Special Rept 95-003:on 950223,TB HVAC Sys Fire/Carbon Dioxide Dampers Rendered non-functional in Support of Plant Mod M1-95-007.Dampers Not Returned to Functional Condition within Required Restoration Period Due to Duration of Mod
ML20081K827
Person / Time
Site: FitzPatrick Constellation icon.png
Issue date: 03/24/1995
From: Harry Salmon
POWER AUTHORITY OF THE STATE OF NEW YORK (NEW YORK
To:
NRC OFFICE OF INFORMATION RESOURCES MANAGEMENT (IRM)
References
95-003, 95-3, JAFP-95-0145, JAFP-95-145, NUDOCS 9503290306
Download: ML20081K827 (2)


Text

, - . . . _ -

dE

~

James A. Fit:Petdek v

" '~

  • Muclear Power Plent P.O. Box 41 .

Lycoming, New York 13093 315 342-3640 -

WrkPbwer Harry P. Salmon, Jr.

Resident Manager :

  • Mweb

!+cil-24 1995 JAFP-95-0145 f

United States Nuclear Regulatory Commission Document Control Desk Mail Station P1-137 Washington, D.C. 20555

SUBJECT:

DOCKET NO. 50-333 SPECIAL REPORT 95-003: NON-FUNCTIONAL FIRE BARRIER PENETRATION SEALS

Dear Sir:

The New York Power Authority (NYPA) submits this Special Report in accordance with the requirements of Administrative Procedure AP-01.04, " Tech Spec Related

, Requirements, Lists, and Tables *". The Report identifies Fire Protection Features that, by plan, were rendered non functional to accommodate certain activities during_

the 1994/1995 Refueling Outage. While these features were non-functional, plant administrative controls were in place to ensure adequate fire protection _was provided.- .

INTRODUCTION:

The Fire Protection Program requirements were removed from Technical Specifications with Amendment 218 to the James A. FitzPatrick Operating License dated November 3,1994. Administrative Procedure AP-01.04 provides centrols for these Fire Protection Program requirements, lists, and tables previously included in Technical Specifications. If the non-functional Fire Protection Features cannot be restored to a functional status within 7 days, the procedure requires a written report to the NRC within 30 days outlining the action (s) taken, the cause for the non-functional Fire Protection Features, and plans and schedule for restoring the Fire Protection Features to a functional status. ]

9503290306 55o324 PDR S

ADOCK 05000333 PDR ,

&[

// I a g .

r

l

~

J United States Nuclear Regulatory Commission l SPECIAL REPORT 95-003: NON-FUNCTIONAL FIRE BARRIER '

PENETRATION SEALS

.' Page 2 DISCUSSION:

Turbine Building HVAC System fire / carbon dioxide (COJ dampers 67CD-3 and 67CD-4, located in the East and West Electric Bays, were rendered non-functional on ,

February 23,1995 in support of plant modification M1-95-007. Immediate actions taken included establishing continuous fire watches for the unprotected areas.

An evaluation of CO2 protected areas at JAF determined that the East and West Electric Bays did not have adequate venting capability during discharge of the CO2 suppression systems. To correct this deficiency, fire /CO2 dampers 67CD-3 and 67CD-4, between the Electric Bays and Turbine Building, were modified to eliminate .

their automatic closure feature when CO2 discharge is initiated. Dampers were reclassified as fire dampers and assigned new system component identifications 67FD-1 and 67FD-9.

Due to the duration of the modification, dampers were not returned to a functional condition within the required restoration period.

EOUIPMENT RESTORATION:

Plant modification MI-95-007 was completed and fire dampers 67FD-1 and 67FD-9 were returned to a functional status on March 21,1995. ,

If you have any questions concerning this matter, please contact Mr. O. Brownell at -

(315) 349-6360.

Very truly yours, i l /

HARRY P. SALMON, JR.

RESIDENT MANAGER cc: USNRC, Region I USNRC Resident Inspector A. Zaremba D. Kerr -