ML20209C446

From kanterella
Jump to navigation Jump to search

Forwards Safety Evaluation Re Tech Spec Mod to Change Limiting Condition for Operation of Fire Suppression Water Sys Based on 830523 Request.Proposed Changes Approved
ML20209C446
Person / Time
Site: Diablo Canyon 
Issue date: 09/15/1983
From: Johnston W
Office of Nuclear Reactor Regulation
To: Novak T
Office of Nuclear Reactor Regulation
Shared Package
ML16340C148 List: ... further results
References
FOIA-86-151 TAC-52310, NUDOCS 8309230508
Download: ML20209C446 (5)


Text

L67i A

a. !.

,e.

' l wr:

,. r

%y

)

SEP 15 983 1

Docket No. 50-275 MEl10RANDUM FOR:

Thomas Novak, Assistant Director for Licensing Division of Licensing FROM:

William V. Johnston, Assistant Director Materials, Chemical & Environmental Technology Division of Engineering

SUBJECT:

TECHNICAL SPECIFICATIONS MODIFICATION FOR DIABLO CANYON UNIT 1 (TAC NO. 52310)

By letter dated May 23, 1983, the licensee requested the following amend-ments to the Diablo Canyon Unit 1 Technical Specifications:

1.

Change the limiting condition for operation of the fire suppression water system to require that both high pressure fire pumps be operable, and 2.

Clarify the surveillance requirements for the halon fire suppres-sion system regarding the need to replace the explosive initiator.

Based on our evaluation, we conclude that the licensee's proposed changes to the Technical Specifications should be approved.

Y Y

WilliamV.Jo(st/n ssistant Director Materials, Chemical & Environmental Technology Division of Engineering

Enclosure:

As stated cc:

R. Vollmer S. Pawlicki D. Eisenhut T. Wambach V. Benaroya T. Sullivan R. Fer uson F. Rosa M. Srinivasan l

J. Wilson AEOD

0. Parr P. Sternberg, Reg. V 1

Contact:

D. J. Kubicki X27743 U bhbh7g.

E

l s

')

Enclosure

+

,}

Chemical Engineering Branch / Fire Protection Section i

Safety Evaluation Report j

Technical Specifications Modification Diablo Canyon Unit 1 Docket No. 50-275 Int'roduction By letter dated May 23, 1983, the licensee requested the following two.

amendments to the Diablo Canyon Unit 1 Technical Specifications:

1.

Change the limiting condition for operation of the fire suppression water system (Section 3.7.9.1) to require that both high pressure fire pumps be operable.

The licensee justified this change because it provides greater assurance of system availability during a single l

failure event.

2.

Change the surveillance requirements for the halon fire suppression system (Section 4.-7.9.4c) to require replacement of the explosive initiator prior to expiration of its service life, i.e., within i

5 years of the date of manufacture.

The licensee justified this change on the basis that the existing sur-veillance requirement is not achievable.

l t

Evaluation Section 3.7.9.1 previously required at least one operable high pressure pump.

However, the licensee identified the need for a greater quantity of water to supply anticipated fire fighting requirements.

Therefore, one pump may not be able to meet this need, depending on the demand from manual hose streams and automatic fire suppression systems.

Con-sequently, the limiting condition for operation will be changed to t

require that two high pressure pumps be operable.

We conclude that this change will provide greater assurance that the required quantity of water for fire fighting will be available and, therefore, is acceptable.

4 1

Section 4.7.9.4 previously required that explosive initiators in the Halon system be replaced at least once per 5 years with initiators 'that have a remaining service life of at least 5 years.

However, the maximum service life of all initiators is 5 years from the date of manufacture.

Therefore, considering storage, shipping and other normal time delays, it is not possible to literally comply with this sur-veillance requirement.

The intent of this requirement is to assure that initiators are not being used beyond their service life.

The licensee's proposed modification will stipulate that initiators are replaced prior to expiration of the service life and is, therefore, acceptable.

l Conclusion Based on our evaluation, we conclude that the licensee's proposed changes to the Technical Specifications should be approved as proposed.

The revised Technical Specifications are shown in the attachments.

I l

i l

-.-...--,.-,,-,.-e,.-

--,---,-------,---,--,,---,,-.w,


s

-- ~~---- - - - - - - - ~ - - - - - - - - - - * - - ~ = ~ - ' - ~ ' - - - - - - ~ " '

q*

ATTACHMENT I

)

Page 2 of 2 PLAN 1 SYSTEMS Y 3/4.7.9 FIRE SUPPRESSION SYSTEMS FIRE SUPPRESSION WATER SYSTEM LIMITING CONDITION FOR OPERATION 3.7.9.1 The fire suppression water system shall be OPERABLE with; f each two s-At least +ne high pressure pump, with a capacity of 2250 gpm, taking a.

suction from the firewater tank containing a minimum usable volume of 270,000 g'allons, with its discharge aligned to the fire suopression* header.

Gravity feed to the fire suppression header from a raw water reservior b.

with a minimum usable volume of 270,000 gallons.

An OPERABLE fire suppression header flow path through distribution c.

piping with OPERABLE sectionalizing control or isolation valves to the yard hydrant curb valves, the last valve ahead of the water flow alarm d_evice on each sprinkler, hose standpipe or spray system riser required to be OPERABLE per specifications 3.7.9.2 and 3.7.9.5.

APPLICABILITY:

At all times.

ACTION:

With either ee pump and its water supply or the raw water gravity a.

. feed water supply inoperable, restore the inoperable equipment to OPERABLE status within 7 days or, in lieu of any other report required by specification 6.9.1, prepare and submit a Special Report to the Commission p0rsuant to Specification 6.9.2 within the next 30 days outlining the plans and procedures to be used to restore the inoperable equipment to OPERABLE status or to provide an alternate backup pump or supply.

The provisions of Specifications 3.0.3 and 3.0.4 are not applicable.

b.

With the fire suppression water system otherwise inoperable:

1.

Establish a backup fire suppression water sysi.em within 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />, and 2.

In lieu of any other report required by Specification 6.9.1, submit a Special Report in accordance with Specification 6.9.2; a)

By telephone within 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />, b)

Confirmed by telegraph, mailgram or facsimile transmission no later than the first working day following the event, and c)

In writing within 14 days following the event, outlining the action taken, the cause of the inoperability and the plans and schedule for restoring the system to OPERA 3LE status.

"Except the suppression header check valve bypass valves shall be closed unless the gravity feed to the suppression header is inoperable

, or inadequate to supply the system for fire protection purposes.

DIABLO CANYON - UNIT 1 3/4 7-36 r

g-a w,-,n.--

.w.,

..e

  • 1 ELANT SYSTEMS 2

Hkl0NSYSTEM LIMITING CONDITION FOR OPERATION t

3.7.9.4 The Protection and Safeguards Actuation System Room Halon System shall be OPERABLE.

APPLICABILITY: Whenever equipment protected by the Halon system is required to be OPERABLE, ACTION:

With the above required Halon system inoperable, within one hour a.

establish a continuous fire watch with backup fire suppression equip-ment for those areas in which redundant systems or components could ce damaged.

Restore the system to OPERABLE status within 14 days or, in li.eu of any other report required by Specification 6.9.1, prepare and submit a Special Report to the Commission pursuant to Specifica-tion 6.9.2 within the next 30 days outlining the action taken, the cause of the inoperability and the plans and schedule for restoring the system to OPERABLE. status.

b.

The provisions of Specifications 3.0.3 and 3.0.4 are not applicable.

SURVEILLANCE REQUIREMENTS 4.7.9.4 The above required Halon system shall be demonstrated OPERABLE:

At least once per 6 months by verifying Halon storage tank weight to a.

be at least 95% of full charge weight and pressure to be be at least 90% of full charge pressure.

b.

At least once per 18 months by:

1.

Verifying the system, including associated ventilation dampers, actuates manually and automatically, upon receipt of a simulated test signal.

2.

Performance of.a flow test through headers and nozzles to assure no blockage.

l c.

^t 1:::t :n:: p:r 5 y::r: by geplacement of the explosive initiator

.with an explosive initiator f7om a certified manufacturing lot **4 I

dich 5:: : 7:::i 'n;; ::rvi:: lif: ef :t 1:::t 5 j::r:.

&t :

prior to the expiration of its service life aM Et 10:st cr.cc per 5 yearsgz%

ou, 9.=w. -

}

DIABLO CANYON - UNIT 1 3/4 7-42 9