ST-HL-AE-1511, Forwards Responses to NRC 851025 Questions & Comments on Fire Hazards Analysis Rept.Encl Includes marked-up Pages Which Will Be Incorporated in Future Fire Hazards Analysis Rept Amend
ML20138N327 | |
Person / Time | |
---|---|
Site: | South Texas ![]() |
Issue date: | 10/31/1985 |
From: | Wisenburg M HOUSTON LIGHTING & POWER CO. |
To: | Knighton G Office of Nuclear Reactor Regulation |
References | |
CON-#485-076, CON-#485-76 OL, ST-HL-AE-1511, NUDOCS 8511050150 | |
Download: ML20138N327 (125) | |
Text
{{#Wiki_filter:The Light c o mp any , , . .. . ., . .. , i , m , . . . . . .o . ... . . , i . . , n. . , :. .. . i , . .. . .. . .. . . . .. . =. . , . : , . . ,, . . . . . . os t ot..: r s i . I 'I.s 's 51-HL AE-1511 F lle to. C9.I7 Mr. George W. Knighton, Chief Licensinc Branch No. 3 Division of Li.'ensing U. S. Nuclear Regulatory Comnission n shington. DC 20555 so;th Texas Projer* Units 1 and ? Docket Nos. STN 50-498, STN 50-499 Resnonses to Varcal PC Ouestions on the FHAH i
Dear Mr. <nig9 ton:
1 Tne attachments enclosed Dravida SIP's response to Fire Hatards Analysis
! Report 'FHAR) questions and co vvats that were v frbally given to *fdP in n ) Meting on 3ctober 25,199').
I"** attachvnts include narW-ups of FHAR pages (where accropriate) which aUl De incorocrated 19 a future FHAR amendment.
; If you ;90uld hase any questions on tnts M tter, please contact Mr. M. E. Powell at (713) 993-1328.
Very truly curs, 0 l P. R. wisenb rq Manager, Nucl'ar Licen tig AQ - j MED/yd Attachmots 05110b0150 051031 pDR ADOCK050%){0 Ll/NRC/H
,,-,-g- . - - , , - - - - - - , - ,---,m-- , , _ , , _ . ,-e y, -n y.. , _,.,_.,,-,,,,,y-,,,,,,,,-_,,_.,g- -
ST-HL AE- 1511 rile No.: G9.17 Ilouston 1.:ghung & Power Comp.iny Page 2 cc: Hugh L. Thompson, Jr., Director Brian E. Berwick, Esquire Division of Licensing Assistant Attorney General for i Office of Nuclear Reactor Regulation the State of Texas U.S. Nuclear Regulatory Co9nission P.O. Box 12548, Capitol Station Washington, DC 20555 Austin, TX 78111 Robert D. Hartin Lanny A. Sinkin Regional Ad91oistrator, Region !v M22 oorter Strael, N.W. #M4 Nuclear Regulatory C(yutssion Washington, DC 20U33 611 Ryan Plaza Drive, Suite 1000 Arlington, TX 76]Il Creste R. Pirfo, Est',i u Hearing Attorney N. Drasad Kadatbi, Project Manager Of fice of the Executive Legal Oirector U.S. Nuclear 9egulatory Commission U.S. Nuclear Regulatory Ccemission 7920 Norfolk Avenue Washington, DC 20555 Bet 9esda, T 20814 Charles Bechnoefer, Esquire Claude E. Johnson Chairman, Atomic Safety & Senior Resident Inspector /STP Licensing Board c/o J.S. Nuclear Regulatory U.S. Nuclear Regulatory Commission Commission Washington, DC 20555 P.O. Box 910 Bay !!ty, TX 77414 Dr. James C. Lamb, !!! 313 Woodhaven Road 4.0. Schwarz, Jr., Esquire Chapel Hill, NC 27514 Bader % Botts One Shell Plaza Judge Frederick J. Shur. Houston, fx 77302 Atomic Safety and Licensing Board U.S. Nuclear Regulatory Ccr'rnission J.R. Na. man, Escutre Washington, DC 20555 Ne nan & Holtz!nger, P.C. 1615 L Street, N.w. Mr. Ray Goldstein. Esquire Washington, DC 20034 1001 vaughn Building 807 Orazos Director, Office of Inspection Austin, TX 78701 and Enforcement U.S. Nuclear Regulatory Commission Citizens for Ecultable utilities, Inc. Washington, DC 20555 c/o Ms. Peggy Ouchorn Route 1, 90* 1694 E.R. Brooks /R.L. Range Brazoria, TX 77422 Central P0ner & Light Company P.O. Oos 2121 *0ocketing 4 Service Section Corpus Christi, TX 78403 Of fice of the Secretary U.S. Nuclear Regulatory Connission H.L. Peterson/G. Pokorny Washington, DC 20555 City of Austin (3 Copies) P.O. Box 1083 Austin, fx 78767 Ad.>1sory r.ownitte a on Ranctor Safeguards U.S. Nuclear Regulatory Com 1$sion J.B. Poston/A. vonRosennerq 1717 H Street City Public Service Board Washington, DC 205 % P.O. Bor 1771 San Antonio, TX 78296 Revisd 9/25/85
- Full size drawings only, all other w/out full site drawings. .
Ll/NRC/H
Attacnment ST-HL-AE-1511 ile No.: C9.17 4Sc I 0F ;q)y 1 South Texas Project Units 1 and 2 Docket Nos. STN 50-498, STN 50-499 Responses to vercal N9C Questions on tha FHAR
- A. Concarison to Appendis A of APC50 9.5-1 l Ouestion Section Page
- l. A.7 4.2-6 Amendment 2 stated that the portions of the fire Prot *ction Progr,tn (FPP)
- w11r1 is .epaired to protect sata shutdown syste>ns required for fuel load, low Dower testing and full power will be operable prior to initiating each stage. Appendix A states that the FPP for the entire reactor unit should Se operational prior to initial fuel Inading in that j unit.
asolutim: HL&P 90 reed to revert o30k to the wording in Amendment 1 of the FHAR wh1Cn stated that the FPP for the entire reactor unit would *)e operational prior to initial fuel Inad. See markva of Section A.7 on page 4.2-6 attache 1. i
)
1 I i j i i i i t 1 l l . l Ll/NRC/H
; i
I I l 1
- 4.7 (twPas t9m in APfrminII A nF aPC53 9.$-1 I
) APPtss3t B A OF APC5g 9.%-3 STP POSITION 1 i A.6. Fuel Scorere areas A.6. Feet 5serege Arese ! 4 88ew Feel Area
! The f i re prot ec t ion pres r ae (plans personael The fare protecteoa proarse (plane, pereoanel and egeipment) for bestJante storing new and egeiPecat) for beeldinge storsag nev
} reacter feel sad for adjacent f are roaes which reactor feel and for adjacent f i re t one s wh s c h 2 c ou ld e f f ec t t he f eel stor age roae sho.Id be could effect the f.el st orage rene we ll t . fully operatieast before fuel se received at folly operational bef ore f eel s e reces.ed. the este.
- 4. 7. Feei LosJsat A. 7. FeeI teeding The fire protection progree for en entire
.' The port ions of the STP Fire Protect eon program reactor west should be fully operatsomet preoc , regwared to protect este shutdown systees 1 to instial Iwel loadsat se that reac t or wes t . reguared for feel leed, low power t est ing sad 2
) l full powe? will be operable prior to instist ang 3 ] i j each stage. The fire besgade will be established, trained and equipped prior to fuel l $ M
# l ,~
toed. _.l q l Y
- C
=
j The . Lye g ca.ect.% go pn~_ 4x l :t ~' e O ve teachr > ~.. t n- ) k -f t* H y crrot omql pr cr to j iv: t ;al f ve' t c a d : ~p ,- i -t.h a t y c r. < 1 s v v :t s <,,>
,A -s -
emme
.T -M i
i b~O
, p
. a ? . l > u5 ! $ 5 CT m a s: l , de 3 I ], l 1 i 4
Attachment ST.HL-AE-1511 File No.: C9.17 b}c2Of')O7 Quest 1on Se: tion Paqe
- 2. 0.1.a 4.2-20 Explain "ints clarification for safe snutdoa'i syst t9s as op;w,+1 to safet y-related syste>ns. . ."
Resolut100: See markup of Section 0.1.a on page 4.2-20 attacned. l l, t l l i L1/rf ./H i h
MacMM r- p4 a 8
'gI-ut.ne isti 'd p, ( ; - t : c, s . STP FMAR s o - e y c I hScN M ID'T 7, 0 d.. j [ 'z, *b s '
4, N v- "1 A N N bs ) ,
. ; 5., <
- s 4 . . . . g,
(
. g v r, a. ,
g
. s w . t e s % , . ~ k.
T U'u.[0 1 s 1
~
7' a .s s
.e b ,
I..c '
- . 1 1.
- * hp .,;
n s, e w .s 9 i
*A. .8. 1.
e s<< a < g a
.. . ,. t . .. < ..
4 taal.g .: . t 12j.:t!!I-g:t :; - 1 .:
- t - -
g 4 e .- ;.; , 1
. .u r. ,.. V,. ,,..a .. 1. . .
- 11. 1 < , .
, a . .. .. u. .t. ,.. oo,. , .t. .. ,. 8, .2 < -, , a s . ....,e .,. . 2 . . .
3 g . -- m. < ..
.j . . 4 , .: l. t ,o .: 1 1. ,. .- .J.
- r.y' . .
i . g u ..
.2 t. . . r s .
s 2 , { ... .- . ..
. .t. .. . - - .
t.
. . . :.F, .I.! a l : t.1 i} : 3. *18 . . . <w .
1 e i .II; L ':t'I *l t a la . -*
- y 12 I -1
- : !. t*/.- * * .ta; t t ,] : .
t
- c. s v t.
't i i ,' . -
- 1-J. : -:: I 2
.:3 1. 1 < - + 4., .. . ., 4 . + l u . 1. .o1l l - t .g . 8 ..: 3. .. I.yl,.
A . w . F
,. t. i..... ,s, : f. :J.a. 47 .r ..... .Y .-t, . . "f...::1. a a .:r .y. . .
- i. . t ..
3 I . 1.. E. ,. .: ..
-- t 2- .s.t.I 3 . v. ~ 1 ,
u . 3 1. .I.t. .: f. -.'. ... , ,< .s .
,g - ~4 r
t ; ;
- j g . . .
' . e e a 3, \ . . 1 E
a, .
. g ... g. ,4 .. .Y .t a. .
s e t. . T.: : ;; -
. ::A th'w 1 *: 2 - .7 -
- Fl y .g
,j i I .t . a. r . .. . . .- y . . 1 . . T ,. ., t. 1 . . "I t.* --
T. a - :[ .r. . t 18 C
. . T. ,,. .t 1 .a .. . . . .t T. f. .. l. . t *:1 . 1 o ..- 1 . ,t1-. . .,. .E 1 .l - .t $. 21 1. t '. *]
i . .
... 1 j t :r, .t 1
c
- i. .t ::t 4 *
- I
. 3 .,
r t, 2 4. !
- f s -1 . t. . J.
i e- 4 .- .- 3 . . u a - - I l J. J. 1 s o o . 1 i
, i t
4.2 20 Amendeent 2 4
Attactm!nt 91-HL-AE-1511 File No.: C9.17 CSOf" \c. E Question Section Page
}. D.l.h 4.2-23 Discuss the walls facing the ESr transforers ai J diking provisions, etc.
to prevent exposare from burning flulii. Resolution: See marwoo on Section 0.1.n on page 4.7-23 attached. I l l l L1/NRC/H
.. .- . ~ _ - . - - -- . , - - _ - . _ _ . ~ - . _ - - . - . - . . ~. _- _ _ . - - - _ , .--_ _-- - ~
I 1 m
- .e-C # +l . -*~
6.7 OlsepAtt%G08 10 AppfuBIs A OF APC$4 9.$.1 7-ArctNDit A e*F APsTR 9. b l STP titSt f tsee a J e. a-D.I.g. se e r,h Waltage - high accet age t ranet.or=er e D.l.a. Dry type staa formera see s aet a i led onesde fare g .Ot s est alleJ aassJe toestdanas contaeasag areas s ent asaams sa f et y-re l at ed sy st ees. J selet y-related swet ees otheeld be et the dry M type .or seselsted and s eesled wa t h sesse-cmebest able lagund. , D.I.h. The only est-talled tran*formere en the D.I.h. SailJenas cent aansag safety-related syste=* wec east y el safet y-related bes idings are two shaelJ be s.ratect ed f ree espoewre er spell 4.lb kW tremefsteers loc ated 80 f eet morth of l tares invalwang est-Estled transferwere by: t he Daesel-Ceaerater Bes id sag. and three aweelsery Eagsacered Saf et y Featwees (ESF) til Locat taa soth t ransf ormers at least w t ramatareers located 10 f eet eser of the teet d e st aat , or Daesel-Cenerator Sealding and 30 f eet morth of the Elect rscal Aus s liary Swildtag.# part s. eses of t24 faswesas that owch bwaldeast walls within the t== walle f ac sag sad within of t he f.5F 7 So feet of est-feIIe4 transformers are traaefereers are 3-hour-rate are 9eresere er without opeasage and have a fare se noted in the Fire Itasajdi Analysis acport.
.resistan=e ratsag et at least three heers. ,
O.l.i. Floor drains are ge nded t o re.o., espec ted ce d D.I.s. Floor drases. se red to regese espected fire firefightang shafer flow from fseed fare Y f aght sag water f low should l>e prownded as those suppressaaet {-stees or head hose limes wathewt , areas wheref seed water Isre suppression systems fleedamosafety-related egwipment. suo draans g U are test alled.Dra ses should also be preveded an eta er areas where hanJ hose lines may be used are ytewaded se areas pr* erected by gae awpptessaen systees. Fa rewster draanage an af such f are f aght sac water could cause those areas as preveded an ad jacent hallwa.s. wascceptable Jaeage to egesp.nent in the area. The methodalogy and c e nter na assos est ed wash F q-e s peent slenseeIJ be anstalled on peJestals er tI.* plant flooJang analyses se fewad sa curbs sho elJ toe preended as regwe red to Coataan Sectosas 1.4 1.4 and 9.1 af the STp FSAS. ]y water and Jerest sa to flaer dramas. (See NFy4 1 92*e. **Jeter proof sag and Drainess of Floors.") Floor drasas an areas beenas roebe. stable legwed Draans se areas cont a maang combest able Isquads are deengaeJ to prevent bac h f low t o sa f et y- 2
*se. el.t have prew a s soas f er preveat a me, t he related areas through sat erc onnec t tag dra s a ss reaJ of the f a re thranegheart the draen erstems. Drainage f rue areas that ear contesa system. Water Jessmage free areas wh4ch seay redsmact nest y are sampled and analyred pr eer to contaan raJeesct test y she eld be saameleJ ased d e st harging t o t he enw a reneemt .
analyzed bef ore Jiss harge to t he emet romecat. ,g y, . . ; f. , , , . , ,.,, ,,; ;, , _.9,,,,,e fse e ef 1ae .ce.ee e ./ . /~.2e / e > e-o e. e rea.s:f .,,,, ,,, . r* cc.y a e's /x f. .:y .: . e,
.f.de t' p.) .;- r e / co. z } f s' s ra te- fie ! fra ~ f$e rCat/ 1*.e .c .pp e c u , ,. . y;te f o o.s . s,. r e .a%a r;a e.
d 4 (>c/ fras.r/se /c ! *$r . ?'~ e ' ** .y ' * " ' ' ' ' ' ' * **J f* Erd Yo ac
- e f ee? e< n e .
ru.res z, e/ec e,;cek, a.a n, r~u ne <n u ra .,e ..r . c . o., of e m
;4 e .re*
ae/ o, . . . . :, e, i .n ,. . ;c. g,e . ., .,
~l cp e -- ? e r' tie - , ./ .fe e" e e e a es ,
af cad ..*. er .n ,,eq . ;g,7 .,,,,,Q , f a S.2 Ifd. ~
,.- , -i+. 9 ---; y t -
t -%=e- e -s- - + - * ---pt-- --- - e- - - - w-- rt- -- r -
Attachment ST-HL-AE-1511 Flle No.: C9.17 OyA of lo't l Question Sect.3, Paqe j 4 D.l.d 4.2-22 i verify that the HLAP response to the FSAR cuestion 280 l?N on combustible , interior finisnes is corre:t and includes all such materials. l l Resolutlon: See marwoo of FSAR Question 28).12N sttached. 1 a l i t
! I -l )
l I l I l l l 1 l ! Ll/NRC/H l l l
--=%..
i -
- - - - - - _ _ , , _ _ . , _ . , - _ , . _ _ . _ . . _ _ _ _ _ _ _ _ _ _ , - - - , _ _ _ _ _ . _ , , _ _ _ _ _ . . _ . . - - - - . _ _ . _ _ _ _ , _ _ _ . . _ _ - . . _ _ . _ _ _ _ _ . . _ _ _ . _ . , _ _ , _ , , , . ,_ . - - _ _ . _ _ . , . , - - . , _ -y-
sTP TsAg M hachmurt OT-liLAD1511 Question 280.12N Provide a list of all interior f!ntsh insulation, sound prnofing, etc. that are other than noneembustible. Indience the flame spread and ntnoke cont ri-buted ratings of each material where availabic. Indicated where their mate-rials are used (by fire area) and in what quantities.
Response
The following finish eaterials are other than noncombustible Suspended acoustical ceiling tiles have a flame spread of 0-25 with a tlnde. writer Laboratories (l'L) label of 25 or under when tested in accord-ance with ASTM E-84, and vill eeet the requirements of Federal Specif1-cation 55-5-118A. The smoke contributed rating is not available. Drywall partitions have a flame apread rating of 15 or less and a smoke I contributed rating of C in accordince with fire test nurtb9 r USC-17-TT-C&H l and/or C A-Vp-45-lHR, OM/ ct re N o.c<. [+W, re f- W4/CCl e d W
- l b M M,lf. .
Vinyl asbestos floor tiles have a flame apread rating of 75 or lean when
. tested in accordance with ASTH E-84, a NBS Smoke Chamber 450 or less i g ) (Specific Optical Smoke Density), and an U1, 992 Flaec Propagation Index 4.0 or less.
Epoxy floor topping at 15 or 20 dry mil film thickness han been tested in accordar.ce with ASTM E-84 and exhibits a flame apread of 10. smoke density of 40, and a fuel contribution of 0. The floor of the Control Room and the Result's Engineer's office are cov-ered with scrilan carpeting that has been tested in accordance with ASTH E-84 and exhibits a fla:re spread rating of 20. a fuel contribution of
- 10. and a smoke density of 10.
1hin-film paints on valls and ceiling in other Category I arees have been 16 tested in accordance with ASTM E-84 and exhibit a flame spread rating of less than 25 with zero fuel contribution and smoke density and are therefore not considered combustible. y; ,J3 - Q~ . The above esterials era used in building areas normally occupied by the power plant operating personnel, and in non-occupied areas such as corridors, equip- [ eent rents, etc. The approximate quantities are given in square feet and are listed by fire areas in lable Q280.12N-l. l36 I l l l l Vol. 3 QLR 9.5-16N Atw nthre n t 47 l
Aftae.hmeni g7.g.gL.(\E.151%
'ih e,9 6 IN 3
m Qer# c g(), /CM
/dseer x, -, . . x. . x .. . / ' l', Thud o. < c. no c k s #ble .Qw; s k e g 64
( biesef Gw. Bid3. 44 g wlg t,.s gy g,gn , ' 9%k-W PSh oppCed lo n e w w l .u s S b l.c Sd5M5 cwe. ns/ w s,% wd cem b u s # Ale , P T V>c cre < y : . .-fa < c >- arplled in con w< h- "s l 4 wn IIs 6 k I2cocler Cm/wi w - Eu dw3 has a Fl=< .spad r+1' $ es ' lo , a swe L. edu sig
, pehv- oj o c, 4 n Mt s k %u Hn, ek of c, I
s ls ll, u< e neh e n ds i v<d en k 'b le .
-t. s- \m_ - 3, .q y^ ~
l i
A Hue hmen+ STP FSAR g. g.g(, O C- 6) \ TABLE Q280.12N-1 APPROXIMATE QUANTITIF.S OF NONCONDUST!!!LF.S (in square f act) I Fire Corpe l..q
- Building Area Fpoxy V-A Ttle 4^; cetting (
i 1940 LAB 2 e ic2o 263o 25o 1 4440 4este +4e 3,4 o Gs3o o 9fo 3 4Ho 4490- Ao ! o o 31 -444 - e i 4ge+4 2e i 4 @ 4 +Q+ 4 t h'o 45 o 67 -4?40- +P40 4eytt-
- i MA* 21 550 / i 27 444 4 6622o !
-' 1 41
'4 !!950/
22 4190 / l l ! s ;:^' L l 4 29 1940 / l
, t
{ 2) 44Ho 4c56o 28 570 / 32 43909 '21. Dio l 75 4449-l 9 7.7o 1 30 800 / ' j *3 460 / 26 310 /
, ;;;" ' ? ^ '! c ,' t^ ! C ' . , , ; ;- c , ; , 5 ;;, ;Q ~
i W JA :UWy~ tef- Ati M t*0* O Ams-
*(From TSAR Table 6.l-4) i j vol. ) 4t.R 9.5-16Na Are n,1, e n t S; 1
l
~ _ _ . _ . _ _ _ _ _ - . _ - . ~ _ _ . __ _ _ -._ _ _.-_-
Attachment ST-Ht.-AE-1511 File No.: G9.17 C.II OC K ,i Omtion Section~ Page S. I).1.j 4.2-24 Explain "In order for f1 e to procaatte throurp a sta!raell, it %st p,ise, throogn the er?.Jivaleit 3 hour fire barrier". Rea.nlut ion : Sco mar <up of Section 0.1.,. on page 4.2-74 att,4 chm. i t l l l Ll/t#tCht
. . nHachnwt sn rm s f4T- HiM DI !
Mt he %f 107 N ( -e y ,. g
.: titt : .: 55- :
2 : . .: : .[ t : - 3::* :: :- et y:}. ! a , . : gt,.:
.; -=. :-- ::: .:
- ':: 24
.. : - 3 . g .:1 k.s-- . : J 2 1,} ::. 2 2.2 2 3 .!: tat
- c [. .:3 r t 2.egf.:!:..:.::32 J , 2 2 .: :
.: - t 3. g : :t- ,22 3
a *.: 3 3.g ':,: ** 2:-
.! :: .: J us...
c- :-4 *:, 2 :: ;
- e n . . t - I g e: = : . : :: : 2
=..:'= 3, 7 ['T :
I :,:. , .
- i. wit. 2.-5 I'r.::
t a x.t: . 2 - i - :3~t:1
- .* t.3
;. 1:- : :3 att l . .t l
- t p 2:i r.
t . s 3. ! t -
.i.ts: .[r g 5 .: 12 i
l
- !::y*t.!t
.. .. [:t... ...,..
Is .!,:t : 3 :t ta. 3:.s 21--:-
-:,::: 1, - . a s.
E . :.2-t ::t *- 2:2 i t:. ) 5t22.:[.ll g;2 84 at: .. :t; l 3 e
... :t. 8::1 :::::
l A. t l 2 -
- . N i ,.
4 a i ~ ' ; E. .t t- 4-t ( R } s ' ws
- a. >...s .e .s I
1 I;A l 's j i,I- :
'2 J : ' .... . . . t. j i.1. .f. r,a. .
- l. ( .; ,.' i s. ... .- , ,1 -
- Ic :..I 12: .
7
. 22..,., 43 . ': 1,., . .2.i. . ;r,>' j ~. 2 i.:2 2 2. i.. s.13 .,y-3 . . -
g
-1: - 1.. .r .
1 -
. 1 .1. 1 . 1 ,gi.22: 2 3. : -:.: . . .
- r
. .::b
- e. .l. ,: r- : s- ., . : - . . 5 << . . ,
E .... , .. i
- e.. ..; --
- '. *,.i a,
- r..
- s, tJ :: n . 2 j i.= g.ic si.s. t .. l 3.;
l a :t . y g ... rg.::s.
. . : 2..IIIgtl g
t := 3 4 d,4
, s f. .,r- ': : t ,, .. . . i ., : .{p.
g : := 1,).l3ggi.[2 3 2- ,2g.. j .J
. ...: : . .... t. ... :.,
i ,
- ', : , J
. . i . .- . .
E., - , , . . . . . . lt'23 1.t: j :. 7 :I' :2t jl.. ['. -I I*h: -[ h u.:i .
; ' '\ ' ' ' ' !'
at:
.' 'i I . .I '- * .',e t
- 1 3
.j 't. .t : i s: *
- g:
.fc. . -' j; l*
2,I...{st'r.. a,E 22.tt -
- l
, 4 3 .
l t ( . .t .
..%.t ., .. g
[ . -
. 8 ,: .. .) .4 4 .t t , ,,, .
ai ..'.;; . . J. ... a a. )' s
- g .. . ,
g 4
.e ,
- f .. '. ~
. .' e t ,
{ i !. ' . - .! -
* 'a . 0..- ., 1 I .# ! '
i t . . l < ,/ ;. 't i - ' . 4.:-24 4.,n ueni ,
/3 Aitach<nc>d 3 pr.m,(E- 15iL t h m d h f l C 2- /!(le / y _
3._. Je/ci,,e Geund r./ t'3. lt a W;lt ool EeI**l i Ec,c h kee 6e^ls
's it F*A / 20 AJE , C o t. t.a ul u D o.sc A oe r tos) /0 ' 23// to)
J's[f t17 3 - 30fe%2 R ..l.r trA e vf W<= p * *
- k l o 1 va P S Wo o l e l J 4e 4 3o.s moe s 1.r T, k
.- apas- sp iso s - w . s,.s awy A. eye a.u.e , -<
{46o6- 30 24' t 4 c- %i'*12 %inae s. e ?.p Ck-*, to L WIS */ *-f den = 7=- I 2 Slt oost - as/ll13) w w . . u ,, , a . .- 39' 2 8/'r e'.# - 7/ t :10 A 4* t- 3 o i.J' i Ra.4 le.e bW f P e b 4 E t t.f ti,e M.( la-L s.t 2 3/1,<.v D// s3S blod - 3 tido 08 e=<bue 9 ef CL.4e h P.re a-<l u! AC Chace A,' T/2sto D/t.3 8 a +v&- to lb.. Re,f 4tc, ti,.c io Recycl< 414 9 ..T t:.
>v' av/r n - 3/si.7 CWL- 3] t wet 'p 4 Res. n i.-k - J .usi,Ev p io ,S V L,e 0.. ~J bg .4 0<C,-po.6r 'f t '
' 41/7111- 3/2 30 Ete l6 - J 6'o 3 De.aene,.l.t,r (.4.sles tu Ice w- I S P, he,ow 1%t,.-al Reagea 64 / J )/p l*,1= '$/g g ry 6, = Ji4,) I D g,; gfpg, t et" hd(I,& kl led ll.
- EA). ale
- egg or opm- sS,% si - swn t :. ...i.,,, co t,,i,.i w ,,m as.u to t e,.
w apisi .a.n t - wo u w . . . . . . . , , c.m i, , 4 c ~ 4 _ . , a a - .. ,.. 1
%4' 'd// .M- 6/ype., 4 446. Gold; 4/f4 tg..f P.,% to u vA t o m t..t,C i, l..t s I
A' 47/2o28-4//cg5 .4 4. t, >) .J a/ ut, ..tav. Ledweet sw e% 4. Hv Ac R e t,.a Die. . a' n/rin .ng n,4 s - ai sc v.i.4 .,,, t. g n.,. so % 4.e o. t..e N, cw.v av s,</ a n p ,,,1 a - u sI w ap .. <a e.s...t,a p,n cu.ae
.* s, r, . iv ,,I e. w wr h i, , o p,,. t.c g ,- w ,,.. i.. w e,,
Chge t o
h I ha.rme n t i G sq 'g.
/ at. AE -1511 4 t hqc,14 of 10*/ /$16e. N .Y 3 _
3
.L /e s , , ,- F v.,d. ,y v1. ll . W e h,,,,, { f l e,( Pe. , i, tc.,. Ce~ia i y
[ Et FAl20M6 , cot o.out O roc A rprion 41 JV/r ,3 7 4 J/2'//- E -3/44s31 /*M foo-s 4 l, w 4 /> ' // '4=je 44 s3 ' 23/2 tic / le 1/tri? [- u ** 3s S f,.ito < /, .r ,- f.p Cus.o.* i. LeggC%.<w-ste it. aIce 09 O'Ifflib bO3l l!4 H .18 so ll Ve ut e *,s . . Ar< n 4e C .I:o e s t .
- Q. p c c L. ,
I A* A/183 7 to J 3/2//8/ 4 .6431 !.* trade g l!.41.e-., ble f a C..J lea s I. * / /<
h Cla s -c l .S ??/ziosh13/194 i464 -31 R eu ter % e w.w 1. 4 % Fn6 l o' 67[ 1.2/2cou k W -J'4 34 R . n a a., e,s.- .a u ve o e. . . . s , _ ~ . .,
sii 5.!/ += 3 /t n i mk,$ 24.a4 QmW Co As; Q. 40 Et. 4 Dende4:.,, ce es.
e., ' &T,/ A 12 A 2) L..Le(,-f.. - ,4 to T. , , P,, . k l,o . A, c h 2/tn 9 O a' n,' % s}r on t. M-aut w< u, c. ,.t : n + h, v n 5 oc , t ra s . . str..,
e-# 6s/ 4.uynr mi awn a.,6, ou. iss s w,. . . i n. , < . n,..
l
-24'- # Of lo ',f'/ 6J 4.i.5- Jt, Oc. A e Co,da, ,4 4., I",,l e. g,,,,til.. e (;)4 ;,,
j 14 * 'I/a ut s* 6 e '.,/ t c e i4 A.f J6 HvA< bv< 1 to o.,2 5 x ..it .u t as t. ..te.,e w e t I gl' '0 (!s pl so Gltonti A .$" 3 0 4th( bulT no DJ t%D Et 0*C ;~) ^*l t, rot so r r vM 86' '2./2 01 t, 60 (./t d 8 'l d.f Jo &lvAC N crTo cu rt. Or;., A./2 Isv r4.e s: r,r/7.e tuti ts' lfol2 c t3 % tol gob *, A S
- d .1 iss!A t Doct to t\v6< Coo m .s n' in4lRo ts \ o (rl1 Cost 0.5 > %- A u k t bu t.1 % vus e, e Ca r3,C TH'Ni :.rthe rny rg ' 51/ 2 oi ", 4 9 (e/t ait 4,7 JJ 4VA ( bocT to 4eAC Rooe 1
u' .. 9,on s to fu r A.r
- 01 aosL svar ,o w e nom
?
a___ AHachrnes* ! b . O $GW M-1511 1
'WacE 8 f 07 !'I '
I !l l ! I i i I e l [4(c 3 _M ? l ;' ' j ;
.L ker., .
0,u4.cf. !W.,ti 8
, s yJ i
((,o{ , e,t.,4 . i P,,, tmt,.,J sea .
; i ! ; i : i . ! , , ,,, , ,f i i G t. f4 /20^2 Co t- uME Dr.s Cf/PDod 41 3yz,/yg 4 c5-/ m.s- se 32 th' Ac oor sioE Eser w mmsw zet l m.s- w a nwau. .we., un m' .n/zios h.srl n.s ae, uss nervet.~a ws,ca w' 3p,,6 4 ss/ n.s sc.nos p,,iue macuum uta tof3 13/ tio 3 A.'as/ m B - 30.si.s> Er. m oe. mauvP rw ..p' awien>wl m.s - s e a eu oeuanu wam \
ga g .
. J e
e i l
=
1
- v e 6 e e e
't .
Attachment ST-M.-AE-1511' File No.: G9.17 TageAof'lo1 Question Section -Page 6 .
.D.1.j 4.2-24 (also Section III.G. pg 4.1-12) 0.3.d 4.2-30 Identify and explain the deviations to the 3 Hour Fire-Rated Barriers.
Resolution: See markup of Section D.I.J on page 4.2-24 and of Section 0.3.d on page 4.2-30. Also see the responses to Question 6. ! {: + L1/NRO/H
" 8 D y$[uo _
yhst;;e g ,C y*i4g&y"
... ce 3
j* m h d t ' r n o r ed el n o . h rsi i eo r nv ee ,r st t our t v aaa ve r eif mr pe a s eb e1 o ",op r w
- er h r e ,h l r f a rt6 c a u g sh ei4 eee rei s s o- nect eF r rR sed , 'r es gahe n N. aeps e ne r M iminh d nah e ol ti r f roli er i r3i ! e r pfwl neil esei d a u f f
- o aort I h ees s viec T ed y ar h a sbI wr ne'l h u t s .
ol l eoo r , rit t en t l r* hpl cr c ' re ouasS o s ra re
- t s e nig: "
if nr or oqui ood el got e soA
- i. yon or ti st
.ieh i ew w
( : Do aet cd af r e3 N et i "e : d nnvr eon d d v e d nh t e O st gard a : ei oae aef rSh oer ed pat a eet ti ra l ee t c I T I i l nr ae" pc"
- =
f
- t es r l i cdi yeR maf e nihbR . eti s l" M et eh d r ad g 1' u*
aif rf o
- i S i e n2 : A uvT xei n d o" nnt O es a 1 ' df o d e arnri oge P c t 7 hs5 : - - e r vl p . vrna eai e .ictd d nnrr eo uah t 9" nie sf P d ci : icrioa noeel vdF l hs e T
S nisf ah e^ oor e n r pcti p n pi rae pl n l e2 re' ot re0 ar5 1
, w r "r I
pe apd cag t pi A eoth vf st w o ag h' e
- rfd eh n 5 e) e : 2 e l e r! 5 r y s teetdE t nor usyn i o a eph o' l l
wi h 9 l nir b raon s nbi t d ro* a st a of - n - our ann o s ei r
- wni R wi 0 ; -- d l p ooridd tf p ow S
C
)
d ,ta a r '; r teea r veeti oatt di s ot ee d c eu8 oh r ri otd P 't e rrS c e c a erwcrd rca s r t ' ir e A rt e cf e w i ee e t ec ot e rot n oeh! n t d nfi t p eeti l s s e' t pa F o ont ! M or e v o or nod cna r ' t c O C l eii : r a ef e r oiern noli ' af o A ( F pec;,iphb orPCf ppi
- E cCf P E ot j t .
i . j , D i. N . e f P P l. 0 I. D wg *
^
l e e A O s e n ,, s'c . r T d e N O f o ee ef l u h t ee v d e r e r J e a o,g nJ e t o b coh o S I R nt b oa i et a r g a n le
- o. f od a nr c p ud eo" F iA nf P A. ,,, { , ,7e nq ;
~ s A
t r o pi e , l r pS ehi N d ~ ; P M O C a r et d cn et rg s ei n t uf a a o hh rfi et s s n yl i id
,d k t t d c . onl at a r o r
p 4, e R s , o,g
- 3
; .i me n poe g pr r ar pr a r 7
4 1 one es h es n neeiios o i r s pf t g odt noet f si e of hd ali nd ea t r od nne e ai ve e t t nr R t e n d ,
, iva ,,
- Puc,,
- s q
w.w t 5 t on l t n and s od ara ( 4 a di ce aeueeeb ei o ) e g,
.g _ \, e s _ .Wyga a nun 9
B m os r r ed eeiei i eoa t v d qpt t as cf y rn l on l us b d s
' cs a t. , ed g S
C f e e nei ot r ed cnnd ew s C 4, , . d < t s gi nur s ot ee noer o a p ;; p p . y 6 , 9 roo {r.w, i P rs e e e , A eyc nmod p a onbs yaitid e gi , i in eD e il t c un , t s n l et ool l enl d a e qi r F a e i vact a v ga nrt eW ,p wnu a. . O ear , oq t . vaomat or e r a A fi e cht gd afi hcr ene l u eoenpen d d , fQ no 34N g % ,*P ) ,g , oe s dd nis geqt rnr e r a g ' X c n nl ed ons ea aree C 4 I D neo orc a uP ul it o hyel bh s A eg g ,
- vo ,
l ctie ht l b a wro l w a.4 V f N E i p t pe eh l s .cnrrrieadh t l ml*
. d o *. 4 mg;, 4 .7 %< A y.. A. 4 h
m e l"* P a ul l si o ewr nl t ourD . P l sb . u a sr we u ei a ouiooe 6r q A
) met e ad ,d eoeenr ed th c rd wiowrh pe s mr d . . ;3 mt r > s d % e, g d
ur pl ci el cf ca
,rh rl aat r asdl e a r eat b c an eomdF e mr e ai r"
e a
* .a t .,
c p
%. s e
i b iyN s t a , w. t eie s eh 4 n o a was ct oeersi et orrr sr od ar rt t oa ns o , e. c ts a c 1 a.
,J4 e O C
( f e nn I nui l ih a eeir nyol oyo0 Ff t bb rf pabd acsd8 se e s . se ea e= p' l l . n o g Ttd o r . i e. ; s f b A s 9 a .e i E S t e, _ k*a d.a d ats e , _ J a *~ 0
- p j
w e c _
- i. .
n E o -e l e d e t
- s I.
%c b cl e -o af cn D
I. C e i %e,n
- A (g, D
s i h ac o s l
- i A
t a P raW e S n
- c g" h i* ld '
a e t
'e A db no i e
- Oc c" t
+ce '4*
a
" dm
- t -
- n E RC h e
8 .r. d V ^f " I P r
- ge7, f, o 3,,
t n
S
, s )
4.7 COMPARISON TO APPENDIE A OP APCSS 9.$=1 APPENDlK A 0F APCSS 9.$-1 STP POSITION D.).c (Cont'd) D.I.c. (Cont'd) Cables are designed to allow wetting with deluge water without electrical faulting. Manual hose stations and portable hand estinguishere are provided st rategics.ily around I ' the plant. Concentrations of safety-related cable outside of containment are provided with , area fire detection. Inside contairseent, concentrations of safety-related cables are equipped with thermal line-type detectors. Safety-related equipment in the vicinity of automatic water suppression systems are I protected from the effects of system m.ilfunction, if required. See response to Itco A.5 above and FSAR Section ).6 for further 2 ~ information. tn p D.3.d. Cable and cable tray penetration of fire 0.3.d. Openings through designated fire barriers for y
- barriers (vertical and horizontal) should be pipe, conduit, and cable trays which separate Y sealed to give protection at least equivalent fire areas are sealed to provide a fire 5 resistance rating at least equal to that of the N y to that fire barrier. The design of fire #
barriers for hos-iaontal and vertical cable barrier itself or have been evaluated by a trays should, as a sinteue, meet the Registered Fire Protection Engineer to ensure requirements of ASTM E-Il9. " Fire Test of acceptability of the boundary. Building Construction and Materials," including the hose stream test. Fire barrier penetration seals are qualified as stated in Appendix R. Section Ill.M. I P :..r;/e easta,:ts y in c tes s . /e n . . , Baner%- e- M. N
, of,,;1 a r
- f y a x ,n w;+ 1 j ,; p j e j e . /e / .s t fle fere / --;<- a.
,' ( ,, gy ;f the ce 4 ;f 1P r~ :. Jai u:r 4;, .r guy r m ;;
wn
./ she dare;r or i f <s e r en (e.j. con /e/ef) 1I~ a y w;&.*n t'h e daaeate. 9' e?,'/
e-. 5 a v,; / //c J' feef sf r/c yr de coade;f es ,'a e J' f7'e f un sa cl f.r f r nt'er t la ~
.r;4 of de dw:ec av weg /, .rute/ s s.a g '
en /.f W*i$ ste A C0" bJ f ."$/c fmod u (cas /s. fee f,' a r e +' ~ #/ /dac'lrd/;se fe a / .0 4 f s.*/ s
Attcchu nt 1 ST-HL-AE-1511 File No.: C9.17 Page R of g ) D _ _ ,
. .e O
I r'-'1 8-l l G .
, t._., 3 i , o /:
4<
.F,@ _ -
_ h*i_ I 3'
- h l:.eq.e
_d:j{h h g$ I ~l ;l : t a if b 5* l I
~ = <s i: ; ~
4 r-<, ; d 1 t _.a I O k
.t.f. , -A -,5; ,
c, l ;t o _[, ;
< El'l
- 1. s
__ .._ L I_ a 3 e si 3-ii ?! 2 TL je ! jE _/ 5
- a l
SOUTH TEXAS PROJECT UNITS 1 & 2 PENETRATION SEAL DETAIL Figure 41 1 I i l [
Attachment-1 ST-IIL- AE-1511 File No. C9.17 Page @ of jO7 Question .Section Page
- 7. D.3.c 4.2-28, 29 Revamp the HL&P I8!sponse to having sprinklers in concentrated cabling areas.
Resolution: See the new writeup of Section 1.3.2 " Fixed Suppression" and Figures 1-1, 1-2, and 1-3 attached. Ll/NRC/H l I l
i Attechm:nt 1 d ST-l{L AE-1511
!: Filej{o.. C9.17 H Fagedl of 10F h
I u TY/# f // A A N .. 1.3.2 Fixed Suppression , The STP fire protection program provides for manual and automatic fire suppression capabilities to prevent the spread of fire between fire zones or fire areas. The FHA evaluated those areas within STP where safe shutdown systems are located and where e.~/sor;/4 a.re,s./s rert a c..er.r .ri : ..r./h,;,r e p
;, g,;st *.*f*' * *f ** A * * */ f: jf ** * * *'y ' ** ** '//** *' '* l * *
- l
As a result of the FRA, fixed fire suppression systems will be provided for substantial fire hazards such as diesel fuel, charcoal filters, oil filled transformers and laundry / change areas. Automatic wet pipe sprinker protection, at the ceiling level, will be provided throu8 aut h the cable spreading rooms and power cable vault. The STP fire protection program provides for manual suppression to prevent the spread of fire between fire zones or fire areas in plant areas with moderate or limited fire hazards, except for certain concentrations of cable in trays outside of the cable spreading rooms / power cable vault. ,4. c v e s'* ie i+
- 4.t ta c. ,,, a , /; , ~ < / s. /ai e. ,, ; e Aicd e,/.4
/ry c.,, /:y .. . it..a are 4 Je chu;/;</ a 'c.. cen /ra /r / or % t conce. /raird .
II n is ev.ssh c..s:.rie/ ./ - w//Avi, of /e 1 ed: e 7 4 1 s re<!~ ii cs//e dry cn /y' * /;*a y<:.si da',<a /.,, ,/ e,:ta,;a frae ,ry a /-/ s /i.z), 2f a c /A /ry y,.y;y was t a e. ,,,i a e / + /e 'c ca,/, ate / ~ , de
,, , e . wa s . /y e < / /. .&t<~ ; < ; f n . . J .r y ,, , ,is : < ~.i /p ., s e.
y /?,e n u WM <e,<</ + a/ya.cy a/ n,,, .. /is,,,, ,<u:,, de eva s /i., A.u.i J<a,- wu :,, //c .e, ea a v.,% Uy o t'
,l s,,s e ,/> > < :y a, /.,,,itic / e ta/ca/;.. ,
dae .r A i:o <i de iee<rsid24j / a /// .n . f <le i
< /e <//ie /:<e I re e/ o/ x fore s/, car is s // a r en, .< / //r e /<.i o f ea J.,,a://c A.4.y wi4 de /?. e s <a /r oa < . V:& ry -/ /o /de 4 >Ye. //<n a s, .c., aj r is w <s ~ . /e ,e s -/, ,, te a ,,, a s. 1 o l' ;o, de .r e <l f:'c co I p r.<//*>>
co<>< 4 : / / d /e r .c r e < .a. , / /4 j
; i .( l l
n
,,s. tso.' .n~<<j ll Attachmsnt 1 l ST-HL-AE-1511 jl '
File No.: C9.17 Page $ of I W P 1 G.'<. ,, ~ le- ./ e</A ,<,.,.7, 10w ,ote, s-e y e 7, e /
/e,y b o /' fr y .c/u dt , ,/ ?
_,y ,,. s ;. , r g ,/..ea j, f < <,
/eayr ). F.y a e / .7 ; #<.s/ra/ei de ,/,., ;< f/o w,. . //
u,/ ,:, ,,t, i e < A < /i. ,,. 1 I l4,,neroas 4r edJ Wfre s /en l,'ke/ W * */ * *9 //e ! S p /<oU
//a / x,e cAss,'/;#/ <s cor,/ain oj " con ce. /r a /el c'/l< , -/- <; coa /gaex//oaJ. .2*r* &r -/G //e- /e/<#no'nel /dtf x# ' con c e < f r a fe/ ca ,,
se ea r de s de 4< /e) co*> /r* /rl
, d, />, < ,,<,< / ?-/ r e .r~fy e etr:=n .
noweeee, .sar, e e a o ~'
- c. ,. / <;n ca //c /es; coo,ftyae</;*"' w/ c/ /:e , _
,e dy .,i e c / /s e eiees J-c/ <r r'* suaAe f/c _
m<noal -/Ir e r~f,o s esri. n e/Xe rs' ,,, a , e ,/.' fpc 4 // - l
, c // a,- e J see ecac/o//c ,f a/ / eat / a ,, e e(fec /ove dose r/ees n s'<. / /de r e.,r o o -se -fi e vau // Ac f /e-p/le s el A. c /e fle ,, e.r ca e e o( ,e / c /s e s.: e e f.
7*/e e r ./:, e, irs /l!/ e a e ea / 4 ey*. , a //c we/ p,ye p ,. ;n d/< ,- \
. p ro /ee f. < ., w: // de , , . > We / a/ /le ce .'//,, / eve / ne t'Tanaa/ ae/ a < f a in d h 1o I
f f,tirjo , p,,a. /e/ w;// c.,f,./1*/e f1,e u pf,', t/c dee<. l I
.g I k.f t3 r e J to l 0f y'$t d' V4-lst a / o'0 *s sY waJ c/e / e-,,,is e d r /< / so *r< co f<
0 f , ole , /a. / '~s a c cr ,to- t:* n o/* ca.nltaf//es did cou // / eve /oo , a 8,e jeow// J'ceira rjo st. c l s'l* 4 //e Are cou // no / /< e,6,, rose /cs/ eo.//r co,/ro//e/ w;a; a , ; r e ,, ,cre . < < ' hy ,,, a , o / s.p/ r < <<i. , l f lfe e /J-
/- E //}ue< -
Attachmsnt 1 ST-HL-AE-1511
, [t a n,p //J 0 $ 0 a C e n / r
- l t l D l lC Yref.f =* [{ t
.rix(s),,,,,apaa,t W* 4l Jy a r n /o'en on e (/)
q /,or ltt! I** l ** b// E ei e I oUJn s, e Z' he (1) s/jseeni .c/s e At V*# $ ftp ere fo'o A Yref {j) l 1 ,'Na7 f Ae f or /ess, ea e/ .c/>c/ o , , ' W'4$ WWO {L) er Mert /reff
$ne$ /* $4ik l
9
e Attcchment 1 fi
' Figure 1-1 ST-HL-AE-1511 l Filo N . C9,.17 s Examples of Concentrated Cable Trays- 4 2 W 6 ' / ~ ' ' ' '
I I I
- 1. l A single stack of cable trays j more than four (4) trays high ;
I I l i i I l 1 I I - !
?
Y*41.,YMAN_} TA/fl 2. Adjacent hori: ental runs i l l l l located fiva (5) feet or less I separation, with more than i l I I I three (3) trays in each { [ t t i vertical stack - a l '!: #' >l I . ; oe ua , i
. I,
- 3. A stack that is more than I I ' three (3) trays high that is '
] g\J%, , less than.five (5) feet apart !,
hori=ontally from a a stack of : 1 I \I I three (3) or more trays which l,5'); ; fall within a 30 degree angle
,,,' from the vertical, starting at the closest edge of the bottom wi ra,ar .S ' avwreetse to y n") 30 * , tray
- 4. g l g g A st'ack that is more than three(3) trays high that is
- I I I three (3) feet or less horizontally from an adjacent I I I I stack of three (3) trays.
4 3' M l sq 41st s) s
, , e s . -fun (2) ,t ys /g / w W /ve *r es.r'</
o
, , , t t ,
Jef erefo'es s'wo b) kt f o r- lfJJ
' ,t ' o n litt , , , ,, ,, ,, ,, , S /41 /">F ~W .r ep a - / 'u - en'6".s' .- /ets ._ i Q _ , o ,, , , , ,
e fo) f;
Attachment 1 f.OG/C s2*oA ff 7'Z //f/N/sVG prNJ 7)'s'af of //Af .l*p/AF%Cfd, TAW- L6tT7fAs / of W k &A 4 0A set!ToAtA f/C, s *R ALL (4/42 7'/4)'J 06'7J/Af (4// .f**/ t* A' UM 6t!// Nt&L 7"'
/trifaffAtti 7tAy fourispoArseas ACA/Mff (Alf/AIA
- ll// fodJ. / / 9 l*1 9 ,
i (oggfMTAe ff) , YJf AmfffkW sVe g 6444$ Y44!! $*f Cattf faa!/ ' #### # F l'^'tf * '"YE' .
-rs A r3,e 1
Airs f YA5 L , Yf) Je9& e fo 44 p, t ba rf f tsan /d Asta ea F m otr1crioat, y sa A fra - , fany f i 1 i terar a Y'I y A YS' g ,arge *L x<><<,? ,,< av .* / V y slew lpprx A Y* /s5 $ser ll# L A YI' / /s$$,vg A* w
' u, i,a<.-
r a.,, za. r r
- e 1
tae H eres /ffAMFAl s&*s4S 2 N* I " #'" Yl! w fyff/////oM m cou rge t. f y ,2 1 sj ? / _def4UATE
- s. ,. , -
Y /~sof S W MG. f _ ffQnnEb O TO EMIEVE. CRIDIT flay BE TMIN FOR USE & PORTMLE UCOERS 20 ME01ATF CtF#MF 74 ECESS PAfl!S
At t as haa n.t i ST-HL AE-1511 File No.. C9.17 , PageS4oflO? ; i I Question Section Page
- 8. D.4 4.2-33 Clarify smo',<e purge modas of the EAB and MAB and ensure the response to FSAR Question 280.09N is consistent.
Resolution: See markup of FSAR Question 280.09N and the associated HL&P response Jttached. l
)
1 l 1 6 1 1 Ll/NRC/H i
M4nchment ! SIP FSAR $7 HL- Ae 1511 Question 280.09N You indicate that the normal ventilation systems vill be used to provide I venting of smoke and other combustion products. Verify that the ventilation j systems are designed to handle the high temperature gases which may be expected. Also provide a description of the operating mode of all such equip-cent serving each area in the event a fire were to occur in that area. Indi-cate the operating modes of the ventilation systems in areas adjacent to the , fire areas. j l [Qf.tf . J
+9Zespbsh i
i Ve M.n . The normal ventilation systems vill provide purS ng i of combustion products and 33 I gases frem the af fected fire area until the fusible themal links melt and ,- release the fire dampers which will isolate the area from adjacent a h7 l also f rcm t.he nor=al ventilation system supply and. exhaust ductuork.gcas, The ~ and mbustion products from the isolated ' area vill be removed by portable vent ! fans and vill not be transferred into any areas containing safe shutdown j quipment or stairvells within the building. - 33
~.._._ - - - . . /.
For those areas where nomal ventilation air is staged from one cubicle to another, the fire dampers vill isolate tha af f ected cubicle f rem adjacent l47 cubicles. The safety-related equipment that may be located in the adjacent cubicles vill not be affected since the primary means of cooling is achieved by dedicated essential chilled water fan-coil units that are completely inde- , pendent of the nor=al ventilation systems. 33 S=oke and heat removal is addressed in the SIP Fire Hazard Analysis Report. l47 1- r NU,' WeEs* TC'C / Cpm' "O 9 4t? /JX 4/Y D G t.fa 7UT) osy "!C [fc fi-/[ C *t [ /WLA !a'C (ff * 'ft.N l cs '.n 1 C C" J)oit. 's . f :('s e el r. c' L r ^! %
/"t L 1 /k d ,s./ , 4 1e n ' Mr:r'st A.'t Lc /1 % , t&L <- t' Ak VL A'T %'t $c L" dws l' To ,*t,/ 6f' jp % ,,) / art ,. *, )}rl .N .r'c ( si R t; .~'I'rL/.'tNO !M TJt~ u l' '> L. Uf ~ '~/ *'[.- k b- ,
7+ (. 0/'tl'/2 7D/k itir /1l '5 L' y's'sy.X*/l[Ly i;L % /. "L. ' C e 1' 'ti tN dIh!.r'tL 7C. / Jc'h 0i- f( 0 $ ' M L '</ ' i c' . ry 40 cc Cacie Le ncN /N 9*c ciMc ev roc l-/2 6 1- 8 Ntt L I O il 0 ED v'*dl ) /,/lo />,rf (_ 'j /h tn t' [ L /!!C(/ N L. iN fit t. A S L Y *Y 'N' S!?O < d ho/ W *//*iL} Lll59 tl/ ?t.:k ( Li.b a f $l.! Vcl. 3 GG 9.5-10M cc. n e. n t .7
Attachment 1 ST-llL-AE 1511 F ile Lo . - C9.17 Page udM of 107
)
Question Section Paqe
- 9. E.1 4.2-38 (III.F 4.1-10)
Identify any safety related areas which do not have detection and explain. Resolution: See the markup of Section E.1 on page 4.2-38 attached. i l l l l P Ll/NRC/H
Attechment 1 ST-HL-AE-1511 File No,* C9.17 Page @ of b l l Question Section Pace
- 10. E.1 4.2-38 l Identify the deviations from NFPA 72D by enveloping the distance and providing justification.
Resolution: 1 See markup of Sectionn E.1 on page 4.2-38 attached. I l l l 4 J a 1 l 1 l l i . Ll/NRC/H I
l ^ 9 4.2 CosePARISON TO APPENDIX A OF APCSS g,$.{ APPLMDIX A OP APCSS 9.5-1 STP l'OS I TIOM E. Fire Detection and Suppression E. Fire Detection and Suppression Fare Detectenn E.I. E.I. F a.re Detection (l,LA ?c./ !?it'AY b ([, g 9tg - e E.l.a. Fire detection systres should as e einimue E.l.a. Detection systems are provided for aressfdhat comply with MFPA 720. " Standard for the contain or present a fire esposure to safe lastallation. Maintenance and llee of shutdown systree, " r 8 Proprietary Protectave Signaling Systees." r*44 W --
! ' - '-- = = r - . 7- -i ec--- A - en radiarann le.sals 2 yadJ14al,gon f igur a tigvL(e .t. . ng.Isenbustiblee-pes eece h These detection systems comply with the requirceente se defined in NFPA 720-1975 escept for the interconnection wiring between
! f the local fire panel and the t ranseat ter whach n i tranoeito the esgnale to the control rous
, panel. This is not considered significant eince the fire panel and t ranseit ty ange 1_ z atty [.~ - - -,r sfg y ',,q located 6 other, anterconnect ion wiring , se run an eteel conduat. and the carcuate are $ . supervised. The fare detectore are heang N y eclected and will be located in accordance with NFFA 72-E, 1918.
l I2 u j g E.I.b. Fire detection systeme should give audible and = I:.l.b. Fire alare belle and system trouble alare horns C ' visual alario and annunc ast ion in the cont rol , provide audible alarme at the local cont rol room. l.ocal audible alarme should also sound c,g g ,, , 7 at the location of the fare. { panele that provide the fire protection systes y,, control for each fire hazard. These loc a l (
- l control panete are norieally located an t he #'
vacinit y of the f are hasards that they protect. Fare protection alarme are annunciated in the cont rol room, displayed q .,, m y visually by cathode ray tut,*, anJ rec orded en r ea rt automatically by printer to provsde a permanent $ e $: en record.
- -* nr Z=
E.l.c. Fire alares shoulJ be distanctive and unique. E.I.c. Fare Alares are dist inctave an.f unsque fro" O>H They should not be capable of beang conlueed other alares. O '. t'8 $
. e with any other plant sy st em ala res. m H et '
y g"g g e B y l Zn So m e A lt f e s s o p: THr P t. A ** Y , O Tf c-.ro ns
- o. \ s L~' F er nooT s ** 3 7
- L L E D DOC To T4r Pers e g-OW Ni& M R A C o A T IO N L OC 4 6"L s sw ,g n g y, yg .
5
~ L'M P/ N G s,Cre. THe.s e. A t EAs CAW B E. c t. G a -
t
^'n e c , ~ re ) ?. ~ m m e , n , r g e. c, e ., o r s uo .rece Buu s r-a g .wo.m ' .v. .w: +n- -u. .m Y \ r5 nc. san.4.<e? ry -1.r.c ss u: nen AC : *?-WN ';
1 Attech:nnt 1
, , , . ST-HL-AE-1511 File No.. C9.17 Page@ of $7 1
G R.O t)P P L A U T~ A rt E A B Asis R E A c.r o c L o ts c orr s us ris t s L o A o t ~' q l c o a r s , st a t t* M T / */ ^*
- W H e de T e L C D h CG A0.
( ! JN E T ri* r nova m e
<. o . rn m c r r u <. t r.u on )
Fugu H A oJ O L t +2 4 H t q n e. A c a A s so so 4.f 0f s s L o s~' to *s 6 0 s T o e r e Le A D t at, GL oq - c A su. Deeen ALre r s ~ ~. Aesa no s A e s a. r o o ,a e n o,e n e e M acu A wic eL A UKIL/ A L Y ,, g4ggg O Q L OQ ~ s!A LVE too No sTA *'*L Low c osteos ys BLf Lo A O oN& S g ec r, s , , - . rh n f r.' ~ *:& in's.to s v' L.o!. s M A L ~'Y' ' Y S ' M tcH AM8c4L AUXs44RY 4 a.o w c ors eo1T s 0 Lt Len o sn s s BLoq - PI P6 cHASGo o Lors orto soJt L G f o r. V G a rst.A rs* H PLKnores Z 4 **ITICO 5" T E N D o st Gy A; L E R IGb L o rs t T G O S O U L C C FD R-L 4 ar Tso n b o & Tr e.rn e at f P E C 3 0P=/ A> E C A t re. t o c.k h 4 m, e. 4 4 a v 4 L.co x A ct:TA c s =) T'
= e 4.c '*w coH oosis a L E L
- A e r ou d, 7 s i ^ n c. w e t t s No .sAr-E $ nar cesaat E M Ja!
L , , ,, , , , , , ,, , ,_ g ( ,, ,,, c Tk E c. r' rt 0 0 3 TI D L C Lo n C oN 4 / AJ THcsc A t g As c c W L ES fo ss e To A roe e o u t. a s t e st of tcss THAN c as~. H a s.* r,'a no x .
AHachment ST-HL-RE-1511 c' N Of ICE Question Section Page
- 11. E.2.e 4.2 41 Explain the largest flow demand which was used in verifying the 2 Hour Fire Water Tank Capacity. ..
Resolution: See markup of S2ction III. A on page 4.1-7 attached. a 1 i l l l Ll/NRC/H
- _ _ _ _ ,.~, ._--_m _.__ __. _ , _ . _ . _ , . _ . - _ _ ,____.___.,___,_,..___m -
4.1 COMPARISON OF STP IfMITS WITH RE@lREMENTS OF ArrgNDig R APPFNDIX R RtJtilPf Mt Ng STP POSITION a lit. SPECIFIC REQUIRPMtNTS fil. SPECIFIC REQUIREMENTS lit.A. Water supplics for fire suppression systeme. III.A. Two separate dedicated water supplice Two separate water supplies shall be provided c.ines ot ing of two tenh o of appros smately 2 to furnisti necessary water volume end pressure 270.000 gallone each for fire protection water to the fire main loop, are installed. The tanks are interconnected so that the fire pumps can take suction frne either Each supply shall consist of a storage tank. or both tenho. A failure of one supply will pump. paping, and appropriate isolation and not result in a failure of the other supply. 2 cont rol valves. Two separate redundant suctions in one or more intake structures from a large body of water (river. take. etc.) will sat s sly the requirement for two separated water storage tanks. These supplies shall be separated so that a failure of one supply will not result in a f ailure of the other supply. y, b = Each supply of the fire water Jistribution The fire water supply is calculated on tp*e t Y system shall be capable of providing for a basis of the largest espected flow rate,e[ a g period of two hours for safety related areas or ;c M period of 2 hours the manimum espected water demands as determined by the fire hasarJe other areas that present a fire esposure hazard analysis for safety related areas or other tosafety-relatedareas.fThe fare water supply areas that psesent a fire esposure hasard to is capable of delivering this design dreand safety-related areas. over the longest route the water supply system. The fire water supply erstem include, When storage tanks are used for combined an underground yard fi e main loop of service-water / fire-water uses the minimum cement-linedductilepronpipe. The water l2 volume for fire uses shall be ensured by means supply (Fresh Water ystem) is capable of of dedicated tanks or by so** physical means refilling either ta in less than 8 hours. N **f en > such as a vert ical standpipe for other water - 2, j[eeday $ n servsce. Administ rat ive cont rols, including locke for tank outlet valves, are unacceptable 7, 5* h as the only means to ensure manieue water ,/, ,,fg g pq g ,g o ;
/ :s voluec. y'/c /aj f o .. .* [, Wo wJ ,* ab*;<Jf Wet .)
- b* * *'l #
'V s: ~ ~y n ~ q
} g,s e :/e e - ~ . y~i f* - , n . , :~. ,, s es:a, ./ na l A *N *E " *n # I cu do.es es sr, s g 7 ff jd Ne s e 4 5 4Q
- f f' Y ' )
*he,.q, ym # w* @ re **=w *M tp-me
- W h g ,pgwg g 9,p _.
^ \
Attachment 1 ST-HL- AE- 1511 File No.: C9.17 Page M of JC,7 Question Section Page f
- 12. E.3.b 4.2-43 Identify the unsupervised valves and the provisions for ensuring water flow.
Resolution: See the markup of Section E.3.b on page 4.2-43 attached.
/ ~ \
l l Ll/tRC/H i
e e-~ *~ o g 4.2 CDMPAa lSON TO APPENDIX A OF AP'.tB 9.5-l APPENDIX A OF APCSs 9.5-l STP POSITION E.3. Water Sprinklere and Mose Standpipe Systems E.J. Water Sprinklere and Mose Standpipe Systems
- E. 3.e. Each automatic sprinkler system and manual hose E.3.e. STP complies. Each automatic errinkler syntes l1 station standpipe should have se independent and hope station standpipe systee in connection to the plent underground water safety-related buildings is eit her connected esin. Meadere fed f roe each end are pe rmit ted independently to the plant unde rgs ound wa t e r inside buildings to supply multiple sprinkler esin or connected to a header within the and standpipe systees. When provided, s uc h building. If such a header is used, two widely headers are considered an estension of the yard separated connections will be provided between main system. The header arrangement ohnuld be the header and the underground main. Adequate such that no single f ailure can impair both t he isolating valves are provided in the main, t he primary and backup fire protection systree. header, and in each system to ensure that no single f ailure could impair both t he primary <
Each sprinkler and standpipe system should be and beckup fire protection systees. Isolating equipped with 056Y (out side screw and yoke) wolves installed underground are of the poet gate valve, or other approved shut of f velve, indicator type; isolating valves installed y, and water flow alare. Sa f e t y-re la t ed equi peent above ground are of the 05&T type. Autnestic '4
- c. that does not itself require sprinkler water oprinkler systees ar; equipped with water flow '
,, fire protection, but is subject to unacceptable alarme. The effect of sprinkler water ]@
s dosage if wetted by sprinkler water discharge, discharge is evaluated as part of the systems >= f) should be protected by water shields or interact ion evaluation. Protection " baffles, requiremente, if any, are noted in STP FSAR Section 3.b. E.3.b. All valves in the f are water systeme should be E. 3 b. ves in the fire protection system whose electrically supe rvised. The electrical improp ooitioning could ef fect the supervision signal should indicate in t he pe r f o rmanc e t he syst em a re superw' . This cont rol room and other appropriate command supervision is ac liehed ei by t emper locatione in the plant (See M/PA 26 evitches which are inet on the valves and ao m1 ut >>
" Supe rvis ion of Valwe e."). which prownde ele n the ce room i f t h, a >= wi re valve posit' s changed, or by lac he $ $f $. m valwee ' he required position and providens 7, (* fr er administ rative cont rols. o>a - P1 m z.
5EE AT TA cHED SHEET R " ; ?, v. e O Pd >* m
<> e.
e ~a q m I 3 re 9"8
i i 4 ! Attechment 1 l ST HL-AE-1511 File No.: C9.17 Paged of [Q2 E,3. b Tls E VA LV E S t ot 'THC FtLE PROT E C.T IO N 31S TC r's WHOSE !!!!k.0 f G L Pos ovie nt e se q couLD AFFdLT THE PERfor.rtA"CE Os: 7HE s ysTEM ate E o7Hs e. s o n* a. c.4r s s b OL H Av2C THEoK fos tT** VC L!flE o BY PLocuo0LC ta A c c c a. D A n c L sas s T tf TE c.H"* L A L. S P EC I FI C A f to n' 5.
'IH E V A L.v E S " TH E Fot E e* LOTE.eT!*N sys1GH sv H ic H E M S W R-6 TH E A V A L. t A B IL* T Y OF w ATG R P ot o M THC FIA E us A T a st. 5 70L Aq E ' tom THC Loots T A *a n S To THE UHortl0NoT3. F ! *' d Looto h 'O TO 7n6 H G A C E nt $ /NS IDG TH E $ IT E ST R. ucTu t G 3 A L. E s o ! ! R Vist D i.e. TH s v Pro v o c C A L A K r13 AT s.o C A L P A ~ S L. S A *> o ON A CouT80L L eo n e t,. T w H s si Har on T H s t e. NO R ot A L A Le G N iv F NT. Sots E EyAM9LES of s o ps xVe sE O V A LUG b IMCLeoE T A *' N t s o L A T!*H W A L U G o, F IL f PunP S J c.r oo d A ** o D r.s CH A L % G V A L V K s , O UIL D s t* Q HE Aoyt 1 se L A Troot V A L V E 5, A sa t) a f Et a n. L C. L o A* 05 L o f, C 3 0 P!L1 V A Lv s, s . su a no .s OPE c.us s E O V A LU E b c c oo s e 27 o e V A LV s .L s.1 : TH LOCAL /H c s c A 7go Ar, s. . e. fa s T /H e t -
C.A TI N Q , A ss O 'TH os C sar o rho u 1* A mo v os A G c.T s'f C A A) S eF P e 5 t To o ^t I N o I L A T *o n'. TH E L A*TTE L q at.o v P of er A Lv 6. 5 c o no s e s r s og VALVES S V c. H As CHacn V A s v E.s Ado Alt lE F V f.LVE s LJ H o c.M ALE c o a i st.o L L 6 0 QY THE O Q U o l T*o o d of TH E p~ o t, G PAersertow nao s y s T E ei p VEur Aoo O F A I A> V A c.vE S o ut. f a s 7 4.v er e N T A co7- VALVE 5 LUNosE P o s To o wa A v. C c ouT n.o L L E. D By T H E. f tK E PROTECT /o^t s't sTE t.s O PE.L A T!*s Q P Lo c s o ur c . THE' Po s o rt ed of VAL.VCs ta I T H LaLAL /N OfC.A Y to d, 5 t) C H AS THE tt A 'N FoL K Loo! s 5 c. 7*o !. Z~ sol A Yeo u v As. v os. s ,
>% st O s upp g yts f C VALv65 !$ V E r?.s F t5 0 B V P M. e L E D o tt E s ai Ar a c os O A ssc E v ITH 7EcfArteAL s P e c t F l e A T oo n's, s =
T H F._ tvoa Nore_A#o^14 v a s. V e s s onteH A e. s nerscenCotw PlacZ HAVE GEr a E JALu A T to A *' o Tu lo s, g e_ po st ria o s aq y, g g. c g, o y Appge7 THE PLo es R. O P s t. A Y o
- d o s= Tuc te it. c pit.o TE. t 're * ** $1 s TE Pt.
Vil c y'L3 tt t' &W /ML. Elc (.7&(,.ALz y % t c); V '.s ( Nc.* Sio ?I Ch %C eML l'A n u n W N Z*d '1. ,a .mcTud
.- C5 [kf: /^ )k{,
i l I l
Attachment 1 ST HL AE 1511 File No.- C9.17 Page $ of lO7 Question Section Page
- 13. E.3.c 4.2-t.4, 44n Explain variances from NFPA 13.
Resolution: See markup of Section E.3.c on page 4.2-44a attached. I l l l l l l LlhEC/H _ . _ . . ._ _ _ _ _ _ _ _ = _ _ _ _ . _ . _ . . _
1 STP filar Attechm:nt 1 l ST-llL AE-1511 File No.. C9.17 N Page $ of [C 7 hD 73 DC
.;: .; 5 I I *: TF e:
- .5 2Q 2%
hkh (g{ 2; :== .. : V
- ]
- t2*_
o
- ef - .5 :
-: _1: =~. *:5 i t. 8 , y ey g b,- -o *t 5,5 3: .
i V
= ;d *;*#,:t! -\* :" ' $t T
s e
- e t--
;o: - =-
3- Nr - e o { s: :. : = .: 8,: *
# ". a 0 0 b*
o": "t*5- : * ", Q
- :: :: ':. t v: g r.: .s : :
- Ql2 g 0.n k
2 e
= .a e2 ::::
r= I! 3e
.s t: _
et" i"72 '4 4 " : ( ': : 8
,3.2d :i e.
V
= ,3 1 V
e%'g - E 4 oij f 0": Atta a4dg h' q M g, 7 fC. }tu ' m se g Q o eh
~
I 0 - If a o e 4 . s a
.: k N E d WN h -
U w p .h v . R s e 4 b $ N h b hqY Dh ) bM* \
> m w cy >
w $w E 9m ' $es P- 3 . 5@ d4N k, 9 J N N 4 R a u 3dD b 'R m N @ \ g s N9 L 'e . g
?
h' b b S S q% c 1 r4 1 f* 3Vy06 h i t ? O >d a t i 3 .:) n M i i w v hu I
! , <3# a t es Gik(w ny h$w g.:%e'oa 2
5$te$gjbs %3 13 s a*$,8%#34"
- u. s v m:. gW s s
r 13< s 4# s,*e,am.!!o- e _s 3b Rt oe
,4 m ,m 1 *< 51 i 4 .T Ul 9 % lM tdn%sb<T ~ %9 $ 5w W d 9 s +
VI \o h
' 'R I) vj ~
d it a d
$ C1 k yk '$ k 9 DW 't k' (s s
T
l ST HL AE 1511 i File No. C9.17 ) l Page $ of [Q2 j i l I Questi e Section Page , 14 E.3.d. 4.2.-45 j Explain whether or not the noncollapsible hoses are rated. 1 i l Resolution: i i I j See the markup of Section E.3.d on page 4.2-45 attached. l i l
\
i I ' l l l
\
l i l \
! l t
t .I l I ,1 I i i }
\
l l i Ll/NRC/H 1 1 l
-ww- ,,- e-ero-r w m- . m em m-- ww <
I l i l I t 4.2 cO*IP A R I SON TO APFfMutt A OF APCSS 9.5-l APPEROt t 4 OF APCS B 9.S-1 STP P058T1088 Interior eenwel hose installation should be E.1.d. The standpipe systems are described in the FNaa E.3.d. oble to reach any locatson with et least one compar e sose to Append t e R. Sec t ion Ill.D. e f f ect ive hose st rese. To accomplish this, etendpipes wath hose connectione, equipped with Mose lengthe are 75 feet i.here feasible, but a maeseum of 75 f eet of I-l/2-anch woven hose lengths of 100 feet are utilised as , jacket-laned fire hose and suitable nosslee required and se permitted by NFPA 14 1976 should be provided an all buildings, incloding Edetson. 1-1/2 in. woven jachet-lined fare containment on all floore and should be spaced hoses and evitable nossles installed on et not more then 100-foot intervale. ecoisotomatic reche in hose cabinet e are weed Indivadwat standpipes should be of et least where fesemble. Branded, noncellapssble hosee 2 instelled on hose reele are used wherever the n 4-incte diameter for multiple hose connectaone end 2-1/2-inch diameter f or eingle hose ability to have a hose streme immediately connections. These systems should f ollow the available, without having to unrect a complete i length of hose, would be advantageous. I requirements of feFPA 14. " Standpipe and Mose Indawsdeel essadpipes are minieue 4 in. in Systeme** for sising, spacing and pipe empport diameter for euttiple fire hose connections and f requirements. 2-1/2 in. in disecter for eingle fire hose eonnectiee, y t.
- Mose statione should be located outside Each standpipe is provided with a shut-of f :
u [ entrances to norestly unoccupied areas and valve. Each firt hose teet or cabinet is j I 2 5
- n inside norestly occupied areas. Standpipes prownded with a dual function ehet-off-l vi serving hose statione in areas housing pressure reducing devices, as req ired. /
eafety-related equiPeent should have shut off l l valves and pressere reJweing devices (if l epplicable) outsade the area. _m l yu:~
.4 ,1 et E- ~
(Ng me , 4- f g
- y.
i
. .*' T F *' %d D/1R C fA. Rat eo 3 h 4 ##~ =3 %D' 3- *G 1 5 s 3 !
cs S 4 il ce e4 e
- Attachment 1s ST IIL-AE-1511 File No. C9.17 Page $l of JN Question Section Page -
i
- 15. F.2 4.2-55 l l
l Provide more information on the cable tray; above suspended ceiling in control room. I Resolution: 1 See the urken of Section F.2 on page 4.2-55 attached. l i l i
}
i e 1 l l l l l Ll/NRC/H
4.2 CtMPARISON TO APPEftDIE A OP APCSS 9.5-3 APPEffDIN A OP APCSS 9.5-1 STP POSITION P.2. Cont rol Woom (Cont 'd) P.7. Control Woom (Cont'd) e The control rocie wentilation intste should he The HVAC system return ducts f rom the cent sol provided with esote detect ion capabilit y to room contain smoke detectors which actuate en automatically alare loc a l l y and isolate the eterm in the control room, llpon receiving this cont rol room vent ilation evette to protect alarm t he operator can remote-manually close operatore by preventing esche from entering the the return deepero f rom the cont rol room and cont rol ro<um. Manually operated wenting of th- divert t he eeone to t he outdoor e. This ellowe control room should be available so that the HVAC System to be put into the smoke purge operators have the option of venting for mode. visibility. Cables should net be located in concealed floor The STP control room has a partial suspended and ceiling spaces. All cables that enter the ceiling with cabling above it. Cabling which enters the cont rol f orse t erminates there, control room should t e manate in the cont rol roce. That is, no cabling should he stoply &mel ! ---- t
- 48 M W i-- M e - :--.:-- g routed t hrough the cont rol room from one area ., 44 **t eee eewt e4-4 heewah t he-e : r e a N
-' N .c -? 4 i!in..-
[ to another. M ms A fised' autsaatic total flooding Halon h if such concealed spaces are used, however, thev should have fieed autrusatic total flooding protection is not provided for cables in this e Halon protection. eres. g e ~~--~ . 1 THL r*J Ssl'u con B osTICLE 4.O n O/Asq jou 7Hg A t. G A EJef e EE LY
\ A6OV G THE 3 0.5 P E ** O E O C C 18., oM, c o ** $ os Ys , o F LEEE 3.33 c a e L E s . TH C' C A M g .s A t G, R 00 7K. D 1&
TRAvs o t. Coa ouoT taHo cH si t S E. V K. t T s c A L. t.Y l ' o u r o p- Tsoc c
- B o aE T s c.o c. n r e o 8 g ro w rug !
c E o L e s' q . T H E TRA15 G r M E e f-O AI Toou o K T o Liff *)' G { UV6~Tecessev YM A:c o c yot 7" ' ^LE" *L ' " *
- 5YS r- "
l* e s A"D E c e 1" TH Lo u c, or Tur s s o n sa a ers . E a At o 0%E J tg es AEE { , TC.Avs - 3 y 4 c g. g o AsoVE E t e ser o TMK t. C ;3 1 } 3 w '!L A T'* " D E TEc.T o t e, A t. sE" Ptods O K O en rue so**c9-L i A 604 E THE c v 'L '*' Gr 70 P LOV* 0 G E A t L1 aa n w but,*oT A I - r F r l E. A s f e s **
- C c A T w s t.ec H A .$ RK f** PLovs 0K o A rg e G
~~n ~, l T H ai C.Faraaoq To Ea$ un E HOS E S T R.C A er A C C Es$ 1-aus ory r o e er n ava t s urpr e ssicas, pou r u.se s rs ra,as At s ,
- t. o e a rf- o ao iMr A e2se e arP re st i e sa e a a s r e.ow> e co oc e ,t e, g w,w m,,,, , ,,, ,,,,g_ l
,ag gos s s r et A r<. Poe.r A e rE toArre Aass Co a rons nari m amKasae,,, w ,4,, _
j toe s v ro TntsoG orcer 7 Ms* co onal a s ene ro z pp, gros asrs p,at s. p.;qqrf,, q . s,ere t rue Q ;; c o a t a.o r stoo rr os c o a r osov o v es.1 n n =' a's e , THE e t n s ano es as T a n =rsnss*ns
\ e.. ,oe. ...1,e. ,,=.t., ~ ,,e , -.. -l \
s ,, c. , , ,o a , oo e
Attachment L ST-llL- AE-1511 File No.: C9.17 ' Page @ of Q3 , Question Section, Page '
- 16. F.3(b) 4.2-57 l
Explain that cable trays are accessible by hose stream and describe
~
deviations from guidelines that could hamper fire brigade access to cable l spreading rooms. t Resolution: See the markup of Section F.3(b) on page 4.2-57 attached. Ll/tEC/H
D 4.7 COMPARISON TO APPENDIX A OF APCS 8 9.5-1 APPENDIX A OF APCSR 9.5-1 STP POSITION F.3. cable Spreadinr, Room (Cont'd) F.3. Cable Spreading Itoon (Cont'd) It must be noted that STP has a unique design, in that there are three separate independent t raine or pathways to achieve and maintain shutdown. A loss of any one of tiee fleree safe shutdown pathways st ill Itaves the STP cperators two pathways to achieve and maintain shutdown. Also, the cable spreading room / power I, cable vault for each train is physically separated f rom the other trains by a fire barrier with a 3-hour fire resistive rating. Each cable spreading room and power cable vault is segregat ed by saf e-shutdown t rain ( A, 8 or C) and is separated f rom the redundant rooms by 3-hour rated fire barriers. Each cable spreading room is separated f rom the adjacent $ p fire areas by 3-hour rated fire barriers. 2 .a
. Smoke and hot gas removal will be accomplished ,
y primarily by temporary flesible ducts and y u (a) At least two remote and separate ent rances portable fans. (See D.4.g.). po are provided to the room for access by fire brigade personnel; and (a) Two remote and separate entrances are provided to the cable spreading rooms and (b) Aisle separation provided between tray power cable vault. g stacks should be at least three feet wide and eight feet high. (b) Ved : ::: f :c ' . ; ,.. J. ,m y ==e i--- mi-a. ui i L i-M e .p.e.eing .m-, .. ; . 4 O i s; " . .Mi e;;;;. J E u^iit u s t ourang a 45 - ., -.
-... autoestic wet N
pipe sprinkler protection is provided at .-
.~.--- the ceiling level to cont rol a fire and 1 2 NA ' ' ~ ~
[ / /c roo m 4, c uceu./ c \ N hour fire barriers of each cable spreading room will contain a fire. bOrqh3 a ( lN n {ll, ,, ., g ,,a r;..
*ne "/ can ,,,;s:a i. . .
h se- \ . ~ w-a ' i- ca c l'l h , / /cs s /
- g. 1
g ,,,}. co f;pr J .* I" / a tr of ~
a ko w e " O g * '" a le m...a/ N M c' s de r*
- b" /* I/ ,, <./ Ja..ws ,, e gyq;esh. 1*/e efore '
PA f"( O f~n .y og e tJJ o'** f /~kett r4 N ..
&;n . igg _ sp.A $ ~a -
7
Attcchm:nt 1 T ST-HL- AE- 1 $ 11 File No.: C9.17 Fage @ of M Question Section Page
- 17. F.5 4.2-60 -
Justify lack of 3 hour separation for switchgear rooms. Resolution: See markup of Section F.5 on page 4.2-60 attached. 4 I i Ll/NRC/H
o 4.2 COMPARISON TO APPfMDIX A OF APCSB 9.5-1 APPENDIX A OF APCS 5 9.5-1 STP POSITION F.S. Switchgear Entwee r.S. Switchrcer Bone gedundant safe shutdown paths will be free from The ESF evitchaear roome each contain one t rain fire damage to achieve and maintain shutdown. of saf et y-related equipment and a re sepa rated f rom each other by floors and ceilings which A fire area or zone boundary will contain a are 3-hour-rated fire barriers. This provides [ postulated fire and allow time for the control two redundant esfe shutdown trains to scheiv e or extinguisbeer.t of this fire before it can and maintain shutonwn in the event of a fire in reasonably by espected to propagate out of the the switchgear room which disables one train of sone or area. safety-related equipment. Switchgear rooms should be separated f rom the Heavy concrete alls with 1 our rated f remainder of t he plant by minimus 3-hour rated doors and u rotected ca e and HvAc fire barriere to the entent practicable. ' penetrat
- e, separat dese fire a es from Automatic fire detection should alare and i
/ other -re sones vi in the ease Thee fire sone b ndaries pro de subet re a rea.
annunciate in the control room and alere ial 2 locally. Fire hose stations anJ portable ob ruct ions w 'ch will Inhi t z on e- r_ zone y entenguishers should be readily available. a re propsgar on. /This f aci t at ates cont ainang to N p and suppressing fires within each switchgear .g
- Acceptable protection for cables that pass room using manual firefighting capabilities and Y thro sgh the switchgear room is automatic water significantly reduces the probability of a fire
$ or gas agent suppression. Such automatic spreading throughout the entire fire area, suppression must consider prevent eng unacceptable damage to electrical equipment and lonization detectore are provided which alarm possible necessary containment of agent at the local panel and in the cont rol room, following discharge. Stanual hose stations and portable fire estinguishere are available outside the room. I The equipment is on f.-inch pade and drains are located in the corridors directly outside the room.
M 3 C'\ -t c2 1 ,* [ - m.- G'
" hD}n a @@$:> " ~-
O M
Att:chmint 1 . ST-HL- AE-1511 ; File No.: C9.17 t/Mg@g d3 q Page@ of (Q3 3 Msser now waere aus wie z soa orre na +ss Aes amracrey mece swa av4c saenr<>ss, sesenre fasse nee edes riam ornee na sawes wirwd iwe SAMG FtA6 4CG% kLL RMAGb7ETCYeb DAWM45 428
/{6et6 W i n .40 Id6 7 E xce s) 4 /Y2/ id stzc Avz A4%~C.
4hC7 4t0 h')(C /d S/2E fin ELEL72/ CAL 724y', Add ACE 2916iLY /[ct6S318LE 7'b Ad 67F6CY/f6 s9s6 s;1264r11 a 4"iasnetas aenres Ame -rgtse omvwts as t.uiria,2 TD /EEE- M B CAdud4 rd fs4Ys IVHfc4 Act dor ssw sec77W f.3,z) gr;b 44c cefsda'sa Atsb /'ccessi&E t &cedrnq7c4
-rb [KFrca;vs m4diun igac srxsaixs m
l l i I l
. = . - . . . . , . - - . - - - _ .AttOcha:nt 1_
, ST-HL- AE- 1511 ' File No.: C9.17 Page $ of JO 2 Question Section Page-
- 18. F.7 4.2-62 Justify lack of 3 hour separation for station battery rooms.
Resolution: See the markup of Section F.7 on page 4.2-62 attached. [ u o i 1 Ll/NRC/H
l ( l J 4.7 COMPARISON TO APPENDIX A OF APCSS 9.$.1 APPENDtX A OP APCSS 9.5-1 STP POSITION F.7. Station Battery mones F.7. Station Battery Rooms Battery rooms should be protected against fire The battery rooms each containing one train of esplosions. Battery rooms should be separated safety related equipment are separated from f roe each other and other areas of the plant by, each other by floors and ceilings which are I barriers having a minieue fire rating of 3-hour rated fire barriers. This provides two 3-hours inclusive of all penetrations and redundant safe shardown trains to achieve and openings. (See NFPA 69, ** Standard on Esplosion maintain shutdown in the event of a fire in the Prevention Systems.") Ventilation systems in battery room which disables one train of the bettery rooma should be capable of safety related equipment. esintaining the hydrogen concentration well below 2 vol. I hydrogen concentration. y concre walls witK 3 hour r d fire Standpipe and hose and portable estinguishers doors and protecte able and AC l should be provided. penetrat' ns, separ e these f* e sones oo
,, other te zones athin the ame fire es.
Alt e rna t ives: / Thesj ire sone oundaries rovide o stantia ob uctions ach will hibit to -to tone 2 [( re propsg son._fThas sacalitates containing (a) Provide a total fire rated barrier - to p enclosure of the battery rooe coeples that and suppressing fires within each battery room 'o
. esceeds the fire load contained in the using eenval firefighting capabilities and y rooe. significantly reduces the probability of a fire m spreading throughout the entire fire area. f ;o (b) Reduce the fire load to be within the fire barrier capability of I-1/2 hours. DC switchgear, battery chargers, and inverters are not located in these rooms. Fire detection Og systems which alare and annunciate in the control room and locally are provideJ. g (c) Provide a remote manual actuated sprinkler Ventilation systems will limit the My systee in each room and provide the concentration well below 21 by volume. Loss of I-1/2-hour fire barrier separation. ventilation will alare in the control room. 'ts 'es en >
Standpipes and portable estingieishers are provided outside the rooe.
$$YN * * :C sa @ 2t t< n e :f I 0 0 > El + (1 19 0 .. e 3 m M rt U9 OYY wW $ ~
n D n. D so D re PJ
Att: chm:nt i ST-HL-AE-1511 , i File No.: C9.17 Page $ of M 7 F7 prnM B4mv Ezns
/dsexr Heavy caca<e wes wrx aisa ara na sus stad Mossrarea cges Ms /ft9tc sextranxs se/Amts-rtie s E fr M E O 16 5 FrMm 07%'?z ft/d6 ECWe5 Nt14/4 Yd6' S
4011M11a rEE) x9 cA uL rjA g e 7] , ACL MAe016C7221 D/64/AWS AM /det&Wft.'C, 3' X 2 ' /d stEc M /.V4C - duc7 Me b'K4' A sise tse. Elecrocdc ce44mr And gar xetdity /kcessete 70 4 efecra's sese .c'rretal. Af.L ANEYM71MS /irlE PAWided 41/7t+ die - 7t4t+r s&v1cc MWC4 Pu//f&T MYdebde/ /H/def1/04 077 QF -rdt Ebbnp. GT"t64s1/865 L d CA fe d N W i k 1 8 6 5 6~ DA91ItAUS &W L/mt1Lx] -ta /EG -ST3 I CMS'deXcd 2 Ofdud4 /4 secmmt 1&rtua ( a t -f/4ys /tc/tyc4 3,2 44)/1126~ AOf Cot /Ced 44d ACSb /lcc6ss/8CE 78 EFFEC 7NE dhfMn4c dasc srzcam. . . . 1 J
Attach:sant 1 ST-HL-AE-1511 File No.: C9.17 Page d of ]Q2 Question Section Page
- 19. F.9 4.2-63/64 Verify hose station and portable extinguisher coverage meets the guidelines.
Resolution: See markup of Section F 9 on page 4.2-63 attached. l 1 1 Ll/fEC/H
F 4.2 COMPARISON TO APPENDIX A OF APCSS 9.5-1 APPENDE R A OF APCSB 9.5-1 STP POSITION F. 7. Station Rattery Rooms (Cont'd) F.1. St at ion Bat tery Rimes (Cont'd) A detection-activated fixed Halon suppression l system which may also be manually act svated covers the control room computer battery room. F.8. Turbine 1.ubrication and control Oil Storage F.8. Turhine 1uhrication and Control Oil Storate and Use Areas and Use Areas A blank fire wall having a minieve resistance Turbine lubrication and cont rol oil is stored rating of three hours should separate all areas and handled in separate areas and buildings containing safety related eyetees and equipeent remote froe safety related systees and } from the turbine oil system, equipment. The turbine generator building and ' the IVC which are adjacent to each other are separated by a 3-hour rated barrier. F 9. Diesel Cenerator Areas F.9. Diesel Cenerator Areas tn Diesel generatore should be separated from each STP has three diesel generatore installed in H
.# other and other areas of the plant by fire the diesel generator building of each unit.
N barriere having a minieue fire resistance Each diesel generator is located in an 9 S rating of three hours. individual room and is separated from any Ld adjacent diesel by a reinforced concrete wall. # Automatic fire suppression such as AFFF foam. 24 inches thick, which has more than a 3-hour-or sprinklere should be installed to combat any fire rating. There are no openings or diesel generator or lubricating oil fires. penetrations through these separating walls. } Autoestic fire detection should be provided to Each diesel generator room is provided with a alare and annunciate in the cont rol room and complete automatic preactiJe sprinkler system alare locally. Drainage for fire fighting that is initiated by a fire detection system 2 water and means for local manual venting of within each race. This detection system will yygy seuke should be provided. Provide a local alare and will alare and en m H et
.ennunc i at e in the control room. Adequate drainage for fire-fighting water is provided. $7hE t* r1 Smoke ventilation is provided by portable fans anJ f lexible duct s. Haee stations and portable hhk
_ O . $ estanguishere are readily aweilable outside the H et
~ ]
Y Ph Oc y g ohg \ -Q W m y e (so r o ue i e^s c sos~s n n.enn a ., ns.,a emo e, ecacace 4 a,g. I
~
cu *SY AT L E A S' raf ;crfeywE r. es $ ; 9 g - y p T c r a .y , ;
.=
l Attachment 1 ST-HL-AE-1511 File No.: C9.17 < Page @ of 37., Question Section Page
- 20. F.ll 4.2-67 Fire protection for safety-related pumps. Verify that detection and manual fire fighting equipment are provided.
Resolution: ! I See markup of Section F.ll on page 4.2-67. l 1 l I l l I 1 l l l l l l Ll/fEC/H i 1
'l n . -, .
y ,, -, . , - , . _ . - - , --
STP FilAH Attach:snt 1 ST HL-AE-1511 4 Filo No : C9.17
- Page h of M
.".1 y
%. 'N, \
- i w s I, .
.o. 4 N g 3 e *
\
\, y* s s a. v . s s
f., w.. s 1
< , L V s b =
e 6 y
.:3 2, 5 2 . so %
2s N
- v .
, \ .. v. .e ,e g N , . . .- w ** 1 %% .4= w ..f5. - ,8 N ,. . \ .w s w o.-.- , g *s %
t e ,
- 1 't M q N.;
a = .
- n e.2 2. a" *. ; e . .a s- .
~ * ~ '5 % C s' { '
E *T" \ ~
' \s t . E. .. . 6eav .% vs e s.
F 1, ,=-, 4 w s
.Q , s \
5 l. - c. t I
- o
, ,".1 2. .*= a ,. s.. *t .. v h - 5 .
S
- - s . ec e.
s6 s s A 4 e %. 4
- 5 1 N. s. .t Nys
- 2. *. *. . '. 3 %.,. S y > m.
s 5
.c g
s< 5 *
. [e.s.%. \ 4\(
s
. .I. E ,.\ . M .,. . ., N iT Y h . m .s ,. n.. e.
o m
/ <
. % ~
- E t '.
E e - E , g . n.
. . ,. - T . :o ~ =0 1. :. t ,* . .o. . o. ..e c. ,. ..* e . " "
s .. ,...
. .E...a. .
4 g .g-.. {.ec. ... o s .g
. e .s, , - ~ . ..e E. 8 ,. : ". 21,g .- . ~. o 8 0 w ' " 1 ". ? ". E --, ci~
c
.c c. . .,Oo.c . . a.. . .o I . G- 3 u
E e.
, To.
su 8......-
.,.o c.
o e.
.t * ,2 .-..ca. ...g, .E : ,,8.*** .
T. o........e.. s . at es n. - o ec
. c e C 6..c.
- 3C g w. .-
g a a. . ,.C y6 . .cw CL
.e.r < m . s 5 a s .c6 c. c. a.s 3 e .ov 1 .<. ,
4.2-67 Amendment 1
Attachment 1 ! ST HL-AE-1511 ! File No.: C9.17
. Page $ of lO 3 i
t Question Section Page
- 21. F.14 4.2-69 Provide information on the-separation, ventilation, etc of Radwaste handling area from the balance of the plant.
Resolution: ! See markup of Section F.14 on page 4.2-69 attached, t l l i I
! i ,
t i.
, l
) : i l I I l , l Ll/fRC/H
,,._,,-n. . . , , - - , , - _ - , , . . - - , _ - - . _ --,,y.---, , . , , . .____,._,c-,-.n , . , ,, -..-,_ . , , _ , , - . . , - - . -_,,,.....,_..m__,.mn.,---,,
p *) . e (* . 2 COMPARISON TO APPFN3tg A OF AFC$5 9.5-1 APPENDIX A OF AFC55 9.5-1 STP POSITlow F.I&. Radweste Building F.14 Radweste Building The redweste building should be separated from The radweste handling area is incorporated into other areas of the plant by fire barriers the mechanical sumiliary building, and is having at least 3-hour ratings. Au t os=s t i c sprinklers should be used in all areas where 6 separated f rom other areas by concrete walls, l1 Ljoors,a..Jceilings, cambustible esterials are located. Automatic /7 fire detection should be provided to annunciate g M I In addition, automatic fire detection which and alaria in the cont rol room and alarm alarms in the control room is provided. Manual locally. During a fire, the wentilation hose stations and port able estinguishere systems in these areas should be capeble of (hand-held and large-wheeled)
~ ~ ~ ~ ~
are provided. being isolated. Water should drain to liquid " ~ ~ '~~
. - 3 radweste building sumps. UNb/IC- #M YMVM./.' WJu% MM Acceptable alternattwe fire protectne's is f'$d//$G0 W b W & N t[/1'f / W O d Q automatic fire detection to alarm =? NMb (M M P M N [I/A/MC~ O /~~ 'n
( D annunciate in the control roors, in addition to manual hose stations and portable estinguishers g pgygfg* g gf.g, g/Jgygfgyp'Af ma consisting of hand-held and large-wheeled { SY37Z)efS /h#I COCA 7bd /dl T M /O#d k M $ l- ==ic=- e irmwn ex4. ~
?;
F.15. Deconea.ination Areas F.15. t'ecentamination Areas The decontamination areas should be prete sted The decontesination area at STF. located in the by automatic sprinklers if fleeunable liquids mechanical ausiliary building, is not used for are stored. Automatic fire detectice. should be the storage of flammable liquide. The provided to annunciate and alare in the e Jat rol decontamination fluids which are stored and room and alar,e locally. The ventilation system used in appreciable quantities (50 aallons) are should be capable of beant isolated. local of the water-based evpc and will not present e I hose stations and hand portable eatinguishers fire harard. Pertable f are eatinguishers are .o os en > should be provided as backup to the sprinkler provided within the area, and hose stations are system. Provided adjacent to t he area, $[Y"n e e J: p to a u h. h, g a y- O.- e 3 2 m M rr
~ tn 3 C3 Y w u3 M E od wL To ,. ,,m. ..eee.eo,.,, g. .g* 9'e*e **6*6hW***'""NW
I r- 2 _
$*ii$ldNfr
[NJEg7 File No.: C9.17 Page M of D F ff %n gk the peutvate'o ms wd MVAC ducts Are m.E 5eafed eith 3-hour rated seals omd I d am te rs , -f-/re propa9 ate'o% fyos +Ao u radwaste h a m d ( A p Are a. -t o other arear , w ill b e imhlbited beca nte of *he Ilo wimp r easoms ! The roctwnste. hemdli+g Area. Is eniclosed by 3 - kour *puivalect co+creta wall s Amd rect w/R doort procu. yod as 3- hour rated .fira doo rs , Tke. I (emetrdiom s are fer ply tmg , dacts amd co.n du;{r, W re ar e. mo efec.tn'ca t -ftay gemetra 6'o+5 40 femehvatiom oyen,:vg y e xceed 3'x\Y1 ( da c.t) im i 53e A4 d Are loc n ted so 4.s mf to prov,de q ' d u'Y *. CY fath for -[ lame -Syre ad beyowl +. h c YScitonste k m d[img syg g. . (MfS P9CEhc. case 4)l]Chc Q 3 ' x I '/2 ' d a c.t peee tro E(om e s is t < com bu stibler are located CMly OM eMe $ide A4d Are A pf'r o y i A4 ttI.e lp to {t {ro4w Of pem.vEkAkO& opethim g. ,
Attcchment 1 - ST-i!L-AE-1511 , Til C9.1 1 Pag Oh b l kf I ._IDE t
+
a sol,'d,'4,' ca t<'em a A, ch. pre sets a age +t ,
.. i.e yte l od. Excegt -{ct d<f u a5% i m
- S't
.. cow buctr' blas yg4 this aven are otit y a c{r ca.dhe.
I~ +n e v< mt dapre, & e ff s:t e velea s
, , ;, g, a A,,,, vfic/ . H*
- l'*A f.'* * */ **5*
s a. es:de /f * = ' y r*v'
** *"' W 'N { ,, g. .,, g i. of , ;,;~ap / rJy &c 8," Q ?,
g dei e o s' i~ Q
,,,,;,,, ga r., a ee.s *Q%~
e,,, .s e .r e(< g - r < Af*/ ey y eat- % y Z fee f.9 w e +'. / - /. u ' o . . .
Attachr nt 1 ST-HL.AE-1511 It $1 1 Me1;o. : Q9r47 (d' .. Od
\Ed. .dA .' I d,de j$ofj_@ A, a .,
- gn ;, 5
,% I I .+.J "'.5 W-33 I L. ,...p . j 4 m 30 t I I I I
- s
- .k 3 hU wZ *\
55
. s . , t 3* g" . . A } - ._3 . . I_ D I . ) ,
I I I I O )
-.. w : m . ,f 0
f - -.o.,-
% ea CNaceSolGN'i O& l ~,
RS
- 1 IIe er i g .s .i O 11l.
*=8 fj {-)
s J!
*l c} 00 y, ,
if,3 i ' i Y I ' I l 'r j 3- it ts 11 I
,, [l , - . !5, e- .Y C w D ' ,1 c...7....a-, - .;
c g;'l =l l
!l I;.,....,;-
1 I ,-
=: -
i >- ;@.: , e 11 m .
'a )..i' i - , - a u s, ( t 3 i
- L9'M lE a t i J .t . at .y Dc8 ;
i % . g t* i i :. I { 1 _ y
',.... r-'---p? e ** D g 0 'M I l !~ ' j.~, 's i ~ ,
e M.: . --;-I
- ;g. i o x ) .: .- I g i 58 )# $
i a i k s l e 1 1 1 1 1
#e
Attachment 1 GT-HL- AE-1511 File No.: C9.17 Page @ of @ $ Question Section Pa
- 2. 111.0 T.le 1-9 Explain "Where a power block area can not be reached with an effective hose stream... additional spr,cial hazard automatic suppression has been provided."
Resolutlon: See markup of Sectior, III.D on page 4.1-9 attached, i 1 Ll/NRC/H
, % / ~
4.1 COMPARISON OP 5TP UNITS WITil REQUIREMENTS OF ApFENDIX R APPE*tDf t R SEQtitREMENTS STP POSITION Ill.D. Manual fire suppression. Standpipe and hose Ill.D. STPisprovidedvphadequatestandpipesystems systems shall be installed so that at least one that will permit parta of the power block 2 ef fective hose etream will be able to reach any containing sa fe , shutdown components to be locat ion that contains or present e an exposure reached by at least one effective hoes fire hasard to structures, systene, or stream. 4 'a:.; ; p:_;- $!;;i e.ce ;;n -:t S: componente important.to safety. rm nep wiin .n vii m iv. Lv.- 3. 4 2 f!.p::n:.2.:;, 7 :-e;.....un uf y i....:
;;:i:1 7.
ry a ; m. n.. .m.. Access to permit effective functioning of the l2 fire brigade shall be provided to all arese All standpipe systees installed at STP conform that contain or present an esposure fire hazard to NFPA 14, 1976 Edition for sizing, spacing, to structures, systems, or component e important and pipe support requiremente. More - restrictive seismic Category 11/1 supports are 2 to safety. I provided where required. The locations of the hose stations are selected to provide optieue Standpipe and hose stations shall be inside rvR accessibility and fire-fighting capability, m
*i 8' cont ainmente and BWR containmente that are not The containment le provided with a sinele water
[2 inserted. Standpipe anJ hose statione inside 8 containment may be connected to a high quality supply line for the hose stations sad fined d water supply of sufficient quantity and suppression systema extended from the fire main l7 pressure other than the fire esin loop if loop. The ccentainment standpipe le normally l plant-specific features prevent entending the dry. fire sein supply inside containment. For But d rywe l l e , standpipe and hose statione shall be
-- "'~~ ~~~----__.N placed outside the dry well with adequate //,w a rer #* -\
lengths of hose to reach any location inside j .,
,/ ,[l % p g ,, , N the dry well with an ef fective hose stress. ce,, [.'r a ** * ," " #, */ ,
p f, f.'c e / 4'errit*/ /a 'sra de A*
- J"y/* !*U* *
- f1yR g 4%,. o .ra,,, e w/a / e-e /Wfe-/[ a s s'em en Q G j w p aj e q :,, ue. ya fre t ~
h f *ded. . Ln
~
OMM f . . _ .-
- o. eo M
~a a
tn 3, r e4
- . . _ . . . . .--..,---m
,a__
Attachment 1 , CT-HL AE-1511 File No.: C9.17 Page h5 of 1D%
+
Question Section Page
- 3. Ill.G. 4.1-11 Identify when the associated circuits analysis will be completed?
Resolution: I The associated circuits analysis is scheduled to be completed prior to March of 1986. l l l l l 1 I l l 1 l l i l l l t J l l l l l Ll/tRC/H I 7 y m,,_w m+,-, ,. .y , yy, , , , y .- _ - , y__, ,,y_,,p,_-_,_f, - ,,. - -- ,..s- --,,,.-----__--..,._w-_. g.,m_e. -n.m- .we- --.,,,-.
l l Attcchrent 1 ) ST-HL AE-1511 l File No.: C9.17 , Page @ of 107 l Question Section Page
- 4. III.G. 4.1-12 '
Explain the t rm " active equipment" Resolution: Active Component Mechanical equipment that is capable of powered physical movement and electrical / electronic /pneunatic equipment that controls and powers active mechanical I components. Pumps, remote. operated valves, MCCS, and process instruments are examples of active components. , Passive Component Mechanical equipment that is not subject to spurious failure due to a fire. Piping, tanks, check valves and manual valves are examples of passive components. l I Ll/NRC/H
t Attachment.1 ST III. AI. lS11 File No. C9.17 Tage VJ oi }Q % Onstion Section Par}e
- 5. 111.G. 4.1-12
, Identify when will evalual.lon of fire protection means in contairyncot be complete? Resolution: The nethod of meeting Appendix R Section III.C.2 for cabling to containment involves some areas which will use greater than 20 foot horizontal separation and other areas which will use either a water suppression curtain systern or radiant energy shields. The detailed l design will be completed prior to May of 1986. As stated in the FHAR, line type heat detectors are provided in the cable trays inside
- cantainnent.
1 i 1 1 l 1 l f 1 l l I i b 'l Ll/NRC/H I._--______.-_.__.___________. _ _ . _ - _ _ _ . _ _ - _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ . _ _ _ _ - _ _ - _ _ _ .
_ _ _ _ _ . ~ _ _ _ _ _ - _ - _ _ . _ . . , _ _ , . _ _ _ _ _ _ . _ _ - _ _ _ _ _ - _ _ _ _ _ _ _ _ _ _ Attochment 1 l ST IIL AE 1511 ' i File No.' C9.17 ' i Page @ of lO% l C. Other FHAR Issaes Question Section gPa e
- 1. 1. Figure 1.1 ,
l Provide a ccpy of the ANI document providing the definition of concentrated cable trays. , p
; Resolution:
A copy of the May 27, 1981 letter fron ANI to Mr. Rod LaReau of HL&P is attached which provides the requested information. l J t i 1 i ) l j l l l k. i L1/NRC/H i
l i LJ l
,_, Attachmeng o S$@QF(( j h AN S ~- ~
FROP; Y [N@Nw3 e -F8kke W 1
~
r . :nn, n, s e n -, '
'svHS , ,_.
f nunt C.Pt o onL M , 'i -* i May 27,1981 Mr. Rod LaResu Director of Irsurance - linuston Lighting & Pnwer D.
- P.O. Sox 1700 Ili.uston, TX 77001 I
Ilear Red: i 11005T0!! Lii;lillN#; & l'o1Ek i ei. Souill TEXAS Philb*l 2 Alli l' Hill'I'l:1) fil l: fla i . li .' ail FikE LO:sS PREVE!.'TIOf3 HANAGER CARE TPAY CONCth*TRATIONS - 6 our meetir.g c ay P 12, you requested an expansion upon what American Nuclear Insurers f elt g, resporsibilities of a site Fire Loss Preventien Manager should esecopa" + m Tire 1.os *reventien Manager should have the authority and responsibility ; 3 Anserv f 0f Pf*P'f *progra=ation saouldfor the satire include but not construction necessarily site. be Thelimited property to the l conservatbe Protectics & Prevention Progra=" as well as the locatin,, and " , attached4 ,w of proposed tenporary facilities, the proper scheduling of Per- 1 ! '3" [b t Pro te c tic: Syste=s and coe.=unications with American Nuclear 3 l In surr' l l Also included for your information ANI's definition of concentrated Icgbtrays. This iten was discussed briefly during our meeting at Brown & Root
/ y 14, l / '"""7 tou have any questions, please cal.1.
l Sincerely,
., z- ,
J. Ytephen Darrah Regional Tield Engineer 4 JSD/kes $/27/81 cc: Mr. K. Kelly, J&H, Houston, Inc. NT '.?.: . Mr...rj.-
. 7. Ger.mani, J&R,ft...... .... . -l, . *se- .
., i. ; L.s f tse . *. ; Lv .a s - tw . , '**r *$ t' t h' %k O *\ C '" h bs 5
- VALt tiO ." ? U2.LI Page QQ of $ 3
_ . . . . , .A>; n u& Lein .b runs A ~<= L _ . .: .3 % ys iu &J Y~ /c' ce bA,,c 'x ~ .n n , sp . oc y n c,,- -L. t_ i... . , t,.j, m,Il al c4A-t
- c x 9, i c. s h erei a_p e cpn
. u .-+. . v. ca. . .'... .%p 41& rre less % 5 $. pp.W L <r.-t-))l, A d 6All v., ii . , A S o
- e,.g le dren veNcAl phae s -
m\ nr< w,u.rs m g t-s En 3 \se l/, bre ce>tshe55 ,\
/
I , i/ I
/ .
t i t i
,f , *30, /
1 _ l L i
/ . . . t ./ _ .. . . . se W.a~ v. m . . . . . $%b &b '
Ne perc Y % c $fsp N. Njn cc.W
.. ~5o s i~nelf o5 '$ree "by,u?ll.u $ nee
- L-f
. . _ . h.<,a S } .br wi% .
3e - cd bL me co-cA,L I I I t t .
. t_ v u ,
1 i L _ _t
. 3 r-t.
o ,. Ic., r . e . - 5.h Aj+ce.T dc -3<G
. . 3r8 son . viees ~*% ee o
'T gacnrient t SI-nL- 4'1 d 4 Y . b V M. .f r) wnks y v r e Li 4J c 2:nyTV'" ~
C C ' r h t'N a g . g . n .,,,,1 - - = ~ - . File No.: C9.17
..... d. .. I \' Pagefjj,ofLOS \ .2 I 1 L 'g 1 -
1
. .. L ' \ L .
L i s i i i . s
. . _...' t L I Hs'--4 ,
W.Tli. S'ho,e. # N w.h 3o* , h e il , 4 ,' b y f 3
- t/ i
- / !
i i ! f i ,
- 4. i ., , ,-
. t_ r*v 3 t , , ,N -
(.u t , i i / t ,
) / . .r m. ,:
i b--.t E' 4 . W *N cr en! y
%e L 3 Tra,. %k Aju,,1 1 % c'L ' 3 Tr w k . . E v.-ple., e Gf,9 v edtu %d y,c ',d- 6, c ,j. .-t . ,);y . . . d 1 .t s . t n\ . . t i \ \ .
t_ , , fK . i e ewe W 3e 3 E
. Ys n e. D hv b Cf hf% r*! 6f R . h.' M t c e . e.
g . \
- o. . mg. - M
l AttachmenttoSI-pglMgg4 e g 3, ; ST.HL. AE.1511 j File No.: C9.17 -
, p g. (16 og }_py l . . 2... i i ....t i . . . . u 1 i.. t 1 . . ... 1 0
i i t t 1
- . . . . . . ...)] N .. o w < . 3 ... % y .. h ... L k . k ; n ,- f .. . . .
- l
__ . . . 3. . . t. i.. .. . . .
. :l n -
t ._ . Nat ova 4%y i ,, s . h ie Ekk rv l I t . . _ . _ _ . . . ... . . ._ . . . . . . _ . . . .
.. .... ..1- -
t . .. . .. . .. . s.. .I. i i i ,
. ... .. t e ' .5 ' -. .e - i. Ges,il. s '- b ' t- . .-. .: u ,
w e b, ' ,4;nce-t- .
. . .. . .. > , t i
____. s. .. i -
/1 , . . . . :. t t 1 6k$r, $ u. 'J ' Ah nh /
t .t i - in 3e c nre a re n:t -
.. . 1 i, i i. g < ~am% 4ai ray, ,.
i.
. .. Og. '
enh *
- ., n p. -
e
A L L e e.lu.s u 6 1 ST-llL AE-1511 Filo No.: C9.11 i Pager ]b of }O' Question Section Page
- 2. 1. Figure 1-2 Change the logic diagram as follows:
a) Indicate that this review is done for all N OCh table ' regardless of whether or not it is concen. b) Change the last diamond to explain that this is to provide an , effective hose stream to the fire. Resolution: A revised copy of Figure 1-2 is provided as Figure 1-3 which is attached to Question 7 of Part A. L1RRC/H i
A % hmed ST- H L- AE- 151)
. Thy M OF \02 Question Section Page 3.
Clear up Item 9 Attachment 3 to ST-HL-AE-1194. Resolution: HL&P's review of the areas of the plant having concentrated cable is provided as an attachment to Question 7 of Part A. e S
- Ll/tRC/H l
Attachment 1 ST-HL-AE-1511 File No.: C9.17 Page @ of {Q3 Question Section Page 4 Non-rated special function fire doors. Provide the same information as River Bend provided. Resolution: The additional information requested is attached. . Ll/fEC/H
Attschment 1
- ST-ilL AE-1511 Filo No.: c9.17 Page % of M With the exception of special function doors (i.e., tornado resistant and fire resistant, watertight and fire resistant, and missile proof and fire resistant doors) the door openings provided in fire resistant barriers are protected by 3 hour fire rated UL-labeled fire door assemblies Although the special function doors are not 3 hour fire rated doors, these doors will provide an adequate level of protection for the areas where they are installed since
- 1. the fire landing on either side of the door is low, and/or
- 2. there are no safe shutdown components on one side of the door and there are necligible combustibles on that side of the door and/or i
- 3. there is an automatic fire suppression systm installed.
Attachment A provides a sternary of the key data for the 10 special function doors, including the fire area and zone which abut the door, the combustible load on each side, suppression, detection and other data such as the door type and drawing references. Attachment B provides a sumary by the type of special function door and the basis for acceptability. Attachment C is a comparison of the six unlabeled watertight and fire resistant doors to fire doors tested or listed as 3-hour fire doors. This comparison indicates that these doors are (1) similar to labeled fire doors in construction, and (2) that adequate gaps are provided between the doors and frames to allow for expansion and distortion during a fire. Similar comparisons have been requested and are being prepared by the marofacturers of the tornado resistant and fire resistant and missile proof and fire resistant doors. Since these doors have only been purchased recently, these two comparisons will be submitted for NRC review as soon as available. It should be noted that the Mosler Safe Company has been awarded the contract for the - missile proof and fire resistant doors and as such this comparison is expected to be similar to the Mosler comparison in Attachment C for watertight and fire resistant doors. These ten special function doors for Unit 1 (Unit 2 is identical) are similar both in type, construction details and fire loading to doors previously approved by the PRC for River Bend Station. Ll/NRC/H ,
Attachment A Special Function / Fire Resistant Door Data South Texas Project - Unit 1 Drawing Ref Fire CONO. SSD Elev/ Col / Door No. Area / Zone Load (BTU /SF) Detection Suppression Equipment Door Type FHAR Fig. No. FHB-338 35 310 3,000 Smoke None None Tornado 60'-0"/M.8-27&28/ 32 145 10,100 Ionization None None Resistant / 3-10 & 3-17 Fire Resistant DGB-104 39 503 10,300,000 Heat Foam-Water Yes* Watertight / 64'0" 45 509 Negligible Ionization None Yes Fire Resistant F.5 & H-16.9 3-32 DGB-105 40 504 10,300,000 Heat Foam-Water Yes* Watertight / 64'-0" 46 510 Negligible Ionization None Yes Fire Resistant D.9 & F.5-16 3-32 DGB-106 41 505 10,300,000 Heat Foam-Water Yes* Watertight / 64'-0 47 511 Negligible Ionization None Yes Fire Resistant C.8 & D.9-16 3-32 DGB-201 45 509 None Ionization None Yes Missile proof 82'-0" DGB roof None None None No Fire Resistant F.5&H-19.4 3-33 DGB-202 46 510 none Ionization None Yes Missile proof 82'-0" DGB roof None ibne None No Fire Resistant D.9&F.5-19.4 3-33 2' 0 3 Trs; DGB-203 47 511 None Ionization None Yes Missile proof 82'-0" DGB roof None None None No Fire Resistant C.8&D.9-l.3[.'4 '. E 3-33 {r N
*These doors seoarate equipment of the same train, l' .e., the sene diesel generator.
/
Drawing Ref Fire COMG. SSD Elev/ Col / Door No. Area / Zone Load (BTU /SF) Detection Suppression Ernipment Door Type FHAR Fig. No. IVC-002 48 403 45,000 tonization flone Yes Watertight / 10'-0"/ Hegligible Ionization Fire Resistant N.5&P.4-20 51 405 tione No 3-35 IVC-003 49 402 80,000 Ionization tione Yes Watertight / 10'-C" 51 405 Negligible Ionization None No Fire Resistant P.4&R-20 . 3-35 ivc-004 50 401 134,000 lonization None Yes Watertight / 10'-0" 51 405 Negligible Ionization ilone No Fire Resistant R&R9-20 3-35
*These doors separate equipment of the same train i.e., the same diesel generator.
7?EN 74:0 LOW [h a :. ? 3, m -,
'"O ausmusumpumas-- , - =sy - =i- . . , ww-you-w w ar ,=m =,mg, mm w sequa
Attachmint i ST-HL-AE-1511 Filo No.: C9.17 Page[llof1{)T j Attachment B Door type: Watertight-fire resistant Door Manufacturer: The Mosler Safe Co. Comparison to labeled Included in Attachment C 3 hour fire door: Door No. Worst Fire Severity Basis for Acceptability DG8-104 128 hours - 45 minutes 1. Automatic foam-water DGS-105 suppression on fire side of DCS-106 dppr/
- 2. Door separated diesel fuel oil supply from the same train of diesel conponents.
- 3. Not required to meet Appendix R Section III.G IVC-002 34 minutes 1. Low fire severity
- 2. No SSD C0mpnnents on other side IVC-003 60 minutes 1. Low fire severity
- 2. No SSD components on other side IVC-004 1 hour - 41 minutes 1. No SDD components on other side
- 2. Negligible combustibles on other side
- 3. Nearest SSD components protected by door IVC-003 which means that we have two' water tight doors and a considerable distance separating the respective pumps.
l l
Attachm nt 1 ST-HL-AE-1511 Filo yo.: C9.17 Attachment B Page E of $ 8 Door type: Missile Proof-Fire Resistant 1 Door Manufacturer: The Mosler Safe Co. ! Comparison to labled Being prepared 3 hour fire door: Door No. Worst Fire Severity Basis for Acceptibility DGB-202 None 1. No anticipated fire severity-DG9-203 either side DGB-204
- 2. Administrative procedues will effectively minimize transient combustibles Door type: Tornado Resistant-Fire Restraint Door Manufacturer: Richardson-Wilcox Comparison to labled 3 hour fire door:
Door No. Worst Fire Severity Basis for Acceptibility FH3-338 Less than 8 minutes 1. Low fire severity
- 2. No SSD component on either side of door
- Mist;r fuig9,1p85 g + ST-ilL- AE-3 511 File No.: Q9.17 ,
Page of LOT HOUSTON LIGHTING 4 POWER COMPANY WATERTIGHT DOOR COMPARISON ' WITH EXISTING FIRE DOOR The following analysis is to compare the Watertight Doors in Specification No. 3A5195S0036 with an existing Fire Labeled Door which was tested in accordance with 'the Standard for Safety for Fire Test of Door Assembly - UL 10B for 3 Hour fire rating (
Reference:
File No. R8440 Attached). The clearance between the door / frame assembly 1.. the area of the labyrinth at the seal for door expansion in case of fire is a nominal 11/16" all around. The calculations will evaluate the largest doors with nominal door dimensions of 46-1/8" Wide x 80-1/8" High and fire test te=perature of approximately 1930.*F. (Doors IVC 002, 003, 004, and 005, DGB 104, 105 and 106) Expansion in Height , .979 , ,439 80-1/8 x 1930' x 6.33~' 2 Expansion in Width , .563 , . 282 46-1/8 x 1930' x 6.33 2 Expansion Across Corners , 1.129 = 569
'92.45 x 1930" x 6.33-5 2 I
Based on the above calculations there would be approximately 1/8" clearance at top and bottom, 11/32" clearance at sides, ) and 9/64" clearance diagonally across corners at the time of the largest expansion. Door and frame construction description as outlined on the Comparison Chart show the Watertight Doors reinforced at all edges and incorporate a minimum of six (6) locking bolts to secure the edges against warpage. The frame is also shown to l be much stronger due to unit welded construction, reinforcing and being continuously welded all around to precast steel embeds for strength. See sketches on Type "A" and Type "B" Doors.
July 9, 1985 . C 0 M P A R I S.O N__C !! A R T U.L. LABELED SPECIAL PURPOSE IIOUSTON LIGIITING 4 POWER SPECIAL PURPOSE WATERTIGill 3 IIOUR FIRE DOOR - REFERENCE DOORS - REFERENCE DRAWING D-K18551., TYPE A AND ITEM FILE NO. R8440 ATTACllED. DRAWING D-K18479, TYPE B ATTACllED Door Construc- Laminated construction of 11 Ga. Solid plate 3/4" or 1" thick A-36 steel reinforced tion cover panels with 1-1/4 thick around periphery with 1" thick x 2" high A-36 bars. polystrene foam filler bonded to Seal housing around periphery adds additional each panel. strength and stiffness. Lock Bolts Mortise type keylock. S t. (6) Lock Dogs 1-5/8 x 2 or six (6) Lock Bolts 1-1/4 Sq. AISI 4140 on door holtwork seating on locking plates of ASTM B148 9C aluminum bronze heat treated 90 ksi minimum tensile and mounted to frame. Ilinge Continuous .090 piano type hinge Two (2) hinge assemblies, one at top and one at with 5/16 diameter hinge pin bottom. Ilinge yokes (A-36) mounted to door and mounted to door and frame with . frame with two (2) 5/8-11 x 3 Ig. screws each
#10-32 x 3/8 Ig. sheet metal yoke. Ilinge leaf (1-1/4 thick A-36) mounted screws on 7-3/4 centers. between door yoke and frame yoke with 5/8 dia-meter ASTM A-434 CL BC CF 41L42 hinge pins.
Frame 11 Ga. pressed steel, bnit welded construction of 3 x S x 3/8 thick angle (A-36) reinforced with 1/4 thick x 1" Ig. bar er (A-36) around periphery. 3/8 thick $$o)p) gussets are welded in lock bolt areas (one g %g side of lock bolt) for additional strength ca stiffness. .kh R " /, 9 -.__ Field Pressed steel frame anchored to Frame assembly continuously field welded alhhh Installation wall with 24 Ga. steel masonry around inside and outside with 3/16" fillet wgid anchors - three (3) on each side to previously installed embed angles and/or plates. and two (2) on top.
l
*I . Attachttsnc 1 'm ST-liL- AE-1511 !
File 'o . : C9.17 l I' age of }D8 NOM. h
-5 RM -
EMBED ll
\ j 1 1/4 X 1 B A R A- 36 / 3/16 V / 3 X 5 X 3/8 ANGLE A-3 6 ,
W SEAL p g l-1/4 X l-1/4 S0. E-] rv, s si d AISI 4140 i \ l' THK. A- 36 , 4 N ND h vrig d \*
/
5 ,2 .b 2 a7
\ O 1/2 THK. GUSSETS E AC A-36 \\ % \\' % N g 16 SIDE OF LOCK BOLTS .
a h 1/4 \ / 1 ON WATERTIGHT 15 I/4 / \ "
+ iTHK.
b-* 1/4 X 1 3/4 BAR A 36 DOOR REE 4 SEAL- ASTM D 2000 1/4XIV2BAR A-36 3/4 TH1 DOOR NEOPRENE 35 TO 40 DUROMETER . 3 1/8 Nih-4Y 2/
- : REF- V8 VI V2-4 8/2\ . . TYPE"A" DOOR . / .!!s 16 *2 +g3/16V N.
s 1 5/8X2 O AISI 4140 ;
-N SE AL 7 ,,g . __
N q , N,/hb +\ a / 4 i ~ A m \\ \\ KN \ ' _2. 16 V \
) 16 few w Aven. Tic,u r I/4 \ /TYP' I/4 / \
1/4 e4 S Mm %.' w ATEL-Tin W T 4 1 A-% I 1/8 NI Y 2 -4 /2 / X SFAL ASTM O2000 N JPRENE 35 TO 40 DUROMETER 1/8 VI /2-4 /2 \ I I l l TYPE"B" DOOR
Attechm:nt 1 , ST-HL-AE-1511 Filo .: C9.17 U UNDERWRITERS LABORATO[tlE OtICACO . penstu sacos,ILL u ELVILLF. Kt . naprit Cta 34. CALIF NC[of
- an independent, not-for-prof t organhalion testingforpublic safety ,
\
l 1 l l l l l File R8440-1 Project 77NK8109 June 6, 1978 l REPORT on SINGLE S* DING SPECIAL PURPOSE TYPE FIRE DOOR AND FRAE .3SEMBLY Under The CLASSIFICATION PROGRAM The Mosler Safe Co. Eamilton, OH copyright 1978 Underwriters Laboratories Inc. Underwriters Laboratories Inc. authorizes the above named company to reproduce this Report provided it is reproduced in its entirety. I e l : 1 I I
i Attechment 1 ' 7
*
- ST-HL- AE-1511 !
2%hseJg. : 6c61A 7 Page 1 Fage'fp of g g File R8440-1 l ( , REEEEIEllEE PRODUCT COVERED _: i l purpose type The product covered by this Report is a spec a i door frame fire door, single swing installed in a pressed steel f re of the single unit type. l f USE: ings The assembly is designed for the protection of openThe door in walls for 3 hr locations. Classified with respect to fire hazard only. A e
- l l
) .. l \
e i
AttcchmInt 1
~ it\ g * ' ST-HL. AE.1511 '
Isshh:(6ppgl7 Page 2 . File RS440-1 : RE RESSEIIIIEE ILLysIgagiggg i Description _ ILL. ., 1 Appearance of exposed side of test assembly before fire test. f' 2 Appearance of unexposed side of test assembly l before fire test. l 3 Chart of furnace temperatures. I 4 Chart of unexposed surface temperature. 5 Appearance of exposed side of test assembly after fire and before hose stream tests. 6 through 17 Construction details of doors. WRH/HSErsn 1 l l l l l l l
,m..
.n - . _ ._ . _sa - ~ a - - - .- - - - ---2 -- - - - - -
i Attachment 1 ST-HL-AE-1511
- C e
{. ' v's
' .a j
da "
=
ine t b,j " 4:.~5 b t
; f;,
l x.. ..~,.:- f.f..*o...'Y
., yp:- .
n.-
, : \ ,,e ~
2, -
#h../
L 4 ,e. F. l p 4- , 1
% 7 $h 9 O Tr.' -"IN59 dU 5 25E -1 . 'sd.fifd:.,2.P .5/d i '"Q ..
m- >i f ... I E sh k )l a:s
' E n wad:f ..
l ! k 1, . a l I WEE - pg* e, . yA-' - p .: 9 .
. / ... -... . , Ke
Attachment 1
. . ST-HL-AE-1511 Fi -
a n' '-
,g;p,y..
V.- so u.t itgi.90,m$$ .. g;.- m..pg
, ,g O. . j, t . e . W. . $ e
[d .a ' . I I
.s . c.'- = 1 .A) . i t B . .::;' 2 ] e,\-( wc.
- y . .). .: -: -
= - . ,. 2; j! . '. -
j .s. . .
) .. , ~
j
. .M. k. ; ,( n N '# - .t* . =.t ~?. . Y. . . ~.. i, 2: 4 -~
4 _/ s; . < 9 ._,... A q D. - 5 , w ' 0 ' la.
'7 .. 'g e
- 4 , Pwe e
...- .w* * ' ' ' '
s,
. , . , li ..t. .v - .v.w ,
N
. g. i Eg, . .ggW-.:. -5 -
v y%. . . c .A g
. n Q .
l
Attsaha;nt li
,,,cato me um ST-HL-AE-1511 ,
1,ly'jj. ins File .: C9.17 Page of w-a-( t,an em ree tsuawesse .Teet ines out im ais._.....- _.. . seO
. . _ _. .. f.
1 I i I I i 1. . i !. l s i.
..u....... -.s .1 .=a -
I e 4.- --
-s 1 i l' .
i - I. - i-
...i..* . - . . .. . .:. .. . . :. . . , a. . .. . . c.~.~... .~ . ~s . . .~v . . v . * ! i - e r ., eso
- b 8-
.t..
- 4 .A
- x.
s ;. . ..
- e. * * ..
'% si > *- ..y. .,
s20
- n a 49.
- t
> .g .. . .
3 ..
* = . .I ~ -
- e .
, , . . j, . - e . l . ' F . ..g. . . .* * .. .
90 l
.2 e - = 0 3 6-E , . g
- n y .- ~
~ .. * * *. f* . W J .. .... ._....... .. _. ,...sa.._.. . . . ._*.a. . . , . . =
s
- e g .. *.
, ."_..4.....
s.
.= . .* r. . . . . . . _ . .
60
- Ja u . .-
.e. t i.. ; i t ' 8 8 '- - -
6 . t' t'-- i ,- I. ..' i. . . . - .
*-. .-.,, =~ =e =.e r . . e. ,a g ,,. wg__._ g . f f_,,.A.. . ? I % - , ?. .1..i .. ,i.,wm , . .. . w 4* , !t .,, ' I a i 1 a l e . 30 - * .W
- : I C*
I i .
** b l - --
- L a .%..
l . Jg(g40Casrt! WW b, .. _ ap*- _
-30 6.. . 8 I ; .t. ! l 3 3.81 ** i-l '- ' ' . . . . -....--- .30 0 -. . .
i i I l s l; \ < l 1.. _.****..P.m.***."..*_.**_*;*...?"*.F:*..t.'.*,t...**..*?*.*.'.*'O I i i , , . ILL.4 b
s 1 e- e l i
' - - . Attechrint 1
(( l ,
,.' h ST-IIL- AD1511 l 1.. ...~ . FilafFo.: C9.17 1 .t
- Page (j_O of 108
; m ,u w u m.. - ,- .
e
/ . / ,i .,i .i .i . . . . ' .i . .
O { t
. i l. . .i.
1 d.i .l g. h i .
..I
- i .
I
. . .t . ,!, ., .f ., .. . .. . .. .!. ; L.; I .- ' . l - .. .. i.e l.;.. .J.:['
ij .L:I!a
? t i- . .l8 l .'. .J 2.. . .e . ..1_
- i. ,
i :
.t . 8 t
1 . -- a..
. g j . . .. ...il i- ,. L; . . .i .j .....!'. a: ..HI.. . i
- i. .. .
1 i l- i. .;-
- .!el g ,1i .. . .l.i.i,,. ,a i i i ..l , i . ,., ;. t ;1 . . ..i ' i ., . .t .: .: ..
- t
.I..* . . . . . , . ., .. . .I i*6 . . .i i.
i .
.- l . l..
i i s l=.,..i,. .
- f. i ..L6:!ji.. 3
\, ,
l l.i . H ! -!-
! i i . .. . . . , p I $..
{. j . .. ! y ' -
. .i . q' .: '. . . , i ,: . . ?,. ,; . . , . . .4..
t ,i I I . '
'Ii!
5: 'l * * [ ! ' s , . ! , . !, . i. . j . , .L.J.
- i. 1 ...,. .. . .. . . .- .. .I .....
.'.21 6 i* < .. - ,, : - ,. II .. . w! 4 . Ig. -
8 . - ' . i . I ! 4 p: p! ' ,. . : ! i;', , ,
.., , !. i 1 i t , I, . . i , , ...., . . .. .I .. . . .... .
e.
.<: l.;. i .S *!;* i .:..; -,8.t ) . > . J '.. ia d.
e., ... i- .,,a.. l
.., y. L - .a..-.;
i , , .]
... .. .. . . . .a m . , . . .4 , l.
l a j . . . . ,
- i. . . .f)n, .' .' *.
l .
, 1 4
s e,.!. '. e .. .. .' . .
- --; i' l. . . . . J.
i; I, .Ii es i i ,i,' . a,, .. 8
. . .j. ..
- .j .
,I f . .
g, t, . ,, .a . I l' ....
..),,. ? .'.I . . .' l.
e. 8 . .-l"_""*'.". . t.l s... b; , !l
.' . * * /":". !ljj . .. .i! p, ., - -- .
t .
)
- 1
, l-l t ,
i l- . ' l '; q .)
' ~ . - -' . .
a.}.1 s- ' k, j p. -- ---, t.j. #
!.1
.-- _ l l
Attach:nent 1 ST-HL- AE-1511
- r. - .
. , . . . . . ",; P 3 agn 2
s e ,, g6 .- - . a at . , t t -1
,_ y5 .i- .- .;,)J .-' . .t%, ~ .. ,j .2 .u l. - ;
6.h 7t . '*:
- g -
.'.din ti .G. m.
(,
?
I
- 5. .yA. t t .
i- - ,n.
- . 9 n
~.
y< J.;y%a .- -
.... : if .: it. . *( '( ..
- :.. e . e
' e i e
p
..' . . y ~ . . 1 ' ',
J
*n - . . ~ .
- e. ..lii
-. . J M. :%; f l' -
Il E ,* l 1 i
.s. ,. . l. 3.- '
a
. . U.dl .x. p?,pf ,
lE
%.G h . h' t-i; ;-gN{a{j lhe r .c~. FE.r- . . o. . .:y-sa u .1 ;: ' _g 0]4.t,t.~1 'iiff- dr7 .79 9;g.
Q:,4 4..g.d;**$pL 3 E . ; f.!. .Y. ;}E
' -- e.
1 : - i,.,,::::
%.;.. p ,
l lj
- Q W) 's / . ,1 li g.
?. , '- fy -
y" "U- . , .
, . b u. .5...: .n - . <w"L. v. .
3 e ,, n-b%d PJ. .; :9- '
- X _ .~ l
. . ' . , ."[ . m- . l
m.a ,
= +Q . . ^
- 4 3 l
e e , e
** * -o N. e O
_ i 19 - em 121 .
.D nn , - l 9
pt-h , o I b D c . 4 e
. t) .
u s
' O ~
l i
-> 1 , .L t
- t. .
e e 9 0 - i
- .7 b
b b._ - hi . 9 4 .- t 3 . I, +
-.. e , A . - ' G - e e
4 _ e
' A
_ ,_, - , , - - , . ~ . , r,r- ,
'F.- ,g-m,. ,, ,e ---
e
hammmmmmLw , REV!S ONS ten utv1 __ etsenietics omit - ,A PPO. l , 15 bV _ ORILL LTAP Fbf? _ . - [ gg y
-/ [12-2.4 Sc.12.
t 2 -I2 EQ C. jJC, - --_
. ST HL. RE-1511 Qa ejn<f ~\0%
i ! i i . TI
! i i APEILTURE .
i ' l CARD
- i l Also Available 03.- ( ,
APNture Card I II -3 i/ . f I . i
! l <. i I ', FILE ! !
neo.c
@/
1 i ILC /_7 __ _ _ l l 1 i
- t IW.ti; FCRT Q.MABEf! l P A C2."T MAME QTV g
i C; J 18752. BOD'1'- H ou s t W'a i
---- ----i - 7 /'. -J 167 47-D S L CiE. l 'S -
h -J I B747-C TAPPIMG PLATE 2 g- . Iw
~
TOLERANCES ORDER NO. c1 %, . .a FRAC. + - DR BY:M o,v.t. ri - TilLE DEC. + - D ATE : 3-4 t *i7 Assy '_OtK Mousius i l ANG. + - CHECK BY: FOR A* ' MATERIAL (SPEC.) DATE: O.R. DDOR APPD PRODUCT Sili DWG. flO. REV FINISH (SPF.C.) DATE[: APPD c J'dOOO8 0 ' (CUST.) %ALL ICONI.CN
~ . . e--
1
o g ,- _- - - * '
--_,e - - - _
l
=
l 7 -
, e s I I . 9= e d .
L .. - i ~D . .
- e d
e f e e _ _ _ _ _ _ _ _ - - _ - _ _ _ - _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ t L __-_-____ _ _ _ _ _ __ _- - _ _ _ _ _ ______ _____t L_____ _ _ . _ _ _ _ _ _ . _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ , , _ _ _ _ _ _ _ _ _ _
~ -
g , pO NS p __ __ __ _ _ _
'e il Foauso view I
i.
.j .l ,
i
* . , ! l
- l .
O,L I h l l
- ! ,-t> (M sw_ese 151 rd%. l l
. t,i t . I : FteT SuecT . I 8 - . I
,. I b q- - . j .
I l f 1Old l V8 N _ l i .
~ . pn l -2*l k' . ,
- e ,
052 l 8 e g .
.. t .
- I *
;A }
G b .
\ .. -- -- -- 6 .- - r- ,-'I"- y ,, _
l l
1
' I .. ? . / - . . .
h 4 3 ! 2 l !- i; e4( visiot.s
.,<..... -...... . , ~ -
e - AMachmen4- l gr-nt-ac-isu . ; TPa cB3oe 102 . \ h TI Mn- xx ur _w E I APEttTURE
- _ _ _ - _ _ _ CARD l
Alm Avallable on Aperture Car.1
=
- t
- g3 .
l
-+ 3 1 -
4 -lf i DR t t.t. t**AA F"2 %.10 SCREW , l I Ot A urut*, ( 6 R40'O.) h - sg 4._- -i[_d _
- f -
i T 'ID
*!. e w vc v= c O -t- i "l' ' ] - C4 l
_. T t2 - t =J_sl9_ . l T FILE ,/q. h RM4-!
.c l-7 ILL*.., y[8 / _ w; '
g64 l ll: i l
- FRIGHT WtMD OUT
. SwtdJG CP DOOR T M AMO IN ,
10L[RAr4CES OROLH NO. f. _ , , , FRAC. + - _,. DEC. + - eit av v.cunwt**as ANG. + - gq , r,,, c e. s s illLL _ g g g , y g gg g g ~ - ta A s taiat (setc 3 f.?J son ~d. R. COCR bu . l I l G A ' ?.M 7 . j'.y- esca.:tj silt owc tso. htv .I DNISH (5PLC.) p, ,} g D JI6315 O T5s u _ D:_ _ i. a n .sio _ { } _ _ m-n., h
- - . -- __. l y
a
,,% ,..e - -
8 l, 7 *
- 6 l, 5
. f_ __ _ __ _-
s t _._ _ _ _ - - _ _ _ _ _ _ _ - .
, t ,
D . f A2 -
~5 w 5 1 1' *1 } - .r 6- -- ~-
1 i y ; ( < _ _ _ _ _ _ i _ _ _ I _ _ _ _ _ _ "_ _ Z _-- -- _ _ _ _ _ . j[ ', )
-p F-'i -
i
\
I t L
\ ; } \
l l \ l I 1
/
w w r
\ -
I "f .
*bu I , \ ; -,h I
- b ,
I 1 ' 1 [I t j i { e cooc 6 l
! I l
j i' [ i .
', 'M 4o sCw. c. ~-
i l\
- I
, \ \ l ' l l I D C '" " I 'C t
[ I I e- - i . ,i EGeew.% 'r I j l, l I l . k l l.J
! I I
II i < i<-'l l e
?
l [ l I ' j i j ; I 49'#*'f , f c l l
. s , . ; r i i ,
l, y
.p l \
g ' 8
- c 5 i O E ,b s [l,, N l, 1 w e j l U s { l
- 6,
( !. i i : i l l I
\ \, 1 5 \,
l 0 ] ' i I i
' r'- I l l 1 , )
l l
]
l ' l [ l, l de ' l ,I , O .
' I l T
i 1 , I t j ( i l e q[
* { j - l l l l 1 l 1 *
[ ,
' l l l
l l l
- l. ' F lA i ,
< \ 'u, *0 ,',
i -- __ _ t I 1 t . O
.I -m -- - ,3 , ,
g-
~ .
_ , , _ _ _ _ . . _ . ~ v y 4 l, . . 3
~
r at vivous 3 Klo E ' q seto atem seaus f i BOTH Euos CN IMStDe. ~
~
- 3 '
- . AHochment . GT-14L. AE 1511
- I 1 .
mH
.i , i 'Pa$ 44 of102 l l l
l \ l \ l .
.~
l l l l l TI a l
' l l
i t APERTURE l i l t
! l CARD I \ \ l i '
l ,l ( l Also Armfl.hge g ' 1 I I l " Aperture Card l ( l I I l , 4 i t
)
i EILE. ghi. : j
\
l \ TN61
\
I 1 l 1 l ILL-h_ l l b l pr t1 usaete Pt.RT utwE ov$., j I I
]{..J28709 ? p. J 7 67 i'D ASSY
- c t.*de . L ocedio n .. ".7"/
a%v rpAME.TCP i l l } ( l 3_
--l< - J 7.D o o t t.51v = rmv e. ui 4c,e sion ; **,*' ,
i 1; i l !
! I \ \ \ _
1 i l l l . 1 ( i i l e,w iu s OF OooR RicuT Meato our I i LEFT O MO h4 t I ' ~ 10LLH AfdCES OriDLR f4C. s 1 FR AC. + - j ' (M] lI DEC. + - b 2,[' A SSy. FRAuc.V/ ELD. f%
'"I,<s*,
u t JvcC I, , , ". .,MW "'
' " 5.R. Door C i.9fi est...x.;
se t ov.c too. H L V. FINISH (SPEC.) r f, . O J2MIO O - [ cg.;i u l ct- G.i u * - z,. 9
- , 9. //d_,o C/5_ ?_)-0 3 _ _ -+
.I 4 3 A.TTwe.hmp/tt '
ST.y.t- AE-1511 D e a .
. _ _ . _ . m
_t " h _ __ _ _ _ __ __ __ _ __J -
< v '
l
-B u - ;6,: , __. g - _ _ _ _ _ _ _ _ _ _ _ _ . _ ,r kV 10 ma e %--_.-___. .
C ___.__________.: __ _ _ __ _ __ _ _ _ _ _ s__ . ; t t. i . 4 g' ag, -d.].2_.' t ' B l la
- i y .
i : x
.= - www mm,_..w du e
i Fou_ Size Sea; A
/
7 p' _ ___ _ _ _ f
\ 6 l . % --
i
. s . ..
l -
.A s s ^ ^
l
- f '; f0Lt.3 TEE 6ECTIOM O-O I
-I -1 1
-~= .- - - ~
i n . _ - . ~ _
. - _ _ _ _ , _ , _ _p_ __ _ __ ^
k ~ 1 ilEV?SIONS
; g stg, _ _ ' CL 5C' tipi C N Datt Arro.
g C.EF. 4_______.________________.___..-.._____ _ _____ ---_-- OF OPE 14thtG k ,7_._- g
, b.
n .
.________________;m____________.___._____ .F B _ _ - -
i _ - + - _ ' s- - si; - 7A '- U Ap, . s d 4. ._ _ g' L._4, , s - __. _ _ _ u-___m . _ . _ _ _ . _ _ . _ . _ _ _ _ _ _ _ . _ _ _ _ _ __ = l - -'
. ,_ 3 -go o q= 40g ,
_.___._________w_.y= .- r .5 v na _ _ _ _ ._ _ _ m .. ._. _ _ _ ._ ' . __ _ _ ._ _ _ C 3J 1
. - . .... -. TI I 4l 4 APERTURE N3 CARD 7,tg , ,/- - - : . R24-10 -1 A Also Available On \ \_ y Aperture Card .
ILtl _ld . I
/ l i )}
J O % _ _ , REM PAPJT Nu n: .i< g . , - , P ART M AMe. orf. 1 0 .J7F _i - ^ r tzAME- LCcK5 ton I.i"..T l
. A. .A.
2 A _n.wo
~~-~
Assx tevauw<s c.Jete i
~3 ;C JIdopS Assv- Loc < WousNG t.
TOLERANCES ORDER NO. FRAC. + _ MO.Inr **o ~~ - DR BY:tA. Cur 4Rc;ild ' Oui T.4.n* DEC + _ DATE: % 2i m , TITLF,bW 4 NE MD ANG. + _ CHECK OY: i stv. ' FOR MATERIAL (SPEC.) DATE: i B.R.Coog APPD g g, . Pocouct Siz E .0..c. nO. REv. l FINISH (SPEC.) APPD; C l J 28-'/OC) l (CUST.) n :. At t ; ;m i u.
+ - ~L1lliff 66nISO-04i 1 - '
, e
s. (. . 3 D . . e 15 gyy
. ... . n o l- - . . e .
l ~ l . s. C / I . G L A 55 F'R M
. A NG. .~ .. *.. ..
l SiOES - C .J7.9577 ( 7. - R. EQ 'O.) ._
. l o [
l .
,. D -
I I I l w . s N Picot. I 4 cozuens\ 7 - - - - gj 3% B c _ m _-__ s O o e _G_Le..s_ rat /.. Akra. . Top t em. . _ C-J Z9 5% ~(? . REC'O.) , , , , , ,
..r . . r. . .
- i. . t - . . . ,
6 -
..s .s . . . . . .c. . . .=. . .
i i
- e . ,' 'l . r: .
g
. e g 9 l
- I
, ~
f - I- . . g .................-.._.,,, ,. , e v g ,, , ,
, , i -c,- r- - .
' - -
- m.4w w wh.way e c
.s q . _ _-- % 4. , , -w , .g ,- ,
_V 2 1 h l liEviSIONS C C re L3 _ c(scairis'ha oasy a psg). r ,
- l. .
h&OCOMCDS sr-u't-AE-L511 ';
.J 1.sr. . 'pq3e,4,of I0%
a . o ' c , i . l ll i i . I c i i i 1 i TI l i APERTURE
- i .
,i o ,i .
CARD i il j . i Also Available o. , 4 : j l APerture Card .
. 1 .
1 l . i i
'g -
I i .
! I -- -.- _ - _ .. ]l o
b . E i j ' i I . l FILE ' Mr
~ ' '
f T446-I' ' ; ILt.*[ N TOLERANCES ORDER NO. Tp 1
- 7 ,,
. . FRAC. + - "
OR UY.t A.cukomat -i' C* + ~ TITLE N u o e. - ANG. + . - DAIE: 7-tT-u CitECK GY: Asw.Gu:.ss FRmae . 1 I ___ IOR c .,,,nw $.4r o # i MATERIAL (SPEC.) DllC: i B.R.DCoQ 3 A D. DAIC. .
. - - PilODUCI SIZE 7..r: ' REV.
FilJISH (SPEC.) ApirD: C ,,) '?.C) 5 7 5 O 1 I
~ . JCUS r.) ScALC . ;n i . ON -
h '
.. .A :. 5l/p Mo-65 -
e A-
.~ ~^ -
L' ' --- _- ._g
. 5 - 4 e
- d e
. . q b
3 . e . 1i 4 08 _ - 9 - __]_~ -. L _ _ ~ h.
. l . . I I
C
~
WP-IG
~
uTVP l
. IG I I
I 2 i i t g:sr. t EE F. l ,'
- i. - > -
u - i. z .
- s. a
- .i j >
l
) ,
{ r! =-.m.. - , ,.. - , - c ._=._ .. m __ .... .
. j' B 1 i
(2.Eff. _ l 3 O I l l
. i .e ! . .. ,. 1 .. g
- et S f* *. ,
* ~
A .
. 1 4
e
. e * / . ;. s,. .
h
$4 I ___.....__...__.............___....,..... .o- ._ _ - . . . - - , , . - - - . _
085
- g.e
- se l
7- ,
"N- . . . . . ' v'"3: 1 3 2 I 1 !
REVISIONS -
; E.C.N. REV. DESCRIPTION DATE APPD.
s
'S . p-}4ac.hmen+
gp HL- AE-1511
.'Th3 ef'1of 108 - - f '
TI . APERTURE I
. CAIlb i . '
I Also Available On l
) Aperture Card .
l -
. i 15
[ [ SLE . :. s - m e s'.r , R.EF. l
, ,,. .. .. ., . . f, ;
l ILL' 12 1 l .. i i l u . J .-- , l 3 frame. A%,us B-3T78 O 2 1
~ ?. Fra Am e A ur ,s.E. 6-3278 I 7 2. l I G sA % F9.A M U_ F$ - 3 2.~l 61 % '
DEM PART KIAME Para.T FJ -
; Q UAtd.
i TOLERANCES ORDER NO. p 1,AC. + o g:, tig
. C. . + .-
3g{ gh>[ HAustion. ohio 45012** NG. + - DR BY: PP D6W IITLE - N ,
.1ATERIAL (SPEC.)
DATE: ~^ 6 ~7 7 A%T (_% AS% b G:A m =:. 8orq% h . E E'Y: FOR
.to to - to'L o 1REV. E j D S "- '
APPD: PROD. CODE. SIZE DWG.NO. RE V. FINISH (SPEC.) DAiE: appo. B 3 7.-7 ei s o (CUST.) SCALE CONT. CN
. . . . - = _
l --
.s h . .
,, m....- .
y - _- -- _ 4 l 3
~
r
~ .
y . - -
' ear ~ . . D . q 2 1 l
1 A- gV P' i C ! I l 1 h. e . .;. (0 i b; - 0 rnd I'
. Os '
g- . B . l t i i i -
,n !
i c 1 i f 1
; panr oviem em.47, ptaxe D "R "^"E' y,,% pm.. !A 'W'^BER DCO R N" C-J 2 6 ? 18. A D. j ?.7 %8 A .a i s747. F A.J 27 2.97 a -B 0.J29535 A J I S747.F A.J 27 297 . i ~
l 4
Q 2 1 REVISIO.NS [ C N HIV Ot SCEiP flore OAl( APPD. e l SNce.hmenI - ogy t AE 1511 paSeqg g 103
~y n .
1 I
.) s s
i e v 6- - 4/<
/ '
i . . - -J 3 ' TI
, FULLstLE % 1 nao secnow A-a . APERTURE u xo -
l4 , , CARD l B.- Also Avdlable On _ _( Aperiarr e . -,1 ,
.g \} -.
3g M- *1
/ i
- ,p\v
/ ', .
e v-W ALF 517 E . E AC.E VIEW _ . _ _
. FILE gQi. ',
OF DETAIL *6 .. T - FI'Md '_ ,
..u- .
ILt if _ TOLERAt4CES ORDER NO.
. . OC' beoi V f, ' ~'* * ~"
FRAC. + - DR BY.%4. CURtaEV.,
,I D EL,. + - TITLE '
y C- ANG. + - DATE : 5-#J 77 Cl(ECK BY; Assv-Ou ree Ocom oU" + l ! FOR 37 Vd 7AATERIAL (SPEC.) DATE: A F'PD: B.R. Door l 32V4 - PHODUCT SIZE DWG. NO. REY. c J ? 87 I& O 1 nNISH (SPEC.) D (CUST.) SCALE l'. ;W I . Uf4 G
.+ . % df060/m -d 7 ~
I
l l l
. i l ^ ' ~ ~ ' ' ^ ~ ^'
eme.sg " " ^
, h%ihebeS ammhe^_ . - -- g ege ^ y- - 4 , i %e *..
a e 4 m 0 D 1
- 1 A -- - - , _ _ _
y, / \ 1 iv i a A- ; l i 1 1 I
- l C
a e g l 4 B -- .O . v. t t O h B 9 e l i t i I l
,g , , . 1 .h . , . 1 S
w i a .
-- ,- w ~ ~ - e% - , . - ,n - -
I l
r- "
,r . i Y 2 1
REV!S'JNS g $lt __ ctscniesics oAit ar'8 0- 3
; ____ . _ _ 1
__ __L _ -l-- i : _-
.+ - . . A Hache+ i s l ,Si-ML- AE-1511 !
I
'f' 79 99 of 1o% I l t_ v , y _ . ~
t TI : b APERTURE : l
' CARD ! t % . I l s : l . r e Also AvailaMe On ' l l Aperture Card e i ,
Puu. Size Sect. A-A J ; i j , l !
. l , l I
g (' t l i
~ l* FILE . :g; . , ,. ,g RF144-f . g. __. . {g -)6"- i ! .~~~- -: l _ ~
PART .i N1 h1 E.R. Rein re. pty .. r' l MVMBER 0009. PaMEt D oOR .C.0 5 EP. ! C-J 2B717- A . D-J 2.7833 A J t 8747-F 37 % ' I C-J 2811 i- 2 . D-J 295Ero A-J 16147- F 32 V4. - l l V .. i TO!.ERANCES ORDER f40 FRAC. + - h03!Si - ~~ ~ ~ DEC + - DR UY:r/..cuptiN3 TITLE yy** , _ DATC: S- t L n_ ._ ASSN IWWC_R COof2 5 CHECK BY: pgg _ so no d MATERIAL (SPEC.) DATE: B. R. Door
- [f. --
PRODUCT SIZ E ~D .','G. f 40. c REV, FINISH (SFEC.) APPD:
~
J 2 8 117 0 (CUST.) SC Alf. s';uta l O.*J ' *
+ . $@//v50/o 0 dB- , - _ --. _ _ , _.,3--- . _ _ _ _ ___y. _ _ - __-
< _ _ , . _ . --= --
o . l 7 ~%..l
- 6 5 '
, e.. ' :. ...:3 ..- .: : . .- :.~ . : . : ; _ . . 4 . .. .:
u
- AHac. Men 4 - -
o ST- H L- AE- L511 -
%Sel of'10% ,M . _ ,,y s.>
l p ,
., , 1 . . w, . . ,
j 6L 6
, f :.(!l , J.
pl c ,p ,- i; rutt sne sen F utt Sit.e__s..e. ct. B. 6 c - 3 /
.g.g. e i , 1 i !
I i h.. ,.l
+ i j , Q l s I- n ' f -
i 1 ; rl i l i d
. !Ulj ,
[ 70 { 'glI i 1 i i - 0 - 4 l
~
l- ] l I e . -] . l - 4 I I [e > i l
.O l j i
l l l l ' S
-
- l l I l l 3
' l l 1 1 I - , l L
D'3 I -
- ! @ l
.. . l l I i
- f. - -
- I I l l A
l____ i 4 _)A. Fin.t StIE
.. .55kr;aMT21 FquOvn!B _ Ecei 6tw or ~~
Ritut A _u_.C m. . _b oar., % o w n . cEFATCW , N- 6 1 7 i c l
,,. ., t......-.. . .......I........ . . . . . . . .1 .. ... ..s . . . J . .~ .. . 5 ..m-
_.,.r
,,,._..-w_..
A 3 2 --* I -
...; .m. ,
OgUQo._
- 03 $CastPl QN (C. _% .(%l
_, p
, i w __ ; _
r- - i y & :
- .. . 'r- ---- :
- o l n; .
; i li, -
i
,,.,_t_
I
~.a I
o h=.. :I , ,g
~
l,- I i
, ,I .i . i i i
i p,' i i , i i _ j' - l l l 1 ,1
- L' l l --
t
.' I, e - lI .
1 l i i ' (g I l ' i _ i i i t, i . 40-0 i, I i i i 1 i l
,I * . i l .
ll i .I l I l C - l 3 li l J,. _c i ' ,'! s is. ';,* - il, l. 1 i , I i it i o i' , , ..
! .i : ; ,ti .@
i- i ci . . ,, _ ; w ,' i ,i , i -
,i qI*
- i'4 i -
j f - i - io__. ,i . , i, ___ _- _ e. s I I i i
.i 'i \ lt ~ 'j }
ll . l
. I;I .
h, . .( . . .l R i (p-r--@~ ~ l' ; ..
, i 'l \ .I !
j,l I _ i i I [ i, i l ti ggg i....___.i l _
,l * -
Q. . m l n. L . p,9,g _ *- ; .a. l g- :
~
a . SiOE. ELCvA'tio9 5e (~OLt. SlIE CETAIL Orr l 4 cesmite siev l '
. r.v... - .i! , ., s I TI. ..i J t.t_ 9 Sm m 09 R:AME [
t b.i
' O APERW U ; ,, '.$_. q i-E I *r - CARD . ! ; i -
[1 ') B_GE,E49 UN t.CR' .n's? 24 s '/2 F t./.T W O. S Aca; , l-
.. 3, . 2 ns .as4i u. w ;r. . .O. u . w u.u.wa umu. . ._ 'l- ~
V'*i '.,. . Abo Avalkbh Da -i;,- -e .3 23c,e I - btoc., s12,s:t r>ct. i.,-'
,_ _ _ _ _ .- _ _ d _ _ __. / . Aperture Card :2t. . .u wo i ca .scet o. u % d T ,ur u t rm . t -- !s i
Tuts see i1 'i'C J 2BllZ - lC0 4' v : 's ui % c l t' 3- . V.w., 4. 4 'S
- '--6 584~5 EC% t'.C.5 *'* 12 m % Flai u O. Met.u.
- i- ;
_1l_ $. i b . 9 0 4'i l B MOk*M* Y PC Ktwoc.w. j it -
.Il
- I . '? 'O .'J 2%18 l ASS' c .,ce n '.. - : 5__. .
l I8 :D J15n10 . I A *a*.' = ->.t u G vee'.o.a r ut .S;
'i . ? Y =_T.J, . O.# %.L ge.,.c , ...,%
h . j,, ,,k . l o.oin;o.
' % A % -s- , '".. .:; :;.,;rettr.mm ', h. ,0. 5..,6..f....._, .. i.".._ - ' ' :.* C '.,/ 5 ."17 C -5 t Oco:
- F' 6: A'4 E g*W l'll b1E D Il
.r ~"-- **
- e s e .
sis ;, ,QQ 7 )
, f_
c . [~*
/ / - "..t*.bvio . 47 6wsW4 "" N "I A u.: am ..; J T*)-[50t'*o* T o - ,,.,.. ...... .., 1., . . bs.t v A L - ...
_..,__._..4 . _ . _ .. . _L _ ._ . = .3 . . I. ..
. _2- ..~..- . .I . . . . . . . . . .
_%510S0/5D-OY
- ^ - ~ ^^ ==
8 l 7 6 5
'E l l
1
. . ,. ,1 i * " , l * . i l , 1 . %. . 3 1 37 4 i
i . - 1 1 i [o A- ~Ia, i
!.- o li l.
7'
, 7, 7' % i A g i - * . .A, ,s . :
- 1 1,\ l i Il '
ls ). ,' l 6 8 !. I, 6 d p r.
- l. .. ... .. - ..
~ )g4/g\ :s l ed s :
ll'
. B -
0 I!. _.e
\ . 1 C . I n N
anur.1 l,g . e 1 tj
- i .4 N . e k. U nx a .- a m L- .-
- I . m
?- F rec , 'i (G
31
'! 2 7I .11. . .. . ?
i*
/&
s I
. , d i 'A-1
( o.
//
W
.!.s ,%. s. /N - = *
[
- A ><
s Da ' t, g ' e
. . s )
g. I- . *
. e y , . e i ! . j $
r . i 1 q e 4_ q_t . I
- i. ,
- . - , i bl y nv. . __$riCTiot.1 A. A . l p .. m .. ..e e. .- . . . . .....e.ee.....' .. . , , , . . . . . . -e - ]
y., __ _ . .- -w----- -
, l 1
n -
. _ __ . .....a__- - 1 - =
4 4 1 l l 3 2 'C. l w.. a a im li !
- .=. a
- x. .m..
.. w . . .r= - ,y --
i y , ,- i - i -
- l. - - ....i . .
.. i -l I
q; - AMachment
. r--- -
- s gr_ ut AE- 151) .
p o i r-
'pq c of lot . I l .. .
1 i 1 . g , I '
' APERTURE .
i
.' CARD j s .
I i & .
' -2
- Also Available On I @ % Aperture Card i ,
b - i y , . FILE I r l RM104 g 4 - i
* .d.,,,.
I i . jLC. 8, i-}q 8 _ .per 'e._'.-.
. 7 -
l '
' t--
llO4 IPART SJVMMR a ; i tt *", , PART N AMt'. 'CWdi
- l 4, I i
U L./f d,ri5* I
~
l C.J 20 *Ill AMT UOOR IM*)iori i i - g, 4 ;
. .I' , W L 2 C J70'llO AW 0004 CUT btOG l l '
B. J 2 5CO G N.V LNF.uP. B oaf 2D L--- --l eJ
. "b 4
l {
- l g _A.J19 b50 V. c c o Et.cr r'. I -
r0 st 5 t'.', .J 29 5 7.9 I I C.o W Rc 5Tcte nuGt.t. ~2
.-p p ..
(c A J ?9 (o S ~5 AOu"1 tvti
* * * &/R View C EECT. "n.4Ri) "I A.Bl444 %} g s .c. --
uY.Bcuo t.OuCSivE T,rc % [a,k-- m} rzi j -- in . = y ati - 1
~ '-- - ' s,d l- A
- h A\. I .
A
.f [ (
4hkrm p_sKN x x x , : e W5 e s.; s %, 4M W.--
^
i ce x x x 1 x - N CTIC*4 6 6 g B l=6
,T N .yp *
- sr 2
~ e lOLLHArnCLS ORCLR 140. ,- rnie. -
E."iOS,9f -~~ - 1 etc + - D 'i ' v. . c ov er n.> . nitt . ' )* 1C50 lu plt.CU.
. ANG. + -
IDh f.1 A l[RI A L (J LC.) o o .A b y f icy
,k, Q {"/,c"y .b , , ,
k./
, ' l' 6H U .'. C, o . O nt V - Iat.G1 ($f'lC ) :,,- , -l 0s..lf5Til lD ,) - .c...,
y :. ,
,.}.,' 'l f. ->Q l' ~~~ . $ 9 e g g ,4 g y . . m ....... , '
v -.
e ------l__..._ r i 6 -.. lm --.-- - _ - 5 i MOTE :
- b '
lo .- ,j - - raevove crvecese eumaitt's o r ,,y - L:a s s AL o a e u,5_ cn. e ,
~.
8 s u ics s st2-icAt. 64ot.G 47 g i
- es A -- , , l f
. i ,5 r
i -jC
-['4I((-
g ^ :j / '
- q'"!. _, - - .- t ,, *, , L e,r ,a ,a s . i' 5-. ;
- P.,:,, , i -
a .r I i' ' f, \g y- I g a [;.f !h
% N i / .l > I r -J-4-,e. .+-
i
- j' ;
I; .
% - 4 y, p,,[.. i{i<t.,i i l i i- -
l ' h: j
.' .. g [
i i t_ g O j O I}_,99 o l
/fl .l 8"D l
I I;<'< ;g
.C i
N O[i. LO l? i ,
, 8 o.
F L-
'l / fi '" 4 !
l C' ' i omittmc cevm
, O e '
r- i
'g . - . .
9 {- f,/ r, (/ lll
/
j
,I i
8
'o " mED et*J . i I4 w i r, - . .%sdoe g ], ' . '._ r n . i ,4 'd .
4 v u ! .
- i. i P NM::q , ,
t i ? :i.-
.i. 1- : . - ,.4 ' a l, qnili .9 i . - ! g3 ,: it i i . 'I ! ! in l l e
(. l
,;_'j./ .
il .
- I .
_klo. ne._.! Rtwve ST7An a=,t
. .g A-a i
u w.r.t,~c 4.
.nn n, I ' / suippcosReptau g . . -f-. / . e, c.a tw ! pteve.tico (t%: ho ost.wn %=i) ,
A( C[
.;2 / . .
l i ..
. }. . f f , .
g *
.4 -
C' l
- gg . bur.*i.'i:E - @ 5 ;w _ _ -y --
t w =3i on i
. .-w_. ;Q 3 :
e-
; p. ,,,_._. _ .._ _ _ .. _ _ _ w 3 -
- , .' - -a, .m - . =
.r 44 , 'p -
6 24 ...,__w..-.. ~.?.*,Z.
;j /!. /. . ~ . g . - 2'//~.(/ .' , h .
i -
}
eMM f .
~'
_ "> 4- 3 c'q 6 . 4
- %- Q G F. ROP g' - . .: ;A i ! ~-
t56 - -- ll - . t l 3 CCof? .-
- f. .i
(((l 7 N -
\> g.c c t' .
g S. _u c.T. .
.ic,_M.
- 1$ - a Oum v,. se m.o.t- ; I I
1 g i I L........-....s....'.... .. ..... . . . . . . . . . . . . . . . .... ....... . . . .. . . .. .;.. . . ; ; s . I
i
... -- - _ _ _ _ ,,, . o l 'f 4 * .V -
3 l 2 6
- I I,
4 vi'., t;m _ .
. Lan . u r . E'l. ' ,c.".-} *
- 3. . { ,
l . q :
* . 3 i * .
I. g ' (Mfachment l '
$T-ML Misl j . 'P j . .- , Q 1011 ' .
_ no.w . . e,o. u m co.-o o> APERTURE . {g@ fwo 'AP roc /i.ih *~ Jar.J.W~cW , i:% @Q9 D T -
...r..-
- -Cc.._ _ < .
- f. t. N., ,'t.. '..
_ . n_ ._ l. ,i'c,; - - Also Available O* -
. Aperture (. r.,
p.t i T ,. s . c .= ~M. ._u_ .
. . . . ...J \ :* .b .
3 ts- -3b- ~ . i w coert Ctosen OW. . in, ract humaasc: Pa n r 6.2,. u e l(A.w
. s ..uc. coco , Wutu 5DAun iS I o.Jin vi A *2*,v. ocoE
- renv e . g ,. wi .w,...e 's ~ ' .l
_Ditt Ssi' o uuce a
-2 iEIf.I't$ 5 T.,uippiwa sicar . 7 "8 l watt use ecomes 3 IC.J2':. ;S- - - , A S*.N G L.a ss e c.f..,,s . a u s.o t e . l*' '
A 64 n 2i) . B.u s st:4 4 I S ,. 2U t r.- l saddN ovs53 r= pus .ou sic.a 3.- 6 li
$ { 0. < 6 8 4 8 -(2Ct's SCf1 CW h =* 8 0 5 E * '/I P o w 4 0 1O
(=
! O J 7.? '.1 $ jGL ads PAurit a.Ov.Act u t. is taut 18,'y ,e
- y.^/64,.
~3
- 6 I A .J_~r.'l l.2.O } P uiT_Y
. . O c. Sc ' 2_0_s A- _l oocrt. CLctr!R
- D4 wiTia'T f LeuG t.co.4 d i
, C) A. S it ' 58. t. ' CcClic
- tratra _
.. . 4*q ,
80 r* ~ il l Se,'!r. B .h tg ra r).cac t . Eur' i gl f2 sc.rz C w Se . 8/3w3. . tr] %.20 = '/y FA 4 4. u8c.Ovat ( Q,%yus ,, *& (c.tep:.c.e )gg[<
. _1_.- ,
l'l D.MI e6 AcG lLf1W.Lewf. tk.LT . S/6 *st. a 2 ue m uQ . 2_ 1 j 13 c .c. t s" .5. o A ltas?x u vT 3,e.it. g 14 A.JIt,r h { Auck;Cf#.-." "J)Chltit41.4*>'C'1 t/~4)0 4 tc P S_ _15__t..J_2_.1 _ .. 84 P'Jf.AU to $5us4 8'E C' ' SC E uot t'. ,. C+4
- tci .1 A'.
6 2 Il R *
-j D _ !r. . _JD' 'lpa ' P ,:@ FILE R N'l o-l q..m. ,o @, -
_n w . 3
/ bt'CT to h- * ',_ i A . l R.M On.b,.05 l 1DLLR At*LLS OHCLFut43 ,p n IRAC. + - ' - ~3 cu
- D[C. + *
- *b s;alf ?.22 81 O # O'"'T '.!C' I3ILL b 6W Flh}AL e* ,,
6 ANG. + 9 'S
/g'f C A U ' e, f p. , h) k.. DCOT.s e% .
{d l MAllkl4L (Si' C ) ?_3,l * - r,, , s. l
.g .
l# L V. nr.a es tc j 'T.' I A.us ;,I'oSiit*lJ.'.G , ,i 7,3, P.,1 tsO. 0 ,
. ' w. . , , , + . ; r- .
. $..__ _ . a. . -a..u'--._.._.-..... &/[Q .-. . . . . f
- l 1
y ,
- m- ma - - w .nm e.a ^
*=aa=**==- - - ^ ^ '
_ . ~ - . . _ , , , _ . . _ _ _ . _ . . . . . . . . . . . , . . . ...-._.,.......,.-.........-..; 8 7 6
] l 5 ** . :: "..~ ; .
e
- .. i'~;. .* .=::::.*::::.~
. * . . J. * ** # 4 . ..T.?..~...*.T.!'""'*
e,
- s. .
j
.o -
l.E._
". ), . ,1 * . * .
a
- e-8 .,7
- ~ p A -a . o % 7 - 6 , TG5.Li. n:. e mu wuom
.som. .,c. co w. .. , g.. .e -A ,,,a *o sQt l ; . _ _ . _. [ -
Ii (i A
~~l i 1 5
t i 's I ..
,1 ,
g L -
- M .1 -
lh\ k '
} f lp ,I,b f}
i y
.,\ . . .g lq g _ /a tug. v oosato 8
n, =I O I h
,,4 o ,w u s. e s., sv r ei. I o 3,=.me.(e.ct t m r J ,v.e
[ 4: ' u. g. c 5; w o e m c o v im ,. i. _ ; j
-l -.~ , nw sma a vseo 1 i i.
vi
- jl l 4 l e1 k
e'- r m.ma
;. ~.- E ' . ?-
k :
. . : a u c uo t e>o w e4cw . .r dl- l 5 ! .~Ti. chi)<iG - j'l 8 e . :: .t I 6uiccao tooto i J.g.._. l z P; e I c g~ J---
p . .n t, j];qowtinsvous uouw overneu. gai.4ast l p 40.{ j ei t eoca. wit.4 io . u
. g T<5 & s ou Fu c,cs. e ]
i- *
. i r ! l, . . .
ii I i _% ,uwceev , N./l?: swe ou corma . e j.) W;,,--] =.*
,{ , ., _y;
- i. -
A" ruu.vnoia weoo e(ocx 4 e DJ')LC.2 ..S~4'?.vF09. e.o n or.o in o m - [#8),
) -P. iGH. T_.M_ t u. c Ou.t S.w_im. ' -- tWI /
_ cuss nocv. tevtesto ou su.swiuc,
~ ' a. 'N
- _ Surcr'A-A 3; t .x C_e L.l' '/4ATu4._C_8't_64_Ie44..
w v t is ema n oco (ta.f. 3 a, m,
,em,,se m x m oc< s- es's'~ < es -- ' '.a "- >=c t.
i, o ooe. .o ., . oc. ,i I en l . t l < 2 T/*1rrYE.rt K s ~~~ atT17euxus lu. .;T.E"O d .' sN,. 81, _D % N..:.*.' -%.. _ f*';us _Rk% .
~~ ~ , - - ,u, -
_. ,ug,4 il G A. l l a G Fn . G L A S S 5"C a u E 4'/.s fuer. P cia
,. m "~. g
_ = - l . ig curw ' roc.u '"u.
; e am is.. - bi L.w_s - -
4
- 1, 1 -
l _oooi4 r=
- 6. Y - 99E- r
- i j, - . - 6=u g g . 1 , .
ns
- I
.t : ~~ e .
I ~7 7 i c j s _ ,. . ae _ 3
. 1
. , , ,,.y- - ._---- -. m.a.,a.ar o s e ^ ^ - - ._ . 1 l l 1 . , -.. .., . 3 . ...... T ,..., ass.....g.aw.d*.%. - v 9 i 2
....,.o, , . .. . . s_c i. si a . ei s.c he tio n. case meno. -
a > g AHoch ment. * ..' - .' t
.' ST-H L . AE- 151 P. - ;
9 .:. Th3 e) Q 4,
- ,;j .
6
* . .? l . . . -- ~ -
- 11 O A RE tt4F. D L'A7c's tu AREA * ,k. ,
_oF 000Q CLOSER. Spot oft , , , .
. " Tac.4 WEtoco are pnovica - ] ,.. -
aDOn tioWt.t. rappim4c, Tusco4 css .
- APERTURE . .: _.
9 FOR Ct.osetsu iA ta.ScRaws g' .
. . e. -- 9 'Also Avel.Me On - *
- Apertere Cassi .. - I -
'.e- i . s t .
_ C ) ;
---.dt"J1 E
- op r:3. ut. Eous_praciar: ' -
._ ..c -FotG".R. A 0 asA*, iAcoc L *SiO.'l ELC1C1 Sic ' "* - i ST E n < G. MC Oult e s u FRt.ME ,*. .* . ~
i . ; 3 .
, 1 4 .. >
,e .gtosuns sTrio Aants e
,. .,, i = ~ .. .- ,?
pan 7 _w a. _...2 ,- -. Y W R n M Att x*:, .~ 3: .Y. .. O.J Z S. ,1 <t_2, 3 'q . 3_.7 %. %d_l t* % [ 0.J*L9 ?.69. t -2 %.'/z .17.'4-. 31'4: lIC*-s l
~ .i . . _ o ,, .
=- .
. . )g
(- _ t
. .. . _I eq. , ;8 .
3. m uo. sertcws h 8 , L nao. . -~--
~
oc. o, 0 t- -a
- )I, . -p b ^ , ^,.p(, ,Q . c. , r ue n.wo eext pite.
g--
.Lo) 3 _
w , ,, , , ,., y,. n N gg44o.q . . A /.' - - y .(' ."lp W' ' : .L.T-s htC Lb c e T ait,-o- r- - - ein w.a.e 'en
- es J.Me. r [ l. 6 LEdWNG # xew!=
~
1LL* 1 - 2=== ,,, h 1 , eguoED TB l
. _ _ _ _ _ . ._2 - .
eoutse 0 l .
,i',.* . ! e . .,._,,. , . . . .... . ' . . y os o g .e eis.
e Is ls,ga6 i v . S-
..f .
QSyf 835+Ij5.,., IFaua ao-ggg ,
~
A { p..*:.. 3,9 . E8 , d... N. M -- EU" a r e, r) t; i. s - r c % ,x K -
.....:.,----.- m;-- 'o n g, yg t e,7 ;, gp3,,3 g ,, 33 , :;,
3,,,33 cyf ' $
. .gv isatt o r " g.w ae m .r,;; n :3 .; , .-
W%
~p . d .* l.' b ' ;;m. .
7_ [- ;,- [ e , O.e , ' * * * .- c
tt t lut s u nt h 1 I -
- ST- HL- RC~ lS \ i e,dof l09 !
File R8440-1 Page T1-1 Issued: 6-6-78 1 I . InsI EEEEEE E E- 1 1 I TEST ASSEMBLY. l The fire test assembly consisted of a single swing, 1-3/4 in. thick special purpose type fire door, and frame assembly. , The door was provided with a full mortise type single-point latch. j DOOR The door was designed for an opening 36 in. in width and j l 80 in. in height. The door consisted of No. 11 gauge steel faces bonded ! to a 1-1/4 in. thick polystyrene core board with Scotch Grio Insulation Adhesive No. 321. Febrication of the test door . was witnessed by a representative of Underwriters Laboratories l Inc. l
%e construction details of the doors are as shown on ILLS. 6 i 4.hrough 17. l ; FRAME The pressed steel single unit frame in which the door was mounted consisted of No. 11 gauge steel, with anchers ,
for fastening into a masonry wall.
. HARDifARE The door was provided with a continuous hinge mounted 3 to the frame and door with No. 10 screws, 7-3/4 in. O.C. . )
i l The door incorporated a Listed mortise type single- ' point latch, with a 3/4 in. throw, secured to the doer with - machine screws. . , I INSTALLATION * '
.m The door was built into a 12 in, thick brick wall in a test frame. After the door.was installed, the clearances averaged 3/16 in. along the top, 0 in. along the hinged edge, 3/32 in, along the latch edge and 5/16 in, above the sill.
The general apperaance of the installed assembly is shown by ILLS. 1 and 2. l l _ _ _ . , . - . . - - ~ . ---
o ,
.... u ....
ST- HL- AE-151 I eI W IDE Page T1-2 Issued: 6-6-78 File R8440-1 FIRE ENDURANCE TEST:
' METHOD Af ter the brick wall had seasoned, the fire test was conducted in accordance with the Standard for Fire Test of Door
- Assemblies, OL10B. observations were made on the Throughout the fire test,the condition of the exposed and unexpected character of the fire, faces, and all developments pertinent to the door as a fire barrier with special reference to stability and flame passage. RESULTS Observations Of Fire Side The fire was luminuous and well-distributed during the fire test. The temperatures within the furnace chamber were controlled in accordance with the Standard Time-Temperature Curve as shown in ILL. 3. The steel faces of the doors began to bow and b'lge durinc After 30 min, no additional bowing the first minute of the test. or bucklinc was observed for the remainder of the 180 min fire test. After 50 min of the exposure, glass began to melt on the surface of the door. This continued uniil tre glass melted completely through af ter 9 hr and 37 min of fire exposure. The general appearance of the exposed face af ter the fire exposure and before application of the hose stream is shown by ILL. 5. Observation Of Unexposed Side
~ The deflections of the door were determined by measurements at about the center-point of the door on a horizontal line at midheight. The f ace of the door bowed into the fire a maximum of 1-1/2 in. at the center point of the door at 180 min . .- of fire exposure.
The hinge edges moved tight against the fra'me and the bottom of the door settled on the sill during the first 15 min of fire exposure. However, the latch edge, at the midheight of the door, deflected a maximum of 3/8 in. away from the stop of the f rame
. a t 180 min .
After 1 hr, 37 min of fire exposure, the top 1/3 of the glass opening melted into the exposed side of the door. The average unexposed surface temperature was 80 F prior After 30 min of fire exposure, the to the start of the test. average surface temperature rise was 1110 F. The recorded temperatures of the unexposed surf ace are shown on ILL. 4.
AMachmefe 7_ ML. AE-15tl e,D'81OT eTj! "'d Page T1-3 . Issued 6-6-78 }l{ File R8440-1 9.
.?
HOSE STREAM TEST _: '
? v% -
, METHOD :e W Immediately after the 180 min fire exposure, the assembly Q j' was withdrawn from the furnace chamber and the door was subf iijacted to the impact and cooling ef fects of the 45 psi hose strea.1 as M:~
- l. specified in the Standard for 3 hr doors. n j:,.
RESULTS i;? l ) the faces of the ~; During application of the hose stream, Normal amounts of water were doors had a tendency to flatten. ilo through projected through the edges and above the sill. .
.fr 9;
openings developed. A maximum' separation of 1-5/8 in. occurred between the frame fi stop and the latch edge of the door, at the midheight. $. :.
+
i m
. P , i 8
N;:
.. . .'C- :
5I c wan/ssr i J l- I I f i I i I ), 4
- ----.---nn -----,-w- - . . , -,n- w,w -r----- --- ---------a ,-+,--,e-,, r-.-,-- - - -,,,,-r-,m, mr-,--m,---.-- s w,-, , -,-n- , - - - - - - -
% @ ment ST-W AE-1511 . gg, %cMof'lof 'f{
Issued: 6-6-78 i3 l Page C1 File R8440-1
- p CONCLUSION b ,
I
- The following conclusions represent the judgement of ?k Underwriters Laboratories Inc. based upon the results of jj' the examination and tests presented in this Report as they y relate to established principles and previously recorded data.
,f FIRE RETARDANT PROPERTIES _
3I Single swinging special purpose type doors for openings installed ,X not exceeding 36 in. in width and 80 in. in height,as describ } in openings in walls for 3 hr locations. ' N The epening which occurred after the glass melted
- our of the door, failed to meet the requirements as specified" Fire Tes in Standard For safety, UL108, The 3/4 in. latch bolt remained effective throughout 1 E
the fire test. - The separation of the door edges from the frame stops, were within the limits specified by the Standard. No fire passed through or around the assembly during the [ y 4 180 min fire test. . . The maximum deflection was 1-1/2 in. af ter 180 min cf fire exposure. ' The average unexposed surface temperature rise measured af ter 30 min of fire exposure was 1110 F. .l
.,1, EOSE STREAM RESISTANCE: -
The application of the 45 psi hose stream immediately after the fire test did not dislodge or appear to weaken the assembly l
;s.
for it remained securely in position.
- REVISED CONSTRUCTION: '
The submitter has proposed to revise thewould
'This construction prevent by ,
elimenating the glass light in the door. ; an opening from occurring should the glass melt out. j Accordingly, it is judged that when constructed the special with the revised details, and as described in this Report, purpose type fire door and frame assembly provides protection for openings in walls for 3 hr locations. ! l i I
. 1
Abe hmen+ 5-Ht-M-\bn S
] 'Pajc.5belos Page C2 Issued: 6-6-78 File R8440-1 CLASSIFICATION AND FOLLOW-UP SERVICE:
A sample of the product covered by this Report has been found to comply with the requirements for Fire Hazard only covering the class and the product is judged to be eligible l' for Classification and Follow-Up Service. The manufacturer is authorized to use the Laboratories' Classification Marking on,such products which comply with the Follow-Up Service Procedure and any other applicable requirements of Underwriters Laboratories Inc. Only those products which properly bear the Laboratories' Classification Marking are considered as Classified by Underwriters Laboratories Inc. The fire door Classification Marking reading, "Special ' Purpose Fire Door and Frame Assembly, Fire Rating: 3 Hr (A)" will cover the size, design, and construction of the door. Report by: Reviewed by:
~
l*bs*w f :=
^ ^ , f WILLIAM R. HARTMANN HOWARD S. ENGERMAN Projec' Engineer Senior Project Engineer Fire Protection Department Fire Protection Department .
WRH/ HSE:sn i I 4 G l l e
- - - - - - --- - - . _ _ _ _ _ __ _ , __}}