4 2.
Accordingly, the license is amended by changes to the Technical Specifications as indicated in the attachment to this license amendment and Paragraph 2.C.(2) of Facility Operating License No. NPF-87 is hereby 1
amended to read as follows:
l 2.
Technical Soecifications and Environmental Protection Plan i
The Technical Specifications contained in Appendix A, as revised through Amendment No. 49, and the Environmental Protection Plan contained in Appendix B, both of which are attached hereto, are hereby incorporated in the license. The licensee shall operate the facility in accordance with the Technical Specifications and the 4
Environmental Protection Plan.
3.
The license amendment is effective as of its date of issuance to be implemented within 30 days.
FOR THE NUCLEAR REGULATORY COMMISSION Timothy J. Polich, Project Manager Project Directorate IV-1 Division of Reactor Projects III/IV
]
Office of Nuclear Reactor Regulation j
Attachment:
Changes to the Technical
~
Specifications Date of Issuance: April I, 1996 i
9604120322 960411 PDR ADOCK 05000445 P
0
. 2.
Accordingly, the license is amended by changes to the Technical Specifications as indicated in the attachment to this license amendment and Paragraph 2.C.(2) of Facility Operating License No. NPF-89 is hereby amended to read as follows:
(2) Technical Snecifications and Environmental Protection Plan The Technical Specifications contained in Appendix A, as revised through Amendment No. 35, and the Environmental Protection Plan contained in Appendix B, are hereby incorporated into this license.
TU Electric shall operate the facility in accordance with the Technical Specifications and the Environmental Protection Plan.
3.
This license amendment is effective as of its date of issuance to be implemented within 30 days.
FOR THE NUCLEAR REGULATORY COMMISSION Timothy J.
olich, Project Manager Project Directorate IV-1 Division of Reactor Projects III/IV Office of Nuclear Reactor Regulation
Attachment:
Changes to the Technical Specifications Date of Issuance: April 1, 1996
Mr. C. Lance Terry TU Electric Company Comanche Peak, Units 1 and 2 l
cc:
Senior Resident Inspector Honorable Dale McPherson U.S. Nuclear Regulatory Commission County Judge l
P. O. Box 1029 P. O. Box 851 l
Granbury, TX 76048 Glen Rose, TX 76043 Regional Administrator, Region IV Office of the Governor U.S. Nuclear Regulatory Commission ATTN:
Susan Rieff, Director 611 Ryan Plaza Drive, Suite 400 Environmental Policy Arlington, TX 76011 P. O. Box 12428 Austin, TX 78711 Mrs. Juanita Ellis, President Citizens Association for Sound Energy Arthur C. Tate, Director 1426 South Polk Division of Compliance & Inspection Dal.las, TX 75224 Bureau of Radiation Control Texas Department of Health Mr. Roger D. Walker, Manager 1100 West 49th Street Regulatory Affairs for Nuclear Austin, TX 78756-3189 Engineering Organization 1
Texas Utilities Electric Company 1601 Bryan Street, 12th Floor Dallas, TX 75201-3411 Texas Utilities Electric Company c/o Bethesda Licensing 3 Metro Center, Suite 610 Bethesda, MD 20814 George L. Edgar, Esq.
Morgan, Lewis & Bockius 1800 M Street, N.W.
Washington, DC 20036-5869 i
l TABLE 2.2-1 (Continued)
I l
TABLE NOTATIONS NOTE 1: Overtemperature N-16 t
2[1+Ts T,-T, ] + K3 (P-P') - f, (aq) l N
K -K i
2 Where:
N Measured N-16 Power by ion chambers, T,
Cold leg temperature, "F, T*
560.5"F for Unit 1, 560.8*F for Unit 2 - Reference T, at RATED THERMAL POWER, l
K 1.150, i
K 0.0134/*F for Unit 1 2
0.0138/*F for Unit 2 l
1+rl The function generated by the lead-lag controller for i
1+rsz T, dynamic compensation, Time constants utilized in the lead-lag controller for r,,
r2 T,, r, ;t 10 s, and 72s3s, K
0.000719/psig for Unit 1 l
3 0.000720/psig for Unit 2 COMANCHE PEAK - UNIT 1 AND 2 2-9 Unit 1 - Amendment No. MrM,49 Unit 2 - Amendment No. 7,35
y TABLE 2.2-1 (Continued) k TABLE NOTATIONS (Continued) 5 g
NOTE 1:
(Continued) 2 7
P Pressurizer pressure, psig, E
P'
- t 2235 psig (Nominal RCS operating pressure),
Laplace transform operator, s,
S h
and f aq is a function of the indicated difference between top and bottom halves of deteck(ors)of the power-range neutron ion chambers; with gains to be selected based on measured instrument response during plant STARTUP tests such that:
For Unit 1 for q -
between -65% and +4%, f (aq) - 0, where q and q are percent l
(1)
RATED,THEbt POWER in the top and, bottom halves of lhe cor,e respectively,
[
and q, + g is total THERMAL POWER in percent of. RATED THERMAL POWER, O
(ii) for each percent that the magnitude of q
-q Setpoint shall be automatically reduced by 1.i exceeds -65%, the N-16 Trip 81% of its value at RATED THERMAL POWER, and (iii) for each percent that the magnitude of q
-q exceeds +4%, the N-16 Trip cc 11 Setpoint shall be automatically reduced by 2.,26% of its value at RATED
[
THERMAL POWER.
e
.