ML20148J382
ML20148J382 | |
Person / Time | |
---|---|
Site: | Crystal River |
Issue date: | 05/23/1997 |
From: | FLORIDA POWER CORP. |
To: | |
References | |
AR-401, NUDOCS 9706170126 | |
Download: ML20148J382 (190) | |
Text
h'h 5 Document Transmittal #: 61546 Date: 5/29/97 Tc: NRC (DC DESK) MAC: N/A Distination:
Description:
Copy Copy Totals Document: Revision: Comment: # INFO CNTL MSTR AR0401 16 MINOR CHANGE 24 1 0 0 Instructions to the Addressee: l lfff fff l)lffh, ffl$, lffllf Please verify the document (s) received agrees with the above information.
~,
Operations department must attach old document (s) or portions of document (s) superseded by the above '/
to this transmittai.
The signature indicates acknowledgment of receipt of the above document (s). Return signed and dated transmittal to Document Control within 15 days at mail code: d NA1C l[\
J T l
Florida Power Corporation Document Control, NA1C 9706170126 970523 Crystal River Energy Complex PDR ADOCK 05000302 15760 W. Power Line St.
P PDR Crystal River, FL 34428-6708 Signature of Addressee: Date:
1 f Rev. 16 l
Effective Date [- [ '
l l
i i
INFORMATION ONLY a ANNUNCIATOR RESPONSE AR-401 FLORIDA POWER CORPORATION <
CRYSTAL RIVER UNIT 3 !
1 i
f3 FSA F ANNUNCIATOR RESPONSE v
APPROVED BY: Interpretation Contact
- ~. G A - 1 ~~ D & .r , Cn M *
(SIGNATURE ON FILE.)
DATE: C2 '/ 7 INTERPRETATION CONTACT: Manager, Nuclear Plant Operations Support
__ . . - . .. - . . _ = - _ . . - . . - - _ _ . - - . . - - . - _ -
l l
d I
l l
$s t 7 TABLE OF CONTENTS SECTION PAGE 1.0 PURPOSE . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
2.0 REFERENCES
- 2.1
.......................... I INPLENENTING REFERENCES . . . . . . ......... 1
, 2.2 DEVELOPNENTAL REFERENCES ..... ........ I l i 3.0 PERSONNEL INDOCTRINATION
- ................... 1
! 4.0 INSTRUCTIONS ............. ............ 2 '
i 5.0 FOLLOW-UP ACTIONS . . . . . . . . . . . . . . . . . . . . . . . 2 i
\
! ENCLOSURES t
{ l Annunciator Response. . . . . . . . . . . . . . . . . . . . . . 3 i
i l 4
i O) 1 4
\s-1 1
i 4
AR-401 Rev. 16 Page i
1.0 PURPOSE 1.1 Establish a reference document for each Annunciator Window on the PSA-X Lampbox.
1.2 Establish operator status for valid Annunciator alarms on the PSA-X l.ampbox.
1.3 Establisn a reference to other procedures which address operator actions for valid Annunciator alarms on the PSA-X Lampbox.
2.0 REFERENCE _1 l
2.1 1 R LLMENTING REFERENCES 2.1.1 OP-409 - Plant Ventilation 2.1.2 OP-417 - Containment Operating Procedure 2.1.3 OP-703 - Plant Distribution System 2.1.4 AP-250 - Radiation Monitor Actuation 2.1.5 AP-513 - Toxic Gas 2.1.6 AP-880 - Fire Protection 2.1.7 OP-417A - Industrial Cooling System 2.1.8 SP-300 - Operating Daily Surveillance Log 2.1.9 PM-294 - Calibration of Robert Shaw Vibra Switches 2.2 DEyfLOPMENTAL REFERENCES 2.2.1 INP0 90-021, Good Practice OP-217, Alarm Response Procedures 2.2.2 Annunciator Window Engraving Drawing E-224-048 3.0 PERSONNEL INp_0CTRINATION
. 3.1- The.. Annunciator System is powered from VBDP-5 Breaker 28.
- l O
i AR-401 Rev. 16 Page 1
i l
)
l l
(~ 4.0 INSTRUCTIONS C
4.1 Respond to alarms on the PSA-X Lampbox as indicated on Enclosure 1, Annunciator Response. 1 j
i 5.0 FOLLOW-UP ACTIONS l
None l
l 1
1 AR-401 Rev. 16 Page 2
. ~ . ~ . - - . - - -. ._. -. - . - . - - . -.- -~ - . - - . . . -
ENCLOSURE 1 (Page 1 of 185)
PSA ANNUNCIATOR RESPONSE PSA-X-01-01 F-01-01 CNTRL COMPLEX FAN TRIP l EVENT POINT 0466 INDICATED CONDITION:
o AHF-17A MOTOR IS NOT ENERGIZED WITH CONTROL HANDLE IN NORMAL AFTER
> START POSITION l
REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o GREEN LIGHT ON WITH A RED FLAG ON CONTROL STATION O RADIATION HIGH RAD ALARM RM-A-5 l
OPERATOR ACTIONS FOR A VALID ALARM:
o INVESTIGATE THE CAUSE OF TRIP l 0 START AHF-178 l 0 RESTORE VENTILATION PER OP-409 o REFER TO AP-250 l
l DISCUSSION:
r
REFERENCES:
,. DRAWING 208-005 SHEET AH-80
- j SENSING ELEMENT: CS/SC, CS/0, 428 lO AR-401 Rev. 16 Page 3
._ _ .._.. _ _..~._._ _. .____._ . _ _.__..___ .
O ENCLOSURE 1 (Page 2 of 185) l PSA ANNUNCIATOR RESPONSE PSA-X-01-01 F-01-01 f CNTRL COMPLEX )
FAN l TRIP EVENT POINT 0467 i
INDICATED CONDITION:
i o AHF-17B MOTOR IS NOT ENERGIZED WITH CONTROL HANDLE IN NORMAL AFTER START POSITION REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o GREEN LIGHT ON WITH A RED FLAG ON CONTROL STATION o RADIATION HIGH RAD ALARM RM-A-5 OPERATOR ACTIONS FOR A VALID ALARM:
o INVESTIGATE THE CAUSE OF TRIP
( o REFER TO AP-250 l
0 START AHF-17A o RESTORE VENTILATION PER OP-409 3 l DISCUSSION:
l
)
REFERENCES:
DRAWING 208-005 SHEET AH-81 1
, , SENSING ELEMENTL CS/SC, CS/0, 428 -
H AR-401 Rev. 16 Page 4
l I
ENCLOSURE 1 O (Page 3 of 185) >
- - PSA ANNUNCIATOR RESPONSE PSA-X-01-01 F-01-01 I
CNTRL COMPLEX i I I FAN l TTt1P
.' l
- 1. I l
EVENT POINT 0470 i INDICATED CONDITION:
o AHF-18A MOTOR IS NOT ENERGIZED WITH CONTROL HANDLE IN NORMAL AFTER j START POSITION REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
O o GREEN LIGHT ON WITH A RED FLAG ON AHF-18A CONTROL STATION OPERATOR ACTIONS FOR A VALID ALARM:
o INVESTIGATE THE CAUSE OF TRIP o START AHF-188 o RESTORE VENTILATION PER OP-409 DISCUSSION:
REFER TO TECH SPECS FOR ADMINISTRATIVE REQUIREMENTS.
REFERENCES:
DRAWING 208-005 SHEET AH-82 SENSING ELEMCNTI' CS/SC, CS/0, 42B O
AR-401 Rev. 16 Page 5
l O ENCLOSURE 1 (Page 4 of 185)
PSA ANNUNCIATOR RESPONSE PSA-X-01-01 F-01-01 l
CNTRL COMPLEX i
FAN TRIP EVENT POINT 0471 INDICATED CONDITION:
o AHF-188 MOTOR IS NOT ENERGIZED WITH THE CONTROL HANDLE IN NORMAL AFTER START POSITION REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o GREEN LIGHT ON WITH A RED FLAG ON AHF-18B CONTROL STATION OPERA 10R ACTIONS FOR A VALID ALARM:
o INVESTIGATE THE CAUSE OF TRIP o START AHF-18A o RESTORE VENTILATION PER OP-409 DISCUSSION:
REFER TO TECH SPECS FOR ADMINISTRATIVE REQUIREMENTS
REFERENCES:
DRAWING 208-005 SHEET AH-83 SENSING ELEMENTT CS/SC CS/0, 42B i
O AR-401 Rev. 16 Page 6 l
l
! / ENCLOSURE 1 (Page 5 of 185)
PSA ANNUNCIATOR RESPONSE PSA-X-01-01 F-01-01 CNTRL COMPLEX FAN TRIP t
i EVENT POINT 0478 INDICATED CONDITION:
o AHF-19A MOTOR IS NOT ENERGIZED WITH CONTROL HANDLE IN NORMAL AFTER START POSITION REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o GREEN LIGHT ON WITH A RED FLAG ON AHF-19A CONTROL STATION o RADIATION HIGH RAD ALARM RM-A-5 )'
OPERATOR ACTIONS FOR A VALID ALARM:
o INVESTIGATE THE CAUSE OF TRIP o REFER TO AP-250 o START AHF-198 o RESTORE VENTILATION PER OP-409 DISCUSSION:
REFERENCES:
_,. DRAWING 208-005 SHEET AH-86
- SENSING ELEMENT: CS/SC, CS/0, 42B iO AR-401 Rev. 16 Page 7
ENCLOSURE 1 ,
(Page 6 of 185) l PSA ANNUNCIATOR RESPONSE PSA-X-01-01 F-01-01 CNTRL COMPLEX FAN g TRIP l l
l l
EVENT POINT 0479 INDICATED CONDITION:
o AHF-19B MOTOR IS NOT ENERGIZED WITH CONTROL HANDLE IN NORMAL AFTER START POSITION REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
i o GREEN LIGHT ON WITH A RED FLAG ON AHF-19B CONTROL STATION i o RADIATION HIGH RAD ALARM RM-A-5 i OPERATOR ACTIONS FOR A VALID ALARM:
o INVESTIGATE THE CAUSE OF TRIP o START AHF-19A o RESTORE VENTILATION PER OP-409 o REFER TO AP-250 DISCUSSION:
REFERENCES:
-, DRAWING 208-005 SHEET AH-87
- SENSING ELEMENT: CS/SC, CS/0, 428
!O f
AR-401 Rev. 16 Page 8
. . _- . - - . = .- - . _ - , _ - __
l i
ENCLOSURE 1
(
(Page 7 of 185)
PSA ANNUNCIATOR RESPONSE PSA-X-01-01 F-01-01 J
CNTRL COMPLEX FAN !
TRIP I
EVENT POINT 0482 l
INDICATED CONDITION:
l o AHF-20A MOTOR FAST SPEED WINDINGS ARE NOT ENERGIZED, CONTROL HANDLE IN THE PUSHED IN NORMAL AFTER START POSITION i
REDUNDANT INDICATION WHICH WILL VERIFY ALARM: I
( o
' k' GREEN FAST SPEED LIGHT ON WITH A RED FLAG ON AHF-20A CONTROL STATION !
o RADIATION HIGH RAD ALARM RM-A-5 '
o T0XIC GAS ACTUATION OPERATOR ACTIONS FOR A VALID ALARM:
o INVESTIGATE THE CAUSE OF TRIP o
NOTIFY CHEMISTRY SAMPLE HOOD VENTILATION IS SECURED o REFER TO OP-409 '
o REFER TO AP-250 OR AP-513 l
DISCUSSION:
IT MAY BE POSSIBLE TO OPERATE AHF-20A/B IN SLOW SPEED WITH AHF-44A/B IN OPERATION TO PROVIDE CHEMISTRY SAMPLE HOOD VENTILATION
REFERENCES:
,. DRAWING 208-005 SHEET AH-88
- l SENSING ELEMENT: CS/SC, CS/0, NC/LAT, 42B O
l l AR-401 Rev. 16 Page 9
i 4
ENCLOSURE 1
! i (Page 8 of 185) i PSA ANNUNCIATOR RESPONSE PSA-X-01-01 F-01-01
- CNTRL COMPLEX 1 FAN TRIP i
1 EVENT POINT 0483 1
INDICATED CONDITION:
o AHF-20A MOTOR SLOW SPEED WINDINGS ARE NOT ENERGIZED, CONTROL HANDLE IN THE PULLED OUT NORMAL AFTER START POSITION REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o O GREEN SLOW SPEED LIGHT ON WITH A RED FLAG ON AHF-20A CONTROL STATION i
OPERATOR ACTIONS FOR A VALID ALARM:
o INVESTIGATE THE CAUSE OF TRIP o NOTIFY CHEMISTRY SAMPLE HOOD VENTILATION IS SECURED o REFER TO OP-409 DISCUSSION:
REFERENCES:
DRAWING 208-005 SHEET AH-88 SEhSINGELEATNTI'CS/SC,CS/0,NC/LAT,42B O
AR-401 Rev. 16 Page 10
_ _ _ _ . _ m. - _ _ ._ .. - - . . _ . _ _ - . . _ . . . _ _ _ . . _ _ _ _ . . .. - _ .
l
() ENCLOSURE 1 (Page 9 of 185)
PSA ANNUNCIATOR RESPONSE PSA-X-01-01 F-01-01 {
CNTRL COMPLEX FAN TitlP 1
EVENT POINT 0484 i I
INDICATED CONDITION:
O AHF-208 MOTOR FAST SPEED WINDINGS ARE NOT ENERGIZED, CONTROL HANDLE IN THE PUSHED IN NORMAL AFTER START POSITION '
REDUNDANT INDICATION WHICH WILL VERIFY ALARM: 1 (j o GREEN FAST SPEED LIGHT ON WITH A RED FLAG ON AHF-208 CONTROL STATION j o RADIATION HIGH RAD ALARM RM-A-5 1 o T0XIC GAS ACTUATION OPERATOR ACTIONS FOR A VALID ALARM:
o INVESTIGATE THE CAUSE OF TRIP o NOTIFY CHEMISTRY SAMPLE HOOD VENTILATION IS SECURED o REFER TO OP-409 o REFER TO AP-250 OR AP-513 l
DISCUSSION:
IT MAY BE POSSIBLE TO OPERATE AHF-20A/B IN SLOW SPEED WITH AHF-44A/B IN OPERATION TO PROVIDE CHEMISTRY SAMPLE HOOD VENTILATION l .
REFERENCES:
,. DRAWING 208-005 SHEET AH-89
- SENSING ELEMENT: CS/SC, CS/0, NC/LAT, 428
- O i
AR-401 Rev. 16 Page 11
g ENCLOSURE 1 g (Page 10 of 185)
PSA ANNUNCIATOR RESPONSE PSA-X-01-01 F-01-01 1
j ,
CNTRL COMPLEX
, j FAN
- TRIP 4 I i l l
EVENT POINT 0485 e
j- INDICATED CONDITION:
o AHF-20B MOTOR SLOW SPEED WINDINGS ARE NOT ENERGIZED, CONTROL HANDLE IN THE PULLED OUT NORMAL AFTER START POSITION 1
REDUNDANT INDICATION WHICH WILL VERIFY ALARM- I o
GREEN SLOW SPEED LIGHT ON WITH A RED FLAG ON AHF-208 CONTROL STATION I
i OPERATOR ACTIONS FOR A VALID ALARM:
o INVESTIGATE THE CAUSE OF TRIP o NOTIFY CHEMISTRY SAMPLE HOOD VENTILATION IS SECURED o REFER TO OP-409 DISCUSSION: (
REFERENCES:
-, DRAWING 208-005 SHEET AH-89
- SENSING ELEMENT: CS/SC, CS/0, NC/LAT, 428 O
AR-401 Rev. 16 Page 12
, 1 a
i
() ENCLOSURE 1 (Page 11 of 185) i PSA ANNUNCIATOR RESPONSE PSA-X-01-01 F-01-01 CNTRL COMPLEX FAN TRIP t EVENT POINT 0489 4
a INDICATED CONDITION:
I o AHF-21A MOTOR IS NOT ENERGIZED WITH THE CONTROL HANDLE IN NORMAL AFTER 1 START POSITION REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
() o GREEN LIGHT ON WITH A RED FLAG ON AHF-21A CONTROL STATION o RADIATION HIGH RAD RM-A-5 o T0XIC GAS ACTUATION l OPERATOR ACTIONS FOR A VALID ALARM:
o INVESTIGATE THE CAUSE OF TRIP o REFER TO AP-250 OR AP-513 o START AHF-21B i o RESTORE VENTILATION PER OP-409 i
DISCUSSION: ,
l 4
REFERENCES:
- DRAWING 208-005 SHEET AH-91
- SENSING ELEMENT: CS/SC, CS/0, 42B AR-401 Rev. 16 Page 13 1
ENCLOSURE 1 (Page 12 of 185)
PSA ANNUNCIATOR RESPONSF PSA-X-01-01 F-01-01 '
. ------ l CNTRL COMPLEX FAN TRIP 1
EVENT POINT 0490 INDICATED CONDITION:
o AHF-21B MOTOR IS NOT ENERGIZED WITH THE CONTROL HANDLE IN NORMAL AFTER START POSITION REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o GREEN LIGHT ON WITH A RED FLAG ON AHF-21B CONTROL STATION O RADIATION HIGH RAD RM-A-5 o T0XIC GAS ACTUATION '
OPERATOR ACTIONS FOR A VALID ALARM:
o INVESTIGATE THE CAUSE OF TRIP o REFER TO AP-250 OR AP-513 o START AHF-21A o RESTORE VEhflLATION PER OP-409 '
4 DISCUSSION:
4
REFERENCES:
-,_ DRAWING 208-005 SHEET AH-92
- SENSING ELEMENT: CS/SC, CS/0, 428 O
AR-401 Rev. 16 Page 14
/ ENCLOSURE 1 (Page 13 of 185)
PSA ANNUNCIATOR RESPONSE PSA-X-01-01 F-01-01 CNTRL COMPLEX FAN TRIP EVENT POINT 0491 INDICATED CONDITION:
o AHF-30 MOTOR IS NOT ENERGIZED WITH THE CONTROL HANDLE IN NORMAL AFTER START POSITION REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o GREEN LIGHT ON WITH A RED FLAG ON AHF-30 CONTROL STATION o T0XIC GAS ACTUATION o RADIATION HIGH RAD ALARM RM-A5 OPERATOR ACTIONS FOR A VALID ALARM:
o INVESTIGATE THE CAUSE OF TRIP o REFER TO OP-409 o REFER TO AP-250 OR AP-513 DISCUSSION:
REFERENCES:
-,. DRAWING 208-005 SHEET AH-93
- j SENSING ELEMENT: CS/SC, CS/0, 42B iO AR-401 Rev. 16 Page 15 l
ENCLOSURE 1
( (Page 14 of 185)
PSA ANNUNCIATOR RESPONSE PSA-X-01-02 F-01-02 CNTRL COMPLEX <
AIR FLOW LOW EVENT POINT 0308 INDICATED CONDITION:
o AIR FLOW FROM "A" BATTEPY ROOM IS LOW AS SENSED BY AH-734-FS REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o POSSIBLE FIRE DAMPER ALARMS OPERATOR ACTIONS FOR A VALID ALARM:
o INVESTIGATE THE CAUSE OF ALARM o CHECK FOR FIRE DAMPER OPERATION o HAVE CHEMISTRY SAMPLE BATTERY ROOM FOR H, CONCENTRATIONS DISCUSSION:
THIS CONDITION MAY BE THE RESULT OF A FIRE DAMPER ACTUATION, CHECK FIRE DAMPERS IN THE CORRECT POSITION. THIS LOSS OF FLOW FROM THE BATTERY ROOM COULD RESULT IN A BUILD UP OF HYDROGEN INSIDE THE BATTERY R00M.
CONSIDERATION SHOULD BE GIVEN TO VENTILATING THE AREA TO PREVENT THE POSSIBILITY OF AN EXPLOSIVE MIXTURE DEVELOPING.
REFERENCES:
.,. DRAWING 208-005 SHEET AH-131
- SENSING ELEMENT: AH-734-FS O
AR-401 Rev. 16 Page 16
.. .-. - .-- _ - - ~ . - - - - ~ -~ - = _ . . . _ . . . - - . . . _ . . . - . = _ _ . . .- ~ ..
4 ENCLOSURE 1
. () (Page 15 of 185)
PSA ANNUNCIATOR RESPONSE PSA-X-01-02 F-01-02 4
CNTRL COMPLEX ;
AIR FLOVV i LOVV l l
i l l EVENT POINT 0309 1
i INDICATED CONDITION:
i o AIR FLOW FROM "B" BATTERY ROOM IS LOW AS SENSED BY AH-735-FS i
REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
- () o POSSIBLE FIRE DAMPER ALARMS 1
j OPERATOR ACTIONS FOR A VALID ALARM:
' o INVESTIGATE THE CAUSE OF ALARM o CHECK FOR FIRE DAMPER OPERATION j o HAVE CHEMISTRY SAMPLE BATTERY ROOM FOR 2H CONCENTRATIONS DISCUSSION:
THIS CONDITION MAY BE THE RESULT OF A FIRE DAMPER ACTUATION, CHECK FIRE DAMPERS IN THE CORRECT POSITION. THIS LOSS OF FLOW FROM THE BATTERY ROOM COULD RESULT IN A BUILD UP 0F HYDROGEN INSIDE THE BATTERY ROOM.
CONSIDERATION SHOULD BE GIVEN TO VENTILATING THE AREA TO PREVENT THE POSSIBILITY OF AN EXPLOSIVE MIXTURE DEVELOPING.
REFERENCES:
_ DRAWING 208-005 SHEET AH-131
- SENSING ELEMENT: AH-735-FS AR-401 Rev. 16 Page 17
n ENCLOSURE 1 Q (Page 16 of 185)
PSA ANNUNCIATOR RESPONSE PSA-X-01-02 F-01-02 l
l !
CNTRL COMPLEX l l AIR FLOW !
l _
LOW l
EVENT POINT 0442 INDICATED CONDITION:
o AHF-16A CONTROL HANDLE IN NORMAL AFTER START, AND DIFFERENTIAL PRESSURE ACROSS AHHE-10A IS <0.063"H O 2 AS SENSED BY AH-123-DPS i
REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o AHF-16A TRIPPED l 0 FIRE DAMPER ALERTS OPERATOR ACTIONS FOR A VALID ALARM:
o INVESTIGATE THE CAUSE OF ALARM o CHECK FOR FIRE DAMPER OPERATION o START AHF-16B TO SUPPL ( SWITCHGLAR ROOMS DISCUSSION:
THIS CONDITION MAY BE THE RESULT OF A FIRE DAMPER ACTUATION, CHECK F' IRE DAMPER POSITION.
REFERENCES:
. DRAWING 208-005 SHEET AH-058, DRAWING 308846
- l SENSING ELEMENT: AH-123-DPS lO I
AR-401 Rev. 16 Page 18
.- . _ _ . _ - = _ _ . . .- . .. - .. ..
3
() ENCLOSURE 1 (Page 17 of 185)
! PSA ANNUNCIATOR RESPONSE PSA-X-01-02 F-01-02 l
i CNTRL COMPLEX SUR FLO>VV LOVW
,i i
EVENT POINT 0446 i
INDICATED CONDITION:
o AHF-168 CONTROL HANDLE IN NORMAL AFTER START, AND DIFFERENTIAL PRESSURE ACROSS AHHE-10B IS <0.050"H O 2 AS SENSED BY AH-124-DPS REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o AHF-16B TRIPPED
_,/ o FIRE DAMPER ALERTS l
OPERATOR ACTIONS FOR A VALID ALARM:
o INVESTIGATE THE CAUSE OF ALARM o CHECK FOR FIRE DAMPER OPERATION o START AHF-16A TO SUPPLY SWITCHGEAR ROOMS DISCUSSION:
THIS CONDITION MAY BE THE RESULT OF A FIRE DAMPER ACTUATION, CHECK FIRE DAMPER POSITION.
REFERENCES:
DRAWING 208-005 SHEET AH-059, DRAWING 308846 SENSINGELEsthTT'AH-124-0PS O
AR-401 Rev. 16 Page 19
g~s l ENCLOSURE 1 gj (Page 18 of 185)
PSA ANNUNCIATOR RESPONSE PSA-X-01-02 F-01-02 CNTRL COMPLEX AIR FLOW LOW EVENT POINT 0468 INDICATED CONDITION:
o AHF-17A, OR AHF-18A CONTROL HANDLE IN NORMAL AFTER START AND A LOW FLOW CONDITION EXISTS IN DUCT WORK OF <0.15"H,0 AS SENSED BY AH-34-DPS REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o LOW FLOW INDICATION ON AH-32-FIR g'q o POSSIBLE FAN TRIP ALARMS OPERATOR ACTIONS FOR A VALID ALARM:
o INVESTIGATE THE CAUSE OF ALARM o ALTERNATE VENTILATION EQUIPMENT TO CLEAR ALARM o REFER TO OP-409 DISCUSSION:
THIS CONDITION MAY BE THE RESULT OF A FAN TRIP, OR A FLOW BLOCKAGE.
ALTERNATING VENTILATION EQUIPMENT SHOULD CORRECT THE CONDITION.
REFERENCES:
DRAWING 208-005 SHEET AH-080, DRAWING 308847 SENSING ELET4ENT':' AH-34-DPS rh U
AR-401 Rev. 16 Page 20
l ENCLOSURE 1 (Page 19 of 105)
PSA ANNUNCIATOR RESPONSE PSA-X-01-02 F-01-02 CNTRL COMPLEX AIR FLOW LOW EVENT POINT 0480 INDICATED CONDITION:
o AHF-19A CONTROL HANDLE IN NORMAL AFTER START AND A LOW FLOW CONDITION EXISTS IN DUCT WORK OF <0.10" H,0 AS SENSED BY AH-176-DPS REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o POSSIBLE FAN TRIP ALARMS O o FIRE DAMPER ALERTS OPERATOR ACTIONS FOR A VALID ALARM:
o INVESTIGATE THE CAUSE OF ALARM o CHECK FOR TRIPPED FIRE DAMPERS o ALTERNATF-VENTILATION EQUIPMENT TO CLEAR ALARM o REFER TO OP-409 DISCUSSION:
THIS CONDITION MAY BE THE RESULT OF A FAN TRIP, OR A FIRE DAMPER ACTUATION. IF ALTERNATING VENTILATION EQUIPMENT DOES NOT CORRECT THE CONDITION THERE IS PROBABLY A FIRE DAMPER TRIPPED.
REFERENCES:
DRAWING 208-005 SHEET AH-086, DRAWING 306847 SENSING ELEMENT: AH-176-DPS O
AR-401 Rev. 16 Page 21
/^T ENCLOSURE 1 Q (Page 20 of 185)
PSA ANNUNCIATOR RESPONSE PSA-X-01-02 F-01-02 CNTRL COMPLEX AIR FLOW LOW EVENT POINT 0486 INDICATED CONDITION:
o AHF-20A CONTROL HANDLE IN NORMAL AFTER START AND A LOW FLOW CONDITICN EXISTS IN DUCT WORK 0F <0.08"H g0 AS SENSED BY AH-36-DPS REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o POSSIBLE FAN TRIP ALARMS O o FIRE DAMPER ALERTS OPERATOR ACTIONS FOR A VALID ALARM:
o INVESTIGATE THE CAUSE OF ALARM o CHECK FOR TRIPPED FIRE DAMPERS o ALTERNATE VENTILATION EQUIPMENT TO CLEAR ALARM o REFER TO OP-409 DISCUSSION:
THIS CONDITION MAY BE THE RESULT OF A FAN TRIP, OR A FIRE DAMPER ACTUATION.
IF ALTERNATING VENTILATION EQUIPMENT DOES NOT CORRECT THE CONDITION THERE IS PROBABLY A FIRE DAMPER TRIPPED.
THIS IS AN EXPECTED ALARM WHEN AHF-20A IS BEING RUN IN SLOW SPEED.
REFERENCES:
DRAWING 208-005 SHEET AH-088, DRAWING 308847 SENSING ELEME'NTT AH-36-DPS o
U AR-401 Rev. 16 Page 22
. - . . _ _ - . . - . - .~ - _ - _ - . - . . .. .
L m
l ENCLOSURE 1 l
.h (Page 21 of 185)
PSA ANNUNCIATOR RESPONSE PSA-X-01-02 F-01-02 CNTRL COMPLEX AIR FLOW LOW EVENT POINT 1545 INDICATED CONDITION:
O AHF-178, OR AHF-18B CONTROL HANDLE IN NORMAL AFTER START AND A LOW FLOW CONDITION EXISTS IN DUCT WORK 0F <0.15"H,0 AS SENSED BY AH-546-DPS i REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
4
' o LOW FLOW INDICATION ON AH-32-FIR ;
o POSSIBLE FAN TRIP ALARMS OPERATOR ACTIONS FOR A VALID ALARM:
o INVESTIGATE THE CAUSE OF ALARM o ALTERNATE VENTILATION EQUIPMENT TO CLEAR ALARM <
o REFER TO OP-409 DISCUSSION:
THIS CONDITION MAY BE THE RESULT OF A FAN TRIP, OR A FLOW BLOCKAGE.
ALTERNATING VENTILATION EQUIPMENT SHOULD CORRECT THE CONDITION.
l
REFERENCES:
DRAWING 208-005 SHEET AH-081, DRAWING 308847
! SENSING ELEIilNi~:' AH-546-DPS I
lO i
l AR-401 Rev. 16 Page 23
M l ENCLOSURE I i (Page 22 of 185) l PSA ANNUNCIATOR RESPONSE PSA-X-01-02 F-01-02 1
, CNTRL COMPLEX AIR FLOW LOW EVENT POINT 1546 i
INDICATED CONDITION:
l o
AHF-19B CONTROL HANDLE IN NORMAL AFTER START AND A LOW FLOW CONDITION EXISTS IN DUCT WORK OF <0.10"H,0 AS SENSED BY AH-547-DPS REDUNDANT INDICATION WHICH WILL VERIFY ALARM: I o POSSIBLE FAN TRIP ALARMS O o FIRE DAMPER ALERTS OPERATOR ACTIONS FOR A VALID ALARM:
o INVESTIGATE THE CAUSE OF ALARM o CHECK FOR TRIPPED FIRE DAMPERS o ALTERNATE VENTILATION EQUIPMENT TO CLEAR ALARM o REFER TO OP-409 DISCUSSION:
THIS CONDITION MAY BE THE RESULT OF A FAN TRIP, OR A FIRE DAMPER ACTUATION. IF ALTERNATING VENTILATION EQUIPMENT DOES NOT CORRECT THE CONDITION THERE IS PROBABLY A FIRE DAMPER TRIPPED.
REFERENCES:
DRAWING 208-005 SHEET AH-086, ORAWING 308847 SENSING ELERENW AH-547-DPS O
AR-401 Rev. 16 Page 24
i 4
ENCLOSURE I (Page 23 of 185)
- PSA ANNUNCIATOR RESPONSE PSA-X-01-02 F-01-02 l
CNTRL COMPLEX 4
AIR FLOW !
Low
~
EVENT POINT 1547 i l
INDICATED CONDITION:
s )
o AHF-20B CONTROL HANDLE IN NORMAL AFTER START AND A LOW FLOW CONDITION EXISTS IN DUCT WORK 0F <0.08"H,0 AS SENSED BY AH-548-DPS i REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
O POSSIBLE FAN TRIP ALARMS
- o FIRE DAMPER ALERTS OPERATOR ACTIONS FOR A VALID ALARM
O INVESTIGATE THE CAUSE OF ALARM i
o CHECK FOR TRIPPED FIRE DAMPERS 0 ALTERNATE VENTILATION EQUIPMENT TO CLEAR ALARM i o REFER TO OP-409 i
f DISCUSSION:
THIS CONDITION MAY BE THE RESULT OF A FAN TRIP, OR A FIRE DAMPER ACTUATION.
IF ALTERNATING VENTILATION EQUIPMENT DOES NOT CORRECT THE CONDITION THERE IS PROBABLY A FIRE DAMPER TRIPPED.
' THIS IS AN EXPECTED ALARM WHEN AHF-208 IS BEING RUN IN SLOW SPEED.
4
REFERENCES:
DRAWING 208-005 SHEET AH-089, DRAWING 308847 SENSING ELEM[NTT AH-548-DPS j
!O AR-401 Rev. 16 Page 25
a t
ENCLOSURE 1 (Page 24 of 185) i
- PSA ANNUNCIATOR RESPONSE PSA-X-01-03 F-01-03 AH Ft.TR 4A/B PRESS HIGH i EVENT POINT 0476 INDICATED CONDITION
o A HIGH DIFFERENTIAL PRESSURE EXISTS ACROSS AHFL-4A 0F >5.20"H,0 AS SENSED BY AH-205-DPS i
REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
.f g o DIFFERENTIAL PRESSURE INDICATOR AH-205-DPII ON REAR OF MCB Q o POSSIBLE FAN TRIP ALARMS o FIRE DAMPER ALARMS OPERATOR ACTIONS FOR A VALID ALARM:
o ALTERNATE VENTILATION EQUIPMENT TO CLEAR ALARM o REFER TO OP-409 DISCUSSION:
THIS CONDITION MAY BE lHE RESULT OF A FAN TRIP, OR A FIRE DAMPER ACTUATION.
IF ALTERNATING VENTILATION EQUIPMENT DOES NOT CORRECT THE CONDITION THERE IS PROBABLY A FIRE DAMPER TRIPPED.
REFERENCES:
DRAWING 208-005 SHEET AH-I31, DRAWING 308847 SENSING ELEfiENG' AH-205-DPS O
Lj AR-401 Rev. 16 Page 26
ENCLOSURE I (Page 25 of 185)
PSA ANNUNCIATOR RESPONSE PSA-X-01-03 F-01-03 AH FLTR 4A/B PRESS HIGH 1
EVENT POINT 0477 INDICATED CONDITION:
O A HIGH DIFFERENTIAL PRESSURE EXISTS ACROSS AHFL-48 0F >5.20"H 2 0 AS SENSED BY AH-206-DPS REDUNDANT INDICATION WHICH WIll VERIFY ALARM:
J o
DIFFERENTIAL PRESSURE INDICATOR AH-206-DPII ON REAR OF MCB o POSSIBLE FAN TRIP ALARMS o FIRE DAMPER ALARMS OPERATOR ACTIONS FOR A VALID ALARM:
o AllERNATE VENTILATION EQUIPMENT TO CLEAR ALARM o REFER TO OP-409 BISCUSSION:
THIS CONDITION MAY BE THE RESULT OF A FAN TRIP, OR A FIRE DAMPER ACTUATION.
IF ALTERNATING VENTILATION EQUIPMENT DOES NOT CORRECT THE CONDITION THERE IS PROBABLY A FIRE DAMPER TRIPPED.
REFERENCES:
DRAWING 208-005 SHEET AH-131, DRAWING 308847 SEOSING ELEMTNTi' AH-206-DPS O
l AR-401 Rev. 16 Page 27
,Q ENCLOSURE 1 V (Page 26 of 185)
PSA ANNUNCIATOR RESPONSE PSA-X-01-04 F-01-04 CNTRL COMPLEX DUCT TEMP HIGH EVENT POINT 0469 INDICATED CONDITION:
o HIGH TEMPERATURE OF >135'F EXISTS IN THE CONTROL COMPLEX SUPPLY DUCT AS SENSED BY AH-207-TS, REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o POSSIBLE FAN TRIP ALARMS O o FIRE DAMPER ALARMS OPERATOR ACTIONS FOR A VALID ALARM:
o INVESTIGATE HIGH TEMPERATURE ALARM o REFER TO OP-409 o REFER TO AP-880 DISCUSSION:
THIS CONDITION MAY BE THE RESULT OF A FIRE IN THE DUCT. IF S0 A FIRE DAMPER ACTUATION IS AN INDICATION OF A VALID ALARM.
REFERENCES:
DRAWING 208-005 SHEET AH-080, DRAWING 308847 SENSING ELEMlNTT AH-207-TS AR-401 Rev. 16 Page 28
a ENCLOSURE 1 '
(Page 27 of 185) i PSA ANNUNCIATOR RESPONSE PSA-X-01-04 F-01-04 4 i N
CNTRL COMPLEX DUCT TEMP HIGH 1
5
- EVENT POINT 0487 ,
INDICATED CONDITION: '
i o
HIGH TEMPERATURE OF >135'F EXISTS IN THE DISCHARGE OF AHF-20A DUCT AS SENSED BY AH-258-TS, l'
REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
- O POSSIBLE FAN TRIP ALARMS o FIRE DAMPER ALARMS j OPERATOR ACTIONS FOR A VALID ALARM:
o INVESTIGATE HIGH TEMPERATURE ALARM i o REFER TO OP-409 o REFER TO AP-880 l
DISCUSSION:
i T!ilS CONDITION MAY BE THE RESULT OF A FIRE IN THE DUCT. IF SO A FIRE DAMPER ACTUATION IS AN INDICATION OF A VALID ALARM.
REFERENCES:
DRAWING 208-005 SHEET AH-088, DRAWING 308847 SENSING ELEMTNTT AH-258-TS
!,O 4
AR-401 Rev. 16 Page 29
'k f-ENCLOSURE 1
( (Page 28 of 185)
, PSA ANNUNCIATOR RESPONSE PSA-X-01-04 F-01-04 1
CNTRL COMPLEX !
DUCT TEMP HIGH I
EVENT POINT 0517 ,
INDICATED CONDITION:
o HIGH TEMPERATURE EXISTS OF >135'F IN THE DISCHARGE OF AHF-20B DUCT AS SENSED BY AH-543-TS, i I
REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o POSSIBLE FAN TRIP ALARMS
- O O FIRE DAMPER ALARMS OPERATOR ACTIONS F0P A VALID ALARM:
o INVESTIGATE HIGH TEMPERATURE ALARM o REFER TO OP-409 o REFER TO AP-880 DISCUSSION:
THIS CONDITION MAY BE THE RESULT OF A FIRE IN THE DUCT. IF SO A FIRE DAMPER ACTUATION IS AN INDICATION OF A VALID ALARM.
REFERENCES:
DRAWING 208-005 SHEET AH-089, DRAWING 308847 i SENSING ELEMlNTi' AH-543-TS AR-401 Rev. 16 Page 30
ENCLOSURE 1
(- (Page 29 of 185)
PSA ANNUNCIATOR RESPONSE PSA-X-01-04 F-01-04 4
CNTRL COMPLEX DUCT TEMP HIGH EVENT POINT 0493
- INDICATED CONDITION:
o HIGH TEMPERATURE OF >l35'F EXISTS IN THE CONTROL COMPLEX RETURN DUCT ON ll ELEVATION 124' AS SENSED BY AH-191-TS 1
REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
q
' O POSSIBLE LOW AIR FLOW ALARMS o FIRE DAMPERS FD-28, AND FD-29 ACTUATE l 4
0PERATOR ACTIONS FOR A VALID ALARM:
o INVESTIGATE HIGH TEMPERATURE ALARM o REFER TO OP-409 i o REFER TO AP-880 4 4 i ,
t 3 DISCUSSION: I J ,
THIS CONDITION MAY BE THE RESULT OF A FIRE IN THE DUCT. IF SO A FIRE I DAMPER ACTUATION IS AN INDICATION OF A VALID ALARM.
]
s
REFERENCES:
DRAWING 208-005 SHEET AH-101, DRAWING 308847
\
SENSING ELERTNTT' AH-191-TS
- O I i
AR-401 Rev. 16 Page 31
p i
ENCLOSURE 1 (Page 30 of 185)
PSA ANNUNCIATOR RESPONSE PSA-X-01-05 F-01-05 CNTRL COMPLEX INST AIR PRESS LOW EVENT POINT 1690 INDICATED CONDITION:
O AIR PRESSURE IN THE RECEIVER OF AHP-1A/lB AS SENSED BY AH-507-PS IS
<55 PSIG I
REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o LOCAL PRESSURE INDICATOR AH-896C-PI ON JOHNSON CONTROL PANEL 25A 1
OPERATOR ACTIONS FOR A VALID ALARM:
o ENSURE THAT AHP-1A/lB ARE RUNNING o
O VERIFY SAV-406 AND SAV-405 (CC STATION AIR SUPPLY VALVES) OPEN o DEENERGIZE AH-517-SV (CC CONTROL AIR SUPPLY VALVE)
ENERGIZE AH-518-SV (CC CONTROL AIR SUPPLY VALVE)
DISCUSSION:
THIS CONDITION MAY RESULT IN THE LOSS OF CONTROL AIR TO CONTROL COMPLEX VENTILATION SYSTEM "A" COMPONENTS AND A LOSS OF "A" SYSTEM AIR TD "AB" SYSTEM COMPONENTS.
REFERENCES:
DRAWING 208-005 SHEET AH-148 SENSING ELdisNTT AH-507-PS O
AR-401 Rev. 16 Page 32
- . _. . . . . . _-. -= -. _. . . _
1 1
' ENCLOSURE 1 (Page 31 of 185)
PSA ANNUNCIATOR RESPONSE PSA-X-01-05 F-01-05 a
CNTRL COMPLEX
- INST AIR PRESS LOW EVENT POINT 1691 1
INDICATED CONDITION:
o AIR PSIG PRESSURE IN THE RECEIVER OF AHP-lC/lD AS SENSED BY AH-509-PS IS <55 1
REDUNDANTINDICATIONWHICHWILLVEk[FYALARM:
O LOCAL PRESSURE INDICATOR AH-894C-PI ON JOHNSON CONTROL PANEL 25B I
OPERATOR ACTIONS FOR A VALID ALARM:
o ENSURE THAT AHP-lC/1D ARE RUNNING o
o VERIFY SAV-406 AND SAV-405 (CC STATION AIR SUPPLY VALVES) OPEN o DEENERGIZE AH-517-SV (CC CONTROL AIR SUPPLY VALVE)
ENERGIZE AH-518-SV (CC CONTROL AIR SUPPLY VALVE)
DISCUSSION:
THIS CONDITION MAY RESULT IN THE LOSS OF CONTROL AIR TO CONTROL COMPLEX VENTILATION SYSTEM "B" COMP 0NENTS AND A LOSS OF "B" SYSTEM AIR T0 "AB" SYSTEM COMPONENTS.
REFERENCES:
DRAWING 208-005 SHEET AH-149 SENSING ELEMlNTT AH-509-PS A
V AR-401 Rev. 16 Page 33
ENCLOSURE 1 (Page 32 of 185)
PSA ANNUNCIATOR RESPONSE PSA-X-01-05 F-01-05 CNTRL COMPLEX INST AIR PRESS LOW EVENT POINT 1692 INDICATED CONDITION:
o REGULATED "A" SIDE CONTROL AIR AS SENSED BY AH-512-PS IS <17 PSIG REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o LOCAL PRESSURE INDICATOR AH-8968-PI ON JOHNSON CONTROL PANEL 25A
(
OPERATOR ACTIONS FOR A VALID ALARM:
o ENSURE THAT AHP-1A/lB ARE RUNNING o
o VERIFY SAV-406 AND SAV-405 (CC STATION AIR SUPPLY VALVES) OPEN o DEENERGIZE AH-517-SV (CC CONTROL AIR SUPPLY VALVE)
ENERGIZE AH-518-SV (CC CONTROL AIR SUPPLY VALVE)
DISCUSSION:
THIS CONDITION MAY RESULT IN THE LOSS OF CONTROL AIR TO CONTROL COMPLEX VENTILATION SYSTEM "A" COMPONENTS AND A LOSS OF "A" SYSTEM AIR TO "AB" SYSTEM COMPONENTS.
REFERENCES:
DRAWING 208-005 SHEET AH-150 SENSING ELE ENTT AH-512-PS O
AR-401 Rev. 16 Page 34
l r~ ENCLOSURE 1
( (Page 33 of 185)
PSA ANNUNCIATOR RESPONSE PSA-X-01-05 F-01-05 CNTRL COMPLEX INST AIR PRESS LOVV EVENT POINT 1693 INDICATED CONDITION:
o AIR PRESSURE FOR DAMPER CONTROL AS SENSED BY AH-513-PS IS <17 PSIG J
REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
g- g o '
LOCAL PRESSURE INDICATOR AH-8958-PI ON JOHNSON CONTROL PANEL 25AB V
OPERATOR ACTIONS FOR A VALID ALARM:
o ENSURE THAT AHP-1A/lB ARE RUNNING o
o VERIFY SAV-406 AND SAV-405 (CC STATION AIR SUPPLY VALVES) OPEN o DEENERGIZE AH-517-SV (CC CONTROL AIR SUPPLY VALVE)
ENERGIZE AH-518-SV (CC CONTROL AIR SUPPLY VALVE) >
DISCUSSION:
THIS CONDITION MAY RESULT IN THE LOSS OF CONTROL AIR TO CONTROL COMPLEX VENTILATION SYSTEM COMPONENTS
REFERENCES:
DRAWING 208-005 SHEET AH-150 SENSING ELE 5ENTT' AH-513-PS O
V AR-401 Rev. 16 Page 35
ENCLOSURE 1 '.
(Page 34 of 185)
PSA ANNUNCIATOR RESPONSE PSA-X-01-05 F-01-05 CNTRL COMPLEX INST AIR PRESS LOW EVENT POINT 1694 INDICATED CONDITION:
o REGULATED "B" SIDE CONTROL AIR AS SENSED BY AH-514-PS IS <17 PSIG REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o I LOCAL PRESSURE INDICATOR AH-894B-PI ON JOHNSON CONTROL PANEL 25B i
v !
OPERATOR ACTIONS FOR A VALID ALARM:
- o. ENSURE THAT AHP-1C/1D ARE RUNNING o
O VERIFY SAV-406 AND SAV-405 (CC STATION AIR SUPPLY VALVES) OPEN o DEENERGIZE AH-518-SV (CC CONTROL AIR SUPPLY VALVE)
ENERGIZE AH-517-SV (CC CONTROL AIR SUPPLY VALVE)
DISCUSSION:
THIS CONDITION MAY RESULT IN THE LOS5 0F CONTROL AIR TO CONTROL COMPLEX VENTILATION SYSTEM "B" COMPONENTS AND A LOSS OF "B" SYSTEM AIR T0 "AB" SYSTEM COMPONENTS.
REFERENCES:
DRAWING 208-005 SHEET AH-150
[ SENSING ELEfi(NTT AH-514-PS O
- AR-401 Rev. 16 l Page 36
4 f ENCLOSURE 1
. (Page 35 of 185)
PSA ANNUNCIATOR RESPONSE PSA-X-01-06 F-01-06 CNTRL COMPLEX AIR DRYER TEMP HIGH j
l EVENT POINT 1695 '
INDICATED CONDITION:
o AIR TEMPERATURE ON THE OUTLET OF AHDR-1A IS >45'F AS SENSED BY AH-510-TS 4
REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
O OPERATOR ACTIONS FOR A VALID ALARM:
o NOTIFY MECH SUPERVISOR IN CHARGE OF HVAC TO INSPECT AHDR-1A FOR PROPER OPERATION DISCUSSION:
AHDR-1A IS REFRIGERATED AIR DRYER WHICH UTILIZES A REFRIGERANT CYCLE TO DRY CONTROL COMPLEX CONTROL AIR SUPPLY. HIGH AIR TEMPS CAN BE CAUSED BY LOW REFRIGERANT CHARGE OR A DIRTY CONDENSER COIL.
REFERENCES:
DRAWING 208-005 SHEET AH-150 SENSING ELEMENT: AH-510-TS AR-401 Rev. 16 Page 37
s ENCLOSURE 1
( )f (Page 36 of 185)
PSA ANNUNCIATOR RESPONSE PSA-X-01-06 F-01-06 I
l CNTHL COMPLEX i AIR DRYER TEh4P HIGH EVENT POINT 1696 c INDICATED CONDITION:
o AIR TEMPERATURE ON THE OUTLET OF AHDR-18 IS >45'F AS SENSED BY AH-Sil-TS l REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
4 i
OPERATOR ACTIONS FOR A VALID ALARM:
o NOTIFY MECH SUPERVISOR IN CHARGE OF HVAC TO INSPECT AHDR-1B FOR PROPER <
OPERATION DISCUSSION: '
AHDR-1B IS REFRIGERATED AIR DRYER WHICH UTILIZES A REFRIGERANT CYCLE TO DRY CONTROL COMPLEX CONTROL AIR SUPPLY. HIGH AIR TEMPS CAN BE CAUSED BY LOW REFRIGERANT CHARGE OR A DIRTY CONDENSER COIL.
d
REFERENCES:
DRAWING 208-005 SHEET AH-150 SENSING ELEMENTI' AH-511-TS O
%)
AR-401 Rev. 16 Page 38
l p ENCLOS_U_RL1
- Q (Page 37 of 185)
PSA ANNUNCIATOR RESPONSE PSA-X-01-07 F-01-07 CHILLED WATER SYSTEM TROUBLE 1 I
EVENT POINT 0518 !
INDICATED CONDITION:
o !
CHP-1A MOTOR IS NOT ENERGIZED WITH THE CONTROL HANDLE IN THE NORMAL AFTER START POSITION !
i REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o i O GREEN LIGHT ON WITH A RED FLAG ON THE CHP-1A CONTROL STATION o RUNNING CHILLER TRIPS ON LOW CHILLED WATER FLOW i
OPERATOR ACTIONS FOR A VALID ALARM:
o START CHP-18 AND CHHE-1B PER OP-409 l
l DISCUSSION:
i l
REFERENCES:
DRAWING 208-076 SHEET CH-03 SENSING ELEfifNTT 42/5CR l
O l AR-401 Rev. 16 Page 39 l
]
7 ENCLOSURE 1 (Page 38 of 185)
PSA ANNUNCIATOR RESPONSE PSA-X-01-07 F-01-07 CHILLED WATER SYSTEM TROUBLE MI EVENT POINT 0519 INDICATED CONDITION:
o CHP-1B MOTOR IS NOT ENERGIZED WITH THE CONTROL HANDLE IN THE NORMAL AFTER START POSITION REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
/- -o GREEN LIGHT ON WITH A RED FLAG ON THE CHP-1B CONTROL STATION o RUNNING CHILLER TRIPPED ON LOW CHILLED WATER FLOW OPERATOR ACTIONS FOR A VALID ALARM:
o START CHP-1A AND CHHE-1A PER OP-409 I
l DISCUSSION:
REFERENCES:
DRAWING 208-076 SHEET CH-04 SENSING ELEMENT: CS/SC, CS/0, 42B RELAY O
AR-401 Rev. 16 Page 40
(]
(j ENCLOSURE 1 (Page 39 of 185) '
PSA ANNUNCIATOR RESPONSE PSA-X-01-07 F-01-07 l
CHILLED WATER SYSTEM i TROUBLE EVENT POINT 0520 INDICATED CONDITION:
o CHHE-1A BREAKER IS OPEN WITH CONTROL HANDLE IN THE NORMAL AFTER START !
POSITION REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o o GREEN LIGHT ON WITH A RED FLAG ON CHHE-1A CONTROL STATION U
OPERATOR ACTIONS FOR A VALID ALARM:
o HAVE BREAKER CUBICLE CHECKED FOR DROPPED TARGETS o SWAP CHILLERS PER OP-409 DISCUSSION:
AN ES BUS UNDERV0LTAGE CONDITION WILL CAUSE THIS CONDITION, THE BREAKER WILL NOT BE ABLE TO BE RECLOSED UNTIL THE UNDERV0LTAGE LOCK OUT HAS BEEN RESET.
REFERENCES:
DRAWING 208-076 SHEET CH-01 SENSING ELEECNTT CS/SC, CS/0, R/B CONTACT O
AR-401 Rev. 16 Page 41
6 ENCLOSURE I f
h (Page 40 of 185)
PSA ANNUNCIATOR RESPONSE PSA-X-01-07 F-01-07 CHILLED WATER SYSTEM TROUBLE EVENT POINT 0521 INDICATED CONDITION:
o CHHE-1B BREAKER IS OPEN WITH CONTROL HANDLE IN THE NORMAL AFTER START POSITION REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
C o GREEN LIGHT ON WITH A RED FLAG ON CHHE-1B CONTROL STATION
\
OPERATOR ACTIONS FOR A VALID ALARM:
o HAVE BREAKER CUBICLE CHECKED FOR OROPPED TARGETS o SWAP CHILLERS PER OP-409 DISCUSSION:
AN ES BUS UNDERVOLTAGE CONDITION WILL CAUSE THIS CONDITION, THE BREAKER WILL NOT BE ABLE TO BE RECLOSED UNTIL THE UNDERVOLTAGE LOCK OUT HAS BEEN RESET.
REFERENCES:
DRAWING 208-076 SHEET CH-02 SENSING ELEMENT: CS/SC, CS/0, R/B CONTACT AR-40I Rev. 16 Page 42
- _ . . . - - _. = _ . .. _ .. __ _ _ - _ _ _ - _ -
l l
I s ENCLOSURE 1
) (Page 41 of 185)
PSA ANNUNCIATOR RESPONSE PSA-X-01-07 F-01-07
} CHILLED WATER SYSTEM TROUBLE i.
(
EVENT POINT 1526 1
INDICATED CONDITION:
o CHT-1 LEVEL IS < 180' 2", OR < 12" BELOW CENTER LINE OF TANK REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o LOCAL LEVEL INDICATOR ON CHT-1 OPERATOR ACTIONS FOR A VALID ALARM:
l 0 CONTACT CHEMISTRY AND REFILL CHT-1 REFER TO OP-409 DISCUSSION:
4 i'
REFERENCES:
DRAWING 208-076 SHEET CH-06 SENSING ELESCNN' CH-660-LSS n
AR-401 Rev. 16 Page 43
~-
- ENCLOSURE 1 (Page 42 of 185)
PSA ANNUNCIATOR RESPONSE PSA-X-01-07 F-01-07 4
CHILLED WATER I SYSTEM TROUBLE EVENT POINT 1554 INDICATED CONDITION:
o CHHE-1A BREAKER HAS NO DC CONTROL POWER REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
O NO INDICATING LIGHTS ON CHHE-1A CONTROL STATION i OPERATOR ACTIONS FOR A VALID ALARM:
o VERIFY " PULL OUT" FUSE BLOCK FOR CHHE-1A BREAKER IS INSTALLED o VERIFY DPDP-5A BREAKER 9 CLOSED DISCUSSION:
THIS CONDITION DISABLES REMOTE BREAKER OPERATION AND PROTECTIVE RELAYING.
REFER TO OP-703 FOR INSTRUCTIONS ON LOCAL BREAKER OPERATION.
THIS IS AN EXPECTED ALARM FOR BREAKER TAGGING OPERATIONS.
REFERENCES:
DRAWING 208-076 SHEET CH-01 SENSING ELEMsNTT 27C RELAY O
V AR-401 Rev. 16 Page 44
()
ENCLOSURE 1 (Page 43 of 185) 1 PSA ANNUNCIATOR RESPONSE PSA-X-01-07 F-01-07 CHILLED WATER SYSTER4 TROUBLE i
l EVENT POINT 1555 INDICATED CONDITION:
o CHHE-1B BREAKER HAS NO DC CONTROL POWER REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o O NO INDICATING LIGHTS ON CHHE-IB CONTROL STATION OPERATOR ACTIONS FOR A VALID ALARM:
o VERIFY PULL OUT FUSE BLOCK FOR CHHE-18 BREAKER IS INSTALLED o VERIFY DPDP-5B BREAKER 9 CLOSED DISCUSSION:
THIS CONDITION DISABLES REMOTE BREAKER OPERATION AND PROTECTIVE RELAYING.
REFER TO OP-703 FOR INSTRUCTIONS ON LOCAL BREAKER OPERATION.
THIS IS AN EXPECTED ALARM FOR BREAKER TAGGING OPERATIONS.
REFERENCES:
DRAWING 208-076 SHEET CH-02
~
SENSING ELEMENT: 27C RELAY d
AR-401 Rev. 16 Page 45
es ENCLOSURE 1
) (Page 44 of 185) q 1
PSA ANNUNCIATOR RESPONSE PSA-X-01-07 F-01-07 1
CHILLED WATER ;
SYSTEM j TROUBLE l EVENT POINT 1556 INDICATED CONDITION:
o CHHE-1A MOTOR WINDING TEMPERATURE IS >105'C, OR CHHE-1A OIL TEMPERATURE IS >170*F.
REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
O o LOCAL CONTROL PANEL - RED INDICATOR LIGHT IS ON FOR "0ll/ MOTOR i,j TEMPERATURE" OPERATOR ACTIONS FOR A VALID ALARM:
o SWAP CHILLERS PER OP-409 DISCUSSION:
THIS CONDITION WILL CAUSE THE CHILLER TO TRIP, THE CONDITION SEALS IN UNTIL THE RESET PUSHBUTTON IS DEPRESSED F4TERENCES: DRAWING 208-076 SHEET CH-05 SENSING ELEMENT: 6R, 2/A AR-401 Rev. 16 Page 46
fg ENCLOSURE 1
( j (Page 45 of 185)
PSA ANNUNCIATOR RESPONSE PSA-X-01-07 F-01-07 CHILLED MfATER SYSTEM TRCHJBLE EVENT POINT 1557 INDICATED CONDITION:
o CHHE-1A REFRIGERANT PRESSURE IS <17.9"HGA REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
rN o LOCAL CONTROL PANEL - RED INDICATOR LIGHT IS ON FOR " LOW PRESSURE" U
OPERATOR ACTIONS FOR A VALID ALARM:
o SWAP CHILLERS PER OP-409 DISCUSSION:
THIS CONDITION WILL CAUSE THE CHILLER TO TRIP, THE CONDITION SEALS IN UNTIL THE RESET PUSHBUTTON IS DEPRESSED
REFERENCES:
DRAWING 208-076 SHEET CH-05 SENSING ELEMENT: 7R, 2/A O
AR-401 Rev. 16 Page 47
l s
ENCLOSURE 1 (s) (Page 46 of 185)
PSA ANNUNCIATOR RESPONSE PSA-X-01-07 F-01-07 1
CHILLED WATER SYSTEh4 TROUBLE EVENT POINT 1558 INDICATED CONDITION:
o CHHE-1A REFRIGERANT PRESSURE IS >9 PSIG REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o O LOCAL CONTROL PANEL - RED INDICATOR LIGHT IS ON FOR "HIGH PRESSURE" OPERATOR ACTIONS FOR A VALID ALARM:
O SWAP CHILLERS PER OP-409 l
DISCUSSION:
THIS CONDITION WILL CAUSE THE CHILLER TO TRIP, THE CONDITION SEALS IN UNTIL THE RESET PUSHBUTTON IS DEPRESSED
REFERENCES:
DRAWING 2,8-076 SHEET CH-05 SENSING ELEMENT: 8R, 2/A AR-401 Rev. 16 Page 48
. -- _ _ . - . _ . . _ ~ ..- - - - _ - - __-_=. _ --- -_-
4 ENCLOSURE 1
( (Page 47 of 185) 1 PSA ANNUNCIATOR RESPONSE PSA-X-01-07 F-01-07 l
CHILLED WATER 1
SYSTERA
- TROUBLE i i
)
EVENT POINT 1559 1
INDICATED CONDITION:
- o CHHE-IA OIL PRESSURE IS < 27 PSIG l
REDUNDANT INDICATION WHICH WILL VERIFY ALARM: l o
O LOCAL CONTROL PANEL - RED INDICATOR LIGHT IS ON FOR " LOW OIL PRESS" i
l OPERATOR ACTIONS FOR A VALID ALARM:
o SWAP CHILLERS PER OP-409 ,
DISCUSSION:
THIS CONDITION WILL CAUSE THE CHILLER TO TRIP, THE CONDITION SEALS IN UNTIL THE RESET PUSHBUTTON IS DEPRESSED
REFERENCES:
DRAWING 208-076 SHEET CH-05 SENSING ELEMENT: 9R, 2/A v
AR-401 Rev. 16 Page 49
l O ENCLOSURE 1 l (d
(Page 48 of 185) i PSA ANNUNCIATOR RESPONSE PSA-X-01-07 F-01-07 s
4 CHILLED WATER .
SYSTEM I TROUBLE !
EVENT POINT 1560 INDICATED CONDITION:
o CHHE-1A DOES NOT HAVE ANY POWER TO THE CONTROL PANEL OR COMPRESSOR MOTOR AS SENSED BY RELAY 14/R REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
p o AMBER " POWER FAILURE" LIGHT ON LOCAL CONTROL PANEL U
OPERATOR ACTIONS FOR A VALID ALARM:
o INVESTIGATE THE CAUSE OF POWER LOSS DISCUSSION:
REFERENCES:
ORAWING 208-076 SHEET CH-05 SENSING ELEMENT: 14R, 2/A O
AR-401 Rev. 16 Page 50
ENCLOSURE I (Page 49 of 185)
PSA ANNUNCIATOR RESPONSE PSA-X-01-07 F-01-07 I i
~
' CHILLED WATER -
SYSTEM TROUBLE I
i EVENT POINT 1561 INDICATED CONDITION:
o CHHE-IB MOTOR WINDING TEMPERATURE IS >105*C, OR CHHE-IB OIL TEMPERATURE IS >170*F. !
REDUNDANT INDICATION WHICH WILL VERIFY ALARM: I o
LOCAL CONTROL PANEL - RED INDICATOR LIGHT IS ON FOR "0ll/ MOTOR TEMP" J
OPERATOR ACTIONS FOR A VALID ALARM:
o SWAP CHILLERS PER OP-409 DISCUSSION:
THIS CONDITION WILL CAUSE THE CHILLER TO TRIP, THE CONDITION SEALS IN UNTIL THE RESET PUSHBUTTON IS DEPRESSED
REFERENCES:
DRAWING 208-076 SHEET CH-06 SENSING ELEMENT: 6R, 2/B O
AR-401 Rev. 16 Page 51
i (N ENCLOSURE I V (Page 50 of 185) I PSA ANNUNCIATOR RESPONSE PSA-X-01-07 F-01-07 CHILLED WATER SYSTEM TROUBLE I
EVENT POINT 1562 INDICATED CONDITION:
o CHHE-1B REFRIGERANT PRESSURE IS <17.9"HGA REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
p o LOCAL CONTROL PANEL - RED INDICATOR LIGHT IS ON FOR " LOW PRESSURE" ;
k OPERATOR ACTIONS FOR A VALID ALARM:
o SWAP CHILLERS PER OP-409 OISCUSSION:
THIS CONDITION WILL CAUSE THE CHILLER TO TRIP, THE CONDITION SEALS IN UNTIL THE RESET PUSHBUTTON IS. DEPRESSED
REFERENCES:
DRAWING 208-076 SHEET CH-06 SENSING ELEMENT: 7R, 2/B O
AR-401 Rev. 16 Page 52
ENCLOSURE I v
) (Page 51 of 185)
PSA ANNUNCIATOR RESPONSE PSA-X-01-07 F-01-07 i
i I
CHILLED WATER '
SYSTEM TROUBLE l
EVENT POINT 1563 1 INDICATED CONDITION:
o CHHE-IB REFRIGERANT PRESSURE IS >9 PSIG REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o LOCAL CONTROL PANEL - RED INDICATOR LIGHT IS ON FOR "HIGH PRESSURE" OPERATOR ACTIONS FOR A VALID ALARM:
o SWAP CHILLERS PER OP-409 4
DISCUSSION: l THIS CONDITION WILL CAUSE THE CHILLER TO TRIP, THE CONDITION SEALS IN UNTIL THE RESET PUSHBUTTON IS DEPRESSED '
REFERENCES:
DRAWING 208-076 SHEET CH-06 SENSING ELEIllNT:' BR, 2/B O
AR-401 Rev. 16 Page 53
p ENCLOSURE 1
.(j (Page 52 of 185)
PSA ANNUNCIATOR RESPONSE PSA-X-01-07 F-01-07 CHILLED WATER SYSTEM I TROUBLE EVENT POINT 1564
__ i INDICATED CONDITION:
o CHHE-1B OIL PRESSURE IS < 27 PSIG REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
i (O
y o LCCAL CONTROL PANEL - RED INDICATOR LIGHT IS ON FOR " LOW OIL PRESS" OPERATOR ACTIONS FOR A VALID ALARM:
o SWAP CHILLERS PER OP-409 DISCUSSION:
THIS CONDITION WILL CAUSE THE CHILLER TO TRIP, THE CONDITION SEALS IN UNTIL THE RESET PUSHBUTTON IS DEPRESSED
REFERENCES:
ORAWING 208-076 SHEET CH-06 SENSING ELEMENT: 9R, 2/B AR-401 Rev. 16 Page 54
. - . - - . _ - _ - - . _ ~ _ .- . .. _
l l
m h ENCLOSURE 1 (Page 53 of 185)
PSA ANNUNCIATOR RESPONSE PSA-X-01-07 F-01-07 CHILLED WATER SYSTEM ,
TROUBLE 1
EVENT POINT 1565 l
INDICATED CONDITION:
7 o
CHHE-1B DOES NOT HAVE ANY POWER TO THE CONTROL PANEL OR COMPRESSOR ,
MOTOR AS SENSED BY RELAY 14/R I REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
^
o AMBER " POWER FAILURE" LIGHT ON LOCAL CONTROL PANEL i J
i OPERATOR ACTIONS FOR A VALIO ALARM:
o INVESTIGATE THE CAUSE OF POWER LOSS DISCUSSION:
REFERENCES:
DRAWING 208-076 SHEET CH-06 SENSING ELEMENT: 14R, 2/B O
i l
AR-401 Rev. 16 Page 55 j
t ENCLOSURE 1 (s (Page 54 of 185)
PSA ANNUNCIATOR RESPONSE PSA-X-02-01 F-02-01 TOXIC GAS MONITOR TROUBLE EVENT POINT 0314 INDICATED CONDITION:
o ONE OR MORE OF THE FOLLOWING MONITORS' LOCAL TROUBLE ALARMS HAS ACTUATED: AH-648-CE AH-652-CE AH-649-CE AH-653 CE REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o LOCAL TROUBLE ALARMS ON AH-648-CE, AH-649-CE, AH-652-CE, OR AH-653-CE O o COMPUTER POINTS S263, S297, S298, S299 FOR T0XIC GAS CONCENTRATION OPERATOR ACTIONS FOR A VALID ALARM:
o INVESTIGATE THE CAUSE OF TROUBLE o NOTIFY I&C TO TROUBLE SHOOT MONITORS DISCUSSION:
i i
REFERENCES:
DRAWING 208-005 SHEET AH-84 SENSING ELEMENT: AH-648-CE, AH-652-CE, AH-649-CE, AH-653-CE AR-401 Rev. 16 Page 56 a
l t
l ENCLOSURE 1 (Page 55 of 185)
PSA ANNUNCIATOR RESPONSE PSA-X-02-01 F-02-01 P"r =-- TOxlCGAS MONITOR
- ; TROUBLE I I l l l l l l l "
l EVENT POINT 0432 i
, INDICATED CONDITION:
o T0XIC GAS >5 PFM CL AS SENSED BY AH-648-CE AND/0R AH-649-CE OR, l >2 PPM S0, SENSED BY AH-652-CE AND/0R AH-653-CE REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o COMPUTER POINTS S263, S297, S298, OR S299 OPERATOR ACTIONS FOR A VAllD ALARM:
o REFER TO AP-513 o REFER TO SP-300 i
DISCUSSION:
I l
l l
REFERENCES:
DRAWINS 208-005 SHF.ET AH-84 SENSINGELEMINT:' Ali-648-CE, AH-652-CE, AH-E,9-CE, AH-653-CE
- O AR-401 Rev. 16 Page 57
i i .
/
ENCLOSURE _1
. - (Page 56 of 185) t PSA ANNUNCIATOR RESPONSE PSA-X-02-01 F-02-01 4
TOXIC GAS NIONITCH4 TROUBLE 1 EVEN' POINT 0800 i
1 INDICATED CONDITION:
, o T0XIC GAS >20 PPM S0 SENSED 2 DETECTORS AT UNITS 1&2 j
I REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o NOTIFICATION OF A SPILL FROM UNITS I&2 4
i
) OPERATOR ACTIONS FOR A VALID ALARM:
o REFER TO AP-513 I
b i
DISCUSSION:
i 4
REFERENCES:
DRAWING 208-005 SHEET AH-84A i SENSING ELEMENT: UNITS 1 3 2 "A" OR "B" S0p DETECTOR O
i AR-401 Rev. 16 Page 58 i
ENCLOSUREl (Page 57 of 185)
PSA ANNUNCIATOR RESPONSE PSA-X-02-04 F-02-04 ClSYSTEM TROUBLE EVENT POINT 1567 INDICATED CONDITION:
o THE 4160V BREAKER FOR THE REACTOR BLDG. " HILLER IS CLOSED AND AN ALARM EXISTS ON THE MICROTECH CONTROL PANEL o LOW DIFFERENTIAL PRESSURE ACROSS CIP-IA Gh CIP-IB REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o A FAULT IS INDICATED ON THE MICR0 TECH FLUORESCENT DISPLAY o CIP-1A OR CIP-1B TRIPS OPERATOR ACTIONS FOR A VALID ALARM:
o o DEPRESS THE " UNIT STATUS" PUSHBUTTON IF NO VISUAL DISPLAY PRESENT DEPRESS THE " FAULT HISTORY" PUSHBUTTON ONCE TO DETERMINE THE CURRENT FAULT, AND EIGHT MORE TIMES FOR THE PREVIOUS EIGHT FAULTS IF DESIRED o CORRECT SOURCE OF THE FAULT, THEN DEPRESS " CLEAR FAULT" PUSHBUTTON AND RESTART THE CHILLER IF DESIRED, REFER TO OP-417A o IF THE CHILLER CANNOT BE RESTARTED, THEN PLACE THE SYSTEM IN THE " FREE" COOLING MODE OR SWAP TO SW COOLING FOR THE RB COOLING UNITS, REFER TO OP-417A o PLACE ALTERNATE CIP IN SERVICE PER OP-417A DISCUSSION:
o HIGH DISCHARGE PRESSURE, WHICH IS HIGH CONDENSOR PRESSURE, TRIPS THE HIGH MECHANICAL PRESSURE SWITCH. FIRST THE SWITCH MUST BE RESET INSIDE MICROTECH, THEN CLEAR FAULT WILL ALLOW RESTART. IF THE FAULT CANNOT BE CLEARED, THEN HVAC PERSONNEL SHOULD BE NOTIFIED FOR RESOLUTION o IF THE CHILLER IS OPERATING WHEN A CIP TRIPS, THEN THIS WILL TRIP THE CHILLER ON LOW FLOW
REFERENCES:
DRAWING 208-077 SHEET Cl-25 SENSING ELEMENi".' RL3-ALM, RL6-ALM, CI-772-DPS O i k
i j AR-401 Rev. 16 Page 59 '
i ENCLOSURE 1
! (~, (Page 58 of 185) i PSA ANNUNCIATOR RESPONSE PSA-X-02-04 F-02-04 l
CI SYSTEh4
) TRCKJBLE I
i EVENT POINT 1568 i
j INDICATED CONDITION: '
- l
' o HIGH VIBRATION ON CIF-1A OR CIF-1B o LOW TOWER BASIN WATER LEVEL REDUNDANT INDICATION WHICH WILL VERIFY ALARM: I 4
o CIF-IA OR CIF-18 HAS TRIPPED
( o CIP-1A OR CIP-1B MAY TRIP ON LOW DP, MAY EXHIBIT CAVITATION, OR MAY CAUSE A TRIP 0F THE RB CHILLER ON LOW FLOW OPERATOR ACTIONS FOR A VALID ALARM:
o NOTIFY HVAC PERSONNEL FOR TRIPPED FAN ON HIGH VIBRATION o VERIFY PROPER VALVE ALIGNMENT FOR LOW BASIN LEVEL o
SECURE PUMP If CAVITATION EXISTS AND ESTABLISH SW COOLING TO THE RB UNTIL PROBLEM IS CORRECTED DISCUSSION:
o THE BASIN WATER LEVEL IS AUTOMATICALLY MAINTAINED WITH TWO FL0AT VALVES OPERATING IN PARALLEL TO SUPPLY EACH TOWER, THE TOWER BASINS ARE CROSSTIED SUCH THAT EITHER VALVE WILL SUPPLY BOTH RESINS. LOW BASIN LEVEL DISABLES THE BASIN WATER HEATERS.
REFERENCES:
DRAWING 208-077 CI-29 AND C1-30 SENSING ELEMCNTI' Cl-784-SS, Cl-785-SS, CI-780-LS, CI-781-LS O
AR-401 Rev. 16 Page 60
i O ENCLOSURE I (Page 59 of 185)
PSA ANNUNCIATOR RESPONSE PSA-X-02-05 F-02-05 Cl CIRC PP 1A/B OVERLOAD EVENT POINT 1879 INDICATED CONDITION:
o CIP-IA OR CIP-IB MOTOR CURRENT IS EXCESSIVE REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o O PUMP MAY TRIP FROM LOW DP AS A RESULT OF LOCKED ROTOR OR VERY HIGH FLOWRATES OPERATOR ACTIONS FOR A VALID ALARM:
o INVESTIGATE OPERATION OF CIP-IA OR CIP-1B o SWAP RB COOLING TO SW IF REQUIRED i
DISCUSSION:
l
REFERENCES:
DRAWING 208-077 CI-27 -
SENSING ELEMENT:
OVERLOAD HEATERS IN INST COMPARTMENT IN UNIT 480V SG RM O '
AR-401 Rev. 16 Page 61
A ENCLOSURE 1 V (Page 60 of 185)
PSA ANNUNCIATOR RESPONSE PSA-X-02-06 F-02-06 Cl CIRC PUMP 2A/B 3A/B TRIP EVENT POINT 0524 INDICATED CONDITION:
o CIP-2A BREAKER OPEN WITH CONTROL HANDLE IN THE NORMAL AFTER START POSITION REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
,A o GREEN LIGHT ON WITH A RED FLAG ON CIP-2A CONTROL STATION N
OPERATOR ACTIONS FOR A VALID ALARM:
o START CIP-28 o HAVE BREAKER CUBICLE CHECKED FOR DROPPED TARGETS DISCUSSION:
REFERENCES:
DRAWING 208-077 SHEET CI-03 SENSING ELEMENT: CS/SC, CS/0, R/B O
AR-401 Rev. 16 Page 62
1 ENCLOSURE I I s (Page 61 of 185) )
PSA ANNUNCIATOR RESPONSE PSA-X-02-06 F-02-06 i
j Cl CIRC PUMP 2A/B 3A/B TRIP EVENT POINT 0526 4
INDICATED CONDITION:
j o CIP-28 BREAKER OPEN WITH CONTROL HANDLE IN THE NORMAL AFTER START !
POSITION I
REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
p o GREEN LIGHT ON WITH A RED FLAG ON CIP-28 CONTROL STATION 1 h !
OPERATOR ACTIONS FOR A VALID ALARM: I 1
o START CIP-2A l 0 HAVE BREAKER CUBICLE CHECKED FOR DROPPED TARGETS !
d i
, DISCUSSION:
t
REFERENCES:
ORAWING 208-077 SHEET CI-04 '
SENSING ELEiliNT:' CS/SC, CS/0, R/B AR-401 Rev. 16 Page 63
l ENCLOSURE 1 i (Page 62 of 185)
PSA ANNUNCIATOR RESPONSE PSA-X-02-06 F-02-06 Cl CIRC PUMP 2A/B 3A/B TRIP EVENT POINT 0528 INDICATED CONDITION i o
CIP-3A CONTROL HANDLE IN NORMAL AFTER START POSITION WITH THE MOTOR NOT ENERGIZED REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
O o GREEN LIGHT ON WITH A RED FLAG ON CIP-3A CONTROL STATION OPERATOR ACTIONS FOR A VALID ALARM:
O SWAP REACTOR CAVITY COOLING TO "B" SIDE PER OP-417 !
o MONITOR REACTOR CAVITY TEMPS ON AH-1003-TIR PER OP-409 DISCUSSION:
A SUSTAINED LOSS OF COOLING TO THE REACTOR CAVITY WILL HAVE ADVERSE EFFECTS ON THE RELIABILITY OF THE NUCLEAR INSTRUMENTATION.
REFERENCES:
DRAWING 208-077 SHEET CI-18 SENSING ELEMENT: CS/SC, CS/0, 42B O
AR-401 Rev. 16 Page 64
w ENCLOSURE 1 I
(Page 63 of 185)
PSA ANNUNCIATOR RESPONSE PSA-X-02-06 F-02-06 Cl CIRC PUMP 2A/B 3A/B TRIP EVENT POINT 0529 INDICATED CONDITION:
o CIP-38 CONTROL HANDLE IN NORMAL AFTER START POSITION WITH THE MOTOR NOT ENERGIZED REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
O o GREEN LIGHT ON WITH A RED FLAG ON CIP-3B CONTROL STATION OPERATOR ACTIONS FOR A VALID ALARM:
o SWAP REACTOR CAVITY COOLING TO "A" SIDE PER OP-417 o MONITOR REACTOR CAVITY TEMPS ON AH-1003-TIR PER OP-409 DISCUSSION:
A SUSTAINED LOSS OF COOLING TO THE REACTOR CAVITY WILL HAVE ADVERSE EFFECTS ON THE RELIABILITY OF THE NUCLEAR INSTRUMENTATION.
REFERENCES:
DRAWING 208-077 SHEET CI-19 SENSING ELEMENT: CS/SC, CS/0, 428 O
AR-401 Rev. 16 Page 65
4 ENCLOSURE 1 (Page 64 of 185) 1 PSA ANNUNCIATOR RESPONSE PSA-X-02-07 F-02-07 Cl CIRC PUMP 2A/B OVERLOAD I -
EVENT POINT 0525 INDICATED CONDITION:
o CIP-2A MOTOR AMPS >II5% RATED LOAD REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o HIGH LOCAL TEMPERATURES ON PUMP AND OR MOTOR OPERATOR ACTIONS FOR A VALID ALARM:
o SHUTDOWN CIP-2A AND START CIP-28 o
INVESTIGATE THE OPERATION OF THE PUMP MOTOR TO DETERMINE THE CAUSE OF I THE ALARM l
DISCUSSION:
THIS ALARM INDICATES THAT THE INTERNAL OVERCURRENT DEVICE HAS ACTUATED I AND THAT THE MOTOR MAY TRIP AT ANY TIME.
REFERENCES:
DRAWING 208-077 SHEET CI-03 SENSING ELEMENT: CS/SC, CS/0, 42B O
1 AR-401 Rev. 16 Page 66
ENCLOSURE 1 i (Page 65 of 185)
PSA ANNUNCIATOR RESPONSE PSA-X-02-07 F-02-07 1
Cl CIRC PUMP 2A/B OVERLOAD EVENT POINT 0527 INDICATED CONDITION:
o CIP-2B MOTOR AMPS >l15% RATED LOAD REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
1 O o HIGH LOCAL TEMPERATURES ON PUMP AND OR MOTOR l
OPERATOR ACTIONS FOR A VALID ALARM:
O SHUTDOWN CIP-2B AND START CIP-2A o INVESTIGATE THE OPERATION OF THE PUMP MOTOR TO DETERMINE THE CAUSE OF THE ALARM DISCUSSION:
THIS ALARM INDICATES THAT THE INTERNAL OVERCURRENT DEVICE HAS ACTUATED AND THAT THE MOTOR MAY TRIP AT ANY TIME.
REFERENCES:
DRAWING 208-077 SHEET CI-04 SENSING ELEMENT: CS/SC, CS/0, 42B O
AR-401 Rev. 16 Page 67
i l
t ENCLOSURE 1 l (Page 66 of 185) l PSA ANNUNCIATOR RESPONSE PSA-X-02-08 F-02-08 l l l l I I Cl PUMP 2 SUCT PRESS l l Low 4 I I i i I t
EVENT POINT 1702 ,
INDICATED CONDITION:
l o' CIP-2A BREAKER IS CLOSED AND SUCTION PRESSURE IS < 5 PSIG AS SENSED BY
- CI-728-PS l
! REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o LOW LOCAL PRESSURES ON PUMP SUCTION GAUGE Cl-99-PI i 1
{ OPERATOR ACTIONS FOR A VALID ALARM:
j o CHECK CIT-I LEVEL o INVESTIGATE THE CAUSE OF LOW SUCTION PRESSURE
,' o VERIFY PROPER OPERATION OF THE REACTOR BLDG CHILLER 1
DISCUSSION:
THIS CONDITION COULD BE CAUSED BY A LOW LEVEL IN THE EXPANSION TANK, OR BY EXCESSIVE PRESSURE DROP ACROSS CIHE-3/CIHE-4A OR THE LEAK RATE TEST COOLER. THE LINE UP 0F THE SYSTEM SHOULD BE VERIFIED.
REFERENCES:
. DRAWING 208-077 SHEET CI-03 SENSING ELEMENT: Cl-728-PS, R/A O
AR-401 Rev. 16 Page 68
t
'n g ENCLOSURE 1 (Page 67 of 185)
PSA ANNUNCIATOR RESPONSE PSA-X-02-08 F-02-08 l l I I l Cl PUMP
,I l SUCT PRESS i l I LOW l I 1
EVENT POINT 1703 1 i
, INDICATED CONDITION:
o CIP-28 BREAKER IS CLOSED AND SUCTION PRESSURE IS < 5 PSIG AS SENSED BY CI-729-PS i 1
REDUNDANT INDICATION WHICH WILL VERIFY ALARM: '
o LOW LOCAL PRESSURES ON PUMP SUCTION GAUGE CI-101-PI i
- OPERATOR ACTIONS FOR A VALID ALARM
O CHECK CIT-1 LEVEL o INVESTIGATE THE CAUSE OF LOW SUCTION PRESSURE o VERIFY PROPER OPERATION OF THE REACTOR BLDG CHILLER a
i DISCUSSION:
THIS CONDITION COULD BE CAUSED BY A LOW LEVEL IN THE EXPANSION TANK, OR BY EXCESSIVE PRESSURE DROP ACROSS CIHE-3/CIHE-4A OR THE LEAK RATE TEST COOLER. THE LINE UP OF THE SYSTEM SHOULD BE VERIFIED.
- ~
REFERENCES:
- -DRAWING 208-077 SHEET CI-04 SENSING ELEMENT: CI-729-PS, R/A O
AR-401 Rev. 16 Page 69
,q '
ENCLOSURE 1 Q (Page 68 of 185)
PSA ANNUNCIATOR RESPONSE PSA-X-02-08 F-02-08 l
l l l
! I I
Cl PUMP l
- SUCT PRESS
- Low I
l EVENT POINT 1704 l
l INDICATED CONDITION:
O CIP-3A CONTROL SWITCH IS IN NORMAL AFTER START, AND SUCTION PRESSURE IS l
< 45 PSIG AS SENSED BY CI-730-PS i
REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o LOW LOCAL PRESSURES ON PUMP SUCTION GAUGE Cl-732-PI OPERATOR ACTIONS FOR A VALID ALARM:
o CHECK CIT-I LEVEL o INVESTIGATE THE CAUSE OF LOW SUCTION PRESSURE o MONITOR REACTOR CAVITY TEMPERATURES ON AH-1003-TIR PER OP-409 DISCUSSION:
THIS CONDITION COULD BE CAUSED BY A LOW LEVEL IN THE EXPANSION TANK, OR BY EXCESSIVE FLOWRATE. THE LINE UP 0F THE SYSTEM SHOULD BE VERIFIED.
A SUSTAINED LOSS OF COOLING TO THE REACTOR CAVITY WILL HAVE ADVERSE EFFECTS ON THE RELIABILITY OF THE NUCLEAR INSTRUMENTATION.
REFERENCES:
- DRAWING 208-077 SHEET CI-18 SENSING ELEMENT: Cl-730-PS, CS/SC, CS/0 D
l l
AR-401 Rev. 16 Pagc- 70
ENCLOSURE 1 (Page 69 of 18S)
PSA ANNUNCIATOR RESPONSE PSA-X-02-08 F-02-08 l l I I I I Cl PUMP SUCT PRESS l l Low I I I I EVENT POINT 1705 j INDICATED CONDITION:
o CIP-3B CONTROL SWITCH IS IN NORMAL AFTER START, AND SUCTION PRESSURE IS
< 45 PSIG AS SENSED BY CI-731-PS REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o LOW LOCAL PRESSURES ON PUMP SUCTION GAUGE Cl-733-PI V(3 OPERATOR ACTIONS FOR A VALID ALARM:
o CHECK CIT-1 LEVEL o ' INVESTIGATE THE CAUSE OF LOW SUCTION PRESSURE o MONITOR REACTOR CAVITY TEMPERATURES ON AH-1003-TIR PER OP-409 DISCUSSION:
THIS CONDITION COULD BE CAUSED BY A LOW LEVEL IN THE EXPANSION TANK, OR '
BY EXCESSIVE FLOWRATE. THE LINE UP 0F THE SYSTEM SHOULD BE VERIFIED.
A SUSTAINED LOSS OF COOLING TO THE REACTOR CAVITY WILL HAVE ADVERSE EFFECTS ON THE RELIABILITY OF THE NUCLEAR INSTRUMENTATION.
REFERENCES:
- DRAWING 208-077 SHEET CI-19 '
SENSING ELEMENT: CI-731-PS, CS/SC, CS/0 O
AR-401 Rev. 16 Page 71
ENCLOSURE 1 (Page 70 of 185)
' 'd PSA ANNUNCIATOR RESPONSE PSA-X-03-01 F-03-01 TURBINE BLDG FIRE ALERT I
I 1
I i EVENT POINT 0443 INDICATED CONDITION:
o TEMPERATURE > 135'F AS SENSED BY AH-125-TS EXISTS IN THE INTAKE PLENUM FOR AHF-16A/168 REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o AHF-16A TRIPS o AHF-16B TRIPS OPERATOR ACTIONS FOR A VALID ALARM:
o ENSURE AHF-16A/AHF-168 ARE SHUT DOWN O REFER TO THE CR3 PRE FIRE PLAN O REFER TO AP-880 DISCUSSION:
THIS CONDITION IS INDICATIVE OF A FIRE OR A HIGH TEMPERATURE IN THE INTAKE DUCT OF AHF-16A/AHF-168.
REFERENCES:
DRAWING 208-005 SHEETS AH-058, ORAWING 308846 SENSING ELEMENT: AH-125-TS lO l
AR-401 Rev. 16 Page 72
i ENCLOSURE 1 (Page 71 of 185) l PSA ANNUNCIATOR RESPONSE PSA-X-03-01 F-03-01 I I
TURBINE BLDG FIRE ALERT
- I i I
l I
l EVENT POINT 0444 INDICATED CONDITION:
4
-l o PRODUCTS OF COMBUSTION HAVE BEEN DETECTED BY AH-126-CE 0 TROUBLE HAS BEEN DETECTED IN THE CIRCUITS FOR AH-126-CE o
TEMPERATURE > 135'F AS SENSED BY AH-126-TS EXISTS IN THE RETURN AIR l DUCT FROM 119' SWITCH GEAR ROOM i
REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
i o
(Q,/ THIS ALARM WILL RESULT IN THE ACTUATION OF THE FOLLOWING FIRE DAMPERS FD-38, FD-40, FD-48, FD-49, AND FD-50 I
j OPERATOR ACTIONS FOR A VALID ALARM: I I
o ENSURE AHF-16A/AHF-16B ARE SHUT DOWN 3
o REFER TO THE CR3 PRE FIRE PLAN
- o REFER TO AP-880 '
i u
DISCUSSION:
THIS CONDITION IS INDICATIVE OF A FIRE OR A HIGH TEMPERATURE IN THE !
RETURN AIR DUCT FROM 119' SWITCH GEAR ROOM TO AHF-16A/AHF-168. I
REFERENCES:
DRAWING 208-005 SHEETS AH-058, AH-060, AND DRAWING 308846 .
SENSING ELEMENT: AH-126-TS, AH-126-CE, 3AH-126-TS/RR-HV-V AR-401 Rev. 16 Page 73
- ~. .~ - - . .. -- - .. --
l l ENCLOSURE 1 (Page 72 of 185) l l PSA ANNUNCIATOR RESPONSE PSA-X-03-01 F-03-01 1
TURBINE BLDG FIRE ALERT EVENT POINT 0448 INDICATED CONDITION:
l 0 PRODUCTS OF COMBUSTION HAVE BEEN DETECTED BY AH-127-CE o TROUBLE HAS BEEN DETECTED IN THE CIRCUITS FOR AH-127-CE o TEMPERATURE > 135'F AS SENSED BY AH-127-TS EXISTS IN THE R: .iN AIR l DUCT FROM 95' SWITCH GEAR ROOM l REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
O o THIS ALARM WILL RESULT IN THE ACTUATION OF THE FOLLOWING FIRE DAMPERS FD-39 AND FD-41 V
OPERATOR ACTIONS FOR A VALID ALARM:
o ENSURE AHF-16A/AHF-16B ARE SHUT DOWN o REFER TO THE PRE FIRE PLAN o REFER TO AP-880 DISCUSSION:
THIS CONDITION IS INDICATIVE OF A FIRE OR A HIGH TEMPERATURE IN THE RETURN AIR DUCT FROM 95' SWITCH GEAR ROOM TO AHF-16A/AHF-168.
REFERENCES:
DRAWING 208-005 SHEETS AH-059, AH-060, AND DRAWING 308846 SEfiSING ELEMENh AH-127-TS, AH-127-CE, 3AH-127-TS/RR-HV-V l
'O l C AR-401 Rev. 16 Page 74
ENCLOSURE I (Page 73 of 185)
O PSA ANNUNCIATOR RESPONSE PSA-X-03-01 F-03-01 TURBINE BLDG FIRE ALERT EVENT POINT 0449 INDICATED CONDITION:
o ONE OF THE FOLLOWING TEMPERATURE SWITCHES HAS ACTUATED AT >135'F AH-153-TS AH-523-TS AH-524-TS REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o FIRE DAMPERS FD-52, FD-53, AND FD-54 TRIP o AHF-25A, AHF-258, AND AHF-25C TRIP IF OPERATING OPERATOR ACTIONS FOR A VALID ALARM:
o NOTIFY TURBINE BUILDING OPERATOR TO INVESTIGATE THESE TURBINE BUILDING SUPPLY FANS o REFER TO AP-880 DISCUSSION:
THIS ALARM INDICATES THAT THE FIRE DAMPERS FOR AHF-25A/B/C HAVE ACTUATED AHF-25A/B/C SHOULD SHUTDOWN AUTOMATICALLY.
REFERENCES:
DRAWING 208-005 SHEET AH-061, AH-70, DRAWING 308846 SENSING ELEMENT: AH-153-TS, AH-523-TS, AH-524-TS, AND RELAY 3HBTIA .
AR-401 Rev. 16 Page 75
I ENCLOSURE 1 (Page 74 of 185) ,
O PSA ANNUNCIATOR RESPONSE PSA-X-03-01 F-03-01 l
__ ___ 1 j
TURBINE BLDG FIRE ALERT EVENT POINT 0450 INDICATED CONDITION:
o ONE OF THE FOLLOWING TEMPERATURE SWITCHES HAS ACTUATED AT >l35'F AH-155-TS AH-527-TS AH-528-TS REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o AHF-26A, AHF-268, AND AHF-26C TRIP IF OPERATING O OPERATOR ACTIONS FOR A VALID ALARM:
o NOTIFY TURBINE BUILDING OPERATOR TO INVESTIGATE THESE TURBINE BUILDING SUPPLY FANS o REFER TO AP-880 DISCUSSION:
THIS ALARM INDICATES THAT THE FIRE DAMPERS FOR AHF-26A/B/C HAVE ACTUATED. AHF-26A/B/C SHOULD SHUTDOWN AUTOMATICALLY.
I
REFERENCES:
DRAWING 208-005 SHEET AH-064, AH-70, DRAWING 308846 l SENSING ELEMENT: AH-155-TS, AH-527-TS, AH-528-TS, AND RELAY 3HBT2 A
V AR-401 Rev, 16 Page 76
.- - . - _ . . . - . = . . . --
ENCLOSURE 1 (Page 75 of 185)
PSA ANNUNCIATOR RESPONSE PSA-X-03-01 F-03-01 TURBINE BLDG FIRE ALERT EVENT POINT 0451 INDICATED CONDITION:
o ONE OF THE FOLLOWING TEMPERATURE SWITCHES HAS ACTUATED AT >135'F AH-154-TS AH-525-TS AH-526-TS REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o AHF-27A, AHF-278, AND AHF-27C TRIP IF OPERATING (0) t OPERATOR ACTIONS FOR A VALID ALARM:
i o
NOTIFY TURBINE BUILDING OPERATOR TO INVESTIGATE THESE TURBINE BUILDING SUPPLY FANS o REFER TO AP-880 DISCUSSION:
THIS ALARM INDICATES THAT THE FIRE DAMPERS FOR AHF-27A/B/C HAVE ACTUATED, AHF-27A/B/C SHOULD SHUTDOWN AUTOMATICALLY.
REFERENCES:
DRAWING 208-005 SHEET AH-067, AH-70, DRAWING 308846 SENSING ELEMENT: AH-154-TS, AH-525-TS, AH-526-TS, AND RELAY 3HBT3 l
AR-401 Rev. 16 Page 77
)
ENCLOSURE 1 (Page 76 of 185)
O PSA ANNUNCIATOR RESPONSE PSA-X-03-01 F-03-01 TURBINE BLDG FIRE ALERT EVENT POINT 1118 INDICATED CONDITION:
o o PRODUCTS OF COMBUSTION HAVE BEEN DETECTED BY AH-723-CE TROUBLE HAS BEEN DETECTED IN THE CIRCUITS FOR AH-723-CE REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o DETECTION OF PRODUCTS OF COMBUSTION WILL TRIP AHF-49 IF RUNNING OPERATOR ACTIONS FOR A VALID ALARM:
o REFER TO THE CR3 PRE FIRE PLAN o REFER TO AP-880 DISCUSSION:
THIS CONDITION IS INDICATIVE OF EITHER TROUBLE IN THE FIRE DETECTION CIRCulTS, OR A FIRE IN THE INSTRUMENT CAL LAB 145' TURBINE DECK.
REFERENCES:
DRAWING 208-005 SHEETS AH-151 AND AH-152 .
SENSING ELEMENT: AH-723-CE O
AR-401 Rev. 16 Page 78
-. _- .- - - - _ .~ .-..- _... - .- - . - - . . . - - . - _
4 ENCLOSURE I (Page 77 of 185)
O PSA ANNUNCIATOR RESPONSE PSA-X-03-02 F-03-02 i
1 .
AUX BLDG FIRE ALERT EVENT POINT 0006 INDICATED CONDITION:
j o PENETRATION COOLING DUCT TEMPERATURE UPSTREAM 0F FD-278 IS >165'F AS 1
SENSED BY AH-1004-TS
- REDUNDANT INDICATION WHICH WILL VERIFY ALARM
- i O PENETRATION COOLING FANS AHF-9A/98 TRIP DN INTERLOCK OPERATOR ACTIONS FOR A VALID ALARM:
o ENSURE AHF-9A/98 ARE SHUTDOWN o INVESTIGATE CAUSE OF ALARM DISCUSSION:
THIS ALARM IS AN INDICATION OF A POSSIBLE FIRE IN THE DUCT WORK.
CONSIDERATION SHOULD BE GIVEN TO CONSULTING FIRE PLANS FOR THE APPROPRIATE ACTIONS. AH-1004-TS IS A MANUAL RESET TEMPERATURE SWITCH LOCATED AT INT. BLDG. 95' ELEV. NEXT TO THE LOCAL CONTROL STATION FOR AHF-9A AND 98.
REFERENCES:
DRAWING 208-005 SHEET AH-056, DRAWING 308849 i SENSING ELEMENT: AH-1004-TS O
AR-401 Rev. 16 Page 79
ENCLOSURE 1 l
(Page 78 of 185)
\
PSA ANNUNCIATOR RESPONSE PSA-X-03-02 F-03-02 l )
I li AUX BLDG FIRE ALERT I
l l l
EVENT POINT 0380 INDICATED CONDITION:
o RB PURGE SUPPLY DUCT TEMP IS >I35'F AS SENSED BY AH-23-TS, OR PRODUCTS OF COMBUSTION HAVE BEEN SENSED BY AH-23-CE AND/0R AH-24-CE, OR RELAY 3PSFP HAS ACTUATED o RB PURGE SUPPLY DUCT TEMP IS <70*F AS SENSED BY AH-645-TS REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
i o PURGE SUPPLY FANS AHF-6A/6B TRIP .
O PURGE SUPPLY DAMPER AHV-ID CLOSES ON LOW PURGE SUPPLY FLOW OPERATOR ACTIONS FOR A VALID ALARM: l 0 INVESTIGATE THE CAUSE OF THE ALARM o SECURE RB PURGE PER OP-417, IF HIGH TEMP ALARM o REFER TO AP-880, IF HIGH TEMP ALARM i
l 0 CHECK CORE FLOOD TANK PRESSURE / TEMP, IF LOW TEMP ALARM DISCUSSION:
THIS IS INDICATIVE OF A FIRE IN THE PURGE SUPPLY FAN DISCHARGE DUCT THE i TEMPERATURE AND PRODUCT OF COMBUSTION DETECTORS SENSE THE DISCHARGE UPSTREAM 0F THE RECIRCULATION DAMPER. THE LOW TEMPERATURE ALARM HAS NO INTERLO"YS ASSOCIATED WITH IT.
- A.
l
REFERENCES:
DRAWING 208-005 SHEETS AH-020, AND AH-15, DRAWING 308849
- ~
SENSING ELEt!EN h AH-23-TS, AH-23-CE, AH-24-CE, AH-645-TS, AND RELAY 3PSFP '
i
- O '
l l
AR-401 Rev. 16 Page 80 i
_ __. _ __ _. . _ - ~ _ _ _ _ - _ _ . _ . _ _ _ _ _ . . - _ . . . _ _ . . -
! 1 4
ENCLOSURE I (Page 79 of 185)
[
PSA ANNUNCIATOR RESPONSE PSA-X-03-02 F-03-02 1
AUX BLDG
] FIRE ALERT I
i EVENT POINT 0387 d
INDICATED CONDITION:
o RB PURGE EXHAUST DUCT TEMP IS >135'F AS SENSED BY AH-295-TS, OR PRODUCTS OF COMBUSTION HAVE BEEN SENSED BY AH-295-CE, OR RELAY 3PEFP HAS ACTUATED
! REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
j o PURGE EXHAUST FANS AHF-7A/78 TRIP iO j OPERATOR ACTIONS FOR A VALID ALARM:
I' o INVESTIGATE THE CAUSE OF THE ALARM o SECURE THE RB PURGE REFER TO OP-417
.l 0 REFER TO AP-880 j
4 i
DISCUSSION:
1 i THIS IS INDICATIVE OF A FIRE IN THE PURGE EXHAUST DISCHARGE DUCT THE d
TEMPERATURE AND PRODUCT OF COMBUSTION DETECTORS SENSE THE DISCHARGE OF l THE FANS l
I REFFDPfCES: DRAWING 208-005 SHEETS AH-020, AND AH-15, DRAWING 308849 SENSIhL ELEMENT: AH-295-CE, AH-295-TS, AND RELAY 3PEFP O
a AR-401 Rev. 16 Page 81
_ . m ._. .. ._ _ _ _ - _ _ - . . _ . _ . . . . _ . _ _ _ _ _ _ _ _
l i
ENCLOSURE 1 (Page 80 of 185)
PSA ANNUNCIATOR RESPONSE PSA-X-03-02 F-03-02 l '
AUX BLDG FIRE ALERT l
EVENT POINT 0391 1
INDICATED CONDITION:
o TEMPERATURE IS >135'F IN SPENT FUEL AIR HANDLING FAN AHF-8A DISCHARGE DUCT WORK AS SENSED BY AH-314-TS i
REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o AHF-8A TRIPS OPERATOR ACTIONS FOR A VALID ALARM:
o INVESTIGATE THE CAUSE OF THE ALARM o REFER TO AP-880 DISCUSSION:
THIS IS INDICATIVE OF A FIRE IN THE SPENT FUEL COOLING UNIT DISCHARGE DUCT CONSIDERATION SHOULD BE GIVEN TO CONSULTING THE FIRE PLANS FOR ADDITIONAL HELP'IN DETERMINING A COURSE OF ACTION
REFERENCES:
DRAWING 208-005 SHEETS AH-026, DRAWING 308849 SENSING ELEMENT: AH-314-TS l
l . -,. .
l lO I
l AR-401 Rev. 16 Page 82
_.. _.._. _ __.._ . . _. _ _ _ ___ _ . _ _.m.
ENCLOSURE 1 (Page 81 of 185)
'y O
PSA ANNUNCIATOR RESPONSE PSA-X-03-02 F-03-02 AUX BLEH3 FH4E ALERT 1
, EVENT POINT 0394 INDICATED CONDITION:
! o
' TEMPERATURE IS >135'F IN SPENT FUEL AIR HANDLING FAN AHF-8B DISCHARGE DUCT WORK AS SENSED BY AH-409-TS 1
REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
{ o AHF-88 TRIPS OPERATOR ACTIONS FOR A VALID ALARM:
o INVESTIGATE THE CAUSE OF THE ALARM
- o REFER TO AP-880 i
i i
- DISCUSSION
THIS IS INDICATIVE OF A FIRE IN THE SPENT FUEL COOLING UNIT OISCHARGE DUCT CONSIDERATION SHOULD BE GIVEN TO CONSULTING THE FIRE PLANS FOR j ADDITIONAL HELP IN DETERMINING A COURSE OF ACTION
REFERENCES:
DRAWING 208-005 SHEETS AH-027 DRAWING 308849 l SENSING ELEMENT: AH-409-TS 4
- O AR-401 Rev, 16 Page 83
l i
ENCLOSURE 1 i (Page 82 of 185)
A PSA-ANNUNCIATOR RESPONSE PSA-X-03-02 F-03-02 l
AUX BLDG l FIRE ALERT EVENT POINT 0403 INDICATED CONDITION:
o TEMPERATURE IS >135'F IN SPENT FUEL AREA AIR HANDLING FAN AHF-10 DISCHARGE DUCT WORK AS SENSED BY AH-377-TS REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o AHF-10 TRIPS !
D l 9 .
OPERATOR ACTIONS FOR A VALID ALARM:
o INVESTIGATE THE CAUSE OF THE ALARM o REFER TO AP-880 DISCUSSION:
THIS IS INDICATIVE OF A FIRE IN THE SPENT FUEL FLOOR AIR HANDLING UNIT DISCHARGE DUCT CONSIDERATION SHOULD BE GIVEN TO CONSULTING THE FIRE PLANS FOR ADDITIONAL HELP IN DETERMINING A COURSE OF ACTION
REFERENCES:
DRAWING 208-005 SHEETS AH-044 DRAWING 308849 SENSING ELEMENT: AH-377-TS O
AR-401 Rev. 16 Page 84
l ENCLOSURE 1
' (Page 83 of 185) d PSA ANNUNCIATOR RESPONSE PSA-X-03-02 F-03-02 i
1 AUX BLDG
, FIRE ALERT I
$ EVENT POINT 0410 i
l INDICATED CONDITION:
o TEMPERATURE IS >135'F IN AUXILIARY BUILDING SUPPLY FAN DISCHARGE DUCT
, WORK AS SENSED BY AH-318-TS i
s 4
REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
1 J
o AHF-llA/llB FANS TRIP
- OPERATOR ACTIONS FOR A VALID ALARM
o INVESTIGATE THE CAUSE OF THE ALARM j o REFER TO AP-880 1
DISCUSSION:
THIS IS INDICATIVE OF A FIRE IN THE AUXILIARY BUILDING SUPPLY FANS DISCHARGE DUCT CONSIDERATION SHOULD BE GIVEN TO CONSULTING THE FIRE PLANS FOR ADDITIONAL HELP IN DETERMINING A COURSE OF ACTION
REFERENCES:
DRAWING 203 005 SHEETS AH-045 DRAWING 308849 SENSING ELEMENT: AH-318-TS AR-401 Rev. 16 Page 85
t ENCLOSURE 1 (Page 84 of 185)
O PSA ANNUNCIATOR RESPONSE PSA-X-03-02 F-03-02 s
AdJX BLCH3 a FIRE ALERT a
J
- EVENT POINT 0416
- INDICATED CONDITION
o TEMPERATURE IS >135'F IN AUXILIARY BUILDING RECIRC FAN SUCTION DUCT j WORK AS SENSED BY AH-375-TS REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o AHF-13 TRIPS O OPERATOR ACTIONS FOR A VALID ALARM:
o INVESTIGATE THE CAUSE OF THE ALARM o REFER TO AP-880 i
i j DISCUSSION:
b THIS IS INDICATIVE OF A FIRE IN THE AUXILIARY BUILDING RECIRC FAN I DISCHARGE DUCT CONSIDERATION SHOULD BE GIVEN TO CONSULTING THE FIRE PLANS FOR ADDITIONAL HELP IN PETERMINING A COURSE OF ACTION 4
REFERENCES:
DRAWING 208-005 SHEETS AH-048 DRAWING 308849 SENSING ELEMENT: AH-375-TS O
1 4
i AR-401 Rev. 16 Page 86 l
ENCLOSURE I (Page 85 of 185) i / \
PSA ANNUNCIATOR RESPONSE PSA-X-03-02 F-03-02 1 AUX BLDG FIRE ALERT i
EVENT POINT 0426 INDICATED CONDITION:
o TEMPERATURE IS >135'F IN AUXILIARY BUILDING EXHAUST DUCT WORK AS SENSED BY AH-354-TS REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o AUXILIARY BUILDING EXHAUST FANS AHF-14A, AHF-148, AHF-14C, & AHF-14D
, TRIP l h i OPERATOR ACTIONS FOR A VALID ALARM:
o INVESTIGATE THE CAUSE OF THE ALARM o REFER TO AP-880 DISCUSSION:
l THIS IS INDICATIVE OF A FIRE IN THE AUXILIARY BUILDING EXHAUST DISCHARGE DUCT, CONSIDERATION SHOULD BE GIVEN TO CONSULTING THE FIRE PLANS FOR ADDITIONAL HELP IN DETERMINING A COURSE OF ACTION
REFERENCES:
DRAWING 208-005 SHEETS AH-001, AND AH-005, DRAWING 308849 SENSING ELEMENT: AH-354-TS .
l O
AR-40I Rev. 16 Page 87
. - - - . = _ . _ . _ . - . - - . . - . . - _ - _ _ - - - . - _ - . . - -
l 1
J ENCLOSURE 1 (Page 86 of 185) i PSA ANNUNCIATOR RESPONSE PSA-X-03-02 F-03-02 ALECBLDG FIRE ALERT 3
4 EVENT POINT 0431 i INDICATED CONDITION:
o 3
" PRODUCTS OF COMBUSTION HAVE BEEN DETECTED BY AH 156-CE o TROUBLE HAS BEEN DETECTED IN THE CIRCUITS FOR AH-156 CE
- o TEMPERATURE > 135*F AS SENSED BY AH-156-TS ET.ISTS AT THE 95' LEVEL INTERMEDIATE BUILDING i i REDUNDANT INDICATION WHICH WILL VERIFY ALARM: )
' i
'(~'N O HIGH TEMPERATURE WILL RESULT IN THE TRIP 0F AHF-24A/B IF RUNNING O l HIGH TEMPERATURE WILL RESULT IN THE ACTUATION OF FD-42, AND FD-43 i OPERATOR ACTIONS FOR A VALID ALARM:
! O REFER TO THE CR3 PRE FIRE' PLAN o REFER TO AP-880 1
DISCUSSION:
i THIS CONDITION IS INDICATIVE OF EITHER A TROUBLE IN THE FIRE DETECTION CIRCUITS, A FIRE OR A HIGH TEMPERATURE IN THE ROOM.
REFERENCES:
DRAWING 208-005 SHEETS AH-51, Aht .H-55. DRAWING 308846 4 SENSING ELERENTY AH-156-CE AH-156-TS, RELAY 3AH-156-TS/RRIA
- O AR-401 Rev. 16 Page 88
ENCLOSURE 1 (Page 87 of 185)
O PSA ANNUNCIATOR RESPONSE PSA-X-03-02 F-03-02 AUX BLENG FIRE ALERT EVENT POINT 0433 INDICATED CONDITION:
l 0
TEMPERATUP.E > 135'F AS SENSED BY AH-157-TS EXISTS AT THE 95' LEVEL INTERMEDIATE BUILDING REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o HIGH TEMPERATURE WILL RESULT IN THE ACTUATION OF FD-42, AND FD-43
- O
, OPERATOR ACTIONS FOR A VALID ALARM:
o REFER TO THE CR3 PRE FIRE PLAN O REFER TO AP-880 i
i DISCUSSION:
THE IS CONDITION IS INDICATIVE OF A FIRE OR A HIGH TEMPERATURE IN THE 95' INTERMEDIATE BUILDING.
REFERENCES:
DRAWING 208-005 SHEETS AH-51, AND AH-55. DRAWING 308846
, SENSING ELEMENT: AH-157-TS, O
i AR-401 Rev. 16 Page 89 a
ENCLOSURE 1 (Page 88 of 185) i id,,
PSA ANNUNCIATOR RESPONSE PSA-X-03-02 F-03-02 4
AUX BLDG FIRE ALERT 4 I EVENT POINT 0435
- INDICATED CONDITION:
4 o PENETRATION COOLING SUPPLY AIR DUCT TEMPERATURE UPSTREAM 0F FD-32 IS
>135'F AS SENSED BY AH-737-TS. OR AH-737-TS TROUBLE CIRCUIT HAS ACTUATED
.l REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o FD-32 FIRE DAMPER CLOSES o LOCAL TROUBLE ALARM ON AH-737-TS OPERATOR ACTIONS FOR A VALID ALARM:
o VERIFY FD-32 CLOSED o REFER TO AP-880 I
DISCUSSION:
I THIS IS INDICATIVE OF A HIGH TEMPERATURE CONDITION IN THE TURBINE BUILDING ADJACENT TO THE FAN INTAKE, OR A PROBLEM WITH THE DETECTOR.
REFERENCES:
DRAWING 208-005 SHEET AH-056, DRAWING 308849 SENSING ELEMENTi AH-737-TS, AH-737-TS TROUBLE CIRCUIT O
AR-401 Rev. 16 Page 90
ENCLOSURE 1 (Page 89 of 185)
O PSA ANNUNCIATOR RESPONSE PSA-X-03-02 F-03-02 AUX BLDG FIRE ALERT EVENT POINT 0437 INDICATED CONDITION:
o PENETRATION COOLING SUPPLY AIR DUCT TEMPERATURE UPSTREAM 0F FD-33 IS
>135'F AS SENSED BY AH-738-TS. OR AH-738-TS TROUBLE CIRCUIT HAS ACTUATED REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o FD-33 FIRE DAMPER CLOSES
\ o LOCAL TROUBLE ALARM ON AH-738-TS V
OPERATOR ACTIONS FOR A VALID ALARM:
o VERIFY FD-33 CLOSED l
l i'
DISCUSSION:
THIS IS INDICATIVE OF A HIGH TEMPERATURE CONDITION IN THE OUTSIDE AIR INTAKE, OR OF A PROBLEM WITH THE DETECTOR
REFERENCES:
DRAWING 208-005 SHEET AH-057, DRAWING 308849 SENSING ELEMENTo AH-738-TS AND AH-38-TS TROUBLE O
AR-40I Rev, 16 Page 91
ENCLOSURE I (Page 90 of 185)
PSA ANNUNCIATOR RESPONSE PSA-X-03-02 F-03-02 i
AUX BLDG FIRE ALERT ,
EVENT POINT 0439 INDICATED CONDITION:
o PENETRATION COOLING FAN DISCHARGE DUCT TEMPERATURE IS >110*F AS SENSED BY AH-305-TS REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
O LOCAL TROUBLE ALARM ON AH-305-TS O OPERATOR ACTIONS FOR A VALID ALARM:
o ENSURE CHILL WATER IS SUPPLIED TO THE OPERATING PENETRATION COOLER o INVESTIGATE THE CAUSE OF THE HIGH TEMPERATURE ALARM o REFER TO AP-880 DISCUSSION:
THIS IS INDICATIVE OF A HIGH TEMPERATURE CONDITION IN THE DISCHARGE OF THE PENETRATION COOLING FANS, OR OF A PROBLEM WITH THE DETECTOR.
REFERENCES:
DRAWING 208-005 SHEET AH-056, DRAWING 308849 l SENSING ELEMENT: AH-305-TS a
O AR-401 Rev. 16 Page 92
.. . .. -. - - . . - . _ . ~ . . . . .. . _ . . . - .. . . . . ._- . . _ . -
l 1
E_NCLOSURE I (Page 91 of 185)
PSA ANNUNCIATOR RESPONSE PSA-X-03-02 F-03-02 d
AUX BLDG FIRE ALERT 1
4 EVENT POINT 0513 4
INDICATED CONDITION:
t o TEMPERATURE > 135'F AS SENSED BY AH-132-TS EXISTS IN CLEAN MACHINE SHOP AIR HANDLING UNIT AHU-2 DISCHARGE l
i l
REDUNDANT INDICATION WHICH WILL VERIFY ALARM: I o HIGH TEMPERATURE WILL RESULT IN A TRIP 0F AHU-2
~
1
, OPERATOR ACTIONS FOR A VALID ALARM:
1 o REFER TO THE CR3 PRE FIRE PLAN o REFER TO AP-880 '
DISCUSSION:
THIS CONDITION IS-INDICATIVE OF A FIRE OR A HIGH TEMPERATURE IN THE DISCHARGE DUCT OF AHU-2.
REFERENCES:
DRAWING 208-005 SHEETS AH-094, DRAWING 308846 SENSING ELEMENT: AH-132-TS O
AR-401 Rev. 16 Page 93
ENCLOSURE I (Page 92 of 185)
O PSA ANNUNCIATOR RESPONSE PSA-X-03-02 F-03-02 1
AUX BLDG FIRE ALERT EVENT POINT 0514 INDICATED CONDITION:
o TEMPERATURE > 135'F AS SENSED 8Y AH-165-TS EXISTS IN HOT MACHINE SHOP AIR HANDLING UNIT AHU-3 DISCHARGE REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o HIGH TEMPERATURE WILL RESULT IN A TRIP OF AHU-3 O OPERATOR ACTIONS FOR A VALID ALARM:
o REFER TO THE CR3 PRE FIRE PLAN o REFER TO AP-880 i
DISCUSSION:
THIS CONDITION IS INDICATIVE OF A FIRE OR A HIGH TEMPERATURE IN THE DISCHARGE DUCT OF AHU-3.
REFERENCES:
DRAWING 208-005 SHEETS AH-095, DRAWING 308846 SENSING ELEMENT: AH-165-TS , .
AR-401 Rev. 16 Page 94
4 ENCLOSURE 1 (Page 93 of 185)
- PSA ANNUNCIATOR RESPONSE PSA-X-03-03 F-03-03 DIESEL ROOM FIRE ALERT j EVENT POINT 0460
- INDICATED CONDITION
' o PRODUCTS OF COMBUSTION HAVE BEEN DETECTED BY AH-364-CE o TROUBLE HAS BEEN DETECTED IN THE CIRCUITS FOR AH-364-CE j
REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
l 0 AN ALARM ON AH-364-CE WILL ACTUATE FD-36 AND FD-37
)
- OPERATOR ACTIONS FOR A VALID ALARM:
1 3
o DEENERGIZE AHF-28A LOCALLY OR VIA ACDP-50 BREAKER 13 ;
I o REFER TO THE PRE FIRE PLAN '
o REFER TO AP-880 1
DISCUSSION:
THIS CONDITION IS INDICATIVE OF EITHER A TROUBLE IN THE FIRE DETECTION CIRCUITS, OR A FIRE IN THE EGDG-IA ROOM.
J
REFERENCES:
DRAWING 208-005 AH-073, AH-076, AND DRAWING 308849 .
SENSING ELEMENT: AH-364-CE, 3AH-364-CE/ RELAY AR-401 Rev. 16 Page 95
4 i
ENCLOSURE 1 (Page 94 of 185)
(N )
\) PSA ANNUNCIATOR RESPONSE PSA-X-03-03 F-03-03 DIESEL ROOM FIRE ALERT i
EVENT POINT 0465 i
INDICATED CONDITION:
j
' o PRODUCTS OF COMBUSTION HAVE BEEN DETECTED BY AH-374-CE ,
o TROUBLE HAS BEEN DETECTED IN THE CIRCUITS FOR AH-374-CE j' l I !
REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
i O
AN ALARM ON AH-374-CE WILL ACTUATE FD-34 AND FD-35
(}
OPERATOR ACTIONS FOR A VALID ALARM:
o DEENERGIZE AHF-28B LOCALLY OR VIA ACDP-50 BREAKER 14 !
o REFER TO THE CR3 PRE FIRE PLAN i o REFER TO AP-880 J
DISCUSSION:
THIS CuNDITION IS INDICATIVE OF EITHER TROUBLE IN THE FIRE DETECTION CIRCUITS, OR A FIRE IN THE EGDG-IB ROOM.
REFERENCES:
DRAWING 208-005 SHEETS AH-073, AH-079, AND DRAWING 308849 .
SENSING ELEMENT: AH-374-CE, 3AH-374-CE/ RELAY O
AR-401 Rev. 16 Page 96 4
s
^
\
ENCLOSURE 1 (Page 95 of 185)
PSA ANNUNCIATOR RESPONSE PSA-X-03-04 F-03-04 i
CNTRL COMPLEX FH4E ALERT EVENT POINT 0481 i
INDICATED CONDITION:
o PRODUCTS OF COMBUSTION HAVE BEEN DETECTED BY AH-33-CE o TROUBLE HAS BEEN DETECTED IN THE CIRCUITS FOR AH-33-CE i
)
i REDUkDANT INDICATION WHICH WILL VERIFY ALARM:
o AN ALARM ON AH-33-CE WILL ALLOW THE CONTROL COMPLEX VENTILATION SYSTEM
{* TO'BE PLACED IN A SMOKE REMOVAL MODE OF OPERATION OPERATOR ACTIONS FOR A VALID ALARM:
o REFER TO THE CR3 FIRE PLAN
. O REFER TO AP-880 DISCUSSION:
THIS CONDITION IS INDICATIVE OF EITHER TROUBLE IN THE FIRE DETECTION CIRCUITS, OR A FIRE IN THE COMMON RETURN DUCT DOWNSTREAM OF AHF-19A/B
REFERENCES:
DRAWING 208-005 SHEETS AH-090, AH-079, AND DRAWING 308847 .
SENSING ELEMENT: AH-33-CE, 3AH-33-CE/ RELAY O
AR-401 Rev. 16 Page 97
i f.NCLOSURE 1 (Page 96 of 185)
- PSA ANNUNCIATOR RESPONSE PSA-X-03-04
- F-03-04 CNTRL COMPLEX FIRE ALERT EVENT POINT 0492 a
INDICATED CONDITION:
o PRODUCTS OF COMBUSTION HAVE BEEN DETECTED BY AH-529-CE o TROUBLE HAS BEEN DETECTED IN Tile CIRCUITS FOR AH-529-CE o
TEMPERATURE > 135'F AS SENSED BY AH-529-TS EXISTS AT THE 124' LEVEL 0F THE CONTROL COMPLEX REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
O o HIGH TEMPERATURE WILL RESULT IN THE ACTUATION OF FD-13 AND FD-84 V
OPERATOR ACTIONS FOR A VALID ALARM:
o REFER TO THE CR3 FIRE PLAN o REFER TO AP-880 I
DISCUSSION:
THIS CONDITION IS INDICATIVE OF EITHER TROUBLE IN THE FIRE DETECTION CIRCUITS, OR A FIRE IN THE 124' ELEVATION OF THE CONTROL COMPLEX a
REFERENCES:
DRAWING 208-005 SHEETS AH-101, AH-106, AND DRAWING 308847 .
SENSING ELEMENT: AH-529-TS AH-529-CE, 3AH-529-TS/ RELAY O
AR-401 Rev. 16 Page 98
1 !
ENCLOSURE 1 ;
(Page 97 of 185)
PSA ANNUNCIATOR RESPONSE PSA-X-03-04 F-03-04 CNTRL COMPLEX FIRE ALERT EVENT POINT 0494 l
INDICATED CONDITION:
o PRODUCTS OF COMBUSTION HAVE BEEN DETECTED BY AH-214-CE o TROUBLE HAS BEEN DETECTED IN THE CIRCUITS FOR AH-214-CE o
TEMPERATURE > 135*F AS SENSED BY AH-214-TS EXISTS AT THE 124' LEVEL OF THE CONTROL COMPLEX. ES 480V "A" SWITCHGEAR ROOM REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o HIGH TEMPERATURE WILL RESULT IN THE ACTUATION OF FD-4 AND FD-16 1
OPERATOR ACTIONS FOR A VALID ALARM: l 0 REFER TO THE CR3 PRE FIRE PLAN l 0 REFER TO AP-880
.1 l
DISCUSSION:
THIS CONDITION IS INDICATIVE OF EITHER TROUBLE IN THE FIRE DETECTION CIRCUITS, OR A FIRE IN THE 124' ELEVATION OF THE CONTROL COMPLEX
REFERENCES:
DRAWING 208-005 SHEETS AH-102, AH-107, AND DRAWING 308847 .
SENSING ELEMENT: AH-214-TS AH-214-CE, 3AH-214-TS/ RELAY ,
O V
)
AR-401 Rev. 16 Page 99
I ENCLOSURE 1 (Page 98 of 185)
PSA ANNUNCIATOR RESPONSE PSA-X-03-04 F-03-04 i
CNTRL COMPLEX FIRE ALERT l
EVENT POINT 0495 INDICATED CONDITION:
o PRODUCTS OF COMBUSTION HAVE BEEN DETECTED BY AH-212-CE o TROUBLE HAS BEEN DETECTED IN THE CIRCUITS FOR AH-212-CE o TEMPERATURE > 135'F AS SENSED BY AH-212-TS EXISTS AT THE 124' LEVEL OF THE CONTROL COMPLEX. ES 480V "B" SWITCHGEAR ROOM REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o HIGH TEMPERATURE WILL RESULT IN THE ACTUATION OF FD-2 AND FD-14 OPERATOR ACTIONS FOR A VALID ALARM:
o REFER TO THE CR3 PRE FIRE PLAN o REFER TO AP-880 DISCUSSION:
THIS CONDITION IS INDICATIVE OF EITHER TROUBLE IN THE FIRE DETECTION CIRCUITS, OR A FIRE IN THE 124' ELEVATION OF THE CONTROL COMPLEX.
REFERENCES:
DRAWING 208-005 SHEETS AH-102, AH-106, AND DRAWING 308847 .
SENSING ELEMENT: AH-212-TS AH-212-CE, 3AH-212-TS/ RELAY O
AR-401 Rev. 16 Page 100
4 ENCLOSURE 1 (Page 99 of 185)
G PSA ANNUNCIATOR RESPONSE PSA-X-03-04 F-03-04 CNTRL COMPLEX FIRE ALERT a
EVENT POINT 0498 INDICATED CONDITION:
' O PRODUCTS OF COMBUSTION HAVE BEEN DETECTED BY AH-216-CE o TROUBLE HAS BEEN DETECTED IN THE CIRCUITS FOR AH-216-CE
, o 4
TEMPERATURE > 135*F AS SENSED BY AH-216-TS EXISTS AT THE 108' LEVEL OF THE CONTROL COMPLEX. ES 4160V "A" SWITCHGEAR ROOM
'i t
REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
O HIGH TEMPERATURE WILL RESULT IN THE ACTUATION OF FD-6 AND FD-18
[}
OPERATOR ACTIONS FOR A VALID ALARM:
o REFER TO THE CR3 PRE FIRE PLAN o REFER TO AP-880 DISCUSSION:
THIS CONDITION IS INDICATIVE OF EITHER TROUBLE IN THE FIRE DETECTION CIRCUITS, OR A FIRE IN THE 108' ELEVATION OF THE CONTROL COMPLEX.
REFERENCES:
DRAWING 208-005 SHEETS AH-103, AH-107, AND DRAWING 308847 .
SENSING ELEMENT: AH-216-TS AH-216-CE, 3AH-216-TS/ RELAY O
AR-401 Rev. 16 Page 101
ENCLOSURE 1 (Page 100 of 185)
U PSA ANNUNCIATOR RESPONSE PSA-X-03-04 F-03-04 CNTRL COMPLEX FIRE ALERT EVENT POINT 0499 INDICATED CONDITION:
o PRODUCTS OF COMBUSTION HAVE BEEN DETECTED BY AH-215-CE o
TROUBLE HAS BEEN DETECTED IN THE CIRCUITS FOR AH-215-CE o TEMPERATURE > 135'F AS SENSED BY AH-215-TS EXISTS AT THE 108' LEVEL OF THE CONTROL COMPLEX. ES 4160V "B" SWITCHGEAR ROOM REDUNDANTINDICATIONWHICHWILLVERIFiALARM:
/ o HIGH TEMPERATURE WILL RESULT IN THE ACTUATION OF FD-5 AND FD-17 OPERATOR ACTIONS FOR A VALID ALARM:
o REFER TO THE CR3 PRE FIRE PLAN o REFER TO AP-880 DISCUSSION:
THIS CONDITION IS INDICATIVE OF EITHER TROUBLE IN THE FIRE DETECTION CIRCUITS, OR A FIRE IN THE 108' ELEVATION OF THE CONTROL COMPLEX.
REFERENCES:
DRAWING 208-005 SHEETS AH-103, AH-107, AND DRAWING 308847 .
SENSING ELEMENT: AH-215-TS AH-215-CE, 3AH-215-TS/ RELAY O
AR-401 Rev. 16 Page 102
ENCLOSURE 1 (Page 101 of 185)
PSA ANNUNCIATOR RESPONSE PSA-X-03-04 F-03-04 CNTRL COMPLEX FIRE ALERT EVENT POINT 0500 4
INDICATED CONDITION:
o PRODUCTS OF COMBUSTION HAVE BEEN DETECTED BY AH-220-CE
- 0 TROUBLE HAS BEEN DETECTED IN THE CIRCUITS FOR AH-220-CE o TEMPERATURE > 135*F AS SENSED BY AH-220-TS EXISTS IN "A" BATTERY CHARGER ROOM REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o HIGH TEMPERATURE WILL RESULT IN THE ACTUATION OF FD-42 AND FD-43 OPERATOR ACTIONS FOR A VALID ALARM:
o REFER TO THE CR3 PRE FIRE PLAN o REFER TO AP-880 DISCUSSION:
THIS CONDITION IS INDICATIVE OF EITHER A TROUBLE IN THE FIRE DETECTION CIRCUITS, A FIRE, OR A HIGH TEMPERATURE IN THE ROOM.
- ~
REFERENCES:
~ DRAWING 208-005 SHEET AH-104 SENSING ELEMENT: AH-220-TS. AH-220-CE.
AR-401 Rev. 16 Page 103
-- . _ . _ = _ _ _ _ - . . _ -. ..
i ENCLOSURE 1
-'s (Page 102 of 185) 1 PSA ANNUNCIATOR RESPONSE PSA-X-03-04 F-03-04 4
CNTRL COMPLEX FIRE ALERT i
1 EVENT POINT 0501 INDICATED CONDITION:
o PRODUCTS OF COMBUSTION H4VE BEEN DETECTED BY AH-217-CE o TROUBLE HAS BEEN DETECTED IN THE CIRCUITS FOR AH-217-CE o TEMPERATURE > 135'F AS SENSED BY AH-217-TS EXISTS IN "B" BATTERY !
CHARGER ROOM j
REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
fT (s / o HIGH TEMPERATURE WILL RESULT IN THE ACTUATION OF FD-19 l
I l
OPERATOR ACTIONS FOR A VALID ALARM:
o REFER TO THE CR3 PRE FIRE PLAN o REFER T0 AP-880
- l DISCUSSION:
THIS CONDITION IS INDICATIVE OF EITHER A TROUBLE IN THE FIRE DETECTION i CIRCUITS, A FIRE OR A HIGH TEMPERATURE IN THE ROOM.
REFERENCES:
~ DRAWING 208-005 SHEETS AH-103, AH-109, AND DRAWING 308847
- SENSING ELEMENT: AH-217-TS, AH-217-CE, AR-401 Rev. 16 Page 104
l 4
ENCLOSURE 1 (Page 103 of 185)
PSA ANNUNCIATOR RESPONSE PSA-X-03-04 F-03-04 I 1
CNTRL COMPLEX FIRE ALERT EVENT POINT 0502 INDICATED CONDITION:
o PRODUCTS OF COMBUSTION HAVE BEEN DETECTED BY AH-219-CE ,
o TROUBLE HAS BEEN DETECTED _IN THE CIRCUITS FOR AH-219-CE !
O TEMPERATURE > 135'F AS SENSED BY AH-219-TS EXISTS IN "A" BATTERY ROOM REDUNDANT INDICATION WHICH WILL VERIFY ALARM: l 0
HIGH TEMPERATURE WILL RESULT IN THE ACTUATION OF FD-9 AND FD-21 l
OPERATOR ACTIONS FOR A VALID ALARM:
o REFER TO THE CR3 PRE FIRE PLAN o REFER TO AP-880 i
DISCUSSION:
THIS CONDITION IS INDICATIVE OF EITHER TROUBLE IN THE FIRE DETECTION CIRCUITS, A FIRE, OR A HIGH TEMPERATURE IN THE ROOM.
REFERENCES:
DRAWING 208-005 SHEETS AH-104, AH-108, DRAWING 308847 SENSING ELEMENT: AH-219-CE, AH-219-TS O
AR-401 Rev. 16 Page 105
c ENCLOSURE 1 (Page 104 of 185)
PSA ANNUNCIATOR RESPONSE ,
PSA-X-03-04 F-03-04 4
1 CNTRL COMPLEX FIRE ALERT 1
EVENT POINT 0503 INDICATED CONDITION:
o PRODUCTS OF COMBUSTION HAVE BEEN DETECTED BY AH-218-CE o TROUBLE HAS BEEN DETECTED IN THE CIRCUITS FOR AH-218-CE o TEMPERATURE > 135'F AS SENSED BY AH-218-TS EXISTS IN THE "B" BATTERY ROOM l
l REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
(' o I HIGH TEMPERATURE WILL RESULT IN THE ACTUATION OF FD-220 AND FD-222 l OPERATOR ACTIONS FOR A VALID ALARM:
o REFER TO THE CR3 PRE FIRE PLAN o REFER TO AP-880 DISCUSSION:
THIS CONDITION IS INDICATIVE OF EITHER TROUBLE IN THE FIRE DETECTION CIRCUITS, A FIRE OR A HIGH TEMPERATURE IN THE ROOM.
REFER TO THE CR3 FIRE PROTECTION PLAN FOR ADMINISTRATIVE REQUIREMENTS.
REFERENCES:
DRAWING 208-005 SHEETS AH-103, AH-108 AND DRAWING 308847
( SENSING ELEMENT: AH-218-CE, AH-218-TS AR-401 Rev. 16 Page 106
ENCLOSURE 1 (Page 105 of 185)
PSA ANNUNCIATOR RESPONSE PSA-X-03-04 F-03-04 l
CNTRL COMPLEX l FIRE ALERT EVENT POINT 0504 ,
i INDICATED CONDITION: {
o PRODUCTS OF COMBUSTION HAVE BEEN DETECTED BY AH-222-CE _
o TROUBLE HAS BEEN DETECTED IN THE CIRCUITS FOR AH-222-CE ;
o TEMPERATURE > 135'F AS SENSED BY AH-222-TS EXISTS IN THE "A" INVERTER !
ROOM REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o HIGH TEMPERATURE WILL RESULT IN THE ACTUATION OF FD-12 AND FD-24 OPERATOR ACTIONS FOR A VALID ALARM:
o REFER TO THE CR3 PRE FIRE PLAN 1
o REFER TO AP-880 l
l DISCUSSION:
)
THIS CONDITION IS INDICATIVE OF EITHER TROUBLE IN THE FIRE DETECTION CIRCUITS, A FIRE OR A HIGH TEMPERATURE IN THE ROOM.
REFER TO THE CR3 FIRE PROTECTION PLAN FOR ADMINISTRATIVE REQUIREMENTS.
REFERENCES:
~. DRAWING 208-005 SHEETS AH-104, AH-109 AND DRAWING 308847 ~
SENSING ELEMENT: AH-222-CE, AH-222-TS O
AR-401 Rev. 16 Page 107 1
i ENCLOSURE 1 g (Page 106 of 185)
'V i PSA ANNUNC.'ATOR RESPONSE PSA-X-03-04 F-03-04 i'
l CNTRL COMPLEX l FIRE ALERT EVENT POINT 0505 4
INDICATED CONDITION:
o PRODUCTS OF COMBUSTION HAVE BEEN DETECTED BY AH-221-CE o TROUBLE HAS BEEN DETECTED IN THE CIRCUITS FOR AH-221-CE o TEMPERATURE > 135'F AS SENSED BY AH-221-TS EXISTS IN THE "B" INVERTER ROOM p REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o HIGH TEMPERATURE WILL RESULT IN THE ACTUATION OF FD-Il AND FD-23 l
I OPERATOR ACTIONS FOR A VALID ALARM:
o REFER TO THE CR3 PRE FIRE PLAN o REFER TO AP-880 DISCUSSION:
THIS CONDITION IS INDICATIVE OF EITHER TROUBLE IN THE FIRE DETECTION CIRCUITS, A FIRE OR A HIGH TEMPERATURE IN THE ROOM.
REFER TO THE CR3 FIRE PROTECTION PLAN FOR ADMINISTRATIVE REQUIREMENTS.
REFERENCES:
DRAWING 208-005 SHEETS AH-104, AH-109 AND DRAWING 308847 SENSING ELEMENT: AH-221-CE, AH-221-TS AR-401 Rev. 16 Page 108
J
[NCLOSURE I (Page 107 of 185) 5 PSA ANNUNCIATOR RESPONSE PSA-X-03-04 F-03-04 CNTRL COMPLEX 1
FIRE ALERT EVENT POINT 0506 INDICATED CONDITION:
o PRODUCTS OF COMBUSTION HAVE BEEN DETECTED BY AH-235-CE o TROUBLE HAS BEEN DETECTED IN THE CIRCUITS FOR AH-235-CE o
TEMPERATURE > 135'F AS SENSED BY AH-235-TS EXISTS IN THE CONTROL COMPLEX STAIR WELL REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
O o HIGH TEMPERATURE WILL RESULT IN THE ACTUATION OF FD-25 OPERATOR ACTIONS FOR A VALID ALARM:
o REFER TO THE CR3 PRE FIRE PLAN o REFER TO AP-880 DISCUSSION:
THIS CONDITION IS INDICATIVE OF EITHER TROUBLE IN THE FIRE DETECTION CIRCUITS, A FIRE OR A HIGH TEMPERATURE IN THE ROOM.
REFER TO THE CR3 FIRE PROTECTION PLAN FOR ADMINISTRATIVE REQUIREMENTS.
REFERENCES:
DRAWING 208-005 SHEETS AH-105, AH-109 AND DRAWING 308847 O SENSING ELEMENT: AH-235-CE AH-235-TS AR-401 Rev. 16 Page 109
ENCLOSURE 1 p (Page 108 of 185)
V PSA ANNUNCIATOR RESPONSE PSA-X-03-04 F-03-04 CNTRL COMPLEX FIRE ALERT EVENT POINT 0507 INDICATED CONDITION:
o PRODUCTS OF COMBUSTION HAVE BEEN DETECTED BY AH-236-CE o TROUBLE HAS BEEN DETECTED IN THE CIRCUITS FOR AH-236-CE o
TEMPERATURE > 135'F AS SENSED BY AH-236-TS EXISTS AT THE 108' LEVEL OF THE CONTROL COMPLEX REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o HIGH TEMPERATURE WILL RESULT IN THE ACTUATION OF FD-26 AND FD-27 OPERATOR ACTIONS FOR A VALID ALARM:
o REFER TO THE CR3 PRE FIRE PLAN O REFER TO AP-880 DISCUSSION:
THIS CONDITION IS INDICATIVE OF EITHER TROUBLE IN THE FIRE DETECTION CIRCUITS, OR A FIRE IN THE 108' ELEVATION OF THE CONTROL COMPLEX
REFERENCES:
- . DRAWING 208-005 SHEETS AH-105, AH-109, AND DRAWING 308847
- SENSING ELEMENT: AH-236-TS AH-236-CE, 3AH-236-TS/ RELAY O
AR-401 Rev. 16 Page 110
. . _ _ . _ __._m.__ . ____.=m _. _ _ _ . _ _ . _ _ _ _ _ . _ . . _ . _ _ . . . _ . . _ . . . . _ . . .
I ENCLOSURE 1
- e (Page 109 of 185)
$k PSA ANNUNCIATOR RESPONSE PSA-X-03-04 F-03-04 i
4 CNTRL COMPLEX FIRE ALERT d
l EVENT POINT 1532
- INDICATED CONDITION
l o TEMPERATURE > 135*F AS SENSED BY AH-534-TS EXISTS IN THE CONTROL COMPLEX MAIN AIR HANDLING SUPPLY DUCT AT 145' ELEVATION 1
l
! REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
l
() o HIGH TEMPERATURE WILL RESULT IN THE ACTUATION OF FD-56 OPERATOR ACTIONS FOR A VALID ALARM: l l
4 o REFER TO THE CR3 PRE FIRE PLAN '
o REFER TO AP-880 l
?
i l l
DISCUSSION:
THIS CONDITION IS INDICATIVE OF A FIRE IN THE MAIN SUPPLY DUCT OF THE CONTROL COMPLEX.
REFERENCES:
~.. DRAWING 208-005 SHEETS AH-101, AH-105, AND DRAWING 308847
- SENSING ELEMENT: AH-534-TS, 3AH-534-TS/RR-HV-AU O
AR-401 Rev. 16 Page 111
j
{ ENCLOSURE 1
~
(Page 110 of 185)
PSA ANNUNCIATOR RESPONSE PSA-X-03-04 F-03-04 l
CNTRL COMPLEX FIRE ALERT EVENT POINT 1533 INDICATED CONDITION:
o PRODUCTS OF COMBUSTION HAVE BEEN DETECTED BY AH-531-CE o TROUBLE HAS BEEN DETECTED IN THE CIRCUITS FOR AH-53I-CE REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
c P00VCTS OF COMBUSTION DETECTION WILL RESULT IN THE ACTUATION OF FD-51 OPERATOR ACTIONS FOR A VALID ALARM:
o REFER TO THE CR3 PRE FIRE PLAN o REFER TO AP-880 '
l DISCUSSION:
THIS CONDITION IS INDICATIVE OF EITHER TROUBLE IN THE FIRE DETECTION CIRCUITS, OR A FIRE IN THE OUTSIDE AIR INTAKE OF THE CONTROL COMPLEX.
REFERENCES:
~. DRAWING 208-005 SHEETS AH-101, AH-106, AND DRAWING 308847 ~
SENSING ELEMENT: AH-53I-CE AR-401 Rev. 16 Page 112
ENCLOSURE 1 (Page 111 of 185) l PSA ANNUNCIATOR RESPONSE PSA-X-03-04 F-03-04 CNTRL COMPLEX FIRE ALERT i EVENT POINT 1534 !
l INDICATED CONDITION:
o PRODUCTS OF COMBUSTION HAVE BEEN DETECTED BY AH-535-CE o
TROUBLE HAS BEEN DETECTED IN THE CIPCUITE FOR AH-535-CE o
TEMPERATURE > 135*F AS SENSED BY AH-63b-TS EXISTS IN THE CONTROL COMPLEX MAIN SUPPLY DUCT 95' ELEVATION REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
( 0 HIGH TEMPERATURE WILL RESULT IN THE ACTUATION OF FD-55 l
1 OPERATOR ACTIONS FOR A VALID ALARM:
o REFER TO THE CR3 PRE FIRE PLAN o REFER TO AP-880 i
DISCUSSION:
THIS CONDITION IS INDICATIVE OF EITHER TROUBLE IN THE FIRE DETECTION CIRCUITS, OR A FIRE IN THE MAIN SUPPLY DUCT OF THE CONTROL COMPLEX.
l i
I
REFERENCES:
-.. DRAWING 208-005 SHEETS AH-101, AH-106, AND DRAWING 308847 *
{ SENSING ELEMENT: AH-535-TS AH-535-CE, 3AH-535-TS/ RELAY l
AR-401 Rey, 16 Page 113 i
ENCLOSURE I (Page 112 of 185)
PSA ANNUNCIATOR RESPONSE PSA-X-03-04 F-03-04 CNTRL COMPLEX FIRE ALERT EVENT POINT 1535 INDICATED CONDITION:
o TEMPERATURE > 135'F AS SENSED BY AH-533-TS EXISTS IN THE CONTROL COMPLEX MAIN RETURN AIR DUCT AT 145' ELEVATION REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o HIGH TEMPERATURE WILL RESULT IN THE ACTUATION OF FD-57
, OPERATOR ACTIONS FOR A VALID ALARM:
o REFER TO THE CR3 PRE FIRE PLAN O REFER TO AP-880 DISCUSSION:
THIS CONDITION IS INDICATIVE OF A FIRE IN THE RETURN AIR DUCT OF THE CONTROL COMPLEX.
REFERENCES:
-,. DRAWING 208-005 SHEETS AH-101, AH-106, AND DRAWING 308847
- SENSING ELEMENT: AH-533-TS. 3AH-533-TS/RR-HV-AT O
AR-401 Rev. 16 Page 114
l' ENCLOSURE 1 (Page 113 of 185) j 3'
l PSA ANNUNCIATOR RESPONSE PSA-X-03-04 F-03-04 {
l CNTRL COMPLEX FIRE ALERT EVENT POINT 1536 INDICATED CONDITION: l i
o PRODUCTS OF COMBUSTION HAVE BEEN DETECTED BY AH-211-CE o TROUBLE HAS BEEN DETECTED IN THE CIRCUITS FOR AH-211-CE o
TEMPERA 10RE > 135'F AS SENSED BY AH-211-TS EXISTS AT THE 134' LEVEL OF THE CONTROL COMPLEX l
1 i
REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o HIGH TEMPERATURE WILL RESULT IN THE ACTUATION OF THE FOLLOWING:
FD-45, FD-46, FD-47, FD-81, FD-82, AND FD-83 OPERATOR ACTIONS FOR A VALID ALARM:
o REFER TO THE CR3 PRE FIRE PLAN o REFER TO AP-880 l
DISCUSSION: I i
THIS CONDITION IS INDICATIVE OF EITHER TROUBLE IN THE FIRE DETECTION )
CIRCUITS, OR A FIRE IN THE 134' ELEVATION OF THE CONTROL COMPLEX IN THE '
CABLE SPREADING ROOM.
REFERENCES:
,. DRAWING 208-005 SHEETS AH-105, AH-107, AND DRAWING 308847
- SENSING ELEMENT: AH-211-TS AH-211-CE, 3AH-211-TS/ RELAY O
I AR-401 Rev. 16 Page 115
. _ - _ .. . . _ . . . - - - . . - - -.- . . . - - . . _ _ - . . . . . = . - -
l l
ENCLOSURE 1 l
(Page 114 of 185)
O PSA ANNUNCIATOR RESPONSE PSA-X-03-05 F-03-05 RUSTY BLDG FIRE ALERT EVENT POINT 0427 INDICATED CONDITION:
o DUCT TEMPERATURE AT DISCHARGE OF AHF-46 IS > 125'F AS SENSED BY AH-667-TS REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o AHF-46 TRIPS DUE TO INTERLOCK OPERATOR ACTIONS FOR A VALID ALARM:
o ENSURE AHF-46 IS SHUTDOWN o INVESTIGATE CAUSE OF ALARM DISCUSSION: .
THIS ALARM IS AN INDICATION OF A POSSIBLE FIRE IN THE DUCT WORK. '
CONSIDERATION SHOULD BE GIVEN TO CONSULTING FIRE PLANS FOR THE APPROPRIATE ACTIONS.
AHF-46 IS THE RUSTY BUILDING RECIRC FAN.
REFERENCES:
_,. DRAWING 208-005 SHEET AH-142
- l SENSING ELEMENT: AH-667-TS i
O AR-401 Rev. 16 Page 116
l l
\
.l ENCLOSURE 1 i (Page 115 of 185)
PSA ANNUNCIATOR RESPONSE PSA-X-03-05 F-03-05 l RUSTY BLDG FIRE ALERT EVENT POINT 0512 INDICATED CONDITION:
o DUCT TEMPERATURE AT DISCHARGE OF AHU-7 IS > 125'F AS SENSED BY AH-670-TS REDUNDANT INDICATION WHICH WILL VERIFY ALARM: i o AHU-7 TRIPS DUE TO INTERLOCK O OPERATOR ACTIONS FOR A VALID ALARM:
o ENSURE AHU-7 IS SHUTDOWN o INVESTIGATE CAUSE OF ALARM DISCUSSION:
THIS ALARM IS AN INDICATION OF A POSSIBLE FIRE IN THE DUCT WORK.
CONSIDERATION SHOULD BE GIVEN TO CONSULTING FIRE PLANS FOR THE APPROPRIATE ACTIONS.
AHU-7 IS THE RUSTY BUILDING AIR CONDITIONING UNIT.
REFERENCES:
DRAWING 208-005 SHEET AH-144 SENSING ELEMENT: AH-670-TS 1
lO AR-401 Rev. 16 Page 117
l i
ENCLOSURE 1 :
(Page II6 of 185) !
M PSA ANNUNCIATOR RESPONSE PSA-X-03-06 l F-03-06 i
FIRE PUMP HOUSE i FIRE ALERT EVENT POINT 0455 1
I' INDICATED CONDITION:
O PRODUCTS OF COMBUSTION HAVE BEEN DETECTED BY AH-386-CE o
TROUBLE HAS BEEN DETECTED IN THE CIRCUITS FOR AH-386-CE l
REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o O
OPERATOR ACTIONS FOR A VALID ALARM:
o NOTIFY TURBINE BUILDING OPERATOR TO INVESTIGATE THE FIRE PUMP HOUSE.
l
[
DISCUSSION:
l l
t
REFERENCES:
DRAWING 208-00S SHEET AH-072
, SENSING ELEMENT; AH-386-CE
- O AR-401 Rev. 16 Page 118
l l
i I
ENCLOSURE 1 (Page 117 of 185)
)
PSA ANNUNCIATOR RESPONSE PSA-X-03-07 F-03-07 l
FIRE l
SYSTEM TROUBLE 1
EVENT POINT 0197 INDICATED CONDITION:
o FIRE SERVICE PANEL IN THE CONTROL ROOM HAS AN UNACKNOWLEDGED OR UNRESET ALARM l
REDUNDANT INDICATION WHICH WILL VERIFY ALARM: J o
ALARM ON THE FIRE SERVICE PANEL OR ONE OF THE PYROTRONICS PANELS O
1 OPERATOR ACTIONS FOR A VALID ALARM:
1 o IMMEDIATE INVESTIGATION OF ALARM CAUSE SHOULD BE INITIATED DISCUSSION:
REFER TO THE CR3 FIRE PROTECTION PLAN FOR ADMINISTRATIVE REQUIREMENTS.
i t
REFERENCES:
DRAWING 208-031 SHEET FS-21
. SENSING ELEMENI;
- l AR-401 Rev. 16 Page 119
ENCLOSURE 1 (Page 118 of 185)
PSA ANNUNCIATOR RESPONSE PSA-X-04-01 F-04-01 l
E I REACTOR BLDG PURGE FAN TRIP l
EVENT POINT 0384 INDICATED CONDITION:
o AHF-7A MOTOR NOT ENERGIZED WITH THE CONTROL HANDLE IN NORMAL AFTER START POSITION REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o GREEN LIGHT ON WITH A RED FLAG ON AHF-7A CONTROL STATION O
OPERATOR ACTIONS FOR A VALID ALARM: 1 o SECURE RB PURGE o REFER TO OP-417 DISCUSSION:
THIS CONDITION MAY BE CAUSED BY ACTUATION OF A FIRE ALERT IN THE DUCT l INDICATED BY EVENT POINT 0387, OR AN FSV-Il4 DELUGE VALVE ACTUATION l
)
REFERENCES:
DRAWING 208-005 SHEETS AH-022, AH-015 l . SENSING ELEMENT- CS/SC, CS/0, 42/49B RELAY -
I j AR-401 Rev. 16 Page 120
ENCLOSURE 1 (Page 119 of 185) :
PSA ANNUNCIATOR RESPONSE PSA-X-04-01 F-04-01 REACTOR BLDG PURGE FAN TRIP EVENT POINT 0385 INDICATED CONDITION:
o AHF-78 MOTOR NOT ENERGIZED WITH THE CONTROL HANDLE IN NORMAL AFTER START POSITION REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o GREEN LIGHT ON WITH A RED FLAG ON AHF-78 CONTROL STATION 1
OPERATOR ACTIONS FOR A VALID ALARM: <
o SECURE RB PURGE '
o REFER TO OP-417 DISCUSSION:
THIS CONDITION MAY BE CAUSED BY ACTUATION OF A FIRE ALERT IN THE DUCT INDICATED BY EVENT POINT 0387, OR AN FSV-ll4 DELUGE VALVE ACTUATION
REFERENCES:
DRAWING 208-005 SHEETS AH-023, AH-015
, SENSING ELEMENI; CS/SC, CS/0, 42/49B RELAY
- 4 f
O AR-401 Rev. 16 Page 121 i
. - . - - . . -- . - . - - - . . - . . . _ , . ~ . . - . -- . - . _ .
ENCLOSURE 1 (Page 120 of 185)
PSA ANNUNCIATOR RESPONSE PSA-X-04-02 F-04-02 l
AH FLTR 1 DIFF PRESS I HIGH EVENT POINT 0497 INDICATED CONDITION:
o DIFFERENTIAL PRESS ACROSS AHFL-1 IS > 5.2 "H,0 AS SENSED BY AH-586A-DPS, OR AH-5868-DPS i
REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o HIGH FLOW INDICATED ON AH-32-FIR !
o LOCAL DIFFERENTIAL PRESSURE INDICATIONS ON AH-586-DPI
{
OPERATOR ACTIONS FOR A VALID ALARM: !
O REDUCE RB PURGE FLOW RATE o REFER TO OP-417 l
DISCUSSION:
THIS CONDITION IS INDICATIVE OF EXCESSIVE FLOW THROUGH THE PURGE EXHAUST FILTERS.
REFERENCES:
DRAWING 308848 SENSING ELEMENT: AH-586A-DPS, AH-586B-DPS lO AR-401 Rev. 16 Page 122
ENCLOSURE 1
, (Page 121 of 185)
U PSA ANNUNCIATOR RESPONSE PSA-X-04-03 F-04-03 REACTOR BLDG MISC CLG FANS TRIP l
EVENT POINT 0360 INDICATED CONDITION:
o AHF-2A MOTOR IS NOT ENERGIZED WITH THE CONTROL HANDLE IN NORMAL AFTER START POSITION REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
l 0 GREEN LIGHT ON WITH A RED FLAG ON AHF-2A CONTROL STATION OPERATOR ACTIONS FOR A VALID ALARM:
o SWAP REACTOR CAVITY COOLING T0 "B" SIDE PER OP-417 o MONITOR REACTOR CAVITY TEMPS ON AH-1003-TIR PER OP-409 l
DISCUSSION:
- . A SUSTAINED LOSS OF COOLING TO THE REACTOR CAVITY WILL HAVE ADVERSE EFFECTS ON THE RELIABILITY OF THE NUCLEAR INSTRUMENTATION.
l
REFERENCES:
DRAWINGS 208-005-AH-031, 308848 l , SENSING ELEUENL: CS/SC, CS/0, 42B RELAY -
t i
AR-401 Rev. 16 Page 123 l
t
~
ENCLOSURE 1 (Page 122 of 185)
PSA ANNUNCIATOR RESPONSE PSA-X-04-03 F-04-03 i
\
REACTOR BLDG MISC CLG FANS l
TRIP
, EVENT POINT 0362 INDICATED CONDITION:
I o
AHF-2B MOTOR IS NOT ENERGIZED WITH THE CONTROL HANDLE IN NORMAL AFTER START POSITION
, REDUNDANT INDICATION WHICH WILL h.RIFY ALARM:
l 0 GREEN LIGHT ON WITH A RED FLAG ON AHF-28 CONTROL STATION <
l OPERATOR ACTIONS FOR A VALID ALARM:
o SWAP REACTOR CAVITY COOLING T0 "A" SIDE PER OP-417 o MONITOR REACTOR CAVITY TEMPS ON AH-1003-TIR PER OP-409 DISCUSSION:
A SUSTAINED LOSS OF COOLING TO THE REACTOR CAVITY WILL HAVE ADVERSE EFFECTS ON THE RELIABILITY OF THE NUCLEAR INSTRUMENTATION,
REFERENCES:
DRAWINGS 208-005-AH-033, 308848
, SENSING ELEENT; CS/SC, CS/0, 428 RELAY
- AR-401 Rev. 16 Page 124
. - -- .. . .- -.=- -.
ENCLOSURE 1 (Page 123 of 185)
I (/
l PSA ANNUNCIATOR RESPONSE PSA-X-04-03 F-04-03 i
! I REACTOR BLDG !
MISC CLG FANS I TRIP l
i EVENT POINT 0365 INDICATED CONDITION:
l O
AHF-3A MOTOR NOT ENERGIZED WITH THE CONTROL HANDLE IN NORMAL AFTER START POSITION ,
i REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o GREEN LIGHT ON WITH A RED FLAG ON AHF-3A CONTROL STATION O
OPERATOR ACTIONS FOR A VALID ALARM:
o ENSURE AHF-38 IS OPERATING o TRANSFER RMA-6 SUCTION, REFER TO OP-417 DISCUSSION:
i i
REFERENCES:
DRAWINGS 208-005-AH-036, 308848
. . SENSING ELEMENT: CS/SC, CS/0, 428 RELAY
- I
!O AR-401 Rev. 16 Page 125
I 1
i ENCLOSURE 1 (Page 124 of 185)
PSA ANNUNCIATOR RESPONSE PSA-X-04-03 F-04-03 i
REACTOR BLDG MISC CLG FANS TRIP EVENT POINT 0368 INDICATED CONDITION:
o AHF-38 MOTOR IS NOT ENERGIZED WITH THE CONTROL HANDLE IN NORMAL AFTER START POSITION <
REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
I o GREEN LIGHT ON WITH A RED FLAG ON AHF-3B CONTROL STATION l O
OPERATOR ACTIONS FOR A VALID ALARM:
o START AHF-3A o TRANSFER RMA-6 SUCTION TO RB ATMOSPHERE, nii:1 TO OP-417 4
DISCUSSION:
RM-A6 MONITORS THE REACTOR BUILDING ATMOSPHERE VIA EITHER THE DUCT OF AHF-38 08 THE R.B. ATMOSPHERE. THE TRANSFER OF THE SAMPLE POINT PER OP-417 IS A MANUAL OPEF:ATION, REFER TO TS FOR ADMINISTRATIVE REQUIREMENTS.
l
REFERENCES:
DRAWINGS 208-305-AH-036, 306348 SENSING ELEMENT: CS/SC, CS/0, 42B RELAY lO AR-401 Rev. 16 Page 126
r ENCLOSURE 1 ;
p (Page 125 of 105) s l
l PSA ANNUNCIATOR RESPONSE PSA-X-04-03 F-04-03 I REACTOR BLDG MISC CLG FANS I TRIP l EVENT POINT 0371 INDICATED CONDITION:
l 0
AHF-4A MOTOR IS NOT ENERGIZED WITH THE CONTROL HANDLE IN NORMAL AFTER START POSITION REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o GREEN LIGHT ON WITH A RED FLAG ON AHF-4A CONTROL STATION O
OPERATOR ACTIONS FOR A VALID ALARM:
o START AHF-4B o REFER TO OP-417 DISCUSSION:
REFERENCES:
DRAWINGS 208-005-AH-038, 308848
, SENSING ELEMENT- CS/SC, CS/0, 42B RELAY -
A AR-401 Rev, 16 Page 127
~ . _ - _
ENCLOSURE 1 (Page 126 of 185) l
,O l PSA ANNUNCIATOR RESPONSE PSA-X-04-03 F-04-03 1
REACTOR BLDG MISC CLG FANS TRIP l
EVENT POINT 0373 INDICATED CONDITION:
o AHF-4B MOTOR IS NOT ENERGIZED WITH THE CONTROL HANDLE IN NORMAL AFTER START POSITION REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
l o GREEN LIGHT ON WITH A RED FLAG ON AHF-4B CONTROL STATION O
OPERATOR ACTIONS FOR A VALID ALARM:
o START AHF-4A o REFER TO OP-417 l
- DISCUSSION
l l
l
REFERENCES:
DRAWINGS 208-005-AH-040, 308848
, SENSING ELEMEND CS/SC, CS/0, 428 RELAY -
O AR-401 Rev. 16 Page 128 1
ENCLOSURE 1 l (Page 127 of 185) k-l PSA ANNUNCIATOR RESPONSE PSA-X-04-03 F-04-03 REACTOR BLDG MISC CLG FANS TRIP l
EVENT POINT 0378 i
INDICATED CONDITION: !
l o AHF-6A MOTOR IS NOT ENERGIZED WITH THE CONTROL HANDLE IN NORMAL AFTER I START POSITION REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o GREEN LIGHT ON WITH A RED FLAG ON AHF-6A CONTROL STATION s o LOSS OF RB PURGE FLOW AS READ ON AH-32-FIR
\.
OPERATOR ACTIONS FOR A VALID ALARM:
o START AHF-6B o REESTABLISH RB PURGE IF REQUIRED o REFER TO OP 417 DISCUSSION:
ONLY ONE PURGE SUPPLY FAN IS REQUIRED FOR ESTABLISHING AN RB PURGE, SOME OF THE THINGS THAT WILL CAUSE THE PURGE SUPPLY FAN TO TRIP ARE A LOSS OF EITHER OF THE PURGE EXHAUST FANS AHF-7A/AHF-7B, ACTUATION OF FIRE ALERT EVENT POINT 0380
REFERENCES:
DRAWINGS 208-005 SHEETS AH-015, AH-20, DRAWING 308848 SENSING ELEMENT: CS/SC, CS/0, 42B RELAY O
AR-401 Rev. 16 Page 129
ENCLOSURE 1
,n (Page 128 of 185)
PSA ANNUNCIATOR RESPONSE PSA-X-04-03 F-04-03 ,
I REACTOR BLDG l MISC CLG FANS l TRIP I EVENT POINT 0379 INDICATED CONDITION:
o AHF-6B MOTOR IS NOT ENERGIZED WITH THE CONTROL HANDLE IN NORMAL AFTER i'
START POSITION REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o GREEN LIGHT ON WITH A RED FLAG ON AHF-6B CONTROL STATION o LOSS OF RB PURGE FLOW AS READ ON AH-32-FIR OPERATOR ACTIONS FOR A VALID ALARM:
o START AHF-6A o REESTABLISH RB PURGE IF REQUIRED o REFER TO OP-417 DISCUSSION:
ONLY ONE PURGE SUPPLY FAN IS REQUIRED FOR ESTABLISHING AN RB PURGE, SOME OF THE THINGS THAT WILL CAUSE THE PURGE SUPPLY FAN TO TRIP ARE A LOSS OF EITHER OF THE PURGE EXHAUST FANS AHF-7A/AHF-7B, ACTUATION OF FIRE ALERT EVENT POINT 0380 REFEP.ENCES: DRAWINGS 208-005 SHEETS AH-015, AH-21, DRAWING 308848 SENSING ELEMENT: CS/SC, CS/0, 428 RELAY O
AR-401 Rev. 16 Page 130
l ENCLOSURE 1 (Page 129 of 185)
C PSA ANNUNCIATOR RESPONSE PSA-X-04-04 F-04-04 1
REACTOR BLDG MISC AIR FLOW l LOW l
EVENT POINT 0364 INDICATED CONDITION:
O AHF-2A AND/0R AHF-28 CONTROL HANDLE IN NORMAL AFTER START AND A LOW DIFF, PRESS. <0.25" H,0 EXISTS AS SENSED BY AH-10-DPS AND/0R AH-532-DPS REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o CLOSED INDICATION OF AHD-1A i
o CLOSED INDICATION ON AHD-1B OPERATOR ACTIONS FOR A VALID ALARM:
o SWAP REACTOR CAVITY COOLING PER OP-417 o MONITOR REACTOR CAVITY TEMPERATURES ON AH-1003-TIR PER OP-409 DISCUSSION:
A SUSTAINED LOSS OF COOLING TO THE REACTOR CAVITY COULD HAVE ADVERSE EFFECTS ON THE RELIABILITY OF THE NUCLEAR INSTRUMENTATION.
IF FLOW CANNOT BE RESTORED THEN CONSIDERATION SHOULD BE GIVEN TO SHUTTING D0WN THE PLANT.
REFERENCES:
' DRAWINGS 208-005 SHEET AH-032, DRAWING 308848
- . SENSING ELEBENL
- . CS/SC, CS/0, 428 RELAY, AH-10-DPS, AH-532-DPS -
O AR-401 Rev. 16 Page 131
! ENCLOSURE 1 !
n (Page 130 of 185) l l
PSA ANNUNCIATOR RESPONSE' PSA-X-04-04 F-04-04 I
REACTOR BLDG MISC AIR FLOW LOW EVENT POINT 0366 l
INDICATED CONDITION:
o AHF-3A CONTROL HANDLE IN NORMAL AFTER START AND A LOW DIFFERENTIAL PRESSURE <0.25" H,0 EXISTS AS SENSED BY AH-13-DPS REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
1 o INCREASING RB TEMPERATURES !
O kJ OPERATOR ACTIONS FOR A VALID ALARM:
o START AHF-38 o REFER TO OP-417 o MONITOR RB TEMPS I
DISCUSSION:
LOSS OF THIS AIR SUPPLY FAN WILL CAUSE RB TEMPERATURES TO INCREASE IN PLACES DUE TO A LACK 0F MIXING FLOW.
l l
REFERENCES:
DRAWINGS 208-005 SHEET AH-037, DRAWING 308848 SENSING ELEMENT: CS/SC, CS/0, 42B RELAY, AH-13-DPS O
AR-401 Rev. 16 Page 132
ENCLOSURE 1 (Page 131 of 185)
PSA ANNUNCIATOR RESPONSE PSA-X-04-04 F-04-04 ;
REACTOR BLDG MISC AIR FLOW LOW EVENT POINT 0369 INDICATED CONDITION:
o AHF-3B CONTROL HANDLE IN NORMAL AFTER START AND A LOW DIFFERENTIAL PRESSURE <0.25" H,02 EXISTS AS SENSED BY AH-15-DPS REDUNDANT INDICATION WHICH WILL VERIFY ntARM:
o INCREASING RB TEMPERATURES O
OPERATOR ACTIONS FOR A VALID ALARM:
o START AHF-3A o TRANSFER RMA-6 SUCTION TO RB ATMOSPHERE, REFER TO OP-417 DISCUSSION:
RM-A6 MONITORS THE REACTOR BUILDING ATMOSPHERE VIA EITHER THE DUCT OF AHF-3B DR THE RB ATMOSPHERE. THE TRANSFER OF THE SAMPLE POINT PER OP-417 IS A MANUAL OPERATION. REFER TO TS FOR ADMINISTRATIVE REQUIREMENTS.
REFERENCES:
DRAWINGS 208-005 SHEET AH-037, DRAWING 308848 SENSING ELEMENT: CS/SC, CS/0, 42B RELAY, AH-13-DPS AR-401 Rev. 16 Page 133
ENCLOSURE I (Page 132 of 185)
O .
PSA ANNUNCIATOR RESPONSE PSA-X-04-04 F-04-04 i
REACTOR BLDG '
MISC AIR FLOW LOW t EVENT POINT 0375 INDICATED CONDITION:
o AHF-4A OR AHF-4B CONTROL HANDLE IN NORMAL AFTER START AND A LOW DIFFERENTIAL PRESSURE EXISTS AS SENSED BY AH-7-DPS REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o INCREASING RB TEMPERATURES !
OPERATOR ACTIONS FOR A VALID ALARM:
o START AHF-4A OR 4B AS REQUIRED o REFER TO OP-417 o MONITOR RB TEMPS DISCUSSION:
LOSS OF THE SG COOLING FANS WILL CAUSE SOME AREAS OF THE R8 TO INCREASE DUE TO LACK OF MIXING FLOW.
REFERENCES:
DRAWINGS 208-005 SHEET AH-038, DRAWING 308848
. SENSING ELEE NT- CS/SC, CS/0, 42B RELAY, AH-7-DPS
- AR-401 Rev. 16 Page 134
4s m. - ia .- 5_-4,---m --4d+m--- s----i.* * - .4-4r -, -A 4 Aaa-.4-44=4+.4 --4--- J- -- 4- J ..w_._. _ - d4 -
ENCLOSURE 1 i
(Page 133 of 185)
PSA ANNUNCIATOR RESPONSE PSA-X-04-05 F-04-05 REACTOR BLDG FAN VfBRATION HH3H EVENT POINT 0361 INDICATED CONDITION:
o AH-ll-ME HAS ACTUATED DUE TO AHF-2A VIBRATION IN EXCESS OF SETPOINT AS l DETERMINED BY PM-294 J REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
l O
OPERATOR ACTIONS FOR A VALID ALARM: ;
o SECURE AHF-2A o SWAP REACTOR CAVITY COOLING T0 "B" SIDE PER OP-417 o MONITOR REACTOR CAVITY TEMPERATURES ON AH-1003-TIR PER OP-409 DISCUSSION:
THIS CONDITION INDICATES THAT A VIBRATION IN EXCESS OF 1.0 G HAS BEEN DETECTED. THERE IS NO WAY TO MONITOR THE VIBRATION FROM OUTSIDE THE REACTOR BUILDING, IHEREFORE IT WILL REQUIRE A REACTOR BUILDING ENTRY TO INVESTIGATE /REPA1R THE PROBLEM.
A SUSTAINED LOSS OF COOLING TO THE REACTOR CAVITY WILL HAVE ADVERSE EFFECTS ON THE RELIABILITY OF THE NUCLEAR INSTRUMENTATION.
j
REFERENCES:
DRAWING 208-005 SHEET AH-133 i SENSING ELEMENT: AH-ll-ME l
lO l
AR-401 Rev. 16 Page 135
._. . . = . . -
l l
ENCLOSURE 1 l c (Page 134 of 185) l l PSA ANNUNCIATOR RESPONSE PSA-X-04-05 F-04-05 REACTOR Bl.DG FAN VfBRATION HIGH l
L EVENT POINT 0363 INDICATED CONDITION:
o AH-12-ME HAS ACTUATED DUE TO AHF 28 VIBRATION IN EXCESS OF SETPOINT AS DETERMINED BY PM-294 REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
l o NONE l
OPERATOR ACTIONS FOR A VALID ALARM:
! O SECURE AHF-2B o SWAP REACTOR CAVITY COOLING T0 "A" SIDE PER OP-417 o MONITOR REACTOR CAVITY TEMPERATURES ON AH-1003-TIR PER OP-409 DISCUSSION:
l l
! THIS CONDITION INDICATES THAT A VIBRATION IN EXCESS OF I 0 G HAS BEEN DETECTED. THERE IS NO WAY TO MONITOR THE VIBRATION FROM OUTSIDE THE REACTOR BUILDING, THEREFORE IT WILL REQUIRE A REACTOR BUILDING ENTRY TO INVESTIGATE / REPAIR THE PROBLEM.
A SUSTAINED LOSS OF COOLING TO THE REACTOR CAVITY WILL HAVE ADVERSE EFFECTS ON THE RELIABILITY OF THE NUCLEAR INSTRUMENTATION.
REFERENCES:
DRAWING 208-005 SHEET AH-'133 SENSING ELEMENT: AH-12-ME
- O
'C l
l l
AR-401 Rev. 16 Page 136 l
l l
l ENCLOSURE 1 i (Page 135 of 185) l l
l PSA ANNUNCIATOR RESPONSE PSA-X-04-05 F-04-05 REACTOR BLDG
! FAN VIBRATION l HIGH i
EVENT POINT 0367 l
l INDICATED CONDITION:
o AH-14-ME HAS ACTUATED DUE TO AHF-3A VIBRATION IN EXCESS OF SETPOINT AS DETERMINED BY PM-294
, REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
l O
OPERATOR ACTIONS FOR A VALID ALARM: 1 o SECURE AHF-3A o ENSURE AHF-3B IS IN OPERATION l l
l DISCUSSION:
l l THIS CONDITION INDICATES THAT A VIBRATION IN EXCESS OF 1.0 G HAS BEEN i i DETECTED. THERE IS NO WAY TO MONITOR THE VIBRATION FROM OUTSIDE THE l l REACTOR BUILDING, THEREFORE IT WILL REQUIRE A REACTOR BUILDING ENTRY TO INVESTIGATE / REPAIR THE PROBLEM.
REFERENCES:
DRAWING 208-005 SHEET AH-133 SENSING ELEII NTT AH-14-ME
!O !
l '
l AR-401 Rev. 16 Page 137 1
l ,
ENCLOSURE 1 l
(Page 136 of 185)
\'
l PSA ANNUNCIATOR RESPONSE PSA-X-04-05 F-04-05 REACTOR BLDG FAN VfBRATION HIGH EVENT POINT 0370 I
INDICATED CONDITION:
o AH-16-ME HAS ACTUATED DUE TO AHF-3B VIBRATION IN EXCESS OF SETPOINT AS DETERMINED BY PM-294 REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
C\
U 1 1
OPERATOR ACTIONS FOR A VALID ALARM:
O SECURE AHF-38 o START AHF-3A o TRANSFER RMA-6 SUCTION TO RB ATMOSPHERE, REFER TO OP-417 DISCUSSION:
THIS CONDITION INDICATES THAT A VIBRATION IN EXCESS OF 1.0 G HAS BEEN DETECTED. THERE IS NO WAY TO MONITOR THE VIBRATION FROM OUTSIDE THE l REACTOR BUILDING, THEREFORE IT WILL REQUIRE A REACTOR BUILDING ENTRY TO INVESTIGATE / REPAIR THE PROBLEM.
l l
l l
REFERENCES:
DRAWING 208-005 SHEET AH-134 SENSING ELEMENT: AH-16-ME
- O l AR-401 Rev. 16 Page 138
ENCLOSURE 1 q (Page 137 of 185) 1 O
PSA ANNUNCIATOR RESPONSE PSA-X-04-05 F-04-05 REACTOR BLOG FAN VlBRATION HIGH EVENT POINT 0372 INDICATED CONDITION:
o AH-8-ME HAS ACTUATED DUE TO AHF-4A VIBRATION IN EXCESS 0F SETPOINT AS DETERMINED BY PM-294 REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
OPERATOR ACTIONS FOR A VALID ALARM:
o SECURE AHF-4A o START AHF-4B DISCUSSION:
THIS CONDITION INDICATES THAT A VIBRATION IN EXCESS OF 1.0 G HAS BEEN DETECTED. THERE IS NO WAY TO MONITOR THE VIBRATION FROM OUTSIDE THE REACTOR BUILDING, THEREFORE IT WILL REQUIRE A REACTOR BUILDING ENTRY TO l INVESTIGATE / REPAIR THE PROBLEM.
REFERENCES:
DRAWING 208-005 SHEET AH-134 l
SENSING ELEMENT: AH-8-ME
- O AR-401 Rev. 16 Page 139
ENCLOSURE 1 (Page 138 of 185)
. C PSA ANNUNCIATOR RESPONSE PSA-X-04-05 l F-04-05 REACTOR BLDG FAN VlBRATION HIGH EVENT POINT 0374 INDICATED CONDITION:
o AH-9-ME HAS ACTUATED DUE TO AHF-4B VIBRATION IN EXCESS OF SETPOINT AS DETERMINED BY PM-294 REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
A V
OPERATOR ACTIONS FOR A VALID ALARM:
o SECURE AHF-4B o START AHF-4A DISCUSSION:
THIS CONDITION INDICATES THAT A VIBRATION IN EXCESS OF I.0 G HAS BEEN DETECTED. THERE 15 NO WAY TO MONITOR THE VIBRATION FROM OUTSIDE THE REACTOR BUILDING, THEREFORE IT WILL REQUIRE A REACTOR BUILDING ENTRY TO INVESTIGATE / REPAIR THE PROBLEM.
I
REFERENCES:
DRAWING 208-005 SHEET AH-134 SENSING ELEMENT: AH-9-ME
- O i AR-401 Rev. 16 Page 140
I ENCLOSURE 1
[ (Page 139 of 185)
PSA ANNUNCIATOR RESPONSE PSA-X-04-07 F-04-07 REACTOR BLDG PURGE AIR FLOW LOVV EVENT POINT 0381 INDICATED CONDITION:
o DIFFERENTIAL PRESSURE ACROSS AH-1-DPS IS < 0.048" H 0 WITH AHF-6A AND/0R AHF-6BCONTROLHANDLEINNORMALAFTERSTARTPOSITI0f4 REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o AHV-10 CLOSES A
OPERATOR ACTIONS FOR A VALID ALARM:
o DETERMINE THE CAUSE FOR THE LOW PURGF SUPPLY FLOW, AND ADJUST THE RECIRC FLOW DAMPER CONTROL TO REESTABLISH FLOW THROUGH THE DUCT DISCUSSION: i l
l
REFERENCES:
DRAWING 208-005 SHEET 20, AND DRAWING 308848
. SENSING ELEMENI;. AHF-6A CS/SC, CS/0, AHF-6B CS/SC, CS/0, AH-1-DPS
- O l
AR-401 Rev. 16 Page 141
ENCLOSURE I p (Page 140 of 185)
\J '
PSA ANNUNCIATOR RESPONSE PSA-X-04-07 F-04-07 REACTOR BLDG PURGE AIR FLOW LOW EVENT POINT 0386 1
INDICATED CONDITION:
, o DIFFERENTIAL PRESSURE ACROSS AH-296-DPS IS < 0.29" H,0 WITH AHF-7A AND/0R AHF-78 CONTROL HANDLE IN NORMAL AFTER START POSITION 4
i REDUNDANT INDICATION WHICH WILL Vf'RIFY ALARM:
)
o LOW FLOW INDICATION ON AH-32-;:R POINT NUMBER 4
! r's, Ns' OPERATOR ACTIONS FOR A VALID ALARM:
i i
o DETERMINE THE CAUSE FOR THE LOW PURGE EXHAUST FLOW, AND CORRECT IF POSSIBLE DISCUSSION:
i THIS CONDIlION IS INDICATIVE OF A LOSS OF INTEGRITY IN THE DUCT WORK AND SHOULD BE INVESTIGATED AS S00N AS POSSIBLE.
THIS IS AN EXPECTED ALARM DURING RB MINI-PURGE.
REFERENCES:
DRAWING 208-005 SHEET 22, AND DRAWING 308848 SENSING ELEMENT: AHF-7A CS/SC, CS/0, AHF-78 CS/SC, CS/0, AH-296-DPS AR-401 Rev. 16 Page 142
l ENCLOSURE 1 !
(Page 141 of 185)
PSA ANNUNCIATOR RESPONSE PSA-X-04-08 F-04-08 CRDM SHROUD COOLING FANS j TRIP 1 EVENT POINT 1224 INDICATED CONDITION:
o BREAKER IN UNIT 3D OF VENT MCC 3B IS OPEN o 42/12CR RELAY FOR THIS CIRCUIT IS DEENERGIZED o AHF-518, AHF-51F, AND AHF-51J ARE NOT RUNNING REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
O o GREEN INDICATOR LIGHT ON VENT MCC 3B CUBICLE 3D o LOCAL BREAKER POSITION OPERATOR ACTIONS FOR A VALID ALARM:
o MONITOR CRDM STATOR TEMPS o NOTIFY ELECTRICAL MAINTENANCE i
DISCUSSION:
THIS ALARM IS INDICATIVE OF AN OVERLOAD CONDITION ON ONE OR MORE OF THE SHROUD FANS POWERED FROM THIS BREAKER. ELECTRICAL MAINTENANCE WILL DETERM THE FAN (S) THAT ARE SHORTED TO ENABLE THE REMAINING FANS TO BE RUN.
REFERENCES:
DRAWING 208-005 SHEET AH-159
, SENSING ELEMNT; 42/12CR RELAY -
AR-401 Rev. 16 Page 143
ENCLOSURE 1 (Page 142 of 185) 4 PSA ANNUNCIATOR RESPONSE PSA-X-04-08 F-04-08 i
- I CRDM SHROUD l COOLING FANS l TRIP I
I 1
EVENT POINT 1225 l INDICATED CONDITION:
l 0 BREAKER IN UNIT 8A 0F VENT MCC 3B IS OPEN
' o 42/34CR RELAY FOR THIS CIRCUIT IS DEENERGIZED o AHF-51C, AHF-51G, AND AHF-51K ARE NOT RUNNING REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o GREEN INDICATOR LIGHT ON VENT MCC 3B CUBICLE 8A o LOCAL BREAKER POSITION )-
l 0PERATOR ACTIONS FOR A VALID ALARM: '
- o NOTIFY ELECTRICAL MAINTENANCE 5
DISCUSSION:
THIS ALARM IS INDICATIVE OF AN OVERLOAD CONDITION ON ONE OR MORE OF THE
/
SHROUD FANS POWERED FROM THIS BREAKER. ELECTRICAL MAINTENANCE WILL DETERM THE FAN (S) THAT ARE SHORTED TO ENABLE THE REMAINING FANS TO BE RUN.
REFERENCES:
ORAWING 208-005 SHEET AH-160 ~
SENSING ELEMENT: 42/34CR RELAY O
AR-401 Rev. 16 Page 144
4 ENCLOSURE 1 (Page 143 of 185)
%J PSA ANNUNCIATOR RESPONSE PSA-X-04-08 F-04-08 >
l l I
CRDM SHROUD l COOLING FANS l TRIP
! l
- I
, EVENT POINT 1226 INDICATED CONDITION:
o BREAKER IN UNIT 10D OF VENT MCC 3B IS OPEN o 42/42CR RELAY FOR THIS CIRCUIT IS DEENERGIZED i o AHF-510, AHF-51H, AND AHF-51L ARE NOT RUNNING
{
l REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
O o GREEN INDICATOR LIGHT ON VENT MCC 3B CUBICLE 10D o LOCAL BREAKER POSITION OPERATOR ACTIONS FOR A VALID ALARM:
o MONITOR CRDM STATOR TEMPS o NOTIFY ELECTRICAL MAINTENANCE i
DISCUSSION:
THIS ALARM IS INDICATIVE OF AN OVERLOAD CONDITION ON ONE OR MORE OF THE SHROUD FANS POWERED FROM THIS BREAKER. ELECTRICAL MAINTENANCE WILL DETERM THE FAN (S) THAT ARE SHORTED TO ENABLE THE REMAINDER TO BE RUN.
l
REFERENCES:
DRAWING 208-005 SHEET AH-161 SENSING ELEMENT: 42/42CR RELAY O
AR-401 Rev. 16 Page 145
ENCLOSURE 1 <
(Page 144 of 185) v PSA ANNUNCIATOR RESPONSE PSA-X-04-08 F-04-08 CRDM SHROUD <
COOLING FANS TRIP '
4 EVENT POINT 1229 1
INDICATED CONDITION:
o BREAKER IN UNIT 8A 0F VENT MCC 3A IS OPEN I o 42/32CR RELAY FOR THIS CIRCVIT IS DEENERGIZED j o AHF-51A, AHF-51E, AND AHF-511 ARE NOT RUNNING 4
3.
REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o GREEN INDICATOR LIGHT ON VENT MCC 3A CUBICLE 8A l 0 LOCAL BREAKER POSITION OPERATOR ACTIONS FOR A VALID ALARM:
o MONITOR CRDM STATOR TEMPS o NOTIFY ELECTRICAL MAINTENANCE l
DISCUSSION: i
.THIS ALARM IS INDICATIVE OF AN OVERLOAD CONDITION ON ONE OR MORE OF THE SHROUD FANS POWERED FROM THIS BREAKER. ELECTRICAL MAINTENANCE WILL DETERM THE FAN (S) THAT ARE SHORTED T0 rtMBLE THE REMAINDER TO BE RUN.
REFERENCES:
DRAWING 208-005 SHEET AH-158 SENSING ELEMENT: 42/32 CR RELAY (Q/
AR-401 Rev. 16 Page 146
ENCLOSURE 1 (Page 145 of 185)
.v-PSA-F ANNUNCIATOR RESPONSE PSA-X-05-01 F-05-01 AUX BLDG l EXHAUST FAN I TRIP EVENT POINT 0417 INDICATED CONDITION:
o AHF-14A BREAKER OPEN WITH CONTROL HANDLE IN THE NORMAL AFTER START POSITION REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o GREEN LIGHT ON WITH A RED FLAG ON AHF-14A CONTROL STATION o AHF-10, AHF-llA, AHF-llB TRIP, IF RUNNING OPERATOR ACTIONS FOR A VALID ALARM:
o SECURE AHF-14C, START AHF-14B AND AHF-14D PER OP-409 o INVESTIGATE CAUSE OF FAN TRIP DISCUSSION:
AUX BLDG EXHAUST FILTER DELUGE VALVE ACTUATION, FSV-Il2 WILL TRIP THIS FAN. THE SUCTION AND DISCHARGE DAMPER POSITION CONTACTS THAT FEED THE FAN RUN INTERLOCK STRING ARE DIFFERENT FROM THE CONTACTS THAT SUPPLY INDICATION ON THE HVAC PANEL.
WASTE GAS DECAY TANK OUTLET VALVES, WDV-436, 437, 438 WILL CLOSE WHEN THIS FAN TRIPS.
REFERENCES:
DRAWING 208-005 SHEET AH-01 SENSING ELEMENT: CONTROL STATION AND BREAKER CONTACTS AR-401 Rev. 16 Page 147
ENCLOSURE i g (Page 146 of 185)
, U PSA-F ANNUNCIATOR RESPONSE PSA-X-05-01 F-05-01 AUX BLDG EXHAUST FAN TRIP EVENT POINT 0419 INDICATED CONDITION:
o AHF-14B BREAKER OPEN WITH CONTROL HANDLE IN THE NORMAL AFTER START POSITION REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o GREEN LIGHT ON WITH A RED FLAG ON AHF-148 CONTROL STATION p o AHF-10, AhF-llA, AHF-11B TRIP, IF RUNNING G 1 OPERATOR ACTIONS FOR A VALID ALARM:
o SECURE AHF-14D, START AHF-14A AND AHF-14C PER OP-409 o INVESTIGATE CAUSE OF FAN TRIP DISCUSSION:
AUX BLDG EXHAUST FILTER DELUGE VALVE ACTUATION, FSV-Il0 WILL TRIP T JS FAN. WASTE GAS DECAY TANK OUTLET VALVES, WDV-436, 437, 438 WILL ' m l WHEN THIS FAN TRIPS.
THE SUCTION AND DISCHARGE DAMPER POSITION CONTACTS THAT FEED THE FAN RUN INTERLOCK STRING ARE DIFFERENT FROM THE CONTACTS THAT SUPPLY INDICATION ON THE HVAC PANEL.
REFERENCES:
DPAWING 208-005 SHEET AH-02 SENSING ELEMENT: CONTROL STATION AND BREAKER CONTACTS AR-401 Rev. 16 Page 148
1 ENCLOSURE 1
,- s (Page 147 of 185)
(
PSA-F ANNUNCIATOR RESPONSE PSA-X-05-01 F-05-01 !
AUX BLDG EXHAUST FAN TRIP 1
EVENT POINT 0421 3
INDICATED CONDITION:
o AHF-14C BREAKER OPEN WITH CONTROL HANDLE IN THE NORMAL AFTER START POSITION REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o GREEN LIGHT WITH A RED FLAG ON AHF-14C CONTROL STATION f- s o AHF-11A, AHF-llB, AHF-10 TRIP, IF RUNNING U
OPERATOR ACTIONS FOR A VALID ALARM:
o SECURE AHF-14A, START AHF-14B AND AHF-14D o INVESTIGATE CAUSE OF FAN TRIP DISCUSSION:
AUX BLDG EXHAUST FILTER DELUGE VALVE ACTUATION, FSV-Il6 WILL TRIP THIS FAN l THE SUCTION AND DISCHARGE DAMPER POSITION CONTACTS THAT FEED THE FAN RUN INTERLOCK STRING ARE DIFFERENT FROM THE CONTACTS THAT SUPPLY INDICATION ON THE HVAC PANEL.
WASTE GAS DECAY TANK OUTLET VALVES, WDV-436, 437, 438 WILL CLOSE WHEN THIS FAN TRIPS.
REFERENCES:
DRAWING 208-005 SHEET AH-03 SENSING ELEMENT: CONTROL STATION AND BREAKER CONTACTS O
AR-401 Rev. 16 Page 149
ENCLOSURE 1 f- (Page 148 of 185)
PSA-F ANNUNCIATOR RESPONSE PSA-X-05-01 F-05-01 AUX BLDG EXHAUST FAN TRIP EVENT POINT 0423 INDICATED CONDITION:
o AHF-14D BREAKER OPEN WITH CONTROL HANDLE IN THE NORMAL AFTER START POSITION REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o GREEN LIGHT ON WITH A RED FLAG ON AHF-14D CONTROL STATION o AHF-10, AHF-11A, AHF-llB TRIP, IF RUNNING O
OPERATOR ACTIONS FOR A VALID ALARM:
o SECURE AHF-148, START AHF-14A AND AHF-14C o INVESTIGATE CAUSE OF FAN TRIP DISCUSSION:
AUX BLDG EXHAUST FILTER DELUGE VALVE ACTUATION, FSV-118 WILL TRIP THIS FAN THE SUCTION AND DISCHARGE DAMPER POSITION CONTACTS THAT FEED THE FAN RUN INTERLOCK STRING ARE DIFFERENT FROM THE CONTACTS THAT SUPPLY INDICATION ON THE HVAC PANEL.
WASTE GAS DECAY TANK OUTLET VALVES, WDV-436, 437, 438 WILL CLOSE WHEN THIS FAN TRIPS.
REFERENCES:
DRAWING 208-005 SHEET AH-04 SENSING ELEMENT: CONTROL STATION AND BREAKER CONTACTS O
AR-401 Rev. 16 Page 150
fNCLOSURE 1 (Page 149 of 185)
PSA-F ANNUNCIATOR RESPONSE PSA-X-05-02 F-05-02 l
AUX BLDG 1 i
EXHAUST FAN l OVERLOAD l 1
EVENT POINT 0418 INDICATED CONDITION:
i o AHF-14A MOTOR AMPS >115% RATED LOAD l
i I
~
REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o AHF-14A TRIPS
' o AHF-14A rilGH MOTOR AMPS INDICATED ON HVAC PANEL l OPERATOR ACTIONS FOR A VALID ALARM: ;
o SECURE AHF-14A AND AHF-14C, START AHF-14B AND AHF-140 AND RESTORE AUX i BUILDING VENTILATION AS REQUIRED PER OP-409 o INVESTIGATE CAUSE OF FAN TRIP DISCUSSION:
THIS ALARM INDICATES THAT EITHER THE TIMED OVERCURRENT OR INSTANTANEOUS OVERCURRENT PROTECTIVE DEVICES HAVE ACTUATED. INSTANTANE0US OVERCURRENT PROTECTIVE RELAY ACTUATION WILL TRIP THE BREAKER.
REFERENCES:
DRAWING 208-005 SHEET AH-01 !
, SENSING ELEMENT; 74-AHF-14A
- i O !
ll AR-401 Rev. 16 Page 151 1
l i
ENCLOSURE 1 p
(Page 150 of 185) i PSA-F ANNUNCIATOR RESPONSE PSA-X-05-02 F-05-02 !
l AUX BLDG !
EXHAUST FAN
, OVERLOAD L
i EVENT POINT 0420 INDICATED CONDITION:
! o AHF-14B MOTOR AMPS >115% RATED LOAD REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o AHF-14B TRIPS q o AHF-14B HIGH MOTOR AMPS INDICATED ON HVAC PANEL U
OPERATOR ACTIONS FOR A VALID ALARM:
o SECURE AHF-14B AND AHF-140, START AHF-14A AND AHF-14C AND RESTORE AUX BUILDING VENTILATION AS REQUIRED PER OP-409
, o INVESTIGATE CAUSE OF FAN TRIP DISCUSSION:
THIS ALARM INDICATES THAT EITHER THE TIMED OVERCURRENT OR INSTANTANE0US OVERCURRENT PROTECTIVE DEVICES HAVE ACTUATED. INSTANTANE0US OVERCURRENT PROTECTIVE RELAY ACTUATION WILL TRIP THE BREAKER.
REFERENCES:
DRAWING 208-005 SHEET AH-02 SENSING ELEMENT: 74-AHF-14B AR-401 Rev. 16 Page 152
ENCLOSURE 1
, 7-s (Page 151 of 185) a LJ PSA-F ANNUNCIATOR RESPONSE PSA-X-05-02 F-05-02 AujX BLDG EXHAUST FAN OVERLOAD EVENT POINT 0422 INDICATED CONDITION:
o AHF-14C MOTOR AMPS >115% RATED LOAD REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o AHF-14C TnIPS
'g o AHF-14C HiGH MOTOR AMPS INDICATED ON HVAC PANEL d
OPERATOR ACTIONS FOR A VALID ALARM:
o SECURE AHF-14A ml0 AHF-14C, START AHF-148 AND AHF-140 AND RESTORE AUX BUILDING VENTIL: 0N AS REQUIRED PER OP-409 o INVESTIGATE CAU- 0F FAN TRIP DISCUSSION:
THIS ALARM INDICATES THAT EITHER THE TIMED OVERCURRENT OR INSTANTANE0US OVERCURRENT PROTECTIVE DEVICES HAVE ACTUATED. INSTANTANE0US OVERCURRENT PROTECTIVE RELAY ACTUATION WILL TRIP THE BREAKER.
REFERENCES:
DRAWING 208-005 5HEET AH-03
. SENSING ELEMENI; 74-AHF-14C
- i AR-401 Rev. 16 Page 153
= . - -_. - _ - -._. -- - - _ ..
l 1
ENCLOSURE 1
- ,q (Page 152 of 185)
D PSA-F ANNUNCIATOR RESPONSE PSA-X-05-02 F-05-02 l
l AUX BLDG EXHAUST FAN OVERLOAD i EVENT POINT 0424 INDICATED CONDITION:
o AHF-14D MOTOR AMPS >l15% RATED LOAD REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
. o AHF-14D TRIPS O o AHF-14D HIGH MOTOR AMPS INDICATED ON HVAC PANEL
, OPERATOR ACTIONS FOR A VALID ALARM:
i o SECURE AHF-148 AND AHF-140, START AHF-14A AND AHF-14C AND RESTORE AUX BUILDING VENTILATION AS REQUIRED PER OP-409 o INVESTIGATE CAUSE OF FAN TRIP DISCUSSION:
i THIS ALARM INDICATES THAT EITHER THE TIMED OVERCURRENT OR INSTANTANE0US OVERCURRENT PROTECTIVE DEVICES HAVE ACTUATED. INSTANTANE0US OVERCURRENT PROTECTIVE RELAY ACTUATION WILL TRIP THE BREAKER, 1
a
REFERENCES:
DRAWING 208-005 SHEET AH-04
, SENSING ELEMENT; 74-AHF-140
- O 4
l AR-401 Rev. 16 Page 154
l l
ENCLOSURE I 7-~s (Page 153 of 185)
,d PSA-F ANNUNCIATOR RESPONSE PSA-X-05-03 F-05-03
! AB FLTR 2A/B/C/D
, AP HIGH EVENT POINT 1552 l
}
I L
INDICATED CONDITION:
l o AUX BUILDING EXHAUST FILTER, AHFL-2A, FLOW IS >5.2" H O AS SENSED BY 2
AH-601-DPS REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o AHFL-2A LOCAL DIFFERENTIAL PRESSURE INDICATOR :
O OPERATOR ACTIONS FOR A VALID ALARM:
o NOTIFY HVAC TO INSPECT FILTER DISCUSSION:
OPERATION OF AUXILIARY BUILDING EXHAUST FANS WITH ONLY THREE AUX BUILDING EXHAUST FILTERS IS PERMITTED.
REFERENCES:
DRAWING 208-005 SHEET AH-131
, SENSING ELEMENT.1 AH-601-DPS -
AR-401 Rev. 16 Page 155
l i
ENCLOSURE 1 (Page 154 of 185) 2 PSA-F ANNUNCIATOR RESPONSE PSA-X-05-03 F-05-03 AB FLTR 2A/B/C/D l AP blGH i
EVENT POINT 1553 i
INDICATED CONDITION:
l o AUX BUILDING EXHAUST FILTER, AHFL-2B, FLOW IS >5.2" H 0g AS SENSED BY AH-602-DPS 4
REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o AHFL-2B LOCAL DIFFERENTIAL PRESSURE INDICATOR OPERATOR ACTIONS FOR A VALID ALARM:
l o NOTIFY HVAC TO INSPECT FILTER DISCUSSION:
OPERATION OF AUXILIARY BUILDING EXHAUST FANS WITH ONLY THREE AUX BUILDING EXHAUST FILTERS IS PERMITTED.
REFERENCES:
DRAWING 208-005 SHEET AH-131
. SENSING ELEMENT; AH-602-DPS
- AR-401 Rev. 16 Page 156
1 1
ENCLOSURE 1 l (Page 155 of 185) )
)
, PSA-F ANNUNCIATOR' RESPONSE PSA-X-05-03 F-05-03 i
AB FLTR 2A/B/C/D {
AP HIGH EVENT POINT 1688 i
INDICATED CONDITION:
i
) o AUX BUILDING EXHAUST FILTER, AHFL-20, FLOW IS >5.2" H 0g AS SENSED BY j AH-603-DPS 1
j REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
1 o AHFL-2C LOCAL DIFFERENTIAL PRESSURE INDICATOR t
U l
OPERATOR ACTIONS FOR A VALID ALARM: i o NOTIFY HVAC TO INSPECT FILTER.
I DISCUSSION:
OPERATION OF AUXILIARY BUILDING EXHAUST FANS WITH ONLY THREE AUX BUILDING EXHAUST FILTERS IS PERMITTED.
REFERENCES:
DRAWING 208-005 SHEET AH-131
, SENSING ELEENT; AH-603-DPS
- o AR-401 Rev. 16 Page 157
1 ENCLOSURE I f3 (Page 156 of 185)
O PSA-F ANNUNCIATOR RESPONSE PSA-X-05-03 F-05-03 AB FLTR 2A/B/C/D AP HIGH EVENT POINT 1689 INDICATED CONDITION:
o AUX BUILDING EXHAUST FILTER, AHFL-2D, FLOW IS >5.2" H O AS SENSED BY 2
AH-604-DPS REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
l o AHFL-2D LOCAL DIFFERENTIAL PRESSURE INDICATOR i O l OPERATOR ACTIONS FOR A VALID ALARM:
o NOTIFY HVAC TO INSPECT FILTER DISCUSSION:
OPERATION OF AUXILIARY BUILDING EXHAUST FANS WITH ONLY THREE AUX BUILDING EXHAUST FILTERS IS PERMITTED.
REFERENCES:
DRAWING 208-005 SHEET AH-131
, SENSING ELEldENI . AH-604-DPS -
O AR-401 Rev. 16 Page 158
-- - ~ . . .
ENCLOSURE 1 frs (Page 157 of 185)
PSA-F ANNUNCIATOR RESPONSE PSA-X-05-04 F-05-04 PENETRATION AIR FLOW l TROUBLE i
l EVENT POINT 0438 INDICATED CONDITION:
o PENETRATION COOLING AIR FLOW IS <0.018" H O 2 AS SENSED BY AH-30-DPS WITH EITHER AHF-9A OR AHF-98 CONTROL STATION IN NORMAL AFTER START REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o LOCAL DIFFERENTIAL FLOW INDICATION O)
's-- ,
OPERATOR ACTIONS FOR A VALID ALARM:
o START BACKVP PENETRATION COOLING FAN O REFER TO OP-417 DISCUSSION:
REFERENCES:
DRAWING 208-005 SHEET AH-56 SENSING ELEMENT: AH-30-DPS O
AR-401 Rev. 16 Page 159
4 ENCLOSURE 1 s
(Page 158 of 185)
PSA-F ANNUNCIATOR RESPONSE PSA-X-05-05 F-05-05 FIRE PP HOUSE FAN TROUBLE EVENT POINT 0454
- INDICATED CONDITION
o FIRE PUMP HOUSE VENTILATION AIR FLOW IS <0.25" H 0 AS SENSED BY EITHER AH-168-DPSANDAHF-33AISRUNNINGORBYAH-173-Dh5ANDAHF-338 RUNNING REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o LOCAL DIFFERENTIAL FLOW INDICATION OPERATOR ACTIONS FOR A VALID ALARM:
o START BACKUP FIRE PUMP HOUSE FAN o CHECK FIRE PUMP HOUSE INLET FILTERS AND OUTLET REGISTERS FOR PROPER l OPERATION DISCUSSION:
FIRE PUMP HOUSE FANS ARE USED FOR FIRE PUMP COOLING AND COMBUSTION AIR FOR DIESEL FIRE PUMPS.
REFERENCES:
DRAWING 208-005 SHEET AH-71 SENSING ELEMENT: AH-173-DPS, AH-168-DPS AND CONTROL STATION CONTACTS O
AR-401 Rev. 16 Page 160
ENCLOSURE 1 (Page 159 of 185)
NJ 4
PSA-F ANNUNCIATOR RESPONSE PSA-X-05-05 F-05-05 FIRE PP HOUSE l
, FAN '
TROUBLE l EVENT POINT 1537 4
INDICATED CONDITION:
1 i o
' AHF-33A BREAKER CLOSED AND CONTROL HANDLE IN THE NORMAL AFTER STOP POSITION REDUNDANT INDICATION WHICH WILL VERIFY ALARM: !
j o RED LIGHT ON WITH A GREEN FLAG ON AHF-33A CONTROL STATION gw o TEMPERATURE IN FIRE PUMP HOUSE >85* F.
o ANY FIRE PUMP RUNNING OPERATOR ACTIONS FOR A VALID ALARM:
i o INVESTIGATE CAUSE OF AUTO START i
4 DISCUSSION:
FIRE PUMP HOUSE FANS ARE USED FOR FIRE PUMP COOLING AND COMBUSTION AIR FOR DIESEL FIRE PUMPS. AT LEAST ONE FAN MUST BE IN OPERATION ANY TIME
. A FIRE PUMP IS IN OPERATION.
4
REFERENCES:
DRAWING 208-005 SHEET AH-71
^
SENSING ELEMENT: CONTROL STATION AND BREAKER CONTACTS i
- o AR-401 Rev. 16 Page 161
i l
1 ENCLOSURE I i q (Page 160 of 185)
/
PSA-F ANNUNCIATOR RESPONSE PSA-X-05-05 F-05-05 FIRE PP HOUSE FAN TROUBLE 1
l EVENT POINT 1538 i l 1
INDICATED CONDITION:
o AHF-338 BREAKER CLOSED AND CONTROL HANDLE IN THE NORMAL AFTER STOP POSITION REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o RED LIGHT ON WITH A GREEN FLAG 04 AHF-338 CONTROL STATION l o TEMPERATURE IN FIRE PUMP HOUSE >85 .-
) o ANY FIRE PUMP RUNNING OPERATOR ACTIONS FOR A VALID ALARM:
o INVESTIGATE CAUSE OF AUTO START l
DISCUSSION:
i l !
FIRE PUMP HOUSE FANS ARE USED FCR FIRE PUMP COOLING AND COMBUSTION AIR FOR DIESEL FIRE PUMPS. AT LEAST ONE FAN MUST BE IN OPERATION ANY TIME A FIRE PUMP IS IN OPERATION.
REFERENCES:
DRAWING 208-005 SHEET AH-72 SENSING ELEMENT: CONTROL STATION AND BREAKER CONTACTS O
l I
AR-401 Rev. 16 Page I62
! l l
ENCLOSURE 1 m
(Page 161 of 185)
( i l PSA-F ANNUNCIATOR RESPONSE PSA-X-06-03 F-06-03 l
DIESEL GEN RM
! FAN TROUBLE i
EVENT POINT 0456 INDICATED CONDITION:
o AHF-22A BREAKER OPEN WITH THE CONTROL HANDLE IN NORMAL AFTER START j
REDUNDANT INDICATION WHICH WILL VERIFY ALARM: l 0 GREEN LIGHT ON WITH A RED FLAG ON AHF-22A CONTROL STATION 1 (f3 ) i OPERATOR ACTIONS FOR A VALID ALARM: '
o IF EGDG-1A IS RUNNING ENSURE AHF-22B IS RUNNING o INVESTIGATE CAUSE OF FAN TRIP DISCUSSION:
DIESEL GENERATOR FANS WILL TRIP IF DIESEL SPEED IS <600 RPM AS SENSED BY EG-19-SS.
SECURING THE FAN LOCALLY WILL ACTUATE THIS ALARM.
l
REFERENCES:
DRAWING 208-005 SHEET AH-75 l . SENSING ELEMENT.: . CONTROL SWITCH CONTACTS -
lO AR-401 Rev. 16 Page 163
.= . . -. - .
- . . _ . . . - = - .
1 ENCLOSURE I t g (Page 162 of 185)
PSA-F ANNUNCIATOR RESPONSE PSA-X-06-03 F-06-03 DIESEL GEN RM FAN l TROUBLE l
EVENT POINT 0457 l
INDICATED CONDITION:
o AHF-228 BREAKER OPEN WITH THE CONTROL HANDLE IN NORMAL AFTER START l
REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o GREEN LIGHT ON WITH A RED FLAG ON AHF-22B CONTROL STATION lO OPERATOR ACTIONS FOR A VALID ALARM:
l o IF EGDG-IA IS RUNNING ENSURE AHF-22A IS RUNNING o INVESTIGATE CAUSE OF FAN TRIP i DISCUSSION:
l DIESEL GENERATOR FANS WILL TRIP IF DIESEL SPEED IS <600 RPM AS SENSED
! BY EG-19-SS.
SECURING THE FAN LOCALLY WILL ACTUATE THIS ALARM.
t i
REFERENCES:
DRAWING 208-005 SHEET AH-74
- , SENSING ELEtjENT; CONTROL SWITCH CONTACTS
- c U
l AR-401 Rev. 16 Page 164 l
. - .- . . - . . _ . _ - _ - - . -. _ . _ - - . . . _ _. . . . - _ - - ~ _ . - . _ _
ENCLOSURE I
'(
(Page 163 of 185)
PSA-F ANNUNCIATOR RESPONSE PSA-X-06-03 F-06-03 DIESEL GEN RM !
FAN TROUBLE EVENT POINT 0458 INDICATED CONDITION:
o DIESEL GENERATOR "A" ROOM DUCT AIR FLOW <0.25" H O AS SENSED BY 2
AH-359B-DPS WITH AHF-228 OR AH-359A-DPS WITH AHF-22A ON REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o LOCAL FLOW INDICATION ON JOHNSON CONTROL PANEL OPERATOR ACTIONS FOR A VALID ALARM:
o IF EGDG-IA IS RUNNING SWAP OPERATING AHF-22 FANS o
NOTIFY AUX BLDG OPERATOR TO ENSURE INLET FILTERS ARE CLEAR OF DEBRIS l AND OBSTRUCTIONS TO AIR FLOW DISCUSSION:
REFERENCES:
DRAWING 208-005 SHEET AH-74
, SENSING ELEMENT; . AH-3598-DPS, AH-359A-DPS
- O AR-401 Rev. 16 Page 165
i i ENCLOSURE 1 g--)g. (Page 164 of 185) l
\, !
} PSA-F ANNUNCIATOR RESPONSE PSA-X-06-03 F-06-03 l 1
- d i l
DIESEL GEN RM FAN TROUBLE l
EVENT POINT 0459 l INDICATED CONDITION: )
o DIESEL GENERATOR "A" CONTROL ROOM TEMPERATURE IS >118' F AS SENSED BY AH-540-TS i
REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
1 o HIGH AMBIENT TEMPERATURE CONDITIONS IN THE "A" DIESEL GENERATOR CONTROL l O
ROOM OPERATOR ACTIONS FOR A VALID ALARM:
o INSPECT "A" DIESEL GENERATOR CONTROL ROOM FOR ANY SIGNS OF A FIRE o LOWER TEMPERATURE BY STARTING AHF-22A OR 22B !
o ENSURE AHF-28A IS RUNNING DISCUSSION:
o 'HIGH AMBIENT TEMPERATURES IN THE CONTROL ROOM CAN ADVERSELY IMPACT THE OPERABILITY OF THE EMERGENCY DIESEL GENERATORS
REFERENCES:
DRAWING 208-005 SHEET AH-76
. SENSING ELEMENI;. AH-540-TS
- O AR-401 Rev. 16 Page 166
l l
l ENCLOSURE I p (Page 165 of 185)
! V i PSA-F ANNUNCIATOR RESPONSE PSA-X-06-03 F-06-03 DIESEL GEN RM FAN TROUBLE EVENT POINT 0461 INDICATED CONDITION:
o AHF-22C BREAKER OPEN WITH THE CONTROL HANDLE IN NORMAL AFTER START REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o GREEN LIGHT ON WITH A RED FLAG ON AHF-22C CONTROL STATION O
OPERATOR ACTIONS FOR A VALID ALARM:
o IF EGDG-IB IS RUNNING ENSURE AHF-22D IS RUNNING o INVESTIGATE CAUSE OF FAN TRIP DISCUSSION:
DIESEL GENERATOR FANS WILL TRIP IF DIESEL SPEED IS <600 RPM AS SENSED BY EG-20-SS.
SECURING THE FAN LOCALLY WILL ACTUATE THIS ALARM.
REFERENCES:
DRAWING 208-005 SHEET AH-77 I. SENSING ELEMENI.: CONTROL SWITCH CONTACTS -
,V n
i l
AR-401 Rev. 16 Page 167
! l l-ENCLOSURE 1
,f-~g (Page 166 of 185)
U PSA-F ANNUNCIATOR RESPONSE PSA-X-06-03 F-06-03 l
DIESEL GEN RM l FAN l
TROUBLE l
l EVENT POINT 0462 INDICATED CONDITION:
o AHF-22D BREAKER OPEN WITH THE CONTROL HANDLE IN NORMAL AFTER START REDUNDANT. INDICATION WHICH WILL VERIFY ALARM:
o GREEN LIGHT ON WITH A RED FLAG ON AHF-22D CONTROL STATION n
v i 4
OPERATOR ACTIONS FOR A VALID ALARM:
o IF EGDG-IB IS RUNNING ENSURE AHF-2?C IS RUNNING o INVESTIGATE CAUSE OF FAN TRIP DISCUSSION:
DIESEL GENERATOR FANS WILL TRIP IF DIESEL SPEED IS <600 RPM AS SENSED BY EG-20-SS.
SECURING THE FAN LOCALLY WILL ACTUATE THIS ALARM.
REFERENCES:
DRAWING 208-005 SHEET AH-78
, SENSING ELEMENT:, CONTROL SWITCH CONTACTS -
lO V ,
AR-401 Rev. 16 Page 168
t ENCLOSURE 1 (Page 167 of 185)
O PSA-F ANNUNCIATOR RFSPONSE PSA-X-06-03 F-06-03 I
i DIESEL GEN RM i i FAN TROUBLE i
EVENT POINT 0463 INDICATED CONDITION:
o DIESEL GENERATOR "B" ROOM DUCT AIR FLOW <0.25" H2 O AS SENSED BY AH-369B-DPS WITH AHF-22D OR AH-369A-DPS WITH AHF-22C ON l
REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o LOCAL FLOW INDICATION ON JOHNSON CONTROL PANEL O
V OPERATOR ACTIONS FOR A VALID ALARM:
o IF EGDG-IB IS RUNNING SWAP OPERATING AHF-22 FANS o
NOTIFY AUX BLDG OPERATOR TO ENSURE INLET FILTERS ARE CLEAR OF DEBRIS AND GBSTRUCTIONS TO AIR FLOW DISCUSSION:
REFERENCES:
DRAWING 208-005 SHEET AH-77
. SENSING ELEMENT; . AH-3698-DPS, AH-369A-DPS
- AR-401 Rev. 16 Page 169
ENCLOSURE I (Page I68 of 185)
PSA-F ANNUNCIATOR RESPONSE PSA-X-06-03 F-06-03 ;
DIESEL GEN RM FAN TROUBLE EVENT POINT 0464 l
INDICATED CONDITION:
o DIESEL GENERATOR "B" CONTROL ROOM TEMPERATURE IS >II8* F AS SENSED BY AH-54I-TS REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o HIGH AMBIENT TEMPERATURE CONDITIONS IN THE DIESEL GENERATOR CONTROL ROOM OPERATOR ACTIONS FOR A VALID ALARM:
o INSPECT "B" DIESEL GENERATOR CONTROL ROOM FOR ANY SIGNS OF A FIRE o LOWER TEMPERATURE BY STARTING AHF-22C OR 22D !
o ENSURE AHF-28B IS RUNNING DISCUSSION:
o HIGH AMBIENT TEMPERATURES IN THE CONTROL ROOM CAN ADVERSELY IMPACT THE OPERASILITY OF THE EMERGENCY DIESEL GENERATORS i
REFERENCES:
DRAWING 208-005 SHEET AH-79
, SENSING ELEMENT: AH-54I-TS -
O AR-401 Rev. 16 Page 170
- . -- - . ~ . . - - .. -- ..
^
ENCLOSURE 1 (Page 169 of 185) 4 !
d 1 PSA-F ANNUNCIATOR RESPONSE PSA-X-06-03 F-06-03 DIESEL GEN RM
, FAN l 4
TROUBLE !
J l 4
EVENT POINT 1539 l
- 1 INDICATED CONDITION:
o AHF-22A BREAKER CLOSED WITH THE CONTROL HANDLE IN NORMAL AFTER STOP
! REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
! o RED LIGHT ON WITH A GREEN FLAG ON AHF-22A CONTROL STATION OPERATOR ACTIONS FOR A VALID ALARM:
o INVESTIGATE CAUSE OF FAN AUTO START 4
j I
DISCUSSION:
i j
DIESEL GENERATOR FANS WILL AUTO START IF DIESEL SPEED IS >600 RPM AS )
- SENSED BY EG-19-SS. '
STARTING THE FAN LOCALLY WILL ACTUATE THIS ALARM.
REFERENCES:
DRAWING 208-005 SHEET AH-74
. SENSING ELEMENT; CONTROL SWITCH CONTACTS -
O AR-401 Rev. 16 Page 171
ENCLOSURE 1 (Page 170 of 185)
PSA-F ANNUNCIATOR RESPONSE PSA-X-06-03 F-06-03 t
t DIESEL GEN RM FAN TROUBLE i
a EVENT POINT 1540 INDICATED CONDITION:
1 o
EGDG-1A SPEED IS >600 RPM AS SENSED BY EG-19-SS AND AHF-22A AND AHF-228 ARE NOT RUNNING j REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o EGDG-IA READY OR RUN LIGHT ON AND AHF-22A AND AHF-228 GREEN INDICATORS
'; ON i
j OPERATOR ACTIONS FOR A VALID ALARM:
l o START AHF-22A AND/0R AHF-228 I l 1
! DISCUSSION:
)
i 4
DIESEL GENERATOR FANS PROVIDE COOLING FOR THE DIESEL GENERATOR ROOM.
OPERATION OF THE EMERGENCY DIESEL GENERATOR WITH NO COOLING FANS RUNNING MUST BE CLOSELY MONITORED S0 AS TO NOT EXCEED 105* ROOM TEMPERATURE.
j REFER TO TS FOR ADMINISTRATIVE REQUIREMENTS
REFERENCES:
DRAWING 208-005 SHEET AH-74 2
~
. SENSING ELEMENT- 3 ERA AND BREAKER CONTACTS
- AR-401 Rev. 16 Page 172
l ENCLOSURE 1
,,.s, (Page 171 of 185)
PSA-F ANNUNCIATOR RESPONSE PSA-X-06-03 F-06-03 DIESEL GEN RM FAN
- TROUBLE h
EVENT POINT 1541 1
INDICATED CONDITION:
o AHF-22B BREAKER CLOSED WITH THE CONTROL HANDLE IN NORMAL AFTER STOP REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o RED LIGHT ON WITH A GREEN FLAG ON AHF-22B CONTROL STATION l O '
OPERATOR ACTIONS FOR A VALID ALARM:
o INVESTIGATE CAUSE OF FAN AU'O START l
DISCUSSION: '
DIESEL GENERATOR FANS WILL AUTO START IF DIESEL SPEED IS >600 RPM AS SENSED BY EG-19-SS.
1 STARTING THE FAN LOCALLY WILL ACTUATE THIS ALARM. I i
I
REFERENCES:
L DRAWING 208-005 SHEET AH-75 I
. SENSING ELEMENT.: CONTROL SWITCH CONTACTS .
l 1
O I
AR-401 Rev. 16 Page 173 4
ENCLOSURE I (Page 172 of 185)
PSA-F ANNUNCIATOR RESPONSE PSA-X-06-03 F-06-03 DIESEL GEN RM FAN TROUBLE EVENT POINT 1542 INDICATED CONDITION:
o AHF-22C BREAKER CLOSED WITH THE CONTROL HANDLE IN NORMAL AFTER STOP REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o RED LIGHT ON WITH A GREEN FLAG ON AHF-220 CONTROL STATION O
OPERATOR ACTIONS FOR A VALID ALARM:
o INVESTIGATE CAUSE OF FAN AUTO START DISCUSSION:
DIESEL GENERATOR FANS WILL AUTO START IF DIESEL SPEED IS >600 RPM AS SENSED BY EG-20-SS.
STARTING THE FAN LOCALLY WILL ACTUATE THIS ALARM.
REFERENCES:
DRAWING 208-005 SHEET AH-77 SENSING ELEltENTt CONTROL SWITCH CONTACTS -
n U
AR-401 Rev. 16 1
Page 174
- - - - - . . . . -- ~ . , . . - - - . - - - - . - .- . _ - ..-. -
1 l
4 ENCLOSURE I (Page 173 of 185)
PSA-F ANNUNCIATOR RESPONSE PSA-X-06-03 F-06-03 DIESEL GEN RM
] FAN j
TROUBLE i
1 EVENT POINT 1543 1
INDICATED CONDITION:
! o EGDG-IB SPEED IS >600 RPM AS SENSED BY EG-20-SS AND AHF-22C AND AHF-22D ARE NOT RUNNING i !
REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o
-(O EGDG-IB READY OR RUN LIGHT ON AND AHF-22C AND AHF-220 GREEN INDICATORS ON-j OPERATOR ACTIONS FOR A VALID ALARM: '
a l 0 START AHF-22C AND/0R AHF-22D DISCUSSION:
DIESEL GENERATOR FANS PROVIDE COOLING FOR THE DIESEL GENERATOR ROOM.
OPERATION OF THE EMERGENCY DIESEL GENERATOR WITH NO COOLING FANS RUNNING '
MUST BE CLOSELY P.ONITORED SO AS NOT TO EXCEED 105' ROOM TEMPERATURE.
REFER TO TS FOR ADMINISTRATIVE REQUIREMENTS.
1
REFERENCES:
DRAWING 208-005 SHEET AH-77 SENSING ELEMENT: 3 ERB AND BREAKER CONTACTS AR-401 Rev. 16 Page 175 i
1 ENCLOSURE I
- (Page 174 of 185)
- (/
l PSA-F ANNUNCIATOR RESPONSE PSA-X;v6-03 F-06-03 DIESEL GEN RM FAN TROUBLE i
i EVENT POINT 1544 i
INDICATED CONDITION:
0 l AHF-22D BREAKER CLOSED WITH THE CONTROL HANDLE IN NORMAL AFTER STOP REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o RED LIGHT ON WITH A GREEN FLAG ON AHF-220 CONTROL STATION
- ! O
] OPERATOR ACTIONS FOR A VALID ALARM:
o INVESTIGATE CAUSE OF FAN AUTO START
- DISCUSSION
2
! DIESEL GENERATOR FANS WILL AUT0 START IF DIESEL SPEED 15 >600 RPM AS SENSED BY EG-20-SS.
, STARTING THE FAN LOCALLY WILL ACTUATE THIS ALARM.
REFERENCES:
DRAWING 208-005 SHEET AH-78
, SENSING ELEMENI; CONTROL SWITCH CONTACTS
- O AR-401 Rev. 16 Page 176
i ENCLOSURE 1 (Page 175 of 185)
O PSA-F ANNUNCIATOR RESPONSE PSA-X-06-04 F-06-04 SAMPLING ROOM FAN TROUBLE EVENT POINT 0508 INDICATED CONDITION:
o AHF-44A BREAKER OPEN WITH CONTROL HANDLE IN THE NORMAL AFTER START POSITION REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o GREEN LIGHT ON WITH A RED FLAG ON AHF-44A CONTROL STATION q o T0XIC GAS ACTUATION g o RADIATION HIGH RAD ALARM RM-A5 OPERATOR ACTIONS FOR A VALID ALARM:
o INVESTIGATE CAUSE OF FAN TRIP o
NOTIFY CHEMISTRY OF LOSS OF SAMPLE HOOD VENTILATION o REFER TO AP-250 OR AP-513 DISCUSSION:
DUCTWORK TEMPERATURE >135* AS SENSED BY AH-402-TS WILL TRIP THIS FAN.
AHF-20A MUST BE RUNNING IN EITHER FAST OR SLOW FOR THIS FAN TO RUN.
REFERENCES:
DRAWING 208-005 SHEET AH-98
, SENSING ELEMENT; CONTROL STATION CONTACTS -
O AR-401 Rev. 16 Page 177
l :
i i
l ENCLOSURE 1 (Page 176 of 185) i PSA-F ANNUNCIATOR RESPONSE PSA-X-06-04 F-06-04 l
SAMPUNG ROOM FAN i
TROUBLE i
EVENT POINT 0509 INDICATED CONDITION:
o AHF-44B BREAKER OPEN WITH CONTROL HANDLE IN THE NORMAL AFTER START POSITION 1
REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
l o GREEN LIGHT ON WITH A RED FLAG ON AHF-44B CONTROL STATION o T0XIC GAS ACTUATION o RADIATION HIGH RAD ALARM RM-A5 OPERATOR ACTIONS FOR A VALID ALARM:
o INVESTIGATE CAUSE OF FAN TRIP o NOTIFY CHEMISTRY OF LOSS OF SAMPLE HOOD VENTILATION o REFER TO AP-250 OR AP-513 DISCUSSION:
DUCTWORK TEMPERATURE >135' AS SENSED BY AH-545-TS WILL TRIP THIS FAN.
AHF-20B MUST BE RUNNING IN EITHER FAST OR SLOW FOR THIS FAN TO RUN.
REFERENCES:
DRAWING 208-005 SHEET AH-99 l , SENSING ELEtgNT;._ CONTROL STATION CONTACTS -
l l
i w
\
i AR-401 Rev. 16 Page 178
ENCLOSURE I (Page 177 of 185)
PSA-F ANNUNCIATOR RESPONSE PSA-X-06-04 F-06-04 l
I SAMPUNG ROOM FAN TROUBLE EVENT POINT 0510 INDICATED CONDITION:
o AHF-44A DUCTWORK TEMPERATURE >I35'F AS SENSED BY AH-402-TS l
i REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o AHF-44A TRIPS !
p o WHITE " TEMP NORM" LIGHT IS OUT FOR AHF-44A CONTROL STATION I C
OPERATOR ACTIONS FOR A VALID ALARM:
o INVESTIGATE CAUSE OF HIGH TEMP I o IF FIRE CONDITIONS EXIST REFER TO AP-880 l 0
NOTIFY CHEMISTRY OF LOSS OF SAMPLE HOOD VENTILATION DISCUSSION:
REFERENCES:
DRAWING 208-005 SHEET AH-98
, SENSING ELEM.ENTt AH-402-TS -
l lO l
AR-401 Rev. 16 Page 179
. - .. _ . _ _ - - . _ ____ ____ . =_. _ - . . _. _
' ENCLOSURE 1 (Page 178 of 185)
PSA-F ANNUNCIATOR RESPONSE PSA-X-06-04 F-06-04 SAMPLING ROOM 4
FAN TROUBLE i
1 EVENT POINT 0511 INDICATED CONDITION:
i o AHF-44A EXHAUST FLOW <0.10" H O 2 AS SENSED BY AH-403-DPS
.1 REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
l 0 LOW FLOW ON LOCAL INDICATION FOR AHF-44A
( l OPERATOR ACTIONS FOR A VALID ALARM:
o INVESTIGATE CAUSE OF LOW FLOW o CONSIDERATION SHOULD BE GIVEN TO SWAPPING TO "B" SIDE CONTROL COMPLEX VENTILATION o NOTIFY CHEMISTRY OF LOSS OF SAMPLE HOOD VENTILATION DISCUSSION:
AHF-20A MUST BE RUNNING PRIOR TO STARTING AHF-44A
REFERENCES:
DRAWING 208-005 SHEET AH-98
, SENSING ELEM.ENT; AH-403-DPS -
AR-401 Rev. 16 Page 180
ENCLOSURE 1 (Page 179 of 185)
_ PSA-F ANNUNCIATOR RESPONSE PSA-X-06-04 F-06-04 SAMPLING HOOM '
j FAN TROUBLE EVENT POINT 1530 1
i INDICATED CONDITION:
o AHF-44B EXHAUST FLOW <0.10" H 2O AS SENSED BY AH-544-DPS 4
a j REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
4 o LOW FLOW ON LOCAL INDICATION FOR AHF-448 lQ j
\
OPERATOR ACTIONS FOR A VALID ALARM:
o INVESTIGATE CAUSE OF LOW FLOW l 0 CONSIDERATION SHOULD BE GIVEN TO SWAPPING T0 "A" SIDE CONTROL COMPLEX VENTILATION o NOTIFY CHEMISTRY OF LOSS OF SAMPLE HOOD VENTILATION
! l DISCUSSION: '
AHF-208 MUST BE RUNNING FRIOR TO STARTING AHF-44B l
l
REFERENCES:
DRAWING 208-005 SHEET AH-99
, SENSING ELEMENT; AH-544-DPS -
AR-401 Rev. 16 Page 181
< l i i
! ENCLOSURE I (Page 180 of 185)
\
PSA-F ANNUNCIATOR RESPONSE PSA-X-06-04 F-06-04 SAMPLING ROOM FAN TROUBLE i
EVENT POINT 1531 INDICATED CONDITION:
o AHF-448 DUCTWORK TEMPERATURE >I35'F AS SENSED BY AH-545-TS REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o AHF-44B TRIPS o
WHITE " TEMP NORM" LIGHT IS OUT FOR AHF-44B CONTROL STATION OPERATOR ACTIONS FOR A VALID ALARM:
o INVESTIGATE CAUSE OF HIGH TEMP o IF FIRE CONDITIONS EXIST REFER TO AP-880 o
NOTIFY CHEMISTRY OF LOSS OF SAMPLE HOOD VENTILATION DISCUSSION:
REFERENCES:
DRAWING 208-005 SHEET AH-99
, SENSING ELEMENT; AH-545-TS
- I G'i AR-401 Rev. 16 Page 182
ENCLOSURE 1
,- (Page 181 of 185)
(j PSA-F ANNUNCIATOR RESPONSE PSA-X-06-0; F-06-05 INTERMEDIATE BLDG FAN TROUBLE EVENT POINT 0376 INDICATED CONDITION:
o AHF-24A BREAKER CLOSED AND DISCHARGE DAMPER AHD-67, CLOSED REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o LOCAL DAMPER INDICATION l 1 w/
OPERATOR ACTIONS FOR A VALID ALARM:
o SHUTDOWN AHF-24A o SWAP T0 "B" SIDE INTERMEDIATE BUILDING FANS PER OP-409 DISCUSSION:
OPERATION OF AHF-24A WITH THE DISCHARGE DAMPER CLOSED MAY CAUSE FAN DAMAGE.
REFERENCES:
DRAWING 208-005 SHEET AH-51
, SENSING ELEMENT _: 2-AHF-24A, AHF-24A-KS -
(~)
I AR-401 Rev. 16 Page 183
[NCLOSURE 1 (Page 182 of 185)
- O PSA-F ANNUNCIATOR RESPONSE PSA-X-06-05 F-06-05 t
INTERMEDIATE BLDG FAN TROUBLE EVENT POINT 0377 l INDICATED CONDITION:
i o AHF-24B BREAKER CLOSED AND ITS DISCHARGE DAMPER AHD-68, CLOSED i
REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
, o LOCAL DAMPER INDICATION
- O I
OPERATOR ACTIONS FOR A VALID ALARM:
i )
o SHUTDOWN AHF-24B j o SWAP T0 "A" SIDE INTERMEDIATE BUILDING FANS PER OP-409 i
DISCUSSION:
OPERATION OF AHF-24B WITH THE DISCHARGE DAMPER CLOSED MAY CAUSE FAN DAMAGE.
4
REFERENCES:
DRAWING 208-005 SHEET AH-52
, SENSING ELEMENT.; 2-AHF-248, AHF-24B-KS -
O AR-401 Rev. 16 Page 184
I l
l ENCLOSURE I (Page 183 of 185)
'O PSA-F ANNUNCIATOR RESPONSE PSA-X-06-05 F-06-05 INTERMEDIATE BLDG FAN TROUBLE EVENT POINT 1548 INDICATED CONDITION:
o AHF-29A BREAKER OPEN WITH CONTROL HANDLE IN THE NORMAL AFTER START POSITION REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o GREEN LIGHT ON WITH A RED FLAG ON AHF-29A CONTROL STATION OPERATOR ACTIONS FOR A VALID ALARM:
o SWAP T0 "B" SIDE INTERMEDIATE BUILDING FANS PER OP-409 o INVESTIGATE CAUSE OF FAN TRIP DISCUSSION:
REFERENCES:
DRAWING 208-005 SHEET AH-53
, SENSING ELEM.ENT; CONTROL STATION CONTACTS
- O
! v I
AR-401 Rev. 16 Page 185
I
(
l ENCLOSURE 1 (Page 184 of 185)
PSA-F ANNUNCIATOR RESPONSE PSA-X-06-05 F-06-05 INTERMEDIATE BLDG FAN TROUBLE EVENT POINT 1549 INDICATED CONDITION:
o AHF-298 BREAKER OPEN WITH CONTROL HANDLE IN THE NORMAL AFTER START POSITION REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o GREEN LIGHT ON WITH A RED FLAG ON AHF-29B CONTROL STATION O
OPERATOR ACTIONS FOR A VALID ALARM:
o SWAP T0 "A" SIDE INTERMEDIATE BUILDING FANS PER OP-409 o INVESTIGATE CAUSE OF FAN TRIP DISCUSSION:
REFERENCES:
DRAWING 208-005 SHEET AH-54
, SENSING ELEMENT.:. CONTROL STATION CONTACTS -
lO AR-401 Rev. 16 Page 186
ENCLOSURE I (Page 185 of 185)
PSA-F ANNUNCIATOR RESPONSE PSA-X-06-08 F-06-08 I
I I
REACTOR BLDG PERSONNEL DOOR l OPEN l
I I
j EVENT POINT 1212 INDICATED CONDITION:
l o
REACTOR BUILDING PERSONNEL OR EQUIPMENT HATCH INNER OR OUTER DOOR NOT CLOSED i
REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o RB D00R INDICATION PANEL MCB PSA SECTION O
OPERATOR ACTIONS FOR A VALID ALARM:
o INVESTIGATE OPEN HATCH o REFER TO OP-417 DISCUSSION:
-REFER TO TS FOR ADMINISTRATIVE REQUIREMENTS.
REFERENCES:
ORAWING 208-064 SHEET ME-04
, SENSING ELEMENT:_ ME-1,3,5&7-KS -
O 4 j
AR-401 Rev. 16 Page 187 (LAST PAGE) l