MONTHYEARML23349A2082023-12-15015 December 2023 TRISO-X, LLC, Response to Request for Additional Information Set 6 (Structural, Material Control and Accounting, and Fire Safety) for the TRISO-X License Application Project stage: Response to RAI ML24020A0102024-01-20020 January 2024 Project Update Letter Regarding the TRISO-X License Application Project stage: Other ML23332A0742024-02-23023 February 2024 Summary of Six Meetings with TRISO-X to Align on Supplement to Responses to Integrated Safety Analysis Requests for Additional Information Project stage: Request ML24060A2392024-02-29029 February 2024 TRISO-X, LLC, Submittal of Supplemental Information for the Electrical/I&C Review of IROFS for the TRISO-X License Application Project stage: Supplement ML24030A8472024-03-0101 March 2024 Summary of Meeting on January 24, 2024, with TRISO-X LLC Project stage: Request ML24066A1812024-03-25025 March 2024 Summary of the Meeting on January 25, 2024, with TRISO-X LLC, to Align a Supplement for Management Measures Review Project stage: Request ML24085A7642024-04-0202 April 2024 Summary of Meeting on March 18, 2024, with TRISO-X LLC, to Align on Draft Set 8 Requests for Additional Information Regarding the Integrated Safety Analysis Project stage: Draft Approval ML24085A7632024-04-0202 April 2024 Enclosure - Participant List for Meeting on March 18, 2024 with TRISO-X LLC Project stage: Meeting ML24085A7622024-04-0202 April 2024 Summary of Meeting on March 18, 2024, with TRISO-X LLC, to Align on Draft Set 8 Requests for Additional Information Regarding the Integrated Safety Analysis Project stage: Request ML24071A1572024-04-0808 April 2024 Enclosure 1 - Participants List for Meetings Held 02-21-24 and 02-22-24 with TRISO-X for Supplement Regarding RAIs on ISA Summary Project stage: RAI ML24071A1562024-04-0808 April 2024 Memorandum - Summary of Meetings on Held on 2-21-24 and 2-22-24 with TRISO-X for Supplements Regarding RAIs on the ISA Summary Project stage: RAI ML24102A1822024-04-24024 April 2024 Enclosure 1 - Participant List for Meeting on April 9, 2024 with TRISO-X LLC Project stage: Meeting ML24102A1812024-04-24024 April 2024 Cover Letter - Summary of Meeting on April 9, 2024, with TRISO-X LLC, to Discuss Supplement Responses to Structural Programmatic Requests for Additional Information Project stage: RAI ML24165A1362024-06-17017 June 2024 6-17-24 Slides Meeting to Discuss an Overview of the TRISO-X License Application Review Status Project stage: Meeting ML24183A2032024-07-31031 July 2024 Enclosure 1 - Participant List for Meeting on June 6, 2024, with TRISO-X, LLC Project stage: Meeting ML24183A2022024-07-31031 July 2024 Memo - Summary of Meeting on June 6, 2024, with TRISO-X, LLC, to Align on the Supplement Responses to Integrated Safety Analysis Requests for Additional Information Project stage: RAI ML24178A4042024-08-0101 August 2024 Enclosure 1 - Participant List for the May 24, 2024 Meeting Regarding the TRISO-X, LLC Supplements for the Integrated Safety Analysis Summary Requests for Additional Information for the License Application Project stage: RAI ML24178A4022024-08-0101 August 2024 Memo - Summary of Meeting on May 24, 2024, with TRISO-X LLC, to Align on the Supplemental Responses to the Integrated Safety Analysis Requests for Additional Information Project stage: RAI ML24206A0462024-08-26026 August 2024 Enclosure - Participant List for Meeting on June 17, 2024 with TRISO-X, LLC Project stage: Meeting ML24198A2352024-08-26026 August 2024 Memorandum - Summary of Meeting Held on June 17 2024 with TRISO-X to Align on NRC Supplement Responses to Management Measures Requests for Additional Information Project stage: RAI ML24198A2342024-08-26026 August 2024 Enclosure - Participant List for June 17, 2024 Meeting with TRISO-X Project stage: Meeting ML24206A0452024-08-26026 August 2024 Memo - Summary of Meeting on June 17, 2024, with TRISO-X, Llc. to Discuss the Status of the License Application Review Project stage: Meeting ML24206A0772024-09-0505 September 2024 Memorandum - Summary of Meeting Held on June 27, 2024 with TRISO-X LAR Structural Meeting Project stage: Meeting ML24228A1262024-09-0505 September 2024 Enclosure 1 - Participant List for Summary of Meeting Held July 17, 2024, with TRISO-X, LLC, to Align on the Supplement Responses to Management Measures and Quality Assurance Requests for Additional Information Project stage: RAI ML24228A1282024-09-0505 September 2024 Memo - Summary of Meeting on July 17, 2024, with TRISO-X to Align on the Supplemental Responses to the Management Measures and Quality Assurance Requests for Additional Information Project stage: RAI ML24254A4092024-10-0808 October 2024 Memo - Summary of Meeting on August 28, 2024, with TRISO-X, LLC to Align on the Supplement Responses to the Management Measures and Quality Assurance Requests for Additional Information (Public) Project stage: RAI ML24254A4102024-10-0808 October 2024 Enclosure - Participant List for Meeting on August 28, 2024 with TRISO-X, LLC (Public) Project stage: Meeting ML24255A3212024-10-0808 October 2024 Memo - Summary of Meeting on August 27, 2024 with TRISO-X to Discuss Draft Supplement Responses to Structural Programmatic Requests for Additional Information Project stage: Draft RAI ML24255A3232024-10-0808 October 2024 Enclosure 1 - Participant List for Meeting on August 27, 2024 with TRISO-X LLC Structural Meeting Project stage: Meeting ML24289A1492024-11-29029 November 2024 Memo - Summary of Meeting on September 9, 2024, with TRISO-X, LLC, to Discuss Responses to the Hydrology Requests for Additional Information Project stage: RAI ML24289A1502024-11-29029 November 2024 Enclosure - Summary of September 9, 2024 with TRISO-X, LLC Participant List Project stage: Other ML24337A1072024-12-20020 December 2024 Enclosure - Participant List for a Structural Meeting with TRISO-X on October 17, 2024 Project stage: Meeting ML24337A1062024-12-20020 December 2024 Memo to TRISO-X, LLC Summary of Meeting Structural Meeting on October 17, 2024 Project stage: Meeting ML24362A1192024-12-31031 December 2024 Memo the Chemical Safety Summary of the TRISO-X Chemical Safety Meeting on October 31, 2024 Project stage: Request ML24362A1202024-12-31031 December 2024 Memo - TRISO-X for the Summary of Meeting on October 31, 2024, with TRISO-X, LLC, to Discuss the TRISO-X Response to the Chemical Safety Requests for Additional Information Project stage: RAI ML24362A1212024-12-31031 December 2024 Enclosure - Participant List for a Meeting with TRISO-X on October 31, 2024 to Discuss Chemical Requests for Additional Information Project stage: RAI ML24332A1122025-01-0202 January 2025 Memo - Summary of Meeting Held on November 7, 2024 with TRISO-X Chemical Safety Request for Additional Information Project stage: RAI ML24332A1112025-01-0202 January 2025 Summary of Meeting Held on November 7, 2024 with TRISO-X Chemical Safety Request for Additional Information Project stage: Request ML24332A1132025-01-0202 January 2025 Enclosure - Participant List for November 7, 2024 Meeting with TRISO-X Project stage: Meeting ML25008A2492025-01-23023 January 2025 Memorandum - Summary of Regulatory Audit for TRISO-X Integrated Safety Analysis Definitions of Unlikely and Highly Unlikely Project stage: Other ML25021A2022025-02-10010 February 2025 Memo - Summary of Meeting with TRISO-X LLC, on ISA Likelihood Definitions Project stage: Meeting ML25057A4622025-03-10010 March 2025 Memo - Summary of Meeting Held on January 16, 2025, with Triso-X LLC, to Discuss Draft Requests for Additional Information on Electrical and Instrumentation and Control Project stage: Draft RAI ML25094A1882025-04-0404 April 2025 Response to Request for Additional Information Seet 9 (Human Factors) for the TRISO-X License Application Project stage: Response to RAI ML25217A4552025-08-0505 August 2025 Triso-X, LLC - Human Factors Supplemental Information for the TRISO-X License Application Project stage: Supplement ML25231A0042025-08-20020 August 2025 Trip Report for Inspection Scope and Construction Schedule Meeting Held on August 5, 2025, with Triso-X, LLC (Enterprise Project Identifier L-2022-PMP-0005) Project stage: Meeting ML25206A4152025-09-0202 September 2025 Memorandum - Meeting Summary of June 25, 2025 to Provide Clarity on Draft Criticality Requests for Additional Information for the Triso-X, LLC, License Application Project stage: Draft RAI ML25195A2192025-09-19019 September 2025 Memorandum - Trip Report for Horizontal Vertical Slice Meeting Held on May 20 and 21, 2025, with TRISO-X, LLC Project stage: Meeting ML25227A1292025-09-19019 September 2025 Enclosure 1 - May 20-21, 2025 Regional Trip Report Input for the ISA Horizontal Vertical Slice Project stage: Other ML25325A2362025-12-0909 December 2025 Memorandum - Summary of July 8, 2025, Meeting to Provide Clarity on Draft Structural RAIs for the TRISO-X License Application Project stage: Draft RAI ML25322A4132025-12-16016 December 2025 Memo - Summary of Call with TRISO-X, Llc. Held on September 15, 2025 to Discuss Supplements for Set 9, RAIs-4 and 5 for Human Factors Project stage: Other 2024-07-31
[Table View] |
Text
OFFICIAL USE ONLY - SECURITY RELATED INFORMATION OFFICIAL USE ONLY - SECURITY RELATED INFORMATION UNITED STATES NUCLEAR REGULATORY COMMISSION WASHINGTON, D.C. 205550001 MEMORANDUM TO:
James Downs, Acting Chief Fuel Facility Licensing Branch Division of Fuel Management Office of Nuclear Material Safety and Safeguards FROM:
Matthew Bartlett, Sr. Project Manager Fuel Facility Licensing Branch Division of Fuel Management Office of Nuclear Material Safety and Safeguards
SUBJECT:
SUMMARY
OF MEETING ON AUGUST 27, 2024, WITH TRISO-X LLC, TO DISCUSS DRAFT SUPPLEMENT RESPONSES TO STRUCTURAL PROGRAMMATIC REQUESTS FOR ADDITIONAL INFORMATION, (ENTERPRISE PROJECT IDENTIFIER L2022PMP0005)
The U.S. Nuclear Regulatory Commission (NRC) hosted a closed Microsoft Teams meeting with TRISO-X, LLC (TRISO-X) on August 27, 2024, from 11:00 a.m. until 12:30 p.m. The purpose of the meeting was to discuss the draft supplemental responses from TRISO-X to the NRC staff to resolves requests for additional information (RAIs) issued via letter dated November 17, 2023 (Agencywide Documents Access and Management System [ADAMS] Accession No. ML23313A110). TRISO-X provided their initial responses to the RAIs via letter dated December 15, 2023 (ML23349A208), which did not resolve the RAIs.
This meeting involved discussion of the response for Structural RAI 22, (Building) Risk Category. It continues discussions from meetings held on January 24, 2024 (ML24030A847),
April 9, 2024 (ML24102A180), and June 27, 2024 (ML24206A077).
CONTACT: Matt Bartlett, NMSS/DFM 301415-7154 A document transmitted herewith contains Security-Related Information. When separated from, this document and are decontrolled.
October 8, 2024 Signed by Bartlett, Matthew on 10/08/24
OFFICIAL USE ONLY - SECURITY RELATED INFORMATION J. Downs 2
OFFICIAL USE ONLY - SECURITY RELATED INFORMATION TRISO-X posted slides to the online portal1 on August 14, 2024, which was the originally scheduled date for this meeting. The NRC staff rescheduled the meeting to August 27, 2024, to allow additional time to review the new information in the slides, which were subsequently emailed to the NRC, see enclosure 2. The slides proposed a new approach to satisfy the performance requirements of Title 10 of the Code of Federal Regulations (10 CFR) §70.61 and 70.64, which included the following points:
1.
Internal equipment is designated as a critical non-structural components (CNSCs) and items relied on for safety (IROFS) to protect against intermediate or high-consequence events resulting from natural phenomena hazard (NPH) events.
2.
Since TRISO-X is crediting CNSC to mitigate the consequences of NPH events, they do not intend to credit any exterior barriers, such as the building structure.
3.
Because TRISO-X is not intending to rely on the building structures to perform a safety function or meet the performance requirements for 10 CFR 70.61, they believe that designing and constructing in accordance with building risk category III, from American Society of Civil Engineers (ASCE) 7-16, Minimum Design Loads and Associated Criteria for Buildings and Other Structures, is appropriate.
The NRC staff stated that TRISO-X needs to demonstrate their approach for all the credible NPH events for the site. The slides are focused on the seismic NPH. TRISO-X indicated they have that information and would provide it in the future.
As TRISO-X does not believe that the building or structures are needed to meet the performance requirements, they plan to meet the baseline design criteria in 10 CFR 70.64 by meeting the building codes (i.e., building risk category III from ASCE 7-16). The NRC staff agreed in principle that structures not important to safety (i.e., that are not IROFS) could be designed based on an industrial code that does not account for radiological hazards. However, the current application indicates the buildings are relied on for preventing or mitigating potential consequences of NPH events. Therefore, the building structures should use an appropriate code that takes account of the applicable hazards (e.g., radiological, chemical, criticality).
ASCE 43, Seismic Design Criteria for Structures, Systems, and Components in Nuclear Facilities would be appropriate for structures important to safety for a fuel cycle facility. The NRC staff can consider a risk informed approach to allow use of an industrial code such as ASCE 7-16, provided a more robust building risk category IV is used to provide more reliability for the nuclear material hazards.
The NRC staff requested TRISO-X to explain their analysis for determining that NPH events do not result in intermediate or high consequence events. TRISO-X stated that since the building is designed to meet the base line design criteria (BDC) according to the international building codes, the NPH events are highly unlikely. The NRC staff stated that TRISO-X appears to be relying on the design of the building as the engineered mitigation to mitigate the consequences of NPH events. TRISO-X stated they do not understand the staff's statement that they need to evaluate NPH events without considering the design of the building to meet the BDC because the unmitigated state should be based on existing features, which includes the design of the building. The staff pointed out that NPH events are different from process safety events. The likelihood of NPH events is independent of the design. Elements of the design relied on to 1 Documents provided on the portal are internal TRISO-X documents not to be docketed in ADAMS.
OFFICIAL USE ONLY - SECURITY RELATED INFORMATION J. Downs 3
OFFICIAL USE ONLY - SECURITY RELATED INFORMATION mitigate the intermediate and high consequences of NPH events need to be identified as IROFS, consistent with 10 CFR 70.61(e).
For the TRISO-X approach to be acceptable to the NRC staff, TRISO-X would need to demonstrate they are only relying on CNSCs to meet the performance requirements. However, this appears to contradict the TRISO-X statements that meeting the BDC is used to ensure NPH events meet the performance requirements. The NRC staff emphasized that meeting the BDC does not replace the requirement to meet 10 CFR 70.61. TRISO-X stated they believe they have adequately considered the potential accident sequences and are addressing the performance requirements. The NRC staff proposed performing an audit at the TRISO-X site to discuss the issues more in-depth and consider specific examples.
TRISO-X raised concern regarding the timing of the supplemental information, which is currently due August 30, 2024. The NRC staff stated that they support moving the date of the supplement to allow further discuss to reach alignment during the audit, which could be held toward the end of September 2024. The NRC staff stated that they will provide an extension for the supplement due date until several weeks after the audit.
TRISO-X pointed out that the existing guidance provided in NUREG1520, Standard Review Plan for License Applications for Fuel Cycle Facilities, regarding NPH analysis, does not adequately address this topic and is a potential cause for the misalignment between TRISO-X and the NRC staff. The NRC staff acknowledged this comment and will consider it as a potential lesson learned topic for resolution in future updates to the guidance.
A list of participants is provided as Enclosure 1. A copy of the TRISO-X slides is provided in (non-public).
Docket No. 07007027
Enclosures:
1.
Participant List (public) 2.
TRISO-X Slides (non-public) cc: trisox@listmgr.nrc.gov
ML24255A320; Memo ML24255A321 OFFICE NMSS NMSS/DFM/FFLB* NMSS/DFM/FFLB NMSS/DFM/FFLB NAME JRudd SPoy MBartlett JGoodridge DATE Sep 12, 2024 Sep 18, 2024 Sep 19, 2024 Sep 20, 2024 OFFICE NRR/DRO/IRSB NMSS/DFM/MSB NMSS/DFM/FFLB*
NMSS/DFM/FFLB NAME TGovan TBoyce SLav JDowns for MBartlett DATE Sep 23, 2024 Sep 20, 2024 Oct 8, 2024 Oct 8, 2024