 Issue dateTitleTopic
JAFP-95-0145, Special Rept 95-003:on 950223,TB HVAC Sys Fire/Carbon Dioxide Dampers Rendered non-functional in Support of Plant Mod M1-95-007.Dampers Not Returned to Functional Condition within Required Restoration Period Due to Duration of Mod24 March 1995Special Rept 95-003:on 950223,TB HVAC Sys Fire/Carbon Dioxide Dampers Rendered non-functional in Support of Plant Mod M1-95-007.Dampers Not Returned to Functional Condition within Required Restoration Period Due to Duration of ModFire Barrier
Fire Protection Program
JAFP-95-0082, Special Rept:On 950109,inoperability of Fire Suppression Features Associated W/Listed Areas Noted.Low Carbon Dioxide Concentration Deficiency Will Be Corrected by Changing Discharge Timer Setpoint22 February 1995Special Rept:On 950109,inoperability of Fire Suppression Features Associated W/Listed Areas Noted.Low Carbon Dioxide Concentration Deficiency Will Be Corrected by Changing Discharge Timer SetpointFire Watch
ML20078L6616 February 1995Special Rept:On 950104,fire Protection Features Inoperable to Accomodate Certain Activities During Refueling outage.Non-functional Fire Protection Features Will Be Restored Prior to Plant RestartFire Barrier
Fire Protection Program
JAFP-94-0252, Special Rept 94-001 Re Fire Barrier Penetration Seals Not Restored within TS Time Frame.Caused by Scope of Work in Steam Tunnel.Roving Fire Watch Posted in Recirculation Motor Generator Set Room & Floor Plugs Removed6 May 1994Special Rept 94-001 Re Fire Barrier Penetration Seals Not Restored within TS Time Frame.Caused by Scope of Work in Steam Tunnel.Roving Fire Watch Posted in Recirculation Motor Generator Set Room & Floor Plugs RemovedFire Barrier
Fire Watch
JAFP-93-0601, Special Rept 93-005 Re Nonfunctional Fire Door for Greater than 7 Days Due to Planned Evolution During Fall 1993 Maint Outage.Continuous Fire Watch Posted for Duration.Maint Completed & Sys Restored on 93110911 November 1993Special Rept 93-005 Re Nonfunctional Fire Door for Greater than 7 Days Due to Planned Evolution During Fall 1993 Maint Outage.Continuous Fire Watch Posted for Duration.Maint Completed & Sys Restored on 931109Fire Barrier
Continuous fire watch
Fire Watch
JAFP-93-0265, Special Rept 93-003 Re Nonfunctional Fire Barrier Penetration Seal Due to Design & Equipment Problems.Drain Piping Installed,Penetration Sealed & Determined to Be Operable on 9304203 May 1993Special Rept 93-003 Re Nonfunctional Fire Barrier Penetration Seal Due to Design & Equipment Problems.Drain Piping Installed,Penetration Sealed & Determined to Be Operable on 930420Fire Barrier
Accidental discharge
Fire Protection Program
JAFP-93-0031, Special Rept 93-002:on 921228,fire Barrier,Installed in Front of Fire Door 76FDR-A-272-5,determined to Be Nonfunctional Based on Unsealed Opening in Barrier.Fire Watch Posted & Maint Work Request Initiated18 January 1993Special Rept 93-002:on 921228,fire Barrier,Installed in Front of Fire Door 76FDR-A-272-5,determined to Be Nonfunctional Based on Unsealed Opening in Barrier.Fire Watch Posted & Maint Work Request InitiatedFire Barrier
Fire Watch
JAFP-93-0011, Updated Special Rept Documenting Inability to Restore Fire Door to Functional Status within Required Time Frame.On 921201,door Determined to Be Nonfunctional & Not Restored Until 921211.As of 930104,two Doors Remain Nonfunctional7 January 1993Updated Special Rept Documenting Inability to Restore Fire Door to Functional Status within Required Time Frame.On 921201,door Determined to Be Nonfunctional & Not Restored Until 921211.As of 930104,two Doors Remain NonfunctionalFire Barrier
JAFP-93-0006, Special rept:post-work Testing & Repair of a Feedwater Return Valve 34NRV-111A Could Not Be Completed within 7-day Period.Continuous Fire Watch & Roving Fire Watch Posted & One Floor Plug Removed on 921219 & Replaced on 9212216 January 1993Special rept:post-work Testing & Repair of a Feedwater Return Valve 34NRV-111A Could Not Be Completed within 7-day Period.Continuous Fire Watch & Roving Fire Watch Posted & One Floor Plug Removed on 921219 & Replaced on 921221Fire Barrier
Continuous fire watch
Fire Watch
JAFP-92-0854, Special Rept:On 921209,fire Barrier Doors Remain Nonfunctional Based Upon Revised Surveillance Test Acceptance Criteria.Revised Surveillance Test Criteria & Improved Maint Work Procedures Implemented17 December 1992Special Rept:On 921209,fire Barrier Doors Remain Nonfunctional Based Upon Revised Surveillance Test Acceptance Criteria.Revised Surveillance Test Criteria & Improved Maint Work Procedures ImplementedFire Barrier
JAFP-92-0782, Special Rept:On 921002,insp of Fire Doors,Using Revised Surveillance Test Procedure Initiated & Fire Barrier Doors Not Restored to Operable Status within 7 Days.As of 921109, 77 Doors Remained Nonfunctional.Fire Watch Posted9 November 1992Special Rept:On 921002,insp of Fire Doors,Using Revised Surveillance Test Procedure Initiated & Fire Barrier Doors Not Restored to Operable Status within 7 Days.As of 921109, 77 Doors Remained Nonfunctional.Fire Watch PostedFire Barrier
Fire Watch
JAFP-92-0570, Special Rept:On 920703,CO-2 Fire Door Required to Close on CO-2 Sys Activation Did Not Fully Close When Released.Fire Door Repaired & Tested Satisfactorily31 July 1992Special Rept:On 920703,CO-2 Fire Door Required to Close on CO-2 Sys Activation Did Not Fully Close When Released.Fire Door Repaired & Tested SatisfactorilyFire Watch
JAFP-92-0454, Special Rept:On 911003,discovered pin-hole Leak in Diesel Fire Pump.Caused by Discharge Pressure.Surveillance Test Procedure Was Revised10 June 1992Special Rept:On 911003,discovered pin-hole Leak in Diesel Fire Pump.Caused by Discharge Pressure.Surveillance Test Procedure Was Revised
JAFP-92-0435, Special Rept:On 920504,CO2 Fire Suppression Sys Declared Inoperable When Walkdown Revealed That 4 Instead of 5 Nozzles Installed in Sys.Caused by Absence of Design Calculations.Replacement Nozzle Installed on 9205183 June 1992Special Rept:On 920504,CO2 Fire Suppression Sys Declared Inoperable When Walkdown Revealed That 4 Instead of 5 Nozzles Installed in Sys.Caused by Absence of Design Calculations.Replacement Nozzle Installed on 920518Continuous fire watch
JAFP-92-0316, Special Rept:On 920406,electric Driven Pump Was Out of Service for Approx 16 Days & 5 H.Caused by Extended Overhaul Time.Electric Motor Was Removed,Overhauled,Tested,Found Satisfactory & Returned to Plant11 May 1992Special Rept:On 920406,electric Driven Pump Was Out of Service for Approx 16 Days & 5 H.Caused by Extended Overhaul Time.Electric Motor Was Removed,Overhauled,Tested,Found Satisfactory & Returned to Plant
JAFP-91-0835, Special Rept:Relay Room CO2 Sys Declared Inoperable Due to Failed Surveillance Test.Caused by Slow Closure Time of Temp Control Damper 70MOD-103.Continuous Fire Watch Established & Design Basis Reconstitution Planned19 December 1991Special Rept:Relay Room CO2 Sys Declared Inoperable Due to Failed Surveillance Test.Caused by Slow Closure Time of Temp Control Damper 70MOD-103.Continuous Fire Watch Established & Design Basis Reconstitution PlannedContinuous fire watch
ML20079L2973 February 1983Telecopy ROs 83-029 & 83-008:on 830202,licensee Informed by Telcon That Error Made in Odyn Base Deck for Reload 4 Cycle 5 Analysis.Caused by Personnel Error in Performing Licensing Analysis.Tech Spec Change Initiated
JAFP-82-1106, Ro:On 820628,combustion in Offgas Sys Observed.Caused by Improper Valve Lineup Allowing More Gas to Recombiner than Dilution Flow Rate Could Support.Incident Discussed W/Shift Supervisor & Training Will Be Developed19 October 1982Ro:On 820628,combustion in Offgas Sys Observed.Caused by Improper Valve Lineup Allowing More Gas to Recombiner than Dilution Flow Rate Could Support.Incident Discussed W/Shift Supervisor & Training Will Be Developed
ML20125B28026 September 1979RO-79-158:on 790926,A/E Advised That HPCI & Automatic Depressurization Sys (ADS) Cabling Affecting Control of HPCI Inboard Steam Supply Isolation Valve Did Not Meet NRC Criteria.Caused by HPCI & ADS Cabling in Same Raceway
ML20071G33318 December 1978RO 78-097/01X-0:during Surveillance of Temp Switches,Instru Were Found Set Above Tech Spec Limit Due to Personnel Using Wrong Conversion Table