. - a u:

bih)(k O ha NAEIJ TELECOPY MESSAGE Certified By hg/

C*

TO:

Prus1 dent and Chief Operating Officer T0:

Director of Regulatory Operation Chairman SRC USNRC Region 1 Senior Vice-President. Nuclear Generation 631 Park Avenue King of Prussia, Pennsylvania 19406 Date/ Time: Jd/f3 AS : s'3 m.

Date/ Time: M6I4

//i\\

W I i

//

FROM:

Power Authority of the State of New York James A. fitzPatrick Nuclear Power Plant P. O. Box 41 Lycoming. New York 13093 EBJECT:

PROMPT REPORTABLE OCCURRENCE DOCKET NO.

50-333 LICENSE NO.

OPR-59 ASSIGNED OR NO.83-029 LER NO.

_83-008 EVENT DATE:

2/2/83 REPORT DATE:

2/3/83 EVENT DESCRIPTION: The licensee was informed by telephone con-versation that an error had been made in the ODYN base deck for Reload 4 Cycle 5 analysis.

This error led to ACPR values for pressurization transients non-conservative with respect to the Supplemental Reload Licensing submittal (Y1003J01A25) values.

The limiting value of CPR used throughout the cycle has been correct since a non-pressurization event has been the mosc limiting.

COMPONENTS INVOLVED: N/A CAUSE and REMEDIAL ACTION:

A personnel error in performing the licensing analysis for Reload 4.

The remedial action:

Technical Specification change i

r FNIgogagg the recalculated ACPR geA POWER 100 Routine Startup Shutdown Routine Shutdown Refueling Steady State Pcver x

Other Load Change Not Applicaole A written follcw-up raport will be submitted within t*,vo weeks.

t/

f.

' CORBIN A. McNEILL. JR.

8302230224 830203 PDR ADOCK 05000333 RESIDENT MANAGER S