Rev 4.1 to Procedure Bwhp 4006-008, Repairing, Determinating,Terminating,Splicing,Taping,Cable Jacket Repair & Application of Ray Chem Kit on Cable
ML20062N785
Person / Time
Site: Braidwood  
Issue date: 03/01/1993
From:
COMMONWEALTH EDISON CO.
To:
Shared Package
ML20062N784 List:
References
BWHP-4006-008, BWHP-4006-8, NUDOCS 9401210117
Download: ML20062N785 (20)


Text

{{#Wiki_filter:- p 7 BwHP 4006-008 E Revision 4.1 REPAIRING, DETERMINATING, TERMINATING, SPLICING, TAPING, 'I CABLE JACKET REPAIR AND APPLICATION OF RAY CHEM KIT ON CABLE A. PURPOSE ~i l To describe methods for terminating or splicing of instrument, control and power cables also insulating / environmentally sealing j electrical connections and terminations using Raychem Heat.

l Shrinkable products or taping.,

.4 B. REFERENCES 1. Specification L-2790 8 y f 2. Applicable S&L approved drawings, 20E-0-3000 series 9 7 3. S.N.E.D. Memo dated 1/8/82 i 4. I.E. Information Notice No. 84-01 ] 5. BwHP 4002-009, Inspection / Certification of Amp Crimp Tools. .j 6. BwHP 4002-022, Certification of Crimps performed using the i Burndy Y35/39 Hypress Crimp Tools. l 7. Applicable manufacturer's instructions and splice kit-information. .} 8. Applicable electrical wiring and schematic drawings. l 9. EQ Binder EQ BB120, EQGEN004, 015, 026, and 027. l

10. DwAP 1100-12, use of Heat Generating Equipment-and Heat
Sources, i
11. UFSAR:

3.11, T3.'11-2, F3.11-1. l

12. Applicable manufacturer's instructions / drawings supplied with taping materials kits.
13. Applicable S&L approved drawings 20E-2-3400, 20E-1-3400, 20E-0-3000N sheets 1 and 2, 20E-0-3000B.
14. Okonite Company drawings D-11486, D-ll489, D-ll490, D-ll492, D-11547, D-11559,'D-11560, D-5715 and D-5731.

i

15. Letter from F. Hennessey Amp Rep. phone 312-351-5030 to H.

Futch 8-22-88. Filed in Central Files in File DSN-1. )

16. Reg. Guide 1.75.

Prohibit splices in Raceways.

17. Standard N-C-0020, N-C-0040 and N-C-0051.

APPROVED Work Request No. 18(091992) ZWBWHP BR AIDWOOD. 3 ' y w.strE u vet.** m i 9401210117 940107 l PDit ADDCK 05000456 ) G PDR s i o

BwHP 4006-008 Revision 4.1 B.

18. NRC Information Notice 88-27 Date 9-12-88.

Inspection of-vendor installed lugs.

19. EAR 88-242 as amended by D. R. Pierce.

Use of isopropyl alcohol for cleaning cable.

20. Vendor Manual 2827 Book 3 GA Technologies RD-23 Rad Monitor.
21. Amp Catalog 75-338 Streamlined 12-88.

Filed in Central Files DSN-1 Approving Lugging Solid Wires.

22. Okonite Manuf acturing Standard Section 9.4.2.2 page 1, Tape Manufacturing Codes.

Filed in Central Files PURCH-6L.

23. Letter from Okonite Co. to Bill Warnis January 27, 1986 on Shelf Life for Okonite Tape.

Filed in Central Files PURCH-6L.

24. BwAP 1100-15 Fire Prevention when welding, cutting, grinding or performing open flame work.
25. Letter to G. Sorensen from D.

Elias Oct. 22, 1986 and letter from J.D. Deress to J.D. Regan Oct. 16, 1986 Vivs. 1/2 OG057A, 79, 80 and 81 be Raychem not tape splice.

26. NRC Information Notice 88-81 Non EQ qualification of Amp Butt Splices when not Raychem or taped.
27. Fax to H. Futch from M. Halderman 3M Ph. 512-984-5516 on manufacture date code and shelf life.

Filed in Central Files PURCH-6L.

28. EAR 89-348 tape motor termination for 4160 volt "V"

type terminations. l

29. ENC-QE-70, ME-P8 Procedure, Table 2.

Shelflives.[a;7,e .~ l $ M r. [fc= r, t m + ', ' - - ; Wgg - C. EEEREOUISITES ps j .i s 1. Equipment is Out-of-Service, if required. Supervisor / Designee VERIFY Prerequisite has been performed. N/A if not applicable. / Initial Date D. ERECAUn0HS 1. All personnel must adhere to the Braidwood Station Radiation Procedures. APPROVED W rk Request No. R 011993 2 18(091992) enuowooo ZWBWHP

1 BwHP 400'6-008' Revision 4.1 D. -2. All personnel must adhere to the Braidwood Station-Out-of-Service Procedures. E 3. All personnel must adhere to the Braidwood Station Administrative Procedures and Maintenance Department Memos. 4. If any foreign substance drips-out of cut cable sheaths during termination, contact the Master electrician for additional instructions. 5. Cables of opposite segregation code or division SHALL NOT be bound (Ty-Rapped) within the same bundle. j Supervisor / Designee VERIFY all precautions have been reviewed. i / [fI Initial. Date " ll >"ca u ng E. LIMITATIONS _AND ACTIONS .['*"' .o e In the event of a conflict betOeen the' referenced documents l i 1. and the S&L approved design drawings, the.S&L approved l drawings will prevail, i 2. All terminations or splices shall use only approved f materials. 3. Supervisory personnel shall indicate method to be used for terminations or splices, and method for insulating 6 terminations or splices. 4. Attachments of this procedure will not be applicable in all cases. Supervisory Personnel will initial /date applicable attachments 5. This procedure may be used for initial installation, repair or replacement of terminations and splices. I 6. Under no circumstance shall more than two (2) lugged connections be landed on a single terminal screw, unless specified by approved design documents, a. In instances where 2 lugs.are landed to a single screw, j they shall be landed back to back. 1 b. Lugs may be bent to facilitate installation but not"so much that it interferes with the terminal screw. APPROVED Work Request No. .I MAR 011993 3 18(091592) .,8,RpjDyf& ZWBWHP

BwHp 4006-008 Revision 4.l~ power. connections requiring bolted connections, such as at E. 7. switchgear, MCC's and motors shall be in accordance with approved drawings, All bolted connections shall use stainless steel a. hardware unless otherwice specified. b. Hardware shall include a bolt and nut with flat washers at each end and the appropriate star, split ring or l believille washer at the nut end unless otherwise specified. Where specified by vendor manuals, approved drawings, etc. 8. torquing requirements shall be observed. When no specific torque is required, connections shall a. be made in a good workmanship-like-manner by a craftsman using proper tools. Conductors not shown to be terminated (unless otherwise l 9. specified under drawing notes), shall be cut to-reach the f arthest spare terminal position, 1 layer of Okonite No. 35 tape applied to cover the exposed conductor or appropriate Ray Chem Kit and bundled with other conductors. pqq f !, 5% 79

10. Cable bend radius requirements shall be observed. "".

jjj See Dwg. 20E-0-3000B 394 h'

11. Stripping of conductors for termination or splicing musk'be 3 done without nicking, breaking or scraping the conductor, Stripping of conductors #10 AWG and smaller shall be a.

done with a stripping tool, Stripping of conductors #8 AWG and larger should be done b. with a sharp knife.

12. Cables to be terminated or spliced shall be adequately dressed and supported, if required.
13. All cables shall be properly identified.

Individual control and instrument FIELD conductors inside

14. equipment, panels, switchgear, MCC's etc., can be extended This if they are too short to reach the termination point.

applies to both safety and non-safety related terminations. All other splices including thermocouple extension wires must have prior engineering approval unless specifically-a. shown as spliced on design documents, Cable splices in raceways are prohibited as per Reg. b. Guide 1.75 Rev. 2 Sept. 1978. APPROVED Work Request No. 4 18(091992) MAR 011993 ZWBWHp ) g,Mg,gg,

i BwHP 4006-008 l Revision 4.1 i E.

15. When cables are being terminated to bus:-

l a. Surfaces shall mate properly. Draw file for flatness if { necessary, b. Contact surf aces shall be bright, clean and free of oxidation. Grease or oil shall be removed from the bus bar using i c. approved cleaner. t d. 'NO-OX-ID' or similar components shall be used if the I bus is not plated. DO Where specified, boots shall be installed over -l "d j e. [fs terminations. Individual terminations / splices shall be documented on b e g [? j

16. " Record of Terminations / Splices".

j t

17. Where Aloxite cloth is specified in this procedure, an i

approved equivalent may be used. l

18. All cables with safety-relatad instrumentation-(Type K) segregation which are located inside containment or in the f

steam tunnel which are terminated at instruments provided with pigtails by the' manufacturer shall not be terminated'at-J terminal blocks. Terminations shall be made with bolted lugs covered with Ray-Chem WCSF-N Heat shrink.

19. Semi-conductor tape roll shall be identified so that it 2

cannot be mistaken for insulating tape.

20. Thermocouple extension wires shall be terminated without lugs.

t

21. When removing a Ray-Chem Kit, all parts of the kit shall be removed.

No parts of kit shall be reused when remaking any connection. This includes shims, bolt. pads, etc.

22. When installing a Ray-Chem Kit any part found nicked, cut, gouged or cracked shall be discarded.

If damage is observed after installation the complete kit shall be removed ~and replaced.

23. Amp PIDG Lugs may be used to lug solid wire.

Use the same lugs, crimpers and dies that would'be.used if the wire was l stranded. 1/20G079, 1/20G080 and 1/20G081. Motor

24. Valves 1/20G057A, l

termina61ons inside the valve are to be insulated using Raychem. They are not to be insulated using a taped; i -l connection. APPROVED Work Request No. I MAR 011993 s 18(091992) B R AIDWOOD '-sne arm. ZWBWHP

BwHP 4006-008 Revision 4.1

25. Cable ties installed outdoors and exposed to sunlight should Cable ties located inside containment and E.

be black ties. i outside of enclosures shall be stainless steel or tefzel, r Standard cable ties may be used inside containment inside enclosures and in all other areas of the plant.

26. Amp PIDG Lugs a.

May be bent once b. May be bent no more than 90' Send radius must be at least the thickness of lug at c. location of bend. Do NOT use square cornered surf ace to make be d. :- -. ..< gp 3 d.

.r
3 h J

U=J Wire strands shall not contact bend. e. y 9 G];,j

27. Amp PIDG butt splices.

Insulated butt splice crimp does not need to be centered a. on butt splice seam, s r Uninsulated butt splice crimp to be centered on butt b. splice seam. If necessary the attachment for termination of cable and the 28. for insulating the termination shall be performed attachment simultaneously. r IP replacement motor comes supplied with factory lugs AND/OR

29. internal connections.

Inspect for cracked or broken lugs, proper size lugs, proper crimp and lugs secure on wire. Isopropyl alcohol or other approved solvents shall be used 30. for all cleaning.

31. Ray Chem splice minimum bend radius 5 times splice outside diameter.

Solenoid coils on valves 1/2 MS001A-D are not to be Solenoid coil wires are to be

32. terminated on terminal board.

ring lug bolted connection to field cable and raychem not Minimum Raychem is 5 1/2 inch as per drawing taped. 20E-1/2-4382H. is applicable if a heat gun is used for tube

33. BwAP 1100-12 shrinking.
34. BwAP 1100-15 is applicable if a torch is used for tube shrinking.

A P P R; O V E D Work Request No. .dAR 011993 6 18(091992) anuowoop ZWBNH.

f BwHP 4006-008 . Revision 4.1 E.

35. Taping material SHALL NOT exceed its shelf life.

Supervisor / Designee VERIFY all Limitations and Actions have been reviewed. / Initial Date F. PROCEDURE 1. VERIFY Amp tool certification date is within 1 year of usage j date. N/A if Amp tool not used. _w p Amp Tool EM #

  1. * *j o

QA # Next Cal Date t . a Initial Date 2. VERIFY BwHP 4002-022, Rev is in package if Burndy l Hypress crimp tool is to be used. N/A if Burndy Hypress not used. Crimp Tool EM # QA # / Initial Date 3. Termination j Work Analyst / Supervisor INITIAL /DATE applicable attachments. l a. Termination of instrunent, control and power cables 600 volt or less, #10 AWG and smaller. ATTACHMENT "A" BwHP 4006-008A1 / b. Termination of power cables 600 volt or less #B AWG and larger. ATTACHMENT "B" BwHP 4006-008A2 / c. Termination of SKV unshielded cable. t ATTACHMENT "C" BwHP 4006-008A3 / d. Termination of SKV and BKV shielded cable. ATTACHMENT "D" BwHP 4006-008A4 / A P P R OV E E-MAR 011993 Work Request No. 7 18(091992) ,83#;Nr S ZWBWHP \\ i

BwHP 4006-008 Revision 4.1 F. 3. e. Splicing of instrument;and control conductors inside equipment. ATTACHMENT "E" BwHP4h06-008A5 / f. Splicing of instrument and control cables. ATTACHMENT "F" BwHP 4006-008A6- / g. Splicing of 5KV or less unshielded power cables. Okonite Drawing D-ll559 ATTACHMENT "G" BwHP 4006-008A7 / h. Splicing'of SKV and 8KV shielded power ,$[7]"$ 7TfQ ,idQ cables. Okonite Drawing D-11489 G. L sf ATTACHMENT "H" BwHP 4006-008A8 / W-s< m i. Termination of control and instrument cable metal shielding braid or tape. i ATTACHMENT _"I" BwHP 4006-008A9 / ) ~ j. Termination of. 82-816-100 HN connector for GA Technologies Model RD-23 Radiation 'i Detector. i ATTACHMENT "J" BwHP 4006-008A10 / j 4. RAY. CHEM insulating. j Work Analyst / Supervisor INITIAL /DATE applicable attachments. l a. WCSF-N Sleeve installation for in-line butt splice crimped connections (1000 volts max) f 1 ATTACHMENT "K" BwHP 4006-008All / b. WCSF-N Sleeve installation for'in-line bolted connections. (1000 volts max) ATTACHMENT "L" BwHP 4006-00BA12 / c. Motor connection kit - stub configuration - 2 Wires per phase. (1000 volts max) ATTACHMENT "M" BwHP 4006-00BA13 / l APPROVED W rk nequest No. MAR 011993 3 i 18(091992) enuowooo

  • ar arv'r*

ZWBWHP l l l[

1 BwHP 4006-008 Revision 4.1 j F. 4. d. Motor Connection Kit 5-8 KV stub connection ATTACHMENT "N" BwHP 4006-008A14 / e. Motor connection kit - In-line bolted connection. (1000 volts max) Note: Attachment "L" may be used if applicable. ATTACHMENT "O" BwHP 4006-008A15 / f. WCSF-N sleeve installation instructions for repairing damaged conduction insulation ATTACHMENT "P" BwHP 4006-008A16 /

q b

g. End sealing kit - unterminated wire 48 and cable. (1000 volts max) ATTACHMENT "Q" BwHP 4006-008A17 /' h. V-stub connection kit - small valve, limit switch and level switch connections. (With cable shim) (1000 volts max) ATTACHMENT "R" BwHP 4006-008A18 / i. V-Stub Connection Kit - small valve, limit switch and level switch connections. (No cable shim)(1000 volts max)' ATTACHMENT "S" BwHP 4006-008A19 / j. Control cable kit - In-line splice. (2-12 conductors) (1000 volts max.) ATTACHMENT "T" BwHP 4006-008A20 / k. Power cable kit - Transition splice. 2-3 conductors (1000 volts max.). ATTACHMENT "U" BwHP 4006-008A21 / 1. Power cable kit - In-line splice. 2-3 conductors. (1000 volts max.) ATTACHMENT "V" BwHP 4006-008A22 / APPROVE 0 MAR 011993 Work nequest No. 18(091992) OsEr8cS 2WBWHP

GwHP 4006-008-Revision 4.1 F. 4. m. Power cable kit - In-line splice. 2-3 conductors. (1000 volts max.) (Similar to Attachment V except larger conductor) ATTACHMENT "W" BwHP 4006-008A23 / n. Instrument cable kit transition splice. t (STP, STT or STQ cables) (1000 volts max.) ATTACEMENT "X" BwHP 4006-008A24 / o. Instrument cable kit - In-line splice. (STP, STT or STQ cables) (1000 volts max.) ,J, p g ATTACHMENT "Y" BwHP 4006-008A25 / [$f p. Installation of Raychem NPK X-CCKN-06-01 Kit on 82-816-1000 HN Connector for GA Technologies Model RD-23 Radiation Detector ATTACHMENT "Z" BwHP 4006-008A26 / 5. Taping Work Analyst / Supervisor INITIAL /DATE applicable attachments. l HQIE

  • Cable jackets with abrasions, gouges or
  • indentations that are not greater than 50% of
  • the jacket thickness, HEED NOI be repaired.
  • Flattened cable in which the ratio of minimum
  • diameter to maximum diameter is greater than 90%

......NEED NQI be repaired. a. Repair of damaged cable jackets. HQ1E Steps 4.a.1) and 4.a.2) apply to 300 volt to 15 KV cable EXCEPT 1/c SKV and 1/c BKV e

  • non-shielded cable.

1) Abrasions, cuts, gouges or indentations. ATTACHMENT "AA" BwHP 4006-008A27 / APPROVtb (dAR 011993 Work Request no. 1g 18(091992) f,7,^,Nr rS ZWBWHP

BwHP 4D06-008 Revision 4.1 F. 5. a. 2) Cables with jacket section(s) torn off cable. ATTACHMENT "AB" BwHP 4006-008A28 /- b. Straight splice for multi-conductor control and instrument cable. ATTACHMENT "AC* BwHP 4006-008A29 / c. Typical pigtail splice for motor connections of 600 volt or less, control and instrument cable. ATTACHMENT "AD" BwHP 4006-008A30 / d. Termination of power cables 600 volts or less. ATTACHMENT "AE" BwHP 4006-008A31 / e. Straight splice for power cables 600 volts or less. ATTACNMENT "AF" BwHP 4006-008A32 / f. Termination of SKV unshielded cables. f""" r <gg ATTACHMENT "AG" BwHP 4006-008-A33 /' J' ,1- ', + U s i 9 Splicing of 5KV unshielded cables. 'j ~ ATTACHMENT "AH" BwHP 4006-008A34 / h. Termination of SKV to 15KV shicided cables. ATTACHMENT "AI" BwHP 4006-008A35 / i. Splicing of BKV shielded cables. Okonite Drawing D-Il489 ATTACHMENT "AJ" BwHP 4006-008A36 / j. Taping of I cable to 2 cables, 1/c #2, 125 volt DC splices. ATTACHMENT "AK* BwHP 4006-008A37 / k. Typical pigtail splices for motor connections of 4160 volts. ATTACHMENT "AL" BwHP 4006-008A38 / 4 A P P R OV E C-idAR 011993 Work nequest no. 18(091992) 07.Mf,,D, ZWBWHP

BwHP 4006-008 ~ Revision 4.1 ee. ...... mene ....se CAUTION TAPING MATERIALS ARE NOT TO BE USED IF PAST ITS *

  • EXPIRATION DATE.

.....e....... ...................mee annemessensee emmen...............emenemme NO.IE Okonite Tape Roll Core will have manufacture

  • date code.

i.e. A6 or A86. The number corresponds to year of manufacture 6 or 86 stands for year 1986. The A is code for month.

  • A - Jan., B - Feb., C - Mar., D - Apr.,

E.- May,* F - June, G - July, H - Aug., J - Sept.,

  • K - Oct., L - Nov. and M - Dec.

Note the letter *

  • I is NOT used.

Add shelf life to manufacture date to obtain expiration date. emmenemme**emeen...emeeneemanaemenneen...... memme ............................e== ...... eeeeeeeeenae liOIE

  • f m

,"*7 Scotch /3m tape uses the following tape core ,a 7g /M e marking. "d (1)XXXX (2)XX (3)XXIX (4)IX (5)X TAPE # SLITTERS JULIAN ROLL # MONTH e INITIALS DATE CODE SLIT

  • d
  • (1) Will be 1 or more numbers corresponding to tape i.e. 27 for 27 Tape or 13 for 13 Tape.

(2) Will always be 2 letters no numbers.

  • (3) Julian date' code i.e. 8241 will be 1988 and a the 241st day (August 28).

This is the date* of manufacture. (4) Roll number will be 2 or more digits. e

  • (5) Month slit will always be one letter.

en..... mennenenemmeneseen...... memeeneneeeeen no NOTE Add manufacture date to shelf life to determine

  • expiration date.

e m e n e m m e... m e......... e m e......................... F. 6. IF taping, step F.5., is to be performed, RECORD applicable date codes and expiration dates. N/A dates for tapes not used. N/A this step if no taping is to be performed. Taping materials shelflife expiration date, a. 1) Okonite T-95 tape Shelf Life 18 Months Date Code Expiration Date APPROVED Work Request No. MAR 011993 32 18(091992) B R AIDWoOD ZWBWHP j

t .BwHP 4006-008 Revision 4.1 L F. 6. a. 2)- Okonite No. 35 tape i i Shelf Life 18 Months Date Code Expiration l Date 3) Glass tape 3M #27 Shelf life 5 Years Date Code Expiration Date r 4) Semi / conducting tape ~ [ Scotch #13 Date Code Expiration Shelf Life 5 Years

Date,

...................................................= NOTE ~* Visually INSPECT nuclear cement for signs of q

  • hardening or separation.

Separation is

  • indicated by a change from normal pink color'to
  • v

.l

  • amber or honey color.

Do not use if any signs:

  • of hardening or separation are observed.

l 6 [ j g

  • Splicing cement will have statement "Use l
  • Before This is expiration
  • date.

The date of manufacture will not be I

  • written on can.

=* 5) Okonite Nuclear Splicing Cement i Shelf Life 12 Months Expiration 'i Date ,[ / u rr " '9r" T j Initial-Date LI (;,, M .j j l "i t i i d 1 APPROVED 1 MAR 011993-la 18(100192) DRAIDWOOD l ZWBWHp

BwHP 4006-008 ~ Revision 4.1 emmennemaneenennenemenemannen.......e==enemanaammee NOTE Sign off steps in the attachments to this a procedure indicate that steps have been performed for ALL terminations / splices covered by the Work Request. Individual conductor terminations / splices are documented by filling in appropriate blocks on Record of Terminations /* Splices. menmanaanmamenesee ammeanamnennemenomannan.nemannaamannennemanamensame g Appropriate steps in the attachments to this procedure may be repeated as many times as

  • necessary to complete all terminations / splices
  • covered by the Work Request.

Entry of terminations / splices on Record of Terminations /

  • Splices with initial /date indicates that all appropriate steps have been completed for that particular conductor.

asen.amenenamanmanaammamananmannaammenamaammamanese NOTE Record determ/reterm and perform verification in accordance with BwAp 400-9T1 or equipment

  • specific procedure.

men....annennesmana.........enne............ .y d2 c' A PP R CP/ E C-MAR 011993 Work Request no. 14 18(091992) nu..AIDWOoD DR nc acnc* ZWBNHp

BwHP 4006-008 Revision 4.1 RECORD OF TERMINATIONS / SPLICES Type Cable Conductor Term. Board /.7-Term. Attachment Term / Splice complete &mber Number / Color Term. No S.Solice Used Initial /Date P / / / / / / / / / / / v' / / / l / / p / / / / / g APPROVED p 18(091592) ZWBWHP ,..AIDWOOD BR nc nsview .1

BwHP 4006-008 ~ Revision 4.1 4 annaamanneene.nenamenemaan amanneannemanamaan.eenes CAUTION DO NOT PLACE COMPLETED SPLICES ON CABLE HANGER

  • l OR INSULATORS AS THE WEIGHT OF THE CABLE MAY

-{ DEFORM THE SPLICE. IF SUPPORTS ARE REQUIRED, PLACE AT EITHER END OF SPLICE. k annemanaamannemanan annemannaeanme===ensammamenaam j NOTE

  • Upon completion of attachments proceed to
  • BwHP 4006-008 step F.8.

..ma. .....en........... nm.ne..................... F. 7. PROCEED to applicable attachment (s) to perform work. / Initial Date i 8. REQUEST temp lift of out of service. N/A this step if not applicable. / Initial Date 1 9. PERFORM functional check to ensure proper equipment operation. N/A this_istep'"ih Mdt applicable. Fra ra a om p% > / t ~ Initial Date ~ ;,3

10. All applicable work completed and any discrepancies and corrective actions noted in comments section.

COMMENTS (Initial /Date all entries): j l s / / \\ Initial Date .Supv. Date' I i I 4 i A PPR CFV E D iAAR 011993 W rk Request No. 3, 18(091592) BRAIDWOOD ZWBWHP i i j l

i BwHP 4006-008 Revision 4.1 G. ACCEPTANCE CRITERIA i

None, a

H. CHECKOFF LISTS / DATA SHRFTS 1. Termination of instrument, control and power cables 600 volt or less, #10 AWG and smaller. ATTACHM2NT "A" DwHP 4006-008A1 2. Termination of power cables 600 volt or less #8 AWG and larger. j ATTACHMENT "B" BwHP 4006-003A2 3. Termination of SKV unshielded cable. ATTACHMENT

  • C" BwHP 4006-008A3 4.

Termination of SKV and 8KV shielded cable. ATTACHMENT

  • D" BwHP 4006-008A4 5.

Splicing of instrument and control conductors inside equipment. yy[tljp ATTACHMENT "E" BwHP 4006-008A5 ,g,-: ' t Ri s Splicing of instrument and control cables. _ 6. ATTACHMENT "F" BwHP 4006-008A6 7. Splicing of unshielded power cables SKV or less. ATTACHMENT "G" BwHP 4006-008A7 8. Splicing of SKV and 8KV shielded power cables. ATTACHMENT "H" BwHP 4006-008A8 9. Termination of control and instrument-cable metal shielding braid or tape. ATTACHMENT "I* BwHP 4006-008A9

10. Termination of 82-816-100 HN connector for GA Technologies Model.RD-23 radiation detector ATTACHMENT "J"

BwHP 4006-008A10 APPROVE (- " '" "*9"**' "

  • idAR 011993 17 18(091592) anaiowoon ZWBWHP I

I i

q BwHP 4006-008 Revision 4.1 H.

11. WCSF-N Sleeve installation for in-line butt splice' crimped connections (1000 volts max) l ATTACHMENT "K" BwHP 4006-008All
12. WCSF-N Sleeve installation for in-line bolted connections (1000 volts max)

ATTACHMENT "L" BwHP 4006-0008A12

13. Motor connection kit - stub configuration

-2 wires per phase. (1000 volts max) ATTACHMENT "M" BwHP 4006-008A13

14. Motor connection kit 5-8 KV stub connection ATTACHMENT "N" BwHP 4006-008A14
15. Motor connection kit - In-line bolted connection. (1000 volts max)

Note: Attachment "L" may be used if applicable. ATTACHMENT "O" BwHP 4006-008A15

16. WCSF-N sleeve installation instructions for repairing damaged conduction insulation m r "' M'!p

,s - 7,,, ATTACHMENT "P" BwHP 4006-008A16 Qs

17. End sealing kit - unterminated wire and cable.

(1000 volts max) s Bw r 4006-00BA17 u ATTACHMENT *Q"

18. V-stub connection kit - small valve, limit switch and level switch connections.

(With cable shim) (1000 volts max) ATTACHMENT "R" BwHP 4006-008A18

19. V-stub connection kit - small valve, limit switch-and level switch connections.

(No cable shim)(1000 volts max.) ATTACHMENT "S" BwHP 4006-006A19

20. Control cable kit - In-line splice.

(2-12 conductors) (1000 volts max.) ATTACHMENT "T" BwHP 4006-008A20 ADPROVED Work Request No. MAR 011993 18 18(091592) ZWBWHP 3.nmowooo. a.wr.cm

BwHP 4006-008 Revision 4.1 'l H.

21. Power cable kit - Transition splice.

(2-3 conductors) (1000 volts max.) ) ATTACHMENT "U" BwHP 4006-008A21

22. Power cable kit - In-line splice.

(2-3 conductors) (1000 volts max.) ATTACHMENT "V" BwHP 4006-008A22

23. Power cable kit - In-line splice.

(2-3 conductors) (1000 volts max.) Similar to Attachment V except larger conductor. ATTACHMENT "W" BwHP 4006-008A23

24. Instrument cable kit transition splice.

(STP, STT or STQ cables) (1000 volts max.) ATTACHMENT "X" BwHP 4006-008A24 P

25. Instrument cable kit - In-line splice.

(STP, STT or STQ cables) (1000 volts max.) st ,,y en ~ ATTACHMENT "Y" BwHP 4006-008A25 i u~

26. Installation of Raychem NPKX-CCKN-06-01

![ D#"* kit on 82-816-1000 HN connector for GA Technologies Model RD-23 radiation detector. ATTACHMENT

  • Z*

BwHP 4006-008A26

27. Repair of abrasions,' burns, cuts, gouges or indentations in the overall jacket of multi conductor cable for 300Vto 15KV, except 1/c SKV and 1/c 8KV non-shielded cable ATTACHMENT "AA" BwHP 4006-00827 i
28. Repair of cables with jacket section(s) torn off cable, 30CV to 15KV excePt 1/C 8KV non-shielded cable.

ATTACHMENT'"AB" BwHP 4006-008A28

29. Straight splice for multi-conductor control and instrument cable.

ATTACHMENT"Ag*pp B g,4006-008A29 Work Request No. i 18(091592) g,,,,,000 ZWBWHP w-e ne a r ver

  • BwHP 4006-008 Revision 4.1 H.
30. Typical pigtail splice for motor connections of 600 volt or less, control and instrument cable.-

ATTACHMENT "AD" BwHP 4006-008A30

31. Termination of power cables 600 volt or less.

ATTACHMENT "AE" BwHP 4006-008A31

32. Straight splice for power cables 600 volts or less.

ATTACHMENT "AF" BwHP 4006-008A32

33. Termination of SKV unshielded cables.

ATTACHMENT *AG" BwHP 4006-008A33

34. Splicing of SKV or less unshielded cables.

ATTACHMENT "AH" BwHP 4006-008A34

35. Termination of SKV to 15KV shielded cables.

ATTACHMENT "AI" BwHP 4006-008A35

36. Splicing of 8KV shielded cables.

M! c., jH ATTACHMENT "AJ" BwHP 4006-008A36 s<> s ds

37. Taping of I cable to 2 cable, 1/c #2, r,, "

125 volt DC splices. gh st ATTACHMENT "AK" BwHP 4006-008A37

38. Typical pigtail splices for motor connections of 4160 volts.

ATTACHMENT "AL" BwHP 4006-008A38 AppROVtv (Final) i4AR 011993 work nequest No. 18(091592) namowooo "'ts "Eva* ZWBWHP -}}