 Issue dateTitleTopic
ML20217A16922 September 1999Part 21 Rept Re Engine Sys,Inc Controllers,Manufactured Between Dec 1997 & May 1999,that May Have Questionable Soldering Workmanship.Caused by Inadequate Personnel Training.Sent Rept to All Nuclear Customers
ML20153D01918 September 1998Part 21 Rept Re Defect in Gap Conductance Analyses for co- Resident BWR Fuel.Initially Reported on 980917.Corrective Analyses Performed Demonstrating That Current Operating Limits Bounding from BOC to Cycle Exposure of 8 Gwd/MtuFuel cladding
ML20153C67717 September 1998Part 21 Rept Re Defect Relative to MCPR Operating Limits as Impacted by Gap Conductance of co-resident BWR Fuel at Facilities.Operating Limit for LaSalle Unit 2 & Quad Cities Unit 2 Will Be Revised as Listed
ML20236N6759 July 1998Part 21 & Deficiency Rept Re Notification of Potential Safety Hazard from Breakage of Cast Iron Suction Heads in Apkd Type Pumps.Caused by Migration of Suction Head Journal Sleeve Along Lower End of Pump Shaft.Will Inspect Pumps
ML20217D02822 April 1998Part 21 Rept Re Additive Constants Used in MCPR Determination for Siemens ATRIUM-9B Fuel by Core Monitoring Sys Were Found to Be non-conservative.SPC Personnel Notified All Customers w/ATRIUM-9B Lead Test AssembliesFitness for Duty
ML20198K5086 January 1998Part 21 Rept Re Transient Analyses at Exposures Prior to End of Cycle.Caused by Component Defect.Notified Commonwealth Edison of Defect & Provided Revised Limits by Siemens Power Corp
ML20203B36910 December 1997Part 21 Rept Re Potential to Exceed Operating Limits.Cycle 8 Delayed Until Fall 1998
ML20198J48716 October 1997Interim Part 21 Rept Re Transient Analyses at Exposures Prior to Eoc.Nonconformance Rept Prepared & Processed by Mgt Review Team
ML20217J61314 July 1997Part 21 Rept Re Incomplete Defined Changes Made to Standby DG W/Emd Diesel Engines by Mfg
ML20140E9679 June 1997Interim Part 21 Rept Re Possibility of non-conservative Fraction of Power Deposited in Hot Rod Under Voided Core Conditions on 970421.Nonconformance Rept Has Been Prepared & Processed by Mgt Review Team
ML20140A47627 May 1997Provides Addl Info to 970429 Part 21 Rept Re Potential safety-related Problem W/Asco HV 266000-007J Scram Solenoid Pilot Valves.Corrective Actions Also Listed
ML20141K77822 May 1997Part 21 Rept Re Critical Heat Flux Data Base Range Not Extensive Enough to Adequately Estimate Uncertainties for Additive Constants Used in Critical Heat Flux Correlation. Safety Limit Calculations Revised
ML20148B0182 May 1997Part 21 Rept Re Failure of Plunger on Solenoid Number 1 to Return to de-actuated Position in Timely Manner When Solenoid Was de-energized.Caused by Plunger Moving While in Energized Condition.Added 'Noise' Test
ML20134Q08027 November 1996Part 21 Rept Re Deficiency of Wkm Model 70-13 Pneumatic Actuators Manufactured by Anchor Darling Valve Company Due to Incorrect Calculation of Bench Set & Supply Air Set Points.All Affected Valves Have Been Reviewed & EvaluatedAnchor Darling
ML20134D85728 October 1996Part 21 Rept Re Steam Isolation Valved Failed to Close within 3-5 Seconds Required by Ts.Caused by One Plunger from Solenoid Missed Machining Operation After Vitron Insert Pressed In.Solenoid Energized
ML20128F5014 October 1996Part 21 Rept & Deficiency Rept Re Wkm Model 70-13 Pneumatic Actuators Mfg by Anchor Darling Valve Co.All Affected Valves Being Reviewed/Evaluated & Design Changes Are Being Initiated as RequiredAnchor Darling
ML20117P31411 September 1996Part 21 Rept Re Deficiency of GE Type RMS-9 Overcurrent Trip Device ProgrammersSafe Shutdown
ML20095K39121 December 1995Final Part 21 Rept 95-015 Re Bldg of Achor Darling Valves W/ Cavitation Trim.Plant Will Perform Monthly Testing of Running Loads on a Loop Valve Until ModifiedTime of Discovery
Anchor Darling
ML20082B52728 March 1995Part 21 Rept Re Notification 9505 Automatic Switch Co Pilot Solenoid Valve Model NP8323A20V.Caused by Failures of MSIVs to Close to Asco Pilot Solenoid Valves.Subj Valves Replaced W/Valcor 3-way Solenoid ValvesTime of Discovery
ML20082E19027 March 1995Part 21 Rept Re Sticking of B Core Assembly to Plugnut on Automatic Switch Co Dual Solenoid Valve Model NP8323A20V. Unit 2 Valves Replaced.Unit 1 Valves Will Be ReplacedTime of Discovery
ML20078S19321 December 1994Final Part 21 Rept Re Nonconservative Assumptions of Turbine Bypass Vot in Plant Transient Analyses for Unit 2.GE Analyses Determined That Deviation Created Potential Substantial Safety HazardTime of Discovery
Feedwater Controller Failure
ML20069A86317 May 1994Final Part 21 Rept Re Secondary Containment Isolation Techno Corp Dampers Equipped W/Parker Hannifin Air Cylinders at LaSalle County Station.All Units 1 & 2 Techno Dampers Equipped W/Parker Air Cylinders Replaced
ML20070N3452 May 1994Part 21 Rept Re Failures of Limit Switch Series EA740-86700 Mfg by Namco Controls Co Due to Excessive Amount of Grease on Contact Block & Contact Carrier & Wrong Matl of O-ring. Series EA740-86700 Switches Replaced w/EA740-50100 Switches
ML20063D0862 February 1994Part 21 Rept Re Possible Anomaly W/Namco Controls EA740 & EA750 Series Limit Switches.Investigation in Progress & Has Not Been Concluded.Vendor Will Advise NRC within Next Thirty Days Re Matter as Addl Info Becomes Available
ML20059L98611 November 1993Part 21 Rept Re Deviation Wherein Fully Open Butterfly Valve Located 15 Pipe Diameters Upstream of Sensors Was Disturbing Flow Profile Enough to Cause Ultrasonic Meter to Indicate 3 to 4% Low.Customers Notified & Valve Removed
ML20056D70715 July 1993Part 21 Rept Re Reportable defect-75 PSIG Relief Check Valve 1 Npt,Emd 9521844,Kepner 416C-1-75
ML20072R67327 March 1991Part 21 Rept Re Increased Air Leakage in Pathway Bellows Corp Bellows Assembly.Assembly Replaced by Parker-Metal Bellows CorpThrough-Wall Leak
ML20043A60927 April 1990Part 21 Rept Re Defective Axial Cracks in Pump Shaft in Region Immediately Above Impeller & in Reactor Recirculation Pumps.Probably Caused by Crack Growth as Thermal Fatigue. Technical Advisory Bulletin Will Be Sent to Each Util
ML20153G0116 May 1988Part 21 Rept Re Potential Defect in Bussman Buss KTK-R Fuse Blocks W/Part Numbers 2078,2079 & 2080.Purchasing Records Reviewed to Identify If Any Parts Were Actually Used or Shipped to Customers.Results Listed
ML20211P72123 February 1987Part 21 Rept Re Rockbestos Coaxial Cable Used in Sorrento Electronics Digital & Analog high-range Radiation Monitor. Insulation Resistance at High Temp Not High Enough for Ion Chamber & Associated Electronics to Operate Properly
ML20212E56319 December 1986Part 21 Rept Re Valve Problem.Houghto 620 Lubricant Attacks & Degrades Aluminum in Valves.Valves Have Been or Being Rebuilt
ML20215D2379 December 1986Part 21 Rept Re Environ Qualification of AMP Butt Splices in GE Drywell Penetrations.Splices Retested by Simulating Postulated LOCA & Failed Due to Excessive Leakage.Ge Contacted Re Repair of Splices
ML20213F96610 November 1986Part 21 Rept Re Failure of Battery inter-rack Connecting Cable Assembly Supplied by Gnb Batteries,Inc.Initially Reported on 861107.Battery Cables Replaced
ML20214M3184 September 1986Potential Part 21 Rept Re Contromatics Actuator W/Jackscrew/ Handwheel Emergency Override Operator.Jackscrew/Handwheel Should Be Used for Emergency Manual Operation Only.Encl Ltr Also Sent to Listed Utils/Ae Firms
ML20207J84925 July 1986Part 21 Rept Re Potential Change in Allowable Operating Repeatability Ranges for 1E Qualified Series 9,8 & 1 Pressure Switches.Licensee Calibr Procedures Should Be Amended to Allow for Cycling (Hysteresis) Effects
ML20198R5753 June 1986Part 21 Rept Re Failure of 103/B212 Type Differential Pressure Switches to Give Scram During 860601 Feedwater Transient.Investigation Continuing
ML20141D8051 April 1986Part 21 Rept Re Model 402 Series Level Control Used for safety-related Application Shipped W/O Torque Check. Customers Will Be Notified by 860428 & Requested to Perform Torque Check.List of Plants Using Component EnclEarthquake
ML20140A52819 December 1985Part 21 Rept Forwarding Ltr Sent to Customers Re Check Valves Missing Lock Welds on Hinge Supports or Hinge Support Capscrews,Per 851121 Request.List of Customers Receiving Ltr Also Encl
ML20133N4695 August 1985Part 21 Rept Re Raychem Wcsf Shrink Sleeving for Sensor/ Connecting Assembly of Safety Relief Valve Monitoring Sys. Testing & Retesting in Progress.Sensor Installation Utilizing Shrink Sleeving Recommended
ML20128G51024 May 1985Part 21 Rept Re Heat Numbers to Be Added & Deleted from Sublist Sheet A,Based on Review of NRC
ML20117L58914 May 1985Part 21 Rept Re Hatch Transfer Starters & Transfer Starter Assemblies.Evaluation of Implementation of QA Program Performed on 850429-0503.Results of Evaluation Verified Seismic Adequacy of Equipment
ML20127N06213 May 1985Part 21 Rept Re Incorrect Short Time Delay Band Lever Inadequately Installed in Low Voltage K-line Circuit Breaker Electromechanical Overcurrent Trip Device.Visual Insp to Determine If Correct Lever Installed Recommended
ML20099F3928 November 1984Part 21 Rept Re Hexcel/Mci Pipe Restraints Found W/Average Dynamic Crush Strength Values Below Acceptable Values. Initially Reported on 841101.Replacement Program in Progress
ML20096A54421 August 1984Part 21 Rept Re Ground Fault Failures of Actuation Solenoids for Crosby Safety Relief Valves PRC 84-24.Problem Still Considered Germane Condition.Memo of 840808 Telcon Updating 840615 Interim Rept Encl
ML20086U42524 February 1984Followup Part 21 Rept Re Defective Mechanical Snubber Capstan Springs Supplied by Pacific Scientific.Affected Utils Listed.Purchasers Have Been Notified & Advised to Work Directly W/Pacific Scientific in Disposition
ML20083J77322 December 1983Final Deficiency Rept Re Defective GE Hma Relays.Initially Reported on 830805.Two Relays Found to Have Insufficient Armature Clearance.Adjustments Made
ML20082Q6922 December 1983Final Deficiency Rept 83-07 Re Design Calculation for Fire Water Sys.Initially Reported on 831102.Preliminary Calculations Completed.Final Rept Will Be Submitted Approx 20 Days Prior to Exceeding 5% Power
ML20085K63612 October 1983Final Deficiency Rept 83-06 Re Asco Solenoid Valves in Control Rod Drive Sys.Initially Reported on 830912.Valves W/Defective Solenoid Plunger Housings Replaced & Spare Parts in Inventory Examined.Plant Operable
ML20077N6151 September 1983Interim Deficiency Rept 83-05 Re Potentially Defective GE Hma Relays Mfg in 1974.Initially Reported on 830805.Two Relays Found W/Insufficient Armature Clearance.Clearance Adjusted.Final Rept Expected by 830923
ML20076A8228 August 1983Corrects Final Deficiency Rept 83-01 Re Riley Temp Indicating Switches.Riley Temp Switches Not Recalibr to Modified Calibr Procedure.Calibr to Be Done Prior to Fuel Load