ML20195G368 | 17 November 1998 | Notice of Violation from Insp on 980909-1019.Violation Noted:As of 980818,licensee Failed to Initiate Measures to Determine Cause or Take Action to Preclude Recurrence of Loose Bolts on Two EDG Lubricating Oil Heat Exchanger Bells | Condition Adverse to Quality |
ML20195G303 | 13 November 1998 | Notice of Violation from Insp on 980915-1022.Violation Noted:On 981022,two Individuals Working Under RWP 984014 Removed Outer Rubber Gloves While Replacing Insulation in Containment | |
ML20196D920 | 10 November 1998 | Notice of Violation from Insp on 981013-19.Violation Noted: Licensee Security Staff Discovered That on Three Occasions Between 980826 & 1002,security Officers Were Found Asleep on Post | |
ML20236N091 | 6 July 1998 | Notice of Violations from Insp on 980421-0608.Violations Noted:On 980424,licensee Failed to Implement Specific Fire Protection Program Requirements in That Welding Machine Was Left Unattended & Energized in Fuel Handling Bldg | Condition Adverse to Quality Fire Protection Program |
ML20248D082 | 19 May 1998 | Notice of Violation from Insp on 980310-0420.Violation Noted:On 980303,licensee Failed to Implement Braidwood Administrative Procedure 2321-18T11,Step E.1,for Sf Pool Skimmer Strainer Level Control | Temporary Modification |
ML20217F528 | 21 April 1998 | Notice of Violation from Insp on 980331-0407.Violation Noted:Licensee Failed to Check That SG Worker Dosimetry Was Present & Correctly Worn | |
ML20216B061 | 8 April 1998 | Notice of Violation from Insp on 980127-0309.Violation Noted:On 971010,21,1219 & 980105,licensee Failed to Require Independent Verification of Proper Sys Alignment for safety-related Valves Repositioned in Steps F.1.4 & F.1.7 | Continuous fire watch Fire Protection Program Fire Watch |
ML20203D915 | 20 February 1998 | Notice of Violation from Insp on 971216-980126.Violation Noted:In Nov 1989,licensee Failed to Initiate Deviation Rept & Take Corrective Measures to Preclude Repetition of Mechanical Failure to All 4 Main Feedwater Check Valves | |
ML20202F232 | 11 February 1998 | Notice of Violations from Insp on 971112-21 & 980115. Violations Noted:Licensee Failed to Follow NSWP-A-15 & Bwap 330-10 Requirements to Issue PIF for Tempering Line Snubber Considered Inoperable on 971110 | |
IR 07100104/2012015 | 2 January 1998 | Notice of Violation from Insp on 971104-1215.Violation Noted:On 971102,inspectors Identified That Licensee Had Failed to Fasten Covers on Incore Neutron Detector Drive Mechanism | |
ML20199A568 | 17 December 1997 | Notice of Violation from Insp on 970923-1103.Violation Noted:On 971014,licensee Instrument Technician Made Error When Changing Setpoints on Unit 2 Containment Area Radiation Monitor 2AR11J.Error Resulted in High Radiation Alarm | Scaffolding |
ML20202C967 | 26 November 1997 | Notice of Violation from Insp on 970812-0922.Violation Noted:On 970814,licensee Personnel Verified Position of 2B Containment Spray Eductor Drain Valve W/O Removing & Reinstalling Locking Device | |
ML20199G118 | 17 November 1997 | Notice of Violation from Insp on 971006-22.Violations Noted: Individual Performing Work on 2CV8149 Valve within Radiologically Posted Area,Failed to Follow Instructions Contained on Posting | High Radiation Area |
ML20211Q848 | 17 October 1997 | Notice of Violation from Insp on 970714-0815.Violation Noted:Licensee Failed to Assure That Degraded Voltage Relay Testing for Divs 11,12,21 & 22 Was Performed Under Suitable Environ Conditions | |
ML20198R259 | 3 October 1997 | Notice of Violation & Proposed Imposition of Civil Penalty in Amount of $55,000.Violation Noted:Eccs Subsystem Consisting of Centrifugal Charging Pump Not Operable | |
ML20198K398 | 2 October 1997 | Notice of Violation from Insp on 961013-970814.Violation Noted:Licensee Failed to Provide Barriers for Redundant Train of Equipment in Same Fire Zones | Fire Barrier Fire Protection Program |
ML20217C484 | 17 September 1997 | Notice of Violation from Insp on 970701-0811.Violation Noted:On 970702,inspectors Observed Unattended & Energized Welding Machine Located Outside 2A Emergency Diesel Generator Room | Fire Protection Program |
ML20216D475 | 26 August 1997 | Notice of Violation from Insp on 970520-0630.Violations Noted:Licensee Had Not Demonstrated That Performance or Condition of Pams Was Being Effectively Controlled Through Performance of Appropriate Preventive Maint | Boric Acid |
ML20149J699 | 24 July 1997 | Notice of Violation from Insp on 970618-24.Violation Noted: on Listed Dates,Inspector Identified That Licensee Did Not Provide Reasonable Assurance That Indirect Methods Could Be Correlated W/Action Measurements | |
ML20141E814 | 17 June 1997 | Notice of Violation from Insp on 970408-0520.Violation Noted:On 970418,inspectors Identified That Licensee Had Taken Open Unit 2 Motor Driven Feedwater Pump Discharge Isolation Valve out-of-svc for Maint W/O Written SE | Foreign Material Exclusion Fire Protection Program Fire Watch Inattentive |
ML20141J925 | 19 May 1997 | Notice of Violation from Insp on 970417-30.Violation Noted: on 970417,inspector Identified That Entrance to High Integrity Container Storage Area of Radwaste Bldg,Area Accessible to Personnel Posted Locked,Not Locked | High Radiation Area Locked High Radiation Area |
ML20141D762 | 9 May 1997 | Notice of Violation from Insp on 970222-0407.Violations noted:1BwFR-S.1 Had Not Been Maintained in That,Operators Were Directed to Start Chemical & Volume Control Sys Positive Displacement Pumps | |
ML20137T117 | 8 April 1997 | Notice of Violation from Insp on 970303-07.Violation Noted:Review of Emergency Preparedness Program Did Not Include Evaluation of Adequacy of Interface W/State of Il | |
ML20137J604 | 31 March 1997 | Notice of Violation from Insp on 961003-970312.Violation Noted:Applicable Portions of Numerous Plant Hot Work Permits Were Not Filled Out as Required by Bwap 1100-15 | Fire Protection Program |
ML20136D896 | 4 March 1997 | Notice of Violation from Insp on 970203-07.Violation Noted: Since 960221,procedure Bwcp 210-14,rev 2,970221,did Not Provide Instructions to Ensure Validity of Intrinsic Germanium Detector Calibrations in Accordance W/App a | |
ML20135B490 | 18 February 1997 | Notice of Violation from Insp on 961130-970110.Violation Noted:Tag Required to Maintain Traceability of safety-related Item Was Removed | Through Wall Leak |
ML20135B588 | 18 February 1997 | Notice of Violation from Insp on 961019-1129.Violation Noted:Construction of Scaffolding on 961107,in Vicinity of Essential Service Water Sys Forebay Not Prescribed by Documented Procedures Appropriate to Circumstances | Foreign Material Exclusion Scaffolding |
ML20134B594 | 22 January 1997 | Notice of Violation from Insp on 961012-1113.Violation Noted:Plant Procedure Bwgp 100-5, Plant Shutdown & Cooldown, Activity Affecting Quality,Was Not Appropriate to Circumstances | |
ML20133E769 | 3 January 1997 | Notice of Violation from Insp on 960907-1018.Violation Noted:On 960918,operations Personnel in CR Were Performing 1BwOS 8.1.1.2.a-2,which Was Inappropriate for Circumstances | |
ML20129H244 | 23 October 1996 | Notice of Violation from Insp on 960727-0906.Violation Noted:On 960821,diesel Operators Did Not Independently Verify Position of Valves 2D02116B,2BwOS 8.1.1.2.a-2, 2B DG Operability Monthly & Semi-annual Surveillance | |
ML20128H086 | 2 October 1996 | Notice of Violation from Insp on 960615-0726.Violation Noted:On 960709,ventilation Damper Controller OPDC-VW008 Which Had Been Altered by Installation of Jumper,Declared Operable,Required Different Operating Procedures | |
ML20149G636 | 6 October 1994 | Notice of Violation from Insp on 940809-0916.Violation Noted:Nuclear Station Operators Performed Equipment Manipulations Outside of Written Procedures W/O Informing Supervisors & Receiving Guidance | |
ML20059A248 | 15 October 1993 | Notice of Violation from Insp on 920726-0831.Violation Noted:Licensee Records Required to Be Maintained by NRC Regulations Not Complete & Accurate in All Matl Respects | |
ML20128K229 | 4 February 1993 | Notice of Violation from Insp on 921201-930119.Violation Noted:Corrective Actions Associated W/Ler 456/90-14 Had Not Been Implemented in Timely Manner | |
ML20128B044 | 26 January 1993 | Notice of Violation from Insp on 930105-08.Violation Noted: Controlled Areas Were Not Conspiciously Posted as to Warn Personnel Approaching Area from Any Direction of Restricted Areas | |
ML20126E830 | 18 December 1992 | Notice of Violation from Insp on 921013-1130.Violation Noted:On 920715,radiation Protection Technician Removed Posting for 1A Letdown Heat Exchanger Room W/O Adhering to Requirements to Verify That Room Had Been Decontaminated | |
ML20059M155 | 14 September 1990 | Notice of Violation from Investigation Conducted Between 851107-880422 & 881101-900416.Violation Noted:Contractor at Plant Site Discriminated Against for Engaging in Protected Activities | |
ML20059B356 | 17 August 1990 | Notice of Violation from Insp on 900617-0728.Violations Noted:Unit 1 Containment Entry Made on 900608,w/containment Integrity Required by Tech Spec,But Containment Personnel Air Lock Leak Test Not Completed within 72 H | |
ML20055G420 | 13 July 1990 | Notice of Violation from Insp on 900429-0616.Violation Noted:On 900603,inadequate Instructions Re Temporary Lift Procedure Expiration Resulted in Failure to Rehang Four Containment Isolation Valves Tags | |
ML20055C756 | 15 June 1990 | Notice of Violation from Insp on 900416-20 & 0430-0504. Violations Noted:Control Cable to Be Attached to Hydraulic Actuator Control Solenoid Did Not Have Specific Station Evaluation | |
ML20055C621 | 17 May 1990 | Notice of Violation from Insp on 900318-0428.Violation Noted:On 891019,Train B of Containment Spray Chemical Additive Sys in Unit 2 Identified Inoperable Resulting in Unanalyzed Flow Rate of 115 Gpm Vs 68 Gpm as Required | |
ML20247R849 | 26 September 1989 | Notice of Violation from Insp on 890730-0916.Violation Noted:Safety Valve Stuck Open During Testing | |
ML20247H835 | 12 September 1989 | Notice of Violation from Insp on 890703-0901.Violations Noted:Survey Not Performed 2 Meters from Sides of Transport Vehicle & Results of Analyses of Samples Taken in 1987 & 1988 Not Contained in Annual Radiological Environ Repts | Annual Radiological Environmental Operating Report |
ML20247A250 | 11 July 1989 | Notice of Violation from Insp on 890601-20.Violation Noted: Recirculation Isolation Valve 2CV8479B for Centrifugal Charging Pump 2B Shut,Rendering Charging Pump 2B Inoperable for More than 7 Days from 890322-0601 | |
ML20247A752 | 16 May 1989 | Notice of Violation from Insp on 890319-0429.Violation Noted:Mod Review for Auxiliary Feedwater Sys Temporary Alteration Did Not Recognize That Mod Will Render Boron Dilution Sys Inoperable for 13 Days | |
ML20246L916 | 15 March 1989 | Notice of Violation from Insp on 890214-17.Violation Noted: on 880720,individual Working in Radioactive Matls Area Did Not Receive Bioassay Following Work Assignment & Exception Not Granted | |
ML20195H439 | 23 November 1988 | Notice of Violation & Proposed Imposition of Civil Penalty in Amount of $75,000.Noncompliance Noted:Electric Equipment Important to Safety Not Properly Qualified by Testing &/Or Analysis & Specific Maint Activities Not Implemented | Post Accident Monitoring Power Operated Valves |
ML20205N035 | 27 October 1988 | Notice of Violation from Insp on 880828-1015.Violation Noted:On 880914,radiation/chemistry Dept Personnel Not Notified of Secondary Sampling Panel/Sink Trouble Condition When Indicated by Alarms | |
ML20151K959 | 22 July 1988 | Notice of Violation from Insp on 880529-0709.Violation Noted:Failure to Properly Declare Initiation of Unusual Event in Accordance W/Emergency Procedure Bwzp 200-1, Braidwood Emergency Action Levels | |
ML20195H965 | 22 June 1988 | Notice of Violation from Insp on 880524-26 & 0531-0602. Violations Noted:Germanium Detectors Used to Demonstrate Compliance W/Tech Specs Improperly Calibr Using Noncertified Radioactive Sources |