k REV. 55 LOSS OF RH COOLING UNIT 1 1BWOA r PR!-10 O

V i

A. EUREQSI ,

This procedure provides actions required to restore RH System cooling in the event RH System cooling is lost during Modes 4, 5, l or 6.

B. SIMEIQMS._.0lLINIRL101mlIl0115

1. The follouing annunciators may cause entry into this procedure:

o RH PUMP TRIP - alarm  ;

o RH PUMP 1A(B) DSCH PRESS HIGH - alarm o RH PUMP 1A(B) DSCH PRESS LOW - alarm o RH PUMP 1A(B) CC FLOW LOW - alarm ,

o RH HX CC WTR FLOW HIGH LOW - alarm o RCS SYSTEM COLD PRESS HIGH - alarm o RCS PRESS HIGH AT LOW TEMP - alarm o CC PUMP TRIP - alarm o CC SURGE TANK LEVEL HIGH LOW - alarm >

o CC PUMP DSCH PRESS LOW - alarm b(~N o REACTOR VESSEL LEVEL LOW - alarm t

2. The following symptoms may cause entry into this procedure:

o Oscillating Rd pump amps.

o Fluctuating RH Pump dsch pressure.

.o Excessive RH Pump noise or vibration, o Fluctuating Letdown Flow when on RH Letdown.

o Decreasing Reactor vessel level ,

o Increasing RCS temperature.

o Increasing RH system temperature.

3. This procedure may be entered from:

o 1BwFR-C.3, RESPONSE TO SATURATED CORE COOLING, Step 1.

o Inability to reduce RCS temperature while shutdown.

o Loss of RH System while operating in Modes 4, 5, or 6.

i 1

APPROVED l APR 5 1990

( .l EEL *?.?.

Q,, - - - --

l 9109170299 910910 POR ADOCK 05000456

! G PDR l Page 1 of 62 l .

0197Q/0018Q/011990) .

REV. 55 LOSS OF RH COOLING UNIT 1 1BWOA I PR!-30 0 .

STEP ACTION / EXPECTED RES GN5E PEIFONSE NOT OBT A4NED ..

CAUIIDH Changes in RCS pressure could teruit in inaccuracies in RCS level readings.

I CAUTIOH Any dilution of the RCS should be stopped until RER Flow has been re-established.

.s

  • ROIE

( With this procedure in effect,

  • notify the Station Director who will *
  • evaluate for GSEP conditions per *
  • Bw2P 200-1, BRWD EMERGENCY ACTION *
  • LEVELS.

1 CHEG RH SYSTEM OPERATION:

a. Verify 1A or 1B RH a. GO TO Step 2.

pump run light - LII Step continued on next page APPROVED APR 5 1990 pmanowooo asvaw O i Page 2 of 62 (0192Q/0018Q/011990)

REY.155- -LOSS,0F RH-COOLING-UNIT 1 1BWOA

, PRI-10 1 STEP - ACTION / EXPECTED RESPON5E REIFONSE NOT OBTAiNED i t

l t

Step.1_(continued)

b. Verify operating RH pump b. Attempt to stabilize RH >

parameters - SIAHLE: system operation as ,

follows:  ;

  • 'IGI-letdown flow. l
  • - Reduce RH pump flow. j
  • RH pump amps
  • Increase RCS level by . i increasing charging flow  !

RH disch presJure

  • - and/or reducing letdown  !

flow. .

  • RH disch flow l IE RH pump parameters do l
  • Reactor Vessel level not stabill:e,  ;

THEN trip the affected RH-  ;

  • RH pump noise / vibration pump and GO-TO Step 3. -}

c LVerify RCS temperature - c. Verify sufficient flow [

SIABLE OR DECEEASllln through RH RX.

3) Verify. proper-operation. J

_ of RH flow control  ;

valtos:  !

o 1RH606/618 o 1RH607/619

2) Verify sufficient CC j flow-through RH HX. j

.UE CC. system is adversely affecting RH l HX operation,

'UIEN GO~TO l 1Bw0A PRI-6.-  !

COMPONENT COOLING i

-MALFUNCTION,while continuing with this  ;

procedure at Step 2. [

t

d. RETURN TO procedure and step . APPROVED '  ;

in effect i APR 5 1990  ;

O == i i

Page 3 of 62

.(0192Q/0018Q/011990)  ;

e if

REV. SS LOSS OF RH COOLING UNIT 1 1BWOA s PRI-10 k-STEP ACTION /EEPECTED RESPON5E PE!FONSE NOT 06TaitiED 2 YERlf.Y POWER TO 4KV ESF BUSES:

a. ESF Buses - BOTH__EHERElZED: a. Restore power to the affected ESF bus per SE
  • Bus 141 bus alive light - LII direction, while continuing
  • Bus 142 bus alive light - LII with this procedure.

3 CHECK RH SYSTEM STATUS:

a. RH hot leg suction valves - a. Manually open RH suction QEEH: valves as required:

o 1RH8701A and B o 1RH8701A and B o 1RH8702A and B o 1RH8702A and B

b. RH Syste:u - INTACT: b. Isolate any leak.
  • At SE discretion, check for leaks

-)

'l 4 CBECT RCS CONDITIONS:

a. RCS Wide Range Pressure - a. Decrease RCS pressure to LESS THAN 31R_2SIG: less than 31Q_ESIG:
  • iPI- 403 o Solid Plant - Throttle
  • 1PI- 405 letdown and charging as necessary to reduce RCS pressure.

o Pzr Bubble - Manually initiate pressurizer spray to reduce RCS pressure:

o 1RY455B o 1RY455C l

o 1CV8145 II either pressure instrument has failed, l IHEH GO TO ATTACHMENT B

(page 32).

APPROVED l

[ ,r S Step continued on next page APR 5 1990 ll$$Evi?w Page 4 of 62 (0192Q/0018Q/011990)

f REV,-55 LOSS OF RH-COOLING UNIT-1 1BWOA- ';

"/~ PRI-10 -

1 ( >)  !

5TEP ACTION / EXPECTED RE5?ON5E :RE5FONSE NOT OBTAiNED j i

I Step 4 (continued)  !

b. RCS level: b. GO TO Attachment A (page 12). l$

o RVLIS AT LEASI_21%

Plenum Region

?

-OR-  !

o lLI-RYO46. RV HL' LEVEL - }

r GREATER _JHAN OR EOUAL TO 393'6" .

i

-OR- '

i o Tygon-level indication - ,

GEEAIEE THAN OR_ EQUAL TO 393'6" '

5 CHECK RH-SYSIEM STAIUS: -

a. 101 hot _ leg _ suction valves -- a. Manually open RH suction f QEEH: valves as required: -

E o' 1RH8701A and B o 1RH8701A and-B 1 o: 1RH8702A and B o 1RH8702A and B

[

b.,RH-System - INTACT: b.. Isolate any leak. ,

  • At SE~ discretion, check for  :

leaks {

i  !

l  !

L I i

t APPROVED y

, APR 5 1990 i O maAicwooo

- aa v= w

i.  ;

l  :

e Page 5 of-62 l (0192Q/0018Q/011990) {

REY. 55 LOSS 0F'RH COOL 1NG UNIT 1 1BWOA x PRI (

STEP ACTION / EXPECTED RESPON5E RESPONSE NOT OST AiNED CMlTLoli Starting redundant RH train prior to

-determining'the cause of the failure of the first train-may.cause a fallure of the redundant-RH-train.

aa e .

Heli attempt to restart the RH

a. Establish RCS cooling per train previously in service.

Bw0P RH-6, PLACING THE RH SYSTEM IN-SHUTDOWN COOLING II neither RH train-can be restored, H Eli continue attempts.to restore either RH train, and 7 -CHECK _RCS_CONDITJ0NS:

a. Verify RCS temperature - a. GO TO Step 8.

STABLE OR DECREASING

b. Verify'RCS level.- b. Recover RCS level per G M TER THAN 393'6" ATTACHMENT.A._(page 12).
c. RETURN T0 procedure and step

-. ] in effect 8 CONTINt1E ATTEMPTS TO RESTORE RH COOLIN3:

a. At-SE discretion -evacuate all

_ personnel from Unit 1 containment Step continued on-next page APPROVED APR-'5 1990 Page 6 of 62 (0192Q/0018Q/011990) m_ . . _ . _ . ._ _ ., _., . .

REV, 55 LOSS OF RH COOLING UNIT 1 IBw0A PRI-10 p

L) <

STEP ACTION / EXPECTED RESP 0fGE PE?FONSE NOT OCTmhED Step 8 (continued)

b. Continue with this procedure at step 9 IE at anytime an RH train becomes available, IllEti:
1) Immediately align the RH train for RCS cooling per Bw0P RH-6, PLACING THE RH SYSTEM IN SHUTDOWN COOLING
2) RETURN TO Step 7 of this procedure 9 SELEC"_ATLKABLLAUA Ht1ERI 1(LES"AB_ISH RCS C60LI 5:

,_.s a. Refer to Table A (page 8) to ,

( ) determine applicable

's l cooling method:

o Bleed and Feed Using Excess Letdown through Loop Drains and Normal Charging -

l ATTACHMENT C (page 33) o Steaming Intact /Non-isolated l SGs - ATECEtiEtiI_D (page 38) o Bleed and Feed Using Pzr PORVs ,

and Normal Charging -

l ATTACHMENT E (page 45) o Refuel Cavity to Fuel Pool Cooling -

l ATTACHMENT F (page 50)

o SI Pump Hot Leg Injection -

I AIIACHMENT G (page 54) o Accumulator Injection -

l ATTACHMENT H (page 58) APPROVED o Inventory Addition via EWST - APR 5 1990 ,

f xl ATTACHMENT I (page 61)

-END-samowoop l

l Page 7 of 62 (0192Q/0018Q/011990)

REV, 55 LOSS OF RH COOLING UNIT 1 IBWOA t 's PRI-10 L) 9 T! ALE _Al page 1 of_11 DETyJ,MINATION_ Qf_EEEECTIVE _ PCE_CHOLIH(i_MEIliODS t

~-

i l MODE MODE I MODE COOLING 4 5 6 METHOD NORMAL w/ hot RCS is REFUEL HEAD w/ hot RCS is Configu side adverse 4 FLOODED OFF side adverse 4 ration vent 3 vent 3 ATTACHMENT C yes yes yes yes yes yes yes yes (cage 33) _

ATTACHMENT D yes yes N/A yes N/A N/A N/A yes

_1page 38)

ATTACHMENT

- E yes yes N/A yec N/A N/A N/A yes (eage 45) ,

(O,)

ATTACHMENT 2 F N/A N/A N/A N/A yes yes N/A N/A

_ipage 50)

ATTACHMENT 1 _1 G yes yes yes yes yes yes yes yes (page 54)

ATTACHMENT H yes yes yes yes yes yes yes yes (page 58)

ATTACHMENT I N/A yes yes yes yes yes yes yes (page 61)

1. SI pump hot leg injection must be initiated as the primary means of RCS cooling and inventory control. Other methods may be used in conjunction with ATTALMENT G but not in place of it.
2. May be used as a cooling method if the boot seal is inflated and refueling cavity is being filled.
3. Refer to FIGURE IBw0A PRI-10-2 (page 10) for an acceptable hot side vent path. ,
4. The RCS is ADVERSE if ALL of the following exist:

-, a. The RCS is EDI intact (any openings) AND l An acceptable RCS hot side vent path is HQI establisted AND

\ 'l~

b.

c. ALL RCS loops are blocked (3oop stops closed or hot leg nozzle dams are installed) APP RCP/ E D APR 5 1990 Page 8 of 62 anuowuvu (01929/0018Q/011990)

r t .

REV.2 55 LOSS-0F-RH COOLING UNIT 1- 1BWOA-  :

PRI-10 D) x <

l i

e I

--t

, i 0 0 TRCS =.100 F' .,_

TRCS = 140 F [

20.0 =  ;

.la.0- i

/

- 16.0 /  :

[ /

/ l 8 o14.0-u -d  ;

gn: / t C a "12.0 / 1 gg f

4 .. / \

1 3- . -

~'

c " 10 < 0

. e1  ;

&y ,,- -r' l ae z a 0-

- t

. l' }

'g:t e- -

. 6~ 0-i

'4.0:  ;

40.0 60.0 -80.0 100.0 120.0 140.0' ;160.0 '180.0 200.0-  !

Time After Shutdown (hrs)~ )

zi

-APPROVED  !

t FIGURE IBw0A,PRI 10-1 APR 5 '1990  !

Time to Reach Saturation Following a ,ajpggoyg  ;

Loss of RHR-at Mid-Loop j i

-i i

i Page 9-of 62 i

( 0192Q/00180/011990)

REV. 55 LOSS OF RH COOLING UNIT 1 1Bw0A PRI-10

(\

0 0 Tges = 100 F -- TRCS ** 1(0 F 35.0 i

0.5 l ~ ~

2 SAFETIES / ~~~

00 -

I ,// -

NOT '

ACCEPTASLE -

25.0 -

s //

26

//

d

' 3 SAFETIES ' _ _____ ___

h 8.3 ___,,,_,,

s.<15.0 e

=  : / '

g ,

ACCEPTABLE z

E 10.0

8. s 0"j' "I"

- E^"*F- ---- --- ---- ----- - - - -

)

5.0 -- /

0.0 -

0.0 100.0 200.0 300.0 400.0 500.0 600.0 700.0 800.0 900.0 TIHE AFTER SHUIDOWN (HRS)

APPROVED TIGURE IBw0A PRI 10-2 APR 5 1999 Vent Path Required to Prevent

(]

V RCS Pressurir.ation anatowovo

      • '5 85= w (0192Q/0018Q/011990)

REV. 55 LOSS OF RH COOLING UNIT 1 3Bw0A

-m; PRI-10

.J _

w

- ~ . . . ,~...

w N W e @ F E E

.  % 3 JE.%) = =

500 ,

. . i , 1 , 4 ,- ,

4 , ,

7 I

! 1

! i3 i I

( i l i l i_ 1 I

\ i l i  !  ! l

\ i ' i ! I i ,

3

\ l I 3 ' I 8

! i  ! 3

\  ! 3 *  ! '  ! i

\ , , .

400 \i i i i i i > > ,

i\ i t

_1

! \ i! i i O I \ l !_ i 3

%  ! !I I I i i  ! I g i !I i i b,. \ i i  !  ! I e 3 v 300- \

1 . .

~

.5 . 1!

f.. W I1

. I (V) H q

\ '

i E

q  ;

e -- s x

i 20g [

3 ' m

, 1 6

3 ,i ,- x, <

_ . i .

o -

x 4 3 .

i a x , <

u.

1

- x .

x x ,

100- '

s, m  :

4 i

, ~ 1

~, e 1

l  ?

I i i e 3 I 10 100 1000 10000 l

TIME (Minutes) l APPROVED FIGUPI 1Bw0A PRI 10-3 APR 5 1990 Required Charging Flow anuowovo

,3 y3 nurn nauw

) Time From Shutdown Page 11 of 62 (0192Q/0018Q/011090)

. . _ ~ - _ . - . _. _

-r

~

i j

REV.J55L LOSS OF RH COOLING UNIT 1 1Bw0A PRI-10 (

O _ _

i

-STEP ACTION / EXPECTED RESPONSE RESFONSE NOT OBTAiNED  :

I ATIACH!iEET_.A_.QAge 1 of 20)  !

RH R'4COVERY WHILE AT REDUCED i

_ILEENIORI.10EDl.IIONS l 1 C iECK-I  :

RH PUMPS SHOULD  !

BE STOE)E2: l

a. RH pump 'ANY RUNNING a. Go To Step 2.  !
b. RCS level: b. Stop the RH Pumps and ,

Go To Step 2,  !

o RVLIS plenum region -  !

-GREATER THAN OR EOUAL  !

TC 377.  !

t

-OR- ,

o ILI-RYO46, RV HL-LEVEL -  ;

GEEAIER THAN OR FOUAL TO 3 9 3

  • 6 ',',

[

-OR- f

-t o Tygon level indication - j GREATER THAN OR EOUAL  !

to 393'6" -[

c. RH. Flow - LESS THAN 3000 gpm- -c.-Reduce RH Flow-to less than  !

or equal to 3000 gpm, _!!

d. RH pumps - HOT CAVITATING d. II the RH Pumps-continue to [

cavitate with adequate RCS- i s level, l IHEN stop the RH Pumps and i GO TO Step 2. l

.e._ RETURN TO procedure and  !

step in effect i

e l .. k l APPROVED i L i APR 5 -1990-  !

r SRAADWOOD 'L

~ ~ ~ '

O L  !

Page 12 of 62 j (0192Q/0018Q/011990) r

? [

{

i

, REV. 55 LOSS OF. RH COOLING UNIT 1 IBWOA PRI-10 STEP ACTION / EXPECTED RES;0N5E PESPONSE NOT OBTAiflED AITACEMENT A_ Qage-.2 of 2Al RH RECOVERY WHILE AT REDUCED INVENTORY CDNDITIONS 2 ISOL AT E - LETDOWN AND KNOWN

-DRAI V )ATHS:-

a. Verify /Close letdown orifice isol valves:
  • 1CV8149A
  • 1CV8149C b, Verify /Close RH to CV Ltdwn Flow Cont Viv:
  • 1CV128
c. Verify /Close.RC Loop Drn Vivs:
  • 1RC8037A
  • 1RC8037B-l.
  • 1RC8037C e'- 1RC8037D-

, 3 DETERMINE TIME TO'RCS BOILING:

! a. Time to core saturation - a.- Go To Step 4 Observe LESS THAN 5 MIIBJIES per' CAUTION-prior-to Step 4. 5 I

FIGURE IBw0A PRI 10-1,  !

! (page 9)  ;

b. GO..TO' Step 13  ;

}

t i

APPROVED }

APR 5 1990' l.

ftsview O ,

~!

i l

Page 13 of 62  :

(0192Q/0018Q/011990) .l

REV. 55 . LOSS OF RH COOLING UNIT 1 IBWOA PRI-10 STEP- ACTION / EXPECTED RES?ON5E RE5FONSE NOT OSTAiNED AIIACEMENT A (Page 3 of_201 RH RECOVERY WHILE AT REDUCED INVENTORY CONDITIONS CAUTION Personnel working in containment should be warned prior-to. refilling

-the RCS to avoid inadvertent-contamination-of' personnel working near RCS openings.

4 CHECK RCS LEVEL:-

a. RCS level: a. GO TO Step 9.

o RVLIS plenum region - LESS O THAN 377.

-OR-o ILI-RYO46, RV HL LEVEL -

LESS THAN 393'6"

-0R-4 o' Tygon level indication -

. LESS THAN 393'6"-

Step continued on next page i - APPROVED

, APR 5 1990 h

d Page 14 of 62 (0192Q/0018Q/011990)

'.REV. 55 LOSS OF RH COOLING UNIT 1 1BWOA PRI-10 i O ACTION / EXPECTED RESPON5E RESPONSE NOT OBT AiNED l

STEP  ;

AIIACHMENT A (Page 4 of 201-RH RECOVERY WHILE.AT REDUCED INVENTORY CONDITIONS Step 4 (continued)

b. RCS level: b. Go TO Step s.

o .RVLIS plenum region - LESI THAN 277.

-OR-

.o I o ILI-RYO46 RV HL LEVEL -

-LESS THAN 392'

-OR-o Tygon level indication - LESS THAN 392'

(]

5 CHECK RCS HOT SIDE VENT PATH-R ESISTANCE:

a. RCS HOT SIDE Vent Path a. II the RCS has a cold

.l resistance ACCEPTABLE leg opening, per FIGURE 1Bw0A PRI 10-2 THEH, refill the RCS per

l .ipage 10)- the.following:
1) Align at-least one.

SI Pp for Hot Leg injection.

2) Start the aligned SI Pp.
3) WHEN RCS level is .

greater than 393'6" .

  • THEH stop the SI Pp.
4) GO To Step 9.

APPROVED APR 5 1990 STSv?w Page 15.of 62 (0192Q/0018Q/011990)

REV. 55 LOSS OF-RH COOLING UNIT 1 1BWOA PRI-10 O

STEP ACTION / EXPECTED RESPONSE ,

RESPONSE NOT OST AiNED.

ATIACHMENT A-(Page_5_of E RH RECOVERY WHILE AT REDUCED INVENTORY CONDITI0liS 6 AllG'LC ENT. CHARGING PP -IE a CENT CHARGING Pp is not TO R EFI _ _ RCS: available, IEEH makeup to the RCS using

a. Open RWST to CENT CHG one of_the following:

pump suction valves: .

o Attachment I, RWST GRAVITY l

  • 1CV112D FILL (page 61) l!

i

-OR-  !

b. Close VCT to CENT CHG

-pump suction valves: o Attachment G. SI PUMP HOT -

LEG INJECTION (page 54) l! !

  • ICVll2B s
  • : ICV 112C -OR-
c. Increase charging flow o Attachment H,_ ACCUMULATOR 1

to maximum by throttling- INJECTION'(page'58) l- t open.1CV121 and 1CV182 }

d. RCS. level - GREATER THAN d. Maintain maximum charging 393'6"- flow-until RCS level is greater than 393'6",

l 7 GOTTO STEP 9'  !

l

[

t

i

?

r APPROVED:

t APR 5 1990 >

< O ==  !!

f

)

l  :

i Page 16 of 62 (0192Q/0018Q/011990) i

?

t REV. 55 LOSS OF RH COOLING UNIT 1 1BWOA-  !

PRI-10 i O  :

STEP ACTION / EXPECTED RES?ON5E RESPONSE NOT OST AiNED  ;

I t

AT_TACHMEET A-(Pare 6 of 101 .[

RH RECOVERY WHILE'AT REDUCED _!

INVENTORY CONDITIONS  ;

8 -8EFILL 3CS VIA CENT  !

CHARGIN-3 PP: .i a.-One Cent Chg Pp - a. Start a Cent Chg Pp IN SERVICE per Bw0P CV-1, STARTUP OF j THE CV SYSTEM.  !

IE a Cent Chg Pp can HQI  !

be started. i THEH makeup to the RCS  :

using one of the following: j t

i o Attachment I. RWST GRAVITY FILL (page 61) llr

-OR-o Attachment G, SI PUMP  !

HOT LEG IN.h ; TION - t (page 54) l --

l '

1

l. -OR- ,

o Attachment H,  ;

ACCUMULATOR INJEh_ .ON (page 58) l!j b.' Increase RCS level to -  !

GREATER THAN 393'6" by  ;

throttling open 1CV121 i and ICV 182--

l t

-c. Throttle 1CV121 to -i maintain desired RCS level  !

t i

9 JPENTIFY A4D ISOLATE ANY L- -RCS LEAKAG E APPROVED  ;

I- I L APR 5 1990 ii t

l BRAIDWOOD '

Ibe etTE R5 m W

_f ,

)

i l- I Page 17 of 62 l (0192Q/0018Q/011990)  !

l

REV. 55 LOSS OF RH COOLING UNIT 1 1Bw0A r 's PRI-10 C) .

STEP ACTION / EXPECTED RES?ON5E PEEFONSE NOT 06T AifiED AT.TAcliMENT A (Eage. 7. .oL201 RH RECOVERY WHILE AT REDUCED INVENTORY CONDITIDNS Il0.TE The time to boiling in the RCS should**

be taken into consideration when

  • determining how much time should be *
  • spent venting the RH system prior *
  • to taking additional actions starting *
  • at Step 10, *
                                                            • t;*********
  • NOTE *
  • If adequate time to completely vent *

()\

\_

  • the RH system is not available, air *
  • can be swept out of the RH lines by *
  • filling the RCS to 394'4" and *
  • running an RH pump at a flowrate *
  • greater than 3000 gpm.
  • 10 VEN' A:FECTE] RH If the affected RH train can T.1ALN JSING RWST: EQI be vented using the RWST THEN:
a. Maintain RCS level while venting RH System 1. Close RH Pump 1A/B Suction from RWST Isol Viv:

o 1SI8812A o 1SI8812B APPROVED Step continued on next page APR 5 1990

-m ll$$EUv$w l

I (0192Q/0018Q/011990)

i

- REV. 55 1BWOA: 4

. LOSS OF RH COOLING UNIT 1 PRI-10 4

-STEP- ACTION / EXPECTED RES?DNSE RESPONSE NOT OBTAiNED-I r

ATTACHMENT A_ Rage 8 of 20) l RH RECOVERX WHILE AT REDUCED -!

INVEllIQEY CONDITIONS __ )

I Step 10 (continued) i i

b. Align the affected RH train 2. Open RH Hot Leg  !

for venting: Suction Viv: l

1) :RH Hot Leg Suction Valves - o 1RH8701A and B [

CLOSED:- o 1RH8702A and B  !

t o 1RH8701A and'B- 3. Open RH to Cold Legs j

.o 1RH8702A'and B 1A&D/lB&C:  !

2) RH to Cold' Legs lA&D/1B&C - o 1SI8809A  !

CLQSID: o ISI8809B i g-w o ISI8809A 4. Close RH HX 1A/B Disch  !

gj o- ISIS 809B Xtie Viv: f I

3) RH Pump 1A/B Suction o 1RH8716A from RWST Isol Valve - o 1RH8716B OPEN:
5. Open lA/B 10I HX FCV:  ;

o ISI8812A i o ISI8812B o 1RH606  :

- o 1RH607 -!

c. Vent RH-train suction piping [

using high point vent valves: 6. Close-1A/B RH Ex Bypass- -!

FCV: -l o 1RH028A-(379' CWA P68)  ;

o 1RH028B-(379' CWA P75) o 1RH618  ;

o 1RH619- ,

t i

APPROVED Step continued on next page  ;

o APR5 1990 i L

O  !

( Page 19 of 62 [

(0192Q/0018Q/011990) i

REV. 55 LOSS OF RH COOLING UNIT 1 1Bw0A PRI-10

[vD STEP ACTION / EXPECTED RES?ONSE REIFONSE NOT OST AiNED ,

AI.TACEMEl[I A (Pate. 9 of._211 RH RECOVERY WHILE AT REDUCED INVElRQRY_C01{DITIONS Step 10 (continued)

d. Vent RH train discharge piping 7. Vent RH train suction using high point vent valves: piping using high point vent valves:

o 1RH026A o 1RH028A (357' S16 1A RH HX RM) (379' CWA P68) l o 1RH026B o 1RH028B (357' V16 1B RH HX RM) (379' CWA P75) l

e. Re-align the affected RH train: 8. Vent RH train discharge piping using high point
1) RH Pump 1A/B Suction from vent valves:

RWST Isol Valve - CLQSID:

(~N o 1RH026A

\s-) o 1SI8812A (357' S16 1A RH HX RM) l o 1SI8812B o 1RH026B (357' V16 1B RH HX RM)

2) RH Hot Leg Suction Valves -

CLQSED: 9. Start the affected pump at a high flow rate and o 1RH8701A and B monitor reactor vessel o 1RH8702A and B level.

When RH pump amps ano

3) RH to Cold Leg 1ALD/lB&C - disch pressure are stable, QEEH: reduce RH flow, o 1SI8809A 10. Shutdown the RH Pump and o 1SI8809B align per SE direction, ll.G0 TO Step 11.

APPROVED APR 5 1990 O

Page 20 of 62 (0192Q/0018Q/011990) i

.- . . . . . - . .. ._ . - . -. ._ - - .~.. . -

-REY.-55 LOSS OF RH COOLING UNIT 1 1BWOA PRI-10

=

STEP ACTION / EXPECTED RES?ONSE RESFONSE NOT OSTAiNED -

AITACHMENT A (Eag,e 10 of 201 RH RECCVERY WHILE AT REDUCED INVENTORY CONDITIONS CAUTIOH Starting an RH pump may result in an RCS level decrease due to shrink or void collapse.

11. RESTORE RH FLOW:
a. RCS level - GEEATIR THAN 393'6" a. Continue with this procedure at step 12, l WHEH RCS level is greater than 393'6", __

l THEN perform Steps lib through lij.

() b. Align the RB system:

1) RH Hot Leg Suction valves - 1) Align valves as necessary QEEN: per ATTACHMENT B, i Step la, (page 32) while <

c 1RH8701A and B continuing with this o 1RH8702A and B ATTACHMENT.

R2)lME Pump Suct From RWST 2) Locally; align valves as Isol Viv - CLOSED: necessary:

1 SIB 812A (343' V13 o 1 SIB 812A o o 1SI8812B 1A CS PP RM asove grating) o 1SI8812B (343' X14 1E RH PP RM above grating)

' APPROVED Step continued on next_page Aea s isso O  : = w.s Page 21 of 62 (0192Q/0018Q/011990) ,

REV 55 LOSS OF RH C0OLING UNIT 1 1BWOA l P"s!-10 O

STEP ACTION / EXPECTED RE5:0N5E l PE FCriSE NOT OBT AifiED ATTAC1111E11T_A._IPace_iL9L202 RH RECOVERY WHILE AT REDUCED II(VIliTORLC01(DIT10liS Step lib (continued)

3) RH to Cold Leg 1AlD/1Bl.C 3) Locally align valves as

- DEEll: necessary:

o 1 SIB 809A o 1518809A o ISIS 809B (387' CWA P50) o ISI8809B (387' CWA PSI)

c. Verify CC Flow t c. Restore U Flow to the RH HI - AVAILABLE: RH HX.

o A RH IiX o B RH HX

d. Verify /Close RH Dsch Flow path flow control vivs:
  • RH HX Flow control viv:

o 1RH606 o 1RH607

  • RH HX Bypass Flow control viv:

o 1RH618 o 1RH619

e. Start one RH pump:

o A RH pump o B RH pump

f. Maintain RCS level -

GREATER _T11 AIL 393 ' 6" APPROVED Step continued on next page APR5 1990

[M07s"v7w Page 22 of 62 (0192Q/0018Q/011990)

t t

REY.--55 LOSS OF RH COOLING UNIT 1 IBWOA PRI-10 l O  !

I l

STEP ACTION / EXPECTED RESPON5E REIFONSE NOT OST AiNED -

ATTACHMENT RH RECOVERY WHIL_A_Rakt_12 AT REDUCEb oL20)

_ ,lHYENIORY CONDITIONS l

Step 11 (continued)

.g. Gradually increase RH flow to desited flowrate

h. Verify RH Flow - EESE RED h. Start trending core exit TC's, and GO TO Step 12.

Observe NOTE prict to lt Step 12. l t

i

1. Verify RCS temperature - 1. Increase cooling flow thru l LESS THAN 140'F the inservice RH HX -i and continue cooling the  !

RCS. RETURN TO Step lig. j

j. RETURN TO procedure and k step in effect l APPROVED APR 5 1990 O

Page 23 of 62 (0192Q/0018Q/011990).

REV. 55 LOSS OF Rii COOLING UNIT 1 1BWOA PRI-10 STEP ACTION / EXPECTED RES;0N5E PE?FONSE NOT OSTa NED ATTAClitiEliT_A_(PageJLcL20) -

Ril RECOVERY WHILE AT REDUCED

_IWEHIORLCOUD1IlfliS r

. ********************************w*t**e*,4

  • liOJE
  • i
  • To maintain RCS pressure low enough *
  • for gravity Feed, at least two SG's * ,

^

  • must be refilled and utilized. *

[

a. RCS pressure - GEEATER a. GO TO Step 13.

IIIAtLOR_. EQUAL _IQ_103.SIG I

(N b. SG - AT_LEASI_TWQ_AYA11ABLE b. Restore at least two Steam Generators to service while continuing with this procedure at Step 13,

c. GO TO Attachment D.

STEAMI!iG I!TTACT/lioll-l ISOLATED SG(s) (page 38)

! APPROVED APR 5 1990

((AiUsY[w L) -

l Page 24 of 62 i (0192Q/0018Q/011990) l

I I

REV. 55 LOSS OF RH COOLING UNIT 1 IBWOA PRI-10 p) v STEP ACTION / EXPECTED RES DN5E REIFONSE NOT OSTaiNED ,

ATTACEMElfLA_ Rage _1Lof_202 RI! RECOVERY WiiILE AT REDUCED IllERIDAI_CfHDlI19115 I:

a. Announce over the plant page system for all unnecessary personnel to evacuate Unit 1 containment
b. Actuate Unit 1 Containment Evacuation Alarm:
1) Select SR channel to provide Containment Evacuation alarm:

e o SR channel 31

( -OR-o SR channel 32

2) Verify Audio Count Rate 2) Place Audio Count Rate Channel selector switch in Channel Selector switch position for SR channel in position for SR l HOI selected in Step 13.b.1 channel RQI selected in above Step 13.b.1.
3) Place selected SR channel Level Trip Switch to

- h1RASS:

  • Chech SR TRIP BYPASSED alarm - LII
4) Bypass BDPS on selected SR channel:

a) Place BDPS TEST / NORMAL toggle switch on card

!TM107 in IESI position: APPROVED e Check BDPS BYPASSED APR 5 1990 alarm - LII agogo, Step continued on next page Page 25 of 62

(0192Q/0018Q/011990)

- -. _ ~ . , - . .-

REV. 55 LOSS OF RH C00Li,NG UNIT 1 IBWOA r~N PRI-10 U

STEP ACTION / EXPECTED RE5:0N5E l PEiFONSE NOT 06TtuhED ATTAClltiEliT_.A_lP. age._li. oL101 RH RECOVERY WHILE AT REDUCED

____IlNIliTORLCONDITIONS

5) Rotate selected SR channel Level Adjust potentiometer fully counter clockwise
6) Place selected SR channel operations selector switch to - LEVEL _ADlDSI position
  • At SR drawer, chech CHANNEL ON TEST light - LII
7) Rotate selected SR channel Level Adjust potentiometer clockwise until HIGH FLUX AT SHUTDOWN alarm - LIT

(}

\_- i l 8) Continue procedure at Step 13c, After at least 3 minutes, de-energir.e the containment Evacuation Alarm by placing the HIGH FLUX AT SEUTDOWN switch to - ELQCK

c. Monitor containment conditions:
1) Notify Rad Protection Dept to monitor containment conditions and provide guidance on protective clothing and equip-ment during containment closure
2) Notify Rhd Protection Dept to provide additional guidance should RCS boiling point be reached before containment closure is completed APPROVf D APR 5 1990 EN="vYa w Page 26 of 62 (0192Q/0018Q/OllOJ0)

, . . - _ ~ _ _

REV. 55 LOSS OF RH COOLING UNIT 1 1Bw0A PRl-10 O -

STEP ACTION / EXPECTED RES?ON5E REEFON5E NOT 06T Aif;ED ATTAClitiEliT_A_ Race _lk_oL201 RH RECOVERY WilILE AT REDUCED IliyEl{IORLC01{D1TIQ1{S 14 1RlllAIE CONTAllMENI_ CLOSURE:

a. Close Unit 1 Containment:
1) Use 1Bw05 XPC-W1. CNMT BLDG PENETRATION WEEKLY SURV.

as a guide

2) Provide at least one barrier between containment atmosphere and areas outside containment 15 gig S_RUMW1G._lR
a. RCFC low speed run a. Manually start RCFCs in lights - LII: low speed.
  • IVP01CA
  • IVP01CB
  • IVP01CC
  • IVP01CD 16 CBECK RCS LEVEL:
a. RCS level - LESS a. GO TO Step 21.

TRAN 393'6"

b. RCS level - LESS b. GO TO Step 20.

T11 AIL 1921 APPROVED APR 5 1990 A"!4%?4 Page 27 of 62 (0192Q/0018Q/011990)

REV. 55 LOSS OF RH COOLING UNIT 1 IBw07 PRI-10 STEP ACTION / EXPECTED RES GN5E FEIFONSE NOT 06T AifiED ATTACliMINT_.A_(Page_1LoL202 RH RECOVERY WHILE AT REDUCED 11ME!IIORY_C0HDITI.0HS R 3 C

a. RCS Hot side vent path a. If the RCS has a cold resistance - AC UPIAELE Icg opening, par __IIGURE_.lBROA_IRL1D.-2 TIILH refill the RCS per Lpage 10) the following:
1) Align at least one SI pump for Hot Leg Injection.
2) Start the aligned SI Pp.

D V

3) WHEH RCS level is greater than 333S ",

IHEN stop the SI Pp.

4) Go 10 Step 21.  ;

l i

r l

l s

l l APPROVED  !

(

APR 5 1990  ;

M Evin I e

a- t l

Page 26 of 62  :

(0192Q/0018Q/011990)

- . - _ . . - _. . _ _ _ _ . _ . . . ~

REV, 55 LOSS OF RH COOLING UNIT 1 IBWOA "ai-10 O_

STEP ACTION / EXPECTED RESrGN5E FE?FONSE NOT CSTmNED ATIACIIMENT_A_LFace_1B_of_201 RH RECOVERY WHILE AT REDUCED IINEtIIORLC0HDIIIO11S 18 II a Cent Charging Pp is not

&lGJ CT11 pARG1NG_EE IV_Edl a NLa available.

THEli mahoup to the RCS using

a. Open RWST to CENT CHG one of the following:

pump suction valves: Attachment I, RWST GRAVITY

. 1CV112D L (page 61) l

. 1CV112E

-OR-

b. Close VCT to CENT CHG pump suction valves: o Attachment G. SI PUMP HOT LEG INJECTION (cage 54) l
  • 1CV112B
  • 1CV112C -OR-
c. Increase charging Flov o Attachmeat H. ACCUMULATOR to maximum by throttling INJECTION (page 58) l open 1CV121 and ICV 182 i

d . RCS level - GEA'AEILIHAll d. Maintain maximum charging f jll%" flow until RCS level is greater than 313'.h".

19 GD_10._SIEE_21 l -

f-APPROV ED APR5 1990

=ta

'O

- - - =_ .

' f f (0192Q/001BQ/011990)

L m. , a .

REV, 55 LOSS OF RH COOLING UNIT 1 IBw0A

- PRI-10 l STEP ACTION / EXPECTED RE5 0N5E PE9FONSE NOT bhTmNED ATTAC!IMElrLA_.(Page_1.9_.0L201 Rif RECOVERY W111LE AT REDUCED llNEliTORI_ CONDITIONS 2

EMhl%V "  :

a. One Cent Chg Pp - a. Start a Cent Chg Pp  :

IILSERY1CE per liw0P CV-1, STARTUP ,

OF Ti!E CV SYSTEM. ,

IE a Cent Chg Pp can NQI be staited.

THEN makeup to the RCS using one of the following:

9 Attachment I, RWST .

GRAVITY TILL (page 61) l'.

(3 ..OR -

(

o Ate:chment G, 51 PUMP ,

.40T LEG I!UECTIO!(

(page 54) l' 0 Attachment !!,

ACCUMULATOR I!UECTION (page 58) l

b. Increase RC5 level to -

GREATIILTHAN 393 ' 6" by thrott3ing open 1CV121 c,nd ICV 182 l c. RCS level - GREAIEILTIIAIL332Lh" c. RETURN TO Step 20a. '

I

d. Throttle ICV 121 to i nointain desired RCS level APPROVED .

APR 5 1990 l

l 0 MSEv7w  ;

[ V - - -

i Page 30 of 62 (0192Q/001SQ/011990) l

REV. 55 LOSS OF RH COOLING UNIT 1 1BWOA q

v PRI-10 STEP ACTION / EXPECTED RESPON5E FE?FONSE NOT OBTmf;ED ATIACliMEliTAIPage_2D_cfJ01 RH RECOVERY VMILE AT REDUCED

__110ZEliERLC011DIT10liS t

21 RES10RLEH C00LitG: r

a. RH Flow - RESIORED a. Restore RCS cooling:
1) Perform one of the following:  ;

o ATTACHMENT C, BLEED AND FEED USING EXCESS LETDOWN THROUGH LOOP I

DRAINS AND NORMAL CHARGING (page 33) l'

-OR-()

O o ATTACHMENT G, SI PUMP HOT LEG INJECTION (page 54)

-OR-o ATTACEMENT H.

ACCUMULATOR INJECTION (page 58)

2) RETURN TO Step 10.
b. RCS temperature - LESS b. Continue cooling with RH, IRAN 140'F RETURN TO Step 21a.

h!bkkFhk ,

-EliD-APPROVED l APR 5 1990 O 3li?%*?&  ;

V l >

Page 31 of 62 (0192Q/0018Q/011990) l

RdV. 55 LOSS OF RH C00'ING UNIT 1 IBWOA t PRI-10 f O  !

I STEP ACTION / EXPECTED RE5 0N5E REEFON5E NOT OST Aif.ED ATTAC11tiENT B_(Page_ Loll)

~

f LOCALLLDEElf1HG_RIL110LLEG_5MCIIDILVALVES  ;

i 1 LOCALLLDEEtLRtLSVC110tLYALYES: i I

a. IE IPI-405 failed, a. II valves can HOI be opened THIH open the following valves: electrically due to failed  !

motor,

  • 1RH8701A (MCC131X2, Cub B1) THEN turn breaker OFE and j
  • 1RH8702A (MCC131X2, Cub B4) locally open with handwheel  ;

as necessary:  ;

IE 1PI-403 failed,  !

-THEN open the following valves o 1RH8701A (377' R7 P68)  !

o 1RH8701B (377' R11 IMB)  :

  • 1RE8701B (NCC132X2, Cub B3) o 1RH8702A (377' R4 P75) i
  • 1RH8702B (MCC132X2, Cub B1) o 1RH8702B (377' R3 IMB) [

t

1) Turn breaker DIE and-open 1) At SE discretion, vent i cubicle door RH trains using high  !

point vent valves.  ;

2) Install jumper between points t 2 and 3 on terminal board e at front of cubicle [
3) Override breaker / door interloch and turn breaker-DH .j
4) WHEN 'M' contactor drops out,  !

THEN turn breaker OEI and ,

remove jumper ,

5) Check valve position by visual  !

inspection or by computer point j

6) At SE discretion, vent RH trains  !

! using high point vent valves- l

- i
b. RETURN TO IBw0A PRI-10, Step _4 i

- END -

APPROVED  ;

APR5 1990 f

= %  ;

O i

f V i l i Page 32 of 62  :

'(0192Q/0018Q/011990)  ;

1

.a .. ; ._ a_ . . .. ; _ _a_._ -

_,,-.__..__.-..,._,,__.]

REY. 55 LOSS OF RH COOLING UNIT 1 IBWOA PRl-10 7-~3 V

STEP ACTION / EXPECTED RE5:0N5E FEicCNSE NOT OSTmNED l ATTACHMENT _C_IEagelof_M BLEED AND FEED USING EXCESS LETDOWN THRU LOOP DRAIHS 1 HORMAL_CHARG1HG. .

HOTE

  • This ATTACHMENT establishes a drain *  !
  • path to the RCDT. This letdown may
  • l
  • be sent to either the HUTS or RWST *
  • via the RCDT. Charging is also *
  • established, which may use either
  • l  ;

l

  • plant conditions to determine which
  • l
  • combination to use. Consider RWST *
  • 1evel, PWST levels, BAT levels,
  • l
  • and HUT capacity.
  • l

() 1 CHECK _RCS_IEMPERAIURE:

a. RCS temperature - LESS_THAH a. GO TO another ATTACHMENT 2101I for RCS cooling per TABLE A (page 8). ,

i 2 CHECLRCILT PUMPS:

^

l a..At least one RCDT pump - a. Resture an RCDT pump or AVAILABLE Go T0 another ATTACHKENT  ;

for RCS cooling per TABLE A (page 8).

II no other cooling method is t I available.

l THEN perform the following:

1) Locally open the RCS Loop i l DRN CHN HDR ISOL to RCDT
valve:

ICV 8350 (377' R12 RCDT Valve Aisle) -

2) Evacuate personnel from ccntainment, l

(q

_j Step continued on next par,ED APPROV e  !

APR5 1990 ,

BRAIDWUVW Page 33 of 62 me+n5M"**

(0192Q/0018Q/011990) i

s- .. . ._ um.v I

REV. 55 LOSS OF RH COOLING UNIT 1 1BWOA

--==_.: __-

STEP ACT10fuEEFEdlED REB 20fGE RE?F0fiSE NOT OSTAifiED i

ATTACMEliT C. Gage._2._of_n BLEED AND TEED USING EXCESS LETDOWN THRU LOOP

__._DRAlliS_f=JiORMALCHARG11fG Step 2a (continued)  !

3) At the Radwaste Pnl, ,

ORE 01J._open RCDT Drain i valvet  !

  • 1RE9163 I i
4) Verify that a CENT CHG Pp l is available prior to establishing a RCS drain  !

path.

5) Verify that the Excess [

LTDWN HXs Common Outlet  !

HDR 18o1 Valve is closed: j

  • 1CV123 l
6) Open the following RCS i Loop Drain Valves:
  • 1RC8037A $
  • 1RC8037B +
  • 1RC8037C
  • 1RC8037D 7)-GO T0 step 7 of this ATTACHMENT. ,

I 3 GECK CENT CHG PUMPS: j

a. At-least one CENT CBG pump - a. GO'TO another Attachment [

AVAILABLE for RCS cooling per i TABLE A_(page 8). ,!

-I APPROVED _}

APR 5 1990  !

l Q O' U?#w E  !

I i

Page 34 of 62 l (0192Q/0018Q/011990) i

-f

REY. 55 LOSS OF RH COOLING UNIT 1 1BWOA PRI-10

[

Qx . - - -

STEP ACTION /f PECTED RE5;CN5E PEEFONSE NOT OST5 NED l

'TTACHMERT_C_ If ace _ 3_rLi}  ;

BLEED AND /EED USING EXCESS LETDOW!{ THRU LOOP ,

DRAlliS_Ll!0Rlh_CHARGRtG  !

l 4 ggL1DfLDJ5CliARGL0f_RCDJ

^

o U-1 RCDT Pump to Recycle HUT's Isol Viv - 0FEl{: ,

  • 1AB8551 (401' V14 10' l

below grating)

-OR- ,

o U-1 RCDT pump to RWST Isol Viv - 02I11: i-1RE9171 (403' CWA From Pil)

  • 1518936 (364' V15 CWA  ;

C along wall)

I 5 ESIABLLSILDRAllLPA11LIOJ1CDl:

a. Excess Ltdun Ex's Common Outlet Hdr Isol - CLOSED:
  • 1CV123
b. RC Loop Drn Viv - 0 Fili:
  • 1RC8037A [
  • 1RC8037B
  • 1RC8037C
  • 1RC8037D
c. RCS Loop Drn Cmn Hdr 1801 to RCDT -

IHRO.IILED:

  • 1CV8350 (377' R12 RCDT Valve Aisle) APPROVED  :

, APR 5 1990 O ""*

l Page 35 of 62 (0192Q/0018Q/011990) l . _

REV. 55 LOSS OF RH COOLING UNIT 1 IBWOA PRl-10

(~~]

m)

STEP ACTION / EXPECTED PE5?ON5E PEIFCNSE NOT 06T4 NED ATTACIIMENLC _ Wage._4_of_D BLEED AND FEED USING EXCESS LETDOWN THRU LOOP

.11M111S_JLR01W1_CMEG1HG_

l 6 YEEIFY RCDT PUHP_S_J1LAU10:

  • IB RCDT pump l 7 CEECK VCT MAKEUP CONIRQL_S1SJ16:
a. Mode selector switch - AUTOMTIC a. Verify RWST level greater than b7 and perform the following:

I

1) Open RWST to CENT CllG Pumps Suction valves:
  • 1CV112D
  • 1CV112E
2) Close VCT Outlet 1801 valves:
  • 1CV112C
3) GO TO Step 8, l:

b, Set boric acid and makeup water flow controller potentiometers - GREATER _THAN >

RCS._3.0A0lLCONCEliTMT10N

c. Control switch - START I 8 YERTFY CHARGlRG_S1SJf!LSIMS:
a. CENT CHG Pumps Mini
  • low Isol valves - OPEN:
  • 1CV8110 APPROVED ,
  • ICV 0111 APR 5 1990
  • 1Cv8114
  • 1CV8116 uuowuvo '

e s na u w

{

( Step continued on next page i

l

! Page 36 of 62 l (0192Q/0018Q/011990) l >

REV, 55 LOSS OF RH COOLING UNIT 1 IBWOA PRI-10 1 STEP ACTION / EXPECTED RES?ONSE PEIFONSE NOT 00TAiNED ATIACEMENT_C_ Rage._i_of_51

-BLEED AND FEED USING EXCESS LETDOWN TH M LOOP DRAINS _ LliORMAL_ CHARGING Step 8 (continued)

b. Charging Line Cnmt Isol Valves - QEEN:
  • 1CV8105
  • 1CV8106
c. Start a CENT CHG pump
d. Monitor RWST level.

IE RWST Level EMPTY alarm energizes-

-THEN trip Cent Chg Pump AND isolate the drain path O

e. Equalize charging and letdown flow N 4

-a. Check RCS temperature - a. Go TO another ATTACIMENT S.IABLE OR DECREASING for RCS cooling per TABLE A (page 8).

I R

a.~II at anytime an RH

-train becomes'available.

THEE:

1) Immediately all'gn the RH Train for RCS cooling per Bw0P RH-6 PLACING THE RH SYSTEM IN SHUTDOWN COOLING APPROVED
2) Return CV, AB, RE and RC Systems. APR5 1990 to normal lineup per SE direction l , ,o.ono w ovow O 3) RETURN TO-1Bw0A'PRI-10, Step 7

- END -

Page 37 of 62 (0192Q/0018Q/011990)

REV. 55 LOSS OF RH COOLING UNIT 1 IBWOA .

,m PRl-10 l Q) - -.

STEP ACTION / EXPECTED RESPON5E PETFONSE NOT GET AiNED ATIACIIMEllLILLEage_LoLll  !

SIEAMING_IIIIACIlR0ll-I SD LATED _ S GISl ,

1 E SIABLISILRCS_C.0DLING_MSING_SG.LSl : 1

a. Check IOS temperature - a. GO To another ATTACHMENT GREATEILTIIAIL111'I for RCS coeling per .

TABLE A (page 8). [

b. Chech Two SGs - AVAILABLE:
1) Associated loop stop 1) II ALL SGs are isolated valves - DEEli IllEti try to unisolate at least one SG.

IE no SG can be made available T!iEli GO T0 another ,

ATTACHMENT for RCS Cooling

<-~ per TABLE A (page 8). l

2) Available vent path: 2) Establish a vent path for at least one SG, o Associated PORV's IE no SG can be made o Steam Dumps available. r IIIEli GO TO another ATTACHMENT for RCS cooling per TABLE A (page 8), l
3) Narrow range levels - 3) Feed SGs using AF GREATER THAN 4% System. Maintain level greater than 4% narrow range.

IE AF System liOI available, I}lEli Go TO Step 2.  ;

4) AF system supplying SG's 4) GO TO Stop 2.

Step continued on next page APPROVED APR 5 1990 Q O^ dees 7S

  • l b - -

l l

L Page 38 of 62 (0192Q/0018Q/011990)

REV. 55 LOSS OF RH COOLING UNIT 1 IBWOA

x PRI-10 (G

STEP ACTION / EXPECTED RE5:0N5E _ PE?FONSE NOT OST Aghb -

ATTACHMENI D_ Cage _2_of_D ,

31IAMlHG__1HTACIZE0H:1101ATID_S GISl Step 1 (continued)

c. Dump steam to condenser from c. Manually or locally dump available SGs: steam from availatie SG(s) using SG PORV(s). ,
1) Check condenser available
2) Place MS header pressure controller in MANUAL and reduce demand signal to zero
3) Place steam dump mode selector switch in STEAM PRESSURE mode

/~') 4) Manually adjust MS header (m,/ pressure controller demand to initiate cooldown ,

d. Check RCS temperature:
1) RCS temperature - S.IABLE 1) IE steam flow from at least i QILDECREASING two available SGs is verified Locally, THEN continue with this attachment .

IE HDI verified, THEH GO T0 another ATTACHMENT for RCS cooling per TABLE A (page 8). l+

2) Continue heat removal by steaming SGs and feeding ,

with AF System i

3) II at anytime an RH train becomes available, l

THEH immediately align it for APPROVED RCS cooling per Bw0P RH-6, PLACING THE RH SYSTEM IN APR 5 1990

, SHUTDOWN COOLING O

\m/ 4) RETURN TO 1Bw0A PRI-10, Step 7

fASNv2=

i 8

(0192Q/0018Q/011990)

REY. S5 LOSS OF RH COOLING UNIT 1 IBw0A  !

PRI-10 i O  !

STEP ACTION / EXPECTED RESPON5E PE5FONSE NOT OBTAifiED j ATIACEMENT D Qage_.Lof] .

SIEAMlHG_INIACILH0ll-ISDLATED_S ESl l CAUIIDH ,

If offsite power is lost after SI ,

reset, then manual action may be  ;

required to restart safeguards  !

equipment.  !

I 2 CHECK FEEDWATER ISQLATION:  !

t

a. FEEDWATER ISOLATION alarm - LII a. GO To Step 3. l
b. Reset SI. if necessary: b. Reset SI per IBw0A PRI-5. CONTROL ROOM INACCESSIBILITY, O~ ATTACEMENT E.
1) Depress both SI reset pushbuttons.
2) Verify SI ACTUATED PERMISSIVE LIGHT - NOT LIT
3) Verify AUTO SI BLOCKED permissive light - LII
4) Verify all automatic SI 4) Deenergize Feedwater signals - CLEARED Isolation-Aux Relays by removing fuses FU-24 and FU-27 at Aux Safeguard Relay Cabinets 1PA27J and IPA 28J. GO TO Step 2e.

[

L 5) CLOSE AND IRIE DEEN 5) IE reactor trip breakers reactor trip breakers will NOI CLOSE, THEN lift lead on TB506-5 in IPA 09J and IPA 10J to-clear P-4 Fignal.

Step continued on next page APPROVED APR E' 1440 MEMw Page 40 of 62 (0192Q/0018Q/011990)

REY. 55 LOSS OF RH COOLING UNIT 1 IBw0A PRI-10 STEP ACTION / EXPECTED RESPON5E RE?FE! SE NOT OSTaiNEt.

I ATTACllMERI_ILlPage_A._oll)  !

SIEAli111G_IllTACIIH01L-1EOLATIILSGIS1 i i

Step 2 (continued) l i

c. Reset feedwater isol i
d. Reset feedwater isol l aux relays j:
e. Verify feedwater isol aux relays i ACTUATED lights - RQI_LII  !

f, CAUT10H Slowly initiate feedwater flow to [

steam generators to limit severe i water hammer to intact SGs. l O _ - - - ,_.

5 IE5G l

a. Verify Condensate System in )

operation: l

1) At-least two CD/CB pump run '[

lights - LII t

2) FW PUMP SUCTION HDR PRESS -!

LOW alarm - NOT LII  ;

b. Place FW reg valves in MANUAL {

and reduce demand to zero {

c. Place-FW reg byp valves in j MANUAL and reduce demand to  ;

zero APPROVED [

Step continued on next page APR5 1990 i O -

T i

Page 41 of 62 f (0192Q/0018Q/011990) i

, . . _ . - . , _ . - _ . . . _ . . . - . . . , - . _ _ . _ . . . . . . _ . _ . . _ , _ , _ . ~ . ~ . - . . _ , - . _ , . , . _ , . . , _ . - , _ . - .

REV. 55 LOSS OF RH COOLING UNIT 1 1BWOA r PRI-10  !

f STEP ACTION /EXPECJED RES?ON5E PEEFONSE NOT OSTmfiED i

ATIACEMENT_ILIEage_LoL13  !

S.TIAMING_IRTACTIHOR-110 LATED _SSLSl ,

f Step 3 (continued) [

d. Start the startup feedwater d. Establish condensate flow  !

pump: to the Steam Generators by i

-l performing the following:  !

i

1) The fc't. lowing interlochs must 1)-Verify at least ene FW be met to start the startup Pp discharge valve is feedwater pump: open!  ;
  • Suction isol valve - QEEN: o 1FWOO2A  !

o 1FWOO2B J-

  • ICB133 o 1FWOO2C o 1FWQ58 I
  • Discharge isol valve - OPEN: ,!

IE condersate flow can NOT O *

  • IFWO59 Recire' control valve switch be established, nIEH GO TO another Attachment for RCS coolin);

in Of.EH position: per TABLE A (page 8). j

  • 1FWO76

{

I

  • Recire isol valve - DEEN:

-* 1FWO58 f

  • Lube o13 preosure - GEEAIER THAN 8 ESIG
e. Manually open FW tempering isolation valves:=  !

.o 1FWO35A  !

t o 1FWO35B o 1FWO35C o 1FWO35D- ,

APPROVED j Step continued on next-page APR 5_1990 _

i al4 MOW Os D i men P.svtw j O i f

Page 42 of 62 l (0192Q/0018Q/011990)

REV. 5S LOSS OF RH COOLING UNIT 1 1BWOA i PRI-10 O l STEP ACTION / EXPECTED RES 0N5E RE3F0fiSE NOT OST Aif.ED I

/

i ATIACHMENT_ILLEate_ft of._1_1  !

ETEAMIHL1HIACIIH0H-110LATEILSED l Step 3 (continued) j

f. Control flow with FW tempering f. Go TO another Attachment  !

flow control valves: for RCS cooling per l!

TABLE A (page 8). I o 1TWO34A l o 1TWO34B [

o 1FWO34C  !

o 1TWO34D.  ;

4 C1EK_SG_LEYEL.S [

a4 Narrow range level in at a. IE feed flow to at 1 cast I least two available SGs - two available SGs is [

GREATEILT&MLA% verified,  ;

THEH maintain flow to O restore narrow range level to greater-than A%.

l II NO verified, I THEH 0 T0 another i ATTACHhENT for RCS cooling per TABLE A (page 8). li

[

t

b. Dump-steam to condenser from b. Manually or locally dump ,

available SGs: steam from available SG(s)  ;

using SG PORV(s).. .

1) Check condenser available )

i

-2) Place MS header pressure ,i controller in MANUAL and i reduce demand signal to zero

3) Place steam dump mode i selector switch in STEAM ,

PRESSURE mode [

4) Manually adjust MS header AFPROVED +

pressure controller demand APR 5 1990-to initiate cooldown

$ $ $w O

I l

Page 43 of 62 (0192Q/0018Q/011990) l t

-. - - , , . _ . . , . . , . ..-. . . - . . . - . . . , - - - - . . - . . - - . . . . ~ - - , - - -

REV, 55 LOSS OF RH COOLING UNIT 1 1BWOA O PRI-10

'b STEP ACTION / EXPECTED RES;ON5E PEEFONSE NOT 06T A.NED  ;

ATIACIIMENT_IL2 Age 7 of_Z2 SIEAMIRLIIITACTL11011-IS O LATED _ S GI D r

i l)

a. Check RCS Temperature - a. GO T0 another ATTACHMENT S.TAEE__0lLDECREASlllG for RCS cooling per TABLE A (page 8). ,
b. Continue heat removal by steaming and feeding SGs 6 f TEMPTS 10 E S10RE
a. II at anytime an RH train  !

becomes available, IHEli:

{'  !

1) Immediately align the RH train for RCS cooling per ,

Bw0P RH-6, PLACING THE RH SYSTEM IN SHUTDOWN COOLING

2) Re-align AF, FW, and CD/CB Systems per SE direction
3) RETURN TO 1Bw0A PRI-10. Step 7

-END- 7 APPROVED APR 5 1990 l

,*:l N 2 ??w

('J L

r i

l Page 44 of 62 (0192Q/0018Q/011990)

REV. 55 LOSS OF RH COOLING UNIT 1 IBWOA p PRI-10 d

STEP ACTION / EXPECTED RE9:0N5E PE?FONSE NOT OSTadjED _

ATTACII!iERTl.IPAGE_L.0L11 BLEED AND FEED USING FZR PORV(S) AND llRluihk_.CliARGlHG 1 RESET SI IF NECESSABI: Reset SI per 1Bw0A PRI-5, CONTROL ROOM

a. Depress both SI reset INACCESSIBILITY, pushbuttons ATTACHMENT E.
b. Verify SI ACTUATED permissive light - HQT_LLI
c. Verify AUTO SI BLOCKED permissive light - LII 2 1 AINMENT ISOLATI0tLIE

(] a. Reset Cnst Isol Phase A a. Roset per IBw0A PRI-5, CONTROL ROOM

() INACCESSIBILITY, ATTACHMENT E.

b. Reset Cnmt Isol Phase B b. Reset per 1Bw0A PRI-5, C0!UROL ROOM I!1ACCES SIBILITY ,

ATTACHMENT E.

c. Reset Cnmt Ventilation 1801
d. Reset SI recirc sump and CENT CHG pumps miniflow isol valves:
  • 1SI8811A
  • 1SI8811B
  • 1CV8110
  • 1CV8111 Step continued on next page APPROVED APR 5 1990
  • /EY$7ufvfw b

ag 62 (0192Q/0018Q/011990)

t I

r REY. 55 LOSS OF RH COOLING UNIT 1 IBWOA  !

PRI-10 s'

STEP- ACTION / EXPECTED RESPON5E  ;+0FONSE NOT OSTmNED i

ATTACEMEtiT E (P. age _.2._oLil l BLEED AND FEED USING PZR PORV(S) AND E0RMALCIIARG11tG Step 2 (continued)

e. Reset SI CENT CHG pumps miniflow isol valves: I i
  • 1CV8114 j
f. Chech SAC run lighte ~ AHLLLT f. Start one SAC per l Bw0P SA-1, STARTUP AND i OPERATION OF STATION [

AIR COMPRESSORS. i I

g. Open-instrument air Cnmt i isol valves:  ;

i

1) IIA 065 t
2) IIA 066 l h.-Open fire protection Cnmt isol valve: {
  • 1FP010  !

, t L  !

t i

i

~!

APPROVED l APR 5 -1990 .

BR AIDWOOD Snaretts Mvestag l O l l

I Page 46 of 62 l (0192Q/0018Q/011990)  !

, _ . _ . _ _ - . _ . . - _ _ _ _ . . _ _ _ _ . _ . _ . . _ _ _ _ _ _ . _ _ . - _ _ . . _ ~ . . - _ - _ _ - . _ .

REY. 55 LOSS OF RH COOLING UNIT 1 IBWOA s PRl-10 STEP ACT!ON/ EXPECTED RE5;CN5E FEiFON5E NOT OBTmfiED ATTACHMENT _E_QAge_L of_il BLEED AND FEED USI!1G PZR FORV(3) AND JiORMALCHARGING_ _

3 YERIFY RCS_f.EED EAlli:

a. Check pump status: a. M <ually start pumps.
  • CENT CHG pumps - AT_12ASI OBE_RUFHING
b. Chech ECCS valve alignment: b. lE a feed path can HOI be established,
1) RWST to CENT CHG pumpo THEN GO To enother suction valves - OEEH: ATTACHMENT for RCS cooling per TABLE A (page 8). l
  • 1CV112D
  • 1CV112E
2) VCT outlet isol valves - CLQSED:
  • 1CV112B

+ 1CV112C

3) Charging line Cnmt isol valves - OPIll:

-

  • 1CV8105
  • 1CVS106
4) CENT CHG pumps to cold legs injection isol valves - CLQSID:
  • 1SIBB01A
  • 1 SIB 801B l

APPROVED APR 5 1990

.=:: =

1 O

Page 47 of 62 (0192Q/0018Q/011990)

AA

REV. 55 LOSS OF RH COOLING UNIT 1 IBWOA PRl-10 ST[ ACTION / EXPECTED REE?ON5E PE EFONSE NOT OSTmhED AIIAC11MEHTl_Eage 4 OLil B LEE D_A!!D_IIE D_U S I NGJ'Z R _EORYI sl_Al'D lt0hCIIARG.IHG La ESlaBLISH RC13LEED_fAlli:

a. Verify power to PZR PORV a. IE either PORV is 110T isol valves - AVAILABLE: available.

TilEH GO To another

  • 1RY8000A ATTACHMENT for RCS cooling
  • 1RY8000B per TABLE A (page 8). l
b. C;cn both PZR PORVs:
  • 1RY455A
  • 1RY456 5 tialtlIAltLflCS HEAT REMOVAL:
  • Operate CENT CHG pu ps as
  • IE minimum flow required l necessary to mainta n minimum can HQI be obtained via normal charging, flow reguired FIGURE .Bw0Aas determined PRI-10-3 (page from
11) TilEN oper CENT CHG puaps to cold leg injection isol valves:

- AND -

  • 1SI8801A
  • 1 SIB 801B
  • Control charging flow to l

maintain PZR level - GREATER THAN 47,

}l _

a. Chech RCS temperature - a. Go TO another STABLE OR DE.CEEASIHG ATTACHMENT for RCS cooling per TABLE A (page B) . l APPROVED APR 5 1990

() __

4"SunY&

Page 48 of 62 (0192Q/0018Q/011990)

REV. S5 LOSS OF RH COOLING UNIT 1 IBWOA PRI-10 (s

(, -

STEP ACTION / EXPECTED REFON5E PEIFONSE NOT OST AifiED ATIACHMEltT_E_& age _5._of_51  :

BLEED AND FEED USING PZR PORV(S) AND l

_. Il0E!BL CILEGillG 1 r

7 TEMPTS __10J1ES10RE gN l

a. II at anytime an RH train becomes available.

TH3n:

t/ Im:pediately align the RH train for RCS cooling per Bw0P RH-6, PLACING THE RH SYSTEM IN SHUTDOWN COOLING

2) Close both PZR PORV(s) 3

( 3) Return CV System lineup to (

normal per SE direction

4) RETURN TO IBw0A PRI-10, Step 7

- -E!D-t f

l APPROVED l

! APR5 1990 (9

V

((ldEE7w Page 49 of 62  ;

(0192Q/0018Q/011990) l

REV. 55 LOSS OF RH COOLING UNIT 1 IBWOA PRI-10 7_

STEP ACTION / EXPECTED REPuu5E PEIFONSE NOT OST AiNED ATIACHMEliT F Qage 1 of 4)

REEUEL_ CAVITY TO FULL POOL _C20LIliG

                                            • n******************
  • NOTE *
  • This ATTACHMENT uses the Refueling *
  • Water Purification pumps with *
  • suction from the refueling cavity. *
  • The pumps discharge to the Spent *
  • Fuel Pool and the effluent is cooled *
  • 'uy the FC trains. Cooler water from *
  • the 5 tent Fuel Pit flows back to *
  • the uavity. *
                                                      • v*************

1 CHECK REACTOR VESSEL _ HEAD _ REMOVED GO TO anot*'t ATf.^.0tIhENT for RCS cuo] '? per TABLE A i p +

.i .

2 CHECK SPENT FUELPQ0L C00 LING:

Ch

(_-) a. At least one cooling train a. Establis.. ..e 'ain of

- IN OPERATION FC coolits IE a train L... HQI be established, THEH GO T0 another ATTACHMENT for RCS coolin e

- per TABLE A (page 8). l 3 SIDE EEEUELING_ _ WATER PURIFLCAl108 kUMPSL

a. LQCALLY STOP Refueling Water "

Purification pumps:

o 0A Pump (364' S12 CWA) o OB Pump (364' S12 CWA)

APPROVED APR 5 1990 EENEL%~

n U

Page 50 of 62 (0192Q/0018Q/031990)

REV. 55- LOSS-0F RH COOLING. UNIT 1 IBWOA  !

- __ PRI-10 l p ,

V  !

STEP ACTION / EXPECTED RESPON5E RE3FONSE NOT OBT AiNED f

i AIIAC M UT F fpage 2 of 4) [

EEEUEL CAVITY TO _ FUEldQQL COOLING (

i 4 REEUEL CAVITY TO FUEL P00L A_IG9MENIl l

a. Check position of the following a. Open any closed component components: II all. components will HQI l open, '
  • Fuel Pool Sluice Gate - QEEN T m GO To another -
  • Transfer Canal Gate ATTACHMENT for RCS: cooling i valve 1FH001 - DEEH per TABLE A (page 8).
  • Transfer Canal Flange - QPEH  !

r 5

g A,l g g N g E g G WATEll REC RCULA" I s GlRE :UE _ CAVITY: i i

a. Locally CLOSE the following i

..O valves:

V

  • Unit-2 Refueling cavity Suction Valves-- CLOSED:  !
  • - 2FC009 (383' R26 P57)  ;

2FC010 (383' CWA P57) .

  • Unit-2 RWST Suction Isol +

valve - CLOSED: i

  • - 2FC8758 (364' + 15' V23 CWA) i
b. Unit-1 RWST Suction Isol valvn - CLOSED:  !
  • 1FC8758 (364' +-15' V13 CWA) c.. Unit-1 Refueling Cavity Suct  !

valves - OPEN:

  • 1FC009 (383' R7 P57)
  • 1FC010 (383' CWA P57) APPROVED {

APR 5 1990 l Step continued.on next page gAgCO_O Page 51 of 62 .

(0192Q/0018Q/011990) ,

h

f

.h REV.-55 LOSS OF-RH' COOLING UNIT 1 1BWOA-  !

-PRI-10  !

-STEP ACTION / EXPECTED RESPONSE PEIFONSE NOTROST AiNED i AIIACHMENT F (page 3 of 4) l REFUEL CAVITY TO FUEL POOL COOLING -;

. . I Step 5 (continue'd)  :

l d, Cask Fill Isol viv - CLESED:

-t OFC001 (401' + 8' Y15 CWA) )

e. Demin Inlet Isol Vivs - CLOSED:
  • 1FC013 (401' Q17 Valve Aisle)

-2FC013 (401' Q19 Valve Aisle)  !

i f 1 Spent Fuel Pit Inlet ]

- valve - QEEH:

-l *-LOFC002A (401' + 10' X15 CWA)

g. OL Refueling Water Purification i

( Pump Suction Isol viv - OPEN: l l

  • OFC003-(364' 512 CWA) 6 LOCA_LY S" ART-REFUE_IU3 }

'WAT E R PURL :ICATION 30 * )S:  !

  • OA Pump '(364' S12 CWA) }
  • OB Pump (364' S12. CWA)  ;

t 7- EVALUATE EF ECTIVENESS i

.0F C00LIN 3 1 ETHOD:

-a.. Check RCS-temperature - a GO To another I STABLE OR DECREASING -ATTACHMENT for RCS cooling per TABLE A-(page 8).

x-  !

I i

APPROVED {

APR5 1990 i O .= =.: 4 i

i t

I Page 52 of 62 I

(0192Q/0018Q/011990) $

u ... cz. _ ,, __

1 REV. 55 LOSS OF RH COOLING UNIT 1 1Bw0A PRI-10 STEP ACTION / EXPECTED RES;ON5E PEIFONSE NOT ObT AiNED ATTACHMERT_11page_4._.oL4J REEUEL_CAV1TY TO JUEL_EQQL CQQLING

~

R

a. II at anytime an RH train becomes available, THEN:
1) Immediately align the RH train for RCS cooling per Bw0P RH-6, PLACING THE RH SYSTEM IN SHUTDOWN COOLING
2) Return FC System lineup to normal per SE direction
3) RETURN TO 1Bw0A PRI-10, Step 7

- END -

APPROVED APR5 1990 Q .

Eb'E N Ew Page 53 of 62 (0192Q/0018Q/011990)

1 i,

~~

LOSS OF RH COOLING UNIT 1 IBWOA  !

r REY. 55 PRI-10

(>j l I

STEP- ACTION / EXPECTED RESPON5E PE3FONSE NOT-OST AiNED

]

ATTACHMENT G (PAGE 1 of 4) [

SI PUMP HOT LEG INJECTION I

-***************************************** l

  • liOIE
  • r
  • This ATTACHMENT uses an SI pump in
  • l
  • a hot' leg injection mode. It should *
  • be-noted that a finite volume of *  :!
  • water exists'in the RWST, and'that
  • i
  • overspill from the RCS may be *
  • . unavailable for injection. *
                                          • www=*=****wA*AwwAa** j
  • liDIE *
  • Evacuate the Containment if any *

=!

  • overspill is expected to occur.
  • j
                                        • w*******ww*n*********  ;

() 1 CHECK RWST LEVEL: I

a. RWSTilevel - GREATER THAN 6% a. GO TO another ATTACHMENT i for RCS cooling per )

TABLE A (page:8).

2 CHECK SI PUMPS:  !

I

a. SI-pump - AVAILABLE: a. Restore one-pump in a  !

reasonable-period of time l14 or GO TO-another 'i o lA SI-Pump ATTACEMENT for RCS' cooling o 1B SI Pump _per TABLE A (page 8). l. ,

e

-3' VERIFY ECCS VALVE LINEUP:

e a./SI' pumps miniflow isolation 'I-valves - OPEN: }

  • 1SI-8813 o 15I-8814_(lA SI Pp) o ISI-8920 (1B SI Pp) APPROVED APR 5 1990 l Step continued on next page e nsysw --

samowevo ,

i Page 54 of 62 i (0192Q/0018Q/011990) ,

v -,

1 I

LOSS OF RH COOLING UNIT 1 1Bw0A -'

REV. 55 , PRI-10 O

STEP ACTION / EXPECTED RE5?ON5E i PEiFON$E NOT OSTMED l

ATIAClil1ERI_G..lPAGI 2 of 41 SLEME,RQI_ LEG _IHJECTIDE Step 3 (continued)

b. SI pumps suctior valves - DEIN:
  • 151-8806 o ISI-8923A (lA SI Pp) o ISI-8923B (IB SI Pp)
c. RCS Hot Leg injection valves -

QEEU:

o 1GI-3802A (lA SI Pp) o ISI-8802B (lB ST Pp)

d. RCS Cold Leg injection valves -

CLQSID:

(

'--~)

  • 151-88213
                                  • <**w********************

liGTE

  • Use the SI Pump Injection only ac *
  • necessary to maintain Reactor Vessel
  • l
  • Level GREATER THAIL213_L6" and to 'i
  • limit RCS average temperature so *
  • that RWST level can be conserved * <
  • and overspill from the RCS *
  • minimized. *
                                            • =************www***

4 S_ TART ONE SI PUMP 5 QNU~OR CNMT 20 REX ERSPILL CON)1T10i:

a. At the first indication of any APPROV ED containment overspill -

EVACUATE CONTAINMENT APR5 1990

$ $ UvYw Page 55 of 62 (0192Q/0018Q/011990)

. - , ,_._ ___.._. _ _ _.._._ ._.__.._ _ _ > _ _ . , ~ .

e. ,

j y

LOSS OF RH COOLING UNIT .1 ,

1BWOA .. l

/,.

c 1REVa 55 PRIwl0  !

. t  :

l l-)

s, a;< \ ,

STEP ACTION / EXPECTED RE5 DON 5E - PTTFONSE NOT OLT AiNED

, .:~  ;

1  :

L ..

H ATIACf21EhT_G._ RAGE 3 .of_1). l

l. SIJR1P HOT LEG 1NJECI1Qll j

=

6 tiORIIGLRWSI_LEXB.: 1 3

a. VXEH RWST. EMPTY ALARM is LII  ;

. . TEN stop the Turining SI pump-  ;

and either use another ATTACFMZNT  ;

or-make-up to RWST with a  !

p bore,ted source ] .,

': 7- CHEC( IF SI FLOW' -;

~'

CAN BE STOPPE); j

.a. Check reactor vessel level: a. Do HQI stop SI

( flow. RETURN TO-

_o -RVLIS plenum. region-- Step 5 of this j '

GE ATIE THAN QR ATTACHMENT.

l.

EQUAL TO 37%  !

I -OR-g:- 1 o ILI-RYO46,.RV HL LEVEL - l s

GE ATIB THAN OR_IQlIAL 1 -T0 393'6"= ,

-OR-  :

I o 'Tygon hose GE ATER IRAN 393'6" ,

b. Do HQI stop SI  !

lb. Check RCS temperature -

SIABLE;OR DECE. EASING flow. RETURN TO  !

Step-5 of this  !

ATTACHMENT.

c. Verify SI pumps miniflow t

irolation valves - DEEH:  :

e- 1SI8813

  • o 15I8814 (lA SI Pp) APPROVED  :

o 15I8920 (1B SI Pp) t APR'5 1990 Step continued on next page

,,,, o, yo, _ _;

e nsmw 6 l

i

'Page 56 of 62 ,

~(0192Q/0018Q/011990) .;

i t

w ., ,. .. ._ ~_ _

~

LOS$ OF RH COOLING UNIT 1 1BWOA REY. 55 PRI-10 4

O _

ST r.P _

l ACTION / EXPECTED RE9?CNEE RE?FONSE NOT 06TyNED AIIACHliMT_Gl EAGE 4 of_O ELPUMP EQI_J,4GJ1LTIC.T1011 Step 7 (continued)

d. Close the RCS hot leg injection valves:

= ISIE802A o ISI8802B e . Ve rif y SI putep HQI_ LEG e. Stop the running injection flow - RIQfEED SI pump.

8 TEMPTS _10 RESTORE QM}gf

a. IE at anytime an RH train becomes available.

( HM:

1) Immediately align the RH train for RCS cooling per Bw0F PJI-6, PLACING THE RH SYSTEM IN SIPJTE0WN COOLING
2) Return SI System lineup to normal per SE direction
3) RETURN TO 1Bw0A PRI-10, Step 7

- END -

APPROVED APR 5 1990 Q ll$AEL&*~

Page 57 of 62 (0192Q/0018Q/011990)

t v

LOSS-OF RH UNIT 1 - 1BWOA - j REY. 55 PRI-10  !

i(

STEP- l ACTION / EXPECTED RESPON5E REEFONSE NOT OST AiNED ATIACIDfEliT H (PAGE 1 of 3)  :

ACCHHULATOR INJECTIOS l I

CAUTION l A rapid high pressure accumulator  ;

injection may disarrange fuel  ;

assemblies if the upper internals  ;

are removed.  !

~

CAUTION  !

The minimum ambient temperature for t pressurization of the accumulator (s) i 1s 70*F.

(

) *****************************************

  • N01I *  !
  • injection to obtain RCS cooling.
  • i i
  • only as necessary to' limit cavity
  • p
  • -spillover.

6 a'. OneTaccumulator pressure - a. Attempt to restore

! - INDICATING ON SCATI accumulator (s) or-Go To  :

another ATTACHMENT for RCS-  ;

cooling per TABLE A l (Page 8). .

b. One accumulator. level - b. Attempt.to restore INDICATING ON SCATI accumulator (s) or:GO To-another ATTACEMENT for RCS i cooling per TABLE A .

l (page 8),

l-L  !

j

-(~ APPROVED ADDC .

1000 samowuvo amens av==  ;

! Page 58 of 62 (0192Q/0018Q/011990) l

LOSS OF RH UNIT 1 1Bw0A n REV. 55 PRI-10 V _- -

- -- 1 STEP CT10.uEXPECTED RESPON5E PE?FONSE NOT 06T AiNED I l

MTACH11MT R (PAGE 2 of 3)  !

SC&lDWiATOL1UJLC11D11 2 EVA _UATEJEEU E . VITY LEVil FOR OVEb )

a. Refuel cavity level low a. Lower refuel cavity level enough to accept contents per Bw0P RE-4 FINAL DRAIN of accumulator without OF REFUEL CAVITY, TRANSFER overspill CANAL AND UPENDER AREAS.

3 g g {UMULATOR DIS (HARGE VALVES

a. At associated MCC Energize accumulator discharge valves:
  • 1SI8808A (MCC 131X2A Cub A3) 1SI8808B (MCC 132X2A Cub A3)

(q j

  • 1SI8808C (MCC 132X2A Cub A2)
  • 1SI8808D (MCC 131X2A Cub A2) 4 INJECT ACCUMULATOR:
a. RCS WR Cold or Hot Leg a. Go To Step 6.

, teraperatures - GREATER THAN OR EUAL TO 140'F

b. Inject one accumulator by b. II all accumulators manually opening its discharge injected isolation valve: IHFJi GO TO another j

ATTACHMENT for RCS cooling

o ISI8808A per TABLE A (page 8). ,

l o 1SI8808B o 1SI8808C o 1SI88030 1

APPROVED APR 5 1990

~S $7#sw (b

Page 59 of 62 (0192Q/0018Q/011990)

LOSS OF Ril UNIT'.1 IBWOA REV. 55- PRI-10 O

STEP- ACTION / EXPECTED RESPON5E REIFONSE NOT OBTA!NED I

ATTACHMENT _R_(PAGE 3 of 3_)

/(C.CUMULAIQH_INJECTIOli Y H a.--At first indication of any overspill - EYACUATE_C.011TAIEMENT 6 EVALUATE lEF::CTIVENESS OF C00LIN 3 i ETHOD:

a. Check RCS level: a. RETURN TO Step 1 of this ATTACHMENT, o RVLIS plenum region - AI LEAST 377.

~

l o lLI-RYO46'RV HL LEVEL -

GREATER THAN OR EOUAL TO f 393'6" l- .o -Tygon hose - GREATER THAN QR EOUAL TO 393 ' 6_'_'

b. Check RCS temperature - b~" RETURN TO Step 1 STABLE OR DECREASING of this-ATTACHMENT.
7. CON"I$JE eTTEM 3"S TO RES"O tER -

CO0 iNG:

a, II at. anytime an RH-train becomes-available,-

THEH: ,

1) Immediately align 1.he RH k train -f or~ RCS cool: ng using i c Bw0P RH-6, PLACING THE RH  !

SYSTEM IN SHUTDOWN COOLING  !

-i

2) Return SI accumualtors to APPROVED i normal lineup _per SE direction i APR.5 1990 i l; 3) RETURN TO 1BwoA PRI-10, Step 7 ,,,  !

! . mens nav=w  ;

- END -  !

l 'l l

Page 60 of 62 l

.(0192Q/0018Q/011990)  ;

.. . -.i

4 LOSS OF RH COOLING UNIT 1 IBw0A .

7_s REV. 55 ,

PRI-10 ,

( l x_/

STEP ACTION /EMPECTED RES;0N5E PE3FONS6 NOT 00T A#NED ATTACIIMEllT_1_QAGE 1 of 2) ,

IWST_GRAYlTY FEED 1 CHECK RRSI_LEYEL:

a. RWST level - ANY INDICAIED a. GO TO another ATTACHMENT ,

LEYEL for RCS cooling per TABLE A (page 8).

2 ESTABLISH FILL PATH FROM RWSI:

a. Verify containment sump ,

outlet isol vivs - CLQSED:

  • 1SI8811A
  • 1SI8811B
b. Verify RH pump suct from hot

,-s leg isol vivs - CLQSED: ,

U o 1RH8701A and B o 1RH8702A and E

c. Verify RH pump dsch viva -

QEEH:

o 1RH8724A

- o 1RH8724B

d. Verify RH EX Flow control vivs - QEEH:

o 1RH606 o 1RH607

e. Verify RE Pp 1A/B Mini-Flow ,

vivs - QEEH:

o 1RH610 o 1RH611 APPROVED >

APR 5 1990 Step continued on next page ,auo ,ooo em+ns ===

Page 61 of 62 (0192Q/0018Q/011990)

t LOSS OF RH COOLING UNIT 1 IBWOA REV, 55 9 PRI-10 STEP- ACTION /ERCTED RESPON5E REiFONSE NOT OST AiNED AITACHMEliT I (PAGE 2 of 21 RWST GFAVITY FEED Step 2 (continued)

f. Verify RH Ex Dsch.Line [

Dwst Isol Vivs - DEEN: {

o ISIB809A I o- ISIB809B

g. Verify RH pump Suct from RWST '

Isol-.Vivs .DIEN: j o ISI8812A- +

o 1SI8812B [

3-  :

EgATEEFFECTIVENESSOFCOOLING O  :

a. Chech RCS level - INCREASIliG a. GO T0 another ATTACHMENT i

i for RCS cooling per l TABLE A (page-8).  !

b. Check RCS level - GREATER b. Continue filling RCS from THAN 393'6"- RWST.  ;

I 4 -CONTINIJE ATTEMPTS TO RESTORE i RH C00 _IN3:

a.=II at anytime an RH train becomes ,  !

available, j IHEH: t

1) Immediately align the RH train-  ;

for RCS cooling per Bw0P RH-6, PLACING THE RH SYSTEM IN f SHUTDOWN COOLING- '{

2)-Return CV/SI systems co normal

-lineup per SE direction

. APPROVED f

3) RN'TO 1Bw0A PRI-10, APR 5 - 1990-l

-END-

)