Special Rept:On 950104,fire Protection Features Inoperable to Accomodate Certain Activities During Refueling outage.Non-functional Fire Protection Features Will Be Restored Prior to Plant Restart
ML20078L661
Person / Time
Site: FitzPatrick Constellation icon.png
Issue date: 02/06/1995
From: Harry Salmon
POWER AUTHORITY OF THE STATE OF NEW YORK (NEW YORK
To:
NRC OFFICE OF INFORMATION RESOURCES MANAGEMENT (IRM)
References
NUDOCS 9502130084
Download: ML20078L661 (3)


Text

. . _ . - _ __- . . _ _ ._.

James A.FitaPetrick

.g Nucleet Power Plant P.o. Dox 41

. - ', Lycoming. New York 13093

' 315 342-3840 esi ent Ma ag Febrxiry 6,1995-JtG? 05-0062 United States Nuclear Regulatory Commission l Document Control Desk Mail Station P1-137 Washington, D.C. 20555

SUBJECT:

DOCKET NO. 50-333 SPECIAL REPORT 95-001: NONFUNCTIONAL FIRE PROTECTION FEATURES  :

l

Dear Sir:

The New York Power Authority (NYPA) submits this Special Report in accordance with the requirements of Administrative ,

Procedure AP-01.04, " Tech Spec Related Requirements, Lists, l and Tables *". The Report identifies Fire Protection Features that, by plan, are being rendered inoperable to accommodate certain activities during the 1994/1995 Refueling Outage. While these Features are inoperable, plant administrative controls are in place to ensure ,

adequate fire protection is provided. This Report applies +

only to Fire Protection Features which are being rendered inoperable as part of planned outage evolutions, and which will be restored functional prior to plant startup. The following identifies the features which have exceeded their action conditions.

BREACHED FIRE BARRIERS The following Fire Barrier penetration seals have been rendered inoperable as-part of planned evolutions during the current refueling outage. These penetration seals have remained inoperable for more than seven days. These are in addition to those identified in special report 95-001 sent to you on January 4, 1995:

o 67FD Turbine Building Oil Room Damper e 67FD Turbine Building Foam Room Damper, El. l 272' e 67FD Turbine Building Foam Room Damper, El.

252' o 72FD Battery Room Vent Supply Fire Damper e 76FDR-A-252 Turbine Building Oil Room Fire Door 1 9502130084 950206 4 V

I' PDR ADDCK 05000333 -

_- . - - - . -. .- -. =. _ _ . _ _ . -

t. SPECIAL REPORT 95-001: NONFUNCTIONAL FIRE

. . PROTECTION FEATURES P, age 2

.

Door

<

  • 76FDR-A-300 Control Room to Relay Room Stairs Fire Door
  • Block wall at north and of Turbine Building, El.

252' These penetration seals have been made inoperable to permit modification, upgrade, or repair of the-penetration seals themselves, to facilitate continuous fire watches established in connection with outage  !

work, or to permit transport of material used during .

outage work.

Fire watches have been established at these locations. l In addition, a roving operator watch surveys the areas of 76FDR-A-286-23 and -24 on a routine basis.

A Special Report is required for these fire barrier breaches since the equipment has been inoperable for l greater than 7 days. <

IMOPERABLE FIRE PROTECTIOM/ DETECTION SYSTEMS ,

The Ten Ton CO System has been rendered inoperable,  !

and has remained inoperable for more than fourteen days. This planned evolution was entered to permit modifications to the control panel for the CO2 System. ,

Backup fire suppression and fire watches have been  ;

established for the affected areas.

A Special Report is required since the equipment has j been inoperable for greater than 14 days.

For each of the above breached barriers and system impairments, AP-01.04 provides direction to ensure adequate fire protection compensatory actions and controls are maintained such as: ,

  • Breach permits are obtained for each fire barrier breached. These permits ensure that proper reviews are obtained, appropriate compensatory fire protection measures are established, and appropriate notifications and postings are made.
  • These non-functional Fire Protection Systems and barriers are included in the Active LCO (Limiting condition for Operation) list for the outage. The list is reviewed and updated daily and presented in daily outage planning meetings.
  • Each proposed Fire Protection System impairment is evaluated on a case by case basis and additional precautions are implemented as appropriate.

i4 SPECIAL REPORT 95-0018 NONFUNCTIONAL FIRE

.'<- ' PROTECTION FEATURES P, age 3 SYSTEM /EQUIPMIMT RESTORATION:

It is intended that these non-functional Fire Protection Features will be restored to functional status in accordance with the requirements of the James A. FitzPatrick Fire Protection program prior to plant restart.

l If you have any questions concerning this matter, please contact Jim Foley at (315) 349-6362.  ;

Very truly yours, f

HARRY P. SALMON, .

RESIDENT MANAGER HPS:JF: tic cc: USNRC, Region I USNRC Resident Inspector A. Zaremba C. Faison (WPO)