/ME Commonwrith Edison

/

One First National Plaza. Chicago. Ilhnois 7 Address Reply to Post Office Box 767 t

/ Chicago. illinois 60690 December 22, 1983 Mr. James G. Keppler, Director Directorate of Inspection and Enforcement - Region III U.S. Nuclear Regulatory Commission 799 Roosevelt Road Glen Ellyn, IL 60137 Eubject:

LaSalle County Station, Unit 2 10 CFR 50.55(e) Notification 83-05 Final Report, G.E. HMA Relays NRC Docket No. 50-374 Reference (a):

C.

W.

Schroeder letter to J. G. Keppler dated September 1, 1983.

Dear Mr. Keppler:

Commonwealth Edison notified your of fice on August 5, 1983 o f a reportable deficiency in accordance with 10CFR50.55(e) concerning potentially defective HMA relays manufactured by the General Electric Cumpany.

The review of all Unit 2 safety related HMA relays was performed in two steps.

At the time of our interim report (Reference (a)) a HMA list had been prepared and inspected per G.E.'s recommended procedure (G.E. FDI TEGX Rev. 0).

Two relays were found to have insufficient armature clearance and have been adjusted.

Further review of electrical drawings added several more panels providing a complete list of safety related HMA relays for LSCS Unit 2.

The second review step involved inspecting the additional panels which did not turn up any defective relays.

Now that all safety related HMA relays with the date codes in question have been inspected and repaired for LSCS Unit 2 we believe this issue is closed.

If there are any questions concerning this subject, please contact this office.

Very truly yours, 8401050413 831222 go" ^oo" RM Ch h 4,g C.

W.

Schroeder Nuclear Licensing Administrator 1m 7857N BEc 2 q (S0i 10

,-ny\\s