Text

.

.s

?'

,,1, p u tauq[0, j

V UNITED STATES M

l 3.y pe( j

~ NUCLEAR REGULATORY COMMISSION Y

,.p, n. ;-

wAssinaTou, o. c.20sss

.9 September 25, 1980 l

j Docket No. 50-312 l

Mr. J. J. Mattimoe Assistant General Manager and

[

Chief Engineer Sacramento Municipal Utility District 6201 5 Street P. O. Box 15830 Sacramento,- California - 95813

Dear Mr. Mattimoe:

We have performed a preliminary review of your Proposed Amendment No. 68 (Fire Protection) to the Rancho Seco Technical Specifications. As previously agreed to by SMUD, the proposed Technical Specifications were to be based upon the relevant fire protection sections of NUREG-0130 " Standard Technical r

Specifications for B&W PWRs" with retention of the existing Rancho Seco Technical Specifications format.

Our review indicates that you have failed to incorporate all the provisions of the Standard Technical Specifications applicable to Rancho Seco fire protection. You are requested to revise your submittal considering the comments provided in Enclosure 1.

The enclosed comments do not specifically identify all of the missing items from your submittal. Consequently, you are requested to review again our Standard Technical Specifications, identify any variances.from the Standard Technical Specifications you request,'and provide and explanation for the variances in your submittal.

Submission of. the revised fire protection Technical Specifications is-requested within 30 days of receipt of this letter.

Sincerely, j;

Y,m p

~x v Rooert W. Reid, Chief Operating Reactors Branch 34 Division of Licensing

Enclosure:

Comments identify missing items 28010220

Sacr $mento !!unicipall Utility Distri ct -

cc w/ enclosure (s):

Christoph'er Ellison, Esq.

David S. Kaplan,' Secretary and Dian Grueufch, Esq General Counsel California Energy dommission 6201 S. Street-1111' Howe Avenue P. ~ 0. Box 15830 Sacramento, California 95825 i

95813 L

Sacramento, California Ms'. Eleanor Schwartz

. Sacramento County California State Office Board of Supervisors.

600 Pennsylvania Avenue, S.E., Rm. 201 l

827 7th Street, Room 424 Washington, D.C.

20003 i

.' Sacramento, California 95814 Docketing and Service Section Susiness and Municipal Department

[ clear y Commission u

eacramento City-County Library Washington, D.C.

20555 828 I Street Sacramento, California 95814 Resident Inspector i

Director, Technical-Assessment P.,0. Box 48 Fair Oaks, California 95628 Divisien Office of Radiation Programs Dr. Richard F. Cole (AW-45N Atomic Safety and Licensing Board i

,J. S. Envircraental Protection Agency Panel f

Crystal Mall f2 U. S. Nuclear Pegulatory Commission Arlington, Virginia 20460 Washington, D.C.

20555 l

U S. Environmental Protection Agency Mr. Frederick J. Shon Region IX Office Atomic Safety and Licensing Board ATTN:

EIS CCORDINATOR Panel 215 Fremont Street U. S.. Nuclear Regulatory Commission San Francisco, California 94111 Washington,.0.C.

20555 l

Mr. Robert S. Borsum Elizabeth S. Bowers,- Esq.

j-

abcock & Wilcox Chairman, Atomic Sr ety and

,duelear Power Generation Division Licensing Board Panel 4uite 420, 7735 Old Georgetown Road U. S. Nuclear Regulatory Commission l

_ Lothesda, Maryland 20014 Washington, DC 20555 Thomas Caxter, Eso.

Shaw, Pittr an,~ Poi!ts & Troworidge 1800 M Street,"if.1-3ashington, D. C. -2003G-Herbert H. Brown, Esq.

Mr. Michael R. Eaton

. Lawrence Coe Lanpher, Esq.

Energy Issues Coordinator Hill, Christcpher ar.d Phillips, F.

C.-

Sierra Club Legislative Office 1900:- M St., f.'.4 1107 9th St., Room 1020 Washington, 0.:C.

20036-Sacramento, CA 95814 Helen Hubbard-P.

0.' 8cx 63 Sunol 1 California 194586

^

D**D 0 WY

w w j\\

of.k k 4

W

-' Sacramento Municipal _ Utility District cc w/ enclosure (s):

i

-A omic Safety and Licensing Board Panel U. S. Nuclear Regulatory Commission Washington, D.C.

20555 Atomic Safety and Licensing Appeal Board Panel U. S. Nuclear. Regulatory Commi'ssion

. Washington, D.C.

20555 f

California Department of Health ATTN: -Chief, Environmental Radiation Control Unit Radiological Health Section 714 P Street, Room 498 Sacramento, California O

b a.

1 4

1 i

Section 3.14.1.1 All fire detection instrumentation that ensure operablility of Safety Related equipment are.to be : listed by type (heat, flame or smoke)iems and those _ instruments which automatically actuate fire protection sys were to be-identified. No type or actuation identification was provide by SMUD, and detection instrumentation in the control and computer room, communications room, turbine generator area, auxiliary building contain-ment penetration valve areas, HPI, LPI and make-up pump areas, etc. were omitted.

Section 3.14.1.2a Locations for monitoring containment air temperatures were omitted.

Section 3.14.3.1 All Safety _ Related area sprinkler systems are to be listed. Areas such as electricas penetrations, reactor coolant system make-up pump, auxiliary building containment penetration valves,. auxiliary building north-20' level, auxiliary building corridor -47' level, etc. were omitted.

Section 3.14.5.la "All stations-in the Auxiliary Building" is not descriptive. Provide a table such as Table 3.7-10 of the Standard Tech. Specs. listing all fire hose stations required to ensure operability of Safety Related equipment.

Section 4.18.1.1 o

Change shutdown period from 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> to 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> or provide justific-ation as to why the 72 hour8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> period is adequate.

Section 4.18.3.1 Provide additional flow path valve alignment verification every 31 days.

Provide-for air flow test performance every 3 years.

Section 4.18.4

'_-Specify CO2 storage tank minimum requirements, as appropriate (such as level and/or pressure)

Provide for flow path valve alignment verification-every 31 days.

I_n addition, a listing of all yard fire hydrants and associated

. hydrant hose. houses that are required to ensure operability of Safety Related equipment must be provided utilizing Table 3.7-11 of the Standard Tech. Specs. as a format example, and associated LCOs and SSs on page 3/4-7-36 of_ the Standard Tech. Specs..should be included. For clarity, in'clusion of:" fire barriers" in the Definitions Section 1.11 is appropriate.