IR 05000346/2022011

From kanterella
(Redirected from ML23004A217)
Jump to navigation Jump to search
Triennial Fire Protection Inspection Report 05000346/2022011
ML23004A217
Person / Time
Site: Davis Besse 
Issue date: 01/05/2023
From: Richard Skokowski
NRC/RGN-III/DORS/EB2
To: Tony Brown
Energy Harbor Nuclear Corp
References
IR 2022011
Download: ML23004A217 (1)


Text

SUBJECT:

DAVIS-BESSE NUCLEAR POWER STATION - TRIENNIAL FIRE PROTECTION INSPECTION REPORT 05000346/2022011

Dear Terry Brown:

On November 22, 2022, the U.S. Nuclear Regulatory Commission (NRC) completed an inspection at Davis-Besse Nuclear Power Station and discussed the results of this inspection with you and other members of your staff. The results of this inspection are documented in the enclosed report.

No findings or violations of more than minor significance were identified during this inspection.

This letter, its enclosure, and your response (if any) will be made available for public inspection and copying at http://www.nrc.gov/reading-rm/adams.html and at the NRC Public Document Room in accordance with Title 10 of the Code of Federal Regulations 2.390, Public Inspections, Exemptions, Requests for Withholding.

Sincerely, Richard A. Skokowski, Chief Engineering Branch 2 Division of Operating Reactor Safety Docket No. 05000346 License No. NPF-3

Enclosure:

As stated

Inspection Report

Docket Number:

05000346

License Number:

NPF-3

Report Number:

05000346/2022011

Enterprise Identifier:

I-2022-011-0036

Licensee:

Energy Harbor Nuclear Corp.

Facility:

Davis-Besse Nuclear Power Station

Location:

Oak Harbor, OH

Inspection Dates:

October 03, 2022 to November 22, 2022

Inspectors:

K. Barclay, Senior Reactor Inspector

M. Domke, Reactor Inspector

B. Jose, Senior Reactor Inspector

Approved By:

Richard A. Skokowski, Chief

Engineering Branch 2

Division of Operating Reactor Safety

SUMMARY

The U.S. Nuclear Regulatory Commission (NRC) continued monitoring the licensees performance by conducting a triennial fire protection inspection at Davis-Besse Nuclear Power Station, in accordance with the Reactor Oversight Process. The Reactor Oversight Process is the NRCs program for overseeing the safe operation of commercial nuclear power reactors.

Refer to https://www.nrc.gov/reactors/operating/oversight.html for more information.

List of Findings and Violations

No findings or violations of more than minor significance were identified.

Additional Tracking Items

Type Issue Number Title Report Section Status URI 05000346/2022011-01 Multiple NFPA 805 Non-Power Operation Transition Issues 71111.21N.05 Open URI 05000346/2021050-07 Potential High Emergency Diesel Generator Field Currents When Adding Manual Loads 71111.21N.05 Closed

INSPECTION SCOPES

Inspections were conducted using the appropriate portions of the inspection procedures (IPs) in effect at the beginning of the inspection unless otherwise noted. Currently approved IPs with their attached revision histories are located on the public website at http://www.nrc.gov/reading-rm/doc-collections/insp-manual/inspection-procedure/index.html. Samples were declared complete when the IP requirements most appropriate to the inspection activity were met consistent with Inspection Manual Chapter (IMC) 2515, Light-Water Reactor Inspection Program - Operations Phase. The inspectors reviewed selected procedures and records, observed activities, and interviewed personnel to assess licensee performance and compliance with Commission rules and regulations, license conditions, site procedures, and standards.

REACTOR SAFETY

71111.21N.05 - Fire Protection Team Inspection (FPTI) Structures, Systems, and Components (SSCs) Credited for Fire Prevention, Detection, Suppression, or Post-Fire Safe Shutdown Review (IP Section 03.01)

The inspectors verified that components and/or systems will function as required to support the credited functions stated for each sample. Additional inspection considerations are located in the fire hazards analysis (FHA) or safe shutdown analysis (SSA).

(1) Fire Zone 237, AFW Pump 1-1 Room, Fire Compartment E-01, Fire Detectors, Dampers, and Suppression Systems
(2) Auxiliary Feedwater (AFW) Pump 1-1, for Post-Fire Safe Shutdown Review
(3) Fire Pumps and Associated Hydraulic Calculation from SSCs Credited for Fire Prevention, Detection, Suppression Perspective

Fire Protection Program Administrative Controls (IP Section 03.02) (2 Samples)

The inspectors verified that the selected control or process is implemented in accordance with the licensees current licensing basis. If applicable, ensure that the licensees Fire Protection Program (FPP) contains adequate procedures to implement the selected administrative control. Verify that the selected administrative control meets the requirements of all committed industry standards.

(1) Combustible Control Program
(2) National Fire Protection Association (NFPA) 805 Monitoring Program

Fire Protection Program Changes/Modifications (IP Section 03.03) (2 Samples)

The inspectors verified the following:

a.

Changes to the approved FPP do not constitute an adverse effect on the ability to safely shutdown.

b.

The adequacy of the design modification, if applicable.

c.

Assumptions and performance capability stated in the SSA have not been degraded through changes or modifications.

d.

The FPP documents, such as the Updated Final Safety Analysis Report, fire protection report, FHA, and SSA were updated consistent with the FPP or design change.

e.

Post-fire Safe Shutdown (SSD) operating procedures, such as abnormal operating procedures, affected by the modification were updated.

(1) FPPCE 22-001, Replacement Valves for Obsolete Fire Protection United Brass Model 45S
(2) FPPCE 22-003, Replacement of TPCW Pump Motors MP7-1 and MP7-3

INSPECTION RESULTS

Unresolved Item (Open)

Multiple NFPA 805 Non-Power Operation Transition Issues URI 05000346/2022011-01 71111.21 N.05

Description:

During the Fire Protection Team Inspection (FPTI), the inspectors identified multiple issues associated with the licensees implementation of their National Fire Protection Association (NFPA) 805 Non-Power Operation (NPO) program.

A review of the licensees NFPA 805 license amendment request (ADAMS Accession Number ML1530A314) and associated supplement (ADAMS Accession Number ML16351A330), the inspectors found the licensee's statement that they would revise plant procedures to incorporate the insights, strategies, and analysis recommended or documented in their NPO Modes Transition Report and add the necessary procedure steps to ensure that key safety functions (KSFs) are achieved and maintained. The inspectors found that the licensee attempted to implement software controls instead of robust procedures and did not incorporate the insights, strategies, and analysis from their NPO Modes Transition Report into their plant procedures. Additionally, the inspectors found that the licensee did not add the necessary procedure steps to ensure that KSFs were achieved and maintained.

The licensees fire risk software was intended to prohibit hot work permits in fire compartments that contained pinch points during outage high risk evolutions (HREs). A pinch point is a fire area or compartment where a single fire could cause a loss of all success paths for a specific shutdown KSF. The software was found to be missing at least 10 fire compartments that should have been flagged as containing a pinch point. Some of the missing fire compartments contained multiple KSF pinch points including one compartment that contained 3 KSFs (Decay Heat Removal, Inventory Control, and Support/Electrical). These missing fire compartments were unprotected during the 2022 refueling outage HRE. An outage review found that only one fire compartment potentially had hot work conducted during the HRE time frame.

The inspectors found that the licensee did not have procedures for implementing all the necessary NFPA 805 NPO features within their fire risk software but relied on informal notes. The licensees informal notes did not specify that all pinch points needed to be protected during HREs. During the 2022 refueling outage HRE, the licensee only selected Inventory Control for hot work permit prevention; however, the decay heat removal, reactivity and support/electrical KSFs should have also been selected. This software implementation error led to four additional compartments being unprotected.

The licensees Fire Hazards Analysis Report, which is also their fire protection program design basis document, contained a Non-Power Operations (NPO) Modes Compliance Summery for each fire area (compartment). The NPO Modes Compliance Summary template stated, in part, that each compartment summary will contain any associated pinch points in the fire compartment and any features and/or controls that provide reasonable assurance that the fuel will be maintained in a safe and stable configuration The inspectors found that the NPO Modes Compliance Summary was inaccurate for all fire compartments that contained a pinch point at Davis-Besse. Specifically, all 46 pinch-point fire compartments contained the following summary, The potential effects of a fire occurring during NPO modes in this fire compartment were reviewed. This review was conducted using the methodology as described in Calculation ARS-DB-11-003. This area does not have any associated pinch points. The lack of failures resulting in a pinch point provides reasonable assurance the fuel will be maintained in a safe and stable configuration. Therefore, the NFPA 805 performance goal for NPO is satisfied.

Davis-Besse Facility Operating License Condition 2.C.(4), Fire Protection, stated, in part, that the licensee shall implement the items listed in Attachment S, Table S-2, Implementation Items, to the FENOC letter dated November 20, 2018, within 2 years following issuance of the license amendment.

S, Table S-2, Implementation Items, found in FENOC letter dated November 20, 2018 (ADAMS Accession Number ML18324A677), contained item DB-1908, Revise Procedures and Conduct Training to Implement NPO Requirements for NFPA 805, and item DB-2049, Develop the DBNPS NFPA 805 Design Basis Document.

The inspectors were concerned that the licensees overall implementation of their NFPA 805 NPO program was not consistent with their license amendment request and associated supplements.

Planned Closure Actions: The inspectors need to consult with the Office of Nuclear Reactor Regulation (NRR) to determine if these issues represent a failure to complete an NFPA 805 transition license condition or other traditional enforcement violation. Additionally, the inspectors need to determine if the differences in implementation would have changed the Agencys conclusion on approving the NFPA 805 license amendment request.

Licensee Actions: There are no immediate licensee actions needed for this unresolved issue. As the inspectors work with NRR, additional questions may develop that will be communicated to the licensee.

Corrective Action References:

CR-2022-07442: 2022 FP Inspection - FHAR Contains Incorrect NPO Compliance Summary CR-2022-07489: 2022 FP Inspection - Fire Protection Expert Software Issue CR-2022-07930: 2022 FP Inspection - Implementation of NPO Does Not Account for All Key Safety Functions URI Potential High Emergency Diesel Generator Field Currents When Adding Manual Loads URI 05000346/2021050-07 71111.21N.

Description:

(Closed) URI 05000346/2021050-07 Potential High Emergency Diesel Generator Field Currents When Adding Manual Loads During the special inspection related to multiple Emergency Diesel Generator (EDG) failures that took place from July 2019 to June 2021, as well as a reactor trip with multiple complicating equipment issues, the inspectors identified an Unresolved Item (URI)05000346/2021050-07 Potential High Emergency Diesel Generator Field Currents When Adding Manual Loads.

On June 24, 2021, while testing the Division 1 EDG, the licensee observed that the EDG output voltage was almost 10 percent above the nominal value. The licensee found that the internal circuit of the RA-70 microprocessor-based reference unit had failed. The RA-70 provides a resistance reference value to the automatic voltage regulator, and it had failed to its high limit setpoint. The licensee repaired the EDG, returned it to service, and performed several assessments to determine if the high voltage condition would have prevented the EDG from performing its safety function and assessed the effects of the high voltage condition on the operation of loads connected to the EDG.

The Team independently reviewed the evaluation and found that the conclusions associated with the downstream EDG loads were reasonable. However, the Team also found that the evaluation did not completely address the effects of adding manual loads to the EDG after automatic load sequencing, and the potential increase in generator exciter current levels.

The Teams concern was that the increased generator exciter currents could cause an exciter component failure and prevent proper operation of the EDG. The licensee subsequently had their contractor (MPR Associates) revise the evaluation to address the concern associated with high generator exciter currents. However, the evaluation was not completed before the conclusion of the special inspection. As a result, the Team was required to document this issue as an Unresolved Item.

The licensee provided the updated high voltage assessment; MPR Associates Report 0200-0213-RPT-001, Revision 3 to the Team on October 11, 2021. The NRC Region 3 inspectors reviewed the report and solicited a peer review by NRC Head Quarters electrical engineering branch. After reviewing the MPR report in detail, both NRC Head Quarters team and the Region 3 team agreed with the MPR report conclusions that potential increase in exciter current while adding manual loads to the EDG after automatic load sequencing, will not damage the exciter components and prevent the EDG from performing its safety function. The NRC inspectors did not identify any violations of more than minor significance. Therefore, this URI is closed.

Corrective Action Reference(s):

CR 2021-04913, EDG Overvoltage During Monthly Run

EXIT MEETINGS AND DEBRIEFS

The inspectors verified no proprietary information was retained or documented in this report.

On November 22, 2022, the inspectors presented the triennial fire protection inspection results to Terry Brown, Site Vice President and other members of the licensee staff.

DOCUMENTS REVIEWED

Inspection

Procedure

Type

Designation

Description or Title

Revision or

Date

71111.21N.05

Calculations

ARS-DB-11-003

Davis-Besse Non-Power Operational (NPO) Modes

Transition Report

71111.21N.05

Calculations

ARS-DB-13-071

Davis-Besse General Variances from Deterministic

Requirements (VFDR) Report

71111.21N.05

Calculations

ARS-DB-13-078

Recovery Actions for Transition Report Attachment G

71111.21N.05

Calculations

ARS-DB-15-085

Fire Protection Safe Shutdown NFPA 805 Recovery Action

Feasibility Study

71111.21N.05

Calculations

ARS-DB-17-112

Fire Risk Evaluation of No. 2 Auxiliary Feedwater Pump

Room (F-01)

71111.21N.05

Calculations

ARS-DB-19-114

Davis-Besse Fire Protection Safe Shutdown Recovery

Action Report

71111.21N.05

Calculations

C-EE-002.01-011

Low Voltage Coordination Calculation

71111.21N.05

Calculations

C-FP-013.10-018

Davis-Besse Power Station - NFPA 805 Safe Shutdown,

Non-Power Operation, and Fire PRA Cable Selection

Calculation

& A02

71111.21N.05

Calculations

C-FP-013.10-020

Davis-Besse Nuclear Power Station - NUREG / CR-6850

Task 9 - Detailed Circuit Failure Analysis

71111.21N.05

Calculations

C-FP-013.10-022

Detailed Fire Modeling - Fire Compartment F-01

71111.21N.05

Calculations

C-FP-013.10-045

Fire Compartment E-01, No. 1 Auxiliary Feedwater Pump

Room

71111.21N.05

Calculations

C-NSA-064.02-

2

Davis-Besse Appendix R Overheating Summary Report

71111.21N.05

Calculations

C-NSA-064.02-

033

Davis-Besse Appendix R Overcooling Summary Report

& A01

71111.21N.05

Calculations

FEM-021-01

Turbine Building Elevation 603 Sprinkler System

71111.21N.05

Calculations

FEM-021-02

Turbine Building Elevation 603 Sprinkler System

71111.21N.05

Calculations

PRA-DB1-17-021

PRA Input to Fire Risk Evaluation for Compartment E-01

71111.21N.05

Corrective Action

Documents

2005-05472

Fire Protection 5 Year Flow Test Results do not Meet

Acceptance Criteria

2/30/2005

71111.21N.05

Corrective Action

Documents

2008-40704

Fire Protection 5 Year Flow Test Results do not Meet

Acceptable Range for C Value

06/21/2008

71111.21N.05

Corrective Action

2014-12504

Fire Protection: 5-Year Flow Test Results do not Meet

08/01/2014

Inspection

Procedure

Type

Designation

Description or Title

Revision or

Date

Documents

Acceptable Range for C-Value

71111.21N.05

Corrective Action

Documents

20-03744

MS5889A Steam Admission to Auxiliary Feed Pump Turbine

  1. 1 Valve Dust Boot Separated

04/27/2020

71111.21N.05

Corrective Action

Documents

20-04512

Auxiliary Feed Water Pump 1, PSL106D Failed to Close

MS106, MS106A

05/24/2020

71111.21N.05

Corrective Action

Documents

21-00610

Service Water (SW) 1382, Supply to Auxiliary Feed Water

Pump (AFP) #1, Stroke Time Outside of Expected Range

01/31/2021

71111.21N.05

Corrective Action

Documents

22-02204

Indications on Welding Around Auxiliary Feed Water Pump

Trip (AFPT) #2 Valve Seat

03/15/2022

71111.21N.05

Corrective Action

Documents

22-02209

Indications on Welding Around AFPT #1 Valve Seat

03/15/2022

71111.21N.05

Corrective Action

Documents

22-02236

AFPT 1 Governor DB-ICS38B: Crank Pivot Pin Boss

Extends Out of Fulcrum Support Preventing Jam Nut

Contact

03/15/2022

71111.21N.05

Corrective Action

Documents

22-05577

Missed Surveillance FP4023-018

08/15/2022

71111.21N.05

Corrective Action

Documents

22-05675

Fire Protection 5-year Flow Test Results do not Meet

Acceptable Range for C Value

07/21/2022

71111.21N.05

Corrective Action

Documents

22-05857

22 Fire Protection Team Inspection Self-Assessment -

Performance Monitoring Program

08/26/2022

71111.21N.05

Corrective Action

Documents

22-07575

North Underground Fire Protection Loop Pipe Rupture

10/09/2022

71111.21N.05

Corrective Action

Documents

22-12602

DB-FP-04023 Attachment 25 - Barriers Need Moved to

45

10/12/2022

71111.21N.05

Corrective Action

Documents

Resulting from

Inspection

22-07442

22 Fire Protection Inspection (FPI) - Fire Hazards

Analysis Report (FHAR) Contains Incorrect Non Power

Operations (NPO) Compliance Summary

10/04/2022

71111.21N.05

Corrective Action

Documents

Resulting from

Inspection

22-07489

22 NRC FPI - Fire Protection Expert Software Issue

10/06/2022

71111.21N.05

Corrective Action

Documents

22-07499

22 NRC Fire Protection Inspection - Fire Protection Piping

Corrosion and Coating Degradation

10/06/2022

Inspection

Procedure

Type

Designation

Description or Title

Revision or

Date

Resulting from

Inspection

71111.21N.05

Corrective Action

Documents

Resulting from

Inspection

22-07920

22 NRC Fire Protection Inspection: Inaccurate

Information Provided in Response to NRC Question

10/19/2022

71111.21N.05

Corrective Action

Documents

Resulting from

Inspection

22-07930

22 NRC FPI - Implementation of NPO does not Account

for All Key Safety Functions

10/19/2022

71111.21N.05

Drawings

E-44B Sheet 14B

Elementary Wiring Diagram Feed Water System Auxiliary

Feed Water Pump (AFP) Discharge to Steam Generator

71111.21N.05

Drawings

M-0006D

Auxiliary Feedwater System

71111.21N.05

Drawings

M-0007B

Piping & Instrument Diagram Steam Generator Secondary

System

71111.21N.05

Drawings

M-309AQ-00004-

0001

Installation Drawing Modulating Valve Models 87J-001 &

87J-002

71111.21N.05

Engineering

Evaluations

200-0213-RPT-

001

Evaluation of High Emergency Diesel Generator 1-1 Voltage

at Davis-Besse

71111.21N.05

Engineering

Evaluations

ARS-DB-13-071

Davis-Besse General VFDR Report

71111.21N.05

Engineering

Evaluations

ARS-DB-17-111

Fire Risk Evaluation of No. 1 Auxiliary Feedwater Pump

Room (E-01)

71111.21N.05

Engineering

Evaluations

ARS-DB-17-112

Fire Risk Evaluation of No. 2 Auxiliary Feedwater Pump

Room (F-01)

71111.21N.05

Miscellaneous

Fire Hazard Analysis Report

03/31/2021

71111.21N.05

Miscellaneous

Davis-Besse Nuclear Power Station NFPA 805 Nuclear

Safety Capability Assessment Report

71111.21N.05

Miscellaneous

Davis-Besse 1R22-1: Contingency Plan for Reactor Coolant

System (RCS) Drain Below Flange Level and Operation

Below 80 Inches Above the RCS Hot Leg Centerline

03/07/2022

71111.21N.05

Miscellaneous

Davis-Besse 1R21-1: Contingency Plan for RCS Drain

Below Flange Level and Operation Below 80 Inches Above

the RCS Hot Leg Centerline

2/11/2020

Inspection

Procedure

Type

Designation

Description or Title

Revision or

Date

71111.21N.05

Miscellaneous

ARS-DB-13-071

Davis-Besse General VFDR Report

71111.21N.05

Miscellaneous

ATL-2021-0118-

ATA-23

DB-1908: NPO Implementation Plan

2/25/2021

71111.21N.05

Miscellaneous

BOP-VT-16-124

Visual Test (VT)-1 of Internal Surfaces: P14-1 Lube Oil

Cooler

04/25/2016

71111.21N.05

Miscellaneous

LRAMR-M06

Aging Management Review of the Auxiliary Feedwater and

Condensate Storage Systems

71111.21N.05

Miscellaneous

OPS-JPM-130

Non-Licensed Operator (NLO), Reactor Operator (RO),

Senior Reactor Operator (SRO) - Actions for a Serious

Station Fire, Area F

11/11/2006

71111.21N.05

Procedures

DB-FP-00007

Control of Transient Combustibles

71111.21N.05

Procedures

DB-FP-00018

Control of Ignition Sources

71111.21N.05

Procedures

DB-FP-04035

Year Flow Test

71111.21N.05

Procedures

DB-OP-02501

Serious Station Fire

24, 26 & 28

71111.21N.05

Procedures

DB-OP-02519

Serious Control Room Fire

& 28

71111.21N.05

Procedures

DB-OP-02529

Fire Procedure

71111.21N.05

Procedures

DB-OP-02802

Serious Station Fire - Generic Train 2 Affected

71111.21N.05

Procedures

DBBP-OPS-1113

Control of Time Sensitive Operator Actions

71111.21N.05

Procedures

LRPD-05

2.11

Aging Management Program Evaluation Results -One Time

Inspection Program

71111.21N.05

Procedures

LRPD-05

2.8a

Aging Management Program Evaluation Results -Fire Water

Program

71111.21N.05

Procedures

LRPD-05

2.8b

Aging Management Program Evaluation Results -Fire

Protection Program

71111.21N.05

Procedures

NG-DB-00117

Shutdown Defense in Depth Assessment

71111.21N.05

Procedures

NG-DB-00302

DBNPS Fire Protection Program

71111.21N.05

Procedures

NOBP-OM-2031

Outage Management Scheduling Process

71111.21N.05

Procedures

NOBP-OP-1113

Control of Time Sensitive Operator Actions

71111.21N.05

Procedures

NOP-OP-1005

Shutdown Defense in Depth

71111.21N.05

Procedures

NOP-OP-1007

Risk Management

71111.21N.05

Self-Assessments ATL-2018-2226-

ATA-141

22 Fire Protection Self Assessment

08/10/2022

71111.21N.05

Work Orders

200759717

FP4035-001 04.000 5 Year Flow Test

07/21/2022

Inspection

Procedure

Type

Designation

Description or Title

Revision or

Date

71111.21N.05

Work Orders

200761805

FP4023-03104.000 Attachment 8 Barrier Visual Inspection

Month

10/03/2021

71111.21N.05

Work Orders

200775095

FP4023-018 04.000 Attachment 25 Barrier Visual Inspection

Month

06/28/2022

71111.21N.05

Work Orders

200785600

FP4036-001 04.000 Fire Door 18 Month Inspection

07/23/2021

71111.21N.05

Work Orders

200800008

FP4049-001 05.000 P5-2 Diesel Fire Pump Test

07/21/2022

71111.21N.05

Work Orders

200809818

FP4047-002 05.000 P5-2 Diesel Fire Pump Test

01/19/2022

71111.21N.05

Work Orders

200810087

FP4048-003 04.5.1 P5-1 Electric Fire Pump Lube Oil

Sample

2/04/2021

71111.21N.05

Work Orders

200810300

FP4048-002 P5-1 Electric Fire Pump Local

05/22/2022

71111.21N.05

Work Orders

200810301

FP4050-001 04.000 P5-1 Electric Fire Pump Flow Test

09/24/2021

71111.21N.05

Work Orders

200816116

Functional Location DB-T81 Fire Water Storage Tank TK 1-

04/10/2022

71111.21N.05

Work Orders

200828720

FP4048-004 04.001 P5-1 Electric Fire Pump 15 Minimum

Run

07/14/2022

71111.21N.05

Work Orders

200828735

FP4048-001 04.002 P5-1 Electric Fire Pump Remote

09/06/2022

71111.21N.05

Work Orders

200830264

FP4048-003 04.5.1 P5-1 Electric Fire Pump Lube Oil

Sample

08/13/2022

71111.21N.05

Work Orders

200831519

FP4047-002 05.000 P5-2 Diesel Fire Pump Test

08/31/2022