ML20076A822
ML20076A822 | |
Person / Time | |
---|---|
Site: | LaSalle |
Issue date: | 08/08/1983 |
From: | Schroeder C COMMONWEALTH EDISON CO. |
To: | James Keppler NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION III) |
References | |
10CFR-050.55E, 10CFR-50.55E, 7106N, 83-01, 83-1, NUDOCS 8308180346 | |
Download: ML20076A822 (1) | |
Similar Documents at LaSalle | |
---|---|
Category:DEFICIENCY REPORTS (PER 10CFR50.55E & PART 21)
MONTHYEARML20217A1691999-09-22022 September 1999
[Table view]Part 21 Rept Re Engine Sys,Inc Controllers,Manufactured Between Dec 1997 & May 1999,that May Have Questionable Soldering Workmanship.Caused by Inadequate Personnel Training.Sent Rept to All Nuclear Customers ML20153D0191998-09-18018 September 1998 Part 21 Rept Re Defect in Gap Conductance Analyses for co- Resident BWR Fuel.Initially Reported on 980917.Corrective Analyses Performed Demonstrating That Current Operating Limits Bounding from BOC to Cycle Exposure of 8 Gwd/Mtu ML20153C6771998-09-17017 September 1998 Part 21 Rept Re Defect Relative to MCPR Operating Limits as Impacted by Gap Conductance of co-resident BWR Fuel at Facilities.Operating Limit for LaSalle Unit 2 & Quad Cities Unit 2 Will Be Revised as Listed ML20236N6751998-07-0909 July 1998 Part 21 & Deficiency Rept Re Notification of Potential Safety Hazard from Breakage of Cast Iron Suction Heads in Apkd Type Pumps.Caused by Migration of Suction Head Journal Sleeve Along Lower End of Pump Shaft.Will Inspect Pumps ML20198K5081998-01-0606 January 1998 Part 21 Rept Re Transient Analyses at Exposures Prior to End of Cycle.Caused by Component Defect.Notified Commonwealth Edison of Defect & Provided Revised Limits by Siemens Power Corp ML20203B3691997-12-10010 December 1997 Part 21 Rept Re Potential to Exceed Operating Limits.Cycle 8 Delayed Until Fall 1998 ML20134Q0801996-11-27027 November 1996 Part 21 Rept Re Deficiency of Wkm Model 70-13 Pneumatic Actuators Manufactured by Anchor Darling Valve Company Due to Incorrect Calculation of Bench Set & Supply Air Set Points.All Affected Valves Have Been Reviewed & Evaluated ML20128F5011996-10-0404 October 1996 Part 21 Rept & Deficiency Rept Re Wkm Model 70-13 Pneumatic Actuators Mfg by Anchor Darling Valve Co.All Affected Valves Being Reviewed/Evaluated & Design Changes Are Being Initiated as Required ML20117P3141996-09-11011 September 1996 Part 21 Rept Re Deficiency of GE Type RMS-9 Overcurrent Trip Device Programmers ML20082B5271995-03-28028 March 1995 Part 21 Rept Re Notification 9505 Automatic Switch Co Pilot Solenoid Valve Model NP8323A20V.Caused by Failures of MSIVs to Close to Asco Pilot Solenoid Valves.Subj Valves Replaced W/Valcor 3-way Solenoid Valves ML20082E1901995-03-27027 March 1995 Part 21 Rept Re Sticking of B Core Assembly to Plugnut on Automatic Switch Co Dual Solenoid Valve Model NP8323A20V. Unit 2 Valves Replaced.Unit 1 Valves Will Be Replaced ML20069A8631994-05-17017 May 1994 Final Part 21 Rept Re Secondary Containment Isolation Techno Corp Dampers Equipped W/Parker Hannifin Air Cylinders at LaSalle County Station.All Units 1 & 2 Techno Dampers Equipped W/Parker Air Cylinders Replaced ML20070N3451994-05-0202 May 1994 Part 21 Rept Re Failures of Limit Switch Series EA740-86700 Mfg by Namco Controls Co Due to Excessive Amount of Grease on Contact Block & Contact Carrier & Wrong Matl of O-ring. Series EA740-86700 Switches Replaced w/EA740-50100 Switches ML20063D0861994-02-0202 February 1994 Part 21 Rept Re Possible Anomaly W/Namco Controls EA740 & EA750 Series Limit Switches.Investigation in Progress & Has Not Been Concluded.Vendor Will Advise NRC within Next Thirty Days Re Matter as Addl Info Becomes Available ML20059L9861993-11-11011 November 1993 Part 21 Rept Re Deviation Wherein Fully Open Butterfly Valve Located 15 Pipe Diameters Upstream of Sensors Was Disturbing Flow Profile Enough to Cause Ultrasonic Meter to Indicate 3 to 4% Low.Customers Notified & Valve Removed ML20043A6091990-04-27027 April 1990 Part 21 Rept Re Defective Axial Cracks in Pump Shaft in Region Immediately Above Impeller & in Reactor Recirculation Pumps.Probably Caused by Crack Growth as Thermal Fatigue. Technical Advisory Bulletin Will Be Sent to Each Util ML20211P7211987-02-23023 February 1987 Part 21 Rept Re Rockbestos Coaxial Cable Used in Sorrento Electronics Digital & Analog high-range Radiation Monitor. Insulation Resistance at High Temp Not High Enough for Ion Chamber & Associated Electronics to Operate Properly ML20207J8491986-07-25025 July 1986 Part 21 Rept Re Potential Change in Allowable Operating Repeatability Ranges for 1E Qualified Series 9,8 & 1 Pressure Switches.Licensee Calibr Procedures Should Be Amended to Allow for Cycling (Hysteresis) Effects ML20198R5751986-06-0303 June 1986 Part 21 Rept Re Failure of 103/B212 Type Differential Pressure Switches to Give Scram During 860601 Feedwater Transient.Investigation Continuing ML20140A5281985-12-19019 December 1985 Part 21 Rept Forwarding Ltr Sent to Customers Re Check Valves Missing Lock Welds on Hinge Supports or Hinge Support Capscrews,Per 851121 Request.List of Customers Receiving Ltr Also Encl ML20128G5101985-05-24024 May 1985 Part 21 Rept Re Heat Numbers to Be Added & Deleted from Sublist Sheet A,Based on Review of NRC ML20127N0621985-05-13013 May 1985 Part 21 Rept Re Incorrect Short Time Delay Band Lever Inadequately Installed in Low Voltage K-line Circuit Breaker Electromechanical Overcurrent Trip Device.Visual Insp to Determine If Correct Lever Installed Recommended ML20099F3921984-11-0808 November 1984 Part 21 Rept Re Hexcel/Mci Pipe Restraints Found W/Average Dynamic Crush Strength Values Below Acceptable Values. Initially Reported on 841101.Replacement Program in Progress ML20096A5441984-08-21021 August 1984 Part 21 Rept Re Ground Fault Failures of Actuation Solenoids for Crosby Safety Relief Valves PRC 84-24.Problem Still Considered Germane Condition.Memo of 840808 Telcon Updating 840615 Interim Rept Encl ML20083J7731983-12-22022 December 1983 Final Deficiency Rept Re Defective GE Hma Relays.Initially Reported on 830805.Two Relays Found to Have Insufficient Armature Clearance.Adjustments Made ML20082Q6921983-12-0202 December 1983 Final Deficiency Rept 83-07 Re Design Calculation for Fire Water Sys.Initially Reported on 831102.Preliminary Calculations Completed.Final Rept Will Be Submitted Approx 20 Days Prior to Exceeding 5% Power ML20085K6361983-10-12012 October 1983 Final Deficiency Rept 83-06 Re Asco Solenoid Valves in Control Rod Drive Sys.Initially Reported on 830912.Valves W/Defective Solenoid Plunger Housings Replaced & Spare Parts in Inventory Examined.Plant Operable ML20077N6151983-09-0101 September 1983 Interim Deficiency Rept 83-05 Re Potentially Defective GE Hma Relays Mfg in 1974.Initially Reported on 830805.Two Relays Found W/Insufficient Armature Clearance.Clearance Adjusted.Final Rept Expected by 830923 ML20076A8221983-08-0808 August 1983 Corrects Final Deficiency Rept 83-01 Re Riley Temp Indicating Switches.Riley Temp Switches Not Recalibr to Modified Calibr Procedure.Calibr to Be Done Prior to Fuel Load ML20077A8961983-07-15015 July 1983 Final Rept Re Potentially Defective Figures 425,426 & 428 Spring Hangers Mfg by Elcen Metal Products Co.Initially Reported on 830617.Review Revealed Spring Hanger Installed at Facility Not Type in Question.Item Closed ML20024B7771983-07-0707 July 1983 Final Deficiency Rept 83-03 Re Medium Voltage Circuit Breakers of Same Type Installed at Limerick Which Inadvertently Closed After Completion of Spring Charging Due to Slipped Close Latch,Discussed in Brown Boveri ML20072A7371983-06-0303 June 1983 Final Deficiency Rept Re Problems W/Riley Temp Switches. Initially Reported on 830316.Based on Engineering Evaluation by Riley,Switches Accurately Perform Intended Function When Calibr W/Modified Procedure ML20083L9751983-05-27027 May 1983 Part 21 Rept Re Failure of Circuit Breakers During Environ Testing.Test Results Indicate That Temp Sensitivity Problem May Be Generic to All Ite Imperial Corp thermal-magnetic Circuit Breakers Calibr for 40 C Svc ML20074A3101983-05-0404 May 1983 Part 21 Rept Re Defect in Shielded Multiconductor Cable Installed in HVAC Control Panels.Mcc Powers Personnel Attached Hold Tags to 13 HVAC Control Panels W/Defect. Evaluation Being Conducted ML20073T1421983-05-0303 May 1983 Updated Interim Deficiency Rept Re Offset & Module Problems of Riley Temp Indicating Switches in Leak Detection Sys. Calibr Procedure Modified.Final Resolution of Module Problem (Hardware Mod) in Progress.Final Rept Expected by 830601 ML20073S6731983-05-0202 May 1983 Interim Deficiency Rept 83-01 Re Temp Offset Problems Experienced W/Riley Temp Switches Installed in Leak Detection Sys.Calibr Procedure Modified & Switches Recalibr. Final Rept Will Be Submitted by 830601 ML20024B7841983-04-28028 April 1983 Followup Interim Rept Re Potential Deficiency in 5HK Switchgear Supplied by Brown Boveri.Circuit Breaker Inadvertently Closed & Tripped Following Spring Charging. Light Spring Added to Close Latch ML20074A2041983-04-26026 April 1983 Interim Deficiency Rept Re Misapplication of Ite Gould Circuit Breakers in post-LOCA Hydrogen Recombiners Supplied by Rockwell Intl.Initially Reported on 830328.Matter Under Investigation.Final Rept by 830808.Reported Per Part 21 ML20074A3191983-04-18018 April 1983 Part 21 Rept Re Defect in Shielded Multiconductor Cable Installed in HVAC Control Panels.All Suspect Panels Inspected & Nonconformance Rept Will Be Issued for Applicable Sites ML20073F6751983-04-0707 April 1983 Final Const Deficiency Rept 82-07 Re Shop Welding by Unauthorized Welders.Zack Co Officially Withdrew Part 21 Rept on 820914 Based on Results of Investigation ML20072P7311983-03-30030 March 1983 Revised Final Deficiency Rept 81-06 Re Crosby Safety Relief Valve IMF-2 Solenoid Valve.Solenoids Have Had Qualified Collet/Yoke Assembly Installed,Closing Out Undervoltage Concern.Valves Qualified Per NUREG-0588 ML20069E4501983-03-16016 March 1983 Final Deficiency Rept Re Significant Deviation from Performance Specs for Sor,Inc Pressure Switches Installed as Part of ECCS Interlock Mod.Initially Reported on 830216. All Leaking O-rings Replaced ML20069E6671983-03-16016 March 1983 Interim Deficiency Rept 83-01 Re Significant Deviation from Performance Specs for Riley Temp Switches in Leak Detection Sys.Initially Reported on 830215.Two Units Returned to GE for Evaluation.Temp Module Resolution Expected by Apr 1983 ML20074A2221983-03-11011 March 1983 Part 21 Rept Re Failure of post-LOCA Hydrogen Recombiner Component During IEEE-323 Qualification Program.Circuit Breaker Not Properly Selected for Specific Application.Plant Operators Notified of Deviation ML20071E9191983-03-0101 March 1983 Final Deficiency Rept 82-08 Re Electrical Penetration Assemblies.Initially Reported on 820817.Replacement Modules Will Be Installed by 830501 ML20070R8521983-01-24024 January 1983 Interim Deficiency Rept 82-08 Re Electrical Penetration Assembly Butt Splices.Replacement Modules for Awg Cable Modules 2 & 6 Ordered from Conax.Final Rept Will Be Provided on or About 830303 ML20028E6511983-01-21021 January 1983 Final Deficiency Repts 82-10 & 11 Re Rigid Strut Pins Mfg by Elcen.Initially Reported on 821223.Test Results Indicate No Load Capacity Data Values Violated.If Such Pins Were Used,Design Margins Not Exceeded ML20073J5211982-12-14014 December 1982 Part 21 Rept Re Likely Failure of post-LOCA Hydrogen Recombiner Component,Dpst Toggle Switch 12TSI-2 Due to Aging & Radiation.Field Bulletins Issued to Install Jumpers Bypassing Switch ML20079J7921982-12-14014 December 1982 Interim Deficiency Rept Re Inadequate Pressure Transducers/ Transmitters Mounted on post-LOCA Hydrogen Recombiners. Initially Reported on 821119.Final Rept Will Be Submitted by 830211.Also Reported Per Part 21 ML20066J5131982-11-18018 November 1982 Final Deficiency Rept Re Overtorqued Anchor Bolts on ECCS Pump Foundation.Initially Reported on 821019.Recheck of Torque Values to Be Performed by 821206.Sargent & Lundy 821110 Evaluation of Anchor Bolt Status Encl 1999-09-22 Category:TEXT-SAFETY REPORT MONTHYEARML20217C9121999-10-12012 October 1999
[Table view]SER Input Authorizing Licensee Proposed Request to Modify Definition of Core Alteration in Section 1.0 of TS & Update Sections 3/4.1,3.4.3 & 3/4.9 to Reflect Proposed Definition Change 05000373/LER-1999-003-04, :on 990902,reactor Scram on Low Reactor Water Level,Was Received.Caused by Personnel Error.Appropriate Disciplinary Action Taken with non-licensed Operator1999-10-0404 October 1999
1999-09-30 |
Text
['O Commonwealth Edison
^ ) one First National Plata. Chictgo, Illinois t
"J Address Reply to: Post Office Box 767 (j Chicago, Illinois 60690 August 8, 1983 Mr. James G. Keppler, Director - Region III U.S. Nuclear Regulatory Commission 799 Roosevelt Road Glen Ellyn, IL 60137
Subject:
LaSalle County Station Unit 2 10CFR50.55(e) Notification 83-01 Correction to Final Report, Riley Temperature Indicating Switches NRC Docket No. 50-374 Reference (a):
C.W.
Schroeder letter to J.G. Keppler dated March 16, 1983.
(b):
C.W. Schroeder letter to J.G. Keppler dated May 3, 1983.
(c):
C.W. Schroeder letter to J.G. Keppler dated June 3, 1983.
Dear Mr. Keppler:
The purpose of this letter is to correct a statement made in 4
Reference (c).
The Unit 2 Riley temperature switches have not yet been recalibrated to the modified calibration procedure suggested by Riley, i
~ 0nly the Unit 1 temperature switches have been recalibrated at this time.
We will complete the calibration on Unit 2, using the same calibration procedure as Unit 1, prior to fuel load.
If there are any questions in this matter, please contact this office.
Very truly yours, k
C.W. Schroeder l
Nuclear Licensing Administrator 1m cc:
Region III Inspector - LSCS Director of Enforcement & Inspection 8308190346 830808 PDR ADOCK 05000374
-7106N S
PDR gg ly, DO