC-474.When examining this support, which is part of a gang hanger, the examination boundary should be e'xtended back to the building structure.

Support sketch 2-GH-QR-7879-03 will also be needed to complete this exam.02.F1.31.0027 2-57-0-1481A-H4 Class 3 57 0-2RB-25701-01 NDE-66 VT-3 NA 1.000 /12.000 F01.031.07" Rigid Restraint O-ISIN4-107A-2.1 Calculation No. OSC-1332-06.

Inspect with D01.020.075.

02.F1.32.0004 2-03-0-1401A-R7 Class 3 03 2-03-01/sht.1 NDE-66 VT-3 NA 1.000 /24.000 F01,032.01; Hyd Snubber O-ISIN4-121 B-2.3 Calculation No. OSC-454. Inspect with D01.020.010, H04.001.008 and H04.001.008A.

02.F1.32.0014 2-57-0-1480A-NWIZ Class 3 57 0-2RB-25701-01 NDE-66 VT-3 NA 0.000 / 12.000 F01.032.06' Mech Snubber O-ISIN4-107A-2.1 Calculation No. OSC-1332-06.

02.F1.40.0019 2-RCSR-FTR Class 2 OM-201-2135 NDE-66 VT-3 NA 0.000 /0.000 F01 .040.01.O-ISIN4-101A-2.1 0-2AB-25106-02 Reactor Coolant Seal Return Filter. This support is listed as 2-51A-3-0-1436A-H79.

Printed 07/14/10 Ick8302 v. 06/18/09 SDQA Cat "C" Oconee 2 7/14/2010 2:17:26 PM Page 76 of 79 This report includes all change~strough addendum ONS2-107 Oconee 2, 4th Interval, outage 4 (EOC-24)Summary Num Component ID ISO/DWG Numbers Class I System Procedure Insp Req Material Sched Thick/NPS Description Comments Cal Blocks Componenet ID 2 Category F-A 02.F1.40.0027 Hyd Snubber 2-50-RCPM-2BI-SS3 Class I 0-1066A O-ISIN4-100A-2.1 0-ISIN4-100A-2.3 NDE-66 VT-3 NA 0.000 1 6.000 F01.040.02; Calculation No. OSC-0991-01-0001, Reactor Coolant Pump 2B1 Motor Snubbers.

Reference PIP 0-096-1575.

Category Q-A 02.Q 1.1.0001 2RC-326-21V Class 1 50 ISI-OCN2-015 ISI-OCN2-006 PDI-UT-8 UT SS-Inconel 1.000/10.750 DE-13-AX-01 DE-13-CIRC-01 Dissimilar Stress Weld 2RC-326 Weld Overlay Pressurizer Surge Piping. Nozzle Pc. 25. Drawing O-ISIN-100A-2.1 Weld 21Vi, listed on weld iso 2RC-326 but drawing ISI-OCN2-015 and ISI-OCN2-006 are listed as the iso's to show where the weld is located on the 2B Hot Leg piping loop and the location for the surge line to nozzle weld location.Weld 2RC-326-21V is weld overlay that covers weld 2-PHB-17 and weld 2-PSL-10.

Inspection in outage 4 does not count in the percentages.

02.Q1.1.0002 2RC-266-23V Class 1 50 iSI-OCN2-016 ISI-OCN2-002 PDI-UT-8 UT SS-Inconel

.531 / 4.00 DE-6-AX-01 DE-6-CIRC-01 Terminal End Dissimilar Stress Weld 2RC-266 Weld Overlay Pressurizer Spray .Nozzle Pc. 45. Drawing O-ISIN-100A-2.1 Weld 23V is listed on weld iso 2RC-266 but drawing ISI-OCN2-016 and ISI-OCN2-002 are listed as the iso's to show where the weld is located on the PZR Spray Line piping loop and the location for the PZR Spray nozzle to SE weld location.Weld 2RC-266-23V is weld overlay that covers weld 2-PZR-WP45 and weld 2-PSP-1. Inspection in outage 4 does not count in the percentages.

Printed 07/14/10 Ick8302 v. 06/18/09 SDQA Cat "'C"'POconee 2 7/14/2010 2:17:26 PM Page 77 of 79 This report includes all changerough addendum ONS2-107 Oconee 2, 4th Interval, outage 4 (EOC-24)Summary Num Category Q-A 02.Q1.1.0003 Terminal End Dissimilar Stress Weld Component ID ISO/DWG Numbers Class I System 2RC-326-22V Class 1 50 ISI-OCN2-002 0-ISIN4-100A-2.1 Procedure Insp Req -Material Sched Description Comments Thick/NPS Cal Blocks Componenet ID 2 PDI-UT-8 UT SS-CS 1.930/11.375 DE-13-AX-01 DE-13-CIRC-01 2RC-326 Weld Overlay Pressurizer Surge. Nozzle Pc. 8. Drawing O-ISIN-100A-2.1 Weld 22V is listed on weld iso 2RC-326 but drawing lSI-OCN2-002 is listed as the iso to show where the weld is located on the PZR Surge nozzle to SE weld location.Weld 2RC-326-22V is weld overlay that covers weld 2-PZR-WP23.

Inspection in outage 4 does not count in the percentages.

The inspectionin outage 5 is part of the 25% of the population of weld overlaid items that is required to be examined during the 10 year interval.

The weld in outage 5 does count in the percentages (25%) for Appendix Q.02.Q1.1.0004 2-PZR-WP91-1-WOL Class 1 50 ISI-OCN2-002 0-ISIN4-100A-2.1 PDI-UT-8 UT SS-CS/2.5 DE-6-AX-01 DE-6-CIRC-01 Terminal End Dissimilar Weld Overlay Pressurizer Relief Nozzle Pc. 31 to Relief Nozzle Safe End Pc. 32. W-X Quadrant.

Weld 2-PZR-WP91-1 has weld overlay added to it and now uses the ID 2-PZR-WP91-1-WOL.

Inspection in outage 4 does not count in the percentage required (25%)for Appendix Q. The inspection in outage 5 is part of the 25% of the population of weld overlaid items that is required to be examined during the 10 year interval.

The inspection of this weld in outage 5 does count in the percentages (25%) for Appendix Q.02.Q1.1.0005 2-PZR-WP91-2-WOL Class 1 50 ISI-OCN2-002 O-ISIN4-100A-2.1 PDI-UT-8 UT SS-CS/2.5 DE-6-AX-01 DE-6-CIRC-01 Terminal End Dissimilar Weld Overlay Pressurizer Relief Nozzle Pc. 31 to Relief Nozzle Safe End Pc. 32. X-Y Quadrant.

Weld 2-PZR-WP91-2 has weld overlay added to it and now uses the ID 2-PZR-WP91-2-WOL.

Inspection in outage 4 doesnot count in the percentage required (25%) for Appendix Q.Printed 07/14/10 Jck8302 v. 06/18/09 SDQA Cat "C" Oconee 2 7/14/2010 2:17:26 PM Page 78 of 79 10 This report includes all changestrough addendum ONS2-107 Oconee 2, 4th Interval, outage 4 (EOC-24)0 Summary Num Component ID ISO/DWG Numbers Class / System Procedure Insp Req Material Sched Description Comments Thick/NPS Cal Blocks Componenet ID 2 Category Q-A 02.Q1.1.0006 2-PZR-WP91-3-WOL Class 1 50 ISI-OCN2-002 0-ISIN4-100A-2.1 PDI-UT-8 UT SS-CS/ 2.5 DE-6-AX-01 DE-6-CIRC-01 Terminal End Dissimilar Weld Overlay Pressurizer Relief Nozzle Pc. 31 to Relief Nozzle Safe End Pc. 32. Z-W Quadrant.

Weld 2-PZR-WP91-3 has weld overlay added to it and now uses the ID 2-PZR-WP91-3-WOL.

Inspection in outage 4 does not count in the percentage required (25%)for Appendix Q.02.Q1.1.0007 2-53A-10-13V Class 1 53A ISI-OCN2-005 2-53A-10 O-ISIN4-100A-2.1 PDI-UT-8 UT SS-Inconel 1.125 /12.000 DE-13-AX-01 DE-13-CIRC-01 Dissimilar Stress Weld Weld Overlay Low Pressure Injection System. Decay Heat Nozzle Inconel Buttering Pc. 34 to Pipe (12" NPS).Weld 2-53A-10-13V is listed on weld iso 2-53A-10 but drawing ISI-OCN2-005 is listed as the iso to show where the weld is located on the 'A" Hot Leg reactor coolant piping loop.Weld 2-53A-10-13V is weld overlay that covers weld 2-PHA-17 and weld 2-53A-10-1OA.

Inspection in outage 4 does not count in the percentages for Appendix Q.End of Report S TA TIS TICS ONL Y Class 1 175 Class 2 87 Class 3 19 Total by Class 281 Systems 281 Total Count 281 Printed 07/14/10 Ick8302 v. 06/18/09 SDQA Cat "C" Oconee 2 7/14/2010 2:17:26 PM Page 79 of 79 4

4.0 Results

Of Insipections Performed The results of each examination shown in the final Inservice Inspection Plan (Section 3 of this report) are included in this section. The completion date and status for each examination are shown. All examinations revealing reportable indications and any corrective action required as a result are described in further detail in Subsections 4.1 and 4.2. Corrective measures performed and limited examinations are described in further detail in Subsections 4.3 and 4.4.4.1 Reportable Indications EOC 24 (Outage 4) did not have any reportable indications during this report period.4.2 Corrective Action Corrective action is action taken to resolve flaws and relevant conditions, including supplemental examinations, analytical evaluations, repair / replacement activities, and corrective measures.

There were no problems that required corrective action during this report period.4.3 Corrective Measures Corrective measures are actions (such as maintenance) taken to resolve relevant conditions, but not including supplemental examinations, analytical evaluations, and repair / replacement activities.

Any corrective measures performed for examinations associated with this report period will be shown on the examination data sheets which are on file at the Duke's Corporate Office in Charlotte, North Carolina.EOC 24 Refueling Outage Report Oconee Unit 2 Section 4 Page 1 of 2 Revision 0 July 14, 2010

4.4 Limited

Examinations Limited examinations (i.e., 90% or less of the required examination coverage obtained) identified during EOC 24 (Outage 4) are shown in the table below.A Request for Relief will be submitted to seek NRC acceptance of the limited coverage for the items listed in the table below.Summary/item Description of Limitation Number 02.133.110.0002 See PIP 0-10-02605 for corrective action on this limitation 02.B3.110.0003 See PIP 0-10-02605 for corrective action on this limitation 02.B3.110.0005 See PIP 0-10-02605 for corrective action on this limitation 02.B39.11.0046 See PIP 0-10-02605 for corrective action on this limitation 02.B9.11.0053 See PIP 0-10-02605 for corrective action on this limitation 02.B9.11.0063 See PIP 0-10-02605 for corrective action on this limitation 02.05.11.0038 See PIP 0-10-02605 for corrective action on this limitation 02.05.21.0035 See PIP 0-10-02605 for corrective action on this limitation Welds 2-51A-0029-94 and 2-HP-0396-23 are Class 2 welds that had PSI exams performed on them during 2EOC-24 and had limited coverage (less than 90%). See PIP 0-10-02605 for the corrective action on these exams.(EOC 24 Refueling Outage Report Oconee Unit 2 Section 4 Page 2 of 2 Revision 0 July 14, 2010 DUKE ENERGY GIPORA TION QUALITY ASSURANCE TECHNICAL SERVICES Scheduleworks Inservice Inspection Database Management System Inspection Results Oconee 2, 4th Interval, Outage4(EOC.24)

FOR INFORMATION ONLYI Summary No 023.10.20.0008 02.B12.30.0001 02.115.210.0001 02.315.210.0002 02.B15.210.0003 02.B15.210.0004 02.615.210.0005 02.B15.210.0006 02.615.210.0007 02.615.210.0008 02.B15.210.0009 02.B15.210.0010 Component ID 2-53A-0-1478A-H1A 2-51A-HP-126 2RC-278-66 2RC-278-70V 2RC-277-50 2RC-277-71V 2R.-278-23 2RC-278-69 2RC-277-24 2RC-277-70 2-PHA-13 2-PHA-14 System 53A 53A 50 50 50 50 50 50 50 50 50 50 Insp Date 05/09/10 05/04/10 04/26/10 04/26/10 04/26/10 04/26/10 04/26/10 04/26/10 04/26/10 04/26/10 04/26/10 04/26/10 Insp Status CLR CLR CLR CLR CLR CLR CLR CLR CLR CLR CLR CLR Insp Geo Limited Ref RFR Comment N N N N N N N N N N N N PT-10-273 PT-1 0-270 VT-10-493 VT-1 0-494 VT- 10-486 VT-10-487 VT-1 0-495 VT- 10-496 VT-1 0-479 VT-10-488 VT-i 0-497 VT-10-498 Printed 7/14/2010 2:20:04 PM Ick8302 v. 01/01/08 SDQA Cat "C" Oconee 2 7/14/2010 2:17:26 PM Page l of 22 FOR INFORM *N ONLY!Insp Insp Insp Geo Summary No Component ID System Date Status Limited Ref RFR Comment 02.B15.210.0011 2-PHA-15 50 04/26/10 CLR N N N VT-10-499 02.B15.210.0012 2-PHB-13 50 , 04/26/10 CLR N N N VT-10-489.. ............ ...... 0 0...... ..... N.. .............N... .....N.. -...........

... ..... .. .. ..... .... ........ ............. ........ .......... ....02.B15.210.0013 2-PHB-14 50 04/26/10 CLR N N N VT-10-490 02.1315.210.0014 2-PHB-15 50 04/26/10 CLR N N N VT-10-491 02.B15.210.0015 2SGA-HL-CON-36 50 04/26/10 CLR N N N VT-10-500' ..... ... .. i .....................- --... ... .... .. .. .. .. ... .. .. .. ... .. .. .. .. ... .. .. .. ... .. .... .. ... .... ..... .. .. .. .. ... .. .. .. ... .. .. .. .. ... .. .. .. ... .. .. .. .. ......... ... .... .... ... .. .. .. ... .. .. .. .. ... .. .. .. ... .. .. .. ..... .... ..... .. .. .. .. ... .. .. .. ... .. .. .. .. ... .. .... ... ........... .. ..... .. .. .. .. .. ... ...................

02.B15.210.0016 2SGB-HL-CON-27 50 04/26/10 CLR N N N VT-10-492 026B15.215.0003 2-PIB1-11 50 04/27/10 CLR N N N VT-10-481 This weld had weld overlay applied over it after the exam in 2EOC-24 was performed.

It will not be accessible for examination in the future.02.615.215.0004 2-51A-35-15A 51A 04/27/10 CLR N N N VT-10-482 This weld had weld overlay applied over it after the exam in 2EOC-24 was performed.

It will not be accessible for examination in the future.O2.B15,215.0007 2-PIB1-7 50 04/27/10 CLR N N N VT-10-480 02.B15.215.0008 2-PIB2-7 50 04/27/10 CLR N N N VT-10-484 02..15.215.0011 2-PDB1-2 50 04/26/10 CLR N N N VT-10-483 02.B15.215.0012 2-PDB2-2 50 04/26/10 CLR N N N VT-10-485 02.615.215.0020 2-PIB2-11 50 04/27/10 CLR N N N VT-10-507 Printed 7/14/2010 2:20:04 PM Ick8302 v. 01/01/08 SDQA Cat "C" Oconee 2 7/14/2010 2:17:26 PM Page 2 of 22 0 Summary No 02.B135.215.0021 02315.215.0026 02.B15.215.0027 02.315.80.0001 02.62.11.0002 02.B2.12.0002 02.B3.110.0002 02.B3.110.0003 Component ID 2-50-7-8 2-PIB1-12 2-PIB2-12 2-RPV-BMI-NOZZLES 2-PZR-WP28 2-PZR-WP7-1 2-PZR-WP34 2-PZR-WP33-3 SYS FOR INFORM 9 N ONLY!Insp Insp Insp Geo stem Date Status Limited Ref RFR Comment 50 04/27/10 CLR N N- N VT-10-508 50 04/27/10 CLR N N N VT-i 0-509 50 04/27/10 CLR N N N VT-10-510 50 04/26/10 CLR N N N VT-10-505 50 05/13/10 CLR N N N UT-10-482 50 05/13/10 CLR Y N N UT-10-484 Greater than 90% coverage.50 05/14/10 REC N N N UT-10-489 Indications

  1. 1 & 2 are subsurface linear volumetric indications that are acceptable per IWB-3510.50 05/13/10 ...LR N N N UT-10-483 50 05/13/10 CLR N N N UT-10-485 50 05/03/10 CLR Y N Y UT-1 0-444 PIP 0-10-02605 was written to determine-the corrective action for the limited coverage achieved for this item.50 05/03/10 CLR Y. N Y UT-1 0-452 PIP 0-10-02605 was written to determine the corrective action for the limited coverage achieved for this item.50 05/03/10 CLR Y N Y UT-10-446 PIP 0-10-02605 was written to determine the corrective action for the limited coverage achieved for this item.SDQA Cat "C" Oconee 2 7/14/2010 2:17:26 PM Page 3 of 22 Printed 7/14/2010 2:20:04 PM Ick8302 v. 01/01/08 Summary No O2.B3.110.0003 02.B3.110.0005 02.B3.120.0002 02.B3.120.0003 02.B3.120.0004 02.B3.120.0005 02.B5.10.0001 02.B5.10.0002 02.B6.60.0001 02.B6.80.0001 Component ID 2-PZR-WP33-3 2-PZR-WP33-1 2-PZR-WP34 2-PZR-WP33-3 2-PZR-WP33-2 2-PZR-WP33-1 2-RPV-WR53 Insp System Date 50 05/03/10 50 05/03/10 50 05/03/10 Insp Status CLR CLR CLR CLR CLR CLR CLR CLR 50 50 50 50 50 05/12/10 05/12/10 05/12/10 05/12/10 05/09/10 FOR INFORMW ONLY!Insp Geo Limited Ref RFR Comment Y N Y UT-10-447 PIP 0-10-02605 was written to determine the corrective action for the limited coverage achieved for this item.Y N Y UT-10-450 PIP 0-10-02605 was written to determine the corrective action for the limited coverage achieved for this item.Y N Y UT-10-451 PIP 0-10-02605 was written to determine the corrective action for the limited coverage achieved for this item.S.. .....................

....U -i 0 -4 9 0..........................................

.... ....................................

N N N UT-10-490 N N N UT-i 0-492 N N N UT-10-493 N N N UT-10-492 N N N UT-NA Greater than 90 % coverage achieved.Y N N UT-NA Greater than 90 % coverage achieved.N N N UT-10-478 N N N VT-10-538 2-RPV-WR53A 50 05/09/10 CLR 2-PZR-MW-STUDS 2-PZR-MW-NUTS 50 50 05/13/10 05/05/10 CLR CLR Printed 7/14/2010 2:20:04 PM Ick8302 v. 01/01/08 SDQA Cat "C" Oconee 2 7/14/2010 2:17:26 PM Page 4 of 22 0 FOR INFORMON ONLY!Insp Insp Insp System Date Status Limited Geo Ref RFR Comment Summary No 02.B7.30.0005 02.B7.30.0006 02.B7.70.0005 02.B9.111.0006 02.89.11.0007

.2.B9.1 1.0008 02.B9.11.0009 02.B9.11.0012 02.B9.11.0013 Component ID 2-SGA-UHHC-STUDS 2-SGB-UHHC-STUDS 2-53A-LP1-STUDS 2-PDA1-2 2-PDA2-2 2-PDBi-2 2-PDBl-2 " 2-P 082-2 2-PIA1-7 2-PIA2-7 50 50 53A 50 50 50 50 50 50 50 50 50 50 50 05/01/10 05/01/10 05/06/10 05/04/10 04/30/10 05/04/10 05/02/10 05/03/10 05/03/10 05/03/10 05/03/10 04/28/10 04/29/10 04/30/10 CLR CLR CLR CLR CLR CLR REC CLR CLR CLR CLR CLR CLR CLR N N N N N N N N N N N N N N VT-10-533 VT-10-534 VT-10-539 PT-10-262 UT-10-398'PT-1 0-261 UT-10-383 Indication

  1. 1 is a subsurface flaw that is acceptable per IWB-3514-2.

PT-10-256 UT-1 0-394 PT-1 0-260 UT-1 0-392 PT-10-254 UT-10-396 PT-10-257 UT-1 0-399 N N N N N N N N N N N N N N N N N N N N N N N N 50 04/30/10 CLR Printed 7/14/2010 2:20:04 PM Ick8302 v. 01/01/08 SDQA Cat "C" Oconee 2 7/14/2010 2:17:26 PM Page 5 of 22 FOR INFORM,*N ONLY!Summary No 02.B9.11.0014 Component ID 2-PIB1-7 System 50 50 02.B9.11.0015 02.B9.111.0020 2-PIB2-7 50 50 Insp Date 05/03/10 05/03/10 05/03/10 05/01/10 04/29/10 04/29/10 Insp Status CLR CLR CLR REC CLR CLR N N N N N N N N N N N N Insp Geo Limited Ref RFR Comment N N N N N N PT-1 0-258 UT-1 0-391 PT-10-259 UT-10-384 Indication

  1. 1 is a subsurface flaw that is acceptable per IWB-3514-2.

MT-10-094 UT-1 0-372 2RC-279-88V 50 50 02.B9.11.0046 2-PIAl-8 50 05/15/10 CLR 50 05/16/10 CLR 02.B9.11.0053 2-PDA2-1 50 05/13/10 CLR Y N Y UT-10-498 Best effort exam for coverage.Y N Y UT-10-499 PIP 0-10-02605 was written to determine the corrective action for the limited coverage achieved for this item.Y N Y UT-10-480 PIP 0-10-02605 was written to determine the corrective action for the limited coverage achieved for this item. )Y N Y UT-10-487 Best effort exam for coverage.Y N Y UT-10-481 PIP 0-10-02605 was written to determine the corrective action for the limited coverage achieved for this item.50 05/13/10 CLR 02.B9.11.0063 2-PDB2-1 50 05/13/10 CLR Printed 7/14/2010 2:20:04 PM Ick8302 v. 01/01/08 SDQA Cat "C" Oconee 2 7/14/2010 2:17:26 PM Page 6 of 22 0 FOR INFORMIN ONLY!0 Insp Insp Insp Geo Date Status Limited Ref Summary No 02.B9.11.0063 02.B9.,11.0068 02.B9.11.0074 023B9.21.0007 02.B9.21.0033 02.B9.21.0038 02.B9.21.0039 02.B9.21.0042 02.B9.21.0043 02.B9.21.0044 02.B9.21.0048 02.B9.21.0066 02.B9.21.0067 02.B9.32.0003 Component ID System RFR Comment 2-PDB2-1 50 05/13/10 CLR 2-53A-1 0-8 2-53A-8-60 2-PDB2-11 2RC-202-17 2RC-203-4 2RC-204-37 2RC-205-1 2RC-205-3 2RC-205-4 2-51A-30-11 2HP-216-4 2HP-216-8 2-PDBI-10 53A 53A 50 51A 51A 51A 51A 51A 51A 51A 51A 51A 05/08/10 05/10/10 05/04/10 05/04/10 05/04/10 05/04/10 05/04/10 05/04/10 05/04/10 05/12/10 05/07/10 05/04/10 CLR CLR CLR CLR CLR CLR CLR CLR CLR CLR CLR CLR Y N Y UT-1 0-486 N Best effort exam for coverage.N N N UT-10-419 N N N UT-10-436 N N N PT-1 0-266 N N N PT-1 0-271 N N N PT-i 0-269 N N N PT-10-267 N N N PT-i 0-265 N N N PT-i10-264 N N N PT-i0-263 N N N PT-1 0-274 N N N PT-10-272 N N N PT-10-268 N N N MT-10-097 (50 05/04/10 .CLR Printed 7/1412010 2:20:04 PM Ick8302 v. 01/01/08 SDQA Cat "C" Oconee 2 7/14/2010 2:17:26 PM Page 7 of 22 0 FOR INFORM* ONLY!Insp Insp Insp Geo Date Status Limited Ref Summary No 02.19.32.0005 02.B9.32.0007 02.B9.40.0005 02.B9.40.0008 02.C3.20.0004 02.C3.20.0016 02.C3.20.0029 02.C3.20.0034 02.C5.11.0009

,02.C5.1 1.0010 02.C5.11.0013 02.C5.11.0014 02.C5.11.0037 Component ID System RFR Comment 2-PDB2-10 2-PIA2-10 2RC-271-7 2-50-7-102 2-01A-0-1481 B-H-11B 2-51A-435B-DKB-1411 2-54A-3-0-435B-H25 2-54A-3-0-1439C-H5 2LP-1 50-39 2LP-150-40 2LP-1 48-89 2LP-148-92 2LP-215-2 50 50 50 50 01A 51A 54A 54A 53A 53A 53A 53A 05104J10 CLR 05/14/10 CLR 04/30/10 CLR 04/29/10 CLR 05/13/10 CLR 02/09/10 CLR 02/09/10 CLR 02/01/10 CLR 02/01/10 CLR 02/01/10 CLR 02/01/10 CLR 02/02/10 CLR N MT-10-098 N MT-10-105 N PT-i10-255 N PT-10-253 N MT-10-100 N PT-09-251 N PT-09-252 N PT-09-250 N UT-09-357 N PT-09-358 N UT-09-359 N UT-09-361 Greater than 90% coverage achieved.N UT-i0-420 53A 05/09/10 CLR N N Printed 7/14/2010 2:20:04 PM Ick8302 v. 01/01/08 SDQA Cat "C" Oconee 2 7/14/2010 2:17:26 PM Page8 of22 FOR INFORMON ONLY!0 Summary No 02.C5.11.0038 02.C5.11.0039 02.C5.11.0040 02.C5.11.0041 02.C5.11.0042 02.C5.11.0043 02.C5.11.0044 02.C5.11.0045 02.C5.11.0046 02.C5.11.0070 02.C5.11.0075 02.C5.11.0077 02.C5.21.0033 02.C5.21.0034 Component ID 2LP-215-27 2LP-215-3 2LP-215-5 2LP-215-6 2LP-215-9 2LP-216-1 2LP-216-10 2LP-216-14 2LP-216-15 2LPS-724-1 2LPS-724-17 2LPS-724-2 2HP-222-126AA 2HP-222-1060 Insp System Date 53A 05/09/10 Insp Insp Status Limited Geo Ref RFR Comment 53A 53A 53A 53A 53A 53A 53A 53A 14B 14B 14B 61A 05/09/10 05/08/10 05/08/10 05/09/10 05/08/10 05/08/10 05/08/10 05/08/10 05/10/10 05/10/10 05/10/10 02/03/10 CLR CLR CLR OLR OLR CLR OLR CLR CLR CLR OLR CLR CLR Y N Y UT-1 0-466 PIP 0-10-02605 was written to determine the corrective action for the limited coverage achieved for this item.N N N UT-10-421 N N N UT-10-415 N N N UT-10-413 N N N UT-1 0-422 N N N UT-10-414 N N N UT-10-416 N N N UT-10-417..

N N N UT-10-418 N N N UT-1 0-437 N N N UT-I10-439 N N N UT-10-438 N N N UT-09-365 N N N UT-09-364 51A 02/03/10 CLR Printed 7/14/2010 2:20:04 PM Ick8302 v. 01/01/08 SDQA Cat "C" Oconee 2 7/14/2010 2:17:26 PM Page 9 of 22 0 Summary No 02.C5.21.0035

.2.C5.21-.0036 02.C5.21.0051 02.C5.21.0053 02.C5.21.0054 02.C5.21.0489 02.C5.51.0005 02.C5.51.0006

-2.C5.51..0014 02.C5.51.0018 Component ID 2HP-341-V1 Insp System Date 51A 02/02/10 2-51A-28-65 2-51 A- 17-97 2-51A-1 7-98B 2-51A-17-98D 2-51 A-1 7-96 2MS-123-27 2MS-103-9 2FDW-210-21 2-03A-67-7 51A 51A 51A 51A 51A 01A 01A 03A 03A 02/02/10 05/11/10 05/05/10 05/05/10 05/11/10 05/12/10 05/15/10 05/14/10 02/03/10 Insp Status CLR CLR CLR CLR CLR CLR CLR CLR CLR CLR FOR INFORI*O N ONLY lnsp Geo Limited Ref RFR Y N Y v'I 0 N N N N N N N N Y Comment UT-09-362 PIP 0-10-02605 was written to determine the corrective action for the limited coverage achieved for this item.UT-09-360 UT-10-479 UT-I 0-386 UT-1 0-387 UT-10-474 UT-1 0-465 UT-10-494 UT-10-488 UT-09-363 Indications 1 & 2 were determined to be geometric reflectors due to weld backing ring.02.C5.51.0022 02.C5.51.0035 2FDW-226-37 2LPS-606-2 03 14B 05/15/10 02/03/10 CLR CLR N N N UT-10-495 N Y N UT-09-367 Indications 1 2, & 3 were determined to be geometric reflectors due to weld backing ring.SDQA Cat "C" Oconee 2 7/14/2010 2:17:26 PM Page 10 of 22 Printed 7/14/2010 2:20:04 PM Ick8302 v. 01/01/08 FOR INFORM'4 ONLY!Insp Insp Insp Geo System Date Status Limited Ref RFR Comment 0 Summary No 02.C5.51.0036 02.C5.51.0038 O2.C5.51..0042 02.C5.51.0053 02.C5.61.0004 02.D1.20.0004 02.D1.20.0009 02.D1.20.0027 02.F1.11.0001 02.F1.11.0008 02.F1.12.0008 02.F1.20.0014 02.F1.20.0025 02.F1.20.0035 Component ID 2LPS-606-3 2LPS-606-82 2FDW-226-36 2-03-18-44AA 2-14-238-24 2-03-0-1401A-R7 2-03A-0-1400A-MDH-1 101 2-57-0-1481A-H4 2-51A-0-1479A-HlOA 2-53A-0-1480A-H26C 2-53A-0-1478A-H 1A 2-51A-3-0-437B-DE048 2-51A-0-1439C-H166 2-53B-0-435B-DE015 14B 02/03/10 CLR 14B 02/03/10 03 05/15/10 03 05/11/10 03A 05/14/10 03 04/29/10 03A 03/01/10 57 05/08/10 51A 04/29/10 53A 04/29/10 53A 05/08/10 51A 04/14/10 51A 02/04/10 53B 02/10/10 CLR CLR CLR CLR CLR CLR CLR CLR CLR CLR CLR CLR CLR N Y N UT-09-368 Indication 1 was determined to be root geometry.N N N UT-09-366 N N N UT-10-496 N N N UT-1 0-471 N N N RT-NA N N N VT-10-543 N N N VT-10-473 N N N VT-i 0-544 N N N VT-10-528 N N N VT-i10-529 N N N VT-10-540 N N N VT-10-477 N N N VT-09-464 N N N VT-09-468 Printed 7/14/2010 2:20:04 PM Ick8302 v. 01/01/08 SDQA Cat "C" Oconee 2 7/14/2010 2:17:26 PM Page 11 of 22 S Summary No 02.F1.20.0040 Component ID 2-53B-2-0-435B-R69 System 53B 02.F1.20.0042 02.F1.20.0054 02.F1.20.0056 02.F1.21.0011 02.F1.21.0016 02.F1.21.0021 02.F17.21.0023 02.F17.21.0030 02.F17.21.0038 02.F17.21.0039 2-53B-1-0-1439C-DE067 2-54A-3-0-1439C-H5 53B 54A Insp Date 02/10/10 02/04/10 02/04/10 02/10/10 05/04/10 Insp Status CLR 2-54A-3-0-435B-R10 2-14-1478F-H6091 2-51A-0-1478A-H13C 2-51A-2-0-438C-SP115 2-51 B-436J-DE01 3 2-53B-5-0-1436A-R5 2-56-438B-DE002 2-56-0-1478A-H 11 FOR INFORIMON ONLY!Insp Geo Limited Ref RFR Comment N N N VT-09-467 54A 14 51A 05/17/10 51A 04/08/10 51B 04/28/10 53B 03/08/10 56 03/09/10 56 05/08/10 CLR REC CLR CLR CLR CLR CLR CLR REC CLR N N N N N N N N N N N N N N N N VT-09-463 VT-09-462 The discrepancies that were found were reviewed by civil engineering and the support was determined to be acceptable for service. Work Order # 01000992 was written to correct problems.VT-09-469 VT-10-536 N N VT-1 0-548 VT-10-478 N N N VT-10-511 N N N VT-i10-475 N N N VT- 10-476 The discrepancies that were found were reviewed by civil engineering and the support was determined to be acceptable for service.N N N VT-10-541 Printed 7/14/2010 2:20:04 PM Ick8302 v. 01/01/08 SDQA Cat "C" Oconee 2 7/14/2010 2:17:26 PM Page 12 of 22 S FOR INFORI*N ONLY!Insp Insp Insp Geo System Date Status Limited Ref RFR Summary No 02.F1.22.0002 021F1.22.0008 02.F1.22.0013 02.F1.22.0023 02.F1.22.0025 02.F1.30.0013 02.F1 .30.0014 02.F1.30.0020 02.F1.30.0035 02.F1.31.0002 02.F1.31.0004 02.F1.31.0015 02.F1.31.0025 Component ID Comment 2-01A-0-1481 B-H 11B 2-01A-0-1480A-HIA 2-51A-435B-DKB-1411 2-53B-5-0-1439A-H56 2-54A-3-0-435B-H25 2-03-0-1439B-H54 2-03A-1-0-1401 B-SR8 2-03A-0-1 400A-MDH-1 101 2-14B-0-437B-JEJ-1 705 2-03A-1-0-1401A-SR28 2-03A-1-0-1401B-SR4 2-07A-1400A-H4089 2-14B-1-0-1439-H-13 01A 05/02/10 REC 01A 51A 53B 54A 03 03A 03A 1 4B 03A 03A 07A 14B 05/11/10 02/10/10 01/27/10 02/10/10 04/28/10 04/27/10 03/01/10 05/13/10 0 7..........

I -2..04/27/10 04/27/10 03/01/10 01/28/10 CLR CLR CLR CLR CLR CLR CLR CLR CLR CLR CLR CLR N N N VT-10-530 The discrepancies that were found were reviewed by civil engineering and the support was determined to be acceptable for service. Work Order # 1895287 was written to correct problems.N N N VT-1 0-545 N N N VT-09-465 N N N VT-09-460 N N N VT-09-466 N N N VT-i0-512 N N N VT-10-514 N N N VT-i0-471 N N N VT-i 0-547 N N N VT-10-515 N N N VT-10-516 N N N VT-10-472 N N N VT-09-461 Printed 7/14/2010 2:20:04 PM Ick8302 v. 01/01/08 SDQA Cat "C" Oconee 2 7/14/2010 2:17:26 PM Page 13 of 22 FOR INFORMNN ONLY!Insp Insp Insp System Date Status Limited Geo Ref RFR Comment Summary No 02.F1.31.0027 02.F1.32.0004 02.F1.32.0014 02.F1.40.0019 02.F1.40.0027 02.G1.1.0001 02.G1.1.0005 02.G1.1.0006 02.G1.1.0007 02.G12.1.0005 02.G12.2.0001 02.G12.2.0002 02.G12.2.0005 Component ID 2-57-0-1481A-H4 2-03-0-1401A-R7 2-57-0-1480A-NWIZ 2-RCSR-FTR 2-50-RCPM-2B1-SS3 2-RCP-2A1 2-RCP-2A2 2-RCP-2B1 2-RCP-2B2 2-PDB2-11 2-RPV-WR53 57 03 57 05/08/10 05/03/10 04/29/10 03/10/10 04/29/10 04/28/10 05/16/10 05/03/10 05/03/10 05/10/10 05/09/10 CLR CLR CLR CLR CLR CLR CLR CLR CLR CLR CLR 50 50 50 50 50 50 N N N VT-1 0-542 N N N VT-i 0-531 N N N VT-10-526 N N N VT-i10-474 N N N VT-10-527 N N N UT-i10-369 N N N UT-10-497 N N N UT-10-376 N N N UT-1 0-378 N N N UT-10-464 Y N N UT-NA Greater than 90 % coverage was achieved.Y N N UT-NA Greater than 90 % coverage was achieved.N N N UT-10-370 2-RPV-WR53A 50 05/09/10 CLR 50 2-PIAI-7 04/29/10 CLR Printed 7/14/2010 2:20:04 PM Ick8302 v. 01/01/08 SDQA, Cat "C " Oconee 2 7/14/2010 2:17:26 PM Page 14 of 22 0 Summary No FOR INFOR M)N ONLY!Insp Insp Insp Geo System Date Status Limited Ref RFR Comment 0 Component ID 02.G12.2.0006 02;G12.2.0007 O2.G12.2.0008 02.G12.2.0009 I2.G12.2.0.10 02.G12.2.0011 02.G12.2.0012 02.G14.1.0001 02.G16.1.0001 02.G16.1.0002 02.G16.1.0003 02.G2.1.0001 02.G2.1 .0002 2-PIA2-7 2-PIB1-7 2-PI1B2-7 50 50 50 2-PDA1-2 2-PDA2-2 50 50 2-PDB1-2 2-PDB2-2 2-PZR-THERM 2 .............

.... ..2-50-7-8 2-50-7-9 2-50-7-ELBOW 2-PDB1-46 2-PDA2-46 50 50 50 50 50 50 50 50 04/30/10 05/03/10 05/01/10 04/30/10 05/02/10 05/03/10 05/03/10 04/27/10 05/03/10 05/03/10 05/03/10 05/07/10 05/04/10 CLR CLR REC CLR REC CLR CLR CLR CLR CLR CLR CLR CLR N N N N N N N N N N N N N UT-10-400 UT-1 0-390 UT-10-385 Indication

  1. 1 is a subsurface flaw that is acceptable per IWB-3514-2.

UT-10-371 UT-1 0-382 Indication

  1. l is a subsurface flaw that is acceptable per IWB-3514-2.

UT-10-395 UT-10-393 VT-10-506 UT-10-379 UT-i 0-3.80 UT-10-381 UT-10-411 UT-10-388 Printed 7/1412010 2:20:04 PM Ick83O2 v. 01101/08 SDQA Cat "C" Oconee 2 7/14/2010 2:17:26 PM Page 15 of 22 FOR INFORK* N ONLY!0 Summary No 02.G2.1.0003 02.G2.1.0004 02.G2.1.0005 02.G2.1.0006 02.G2.1.0007 02.G2.1.0008 02.G2.1.0009 02.G2.1.0010 02.G2.1.0011 02.G2.1.0012 02.G2.1.0013 02.G2.1.0014 02.G2.1.0015 02.G2.1.0016 Component ID 2-PDAl-46 2-PDB2-46 2-PDAl-11 2-PDA2-11 2-PDB2-11 ,2-PDBI-11 2-P DB.1-47 2-PDB2-47 2-PDA1-47 2-PDA2-47 2RC-204-37 2RC-202-17 2RC-203-32 2RC-205-1 Insp Insp System Date Status 50 05/04/10 CLR 50 05/07/10 CLR 50 05/10/10 CLR 50 05/10/10 CLR 50 05/10/10 CLR 50 05/10/10 CLR 50 05/10/10 CLR 50 05/10/10 CLR 50 05/10/10 CLR 50 05/10/10 CLR 50 05/06/10 CLR 50 05/09/10 CLR 50 05/06/10 CLR 50 05/09/10 CLR Insp Geo Limited Ref RFR Comment N N N UT-1 0-389 N N N UT-10-412 N N N UT-1 0-456 N N N UT-10-458 N N N UT-i 0-462 N N N UT-10-460 N N N UT-1 0-461 N N N UT-1 0-463 N N N UT-1 0-457 N N N UT-i10-459 N N N UT-10-401 N N N UT-10-432 N N N UT-1 0-402 N N N UT-1 0-433 Printed 7/14/2010 2:20:05 PM Ick8302 v. 01/01/08 SDQA Cat "C" Oconee 2 7/14/2010 2:17:26 PM Page 16 of 22 FOR INFORM*N ONLY!0 Insp Insp Insp System Date Status Limited Geo Ref RFR Comment Summary No 02.G2.1.0017 02.G2.1.0018 02.G2.1.0019 O2.G2.1 .0020 02.G2.1.0021 02.G2.1.0022 02.G2.1.0023 02.G2.1.0024 02.G4.1.0001 02.G4.1.0002 02.G4.1.0003 02.G4.1.0004 02.G4.1.0005 02.G4.1.0006 Component ID 2RC-203-3 2RC-202-19 2RC-204-20 2RC-205-3 2A2 THERM-SLEEVE 2B1 THERM-SLEEVE 2A1 THERM-SLEEVE 2B2 THERM-SLEEVE 2RC-202-1.7 2RC-202-19

.............

....................2RC-205-1 2RC-205-3 2HP-218-18 2HP-214-13 50 50 50 50 50 50 50 50 51A 51A 51A 51A 51A 51A 05/06/10 05(09/10 05/06/10 05/09/10 05/05/10 05/06/10 05/04/10 05/07/10 05/09/10 05/09/10 05/09/10 05/09/10 05/12/10 05/10/10 CLR CLR CLR CLR CLR CLR CLR CLR CLR CLR CLR CLR CLR CLR UT-10-403 UJT-10-435 UT-1 0-470 UT-10-434 RT-NA RT-NA RT-NA RT-NA UT-1 0-426 UT-10-427 UT-1 0-428 UT-1 0-430 UT-1 0-469 UT-10-442 Printed 7/14/2010 2:20:05 PM Ick8302 v. 01/01/08 SDQA Cat "C" Oconee 2 7/14/2010 2:17:26 PM Page 17 of 22 FOR INFOR W)N.ONLY!Insp Insp Insp System Date Status Limited Geo Ref RFR Comment Summary No 02.G4.1.0007 02.G4.1.0008 02.G4.1.0009 Component ID 2HP-214-15 2RC-202-4 2RC-203-4 51A 51A 51A 51A 05/10/10 05/07/10 05/09/10 05/04/10 CLR CLR CLR CLR N N N Y N N N N N N N N UT-10-440 RT-NA UT-1 0-429 RT-NA 02.G4.1.0010 02.G4.1.0011 O2.G4.1.0012 02.G4.1.0013 O2.G4.1.0014 02.G4.1.0015 O2.G4.1 .0016 02.G4.1.0017 2RC-204-4 2RC-205-4 51A 51A 51A 51A 51A 51A 51A 51A 51A 51A 05/06/10 05/05/10 05/06/10 05/06/10 05/09/10 05/10/10 05/11/10 05/11/10 05/11/10 05/10/10 2HP-214-14 2HP-216-7 2HP-216-8 2HP-216-9 2HP-217-10 2HP-217-11 CLR CLR CLR CLR CLR CLR CLR CLR CLR CLR CLR Greater than 90% coverage.UT-10-404 RT-NA UT-1 0-405 RT-NA UT-1 0-431 UT-10-441 UT-i10-455 UT-10-454 UT-1 0-453 UT-1 0-424 51A 05/10/10 N N N UT-10-425 Printed 7/14/2010 2:20:05 PM Ick8302 v. 01/01/08 SDQA Cat "C" Oconee 2 7/14/2010 2:17:26 PM Page 18 of 22 0 Summary No 02.G4.1.0018 O2.G4.1.0019 02.G4.1.0020 02.G4.1.0021 02.G4.1.0022 02.G4.1.0023 02.G4.1.0024 02.G4.1.0025 02.H3.1.0007 Component ID 2HP-217-12 2HP-218-20 2HP-218-21 2HP-218-22 2RC-203-32 2RC-203-3 2RC-204-37 2RC-204-20 2-03-18-25 System 51A 51A 51A 51A 50 50 50 50 03 Insp Date 05/10/10 05/12/10 05/12/10 05/12/10 05/06/10 05/06/10 05/06/10 05/06/10 05/15/10 Insp Status CLR CLR CLR CLR CLR CLR CLR CLR FOR INFORI ON ONLY!Insp Gf O NY Limited Ref RFR Comment N N N UT-i 0-423 N N N UT-10-406 N N N UT- 10-468 N N N UT-1 0-467 N N N UT-I10-407 N N N UT-10-408 N N N UT-10-409 N N N UT-10-410 UT-NA Thickness readings were taken on a grid per NDE-946 and forwarded to Oconee Engineering.

03 05/15/10 UT-NA 02.H3.1.0008 2-03-18-25G Thickness readings were taken on a grid per NDE-946 and forwarded to Oconee Engineering.

UT-NA Thickness readings were taken on a grid per NDE-946 and forwarded to Oconee Engineering.

02.H3.1 .0009 2-03-18-43A 03 05/13/10 Printed 7/14/2010 2:20:05 PM Ick8302 v. 01/01/08 SDQA Cat "C" Oconee 2 7/14/2010 2:17:26 PM Page 19 of 22 Summary No 02.H3.1.0010 FOR INFORMON ONLYI Insp Insp Geo Component ID 2-FWD60-A Insp System Date 03 05/13/10 03 05/13/10 Status Lin 02.H3.1.0011 2-03-18-43AA 02.H4.1.0002 02.H4.1.0008 2-03-0-1439B-H54 2-03-0-1401A-R7 03 03 03 01A OIA 01A 04/28/10 05/13/10 05/03/10 05/13/10 04/27/10 04/26/10 CLR CLR CLR CLR CLR REC nited Ref RFR Comment UT-NA Thickness readings were taken on a grid per NDE-946 and forwarded to Oconee Engineering.

UT-NA Thickness readings were taken on a grid per NDE-946 and forwarded to Oconee Engineering.

N N N VT-10-513 N N N MT-10-102 N N N VT-10-532 N N N MT-10-101 N N N VT-10-518 N N N VT-10-521 The discrepancies that were found were reviewed by civil engineering and the support was determined to be acceptable for service.N N N VT-10-519 The discrepancies that were found were reviewed by civil engineering and the support was determined to be acceptable for service. Work Order # 01007912 was written to correct problems.N N N VT-10-517 N N N VT-10-522 02.H4.1.0032 2-01A-0-1401B-R6 02.H4.1.0033 2-01A-0-14011B-H-10 REC 02.114.1.0034 2-01A-0-1401B-Ri5 01A 04/26/10 02.H4.1.0035 02.H4.1.0036 2-01A-OM-200-30-MS-1 2-01A-OM-200-30-MS-2 01A 04/26/10 CLR 01A 04/26/10 CLR Printed 7/14/2010 2:20:05 PM Ick8302 v. 01/01/08 SDQA Cat "C" Oconee 2 7/14/2010 2:17:26 PM Page 20 of 22 Summary No 02.H4.11.0037 02.H4.1.0038 02.H4.1.0039 02.H4.1.0040 02.H4.1.0050 Component ID 2-01A-0-1441-H16 2-01A-0-1441 -R9-1 2-01A-0-1441-H-17 2-01A-0-1401B-H18 2-01A-0-1441-R9-2 Insp System Date 01A 05/11/10 Insp Status REC FOR INFORV) N ONLY Insp Geo Limited Ref RFR N N N 01A 04/30/10 CLR 01A 05/04/10 REC 02.H4.1.0051 2-OIA-0-1441-R9-3 01A 01kA 01A 01A 01A 01A 01A 01A O1A 01A 05/04/10 04/26/10 04/30/10 04/29/10 05/13/10 04/29/10 05/13/10 04/29/10 05/09/10.05/12/10 CLR CLR CLR CLR CLR CLR CLR CLR CLR CLR N N N N N N N N N N N N Comment VT-10-546 The discrepancies that were found were reviewed by civil engineering and the support was determined to be acceptable for service.MT-10-095 VT-1 0-535 The discrepancies that were found were reviewed by civil engineering and the support was determined to be'acceptable for service. Work Order # 01007908 was written to correct problems.VT-10-537 VT-10-520 MT-10-096 VT-10-523 MT-10-103 VT-10-524 MT-10-104 VT-10-525 MT-10-099 UT-10-475 02.H4.1.0052 2-01A-0-1441-R9-4 02.H5.1.0001 02.H5.1.0002 2-01A-0-1441-Hi 2-MS9A-A Oconee 2 7/14/2010 2:17:26 PM Page 21 of 22 Printed 7/14/2010 2:20:05 PM Ick8302 v. 01/01/08 SDQA Cat "C" Summary No 02.H5.1.0002 Component ID 2-MS9A-A FOR INFOR?)N ONLY!Insp Insp Insp Geo System Date Status Limited Ref RFR Comment 01A 05/11110 UT-NA Thickness readings were taken on a grid per NDE-946 and forwarded to Oconee Engineering.

02.H6.11.0003 2MS-103-39 01A 05/12/10 CLR 01A 05/11/10 N N N UT-10-476 UT-NA Thickness readings were taken on a grid per NDE-946 and forwarded to Oconee Engineering.

02.H5.1.0004 2-MS 10A-A 01A 05/12/10 CLR 01A 05/11/10 N N N UT-10-477 UT-NA Thickness readings were taken on a grid per NDE-946 and forwarded to Oconee Engineering.

02.Q1.1.0001 02.Q1.1.0002 02.Q1.1.0003 02.Q1.1.0004 02.Q1.1.0005 02.Q1.1.0006 02.Q1.1.0007 2RC-326-21V 2RC-266-23V 2RC-326-22V 2-PZR-WP91-1-WOL 2-PZR-WP91-2-WOL 2-PZR-WP91-3-WOL 2-53A-10-13V 50 05/12/10 CLR 50 05/03/10 CLR 50 05/12/10 CLR 50 05/01/10 CLR 50 05/01/10 CLR .50 05/01/10 CLR 53A 05/10/10 CLR N N N N N N N N UT-10-472 N UT-10-377 N UT-10-473 N UT-10-373 N UT-10-374 N UT-10-375 N UT-10-443 Printed 7/14/2010 2:20:05 PM Ick8302 v. 01/01/08 SDQA Cat "C" Oconee 2 7/14/2010 2:17:26 PM Page 22 of 22 5

5.0 Owner's

Report for Repair and Replacement Activities As required by the applicable code, records of Class 1 and Class 2 Repair/Replacement Activities are included on NIS-2 forms in this section.There are 2 Class 1 NIS-2 forms included in this section for work performed during the 2EOC-23 reporting period. PIP 0-09-00530 was written to document that work orders 1762586 and 1779633 had work completed during 2EOC-23, but the documentation was not completed in time for the NIS-2 forms to be incorporated into 2EOC-23 report.The individual work request documents and manufacturers' data reports are on file at Oconee Nuclear Station. /5.1 Class 1 and 2 Preservice Examinations As required by the applicable code, Preservice Inspection (PSI) Examinations were performed on ISI Class land Class 2 items during this report period. PSI Examination data for items listed below is on file in the Oconee Nuclear Station QA Vault.Work Order 1869317 was written to apply weld overlay on a Class 1 drain nozzle to safe-end weld in system 51A. A PSI UT exam was performed on the weld overlay (Weld # 2-51A-0035-136V).

In addition to the information above, there is a list for PSI exams that were performed and the list is located behind the NIS-2 forms in this section. The list has one page and is entitled "Preservice Examinations of Class 1 & 2 Welds".PSI examination data for items on the list previously mentioned is on file in the Oconee Nuclear Station QA Vault.EOC 24 Refueling Outage Report Oconee Unit 2 Section 5 Page 1 of 1 Revision 0 July 14, 2010 Form NIS-2 Owner's Report for Repair/Replacement Activity As required by the provisions of the ASME Code Section XI U.S Work Order Number 1 1780230 Sheet 1 of 3 1. Owner 2. Plant Unit Duke Energy Carolinas, LLC Oconee Nuclear Station ONS -2 526 South Church Street 7800 Rochester Hwy Date Charlotte, NC 28201-1006 Seneca, SC 29672 6/3/2010 3. Work Performed by Type Code Symbol Stamp Not Applicable Duke Energy Carolinas, LLC Authorization Number 526 South Church Street Not Applicable Charlotte, NC 28201-1006 Expiration Date Not Applicable

4. Identification of System, ASME Class Reactor Coolant System, ASME Class 1 5.(a) Applicable Construction Code: USAS B31.7 19 69 Edition, No Addenda, Code Case (b) Applicable Edition Section Xl Utilized For R/R Activity 19 98 Edition, 2000 Addenda.(c) Applicable Section XI Code Case(s)6. Identification of Components Name of Name of Manufacturer National Other Year Corrected, ASME Component Manufacturer Serial Number Board No. Identification Built Removed, Code or Installed Stamped (Yes / No)2RC-2 Kerotest Unknown Unknown Unk Removed 2RC-2 Flowserve 48BLT 2285 2008 Installed YES 2RC-210 Velan 062044-1 None 2006 Installed YES 2RC-211 Flowserve 89BNV 2428 2009 Installed YES Piping DEC None None 2010 Corrected NO Support /w Snubber Grinnell None None Unk. Removed NO 50-0-1481A-Hi Support/w Snubber DEC None None 2010 Corrected NO 50-0-1481 A-H3 Support/w Snubber DEC None None 2010 Corrected NO 2-50-0-1481 A-H6 7. Description of Work Replaced valve 2RC-2 and portion of RC piping, installed Valve 2RC-210 and 2RC-21 1, and modified, removed and installed support/restraints.
8. Test Conducted D Hydrostatic D Pneumatic 0 Nominal Operating Pressure D Exempt D Other Pressure PSI Test Temperature OF Form NIS-2 Owner's Report for Repair/Replacement Activity As required by the provisions of the ASME Code Section XI S Work Order Number 1780230 Sheet 2 of 3 1. Owner 2. Plant Unit Duke Energy Carolinas, LLC Oconee Nuclear Station ONS -2 526 South Church Street 7800 Rochester Hwy Date Charlotte, NC 28201-1006 Seneca, SC 29672 6/3/2010 3. Work Performed by Type Code Symbol Stamp Not Applicable Duke Energy Carolinas, LLC Authorization Number 526 South Church Street Not Applicable Charlotte, NC 28201-1006 Expiration Date Not Applicable
4. Identification of System, ASME Class Reactor Coolant System, ASME Class I"5.(a) Applicable Construction Code: USAS B31.7 19 69 Edition, No Addenda, Code Case (b) Applicable Edition Section Xl Utilized For R/R Activity 19 98 Edition, 2000 Addenda.(c) Applicable Section Xl Code Case(s)6. Identification of Components Nameof Name of Manufacturer National Other Year Corrected, ASME Component Manufacturer Serial Number Board No. Identification Built Removed, Code or Installed Stamped (Yes / No)Support/w SSnubber Snubber Grinnell None None Unk. Removed NO 50-0-148 1A-H7 Support/w Snubber 50-0-1481A-DEC None None 2010 Installed NO H7 Support 2-50-1481A-'

DEC None None 2010 Corrected NO_H6688Nt)w Support 2-50-148 IA- DEC None None 2010 Installed NO H6689 (New)Snubber Grinnel 35407 Unk. Removed NO For H I Snubber Grinnel 33408 Unk. Removed NO for H7 Z Snubber Anvil 36430 Unk. Installed NO for H7 Snubber Sbr HAnvil 37350 Unk. Installed NO for H6689 II I t 4 + 4 4 Form NIS-2 Owner's Report for Repair/Replacement Activity As required by the provisions of the ASME Code Section XI I Work Order Number 1780230 Sheet 3of 3 F 9. Remarks (Applicable Manufacturer's Data Reports to be attached)0 S/R 50-0-1481A-H3, existing Grinnell Snubber Ser. # 36554 UTC 1832940, Clamp UTC 195366, Tube Steel UTC 1891638 &1944314, Flat Bar UTC 1929450, Rear Bracket UTC 1954313, load pin UTC 1907439@ S/R 2-50-0-481A-H6, Round Bar UTC 1930814, Plate UTC 1823969§ S/R 50-0-481 A-H7, Anvil Snubber Ser. # 36430 UTC 01953111, Clamp UTC 1912968, Beam UTC 1898849, Angle UTC 1892608, Rear Bracket UTC 1900953, load pin UTC 1907439 0 0 0 0 CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code, Section X1.Type Code Symbol Stamp Not Applicable

, Certificate of Authorization Number Not Applicable Expiration Date Not Applicable Signed ____-,_-Date.

___0____Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of o,,7,v 2,vZ0.1,v,4 and employed by HSB CT of Hartford, Connecticut have inspected the components described in this Owner's Report during the period --3 to -2?-.o ,and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

____ ___ ____ ___Commissions 9'L .2__ A//A, 7'C ziInspector's Signature National Board, State, Province, and Endorsements Date / -/Q Form NIS-2 Owner's Report for Repair/Replacement Activities As required by the provisions of the ASME Code Section Xl Work Order Nunbe 01838586 -01 Sheet Page 1 of 2 I.Owner Duke Energy Carolinas, LLC 2. Plant Oconee Nuclear Station Unit 2 526 South Church Street 7800 Rochester Hwy .Date 5/13/2010 Charlotte, NC 28201-1006 Seneca, SC 29672-0752

3. Work Performed By Type Code Symbol Stamp I Not Applicable Duke Energy Carolinas, LLC Authorization Number 526 South Church Street Not Applicable Charlotte, NC 28201-1006 Expiration Date Not Applicable
4. Identification of Systems, ASME Class Reactor Coolant , ASME Class 1 5.(a) Applicable Construction Cod USAS B31,1 1967: EditionR No Addenda No Code Case (b) Applicable Edition Section Xl Utilized For RIR Activity 1998: Edition, 2000. Addenda (c) Applicable Section Xl Codes Cases(s) None 6. identification of Coimponents Name of Component Manufacturer.

Manufacturer National Other Year Corrected, ASME Code Serial Number Board No identification Built Removed or Stamped I I I I I I Installed (Yes/No)1) 50-0-1479A-H2A, Config. B Grinnell N/A IUNK N/A UNK Removed No reservoir.

50-0-1479A-H2A, Config. A Anvil 36558 LUNK UTC UNK Installed No reservoir.

1832940 7. Descrption of Work REBUILD HYDRAULIC SNUBBER 8. Test Conducted Li Hydrostatic Li] Pnuematic E] Nominal Operating Pressure Li Excempt [W1 Other Visual Pressure PSI Test Temperature Deg. F]

Form NIS-2 Owner's Report for Repair/Replacement Activities As required by the provisions of the ASME Code Section Xl Work Order Numbe Sheet 01838586 -01 Page 2 of 2 7. Remarks (Applicable Manufactuen's Data Reports to be attached)1) Rebuilt snubber due to leaking seals, CERTIFICATION OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code,Section XI Type Code Symbol Stamp Not Applicable Certificate of Autherization Number Not Applicable Expiration Date Not Applicable Signed __ _ _ _ Date _ _ _ _ _Owner or Owner's Designee, Title CERTIFICATION OF INSERVICE INSPECTION I. the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and 'State or province of F/LORIPA11 and employed by " HSB CT " of .,, Hartford, Connecticut have inspected the components described in the Owner's Report during the period 9-//- .2 o>03 to 7 .2o ___, and state that to the best of my.. knowledge and. belief, the Owner has performed examinations and taken corrective measures described in this.Owner's Report. in accordance with the requirements of the ASME Code, Section Xl.By signing this certificate neither the inspector nor his employer make any warrenty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind rising from or connected with this inspection.

Commision(s) rzoard, 7 t P en d inspclors

~~ilieNational Board, State, Province, and Endorsements Date Oý~ -----

Form NIS-2 Owner's Report for Repair/Replacement Activities S As required by the provisions of the ASME Code Section XI Work Order Numbe 01838586 -02 Sheet Page 1 of 2 1. Owner Duke Energy Carolinas, LLC 2. Plant Oconee Nuclear Station Unit 2 I 2 526 South Church Street 7800 Rochester Hwy Date 5/13/2010 Charlotte, NC 28201-1006 Seneca, SC 29672-0752

3. Work Performed By rType Code Symbol Stamp Not Applicable Duke Energy Carolinas, LLC t Authorizatio~n Number 526 South Church Street Not Applicable Charlotte, NC 28201-1006 Expiration Date Not Applicable
4. Identification of Systems, ASME Class Reactor Coolant , ASME Class I (a) Applicable Construction Cod USjQ3j 1967: Edition. N2 Addenda No Code Case (b) Applicable Edition Section XI Utilized For RJR Aclivity 1998: Edition, 2000 Addenda (c) Applicable Section Xl Codes Cases(s) None 6. identification of Coimponents Name of Component Manufacturer.

Manufacturer National Other Year Corrected, ASME Code 1 Serial Number Board No identification Built Removed or Stamped Installed (Yes/No)1) 50-0-1481A-H3, Reservoir Valve Grinnell 36971 UNK N/A UNK Removed No Block 50-0-1481A-H3, Cylinder seals Anvil N/A UNK UTC UNKI Installed No".. 1.830992 ,,., 50-0-1481A-H3, Config. A Cylinder Anvil 36554 UNK aUTC UNK Installed No kit 1832940 7. Description of Work REBUILD HYDRAULIC SNUBBER 8. Test Conducted-Hydrostatic 7 Pnuematic

[ Nominal Operating Pressure E Excempt "k Other Visual Pressure PSI Test Temperature Deg. F Form NIS-2 Owner's Report for Repair/Replacement Activities O As required by the provisions of the ASME Code Section Xl Work Order Numbe Sheet 01838586 02 Page 2 of 2 7. Rerharks (Applicable Manufactueres Data Reports to be attached)1) Replaced Reservoir Valve Block with Config. A Cylinder kit and cylinder seals.CERTIFICATION OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code,Section XI Type Code Symbol Stamp Not Applicable Certificate of Autherization Number Not Applicable Expiration Date Not Applicable Signed , '/ K >p_ _ _ _ __Date S11__311-__0 Ownero Owrs Designee, Title CERTIFICATION OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and State or province of oDl ., employedby HSB CT of Hartford, Connecticut have inspected the components described in the Owner's Report during the period -//- ,20 to e -.2o/ , and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owners Report in accordance with the requirements of the ASME Code, Section XL.By signing this certificate neither the inspector nor his employer make any warrenty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind rising from or connected with this inspection.

Commision(s)

X A z A-s Inspectors tue National Board, State, Province, and Endorsements Date 8 Form NIS-2 Owner's Report for Repair/Replacement Activities As required by the provisions of the ASME Code Section XI I.Work Order Numbe 01838586 -22 Sheet Page 1 of 2 1. Owner Duke Energy Carolinas, LLC 2. Plant Oconee Nuclear Station Unit j 2 526 South Church Street 7800 Rochester Hwy a Charlotte, NC 28201-1006 Seneca, SC 29672-0752

3. Work Performed By Type Code Symbol Stamp Not Applicable Duke Energy Carolinas, LLC Authorization Number 526 South Church Street Not Applicable Charlotte, NC 28201-1006 Expiration Date Not Applicable
4. Identification of Systems, ASME Class Low Pressure Injection , ASME Class 1 5.(a) Applicable Construction Cad USAS 831.1 1967: Edition, No Addenda No Code Case (b) Applicable Edition Section XI Utilized For R/R Activity 1998: Edition, 2000 Addenda (C) Applicable Section X) Codes Casesis) NO-6. Identificaticn of Coimpoenents Name of Component Manufacturer:

Manufacturer National Other Year Corrected, ASME Code Serial Number Board No identification Built Removed or Stamped_ I I _ I _ Installed (Yes/No)1) 53-0-1478A-H3, 2 1/2 x 5 Grinnell 35060 UNK N/A UNK Removed No Hydraulic Snubber 53-0-1478A-H3, 2 1/2 x 5 Hydraulic Anvil 36548 UNK UTC UNK Installed No Snubber ., 1956422 7. Description REPLACE HYDRAULIC SNUBBER 8. Test Conducted D] Hydrostatic

_- Pnuematic E] Nominal Operating Pressure -Excempt [ Other Visual Pressure PSI Test Temperature Deg. F Form NIS-2 Owner's Report for Repair/Replacement Activities As required by the provisions of the ASME Code Section XI Work Order Numbe Sheet 01838586 -22 Page 2 of 2 7. Remarks (Applicable Manufactuerr's Data Reports to be attached)1) Replaced snubber due to leaking seals.CERTIFICATION OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code,Section XI Type Code Symbol Stamp Not Applicable Certificate of Autherization Number Not Applicable Expiration Date Not Applicable Signed ___.......

Date ,_/0__/_Owner or Owner7s Designee, Title CERTIFICATION OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the Nattonal Board of Boiler and Pressure Vessel Inspectors and State orprovince of and employed by HSB CT of '.Hartford.

Connecticut*

.: have inspected the components described in the Owner's Report during the period 8-1/- .2D9 ___ to 7- 8 -2o / O .. and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.By signing this certificate neither the inspector nor his employer make any warrenty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind rising from or connected with this inspection.Z Commision(s) ,ez;. _ ,V" ..

National Board, State. Province, and Endorsements Date J'u-Y 8 2 Form NIS-2 Owner's Report for Repair/Replacement Activity As required by the provisions of the ASME Code Section Xl Work Order Number 1845096 Sheet 1 of 2 1. Owner 2. Plant Unit Duke Energy Carolinas, LLC Oconee Nuclear Station ONS -2 526 South Church Street 7800 Rochester Hvwy Date Charlotte, NC 28201-1006 Seneca, SC 29672 7/13/2010 3. Work Performed by Type Code Symbol Stamp Not Applicable Duke Energy Carolinas, LLC Authorization Number 526 South Church Street Not Applicable Charlotte, NC 28201-1006 Expiration Date Not Applicable

4. Identification of System, ASME Class Reactor Coolant, ASME Class I 5.(a) Applicable Construction Code: USAS B31.7 19 68 Edition, No Addenda, NO Code Case (b) Applicable Edition Section XI Utilized For R/R Activity 19 98 Edition, 2000 Addenda.(c) Applicable Section XI Code Case(s) None 6. Identification of Components Name of Name of Manufacturer National Other Year Corrected, ASME Component Manufacturer Serial Number Board No. Identification Built Removed, Code or Installed Stamped (Yes / No)2-50-1D.E.C.

NONE NONE NONE 1973 Corrected NO H6707 ; Hanger 7. Description of Work Replaced bent/damaged rod on support.8. Test Conducted F-- Hydrostatic F Pneumatic D Nominal Operating Pressure [7 Exempt D Other Pressure PSI Test Temperature OF Form.NIS-2 Owner's Report for Repair/Replacement Activity As required by the provisions of the ASME Code Section XI Work Order Number Sheet-1845096 2 of 2 9. Remarks (Applicable Manufacturer's Data Reports to be attached)o 3/8" Diam. Round Bar, Carbon Steel, ASTM A36, UTC # 01892605; M HT 502193 0 0 o S 0 0 CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code,Section XI.Type Code Symbol Stamp Not Applicable Certificate of Authorization Number Not Applicable Expiration Date Not Applicable Signed Zachary Ashcraft/Engineer Date 7/13/2010--Ofer or OwnCr's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of FJo R;DA and employed by HSB CT of Hartford, Connecticut have inspected the components described in this Owner's Report during the period 5- ' 261 to 7- 14 -,o , and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section Xl.By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the.Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

Commissions 61-/ , ZE. A3iA'I. iS InspectoPrgnature National Board,-State Province, and Endorsements Date ,'-/ /4, ,e/

Form NIS-2 Owner's Report for Repair/Replacement Activity As required by the provisions of the ASME Code Section XI q Work Order Number 01855940-01 Sheet 1 of 2 1, Owner 2. Plant Unit Duke Energy Carolinas, LLC Oconee Nuclear Station ONS -2 526 South Church Street 7800 Rochester Hwy Date Charlotte, NC 28201-1006 Seneca, SC 29672 5/17/2010 3. Work Performed by Type Code Symbol Stamp Not Applicable Duke Energy Carolinas, LLC Authorization Number 526 South Church Street Not Applicable Charlotte, NC 28201-1006 Expiration Date Not Applicable 4, Identification of System, ASME Class Reactor Coolant, ASME Class 1 5.(a) Applicable Construction Code: USAS B31.7 19 69 Edition, No Addenda, None Code Case (b) Applicable Edition Section Xl Utilized For R/R Activity 19 98 Edition, 2000 Addenda.(c) Applicable Section XI Code Case(s) None 6. Identification of Components Name of Name of Manufacturer National Other Year Corrected, ASME Component Manufacturer Serial Number Board No. Identification Built Removed, Code or Installed Stamped (Yes / No)Spare Pressurizer Code Saetyuvale Dresser BL-08895 n/a none 1971 Corrected YES Code Safety valve 7. Description of Work Installed replacement disc, serial number ADW-52 from stock.8. Test Conducted F-" Hydrostatic D Pneumatic

[- Nominal Operating Pressure D Exempt Other Set Pressure & leak Pressure PSI Test Temperature OF d9j1,X (f vlý ý Form NIS-2 Owner's Report for Repair/Replacement Activity As required by the provisions of the ASME Code Section XI Work Order Number Sheet 1 01855940-01 2 of 2 9. Remarks (Applicable Manufacturer's Data Reports to be attached)o Disc serial number ADW-52.O NOTE: For traceability, Valve serial number BL-08895 was installed on work order: 01880753-06.

0 0 G 0 0 0 0 CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code,Section XI.Type Code Symbol Stamp Not Applicable Certificate of Authorization Numb.Ver .Not Applicable Expiration Date Not Applicable Signed , Sr. Engineer Date 7- / 0Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of FA,2,O A. and employed by HSB CT of Hartford, Connecticut have inspected the components described in this Owner's Report during the period .5r-/7---/o to 7-1.7 -ZO/0 , and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section X1.By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

Commissions A A19 /Insp-ecs Signature National Board, Stafe, Province, and Endorsements Date 7u-i v /.z...Z ,o/ -f~~e ~

Form NIS-2 Owner's Report for Repair/Replacement Activity As required by the provisions of the ASME Code Section XI Work Order Number 01856049-01 Sheet 1 of 2 1. Owner 2. Plant Unit Duke Energy Carolinas, LLC Oconee Nuclear Station ONS -0 526 South Church Street 7800 Rochester Hwy Date Charlotte, NC 28201-1006 Seneca, SC 29672 5-18-10 3. Work Performed by Type Code Symbol Stamp Not Applicable Duke Energy Carolinas, LLC Authorization Number 526 South Church Street Not Applicable Charlotte, NC 28201-1006 Expiration Date Not Applicable

4. Identification of System, ASME Class Reactor Coolant, ASME Class 1 5.(a) Applicable Construction Code: USAS B331.7 19 69 Edition, No Addenda, None Code Case (b) Applicable Edition Section XI Utilized For R/R Activity 19 98 Edition, 2000 Addenda.(c) Applicable Section Xl Code Case(s) None 6. Identification of Components Name of Name of Manufacturer National Other Year Corrected, ASME Component Manufacturer Serial Number Board No. Identification Built Removed, Code or Installed Stamped (Yes I No)PORV, RC-66 Dresser BY-93617 none none 2004 Corrected YES Spare____________

_______ ___ __7. Description of Work Replaced pilot disc assembly, serial number ADZ06."8. Test Conducted]Hydrostatic

]Pneumatic 1:] Nominal Operating Pressure 1 Exempt Other Set pressure test Pressure PSI Test Temperature OF (f o47 Form NIS-2 Owner's Report for Repair/Replacement Activity As required by the provisions of the ASME Code Section X1 I I Work Order Number I Sheet 2 of 2 01856049-01

9. Remarks (Applicable Manufacturer's Data Reports to be attached)0 Pilot disc assembly, serial number ADZ06 0 o o 0 0 CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code,Section XI.Type Code Symbol Stamp Not Applicable Certificate of Authorization Number Not Applicable Expiration Date Not Applicable Signed e .zi,, / -Sr. Engineer Date 5/18/2010 Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of .--Sg Zv L ,w_ .Q and em ployed by HSB CT of Hartford, Connecticut have inspected the components described in this Owner's Report during the period //- Z -7 to I-e L5-- o , and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

_ _ _ _ _ _ _ _ _ _ _ Com m issions S e-f "_. ,,- ,,.f Inspector's Signature National Board, State, Province, and Endorsements Date *__ --,, _ ____o Form NIS-2 Owner's Report for Repair/Replacement Activity As required by the provisions of the ASME Code Section Xl Work Order Number 1 01866950 Sheet 1 of 2 1. Owner 2. Plant Unit Duke Energy Carolinas, LLC Oconee Nuclear Station ONS -2 526 South Church Street 7800 Rochester Hwy Date Charlotte, NC 28201-1006 Seneca, SC 29672 5/23/2010 3. Work Performed by Type Code Symbol Stamp Not Applicable Duke Energy Carolinas, LLC Authorization Number 526 South Church Street Not Applicable Charlotte, NC 28201-1006 Expiration Date Not Applicable

4. Identification of System, ASME Class High Pressure Injection, ASME Class I 5.(a) Applicable Construction Code: USAS B31.7 19 69 Edition, No Addenda, No Code Case (b) Applicable Edition Section XI Utilized For R/R Activity 19 98 Edition, 2000 Addenda.(c) Applicable Section XI Code Case(s) None 6. Identification of Components Name of Name of Manufacturer National Other Year Corrected, ASME Component Manufacturer Serial Number Board No. Identification Built Removed, Code or Installed Stamped (Yes / No)~UTC 1901035, Valve 2HP-990 Flowserve 76BKE 1983 STC 901035,E 2007 Installed YES Serial #: 76BKE 7. Description of Work EC100145 installed new valves 2HP-983, -984, -985, -986, -987, -988, -989, and -990. Valve 2HP-990 is ISI A. All other valves are ISI B.w8. Test Conducted[]Hydrostatic E]Pneumatic Nominal Operating Pressure 1 Exempt ED Other Pressure PSI I Test Temperature

_- _ OF Form NIS-2 Owner's Report for Repair/Replacement Activity As required by the provisions of the ASME Code Section Xl Work Order Number 01866950 Sheet 2 of 2 9. Remarks (Applicable Manufacturer's Data Reports to be attached)0 0 0§0 0 0 CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code,Section XI.Type Code Symbol Stamp Not Applicable Certificate of Authorization Number Not Applicable Expiration Date Not Applicable Signed Sir/ Date 524p.I 0 Ow-ner or Oxv rsDesignee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of ?._ / _. 9 and employed by HSB CT of Hartford.

Connecticut have inspected the components described in this Owner's Report during the period _ -__--_o ___to g , and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

Inspector's Signature Commissions FLJ 2-J f IS __.__- Z_National Board, State. Province.

and Endorsements Date 66-a __

Form NIS-2 Owner's Report for Repair/Replacement Activity As required by the provisions of the ASME Code Section Xl Work Order Number 01869317 Sheet 1 of 2 1. Owner 2. Plant Unit Duke Energy Carolinas, LLC Oconee Nuclear Station ONS -2 526 South Church Street 7800 Rochester Hwy Date Charlotte, NC 28201-1006 Seneca, SC 29672 6/8/2010 3. Work Performed by Type Code Symbol Stamp Not Applicable Duke Energy Carolinas, LLC Authorization Number 526 South Church Street Not Applicable Charlotte, NC 28201-1006 Expiration Date Not Applicable

4. Identification of System, ASME Class Reactor Coolant, ASME Class I 5.(a) Applicable Construction Code: USAS B31.7 19 69 Edition, No Addenda, No Code Case (b) Applicable Edition Section X1 Utilized For R/R Activity 19 98 Edition, 2000 Addenda.(c) Applicable Section X1 Code Case(s) 2142-2. N-504-3, and N-638-1 6. Identification of Components Name of Name of Manufacturer National Other Identification Year Corrected, ASME Component Manufacturer Serial Number Board No. Built Removed, Code or Installed Stamped (Yes I No)Reactor Coolant System 2-1/2" Letdown Line:RCS Nozzle 13&W None None Weld # 2R1BI-1 1 1974 Corrected NO to safe-end butt weld Reactor Coolant System 2-1/2" Item 88 on Dwgs: Letdown Line: B&W None None OM 1201-1472.001 1974 Corrected NO Safe End OM 1201-3415.001 Reactor Coolant System 2-1/2" Letdown Line: B&W None None Weld f 2-5 1A-0035 1974 Corrected NO Safe-end to pipe 15A elbow butt weld Reactor Coolant System 2-1/2" Letdown Line: SS B&W None None None 1974 Corrected NO pipe elbow S/R # 2-59-0-1478A4-590 DPCo. None None None UNK Corrected NO 1478A-H-28
7. uescription ot Work A full structural weld is applied over: I )a portion oftthe low alloy steel RCS nozzle, 2) the nozzle to safe-end butt weld, the safe-end, 3) the safe-end to piping elbow butt weld, and 4) a portion of a letdown line pipe elbow. SIR also modified.8. Test Conducted-Hydrostatic

-]Pneumatic M Nominal Operating Pressure 1-- Exempt R Other Pressure PSI Test rc mperature OF Form NIS-2 Owner's Report for Repair/Replacement Activity As required by the provisions of the ASME Code Section XI I Work Order Number 01869317 Sheet 2 of 2 9. Remarks (Applicable Manufacturer's Data Reports to be attached)0 2S/R # 2-59-0-1478A-H28, portion of channel removed 0 0 0 0 0 0 0§CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code,Section XI.Type Code Symbol Stamp Not Applicable Certificate of Authorization Nu ber Not Applicable Expiration Date Not Applicable Signed a 7 JA.4'- AIc .9 Date /Owner or Owner's Designee, Title -CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Sor,-v , and employed by HSB CT of Hartford, Connecticut have inspected the components described in this Owner's Report during the period .5-- /s-,o to 7- 7-/o , and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section Xl.By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

Inspector's Signature Date 7- "7-le Commissions SC- ?-3 ,2 /A,C 1 National Board, State, Province, and Endorsements Form NIS-2 Owner's Report for Repair/Replacement Activity As required by the provisions of the ASME Code Section XI U Work Order Number 01879162 Sheet 1 of 2 1. Owner 2. Plant Unit Duke Energy Carolinas, LLC Oconee Nuclear Station ONS -2 526 South Church Street 7800 Rochester Hwy Date Charlotte, NC 28201-1006 Seneca, SC 29672 6/1/2010 3. Work Performed by Type Code Symbol Stamp Not Applicable Duke Energy Carolinas, LLC Authorization Number 526 South Church Street Not Applicable Charlotte, NC 2820 1-1006 Expiration Date Not Applicable

4. Identification of System, ASME Class Reactor Coolant System, ASME Class I 5.(a) Applicable Construction Code: USAS B31.7 19 69 Edition, No Addenda, No Code Case (b) Applicable Edition Section Xl Utilized For R/R Activity 19 98 Edition, 2000 Addenda.(c) Applicable Section XI Code Case(s) None 6. Identification of Components Name of Component Name of Manufacturer Manufacturer Serial Number National Board No.Other Identification Year Built Corrected, Removed, or Installed ASME Code Stamped (Yes I No)4 4 + + + 4 I) Piping DEC None None None 2010 Installed NO 7. Description of Work EC 103426 replaced two Furmanite injection fittings with an pump. Reference OM- 1201 .D-0057-001 for details.alternate leak injection fitting on the 2A2 reactor coolant-I!8. Test Conducted-Hydrostatic F Pneumatic Z Nominal Operating Pressure -- Exempt D Other Pressure PSI Test Temperature OF Form NIS-2 Owner's Report for Repair/Replacement Activity As required by the provisions of the ASME Code Section XI Work Order Number Sheet I 01879162 2 of 2 9. Remarks (Applicable Manufacturer's Data Reports to be attached)o An alternate leak iniection fitting consists of a 1/4" pipe plug UTC#0001915059 and 1/8" injection valve UTC.#0000883033 0 0 0 0 0§0 CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code,Section XI.Type Code Symbol Stamp Not Aplplicable Certificate of Authorization Number Not Applicable Expiration Date Not Applicable Signed -c Rick Burgess, Sr. Technical Specialist Date 6/1/2010 Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of _-and employed by HSB CT of Hartford, Connecticut have inspected the components described in this Owner's Report during the period _ to .7- -_.____ , and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

_.____,,,._

Commissions

_A __In rco S tNational Board, State, P rovince. and Endorsements Date.2L4,.o)

Form NIS-2 Owner's Report for Repair/Replacement Activity As required by the provisions of the ASME Code Section XI'U Work Order Number 01903357-01 Sheet 1 of 2!1. Owner 2. Plant Unit Duke Energy Carolinas, LLC Oconee Nuclear Station ONS -2 526 South Church Street 7800 Rochester Hwy Date Charlotte, NC 28201-1006 Seneca, SC 29672 5/12/2010 3. Work Performed by Type Code Symbol Stamp Not Applicable Duke Energy Carolinas, LLC Authorization Number 526 South Church Street Not Applicable Charlotte, NC 28201-1006 Expiration Date Not Applicable

4. Identification of System, ASME Classc ao4g"77ASME Class I 5.(a) Applicable Construction Code: USAS B31.7 19 69 Edition, No Addenda, N/A Code Case (b) Applicable Edition Section Xl Utilized For R/R Activity 19 98 Edition, 2000 Addenda.(c) Applicable Section XI Code Case(s) None 6. Identification of Components Name of Name of Manufacturer National Other Year Corrected, ASME Component Manufacturer Serial Number Board No. Identification Built Removed, Code or Installed Stamped (Yes I No)2RC-160 Valcor Unknown Unknown None 1997 Corrected YES 7. Description of Work Replaced the disc assembly in 2RC-160 Valcor Solenoid Valve.8. Test Conducted D Hydrostatic E] Pneumatic E Nominal Operating Pressure Exempt LI Other Visual Pressure .PSI Test Temperature OF v Form NIS-2 Owner's Report for Repair/Replacement Activity As required by the provisions of the ASME Code Section XI I Work Order Number Sheet 01903357-01 2 of 2 9. Remarks (Applicable Manufacturer's Data Reports to be attached)o Disc assembly, Cat ID 436024, UTC # 0000984929 0 A 0 0 0 0.CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code,Section XI.Type Code Symbol Stamp Not Applicable Certific e of Authorization Number Not Applicable Expiration Date Not Applicable Signe -M Date 0/OTk wner or Owner's Designee, Title 6'CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of ,C-/.,,esO,q and employed by HSB CT of Hartford, Connecticut have inspected the components described in this Owner's Report during the period .T-to 1'-2/1 -,o and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

Commissions

'A 7' 4r nsp r's Signature National 13orrd, State, Prov'nce, and Endorsements Date .ýOL,/ g, I, Form NIS-2 Owner's Report for Repair/Replacement Activity As required by the provisions of the ASME Code Section XI p Work Order Number 1 01915262 Sheet 1 of 2 1. Owner 2. Plant Unit Duke Energy Carolinas, LLC Oconee Nuclear Station ONS -2 526 South Church Street 7800 Rochester Hwy Date Charlotte, NC 28201-1006 Seneca, SC 29672 6/1/2010 3. Work Performed by Type Code Symbol Stamp Not Applicable Duke Energy Carolinas, LLC Authorization Number 526 South Church Street Not Applicable Charlotte, NC 28201-1006 Expiration Date Not Applicable

4. Identification of System, ASME Class Reactor Coolant, ASME Class I 5.(a) Applicable Construction Code: USAS B331.7 19 69 Edition, No Addenda, No Code Case (b) Applicable Edition Section XI Utilized For R/R Activity 19 98 Edition, 2000 Addenda.(c) Applicable Section XI Code Case(s) None 6. Identification of Components Name of Component Name of Manufacturer Manufacturer Serial Number National Board No.Other Identification Year Built Corrected, Removed, or Installed ASME Code Stamped (Yes / No).4. .4- .4. 4 4 Valve 2RC-213 Flowserve 90BQA 2630 UTC 1957435 2010 Installed YES (I) Support 2-57-148) B-H6694 2 DEC None None None UNK Corrected NO (2) Support 2 DEC None None None UNK Corrected NO 14811B-H6695 (3) Support 2-57-, DEC None None None UNK Corrected NO 14811B-H6692
  • h h 7. Description of Work EC 103030 installed two I" vent valves on pressurizer vent piping. 2RC-2 13 is Class A. 2RC-214 is Class B. Modified supports 2-57-1481 B-H6694, 2-57-1481 B-H6692, 2-57-1481 B-H6695 mu 8. Test Conducted D Hydrostatic E] Pneumatic N Nominal Operating Pressure F Exempt [-- Other Pressure ____ PSI Test Temperature OF Form NIS-2 Owner's Report for Repair/Replacement Activity As required by the provisions of the ASME Code Section X I Work Order Number Sheet I 01915262 2 of 2 9. Remarks (Applicable Manufacturer's Data Reports to be attached)o Support 2-57-1481B-H6694, attached 1/4" x 1" x 2-3/4" plate@ Support 2-57-1481B-H6695, replaced 1/4" x 1" x 2-3/4" plate O Support 2-57-1481B-H6692, attached 1/4" x I" x 2-3/4" plate 0 0 0 0 CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code,Section XI.Type Code Symbol Stamp Not Applicable Certificate of Authorization Number Not Applicable Expiration Date Not Applicable Signed Ax ., Al Bill Foster, Engineer Ill Date 6/1/2010 Owner or Ox-ncrIs Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of -zo_,1 and employed by HSB CT of Hartford, Connecticut have inspected the components described in this Owner's Report during the period ___ to -- ;- /. , and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any. personal injury or property damage or a loss of any kind arising from or connected with this inspection.

_ýa Commissions SC

/ý'nspe ctor'sSignature National Board, State, Province, and Endorsements Date ___-" "/_

Form NIS-2 Owner's Report for Repair/Replacement Activity As required by the provisions of the ASME Code Section XI'U Work Order Number 01922410-01 Sheet 1 of 2 1. Owner 2. Plant Unit Duke Energy Carolinas, LLC Oconee Nuclear Station ONS -2 526 South Church Street 7800 Rochester Hwy Date Charlotte, NC 28201-1006 Seneca, SC 29672 3. Work Performed by Type Code Symbol Stamp Not Applicable Duke Energy Carolinas, LLC Authorization Number 526 South Church Street Not Applicable Charlotte, NC 28201-1006 Expiration Date Not Applicable

4. Identification of System, ASME Class Reactor Coolant, ASME Class 1 5.(a) Applicable Construction Code: USAS B31.7 19 69 Edition, No Addenda, NA Code Case (b) Applicable Edition Section X1 Utilized For R/R Activity 19 98 Edition, 2000 Addenda.(c) Applicable Section X1 Code Case(s) None 6. Identification of Components Name of Name of Manufacturer National Other Year Corrected, ASME Component Manufacturer Serial Number Board No. Identification Built Removed, Code or Installed Stamped (Yes I No)2RC-156 Valcor Unknown Unknown None 1997 Corrected YES U.I 4, 4 4- + I.* 4 4- 4 4 4, 4 4 4- 4 + 4, +1 4- + 4 4 4, 4 4 4 4- 4, 4, 4 7. Description of Work Replaced the disc assembly in 2RC-156 Valcor Solenoid Valve during seat leak repair U v 8. Test Conducted F-1 Hydrostatic Pneumatic Nominal Operating Pressure [] Exempt Z Other Visual Pressure PSI Test Temperature OF Form NIS-2 Owner's Report for Repair/Replacement Activity As required by the provisions of the ASME Code Section X1 A CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code,Section XI.Type Code Symbol Stamp Not Applicable Certificate of Authorization Number Not Applicable Expiration Date Not Applicable Signed __ _ ___, _ ______ __ _ Date 6-A"/i0 ( Owner or Owner's Designee, Title I CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of and employed by HSB CT of Hartford, Connecticut have inspected the components described in this Owner's Report during the period .S /,/- X0,/0 to 7-1. -,Zo1/ , and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

! _

..4z ,4/T7 " A/C /.A-C Co msin c/-. --16 AF AI ' -R AlU /.C'Date LTuj.Yv;lnse s Signature P12 i6It Nation@I Board, StaterProvirnce, and Endorsements Form NIS-2 Owner's Report for Repair/Replacement Activity As required by the provisions of the ASME Code Section XI Work OrdeI 40 1 o r Number 1762586 Sheet I of 2 1. Owner 2. Plant Unit Duke Power Company Oconee Nuclear Station ONS -2 526 South Church Street 7800 Rochester Hwy Date Charlotte, NC 28201-1006 Seneca, SC 29672 1/27/2009 3. Work Performed by Type Code Symbol Stamp Not Applicable Duke Power Company Authorization Number 526 South Church Street Not Applicable Charlotte, NC 2820 1-1006 Expiration Date Not Applicable

4. Identification of System, ASME Class GWD, ASME Class/$-5.(a) Applicable Construction Code: USAS B3 1.1 19 67 Edition, No Addenda, Code Case (b) Applicable Edition Section Xl Utilized For R/R Activity 19 98 Edition, 2000 Addenda.(c) Applicable Section X1 Code Case(s)6. Identification of Components Name of Name of Manufacturer National Other Year Corrected, ASME Component Manufacturer Serial Number Board No. Identification Built Removed, Code or Installed Stamped (Yes / No)1)802 Duke N/A N/A N/A 2008 Corrected NO 148013-H6700 (2) S/R 2-57-(28IB Duke N/A N/A N/A 2008 Corrected NO 148013-H6701 (3) S/R 2-(3)01908-Duke N/A N/A N/A 2008 Removed NO OD201908-01 (4) S/R 2-(4)0]908-Duke N/A N/A N/A 2008 Removed NO OD201908-02 (5) S/R 2-(5)01908-Duke N/A N/A N/A 2008 Removed NO OD201908-03
7. Description of Work Pipe Hanger modifications and removals.Test Conducted D Hydrostatic D_ Pneumatic D Nominal Operating Pressure Exempt D Other Pressure PSI Test Temperature OF Form NIS-2 Owner's Report for Repair/Replacement Activity /As required by the provisions of the ASME Code Section XI Work Order Number 01762586 Sheet 2 of 2 9. Remarks (Applicable Manufacturer's Data Reports to be attached)o S/R 2-57-1480B-H6700:

Removed U-bolt, added (2) angles I l/2"x 1 1/2" x 1/4"* S/R 2-57-1480B-H6701:

Added flat bar 1/2" x 3/4" x 2 1/2" O S/R 2-OD201908-01:

Removed angle, plate and anchor bolts O S/R 2-OD201908-02:

Removed angle 2 1/2" x 2 1/2" x 1/4" 0 S/R 2-OD201908-03:

Removed angle 2 1/2" x 2 1/2" x 1/4" 0 0 0 CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code,Section XI.Type Code Symbol Stamp Not Applicable Certificate of Authorization Number Not Applicable Expiration Date Not Applicable Signed d,)J .t)-, 5 " j,, Date /Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of rlat%-,V ýl ., 'x2,, and employed by HSB CT of Hartford, Connecticut have inspected the components described in this Owner's Report during the period to e -,&"- 0,7 , and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

I______________________

Commissions

_________//_________

Inspector's Signature National Board, State, Province, and Endorsements Date 1-7-J'-07' Form NIS-2 Owner's Report for Repair/Replacement Activity As required by the provisions of the ASME Code Section XI Work Order Number 1779633 Sheet I of 22. Plant Unit Duk[e Power Company Oconee Nuclear Station ONS -2 526 South Church Street 7800 Rochester Hwy Date Charlotte, NC 28201-1006 Seneca, SC 29672 12/3/2008 3. Work Performed by Type Code Symbol Stamp Not Applicable Duke Power Company Authorization Number 526 South Church Street Not Applicable Charlotte, NC 28201-1006 Expiration Date Not Applicable

4. Identification of System, ASME Class Steam Generator, ASME Class 1 5.(a) Applicable Construction Code: ASME Section II1 19 89 Edition, No Addenda, No Code Case (b) Applicable Edition Section XI Utilized For R/R Activity 19 98 Edition, 2000 Addenda.(c) Applicable Section Xl Code Case(s) None 6. Identification of Components Name of Name of Manufacturer National Other Year Corrected, ASME Component Manufacturer Serial Number Board No. Identification Built Removed, Code or Installed Stamped (Yes / No)Inspection Port l est Cover B & W Canada 160K-01 214 PN# 5231484 2005 Removed YES ssembly # I Inspection Port Test Cover B & W Canada 160K-02 215 PN# 5231483 2005 Removed YES Assembly #2 Inspection Port Test Cover B & W Canada 160K-03 216 PN# 5231760 2005 Removed YES Assembly #3 Inspection Port Test Cover B & W Canada 160K-03 216 PN# 5231854 2005 Removed YES Assembly #3 Flange Inspection Port Test Cover B & W Canada 160K-04 217 PN# 5231790 2005 Removed YES Assembly #4 Inspection Port B & W Canada 006K-03 207 PN# 5206081 2003 Installed YES Cover @ Port #9 Inspection Port B & W Canada 006K-03 207 PN# 5206081 2003 Installed YES Cover @ Port #10 Inspection Port B & W Canada 006K-03 207 PN# 5206081 2003 Installed YES Cover @ Port #11 Inspection Port B & W Canada 006K-03 207 PN# 5206081 2003 Installed YES Cover @ Port #14 7. Description of Work n Unit 2 "A" Steam Generator one instrumented inspection port cover was removed at each support location at #9, #10,#11 and #14 and the original port cover was installed.
8. Test Conducted_ Hydrostatic 0 Pneumatic 0 Nominal Operating Pressure F Exempt F Other Pressure PSI Test Temperature OF..-0 Form NIS-2 Owner's Report for Repair/Replacement Activity As required by the provisions of the ASME Code Section X1 Work Order Number 1779633 I Sheet 2 of 2.Remarks (Applicable Manufacturer's Data Reports to be attached)0 0 0 CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code,Section XI.Type Code Symbol Stamp Not Applicable Certificate of Authorization Number Not Applicable Expiration Date Not Applicable Signed ¢/ K.W. Rannou/ Engineer Date 12/3/2008 Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Ako.er,/ Z-vozVA and employed by HSB CT of Hartford, Connecticut have inspected the components described in this Owner's Report during the period & -//- 0 6 to -Y- f f , and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

____________________Commissions ,iJL ~~u, Inspector's Signature National Board, State, Province, and Endorsements Date 3- '- C f Form NIS-2 Owner's Report for Repair/Replacement Activity As required by the provisions of the ASME Code Section XI I Work Order Number 1827688 Sheet 1 of 2 1. Owner 2. Plant Unit Duke Power Company Oconee Nuclear Station ONS -2 526 South Church Street 7800 Rochester Hwy Date Charlotte.

NC 28201-1006 Seneca, SC 29672 3/25/2009 3. Work Performed by Type Code Symbol Stamp Not Applicable Duke Power Company Authorization Number 526 South Church Street Not Applicable Charlotte, NC 28201-1006 Expiration Date Not Applicable

4. Identification of System, ASME Class Reactor Building Spray System, ASME Class 2 5.(a) Applicable Construction Code: ASME Section III 19 74 Edition, 1975 Addenda, Code Case (b) Applicable Edition Section X! Utilized For R/R Activity 19 98 Edition, 2000 Addenda.(c) Applicable Section XI Code Case(s) None 6. Identification of Components Name of Name of Manufacturer National Other Year Corrected, ASME Component Manufacturer Serial Number Board No. Identification Built Removed, Code or Installed Stamped (Yes / No)2BS-27 BNL Ind. Inc. A070815-1-4 Unknown PN# 05D-2015 2007 Installed YES A07085-1-4UTC#

1906160 PN# 05D-2015 2BS-28 BNL Ind. Inc. A070815-1-5 Unknown PN# 19016 2007 Installed YES UTC# 1906161 2BS-29 BNL Ind. Inc. A 070815-1-6 Unknown UT# 19016 2007 Installed YES UTC# 1906162 7. Description of Work Install 3 high point vents on 2B Reactor Building Spray header.8. Test Conducted D- Hydrostatic

] Pneumatic N Nominal Operating Pressure Exempt [N Other Visible Pressure PSI Test Temperature OF Form NIS-2 Owner's Report for Repair/Replacement Activity As required by the provisions of the ASME Code Section XI Work Order Number 1827688 Sheet 2of 2 9. Remarks (Applicable Manufacturer's Data Reports to be attached)o Installation included: a) 1" pipe cap, SC48381, ASME SA182, F304, 3000#b) 1" pipe, SC 149441. ASME SA376, TP304, Sch 80 c) 3/8" plate, SC 151125, ASME SA240, 304 hot rolled d) 1" ball valve, SC859599, SA479, 316 SS; SA453 Gr 660 bolting 0 0§0 0 CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code, Section Xl.Type Code Symbol Stamp Not Applicable Certificate of Authorization Number Not Applicable Expiration Date Not Applicable Signe Date _____-"/_

_Ownerr Owner's De itle CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of 5"o ,7-, , and employed by HSB CT of Hartford, Connecticut have inspected the components described in this Owner's Report during the period --d to .- 1., 07 , and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

Commissions 5" 3 ..,/A,5=-Inspector' s Signature Date "'-,2- :,,,'National Board, State, Province, and Endorsements Form NIS-2 Owner's Report for Repair/Replacement Activities As required by the provisions of the ASME Code Section XI Work Order Nmbo-.3 Sheet 01843596 -01 Page 1 of 2 1. Owner Duke Energy Carolinas, LLC 2. Plant Oconee Nuclear Station Unit I 2 526 South Church Street 7800 Rochester Hwy Charlotte, NC 28201-1006 Seneca, SC 29672-0752

3. Work Performed By Type Code Symbol Stamp Not Applicable Duke Energy Carolinas, LLC Authorization Number 526 South Church Street Not Applicable Charlotte, NC 28201-1006 Expiration Date Not Applicable
4. Identification of Systems, ASME Class Low Pressure Service Water , ASME Class 2 5.(a) Applicable construction Cod USAS B31.1 1967: Edition, No Addenda No Code Case (b) Applicable Edition Section Xl Utilized For RPR Activity 1998: Edition, 2000 Addenda (c) Applicable Section Xi Codes Cases(s) None 6. Identification of Coimponents Name of Component Manufacturer:

Manufacturer National Other Year Corrected, ASME Code Serial Number Board No identification Built Removed or Stamped I I I I I I Installed (Yes/No)4 inch Sch 40 pipe Duke N/A UNK N/A 2010 Installed No 7. Description of Work Replacement of 4 ft section of 4 inch Sch 40 carbon steel (CS) piping between valve 2LPSW-564 and 10 inch header with new CS pipe.8. Test Conducted F- Hydrostatic D Pnuematic

[ Nominal Operating Pressure R Excempt R] Other Funtional Pressure PSI Test Temperature Deg. F Form NIS-2 Owner's Report for Repair/Replacement Activities As required by the provisions of the ASME Code Section XI Work Order Numbe Sheet 01843596 -01 Page 2 of 2 7. Remarks (Applicable Manufactuerr's Data Reports to be attached)4" Sch. 40 SA1 06 Gr. B pipe, Cat. ID 0000149336 CERTIFICATION OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code, Section Xl Type Code Symbol Stamp Not Applicable Certificate of Autherization Number Not Applicable Expiration Date Not Applicable Signed Geary L. Armentrout, Principal Engineer ate5/18/2010 Owner or Owners Designee, Title CERTIFICATION OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and State or province of , L.-.dw, and employed by HSB CT of Hartford, Connecticut have inspected the components described in the Owners Report during the period /0 -1 o-c ' to o -.- ,O , and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.By signing this certificate neither the inspector nor his employer make any warrenty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind rising from or connected with this inspection.

~~~~~Commision(s)

&'C"_,. U/ _Inspector's Signature National Board, State, Province, and Endorsements Date Form NIS-2 Owner's Report for Repair/Replacement Activity As required by the provisions of the ASME Code Section XI Work Order Number 1 01873906 Sheet 1 of 2 1. Owner 2. Plant Unit Duke Energy Carolinas, LLC Oconee Nuclear Station ONS -2 526 South Church Street 7800 Rochester Hwy Date Charlotte, NC 28201-1006 Seneca, SC 29672 6/2/2010 3. Work Performed by Type Code Symbol Stamp Not Applicable Duke Energy Carolinas, LLC Authorization Number 526 South Church Street Not Applicable Charlotte, NC 28201l-1006 Expiration Date Not Applicable

4. Identification of System, ASME Class High Pressure Injection, ASME Class 2 5.(a) Applicable Construction Code: USAS B31.7 19 69 Edition, No Addenda, No Code Case (b) Applicable Edition Section XI Utilized For R/R Activity 19 98 Edition, 2000 Addenda.(c) Applicable Section Xl Code Case(s) None 6. Identification of Components Name of Name of Manufacturer National Other Year Corrected, ASME Component Manufacturer Serial Number Board No. Identification Built Removed, Code or Installed Stamped (Yes / No)Valve 2HP-103 Crane Co OA21447-06 UNK UNK UNK Removed NO Valve 2HP-107 Crane Co OA21447-05 UNK UNK UNK Removed NO Valve 2HP-I II Crane Co OA21447-05 UNK UNK UNK Removed NO Valve 2 HP-103 Valv'ech.

Inc. 10102224 None UTC 1958219 2010 Installed YES Valve 2HP-107 ValvTech.

Inc. 10102222 None UTC 1958217 2010 Installed YES Valve 2HP- I0I ValvTech.

Inc. 10102223 None UTC 1958218 2010 Installed YES Valve 21HP-993 ValvTech.

Inc. 10102225 None UTC 1958220 2010 Installed YES (1) Piping DEC None None None 2010 Installed NO (2) Support 2-51A-6-0-435B-DEC None None None UNK Corrected NO SR58 1 1 7. Description of Work EC100768 -Replaced 6" Class B valves 2HP-103, -107, and -1. Installed new 6" flanged valve 2HP-993. Replaced 1/2" vent 2HP-443, added new 1/2" vents 2HP-991 and -992. Modified support/restraint.

8. Test Conducted D Hydrostatic Pneumatic Nominal Operating Pressure [] Exempt D Other Pressure PSI Test Temperature OF Form NIS-2 Owner's Report for Repair/Replacement Activity As required by the provisions of the ASME Code Section X1 Work Order Number 1 01873906 Sheet 2 of 2 9. Remarks (Applicable Manufacturer's Data Reports to be attached)0 Installed 6" piping, (8) 6" flanges, (192) 3/4" nuts, and (96) 3/4" studs 0 Support 2-51 A-6-0-435B-SR58, removed plate and installed Fig. 640 sway strut and 6" pipe clamp 0 0 0 0 0 0 0 CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code,Section XI.Type Code Symbol Stamp Not Applicable Certificate of Authorization Number Not Applicable

_ Expiration Date Not Applicable Signed ____ William W Foster Jr, Engineer Ill Date 6/2/2010 OAneorvor wner's Designee.

Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of S-oe,-'A,.e,.,/, and employed by HSB CT of Hartford, Connecticut have inspected the components described in this Owner's Report during the period .3-V-.,,o

_ to ( -7.- o , and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section Xl.By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

4 ~4~ui~#'Inspector's Slgnature Date ,_"-/'2 Commissions SC? ?.1.A/A 6C, /_S National Board. State, Provincc, and Endorsements Form NIS-2 Owner's Report for Repair/Replacement Activity As required by the provisions of the ASME Code Section XI F Work Order Number 01880548-02, -06 Sheet1 of 2 e p->1. Owner 2. Plant Unit Duke Energy Carolinas, LLC Oconee Nuclear Station ONS -2 526 South Church Street 7800 Rochester Hwy Date Charlotte, NC 28201-1006 Seneca, SC 29672 5/11/2010 3. Work Performed

'by Type Code Symbol Stamp Not Applicable Duke Energy Carolinas, LLC Authorization Number 526 South Church Street Not Applicable Charlotte, NC 28201-1006 Expiration Date Not Applicable

4. Identification of System, ASME Class LPSW -Piping to 2C Reactor Building Cooling Unit (RBCU) Coils, ASME Class 2 5.(a) Applicable Construction Code: USAS B31.7 19 69 Edition, No Addenda, No Code Case (b) Applicable Edition Section XI Utilized For R/R Activity 19 98 Edition, 2000 Addenda.(c) Applicable Section XI Code Case(s) None 6. Identification of Components Name of Name of Manufacturer National Other Year Corrected, ASME Component Manufacturer Serial Number Board No. Identification Built Removed, Code or Installed Stamped (Yes / No)2C RBCU Coil bolting -for coils Duke Unknown None None 2010 Installed NO 1,2,3 & 4 (1)7. Description of Work Preventative Maintenance (PM) on the 2C RBCU Coils # 1, #2, #3 & #4 (tube cleaning & ECT) required removal of the cooler waterbox.

This involved disassembling the Low Pressure Service Water (LPSW) piping from the coils. The 5/8-inch diameter LPSW piping bolting material for piping-to-coil flanges required replacement due to surface degradation.

8. Test Conducted D Hydrostatic 1 Pneumatic , Nominal Operating Pressure [-- Exempt D Other Pressure PSI Test Temperature OF Form NIS-2 Owner's Report for Repair/Replacement Activity As required by the provisions of the ASME Code Section XI Work Order Number 01880548-02, -06 Sheet 2 of 2 9. Remarks (Applicable Manufacturer's Data Reports to be attached)o Replaced one hundred twenty-eight (128) 5/8-inch diameter nuts and sixty-four (64) 5/8-inch diameter studs on the 2C RBCU,#1, #2, #3 and #4 Coils' flanges. The Catalog ID # for the nuts is 293556 and the UTC #'s were 0001949181

& 0001953584.

The CataloL ID # for the stud material (threaded rod) is 297412 and the UTC # was 0001949785.

0 0 0 0 0§CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code,Section XI.Type Code Symbol Stamp Not Applicable Certificate of Authorization Number Not Applicable Expiration Date Not Applicable Signed -Engineer Date 5/111 2-Ofo 9vner or Ownerfs Designee, TitleI CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of e._ '.,=.,O.-

and employed by HSB CT of Hartford, Connecticut

  • have inspected the components describec:1 in this Owner's Report during the period 7-Z F-C 7 to --2 7-,'a , and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section Xl.By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

I .._ ..... .q " , "VýAoll,/

,, Inspector's Signature Date -/0 Commissions.

... .National Board, State, Province, and Endorsements Form NIS-2 Owner's Report for Repair/Replacement Activity As required by the provisions of the ASME Code Section XI U I Work Order Number 01880740 Sheet 1 of 2 1. Owner 2. Plant Unit Duke Energy Carolinas, LLC Oconee Nuclear Station ONS -2 526 South Church Street 7800 Rochester Hwy Date Charlotte, NC 28201-1006 J Seneca, SC 29672 5/22/2010 3. Work Performed by Type Code Symbol Stamp Not Applicable Duke Energy Carolinas, LLC Authorization Number 526 South Church Street Not Applicable Charlotte, NC 28201-1006 Expiration Date Not Applicable 4, Identification of System, ASME Class 2BA-172, Breathing Air System, ASME Class 2 51 (a) Applicable Construction Code: USAS B31.7 19 69 Edition, No Addenda, No Code Case (b) Applicable Edition Section XI Utilized For RFR Activity 19 98 Edition, 2000 Addenda.(c) Applicable Section Xl Code Case(s) None 6. Identification of Components Name of Component Name of Manufacturer Manufacturer Serial Number National Board No.Other Identification Year Built Corrected, Removed, or Installed ASME Code Stamped (Yes I No)1. 4 4. 4- 4 4. I 2BA-172 ITT Engineered Valves UNK UNK UTC 0001924056 UJNK Installed NO 7. Description of Work Modification replaced original EPDM (rubber based) seat rings with PEEK (Polymer) based seat rings. The PEEK is not suitable for applications where tight sealing is required.

A new set of EPDM seat rings were installed back in 2BA-172. The ball was also replaced to make sure that the ball was not contributing to the leakage. There was no defect found on the original ball.-p 8. Test Conducted D Hydrostatic 0 Pneumatic D- Nominal Operating Pressure El Exempt Z Other Cont Isol Seat Leak Pressure PSI Test Temperature OF Form NIS-2 Owner's Report for Repair/Replacement Activity As required by the provisions of the ASME Code Section XI Work Order Number Sheet 01880740 2 of 2 9. Remarks (Applicable Manufacturer's Data Reports to be attached)o Part= Ball for 2" ITT ball valve.., catalog ID 311092, UTC # 000192, Trace PN # 16394, Heat Code # 9GHN-1 & -2 e 0 0 0 CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code, Section Xl.Type Code Symbol Stamp Not Applicable Certificate of A rizati n u Not Applicable Expiration Date Not Applicable Signed --,'dfzAC " , , David D King Date 5-22-2010 0 ner or Design e, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of and employed by HSB CT of Hartford, Connecticut have inspected the components described in this Ownees Report during the period ,y.-o to 8-.1o/' ,and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any Kind arising from or connected with this inspection.

Commissions

/7 X/8 A4-',/V WS IS In r's Signature National Board, State, Province, and Endorsements Date ,-ZL" , 2o/o Form NIS-2 Owner's Report for Repair/Replacement Activity As required by the provisions of the ASME Code Section X1 U Work Order Number 01881074-01 Sheet 1 of 2 1. Owner 2. Plant Unit Duke Energy Carolinas, LLC Oconee Nuclear Station ONS -2 526 South Church Street 7800 Rochester Hwy Date Charlotte, NC 28201-1006 Seneca, SC 29672 5/13/2010 3. Work Performed by Type Code Symbol Stamp Not Applicable Duke Energy Carolinas, LLC Authorization Number 526 South Church Street Not Applicable Charlotte, NC 28201-1006 Expiration Date Not Applicable

4. Identification of System, ASME Class High Pressure Injection, ASME Class 2 5.(a) Applicable Construction Code: USAS B31.7 19 69 Edition, No Addenda, No Code Case (b) Applicable Edition Section Xi Utilized For R/R Activity 19 98 Edition, 2000 Addenda.(c) Applicable Section Xl Code Case(s) None 6. Identification of Components Name of Name of Manufacturer National Other Year Corrected, ASME Component Manufacturer Serial Number Board No. Identification Built Removed, Code or Installed Stamped (Yes I No)2HP-31 Fisher Controls 4768610 None None 1971 Corrected NO 7. Description of Work PM performed on the valve found the valve plug was eroded F8. Test Conducted D Hydrostatic n Pneumatic D Nominal Operating Pressure D Exempt [] Other Visual Pressure PSI Test Temperature OF Form NIS-2 Owner's Report for Repair/Replacement Activity As required by the provisions of the ASME Code Section XI Work Order Number Sheet 0 -01881074-01 2 of 2 9. Remarks (Applicable Manufacturer's Data Reports to be attached)O Valve plug/stem assembly, CAT ID 860541, UTC 00001938474 0 0 0 0 o CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code,Section XI.Type Code Symbol Stamp Not Applicable Certificate of Authorization Number Not Applicable Expiration Date Not Applicable Signed Date S_1_1, __ _Owner or Owner's Designee, TVitle I CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of F-zo,/ IDA and employed by HSB CT of Hartford, Connecticut have inspected the components described in this Owner's Report during the period 5 .2 0 / c5 to 0 -,2n1 , and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section Xl.By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

Commissions

_v/- A.4, Ivs /s I ector's Signature National Board, State, Prbvince, and Endorsements Date37.LvR -q ,

Form NIS-2 Owner's Report for Repair/Replacement Activity As required by the provisions of the ASME Code Section XI S I Work Order Number 01884502-02, -06 Sheet lof 2c}1. Owner 2. Plant Unit Duke Energy Carolinas, LLC Oconee Nuclear Station ONS -2 526 South Church Street 7800 Rochester Hwy Date Charlotte, NC 28201-1006 Seneca, SC 29672 5/11/2010 3. Work Performed by Type Code Symbol Stamp Not Applicable Duke Energy Carolinas, LLC Authorization Number 526 South Church Street Not Applicable Charlotte, NC 28201-1006 Expiration Date Not Applicable

4. Identification of System, ASME Class LPSW -Piping to 2B Reactor Building Cooling Unit (RBCU) Coils, ASME Class 2 5.(a) Applicable Construction Code: USAS B31.7 19 69 Edition,.

No Addenda, No Code Case.(b) Applicable Edition Section XI Utilized For R/R Activity 19 98 Edition, 2000 Addenda.(c) Applicable Section X1 Code Case(s) None 6. Identification of Components Name of Name of Manufacturer National Other Year Corrected, ASME Component Manufacturer Serial Number Board No. Identification Built Removed, Code or Installed Stamped (Yes / No)IRBCU Coil olting -for coils Duke Unknown None None 2010 Installed NO 1,2,3 &4 (I)7. Description of Work Maintenance on the 2B RBCU Coils # 1, #2, #3 & #4 (tube cleaning) required removal of the cooler waterbox.

This involved disassembling the Low Pressure Service Water (LPSW) piping from the coils. The 5/8-inch diameter LPSW hiping bolting material for piping-to-coil flanges reouired replacement due to surface degradation.

d S.Test Conducted Tes] Hydrostatic ted Pneumatic Nominal Operating Pressure [-- Exempt Other Pressure PSI Test Temperature OF Form NIS-2 Owner's Report for Repair/Replacement Activity As required by the provisions of the ASME Code Section XI I Work Order Number Sheet 0 01884502-02, -06, 2 of 2 9. Remarks (Applicable Manufacturer's Data Reports to be attached)0 Replaced one hundred twenty-eight (128) 5/8-inch diameter nuts and sixty-four (64) 5/8-inch diameter studs on the 2B RBCU,#1, #2, #3 and #4 Coils' flanges. The Catalog ID # for thenuts is 293556 and the UTC # was 0001949181.

The Catalog ID # for the stud material (threaded rod) is297412 and the UTC # was 0001953045.

0 o 0 0 o CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code, Section Xl.Type Code Symbol Stamp Not Applicable Certificate of Authorization Number Not Applicable Expiration Date Not Applicable Signed )O/T,-,//

Engineer Date 57i /20/cywner or Owner' Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of _,,, , and employed by HSB CT of Hartford, Connecticut have inspected the components described in this Owner's Report during the period f_ -_- _ 41 F to ar-- 7./bI , and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

_____a________Commissions Sc-1/T Inspector's Signature National Board, State, Province, and Endorsements Date !97- ?&7-lo Form NIS-2 Owner's Report for Repair/Replacement Activity As required by the provisions of the ASME Code Section XI U.Work Order Number 01884503-02, -09 Sheet 1. Owner 2. Plant Unit Duke Energy Carolinas, LLC Oconee Nuclear Station ONS -2 526 South Church Street 7800 Rochester Hwy Date Charlotte, NC 28201-1006 Seneca, SC 29672 5/11/2010 3. Work Performed by Type Code Symbol Stamp Not Applicable Duke Energy Carolinas, LLC Authorization Number 526 South Church Street Not Applicable Charlotte, NC 28201-1006 Expiration Date Not Applicable

4. Identification of System, ASME Class LPSW -Piping to 2A Reactor Building Cooling Unit (RBCU) Coils, ASME Class 2 5.(a) Applicable Construction Code: USAS B31.7 19 69 Edition, No Addenda, No Code Case (b) Applicable Edition Section Xl Utilized For R/R Activity 19 98 Edition, 2000 Addenda.(c) Applicable Section XI Code Case(s) None 6. Identification of Components Name of Name of Manufacturer National Other Year Corrected, ASME Component Manufacturer Serial Number Board No. Identification Built Removed, Code or Installed Stamped (Yes I No)TA RBCU Coil olting -for coils Duke Unknown None None 2010 Installed NO 1,2&a3 (I)7. Description of Work Maintenance on the 2A RBCU Coils 4 1, #2 & #3 (tube cleaning) required removal of the cooler waterbox.

This involved disassembling the Low Pressure Service Water (LPSW) piping from the coils. The 5/8-inch diameter LPSW h iping bolting material for piping-to-coil flanges required replacement due to surface degradation.

I-8. Test Conducted D- Hydrostatic

-Pneumatic M Nominal Operating Pressure E] Exempt D Other Pressure PSI Test Temperature

_F Form NIS-2 Owner's Report for Repair/Replacement Activity As required by the provisions of the ASME Code Section XI Work Order Number Sheet 0 01884503-02, -09 2 of 2 9. Remarks (Applicable Manufacturer's Data Reports to be attached)0 Replaced one hundred twenty-eight (128) 5/8-inch diameter nuts and sixty-four (64) 5/8-inch diameter studs on the 2A RBCU,#1, #2 & #3 Coils' flanges. The Catalog ID # for the nuts is 293556 and the UTC # was 0001949181.

The Catalog ID # for the stud material (threaded rod) is 297412 and the UTC #'s were 0001954093 and 0001945248.

0 0 0 o 0 o CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code,Section XI.Type Code Symbol Stamp Not Applicable Certificate of Authoriza on Number Not Applicable Expiration Date Not Applicable Signed 9Engineer Date 5 u2 f Ow er or Owner's De ignee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State orProvince of ..v,*2Loedzoo and employed by HSB CT of Hartford, Connecticut have inspected the components described in this Owner's Report during the period <P-e &'- to 7-- ?_ 7-/0 , and state that to the best of my knowledge and belief, the Owner has. performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section Xl.By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

f Commissions 3 '-'-, 'CS, Inspector's Signature National Board, State, Province, and Endorsements Date 5- _ -/

Form NIS-2 Owner's Report for Repair/Replacement Activity As required by the provisions of the ASME Code Section XI U.Work Order Number 01895070 Sheet 1 of 3 1. Owner 2. Plant Unit Duke Energy Carolinas, LLC Oconee Nuclear Station ONS -2 526 South Church Street 7800 Rochester Hwy Date Charlotte, NC 28201-1006 Seneca, SC 29672 5/19/20 10 3. Work Performed by Type Code Symbol Stamp'N' Stamp Duke Energy Carolinas, LLC Authorization Number 526 South Church Street Not Applicable Charlotte, NC 28201-1006 Expiration Date Not Applicable

4. Identification of System, ASME Class High Pressure Injection (HPI), ASME Class 2 5.(a) Applicable Construction Code: USAS B31.7 19 69 Edition, No Addenda, Yes Code Case (b) Applicable Edition Section XI Utilized For R/R Activity 19 98 Edition, 2000 Addenda.(c) Applicable Section X1 Code Case(s)6. Identification of Components Name of Name of Manufacturer National Other Year Corrected, ASME Component Manufacturer Serial Number Board No. Identification Built Removed, Code or Installed Stamped (Yes I No)I 2HP-139 Velan UNKNOWN UNKNOWN B12-354B-13MS UNK Removed NO 4" Manual Gate FS/2/51/71 2 2HP-139 Velan 102002 UNKNOWN DMV-1711 UNK Installed YES 4" EMO Gate UTC # 1958870 3 2HP-140 Velan UNKNOWN UNKNOWN B12-374B-13MS UNK' Removed YES 4" Manual Globe FS/2/51/72 4 2HP-140 CCI 104754-021-1 UNKNOWN DMV-1710 2010 Installed YES 4" EMO Drag UTC # 1959508 5 4" SS Pipe DPCo. UNKNOWN UNKNOWN See Page 3 for UNK Installed NO and elbows material details.6 Support See Page 3 for 2-51A-0-1438A-DPCo. UNKNOWN UNKNOWN parts breakdown UNK Removed NO FJM-1501 7 Support See Page 3 for 2-51A-1438A DPCo. UNKNOWN UNKNOWN parts breakdown UNK Installed NO H5650 I I I II_ I 7. Description of Work EC 91857: Replaced manual valves 2HP-139 & 2HP-140 with new EMO operated valves. Installed new piping to accommodate installation.

Removed one pipe support (2-51A-0-143 8A-FJM-1501) and installed one new pipe support (2-51A-1438A-H5650).

Replaced 21P-13 8 body/bonnet joint nuts and studs due to corrosion on existing discovered when the bonnet was removed for purge path. Replaced new 2HP-139 body/bonnet joint nuts.8. Test Conducted F-] Hydrostatic Pneumatic X Nominal Operating Pressure D Exempt Ml Other Pressure NOP PSI Test Temperature NOT OF Form NIS-2 Owner's Report for Repair/Replacement Activity SAs required by the provisions of the ASME Code Section XI UWork Orde r5Number 1 01895070 Sheet 2 of 3 1. Owner 2: Plant Unit Duke Energy Carolinas, LLC Oconee Nuclear Station ONS- 2 526 South Church Street 7800 Rochester Hwy Date Charlotte, NC 28201-1006 Seneca, SC 29672 5/19/2010 3. Work Performed by Type Code Symbol Stamp Not Applicable Duke Energy Carolinas, LLC Authorization Number 526 South Church Street Not Applicable Charlotte, NC 28201-1006 Expiration Date Not Applicable

4. Identification of System, ASME Class High Pressure Injection (HPI), ASME Class 2 5.(a) Applicable Construction Code: USAS B31.7 19 69 Edition, No Addenda, YES Code Case (b) Applicable Edition Section Xl Utilized For R/R Activity 19 98 Edition, 2000 Addenda.(c) Applicable Section XI Code Case(s)6. Identification of Components Name of Name of Manufacturer National Other Year Corrected, ASME Component Manufacturer Serial Number Board No. Identification Built Removed, Code or Installed Stamped...._ (Yes / No)8 2HP-138 Velan UNKNOWN UNKNOWN FS/2/51/70 UNK Removed NO Body Bonnet Studs Rod, Threaded 9 2HP-138 Velan UNKNOWN UNKNOWN 7/8" CAT ID UNK Installed NO Body Bonnet Studs 297414 10 2HP-138 Velan UNKNOWN UNKNOWN FS/2/51/70 UNK Removed NO Body Bonnet Nuts Nut,_Heavy 11 2H-138Nut, Heavy 11 2HP-138 Velan UNKNOWN UNKNOWN Hex, 7/8" CAT UNK Installed NO Body Bonnet Nuts ID 131797 12 2HP-139 Heavy Hex (New Valve) Velan 102002 UNKNOWN Nuts (12) 2009 Removed Yes Body Bonnet Nuts 13 2HP-139 Heavy Hex (New Valve) Velan 548577 UNKNOWN Nuts 1- 1/4" UNK Installed Yes Body Bonnet Nuts 8UN, 2B Form NIS-2 Owner's Report for Repair/Replacement Activity As required by the provisions of the ASME Code Section XI SWork Orde'Number Sheet 8595.5-5--

3 of 3 7- I-/6.9. Remarks (Applicable Manufacturer's Data Reports to be attached)9. Remarks (Applicable Manufacturer's Data Reports to be attached)1 Removal of existing valve 2HP-139.2 Install new valve 2HP-139.3 Removal of existing valve 2HP-140.4 Install new valve 2HP-140.5 4" Piping (SA 376, SCH 160, SS, UTC #1924660) and elbows (SA403, SCH 160, SS, UTC # 1924166) to support install of new valves and re-route of associated piping.6 Removal of existing pipe support 2-51A-0-1438A-FJM-1501 (support steel and miscellaneous hardware).

Item #1 (3/4" A36 Plate), Item #2 (2-1/2" 11N 1230 Anchors), Item #3 (Sway Strut), Item #4 (4 1/2" Pipe Clamp), Item #5 (2 Y2" Phillips Anchors)7 Install new pipe support 2-51A-1438A-H5650 (support steel and miscellaneous hardware)Item #1 (TS 4 x 4 x 3/8" UTC # 1939650), Item #2 (PL /" A36 UTC #1955213)Item #3 (/" Anchors, Hilti KB3 UTC #952257), Item #4 ( 1/" PL, A36, UTC #1925205)Item #5 (1/4/" PL, A36, UTC #1894551)8 -1 1 Replace bonnet studs and nuts for 2HP-138 (disassembled for purge path)12-13 Replace (new) 2HP-139 Body / Bonnet joint nuts CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code, Section Xl.Type Code Symbol Stamp Not Applicable Certificate of Authorization Number Not Applicable Expiration Date Not Applicable Signed -Date VO 9-/ 11C Owner or Owner's F0 CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of r'o/Z;pA and employed by 1 4 AtJFG _n ZJt.of CT have inspected the components described in this Owner's Report during the period -2e- , to 7- /Is,0.2o/o , and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section Xl.By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

Commissions Z J Al r R AAk ,IS National BEard State, Pro nce, and Endorsements Form NIS-2 Owner's Report for Repair/Replacement Activity As required by the provisions of the ASME Code Section XI S Work Order Number 1895287-05 Sheet 1 of 2 1. Owner 2. Plant Unit Duke Energy Carolinas, LLC Oconee Nuclear Station ONS -2 526 South Church Street 7800 Rochester Hwy Date Charlotte, NC 28201-1006 Seneca, SC 29672 5/16/2010 3. Work Performed by Type Code Symbol Stamp Not Applicable Duke Energy Carolinas, LLC Authorization Number 526 South Church Street Not Applicable Charlotte, NC 28201-1006 Expiration Date Not Applicable

4. Identification of System, ASME Class Unit 2 Main Steam System, ASME Class 2 5.(a) Applicable Construction Code: USAS B31.7 19 68 Edition, No Addenda, No Code Case (b) Applicable Edition Section Xl Utilized For R/R Activity 19 98 Edition, 2000 Addenda.(c) Applicable Section Xl Code Case(s) None 6. Identification of Components Name of Name of Manufacturer National Other Year Corrected, ASME Component Manufacturer Serial Number Board No. Identification Built Removed, Code or Installed Stamped (Yes I No)2-OIA-0-1480A-D.E.C. NONE NONE NONE 1973 Corrected NO H I B; Hanger I I d .1. _________

J .L L I ______7. Description of Work Replaced both load rods, the load studs, weldless eye nuts, associated hext nuts replaced, and bar spacers installed to maintain spacing requirements of clamp. Items were not damaged, replacement was optional.w p Iw 8. Test Conducted F-1 Hydrostatic E] Pneumatic

.Nominal Operating Pressure Z Exempt D Other Pressure PSI Test Temperature OF Form NIS-2 Owner's Report for Repair/Replacement Activity As required by the provisions of the ASME Code Section XI SWork Order Number ISheet 1 1895287-05 2 of 2 9. Remarks (Applicable Manufacturer's Data Reports to be attached)o Tack Weld on spacer bar installation; UTC # 01944677 0 Load pins(round bar); 1-3/4" diameter; ASTM A193 B7, UTC # 01057254 O Heavy Hex Nut; 1-1/2"; ASTM A194 GR 2H; UTC 01822181 and UTC # 1937771 o Heavy Hex Nut; 1-1/2"; ASTM SA194 GR 2H; UTC # 01910097 0 Weldless Eye Nut; 1-1/2"; Forged CS; UTC 01960236 0 Rod; 1-1/2"; ASME A193 GR B7; UTC 01000505 0 CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code, Section Xl.Type Code Symbol Stamp Not Applicable Certificate of Authorization Number Not Applicable Expiration Date Not Applicable Signed _9_ r -I .F T/4_" Engineer Date 5/16/2010--- ( ner or Owner's Desrgnee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of -and employed by HSB CT of Hartford, Connecticut have inspected the components described in this Owner's Report during the period .t--/- .2o to 7 -.. ole , and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

I ---.Commissions A7" At,, .X ' AI' /,r.Inspe sSignature State,'Provi5ce, and Endorsements Date 1_2. .oio A -

Form NIS-2 Owner's Report for Repair/Replacement Activity As required by the provisions of the ASME Code Section XI Work Order Number 01922582-01 Sheet 1 of 2 1. Owner 2. Plant Unit Duke Energy Carolinas, LLC Oconee Nuclear Station ONS -2 526 South Church Street 7800 Rochester Hwy Date Charlotte, NC 28201-1006 Seneca, SC 29672 5/15/2010 3. Work Performed by Type Code Symbol Stamp Not Applicable Duke Energy Carolinas, LLC Authorization Number 526 South Church Street Not Applicable Charlotte, NC 28201-1006 Expiration Date Not Applicable

4. Identification of System, ASME Class Spent Fuel Cooling, ASME Class 2 5.(a) Applicable Construction Code: USAS B31.7 19 69 Edition, No Addenda, none Code Case (b) Applicable Edition Section XI Utilized For RIR Activity 19 98 Edition, 2000 Addenda.(c) Applicable Section XI Code Case(s) none 6. Identification of Components Name of Name of Manufacturer National Other Year Corrected, ASME Component Manufacturer Serial Number Board No. Identification Built Removed, Code or Installed Stamped (Yes / No)Anderson 2SF-129 Greenwood N93355 n/a none 1999 Removed YES Crosby 0008 Anderson Anderson N933 .55-00-2SF-129 Greenwood 001 n/a none 2009 Installed YES Crosby 1 -~ t 4 1* *1- 4-t -~ .$- 4 4--h 7. Description of Work Install spare valve from stock.8. Test Conducted D Hydrostatic

[-] Pneumatic Nominal Operating Pressure []D Exempt [ Other F/V visual leak check Pressure PSI Test Temperature

_F Form NIS-2 Owner's Report for Repair/Replacement Activity As required by the provisions of the ASME Code Section XI Work Order Number Sheet 01922582-01 2 of 2 9. Remarks (Applicable Manufacturer's Data Reports to be attached)o Replaced with new tested valve from stock. Serial number N93355-00-0016.

0 0 0 0 0§CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code,Section XI.Type Code Symbol Stamp Not Applicable Certificate of Authorization Number Not Applicable Expiration Date Not Applicable Signed ýý ?1-cý /Sr. Engineer Date 5/15/2010 Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of -and employed by HSB CT of Hartford, Connecticut have inspected the components described in this Owner's Report during the period 57- (0 -__.o_ o to 7-/2- 2olo , and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

2 Commissions, lnsp .'s Signature National -Board, State, Province, and Endorsements Date .hI7 iL/ 2 go/

Date: 06/21/10 Sheet: 1 of 1 TO: ONS ISIM Plan Manager FROM: ONS QA Tech. Support PRESERVICE EXAMINATIONS OF CLASS I & 2 WELDS RE: As required by ASME Section XI 1998 Edition with 2000 addenda. Pre-service examinations were performed on ISI Class 1 & 2 welds made during the U2EOC24 outage timeframe.

The following is a list of the welds that received pre-service examinations during this outage timeframe.

WORK ORDER WELD NUMBER ISI CLASS INSPECTION TYPE NUMBER MT PT RT UT 2RC-0266-28, 29, 30, 31, 32, 33, 34, 1780230 35, 36, 37, 38, 39, 1 X 40, 41, 42, 47, 48, 49, 50, 51, 52, 57, 58, & 59 2HP-0396-23, 24, 1895070 &25 2 X X 2-51A-0029-94 Prepared By: PBJ 06-21-10 6

6.0 Pressure

Testin, ISI Pressure Tests are conducted and managed by zones. Each pressure test zone required by the ISI Plan and the completion status of those zones are listed in this report.Pressure Test Zones OZ2L-42A and OZ2L-42B were incorrectly listed in EOC23 Summary Report as being completed on December 10, 2008. Problem Investigation Process (PIP) 0-10-01167 documents this error and gives instructions to include the corrected completion dates in this EOC24 report. Reference Table 6-2 for the corrected completion dates.The Class 1 (Category B-P) leakage test is required each refueling outage. Table 6-1 shows the completion data of the Class 1 (Category B-P) leakage test zones conducted during refueling cycle EOC24.Table 6-1 Detailed Class 1 Listing EOC24 Zone Completion EO0C24 VT-2 Code Case(s)-Number Boundary Dwg Status Examination Date Used OZ2L-1A O-ISIL4-100A-2.1 Complete 05/28/10 None O-ISIL4-10OA-2.2 O-ISIL4-100A-2.3 O-ISIL4-101A-2.1 O-ISIL4-101A-2.4 O-ISIL4-102A-2.1 O-ISIL4-102A-2.3 O-ISIL4-1 1OA-2.1 O-ISIIL4-1 1OA-2.4 OZ2L-16 O-ISIL4-101A-2.4 Complete 05/28/10 None The Class 2 (Category C-H) leakage tests are required each period. Table 6-2 shows the completion data of the Class 2 (Category C-H) leakage tests zones required for the 2 nd Inspection Period which ends 09/09/2011.

Table 6-2 Detailed Class 2 Listig VT-2 Code Zone Examination Case(s)Number Boundary Dwg Completion Status Date Used 1 IZ2L-10 O-ISIL4-101A-2.3 Complete 10/25/08 None 2 IZ2L-11 O-ISIL4-101A-2.3 Complete 10/25/08 None 3 IZ2L-12 O-ISIL4-101A-2.3 Incomplete I O-ISIL4-101A-2.4 4 IZ2L-13 O-ISIL4-101A-2.3 Complete 03/24/10 None Refueling Outage Report EOC24 Oconee Unit 2 Section 6 Page 1 of 4 Revision 0 June 15, 2010 VT-2 Code Zone Examination Case(s)Number. Boundary Dwg Completion Status Date Used 5 IZ2L-14A 0-ISIL4-101A-2.3 Complete 12/01/08 None 6 IZ2L-14B 0-ISIL4-101A-2.3 Complete .12/01/08 None 7 IZ2L-20 0-ISIL4-101A-2.3 Complete 02/22/10 None 8 IZ2L-22 0-ISIL4-101A-2.3 Incomplete 0-ISIL4-102A-2.1 0-ISIL4-102A-2.2 0-ISlL4-104A-1.2 9 IZ2L-24 0-ISIL4-102A-2.1 Complete 01/05/10 None 0-ISIL4-103A-2.1 10 IZ2L-25 0-ISIL4-102A-2.1 Incomplete 0-ISIL4-103A-2.1 11 IZ2L-27A 0-ISIL4-102A-2.1 Complete 05/21/10 None 0-ISIL4-102A-2.2 12 IZ2L-27B 0-ISIL4-102A-2.2 Complete 12/06/08 None 13 IZ2L-4 0-ISIL4-101A-2.1 Complete 02/18/10 None 14 IZ2L-41 0-ISIL4-109A-1.1 Complete 05/22/10 None 15 IZ2L-48 0-ISIL4-122A-2.1 Complete 02/18/10 None 0-ISIL4-122A-2.2 0-ISIL4-122A-2.3 0-ISiL4-122B-2.1 0-ISIL4-122A-2.4 16 IZ2L-5 0-ISIL4-101A-2.1 Incomplete 0-ISlL4-101A-2.3 17 IZ2L-60 O-ISIIL4-124B-2.2 Complete 06/05/08 None O-ISIIL4-124B-2.4 18 OZ2L-14B 0-ISIL4-101A-2.4 Complete 12/01/08 None 19 OZ2L-15 O-ISIL4-101A-2.4 Complete 12/10/08 None 20 OZ2L-16 0-ISIL4-101A-2.4 Complete 12/08/08 None 21 OZ2L-17 0-ISIL4-101A-2.2 Complete 12/08/08 None 22 OZ2L-17B 0-ISIL4-101A-2.2 Complete 05/17/10 None Refueling Outage Report EOC24 Oconee Unit 2 Section 6 Page 2 of 4 Revision 0 June 15, 2010 VT-2 Code Zone Examination Case(s)Number Boundary Dwg Completion Status Date Used 23 OZ2L-18 O-ISIL4-101A-2.2 Complete 12/06/08 None 24 OZ2L-19A O-ISIL4-104A-1.1 Complete 05/03/09 None O-ISIL4-101A-2.5 25 OZ2L-19B O-ISIL4-101A-2.5 Complete 11/27/08 None 26 OZ2L-1A O-ISIL4-101A-2.1 Complete 12/10/08 None 0-ISIL4-101A-2.5 27 OZ2L-2 O-ISIL4-101A-2.1 Complete 12/10/08 None 0-ISIL4-101A-2.4 0-ISIL4-101A-2.5 28 OZ2L-21 0-ISIL4-102A-2.1 Complete 12/06/08 None 0-ISIL4-102A-2.2 0-ISIL4-104A-1.2 29 OZ2L-23 O-ISIL4-101A-2.2 Complete 12/05/08 None 0-1SIL4-102A-2.1 0-ISIL4-102A-2.2 30 OZ2L-26 0-ISIL4-102A-2.2 Complete 12/06/08 None 31 OZ2L-28 0-ISIL4-102A-2.2 Complete 05/21/10 None 32 OZ2L-29 0-ISIL4-102A-2.2 Complete 12/06/08 None 33 OZ2L-29A 0-ISIL4-102A-2.2 Complete 12/06/08 None 0-ISIL4-102A-2.3 34 OZ2L-3 0-ISIL4-101A-2.1 Complete 12/10/08 None 35 OZ2L-30 0-ISIL4-102A-2.2 Complete 12/06/08 None 36 OZ2L-30A O-ISIL4-102A-2.2 Complete 12/06/08 None 0-ISIL4-102A-2.3 37 OZ2L-31A 0-ISIL4-102A-2.3 Complete 12/25/08 None 38 OZ2L-31B 0-ISIL4-102A-2.3 Complete 12/25/08 None 39 OZ2L-31C 0-ISIL4-102A-2.3 Complete 12/25/08 None 40 OZ2L-39 0-ISIL4-104A-1.1 Complete 05/01/10 None 41 OZ2L-42A O-ISIL4-11OA-2.1 Complete 04/22/10 None 42 OZ2L-42B 0-ISIL4-11OA-2.1 Complete 04/22/10 None Refueling Outage Report EOC24 Oconee Unit 2 Section 6 Page 3 of 4 Revision 0 June 15, 2010 VT-2 Code Zone Examination Case(s)Number Boundary Dwg Completion Status Date Used 43 OZ2L-44 0-ISIL4-11OA-2.1 Complete 05/28/10 None O-ISlIL4-121 B-2.3 O-ISIL4-121 B-2.5 0-ISIL4-121D-1.2 O-ISIL4-121D-2.1 O-ISIL4-122A-2.1 0-ISIL4-133A-2.5 44 OZ2L-6 0-ISIL4-101A-2.1 Complete 12/10/08 None 0-ISIL4-101A-2.2 O-ISIL4-109A-1.1 45 OZ2L-6B 0-ISIL4-101A-2.2 Complete 05/17/10 None 46 OZ2L-64 O-IS11L4-124B-2.2 Complete 12/10/08 None 47 OZ2L-65 0-ISIL4-124B-2.4 Complete 12/10/08 None 48 OZ2L-7 0-ISIL4-101A-2.2 Complete 11/30/08 None 0-ISIL4-101 A-2.3 49 OZ2L-7B 0-ISIL4-101A-2.3 Complete 11/30/08 None 0-ISIL4-102A-2.1 0-ISIL4-102A-2.2 50 OZ2L-9 0-ISIL4-101A-2.3 Complete 12/06/08 None 0-ISIL4-102A-2.1 O-ISIL4-1102A-2.2 Refueling Outage Report EOC24 Oconee Unit 2 Section 6 Page 4 of 4 Revision 0 June 15, 2010