ML20217K844

From kanterella
Jump to navigation Jump to search
Submits Revised Commitment to NRC Bulletin 90-01,Suppl 1 for Hope Creek Generating Station
ML20217K844
Person / Time
Site: Hope Creek PSEG icon.png
Issue date: 10/15/1999
From: Salamon G
Public Service Enterprise Group
To:
NRC OFFICE OF INFORMATION RESOURCES MANAGEMENT (IRM)
References
IEB-90-001, LR-N99424, NUDOCS 9910260271
Download: ML20217K844 (2)


Text

1 m,' .

I

, Publip Service Electric and Gas Cornpany P.O. Box 236 Hancocks Bridge, New Jersey 08038 0236 1 Nuclear Business Unit OLT15 agg l l

LR-N99424 I

United States Nuclear Regulatory Commission j Document Control Desk l I

Washington, DC 20555.

REVISED COMMITMENT TO NRC BULLETIN 90-01, SUPPLEMENT 1 HOPE CREEK GENERATING STATION l FACILITY OPERATING LICENSE NPF-57 l DOCKET NO. 50-354

)

l Gentlemen: l In accordance wit'i he t Nuclear Energy Institute (NEI) process for managing NRC commitments ann assc&'ed NRC notification, this correspondence is being submitted to' discuss a commitment that has been changed, but has not previously been reported.

This revised commitment was not included in 1998 Summary of Revised Regulatory )

Commitments for Hope Creek that was submitted on February 22,1999. The commitment was evaluated in accordance with the NEl guidance in 1998, and the commitment change was implemented; however, the Commitment Change Evaluation Summary Form was not processed correctly at that time. )

In response to NRC Bulletin 90-01, Supplement 1, " Loss of Fill-Oil in Transmitters Manufactured By Rosemount", Public Service Electric and Gas committed to perform an Enhanced Monitoring Program for 264 safety related and 1 non-safety related ,

Rosemount 1153 transmitters at Hope Creek. The Enhanced Monitoring Program l includes drift monitoring, transient response monitoring, Technical Specification  :

required channel checks, and process noise monitoring (as required).

NRC Bulletin 90-01, Supplement 1, establishes criteria that allows Rosemount 1153 transmitters to be excluded from the Enhanced Monitoring Program. Based on the trending data, the Rosemount 1153 transmitters in the Enhanced Monitoring Program C at Hope. Creek satisfy the criteria to be excluded from the Enhanced Monitoring Program. Therefore, Hope Creek has eliminated the dr". monitoring portion of the Enhanced Monitoring Program. The other aspects of the Enhanced Monitoring Program remain in effect. Wl 9910260271 991015 PDR ADOCK 05000354 O PDR

r< .u

,- Thepw/erisinyour}mKk 95 2168 REV 6,N

Y, ,$ ,

L L Docurnent Control Dcsk 2- $T1$ gg !

LR-N99424 l

If you have any questions or comments on this transmittal, please contact Robin L Ritzman at (856) 339-1445.

l l

!. Sincerely,

/

r

%c Gabor Salamon i Licensing Manager l

l. 1 o

l l- ' c: Mr. Hubert J. Miller, Administrator- Region I L. U. S. Nuclear Regulatory Commission

. 475 Allendale Road l l King of Prussia, PA 19406 l - ,

l Mr. R. Ennis, Licensing Project Manager l

! U. S. Nuclear Regulatory Commission One White Flint North Mail Stop 881 11555 Rockville Pike Rockville, MD 20852 USNRC Senior Resident inspector (X24)

Hope Creek Generating Station l

Mr. K. Tosch, Manager, IV Bureau of Nuclear Engineering PO Box 415 Trenton, NJ 08625 RAR/

u-