o WOLF CREEK GEtERATING STATION DOCKET NO: 50-482 FACILITY OPERATING LICENSE: IFF-42 ABNRL StBemRY W SAFETY EVAIBhTIGIS REPORT NO: 2 .
REPORT PERIOD: JANUARY 1, 1986 to DECEMBER 31, 1986 ,
Subnitted by:
Wolf Creek Nuclear Operating Corporation G7031 BOO 2B 870311 2 PDR ADOCK 0500 ,
R
i o ,
Annual Sumary of Safety Evaluations This report contains a sumary of safety evaluations on proposed changes, tests, and experiments performed pursuant to 10CFR 50.59(a) during 1986.
This report is being subnitted in accordance with the requirements of 10CFR
- 50. 59 (b) .
- 1. Proposed FSAR, Appendix 3A, Section 5.8.2.4, revision - Originated to allow the use of state-of-the-art digital multifrequency eddy current inspection of steam generator tubing. tb unreviewed safety or environmental questions are generated as a result of this FSAR revision.
- 2. Proposed FSAR, Section 4.2.4.2.C.2, revision - Originated to allow fuel rod weld enclosures to be nondestructively examined by a qualified method (e.g. x-ray, ultrasonics, etc.) in accordance with Westinghouse specifications. Ib unreviewed safety or environmental questions are generated as a result of this FSAR revision.
- 3. Proposed FSAR, Sections 4.3.2.7.5, 4.3.2.3.1, 4.3.3.3, 4.3.4 and Table 4.1-2, revision - Originated to change the reload design methodology by modifying the nuclear physics W PALADON code in order to improve agreement between the nodal (PALADON) and fine mesh diffusion theory ('IORTISE) calculations. No unreviewed safety or environmental questions are generated as a result of this FSAR revision.
- 4. Proposed FSAR, Sections 6.2.1.5 and 15.6.5, revision - Originated to revise the large break WCA analysis based upon performance of the approved Westinghouse 1981 DOCS evaluation nodel with BART code to satisfy WCGS Operating License condition 2.C.12. tb unreviewed safety or environmental questions are generated as a result of this FSAR revision.
- 5. Proposed FSAR, Section 11.4, revision - Originated to make chapter 11 consistent with current regulations by including references to 10CFR 61, 10CFR 71 and 49CFR 173. Also, a description of the bulk waste disposal station is added. Ib unreviewed safety or environmental questions are generated as a result of this FSAR revision.
- 6. Proposed FSAR, Table 13.1-1 and Figure 13.2-1 Sheets 1-6, revision
- Originated to delete the requirement for the Superintendent of Operations to maintain an SRO License. Ib unreviewed safety or environmental questions are generated as a result of this FSAR revision.
- 7. Proposed FSAR, Section 15.4.6.2, revision - Originated to reflect bounding boron concentration safety analysis parameters in support of cycle 2 design and all future reloads. Also, several assumptions are rewritten to reflect the changes in initial / critical boron concentrations. tb unreviewed safety or environmental questions are generated as a result of this FSAR revision.
- 8. Proposed FSAR, Section 15.7, revision - Originated to allow fuel handling operations without running the hydrogen mixing fans and containment coolers. No unreviewed safety or environmental questions are generated as a result of this FSAR revision.
- 9. WCGS Cycle 2 10CFR50.59 Evaluation - Originated to evaluate the FSAR chapter 15 events with the Cycle 2 reload design. No unreviewed safety or environmental questions are generated as a result of this evaluation.
- 10. Plant Modification Request 00307 - Originated to replace certain breakwire detectors with steel grating. No unreviewed safety or environmental questions are generated as a result of this plant modification.
- 11. Plant Modification Request 00354, revisions 0 through 4 -
Originated to provide an all weather surface and pads to support cranes and vendor trailers east of the Reactor Building. A service drive and electrical power supplies will be provided to support the known needs of this area during refueling outages and Post Tension System inspection activities. No unreviewed safety or environmental questions are generated as a result of this plant modification.
- 12. Plant Modification Request 00378, revisions 0 through 2 -
Originated to provide a method to transport the filter transfer cask from the Auxiliary Building filter /demineralizer room to the filter drop area of the Radwaste Building. No unreviewed safety or environmental questions are generated as a result of this plant rmdification.
- 13. Plant Modification Request 00415, revision 1 - Originated to clarify that air flow measurement should comply with ANSI standard on this PMR, which changes the method for measuring the air flow during a filtration leakage test on the Fuel Building filtration system FGG02B. No unreviewed safety or envirormental questions are generated as a result of this plant modification.
- 14. Plant Modification Request 00428, revisions 7 through 9 -
Originated to provide changes to construction detail for this PMR, which provides office space for the simulator instructors at the Education Center. No unreviewed safety or environmental questions are generated as a result of this plant modification.
- 15. Plant Modification Request 00441, revisions 3 through 5 -
Originated to provide changes to construction detail for this PMR, which provides Control Room annunciation of:
(1) ESFAS not in normal operating mode, (2) RCP upper bearing lube oil reservoir level, and (3) ERFIS initiate.
No unreviewed safety or environmental questions are generated as a result of this plant modification.
Page 2 of 39
F
.9 9 *
- 16. Plant Modification Request 00489, revisions 0 and 1 - Originated to secure the remote radiator for the Daergency Offsite Facility emergency diesel to its concrete pad. No unreviewed safety or environmental questions are generated as a result of this plant modification.
- 17. Plant Modification Request 00536 - Originated to relocate the emergency trip valve for the hydrogen seal oil unit fire protection system, tb unreviewed safety or environmental questions are generated as a result of this plant modification.
- 18. Plant Modification Request 00540, revisions 0 and 1 - Originated to provide radiation survey capability of Radwaste and Auxiliary Buildings filters and demineralizers. No unreviewed safety or environmental questions are generated as a result of this plant modification.
- 19. Plant Modification Request 00574, revision 1 - Originated to provide a written safety evaluation for this PMR which changes the piping to the level transmitters for the Solid Radwaste System caustic and acid addition tanks. No unreviewed safety or environmental questions are generated as a result of this plant modification.
- 20. Plant Modification Request 00590, revision 1 - Originated to allow the use of existing junction boxes to house the splices for the high temperature pigtails running to the 12 Steam Dump Velves, AB HY034 thru AB HYO45. Ib unreviewed safety or environmental questions are generated as a result of this plant modification.
- 21. Plant Modification Request 00639 - Originated to provide an interconnection for sample lines IIB-ll2-IIXD-3/4" and HB-ll3-IlXD-3/4" to allow for more effective and easier sampling. tb unreviewed safety or environmental questions are generated as a result of this plant modification.
- 22. Plant Modification Request 00657, revisions 1 through 3 -
Originated to change the method of attachment of the diaphram to the Boric Acid Tanks. tb unresiewed safety or environmental questions are generated as a result of this plant modification.
- 23. Plant Modification Request 00664, revisions 1 and 2 - Originated to change the insulation specification on the Chemical and Volume Control heat exchanger SBG02 heads. No unreviewed safety or environmental questions are generated as a result of this plant nodification.
- 24. Plant Modification Request 00692, revision 1 - Originated to provide a safety evaluation for this PMR, which relocates a drain pipe to allow clearance for Floor and Equipment Drain System float ball LF LE010 which may execute full travel. No unreviewed safety or environmental questions are generated as a result of this plant modification.
Page 3 of 39
r
- 25. Plant Modification Request 00698, revision 1 - Originated to provide a safety evaluation to this PMR, which allows closing the nitrogen to steam generator blowdown isolation valve EP V079 when this blowdown is not reeded to prevent overpressurizing EP PIC-1 sensing bourdon tube. No unreviewed safety or environmental questions are generated as a result of this plant modification.
- 26. Plant Modification Request 00701, revision 2 - Originated to add FSAR Figure 1.2-13 to this PMR, which provides storage for spare Reactor Vessel head O-rings. No unreviewed safety or environmental questions are generated as a result of this plant modification.
- 27. Plant Modification Request 00705 - Originated to change appropriate sections and drawings in the FSAR so that number 7 transformer in the Wolf Creek substation switchyard (installed by PMR 00858) may be utilized to supply the ESF transformer number
- 1. No unreviewed safety or environmental questions are generated as a result of this plant modification.
- 28. Plant Modification Request 00722, revision 1 - Originated to allow an additional 2 percent tolerance to the resistance value for Gould-shawmuts fuses to allow for metering inaccuracies. No unreviewed safety or environmental questions are generated as a result of this plant modification.
- 29. Plant Modification Request 00726, revision 1 - Originated to add a proposed Technical Specification change to this PMR, which replaces the steam generator pipe accelerometer with one having a Sg range. No unreviewed safety or environmental questions are generated as a result of this plant modification.
- 30. Plant Modification Request 00766 - Originated to install a switch on the Reactor Operator desk which will allow connecting Gaitronics line 5 directly to the page, so the Control Room personnel may monitor refueling operations. No unreviewed safety or environmental questions are generated as a result of this plant modification.
- 31. Plant ibdification Request 00789, revisions 5 and 6 - Originated to provide larger pans with notching to remove interference with MSIV platforms to this PMR which provides drip pam for the Main Steam Isolation Valves and Main Feedwater Isolation Valves to keep leaking oil from soaking the insulation. No unreviewed safety or environmental questions are generated as a result of this plant modification.
- 32. Plant Modification Request 00791, revision 1 - Originated to modify the Engineered Safety Features Actuation System Beta Tone III alarm cards to accomodate a new type IC, since the original IC is no longer available. No unreviewed safety or environmental questions are generated as a result of this plant modification.
Page 4 of 39
- 33. Plant Modification Request 00804, revisions 1 through 4 -
Originated to provide quick disconnect of the CRDM ventilation ductwork. No unreviewed safety or environmental questions are generated as a result of this plant modification.
- 34. Plant Modification Request 00810, revision 1 - Originated to provide a safety evaluation for the PMR, which corrects the cable schemes on drawing E-03SA18 to agree with the schematic details on drawings E-13GK01A and E-13GK01B. No unreviewed safety or environmental questions are generated as a result of this plant modification.
- 35. Plant Modification Request 00830 - Originated to reduce the sample volume for the failed fuel monitor. No unreviewed safety or environmental questions are generated as a result of this plant modificatlon.
- 36. Plant mdification Request 00841, revision 1 - Originated to correct a drawing to reflect the part number change in the PMR, for a Trans America Delaval 4-20 MA D.C. converter. No unreviewed safety or environmental questions are generated as a result of this plant modification.
- 37. Plant Modification Request 00848, revision 1 - Originated to provide a safety evaluation for the PMR, which changes a part number for a Solid Stat.e Controls 480/120 volt, single phase, regulating transformer. No unreviewed safety or environmental questions are generated as a result of this plant nodification.
- 38. Plant Modification Request 00852, revision 1 - Originated to provide a safety evaluation for the PMR, which relocates the bellows seals for the Recycle Evaporator and Waste Evaporator to facilitate calibration. No unreviewed safety or environmental questions are generated as a result of this plant modification.
- 39. Plant Modification Request 00857, revision 2 - Originated to correct editorial errors on the PMR, which replaces Essential Service Water restraint EF05-R005/1410 No unreviewed safety or environmental questions are generated as a result of this plant modification.
- 40. Plant Modification Request 00858, revisions 1 through 3 -
Originated to install transformer 7 in the Wolf Creek substation switchyard and provide control and indication in the Control Room for this alternate supply to ESF transformer number 1. No unreviewed safety or environmental questions are generated as a result of this plant modification.
- 41. Plant Modification Request 00899, revisions 0 through 11 -
Originated to replace the Safety Injection Accumulator level transmitters with Rosemont transmitters, relocate them with five foot capilaries and provide a permanent platform for access to transmitter EP LT-0954. No unreviewed safety or environmental questions are generated as a result of this plant mcdification.
Page 5 of 39
r
, o- ,
- 42. Plant Modification Request '00904 - Originated to install manual gate valves downstream of ESW check valves EF-V046 and EF-V076 to allow testing the check valves. Ib unreviewed safety or environmental questions are generated as a result of this plant modification.
'43. Plant Modification Request 00915 - Originated to provide access to the Secondary Alarm Station radio console for maintenance. No unreviewed safety or environmental questions are generated as a result of this plant modification.
- 44. Plant Pbdification Request 00990, revisions 0 and 1 - Originated to delete certain annunciator points fran the Balance of Plant computer. %ese points had been reserved for diagnostic purposes, but never utilized. Ib unreviewed safety or environmental questions are generated as a result of this plant modification.
- 45. Plant Modification Request 00991, revisions 0 and 1 - Originated to relocate the instrument taps for differential pressure transmitters for cation bed and mixed bed demineralizers, reactor coolant filter and boric acid filter. No unreviewed safety or environmental questions are generated as a result of this plant modification.
- 46. Plant Modification Request 00999 - Originated to provide a fence to run fran the Reactor Building to the Diesel Generator building, around the Radwaste building. W e area inside the fence will become a Radiation Controlled Area. tb unreviewed safety or environmental questions are generated as a result of this plant modification.
- 47. Plant Modification Request 01000 - Originated to convert a locker room in the Shop Building into office space. No unreviewed safety or environmental questions are generated as a result of this plant modification.
- 48. Plant Modification Request 01005, revision 1 - Originated to provide a safety evaluation for the PMR, which provides an insulation specification for a 24"/20" reducer on the suction of Main Feedwater Pump 'A'. No unreviewed safety or environmental questions are generated as a result of this plant modification.
- 49. Plant Modification Request 01006 - Originated to add an Oil Mist Eliminator, FANO3, in the discharge line of the Degasifier Vacuum Pumps, CAN0lA and B, in order to improve the reliability of the Condenser Air Removal Radiation Monitor, GE RE-92. No unreviewed safety or environmental questions are generated as a result of this modification.
- 50. Plant Madification Request 01010, revision 1 - Originated to provide a safety evaluation for the PMR, which approves a part number change for a single pin recorder for the Containment
, hydrogen monitor. No unreviewed safety or environmental questions are generated as a result of this plant modification.
Page 6 of 39
F'
~
- 51. Plant Modification Request 01013, revision 1 - Originated to provide a safety evaluation for the PMR, which corrects Specification 10466-M-162D for two spool pieces in the steam generator blowdown piping. Ib unreviewed safety or environmental questions are generated as a result of this plant modification.
- 52. Plant Modification Request 01027, revision 1 - Originated to provide a safety evaluation for the PMR, which accepts readings taken on the clearance between the stuffing box and shaft of 'A' Centrifugal Charging Pump. No unreviewed safety or environmental questions are generated as a result of this plant modification.
- 53. Plant Modification Request 01083, revisions 0 and 1 - Originated to provide a linear scale on the Reactor Coolant Pump seal flow indicators. Ib unreviewed safety or environmental questions are generated as a result of this plant modification.
- 54. Plant Modification Request 01099, revisions 1 through 3 -
Originated to change the insulation specifications and revise the safety evaluation to the PMR, which nodified the containment coolers. Ib unreviewed safety or environmental questions are generated as a result of this plant modification.
- 55. Plant Modification Request 01106 - Originated to provide a circuit for testing the relays which control the pressurizer power operated relief valves. Ib unreviewed safety or environmental questions are generated as a result of this plant modification.
- 56. Plant Modification Request 01143, revisions 0 through 2 -
Originated to encapculate the hinge pins on the feedwater check valves to the steam generators. Ib unreviewed safety or environmental questions are generated as a result of this plant modification.
- 57. Plant Modification Request 01149, revisions 0 and 1 - Originated to provide larger reservoirs for the MSIV's and MFIV's. No unreviewed safety or environmental questions are generated as a result of this plant modification.
- 58. Plant Modification Request 01152, with revisions 1 through 16 -
Originated to reduce the false and nuisance alarm rate on the Security. perimeter zones. No unreviewed safety or environmental questions are generated as a result of this plant modification.
- 59. Plant Modification Request 01153, with revisions 1 through 4 -
Originated to reduce the falso and nuisance alarm rate on the Security perimeter zones. Ib unreviewed safety or environmental questions are generated as a result of this plant modification.
- 60. Plant Modification Request 21157 - Originated to provide a fire barrier in the floor openings in the Auxiliary Building which provide access to the containment post-tensioning system tendons.
No unreviewed safety or environmental questions are generated as a result of this plant modification.
Page 7 of 39
.. t .
- 61. Plant Modification Request 01186, revision 2 - Originated to change .the paperwork associated with the addition of a permanent nitrogen charging system for the Main Steamline Isolation Valve and Feedwater Isolation Valve nitrogen accumulators. Ib .
unreviewed safety or environmental questions are generated as a result of this plant modification.
- 62. Plant Modification Request 01206, revisions 0 through_2 -
Originated to provide a threaded cap on the blind flange connection for vent valves BG V496, m V206, m v207, m V208 and m V209 to promote venting of the Dnergency Core Cooling System.
No unreviewed safety or environmental questions are generated as a result of this plant modification.
- 63. Plant Modification Request 01233, revisions 1 and 2 - Originated to revise the valving and provide a safety evaluation for the PMR, which replaces the level instruments on the Caustic and Acid Storage Tanks. No unreviewed safety or environmental questions are generated as a result of this plant modification.
- 64. Plant Modification Request 01235, revisions 1 through 4-Originated to improve the comunication systems throughout the power block. No unreviewed safety or environmental questions are generated as a result of this plant modification.
- 65. Plant Modification Request 01250 - Originated to reduce the noise level in the Control Room by reducing the ventilation system air flow. No unreviewed safety or environmental questions are generated as a result of this plant modification.
- 66. Plant Modification Request 01297 - Originated to allow removal of the drive train gears from the mixer for the boron injection surge tank, TEM 02. No unreviewed safety or environmental questions are generated as a result of this plant modification.
- 67. Plant Modification Request 01309, revision 2 - Originated to change the Dnergency Plan communication system. No unreviewed safety or environmental questions are generated as a result of this plant modification.
- 68. Plant Modification Request 01317, revisions 1 and 2 - Originated to revise the FSAR and safety evaluation and correct other documentation for this PMR, which provides better control for the temperature in the EHC cabinet room, room 4504. No unreviewed safety or environmental questions are generated as a result of this plant modification.
- 69. Plant m dification Request 01327, revisions 1 through 3 -
Originated to provide work platforms around the Main Steam Isolation Valves and Main Feedwater Isolation Valves. Ib unreviewed safety or environmental questions are generated as a result of this plant modification.
Page 8 of 39
- 70. Plant ibdification Request 01333, revisions 3 and 4 - Originated to modify the piping, add a safety evaluation and improve the documentation to this PMR, which improves the drainage in the Decontamination System. No unreviewed safety or environmental questions are generated as a result of this plant modification.
- 71. Plant Modification Request 01358, revisions 0 and 1 - Originated to eliminate the Boron Injection Recirculation System (BIRS) annunciators. Since Boron Injection Tank concentration has been reduced to 2000 ppm, the BIRS is no longer required to be in service. Ib unreviewed safety or environmental questions are generated as a result of this plant nodification.
- 72. Plant Modification Request 01363 - Originated to correct the causes of cavitation damage that is occurring in Centrifugal Charging Pump Control Valve, BG FCV-121. No unreviewed safety or environmental questions are generated as a result of this plant modification.
- 73. Plant Modification Request 01373 - Originated to permanently mark the Control Room meter faces to indicate normal operating ranges.
No unreviewed safety or environmental questions are generated as a result of this plant modification.
- 74. Plant Modification Request 01382, revisions 0 and 1 - Originated to replace the Allen Bradley differential pressure switches which are not qualified to IEEE standards with qualified United Electric pressure switches on the Emergency Diesels. No unreviewed safety or environmental questions are generated as a result of this plant modification.
- 75. Plant Modification Request 01395, revisions 4 and 5 - Originated to provide construction details for the PMR, which provides bolted covers on 18 manholes. No unreviewed safety or environmental questions are generated as a result of this plant modification.
- 76. Plant Modification Request 01410, revision 1 - Originated to repair the floor of 'F' traveling screen well at the Circulating Water Screen ibuse. No unreviewed safety or environmental questions are generated as a result of this plant modification.
- 77. Plant ibdification Request 01425 - Originated to provide two spare halon bottles and associated storage racks for the Control Roan halon system. No unreviewed safety or environmental questions are generated as a result of this plant modification.
- 78. Plant Modification Request 01443, revision 2 - Originated to correct the documentation for the PMR, which adds two drains for each drip pan installed on the Main Steam Isolation Valves and Main Feedwater Isolation Valves. Ib unreviewed safety or environmental questions are generated as a result of this plant modification.
Page 9 of 39
g
- 79. Plant bbdification Request 01459 - Originated to revise the oxygen and hydrogen reserve storage bank low pressure switches setpoint to 1900 psig. Ib unreviewed safety or environmental questions are generated as a result of this plant modification.
- 80. Plant !bdification Request 01469 - Originated to extend the shelf life on " COMBS" master controllers for the Polar Crane. tb unreviewed safety or environmental questions are generated as a result of this plant modification.
- 81. Plant Modification Request 01474, revisions 0 through 2 -
Originated to change the number and location of the plant telephones. tb unreviewed safety or environmental questions are generated as a result of this plant modification.
- 82. Plant Modification Request 01477 - Originated to extend the shelf life on Chevron SRI Greese 2. No unreviewed safety or environmental questions are generated as a result of this plant modification.
- 83. Plant Modification Request 01478 - Originated to install a drain valve assembly on the gear boxes for the bridge and trolley drive, main and auxiliary hoists of Polar Crane HKE13 to prevent oil spillage during oil change and to simplify periodic maintenance.
Ib unreviewed safety or environmental questions are generated as a result of this plant modification.
- 84. Plant Modification Request 01482, revisions 0 and 1 - Originated to keep the Boron Dilution Flux Doubling relays operational while other relays are in test. Ib unreviewed safety or environmental questions are generated as a result of this plant modification.
- 85. Plant Modification Request 01502, revisions 0 through 5 -
Originated to provide administrative controls for performance of the first Containment Post-Tensioning System inspection, as required by Technical Specification 4.6.1.6.1. This PMR includes safety evaluations of the work including hoisting and transporting the equipment involved and failure of the hoisting equipment. No unreviewed safety or environmental questions are generated as a result of this plant modification.
- 86. Plant Modification Request 01503 - Originated to revise the drawings to depict the as-built vendor wiring for the condensate demineralizer system caustic heat tracing panel. No unreviewed safety or environmental questions are generated as a result of this plant modification.
- 87. Plant Modification Request 01505 - Originated to replace the carbon steel sample lines for the lime softener precipitator with stainless steel. No unreviewed safety or environmental questions are generated as a result of this plant modification.
- 88. Plant Modification Request 01511 - Originated to provide further instructions for calibrating the field monitor relay for the Circulating Water System. No unreviewed safety or environmental questions are generated as a result of this plant modification.
Page 10 of 39
c .. ,
- 89. Plant Modification. Request 01517~" Originated to change the part number for the body to solenoid seal for the. pressurizer power.
operated, relief valve. No unreviewed safety or environmental questions are generated as a result of this plant modification.
- 90. sPlant Modification Request 01518, revisions 0 and 1 - Originated to change the Diesel Generator' lube oil keep warm pumps.. No '
unreviewed safety or environmental questions are generated as a result of this plant modification.
. 91. Plant Modification Request 01520 - Originated to provide encapsulation of valves BB V082, BB V083 and BB V099 which are experiencing leakage thru the valve packing. No unreviewed safety or environmental questions are generated as a result of this plant modification.
- 92. Plant Modification Request 01533 - Originated to relocate thermal detector KC-XSil-CD-lll-001~to provide maximum fire protection.for the 'Ibrbine Driven Auxiliary Feedwater Pump area. No unreviewed safety or environmental questions are generated as a result of this plant modification.
- 93. Plant Modification Request 01542 - Originated to replace the piston slide assembly-of certain Main Steam Isolation valves and Feedwater Isolation Valves 4-way hydraulic directional control valves. No unreviewed safety or environmental questions are generated as a result of this plant modification.
- 94. Plant Modification Request 01546 - Originated to replace the telykote lubricant with Zeniplex 2 on the hydraulic.4-way directional control' valves for the Main Steam Isolation Valves and .
the Main Feedwater Isolation Valves. No unreviewed safety or environmental questions are generated as a result of this plant modification.
- 95. Plant Modification Request 01547, revisions 0 through 2 -
Originated to allow the temporary use of eight studs and nuts which do not meet the requirements of ASME Boiler and Pressure Vessel Code,1974 Edition, Se tion II, Part A, on valve BG V174.
No unreviewed safety or environwntal questions are generated as a result of this plant modificath ..
- 96. Plant Modification Request 01549 - Originated to provide quick disconnects on valves llA V107 and IIA Vl98 to make it more convenient for obtaining a sample. No unreviewed safety or environmental questions are generated as a result of this plant modification.
- 97. Plant Modification Request 01551 - Originated to provide a manual valve upstream of check valve IIA-V037 in the nitrogen supply line to the Gas Decay Tank header. No unreviewed safety or environmental questions are generated as a result of this plant modification.
4 l
Page 11 of 39
,s , _ _ - _ - _ -
g.., --
- 98. Plant Modification Request 01553 - Originated to allow the temporary use of gaskets installed 30 days after the expiration of their shelf life in three limitorque operations. No unreviewed safety or environmental questions are generated as a result of this plant modification.
- 99. Plant Modification Request 01555 - Originated _ to replace the actuator springs on Auxiliary Feedwater Valves AL IN06, AL IN08, AL IW10 and AL IW12 to prevent development of a hydraulic lock.
No unreviewed safety or environmental questions are generated as a result of this plant modification.
100. Plant Modification Request 01557 - Originated to change the annunciators involving the low pressure alarm setpoints for the accumulators for the Main Feedwater Control Valves, Auxiliary Feedwater Control Valves and Main Steam Atmospheric Relief Valves to enhance system operability. Ib unreviewed safety or environmental questions are generated as a result of this plant modification.
101. Plant Modification Request 01560 - Originated to correct drawings M02KJ03 and M02KJ06 and FSAR figure 9.5.7-1 sheets 1 and 2 to j reflect as-built conditions on the Dnergency Diesels. No unreviewed safety or environmental questions are generated as a result of this plant modification.
102. Plant Modification Request 01562 - Originated to provide a permanent sampling connection for the Refueling Water Storage Tank by connecting tubing and a valve to valve BN V018. No unreviewed safety or environmental questions are generated as a result of this plant modification.
103. Plant Modification Request 01564 - Originated to change the code class for certain valves and piping associated with vent and drain lines on the Oomponent Cooling Water System from ASME Section III to ANSI B31.1 special scope. No unreviewed safety or environmental questions are generated as a result of this plant modification.
104. Plant Modification Request 01566, revisions 0 and 1 - Originated to install fire dampers in the INAC penetrations for Room 1405.
No unreviewed safety or environmental questions are generated as a result of this plant modification.
105. Plant Modification Request 01572 - Originated to verify the acceptability of the as-built Hot Tool Roan for storage of tools, equipment, etc. that are used in the radiologically controlled areas of the plant. No unreviewed safety or environmental questions are generated as a result of this plant modification.
106. Plant Modification Request 01573, revisions 0 through 2 -
Originated to replace 1 1/2" steam generator blowdown piping with 4" schedule 160 piping to reduce erosion. No unreviewed safety or environmental questions are generated as a result of this plant
, modification.
Page 12 of 39 i
107. Plant Modification Request 01574 - Originated to prevent back flow into the Decontamination Exhaust scrubbers drain lines. No unreviewed safety or environmental questions are generated as a result of this plant modification.
'198. Plant Modification Request 01577 - Originated to improve the ventilation frm the Auxiliary Building Sampling Room Exhaust Hood SJ143. 'Ihis change involves the addition of a booster fan in the hood exhaust duct and the rebalancing of the Auxiliary Building ventilation. No unreviewed safety or environmental questions are generated as a result of this plant modification.
109. Plant Mdification Request 01587 - Originated to remove radwaste compactor SHC04 from containment. No unreviewed safety or environmental questions are generated as a result of this plant modification.
110. Plant Modification Request 01591 - Originated to provide storage racks for ladders throughout the plant. No unreviewed safety or environmental questions are generated as a result of this plant modification.
111. Plant Modification Request 01594 - Originated to modify the secondary liquid waste (HF) evaporator system to allow it to process liquid radwaste. No unreviewed safety or environmental questions are generated as a result of this plant modification.
112. Plant Modification Request 01596 - Originated to show valves EF V040 and EF V072 as locked throttled valves to ensure that Essential Service Water flow to each Control Room air conditioner is 140 gpn. No unreviewed safety or environmental questions are generated as a result of this plant modification.
113. Plant Modification Request 01619 - Originated to modify the Recycle Evaporator sample line HE-ll8-HCD-3/4". No unreviewed safety or environmental questions are generated as a result of this plant modification.
114. Plant Ndification Request 01624, revisions 0 through 2 -
Originated to provide a positive means for venting starting air from the rack boost cylinder and associated shuttle valves to prevent potential overspeed shutdown of the emergency diesel engines. No unreviewed safety or environmental questions are generated as a result of this plant modification.
115. Plant Modification Request 01634 - Originated to provide an isolation valve for the Reactor Coolant Drain Tank relief valve.
'Ihe isolation valve would normally be locked open. No unreviewed safety or environmental questions are generated as a result of this plant modification.
116. Plant Modification Request 01639, revisions 0 through 2 -
Originated to provide seal caps on valves BB V8378A and BB V8378B to control bonnet to body leakage. No unreviewed safety or environmental questions are generated as a result of this plant modificatlon.
Page 13 of 39
117. Plant Modification Request 01642, revisions 0 and 1 - Originated to change the-ring setting on the-Main Steam Safety Valves in accordance with NRC Information Notice 86-05. No unreviewed safety or environmental questions are generated as a result of this plant modification. .
118. Plant Modification Request 01643 - Originated to weld repair holes drilled .into the valve body on valve AE V330. No unreviewed s
safety or environmental questions are generated as a result of this plant modification.-
119. Plant Modification Request 01652, revisions e and 1 - Originated to allow replacement of the- 1/3 horsepower vacuum sample pump with one rated at 1/2 horsepower on 10 process radiation monitors.
Certain mechanical and electrical ccaponents were also changed to accommodate the larger pump. No unreviewed safety or
" environmental questions are generated as a result of this plant.
modification.
120. Plant Modification Request 01658 - Originated to allow the use of alternate part numbers on two gaskets for the motor driven -
Auxiliary Feedwater Pumps. No unreviewed safety or environmental '
questions are generated as a result of this plant modification.
121. Plant Modification Request 01663 - Originated to provide an external port connecting the solenoid valve upper port to the chamber above the valve plug on both pressurizer pilot operated relief valves BB PCV-455A and BB PCV-456A. No unreviewed safety or environmental questions are generated as a result of this plant modification.
122. Plant Modification Request 01669 - Originated to increase the maximum stroke times for Auxiliary Feedwater System valves AL HV-30, AL HV-31, AL HV-32 and AL HV-33 from 15 to 18 seconds. No unreviewed safety or environmental questions are generated as a
- result of this plant modification. ,
123. Plant Modification Request 01683, revisions e and 1 - Originated to replace a vendor supplied jumper wire in twelve Limitorque operators. No unreviewed safety or environmental questions are generated as a' result of this plant modification.
124. Plant Modification Request 01702 - Originated to relocate a 6 inch fire protection system check valve. No unreviewed safety or environmental questions are generated as a result of this plant modification.
125. Plant Modification Request 01718 - Originated to add a base station / annunciator to the Secondary Alarm Station console. tb unreviewed safety or environmental questions are generated as a result of this plant modification.
126. Plant mdification Request 01722, revisions 0 through 7 -
Originated to verify and/or modify the motor operated valve switch settings . No unreviewed safety or environmental questions are generated as a result of this plant modification.
Page 14 of 39
127. Plant tbdification Request 01737, revisions 0 and 1 - Originated to provide an electric domestic water heater to supply the sinks and showers in the Health Physics area. It also provides protection against failure of the steam supply valve, KD PCV-2, to the plant domestic hot water heater. tb unreviewed safety or environmental questions are generated as a result of this plant modificatlon.
128. Plant Modification Request 01741 - Originated to modify the Condensate Demineralizer (AK) system acid dilution water piping.
Ib unreviewed safety or environmental questions are generated as a result of this plant modification.
129. Plant Modification Request 01754 - Originated to remove the special instrumentation that was built into Steam Generator "D".
tb unreviewed safety or environmental questions are generated as a result of this plant modification.
130. Plant Modification Request 01790 - Originated to improve the turbine generator trip system reliability and reduce the probability of forced outages. tb unreviewed safety or ,
environmental questions are generated as a result of this plant modification.
131. Plant Modification Request 01791 - Originated to incorporate Westinghouse Field Change Notice SAPM 19728 into the drawings. tb unreviewed safety or environmental questions are generated as a result of this plant modification.
132. Plant Modification Request 01793 - Originated to replace the failed actuator on Control Room air conditioning unit valve GK V765 with one having a different model number. tb unreviewed safety or environmental questions are generated as a result of this plant modification.
133. Plant Modification Request 01796 - Originated to provide for venting entrapped air from the cooling water lines to the Chilled Water system lube oil cooler. Ib unreviewed safety or environmental questions are generated as a result of this plant modificatlon.
134. Plant Modification Request 01818, revisions 0 and 1 - Originated to route the discharge piping for the Auxiliary Feedwater Control / Main Steam Atmspheric Relief Valves Accumulator relief valves to outside. tb unreviewed safety or environmental questions ace generated as a result of this plant nnlification.
135. Plant Modification Request 01820 - Originated to relocate the Condensate Pump discharge sample tap. tb unreviewed safety or environmental questions are generated as a result of this plant modification.
136. Plant ibdification Request 01831 - Originated to identify the proper reference documentation for calibration of the thermocouple / core cooling monitor. tb unreviewed safety or l environmental questions are generated as a result of this plant l modification.
l Page 15 of 39 1
f 137. Plant Mxlification Request 01842, revisions 0 and 1 - Originated to modify the wiring to motor operated valve limit switches. tb unreviewed safety or environmental questions are generated as a result of this plant modification.
138. Plant Modification Request 08143 - Originated to allow the studs, nuts and washers to be left in the Reactor Vessel Head while it is being lifted from the vessel. 16 unreviewed safety or environmental questions are generated as a result of this plant modification.
139. Plant Modification Request 01855 - Originated to allow installation of IIeli-Coils in Steam Generator manway bolt holes.
Ib unreviewed safety or environmental questions are generated as a result of this plant modification.
140. Plant tbdification Request 01864 - Originated to change the part number for replacement diaphragms for Masonellan diaphragms for casing sizes 18 and 9. tb unreviewed safety or environmental questions are generated as a result of this plant modification.
141. Plant Rxilfication Request 01877 - Originated to modify the time delay circuit for starting the Diesel Fire Pump. Ib unreviewed safety or environmental questions are generated as a result of this plant modification.
~
142. Plant Kxlification Request 01879 - Originated to replace the casing drain lines of the Reactor Makeup Water Transfer Pumps with pipe plugs. tb unreviewed safety or environmental questions are generated as a result of this plant modification.
143. Plant Mxlification Request 01886, revisions 0 and 1 - Originated to replace the travel stops for 11/2" Yarway liy-Drop valves. tb unreviewed safety or environmental questions are generated as a result of this plant modification.
144. Plant Modification Request 01888, revisions 0 and 1 - Originated to hard surface an area of Essential Service Water piping that is experiencing erosion. tb unreviewed safety or environmental questions are generated as a result of this plant modification.
145. Plant ibdification Request 01903, revisions 0 and 1 - Originated to repair and hard surface an area of Essential Service Water piping that is experiencing erosion. tb unreviewed safety or environmental questions are generated as a result of this plant modification.
146. Plant Rxlification Request Kt184-044, revisions 0 through 2 -
Originated to replace the heaters in the Fuel Building ventilation system with electric heaters. tb unreviewed safety or environmental questions are generated as a result of this plant modification.
147. Plant ILbdification Request KN84-049 - Originated to provide visual flow verification for the heat exchanger for the diesel fire pump. tb unreviewed safety or environmental questions are generated as a result of this plant modification.
Page 16 of 39
148. Plant Modification Request KN84-051, revisions 1 through 4 -
Originated to improve the Security Building ventilation system.
tb unreviewed safety or environmental questions are generated as a result of this plant modification.
149. Plant Mcxlification Request KN84-057, revisions 1 through 3 -
Originated to provide annunciation of Engineered Safety Features status panel trouble on loss of power, ground fault and panel entry. No unreviewed safety or environmental questions are generated as a result of this plant modification.
150. Plant Modification Request KN84-065, revisions 0 through 2 -
Originated to relocate radiation monitor SD-RE-41 to the Manipulator Crane. No unreviewed safety or environmental questions are generated as a result of this plant modification.
151. Plant Modification Request KN84-071, revisions 1 through 9 -
Originated to provide a Breathing Air System. No unreviewed safety or environmental questions are generated as a result of this plant mdification.
152. Plant Modification Request KN84-075, revision 1 - Originated to install a neutralization system in the water treatment system to neutralize the waste. tb unreviewed safety or environmental questions are generated as a result of this plant modification.
153. Plant Mcxlification Request KN84-076, revisions 0 and 1 -
Originated to install check valves in the Centrifugal Charging Pumps flow path to the Regenerative !! eat Exchanger. No unreviewed safety or environmental questions are generated as a result of this plant modification.
154. Plant Modification Request KN84-079 - Originated to relocate piezameters and settle monuments and install inclinometers on the main dam. No unreviewed safety or environmental questions are generated as a result of this plant modification.
155. Plant Modification Request KN84-088, revisions 0 and 1 - ,
originated to install permanent flow indicators for the Auxiliary Feed Pumps. tb unreviewed safety or environmental questions are generated as a result of this plant modification.
156. Plant Modification Request KN84-089, revisions 0 and 1 -
Originated to provide silicone / fiberglass sleeves on the inboard side of the Chnax connector on Valcor furnished valves. No unreviewed safety or environmental questions are generated as a result of this plant modification.
157. Plant Hodification Request KN84-091 - Originated to replace the Secondary Liquid Waste Evaporator level monitor with an Endress &
llanser ultraconic level instrument. tb unreviewed safety or environmental questions are generated as a result of this plant modification.
Page 17 of 39
158. Plant Modification Request KN85-101, revision 7 - Originated to provide a chlorine injection system for the Essential Service Water System. tb unreviewed safety or environmental questions are generated as a result of this plant modification.
159. Plant Modification Request WO83-ZL004 - Originated to correct excessive erosion damage at the main dam, tb unreviewed safety or environmental questions are generated as a result of this plant modification.
160. Plant Modifcation Request WO84-BB089, revisions 0 through 3 -
Originated to provide annunciation if the RHR system is not properly isolated when RCS pressure is increased, tb unreviewed safety or environmental questions are generated as a result of this plant modification.
161. Plant Modification Request WO84-BG105 - Originated to provide quick disconnects on valves BG V243 and BG V244 to make it more convenient for obtaining a sample. Ib unreviewed safety or environmental questions are generated as a result of this plant modification.
162. Plant Modification Request WO84-CS064, revisions 1 through 6 -
Originated to improve the radio cmmunications throughout the \
power block. tb unreviewed safety or environmental questions are generated as a result of this plant modification.
163. Plant Modification Request WO84-DC069, revision 1 - Originated to assign circuit numbers to the DC system breakers. Ib unreviewed safety or environmental questions are generated as a result of this plant modification.
164. Plant Modification Request WO84-JE075, revisions 1 through 3 -
Originated to provide easier sampling of the Emergency Fuel Oil Storage Tank. tb unreviewed safety or environmental questions are generated as as result of this plant modification.
165. Plant Modification Request WO84-KC071, revision 1 - Originated to change the hand pull stations on the fire protection system for the main generation transformers and startup transformers to
! provide annunciation only. tb unreviewed safety or environmental l
questions are generated as a result of this plant modification.
166. Plant Modification Request WO84-KE023, revisions 0 through 3 -
Originated to provide additional tool hangers on the wall of the t cask loading pit. The PMR also adds air and electric service to allow the use of the RCC Changing '1bol from the spend fuel pool bridge crane. tb unreviewed safety or environmental questions are generated as a result of this plant modification.
167. Plant Modification Request WO84-KC028, revisions 0 and 1 -
Originated to provide a load cell on the spent fuel pool bridge crane. tb unroviewed safety or environmental questions are generated an a result of this plant modification.
Page 18 of 39
o ,
168. Plant Modification Request WO84-SJ029 - Originated to replace the grab sample station purging jumpers and sample faucets with a combined jumper-faucet assembly in the nuclear sampling system.
No unreviewed safety or environmental questions are generated as a result of this plant modification.
169. Plant Modification Request WO85-SK01, revisions 0 through 5 -
Originated to change the Control Room entrance door for easier access. Ib unreviewed safety or environmental questions are generated as a result of this plant modification.
170. Safety Evaluation 86-SE-001 - Originated to allow the installation of performance monitoring instrumentation on secondary plant equipment. tb safety related equipment is affected. Ib unreviewed safety or environmental questions are generated as a result of this temporary modification.
171. Safety Evaluation 86-SE-002 - Originated to allow defeating the Turbine setback on loss of a Circulation Water Pump. Ib unreviewed safety or environmental questions are generated as a result of this temporary modification.
172. Safety Evaluation 86-SE-003 - Originated to eliminate the axial flux difference target band and its associated penalty. It also causes a small change to the Over-Temperature Differential Temperature setpoints. This change, which allows greater operating flexibility, is a result of the Nuclear Steam Supply System vendor recalculating the allowable margins in the accident analysis. No unreviewed safety or environmental questions are generated as a result of this proposed Technical Specification Change.
173. Safety Evaluation 86-SE-004 - Originated to allow defeating the runback of the Main Turbine on loss of a Circulating Water Pump.
Ib unreviewed safety or environmental questions are generated as a result of this temporary modification.
174. Safety Evaluation 86-SE-005 - Originated to allow opening the two Tornado Missile Resistant Plugs marked A-3010-1 and 2 to facilitate repair to Main Steam Isolation Valve Hoists HKF29A and B. Conditions were established to provide for Shift Supervisor notification of any tornado threats during the estimated 72 hour8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> repair time. No unreviewed safety or environmental questions are generated as a result of this temporary nodification.
175. Safety Evaluation 86-SE-007 - Originated to replace a section of 1.5 inch carbon steel pipe and flange with 1.5 inch schedule 40 inconel pipe and a stainless steel flange in the condensate '
domineralizer system. The carbon steel pipe and flange had corroded, apparently due to reaction with acid feeding in just downstream and leaking through a check valve. tb unreviewed safety or environmental questions are generated as a result of this temporary modificaticn.
Page 19 of 39
176. Safety Evaluation 86-SE-008 - Originated to allow the removal of the valve internals from the recirculation manual stop valve, HF V326, for the Secondary Liquid Waste System High TDS Collector Tanks. Ib unreviewed safety or environmental questions are generated as a result of this temporary modification.
177. Safety Evaluation 86-SE-009 - Originated to reroute the emergency diesel engine starting air compressors CKJ01A and CKJ01D condensate dump valve drain piping directly to a drain. No unreviewed safety or environmental questions are generated as a result of this temporary modification.
178. Safety Evaluation 86-SE-010 - Originated to reroute the emergency diesel engine starting air compressors CKJ01B and CKJ01C condensate dump valve drain piping directly to a drain. tb unreviewed safety or environmental questions are generated as a result of this temporary modification.
179. Safety Evaluation 86-SE-Oll - Originated to install a site-manufactured alignment pin in the number 5 cylinder of the Positive Displacement Charging Pump. Once aligned, pump integrity and reliability is maintained by other supplier manufactured parts, and the pump will function and perform as originally supplied. tb unreviewed safety or environmental questions are generated as a result of this temporary modification.
180. Safety Evaluation 86-SE-012 - Originated to provide a connection point for a Temporary Demineralized Water Unit. The connections were made to non-safety related piping. No unreviewed safety or environmental questions are generated as a result of this temporary mdification.
181. Safety Evaluation 86-SE-013 - Originated to allow the installation of sample lines of the rotometer for Main Condenser Vacuum Pumps CCG01A, B, and C. 'Ihe rotometer piping is not safety related. Ib unreviewed safety or environmental questions are generated as a result of this temporary modification.
182. Safety Evaluation 86-SE-014 - Originated to allow the installation of sample lines on the discharge of Condensate Pumps PAD 01A, B and C. The affected piping is not safety related. Ib unreviewed safety or environmental questions are generated as a result of this tempotary modificatlon.
183. Safety Evaluation 86-SE-015 - Originated to allow the installation of a speaker on the Gaitronics at the Reactor Operator's Desk in the Control Room, tb unreviewed safety or environmental questions are generated as a result of this temporary modification.
184. Safety Evaluation 86-SE-016 - Originated to allow the installation of "B" reactor trip bypass breaker into the "A" reactor trip breaker cubicle during hot full flow control rod system testing.
No unreviewed safety or environmental questions are generated as a result of this temporary modification.
Page 20 of 39
u - 1 + ,,
g, # )
/ 185i:' Safety Evaluation 86-SE-017'- Originated to disconnect the input d;e,y e
JQ of free-field' strong motion accelercmieter SG-AR-1 from Seismic p I G Instrumentation' Panel SGJ58 while reworking the accelerometer. . No 4 - ',_ '" '
unreviewed safety or environmental questions are generated as a
~
J d., ,Mresult of this temporary modification.
-186. , Safety Evaluation 86-SE-018 - Originated to allow connection of an ungrounded 15 volt direct current power supply to.the output of
~
j power supply CPS-ll7 in Seismic Instrumentation Panel' SG058, due 4 /;N to the failure of CPS-ll7. No unreviewed safety or. environmental
- questions are generated as a result of this temporary 4
'. modification. -
% 4
%% s 187. Safety Evaluation 86-SE-019 ~ Originated to provide temporary
[D vpower from the PG bus to a compressor and to connect 'the output of
- 'tbat temporary compressor to the plant service air system at. valve
@ +
+ KA V104. No unreviewed safety or environmental questions are
,*. 4
_ e generated as 'a result of this temporary modification.
'w .
ae + . 7188. - Safety Evaluation 86-SE-020 - Originated to allow removal of the S #
card for. alarm window 90B (Diesel Generator Fuel Tank B Level Iow) at.the annunciator logic cabinet to silence a nuisance alarm for y' ((
thaf Eindow. % is-alarm is not safety related. No unreviewed safety or environmental questions are generated as a result of this tem;x>rary modification.
, 7 y
_3 <'189. Safety Ev'aluation 86-SE-021 - Originated to allow the installation of a temporary tail piece on high pressure heater 7A relief valve, AE V979, to divert its flow to a separate point in the same drain,
'while workmen were working on High Pressure Heater 7B relief valve. Since both relief valves normally. discharge to a conunon header, this temporary modification was needed for personnel safety. .No unreviewed safety or environmental questions are generated'ac a result of this temporary modification.
190 Safety Evaluation 86-SE-022 - Originated to allow the installation fof temporary e
piping from AE V980 to AE V989 to circumvent blockage in Seal Watar Transmitter instrument root valve AE V989. We
" jumper was needed to ensure proper seal water flow to Steam Generator Feed Punp B. No'unreviewed safety or environmental l questions are generated as a result of this temporary modification.
c ,s 191. " Safety Evaluation 86-SE-023 - Originated to allow the improvement of communications for turbine generator testing by replacing four
,j handsets with headsets on the Gaitronics communications system.
,, t.tWunreviewed safety or environmental questions are generated as a
,,,i f
' %3 ult of this temporary modification.
.g
- 192. Safety Evaluation 86-SE-024 - Originated to allow reterminating the' cable to the Standby Diesel Generator KKJ01A jacket water heater by cutting off the damaged section, stripping and using heat shiinking tubing, until new cable can be installed under Plant Modification Request 1329. No unreviewed safety or
- envirordnental questions are generated as a result of this temporary modification.
Page 21 of 39
'i
{ , --- -..__- --
I 193. Safety Evaluation 86-SE-025 - Originated to allow the installation of the shaft seal on Emergency Exhaust Fan assembly CGG02B using four temporary bolts. tb unreviewed safety or environmental questions are generated as a result of this temporary mdification.
194. Safety Evaluation 86-SE-026 - Originated to allow the charging of a single cell in non-safety related battery PKl4. Ib unreviewed safety or environmental questions are generated as a result of this temporary modification.
195. Safety Evaluation 86-SE-027 - Originated to allow the removal of alarm card 15 for alarm window 93D, Instrument Air Humidity High, in RK045E3, cubicle 5 until the air dryer unit is repaired. tb unreviewed safety or environmental questions are generated as a result of this temporary modification.
196. Safety Evaluation 86-SE-028 - Originated to allow the installation of pressure gauges on the Domineralized Water Degasification Pumps PAN 02A and PAN 02B, to obtain suction pressure. Ib unreviewed safety or environmental questions are generated as a result of this temporary modificaticn.
197. Safety Evaluation 86-SE-029 - Originated to allow installation of a hose to demineralized water valve AN V079 for use in cleaning the Main Steam Isolation valve Ibom. tb unreviewed safety or environmental questions are generated as a result of this temporary modificatlor..
198. Safety Evaluation 86-SE-030 - Originated to allow lifting leads 97 and 98 on 'IB4 in cabinet RK045C4 to clear a ground on cable 6 LER0711A which feeds annunciator RK045, North Condensate Pit Sump Level fligh Alarm. No unreviewed safety or environmental questions are generated as a result of this temporary mdification.
199. Safety Evaluation 86-SE-031 - Originated to reverse the wires on terminals 'IB4-8-01 and TB4-8-04 in panel RP05BC for the Diesel Generator "A" day tank level control circuit to make the wiring agree with the schematic diagram, tb unreviewed safety or environmental questions are generated as a result of this temporary modification.
200. Safety Evaluation 86-SE-032 - Originated to allow lifting the horizontal proximity lead on Reactor Coolant Pump "A" vibration monitor, to prevent nuisance alarms in the Control Room. Ib unreviewed safety or environmental questions are generated as a result of this temporary modification.
201. Safety Evaluation 86-SE-033 - Originated to allow the installation of pressure gauges and isolation valves in the service gas system upstream of the flex connections to the accumulators for the Main Steam Isolation Valves and the Feedwater Isolation Valves. Ib unreviewed safety or environmental questions are generated as a result of this temporary modification.
Page 22 of 39
202. Safety Evaluation 86-SE-034 - Originated to allow the removal of power fr m dampers GF D062 and GF D063 while the associated ductwork was being cleaned. No unreviewed safety or environmental questions are generated as a result of this temporary modification.
203. Safety Evaluation 86-SE-035 - Originated to allow the installation of pressure gauges to the Main Turbine steam seal lines. No unreviewed safety or environmental questions are generated as a result of this temporary modification.
204. Safety Evaluation 86-SE-036 - Originated to allow lifting wire J405-7 in cable SACQ08A to defeat the low T-ave signal to the Stop Turbine Ioading Circuit, until the NRC Group 04 circuit card can be replaced with a NBC Group 10 circuit card pursuant to Plant Modification Request 01198. No unreviewed safety or environmental questions are generated as a result of this temporary modification.
205. Safety Evaluation 86-SE-037 - Originated to defeat the invalid alarms from Radiation Monitors SJ RE02 and GE RE92 which provide input to the Blowdown and Sample Isolation Valves. Redundant monitors BM RE25 and BM RE52 provide the same isolation capability. No unreviewed safety or environmental questions are generated as a result of this temporary modification.
206. Safety Evaluation 86-SE-038 - Originated to cap the four drains to the Floor and Equipment Drainage System from the Main Steam
. Isolation Valve Room while Fyrquel hydraulic fluid was being cleaned up in the room. No unreviewed safety or environmental questions are generated as a result of this temporary modification.
207. Safety Evaluation 86-SE-039 - Originated to allow machining off 3/32 inch frm the bottom of the set screw that prevents movement of the nozzle ring on relief valve BG V8118 for the Positive Displacement Charging Pump. No unreviewed safety or environmental questions are generated as a result of this temporary modification.
208. Safety Evaluation 86-SE -040 - Originated to allow the installation of test gauges on the suction and discharge of Steam Generator Feed Pump "B". No unreviewed safety or environmental questions are generated as a result of this temporary modification.
209. Safety Evaluation 86-SE-041 - Originated to allow replacement of a broken weatherhead (junction box) for low temperature switch TSL-063 for Diesel Generator RKJ001A engine coolant system. 'Ihe replacement weatherhead has the same form fit and function, but is from a different manufacturer. No unreviewed safety or environmental questions are generated as a result of this temporary modification.
Page 23 of 39
]
v u ..
210. Safety Evaluation 86-SE-042 '- Originated to allow the installation of filter / dryer elements on the suction and discharge refrigerant lines for the 'Ibrbine Building Process Sampling Lab Air Handling
= Unit SGE15. No unreviewed safety or environmental questions are generated as a result of this temporary modification.
211.- Safety Evaluation 86-SE-043 - Originated to allow a restraint of stainless steel wire to be employed to hold a flared swagelok fitting connection together where the stem leakoff tubing for valve BG HV8146 connects to the two inch leakoff header. %e tubing is D-augmented, non-seismic I. No unreviewed safety or environmental questions are generated as a result of-this temporary modification.
'212. Safety Evaluation 86-SE-044 - Originated to demonstrate the operability of the Reactor Coolant System pressure isolation valves BB PV8702A, BB PV8702B, EJ HV8701A, and EJ HV8701B by_
~
verifying that the measured leakage meets the acceptance criteria of Technical Specifications 4.4.6.2.2. No unreviewed safety or.
environmental questions are generated as a result of this special test procedure.
213. Safet'y Evaluation 86-SE-045 - Originated to allow connection of a
. temporary hose from Chemical and Volume Control System drain valve BG V454'to drain _ valve' BG V580 to provide a flow path for _ Reactor-Coolant Pump seal water return while conducting Incal_ Leak Rate Testing of penetration P-24. No unreviewed safety or environmental questions are generated as a result of-this
5 214. Safety Evaluation 86-SE-046 - Originated to divert Reactor ' Coolant
'~ Pump seal water return through the temporary hose installed by Safety Evaluation 86-SE-45, while conducting Local Leak Rate Testing of penetration P-24. No unreviewed safety or
' environmental questions are generated as a result of this special :
test procedure.
215. Safety Evaluation 86-SE-047 - Originated to allow installation of a pressure gauge on the suction of "B" Centrifugal Charging Pump
.' to facilitate performance of a surveillance test. No unreviewed safety or environmental questions are generated as a result of ,
! this temporary modification.
216. Safety Evaluation 86-SE-048 - Originated to allow the use of the five ton hoist of the cask handling crane to transport a dunny fuel assembly from the new fuel storage area to the upender, to facilitate functional testing of the upender. W e fuel pool is flooded, the transfer canal is not, and the transfer canal gate is in place, preventing the use of the spent fuel pool bridge crane.
tere is no fuel in the spent fuel pool. No unreviewed safety or
-environmental questions are generated as a result of this temporary modification.
1 l
Page 24 of 39 2 _. . _ . _ _ . _ _ _ . _ . _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ ,_ - _ . _ ... _ _ . ,._,
., .l y .. ,
.217. Safety Evaluation 86-SE-049.- Originated to allow the use of a temporary cover and fasteners on the lower right hand side of class IE, IEEE 323 qualified 480 Volt Motor Control Center NG03T, because the original cover was lost. No unreviewed safety or environmental questions are generated as a result of this temporary modification.- -
218. ' Safety Evaluation 86-SE-050, revisions 6 and 1 - Originated to allow gagging.of Reactor Coolant Drain Tank relief valve HB-7160 which has been frequently lifting at low tank pressures.
Overpressure protection is.provided by relief valve HB-7169. A gate valve between the tank and this relief valve is to be tagged open to ensure a flow path. No unreviewed safety or environmental' questions are generated as a result of this temporary modification.
219. Safety Evaluation 86-SE-052 - Originated to. temporarily jumper out-the, faulty master SCR Controller for Heating Coil EGG 10A for Emergency Exhaust Filter Adsorber Unit FGG02A. . Ihe jumper will energize the Heating Coil each time the ' associated exhaust fan is energized to ensure incoming air.is maintained below 70 percent
' humidity. No unreviewed safety or. environmental questions'are generated as a result of this' temporary modification.
220. Safety Evaluation 86-SE-053.- Originated to allow a mechanism for using demineralized water to cool the bearings of.the pumps supplying gland and motor cooling water for Circulating Water Pumps 1CW0lPA, B and C. No unreviewed safety or environmental questions are generated as a result of this temporary modification.
221. Safety Evaluation 86-SE-054 - Originated to allow the installation of. unions in piping lines 044-HBD-1", 043-HBD-1 1/2", 079-ICD-1" and 078-HBD-1 1/2" to. facilitate removal of waste gas traps FHA 02 and FHA 03 for inspection and maintenance. No unreviewed safety or environmental questions are generated as a result of _ this temporary modification.
222. Safety Evaluation 86-SE-055 - Originated to allow the installation of temporary differential pressure gauges across ventilation
< filters FGT01, FGE01, FGK03 and FGLO2 to measure flow during unit vent flow testing. No unreviewed safety or environmental questions are generated as a result of this temporary modification.
223. Safety Evaluation 86--SE-056 - Originated to allow the temporary installation of a spliced cable to supply power to the jacket water heater EKJ01A of Emergency Diesel Generator "A" since the insulation on the vendor supplied cable damaged, allowing a short to ground. No unreviewed safety or environmental questions are
- - generated as a result of this temporary modification.
224. Safety Evaluation 86-SE-057 - Originated to provide a portable air compressor to back up the instrument air system. No unreviewed safety or environmental questions are generated as a result of this temporary modification.
Page 25 of 39
, . _ _ . . ~. ___ . __ _ ,_. _ _ _ _ _ _ _ _ _ _ _ _ _
k - &: .
225.. Safety' Evaluation'86-SE-058 . Originated to delete'the particulate =
. : and-iodine: portions from, Surveillance Test STS IC-250A.for Containment, Atmospheric Radiation Monitor GT RE-32 until repair; parts can be received. No unreviewed safety or' environmental
- questions are generated-as a.. result of this temporary ,
L . modification.
~226. Safe'ty Evaluation 86-SE-059 -' Originated to defeat the "B" Steam Generator low-low trip signal while the reactor is . shutdown, the "B" Steam Generator is drained and the "B" Diesel Generator is being tested.: No.unreviewed safety or environmental questions are.
generated as.a result of this temporary modification.
i
.227. Safe'ty Evaluation 86-SE-060 - Originated to' provide temporary shielding on Pressurizer spray control valves BB PCV4558 and BB PCV455C. No unreviewed safety or environmental questions are '
generated as a result of this temporary modification.
228. Safety Evaluation '86-SE-061 - Originated to change certain.Gai- - ~
tronics: handset stations to headset stations whila Reactor Coolant
- System Isolation Valve Leakage Test is being conducted.per STS PE-
~
019. No'unreviewed safety or environmental questions are generated as a result of.this temporary modification.
. .i 229.: Safety Evaluation 86-SE-062 - Originated to provide temporary shielding on hot leg manifold valve BB V8073C. No unreviewed safety or' environmental questions are generated as a result of-
~
this temporary shielding request.
r 230. . Safety Evaluation 86-SE-063 originated to cut off damaged threads and rethread the pipe for the condenser-vent GK V050 for
~
- the Control Room Air Conditioner Unit. No unreviewed safety or 4 environmental questions are generated as a result of this t temporary modification.
b 231. Safety Evaluation ~86-SE-064 - Originated to remove power from two -
1 heaters in the Essential Service Water Pump Room and to provide a ,
i load shed signal for lighting transformer XQB-51 until a ground can be cleared. No unreviewed safety or environmental questions are generated as a result of this temporary modification.
V i 232. Safety Evaluation 86-SE-065 - Originated to change certain Gai-tronics handset stations to headset stations while Reactor Coolant System Isolation Valve leakage test STS PE-019 is being conducted. No unreviewed safety or environmental questions are -
2 generated as a result of this temporary modification.
j'
+
233. Safety Evaluation 86-SE-066 - Originated to defeat the interlocks
- on the two ton hoist on the cask handling crane to allow it to transport a dumy fuel assembly from the new fuel storage area to
! the upender in the Fuel Building. No fuel is stored in the fuel pool. No unreviewed safety or environmental questions are generated as a result of this temporary modification.
T 1 ,
Page 26 of 39
~
-225. . Safety Evaluation 86-SE-058'. Originated to delete the particulate and-iodine ~ portions from Surveillance Test STS IC-250A for Containment Atmospheric Radiation Monitor GT'RE-32 until repair parts can be received. -No unreviewed safety or environmental questions are generated as a result of this temporary modification.
226. ;; Safety Evaluation' 86-SE-059 .- Originated to defeat the "B"- Steam Generator low-low trip signal while the reactor is shutdown, the
- "B" Steam Generator is-drained and the "B" Diesel Generator is being tested. No unreviewed safety or environmental questions are generated as a result of :this temporary modification.
227. Safety Evaluation 86-SE-060 . Originated to provide temporary .
shielding on Pressurizer spray control valves BB PCV455B and BB o> ~
PCV455C. No unreviewed safety or environmental questions are generated as a' result of this temporary modification.
228. -Safety Evaluation 86-SE-061 - Originated to change certain Gai-tronics handset stations to headset stations while Reactor Coolant System Isolation Valve Leakage Test is being conducted per STS PE-019. No unreviewed safety or environmental quections are generated 'as a result of this temporary modification.
229. Safety Evaluation 86-SE-062 - Originated to provide temporary l
shielding on hot leg manifold valve.BB V8073C. No unreviewed safety or environmental questions are generated as a' result of
- . this temporary shielding request.
230. Safety Evaluation 86-SE-063 - Originated to cut off damaged threads and rethread the' pipe for the condenser vent GK V050 for the' control Room Air Conditioner Unit. No unreviewed safety or
' environmental. questions are generated as a result of this i temporary modification.
231. ' Safety Evaluation 86-SE-064 - Originated to remove power from two heaters;in the Essential Service Water Pump Room and to provide a load shed signal for lighting transformer XQB-51 until a ground
- j. can be cleared. No unreviewed safety or environmental questions
- are generated-as a result of this temporary modification.
232. Safety Evaluation 86-SE-065 - Originated to change certain Gai-
[
tronics handset stations to headset stations while Reactor Coolant System Isolation Valve leakage test STS PE-019 is being i conducted. No unreviewed safety or environmental questions are v generated as a result of this temporary modification.
233. Safety Evaluation 86-SE-066 - Originated to defeat the interlocks t.
on the two ton hoist on the cask handling crane to allow it to transport a dumy fuel assembly from the new fuel storage area to the upender in the Fuel Building. No fuel is stored in the fuel pool. No unreviewed safety or environmental questions are j generated as a result of this temporary modification.
i Page 26 of 39
d
. 234. ' Safety Evaluation 86-SE-068 --Originated to' allow deletion of
-particulate.and iodine portions of.the Analog Channel Operation test on Containment Radiation Monitor GT RE-32 while these portions ~of the Radiation Monitor are inoperable. .No unreviewed .
safety or environmental questions are generated as a result of this temporary surveillance test procedure' change.
235. Safety Evaluation 86-SE-0701-JOriginated to replace the pump-casing drain line with a plug on' Reactor Make-Up Water Pump
.PBL91B. No unreviewed safety or environmental questions are generated as a result of this temporary modification.
236'.. Safety Evaluation 86-SE-07'l - Originated to allow the Superintendent of Operations to become a'"previously licensed
-Senior Reactor Operator at Wolf Creek Generating Station". No~
unreviewed safety or environmental questions.are. generated as a result of this proposed change to the Final Safety Analysis Report.
l .
237. Safety Evaluation 86-SE-072 - Originated to allow attaching stainless steel tubing to the telltale leak-off hole.in the~
Positive Displacement Charging Pump discharge relief valve in order -to quantify the leak-off. No unreviewed safety or environmental questions are generated as a' result of this temporary modification.
-238. Safety Evaluation 86-SE-073 - Originated-to allow replacement of a
~
drain line with a plug on Control Building air conditioning -heat exchanger SGK05A. No unreviewed safety or environmental questions are generated as a result of this temporary modification.
239. Safety Evaluation 86-SE-074 - Originated to allow replacement of the diaphram on Steam Generator "C" blowdown control valve BM IN003 with a diaphragm from the same manufacturer with the same form, fit and shape but not certified as an identical replacement. 'Ihis valve fails closed on a loss of diaphragm. : No
~
unreviewed safety or environmental questions are generated as a result of this temporary modification.
240. Safety Evaluation 86-SE-075 - Originated to allow defeating a faulty isolation signal from Steam Generator Blowdown Radiation Monitor BM RE-52 while'the monitor is out of service. No unreviewed safety or environmental questions are generated as a result of this temporary modification.
241. Safety Evaluation 86-SE-076 - Originated to allow operating the plant in Mode 2, Startup, with the Main Steamline Isolation Valves and Main Feedwater Isolation Valves closed while releasing steam through one atmospheric steam dump valve and feeding that Steam Generator from the Auxiliary Feedwater System. No unreviewed safety or environmental questions are gencrated as a result of this temporary procedure change.
Page 27 of 39
l 242. Safety Evaluation 86-SE-077 - Originated to change the
} responsibility of the warehw se and associated activities from the l
Superintendent of Maintenance to the Procurement and Materials Manager. Ib unreviewed safety or environmental questions are generated as a result of this temporary procedure change.
243. Safety Evaluation 86-SE-078 - Originated to allow connection of a piping jumper, consisting of a check valve, strainer and hose from one inch drain valve LF-V078 to one inch drain valve HB-V009 so that the Liquid Radwaste System may be used to remove water from the Containment Normal Sumps while local Leak Rate Testing is being conducted on the normal flow path at penetration P-32. Ib unreviewed safety or environmental questions are generated as a result of this temporary modification.
244. Safety Evaluation 86-SE-079 - Originated to allow connection of a hose between BG V454 and BG V580 to provide an alternate flow path for Reactor Coolant Pump (RCP) seal return flow to the Reactor Coolant Drain Tank while stroke testing the seal return Containment Isolation Valves during BCP operation. No unreviewed safety or environmental questions are generated as a result of this special test procedure.
245. Safety Evaluation 86-SE-080 - Originated to allow a stroke test of Residual Heat Removal valves EJ IN-8701A, EJ IN-8701B, BB PV-8702A and BB PV-8702B while the plant is being maintained in Mode 3, Hot Standby. Ib unreviewed safety or environmental questions are generated as a result of this temporary procedure change.
246. Safety Evaluation 86-SE-087 - Originated to allow the replacement of the Safety Grade gasket on the Control Building air conditioning unit compressor heat exchanger with a cmmercial grade gasket of the same form, fit, function, material and manufacturer. Ib unreviewed safety or environmental questions are generated as a result of this temporary modification.
247. Safety Evaluation 86-SE-088 - Originated to allow the installation of a pressure gage on Service Water header vent valve EA V107. tb unreviewed safety or environmental questions are generated as a result of this temporary modification.
248. Safety Evaluation 86-SE-089, revisions 0 and 1 - Originated to temporarily supply the Main Steam Enclosure Supply Air Unit, SGF01, heating coil with chilled water from the Containment Shutdown Purge Unit, SGT01, during the summer months. Ib unreviewed safety or environmental questions are generated as a result of this temporary modification.
249. Safety Evaluation 86-SE-090 - Originated to temporarily remove fire detector zone 115 from the alarm circuit for the Auxiliary Building so that another zone in the Auxiliary Building could activate the alarm if needed. Zone 115 is in continuous alarm and being checked hourly by a fire watch. No unreviewed safety or environmental questions are generated as a result of this temporary modification.
Page 28 of 39
=.
250. Safety Evaluation 86-SE-091 - Originated to temporarily replace the stainless steel bushings on the handwheel shaft for door 13251, Auxiliary Feedwater Pump Poom "B", with a bronze bushing.
No unreviewed safety or environmental' questions are generated as a result of this temporary modification.
251. Safety Evaluation 86-SE-092, revisions 0 and 1 - Originated to provide a temporary access to the Auxiliary Building frm the Communications Corridor via room 1403 on the 2026 foot elevation during the refueling outage. Ib unreviewed safety or environmental questions are generated as a result of this temporary modification.
252. Safety Evaluation 86-SE-093 - Originated to disable the local alarm bell for the Fire Protection System remote panel KC 257, which controls the preaction valve for some cable trays on the 2000 foot elevation of the Auxiliary Building. No fire detection or suppression capability.is affected. No unreviewed safety or environmental questions are generated as a result of this temporary modification.
253. Safety Evaluation 86-SE-094 - Originated to defeat the automatic fire protection deluge on the main transformers. No unreviewed safety or environmental questions are generated as a result of this temporary modification.
254. Safety Evaluation 86-SE-096 - Originated .to allow the use of temporary pumps in the Turbine Building condensate pit sumps. No unreviewed safety or environmental questions are generated as a result of this temporary modification.
255. Safety Evaluation 86-SE-097 - Originated to change the computer setpoints to comply with Amendment No. 1 to the WCGS Technical Specification which allowed Power Distribution Control by a methodology called Relaxed Axial Offset Control. No unreviewed safety or environmental questions are generated as a result of this cmputer setpoint change.
256. Safety Evaluation 86-SE-098 - Originated to allow the temporary use of a non-nuclear safety grade capacity control valve on the Control Room air conditioning unit SGK04B. No unreviewed safety or environmental questions are generated as a result of this temporary modification.
257. Safety Evaluation 86-SE-102 - Originated to provide a temporary rack to hold the Westinghouse BPRA tool and RCCA tool in the Cask Loading Pit. No unreviewed safety or environmental questions are generated as a result of this temporary modification.
258. Safety Evaluation 86-SE-103 - Originated to allow the temporary installation of an air empressor on the breathing air system. tb unreviewed safety or environmental questions are generated as a result of this temporary modification.
Page 29 of 39
o
. =- . ,
259. Safety Evaluation 86-SE-104 - Originated to allow installing hardware to provide access from either side of doors 32051, 32071, 32091 and 321?.l. No unreviewed safety or environmental questions are generated as a result of this temporary modification.
260. . Safety Evaluation 86-SE-106 - Originated to allow temporary replacement of the o-ring seal on the pump side of the coupling on Auxiliary Feedwater Pump, PAIUIB, with a commercial grade o-ring until a replacement can be obtained frm the vendor. No unreviewed safety or environmental questions are generated as a result of this temporary modification.
261. Safety Evaluation 86-SE-107 - Originated to replace the caps at valves SPC002 and SPC003 with Swagelok Quick-Connects to facilitate obtaining tritium grab samples. No unreviewed safety or environmental questions are generated as a result of this temporary modification.
262. Safety Evaluation 86-SE-108 - Originated to replace the plugs at valves SPC001 and GS V030 with Swagelok Quick-Connects to facilitate obtaining tritium grab samples. No unreviewed safety or environmental questions are generated as a result of this temporary modification.
263. Safety Evaluation 86-SE-109 - Originated to replace part of the Process Sampling System 3/8" sample tubing from the Steam Generator Blowdown line with 3/4" pipe. No unreviewed safety or environmental questions are generated as a result of this temporary modification.
264. Safety Evaluation 86-SE-110'- Originated to replace Safety Evaluation 85-SE-33 which contained a statement that could be misinterpreted. It concerns a change to Surveillance Test Procedure STS IC-925 which allows using Essential Service Water pumps to test the flow thru the Containment Coolers. No unreviewed safety or environmental questions are generated as a result of this temporary procedure change.
265. Safety Evaluation 86-SE-lll - Originated to allow defeating the isolation signal from radiation monitor BM-RE-52 while awaiting test equipment repair. There is no flow thru the system that is monitored by BM-RE-52. Should flow be initiated, action 32 of Technical Specifications 3.3.3.10 would be entered. No unreviewed safety or environmental questions are generated as a result of this temporary modification.
266. Safety Evaluation 86-SE-ll6 - Originated to temporarily install a skid mounted air cmpressor to supply the service and/or instrument air systems. No unreviewed safety or environmental questions are generated as a result of this temporary modification, i
Page 30 of 39
267. Safety Evaluation 86-SE-ll7 - Originated to defeat blowdown and sample isolation caused by spurious alarms on process radiation i monitor BM-RE-52, since blowdown flow is not being routed thru the discharge path monitored by BM-RC-52. Ib unreviewed safety or environmental questions are generated as a result of this temporary modification.
268. Safety Evaluation 86-SE-ll8 - Originated to temporarily fill the electro-hydraulic actuator for valve GK V765 in the Control Room air conditioning unit with commercial grade hydraulic oil SCH824 manufactured by Mobil Oil Co. No unreviewed safety or environmental questions are generated as a result of this temporary modification.
269. Safety Evaluation 86-SE-119 - Originated to temporarily encapsulate a non-safety related 1 inch drain line on the main steam line piping down stream of the Main Steam Isolation Valves.
Ib unreviewed safety or environmental questions are generated as a result of this temporary modification.
270. Safety Evaluation 86-SE-120, revisions 0 and 1 - Originated to allow temporary lead blanketing of the Pressurizer Spray Valves and associated piping during Modes 5 and 6. Ib unreviewed safety or environmental questions are generated as a result of this
-temporary modification.
271. Safety Evaluation 86-SE-121 - Originated to modify the security computer software concerning the card reader for door 14031. Ib unreviewed safety or environmental questions are generated as a result of this temporary modification.
272. Safety Evaluation 86-SE-122 - Originated to temporarily relocate a '
card reader associated with room 1403. No unreviewed safety or environmental questions are generated as a result of this temporary modification.
273. Safety Evaluation 86-SE-123 - Originated to temporarily provide power to process radiation monitor BM-RE-52 frce a convenience outlet to determine if its normal power is the cause of its spurious alarms. (See Safety Evaluation 86-SE-ll7). Ib unreviewed safety or environmental questions are generated as a result of this temporary modification.
274. Safety Evaluation 86-SE-124 - Originated to temporarily install an isolation transformer in the power supply line to process radiation monitor BM-RE-52 and its normal power supply from breaker PG17LBF315. (See Safety Evaluations 86-SE-ll7 and 86-SE-123). No unreviewed safety or environmental questions are generated as a result of this temporary modification.
275. Safety Evaluation 86-SE-125 - Originated to temporarily provide power to process radiation monitor BM-RE-52 from a convenience outlet. Fluctuations in its normal power supply are causing spurious alarms. An attempt to filter these fluctuations with an isolation transformer (See Safety Evaluation 86-SE-124) was unsuccessful. Ib unreviewed safety or environmental questions are generated as a result of this temporary modification.
Page 31 of 39
276. Safety Evaluation 86-SE-126 - Originated to allow the temporary replacement of perimeter detection units with those of another manufacturer. No unreviewed safety or environmental questions are generated as a result of this temporary modification.
277. Safety Evaluation 86-SE-127 - Originated to temporarily install a commercial grade electric hot water heater which could be valved into the domestic water system to supply showers and sinks in the Health Physics area upon loss of normal hot water. No unreviewed safety or environmental questions are generated as a result of this temporary modification.
278. Safety Evaluation 86-SE-129 - Originated to provide a temporary Breathing Air manifold inside containment. No unreviewed safety or environmental questions are generated as a result of this temporary modification.
279. Safety Evaluation 86-SE-130 - Originated to temporarily install porous disk snubbers in the instrument lines on the emergency diesel engines jacket water pump and intercooler pump. Ib unreviewed safety or environmental questions are generated as a result of this temporary modification.
280. Safety Evaluation 86-SE-131 - Originated to provide a shroud to prevent impingement of cold air on the low temperature alarm switch for the Diesel Generator jacket water heating system. No unreviewed safety or environmental questions are generated as a result of this temporary modification.
281. Safety Evaluation 86-SE-132 - Originated to temporarily change the torque switch setting for valve AL HV33 pending a revision to PMR 1722. No unreviewed safety or environmental questions are generated as a result of this temporary modification.
282. Safety Evaluation 86-SE-133 - Originated to allow temporary lead blanketing of the CVCS regenerative heat exchanger during Modes 5 and 6. No unreviewed safety or environmental questions are generated as a result of this temporary modification.
283. Safety Evaluation 86-SE-134 - Originated to temporarily defeat Radiation Monitor BM-RE-52 isolation signal while no flow exists in the fluid it monitors to prevent blowdown isolation from its spurious alarms. No unreviewed safety or environmental questions are generated as a result of this temporary modification.
284. Safety Evaluation 86-SE-135 - Originated to allow temporary lead blanketing of the CVCS excess letdown heat exchanger during mdes 5 and 6. No unreviewed safety or environmental questions are generated as a result of this temporary modification.
285. Safety Evaluation 86-SE-136 - Originated to temporarily allow access to the Auxiliary Building from the 2032 foot level of the Comunications Corridor during the refueling outage. tb unreviewed safety or environmental questions are generated as a result of this temporary modification.
Page 32 of 39
, . - . _. - . .-. .- - -. . = . - _. --
W. , # ,
c 286. -Safety Evaluation 86-SE-137'- Originated to allow temporary lead blanketing of the reactor vessel. head while it is on-the' storage standJ No unreviewed safety or environmental-questions are_ ,
. generated-as a result of this temporary modification.
~
287. Safety Evaluation 86-SE-139 - Originated to temporarily bypass an
~
underground'section Auxiliary Boiler excess fuel oil return line.
No.unreviewed safety or environmental questions are-generated as a result of this temporary modification..
288. Safety Evaluation 86-SE-141 - Originated to temporarily.-remove l two 15KW heaters from service in the ESW pumphouse and to provide a functional load shed signal for lighting transformer XQB-51. 'No unreviewed safety or environmental questions are generated as a result of this temporary modification..
289. Safety Evaluation 86-SE-142'- Originated to' temporarily defeat the automatic isolation feature of the Feedwater Isolation Valves, during Modes 4, 5 and 6. No unreviewed safety or environmental 1 -questions are generated as a result of this temporary modification.
290. ' Safety Evaluation 86-SE-143 - Originated t' o temporarily install
~
pressure gauges on_the discharge of steam generator drain' pumps
.PBM03A and PBM03B. No unreviewed safety or environmental
' questions are generated as a result of this temporary 7
modification.
291. Safety Evaluation 86-SE-144 - Originated to temporarily prevent '
flow thru the gland stem leakoff tubing for valves BB V8085, BG *
, LV459 and BG LV460. No unreviewed_ safety or environmental questions'are generated as a result of this temporary j modification.
- 292. I Safety Evaluation 86-SE-145 - Originated to allow a filter purchased for special scope usage to be used as CVCS filter FBG06,'
- downstream of the letdown demineralizers. No unreviewed safety or
! environmental questions are generated as a' result of this temporary modification.
l 293.- Safety Evaluation 86-SE-146 - Originated to allow temporary lead blanketing of RCS loop 2 drain valves BB-V028 and BB-V029, during Modes 5 and 6. No unreviewed safety or environmental questions i are generated as a result of this temporary modification.
294. Safety Evaluation 86-SE-147 - Originated to allow temporary lead blanketing of RCS pipe 54-BCA-3" (loop 3 to CVCS letdown), during modes 5 and 6. No unreviewed safety or environmental questions are generated as a result of this temporary modification.
- l. 295. Safety Evaluation 86-SE-148 - Originated to allow temporary lead blanketing of RCS pipe 74-BCA-2" and valve BB V065 (loop 4 to excess letdown), during Modes 5 and 6. No unreviewed safety or l environmental questions are generated as a result of this
Page 33 of 39
. _ . _ u ._ _
__ u _ _ _ _ _ - - _
,s . .
I I
296. Safety Evaluation 86-SE-149 - Originated to temporarily defeat Radiation bbnitor BM-RE-52 Blowdown and Sample Isolation Signal to prevent unnecessary isolations frm its spurious alarms. tb unreviewed safety or environmental questions are generated as a result of this temporary modification.
297. Safety Evaluation 86-SE-150 - Originated to allow temporary lead blanketing of RCS loop 1 RTD manifold valves BB V8073A, BB V8074A, BB V006, BB V012, BB V013 and BB V014 and associated piping 17-BCA-2" and BCB-3/4", 2007'6" to 2015' elevation, during Modes 5 and 6. Ib unreviewed safety or environmental questions are generated as a result of this temporary modification.
298. Safety Evaluation 86-SE-151 - Originated to allow temporary lead blanketing of RCS loop 1 drain valves BB V008 and BB V009 and pipe 20-BCA-2", during Modes 5 and 6. Ib unreviewed safety or environmental questions are generated as a result of this temporary modification.
299. Safety Evaluation 86-SE-152 - Originated to temporarily defeat the Steam Generator IoIo water level trip signals during bbdes 4, 5 and 6. No unreviewed safety or environmental questions are generated as a result of this temporary modification.
300. Safety Evaluation 86-SE-153 - Originated to allow temporary lead blanketing of RCS loop 2 RTD manifold valves BB V8073B, BB V8074B, BB V031, BB V038, BB V039, associated piping and 33-BCA-3" from 2008'6" to 2015' elevation, during Modes 5 and 6. No unreviewed safety or environmental questions are generated as a result of this temporary modification.
301. Safety Evaluation 86-SE-154 - Originated to allow temporary lead blanketing of RCS loop 3 RTD manifold valves BB V8073C, BB V8074C, BB V045, BB V051, BB V053, BB V054 and associated piping 49-BCA-3", 51-BCA-2" and BCB-3/4", during bbdes 5 and 6. Ib unreviewed safety or environmental questions are generated as a result of this temporary modification.
302. Safety Evaluation 86-SE-155 - Originated to allow temporary lead blanketing of RCS loop 4 RTD manifold valves BB V8073D, BB V8074D, BB V" 1, BB V070, BB V073, BB V074, the RTD manifold, associated pip. J, 65-BCA-2", 66-BCA-3", 68-BCA-2" and 215-BCA-2" frm 2008'6" to 2015' elevation, during Modes 5 and 6. tb unreviewed safety or environmental questions are generated as a result of this temporary modification.
303. Safety Evaluation 86-SE-156 - Originated to allow temporary lead blanketing to be laid flat on top of the grating of the work platform beneath RCP "C", during Modes 5 and 6. tb unreviewed safety or environmental questions are generated as a result of this temporary nodification.
304. Safety Evaluation 86-SE-157 - Originated to allow temporary lead blanketing of CVCS piping 020-HCB-4" and 204-HCB-3", during Modes 5 and 6. tb unreviewed safety or environmental questions are generated as a result of this temporary modification.
Page 34 of 39
.. o .
305. Safety Evaluation 86-SE-158 - Originated to allow the temporary removal of the internals to check valve HF V310 to allow flow from the Secondary Waste System evaporator bottoms to the bulk waste disposal connection. Ib unreviewed safety or environmental questions are generated as a result of this temporary modification.
306. Safety Evaluation 86-SE-159 - Originated to allow the replacement of two 0-rings fitted at the bottom of the vertical stop of the actuator for Essential Service Water to Control Building HVAC valve GK V768, with O-rings made of Viton. Ib unreviewed safety or environmental questions are generated as a result of this temporary modification.
307. Safety Evaluation 86-SE-160 - Originated to allow automatic transfer switches to be temporarily installed in the non-class IE Instrument AC Power System in accordance with drawings provided in PMR 935 preliminary package. Ib unreviewed safety or environmental questions are generated as a result of this temporary modification.
308. Safety Evaluation 86-SE-161 - Originated to temporarily allow lifting lead 14GKYO2BB-1 at damper 6KHZ40B for troubleshooting while the damper is blocked open, the position required for a CRVIS signal. Ib unreviewed safety or environmental questions are generated as a result of this temporary modification.
309. Safety Evaluation 86-SE-162 - Originated to allow temporary lead blanketing of Steam Generator "A" primary side drain line 230-BCB-3/8" and valve BB V265 during Modes 5 and 6. Ib unreviewed safety or environmental questions are generated as a result of this temporary modification.
310. Safety Evaluation 86-SE-163 - Originated to allow tack welding the breaker rack-out assist rod to its bracket in breaker NB0ll3. tb unreviewed safety or environmental questions are generated as a result of this temporary modification.
311. Safety Evaluation 86-SE-164 - Originated to temporarily allow removal of a spool piece down stream of Essential Service Water valve EF HV-47, closing EF HV-47 and blank flanging the pipe at the other end of the spool piece. Flow will be maintained through parallel valve EF HV-49. Ib unreviewed safety or environmental questions are generated as a result of this temporary modification.
312. Safety Evaluation 86-SE-165 - Originated to temporarily allow connecting a 1 1/2" hose from the Demineralized Water Tank valve AN-V003 to the sludge lance trailer. Ib unreviewed safety or environmental questions are generated as a result of this temporary nodification.
313. Safety Evaluation 86-SE-166 - Originated to temporarily supply domestic water to the Computer Room cooling coils SGE10A and 10B during the Service Water outage. tb unreviewed safety or environmental questions are generated as a result of this temporary modification.
Page 35 of 39
1 F
~
.e w ,
314. Safety Evaluation 86-SE-167 - Originated to temporarily replace five Gai-tronics handset stations with headset stations during LLRT testing. No unreviewed safety or environmental questions are generated as a result of this temporary modification.
315. Safety Evaluation 86-SE-168 - Originated to allow shortening the nozzle ring set screw for Positive Displacement Charging Pump relief valve BG-8118. No unreviewed safety or environmental questions are generated as a result of this temporary modification.
316. Safety Evaluation 86-SE-170 - Originated to temporarily use a hose to bypass a portion of the Evaporator Bottoms Tank discharge piping that has been blocked with crystalizad boron. No unreviewed safety or environmental questions are generated as a result of this temporary modification.
317. Safety Evaluation 86-SE-171 - Originated to utilize comercial grade rivets to repair damper GK-D300. No unreviewed safety or environmental questions are generated as a result of this temporary maification.
318. Safety Evaluation 86-SE-172 - Originated to connect a hose to route the Recycle Evaporator concentrates to the Spent Fuel Pool:
No unreviewed safety or environmental questions are generated as a result of this temporary modification.
319. Safety Evaluation 86-SE-173, revisions 0 and 1 - Originated to allow corrosion test coupons to be installed in the Service Water System, Condenser Vacuum Pump Seal Cooler and Stator Cooler Heat Exchanger. No unreviewed safety or environmental questions are generated as a result of this temporary modification.
320. Safety Evaluation 86-SE-174 - Originated to defeat the high vibration trip from the Instrument and Service Air Compressor. No unreviewed safety or environmental questions are generated as a result of this temporary maification.
321. Safety Evaluation 86-SE-175 - Originated to replace the vent tubing from the fuel return header of "A" Diesel Generator to its accumulator tank with slightly thicker walled tubing. No unreviewed safety or environmental questions are generated as a result of this temporary modification.
322. Safety Evaluation 86-SE-176 - Originated to remove two 15KW heaters from service at the ESW pump rom and provide a functional load shed signal for stand by lighting transformer XQB-51. Ib unreviewed safety or environmental questions are generated as a result of this temporary maification.
323. Safety Evaluation 86-SE-177 - Originated to jumper two limit switches on the Spent Fuel Btidge Crane to allow it to be used to move the Decon Machine to the Fuel Transfer Canal. No unreviewed safety or environmental questions are generated as a result of this temporary modification.
Page 36 of 39
, u9 a. .-
! 4 324. ; Safety Evaluation 86-SE-178L- Originated to change two Gai-Tronics
. stations from handsets to headsets.; No unreviewed. safety or-environmental' questions are generated as a result of this-
~
l 325. < Safety. Evaluation 86-SE-179 - Originated to allow connection of a=
temporary dp cell across flow; element m FE-928 and use it instead of. flow indicator m FI-928A.for measuring, leakage.from BCS '
pressure isolation valves. No unreviewed safety or environmental
, questions are generated as a result of this temporary modification.
326. Safety Evaluation 86-SE-180 - Originated to change one Gai-Tronics station frce handset to headset. No unreviewed safety or
~
environmental questions are generated as a result of this temporary modification.
- 327. Safety. Evaluation 86-SE-181 - Originated to provide two connections from the Service Water System and one connection from the Gland Water System to the MIC and Biocide Analysis trailer at
. the Circ Water Screen House. No unreviewed safety or environmental questions are generated as a result of this temporary modification.
L 328. Safety Evaluation 86-SE-182 - Originated to cap the packing leak--
off line for Steam Generator blowdown valve BM V002. No-unreviewed safety or environmental questions are generated as a
. result of this temporary modification.
329.' Safety Evaluation 86-SE-183 - Originated to replace the hand driven chain operated hoist HKF-13 with an electric motor driven hoist. No unreviewed safety or environmental questions are generated as a result of~this temporary modification.
330. Safety Evaluation 86-SE-184 . Originated to replace hand-driven hoist HKF-33 with a motor-driven hoist. No unreviewed safety.or
]~
i environmental questions are generated as a result of this-temporary modification.-
l -331. Safety Evaluation KELKNP 86-1901 - Originated to allow an experimental application of aquatic herbicide to control potamogeton growth in certain areas of the cooling lake. No
- . unreviewed safety or environmental questions are generated as a j result of this experimental application.
j 332. Technical Specification Change Request - Originated to request a one-time deferment of the 18 month surveillance interval for certain surveillances that require the plant in Cold Shutdown for p their performance. No unreviewed safety or environmental questions are generated as a result of this Technical Specification change request.
333. Technical Specification 3.2.1 Change Request - Originated to change the required Axial Flux Difference specification. No
- unreviewed safety or environmental questions are generated as a result of this Technical Specification change request.
Page 37 of 39 i .-
1 4z
~
- w. e _,.
334. . Technical Specification 3.7.1.6 Change Request - Originated to add an operability requirement for the Steam Generator Atmospheric Relief Valves. No unreviewed safety or environmental questions are generated as a result of this Technical Specification change request.
335. Technical Specification 3/4.3.3.8, 3/4.7.10 and 3/4.7.11 Change Request - Originated to delete Fire Protection from the Technical Specifications. Ib unreviewed safety or environmental questions are generated as a result of this Technical Specification change request.'
336. Technical Specification 4.6.1.2.d. Change Request -_ Originated to request a one-time deferment to the specified 24 month maximum surveillance interval for Iocal Leak Rate Testing of certain Containment Penetrations that require the plant in Cold Shutdown to perform. Ib unreviewed safety or environmental questions are generated as a result of this Technical Specification change request.
337. Technical Specification 4.7.8 Change Request - Originated to request an extension of the time limit for performing the first-inservice visual inspection of snubbers that are inaccessable until the unit had to be shut down for other reasons, such shut down to occur not later than the first refueling outage. No
< unreviewed safety or environmental questions are generated as a result of this Technical Specification change request.
338. Technical Specifications 3/4.8 Change Request - Originated to reduce the emergency diesel testing requirements to comply with manufacturer recomendations and reduce unnecessary wear on the engines due to testing. No unreviewed safety or environmental questions are generated as a result of this Technical Specification proposed revision.
339. Technical Specification 3/4.8.4.1 Change Request - Originated to eliminate the requirement to periodically measure the resistance; remove Table 3.8-1 and to replace reference to it with "whose circuit limiting fault current exceeds the penetration rating shall be operable". No unreviewed safety or environmental questions are generated as a result of this Technical Specification change request.
340. Technical Specification 5.3.1 Change Request - Originated to delete the maximum fuel rod weight limit of 1766 grams of uranium, tb unreviewed safety or environmental questions are generated as a result of this Technical Specification change request.
341. Technical Specification Section 6 Change Request - Originated to reflect the changes to the administrative organization that are required by establishment of the Wolf Creek Nuclear Operating Corporation. Ib unreviewed safety or environmental questions are generated as a result of this Technical Specification change request.
Page 38 of 39
w .s . e- ,
342. Technical Specification Section 6 Change Request - Originated to supplement an earlier submission to administrative organization as
. shown in Technical Specifications and to add a member to the Nuclear Safety Review Committee. These changes result from the.
formation of the Wolf Creek Nuclear Operating Corporation as well as from a reorganization of a portion of the Quality Branch. No unreviewed safety or environmental questions are generated as a result of this proposed change to the Technical Specifications.
343. Technical Spoecification 6.2 and 6.5.2.2 Change Requests.-
Originated to change two position titles, change a reporting relationship, revise the Unit Organization Figure and add positions to the Nuclear Safety Review Conmittee. No.unreviewed safety or environmental questions are generated as a result of this Technical Specification change request.
344. Technical Specification 6.2.3.1 and 6.2.3.4 Change' Requests -
Originated to have the Independent Safety Engineering Group report to the Nuclear Safety Review Conmittee Chairman. No unreviewed safety or environmental questions are generated as a result of this proposed change to the Technical Specifications.
i Page 39 of 39
- .- .-, ,- .-