Framatome, Inc., Part 21 Notification of Existence of a Defect
ML23117A043
Person / Time
Site: Calvert Cliffs, Oconee, PROJ0728  
Issue date: 04/20/2023
From: Gayle E
Framatome
To:
Document Control Desk, Office of Nuclear Reactor Regulation
References
NRC:23:011
Download: ML23117A043 (1)


Text

framatome April 20, 2023 NRC:23:011 U.S. Nuclear Regulatory Commission Document Control Desk 11555 Rockville Pike Rockville, MD 20852 1 O CFR 21 Notification of Existence of a Defect This letter provides notification of a reportable defect in accordance with 10 CFR 21.21(d). This defect was reported to the NRG Operations Center by email at 4:01 p.m. EST on April 7, 2023, Event No. 56457.

The defect concerns the erroneous change of state of Eaton breakers and potentially affected parts. The nature of the defect, location of basic components, corrective actions to date and advice related to the defect are discussed in Attachment 1.

If you have any questions related to this information, please contact me by telephone at *

(434) 832-3347, or by e-mail at Gayle.Elliott@framatome.com.

Sincerely, ELLIOTT Gayle r

\J J,Digit1lly signed by ELLIOTTG*ylo t-TJJ.~~23.04.20 10:43:46 -04'00'

(/

C Gayle Elliott, Director Licensing & Regulatory Affairs Framatome Inc.

cc:

N. Otto Project 728 Attachments:

1 - Notification of 10 CFR 21 Defect Framatome Inc.

,i31$ 9ld Forest Rqad Lynchburg, VA 24501 Tel: (434f832-3000 www:framatome.com

Document Control Desk April 20, 2023 NRC:23:011 Page A-1 Notice of 10 CFR 21 Defect and Failure to Comply

Subject:

Notification of 10 CFR 21 Defect Name and Address of Individual Informing the Commission:

Title:

Gayle Elliott Director, Licensing Regulatory Affairs Framatome Inc.

3315 Old Forest Road Lynchburg, Va.

Breaker - Erroneous Change of State Identification of Basic Activity:

Eaton Corporation Breakers Basic Activity Supplied By:

Framatome Inc.

Nature of Defect:

In 2011, Fi-amatome Inc. (Framatome) supplied a DS-206DC Breaker that closed at the end of a charging cycle. This is not supposed to occur. The DS-206DC circuit breaker is a power circuit breaker. A power circuit breaker has a mechanism that must be CHARGED before the breaker can be CLOSED. Once the breaker is CHARGED, it must remain CHARGED until the end user commands the breaker to CLOSE. A power circuit breaker is charged by extending the closing springs. The power circuit breaker is closed by releasing the energy in the closing springs. The circuit breaker went from CHARGED directly to CLOSED without the end user initiating a command to CLOSE the breaker.

The cause of the "auto-close" (automatic closure of the breaker at the end of the charging cycle) was that Eaton made the trigger roller (Eaton Part#

783A446H01) out of round. The trigger roller is a component in the main cam assembly (Eaton Part# 436B418G03). Normally, after the breaker is charged, the trigger roller on the main cam assembly contacts the close prop. The trigger

Document Control Desk April 20, 2023 NRC:23:011 PageA-2 roller and close prop remain in contact until the end user commands the breaker to be closed. Since the trigger roller is made "out of round" to a degree higher than specified by Eaton's design drawings, and if the trigger roller is radially located in in a certain position, the trigger roller could "roll past" the close prop, release the stored energy in the closing springs and close the breaker. These OS power breakers must be racked into the connected position before they can transmit power to their connected load. If this breaker were to open and then charge (electrically or manually) and "auto-close", this would result in a possible unwanted start of the load the breaker is associated with (motor, heater, etc.).

Defect Determination Date:

This issue was determined to be a 10 CFR 21 Defect on April 6, 2023.

Location of Basic Components:

Framatome supplied breakers and/or potentially affected parts (such as the main cam assembly) to the following customers:

Calvert Cliffs / Electrical Load / DS-206, DS-416 Breakers KRSKO / Electrical Load / DS-206DC Breakers Oconee I Reactor Trip Switchgear/ DSll-516 Breakers STP / Electrical Load / DS-206, DS-416 Breakers TVA/ Electrical Load/ DS-206, DS-416 and DS-632 Breakers Corrective Actions to Date:

Eaton made changes to their manufacturing process to correct the issue.

Affected utilities will be provided an inspection procedure to determine if the defect is located in affected components that may be in storage or in operation.

Advice Related to the Defect:

Framatome will be providing written correspondence to each affected customer to advise that this issue is a reportable defect. Framatome will respond to technical questions as requested.