MONTHYEARML20211H4311999-08-27027 August 1999 Revised Bases for TS 2.2.1, Reactor Trip Sys Instrumentation Setpoints ML20211D9201999-08-20020 August 1999 Revised Pages to Third Ten Year ISI Program & Relief Requests ML20210L1631999-08-0404 August 1999 Proposed Tech Specs,Ack Establishment of Seal Injection for RCP in Isolated & Drained Loop as Prerequisite for vacuum-assisted Backfill Technique & Extending Drained Loop Verification to 4 H Prior to Commencing Backfill Operation ML20212J3041999-06-22022 June 1999 Proposed Tech Specs Re Revised Surveillance Frequency & Action Times Reactor Trip & ESFAS ML20195B5881999-05-14014 May 1999 Rev 8,Change 2 to Vepc North Anna Unit 2 IST Program Plan for Pumps & Valves Second Insp Interval,901214-001214 ML20195B5691999-05-14014 May 1999 Rev 8,Change 2 to Vepc North Anna,Unit 1 IST Program Plan for Pumps & Valves Second Insp Interval 901214-001214 ML20206N3691999-05-0606 May 1999 Proposed Tech Specs,Revising Surveillance Frequency for RTS & ESFAS Analog Instrumentation Channels & Modifying AOT & Action Times for RTS & ESFAS Analog Instrumentation Channels & Actuation Logic ML20206G8361999-05-0303 May 1999 Proposed Tech Specs,Deleting &/Or Relocating Addl primary- to-secondary Leak Rate Limits & Enhanced Leakage Monitoring Requirements Imposed Following 1987 SG Tube Rupture Event ML20206H0301999-05-0303 May 1999 Proposed Tech Specs Bases Page B 3/4 6-1,allowing Use of NRC Staff Approved/Endorsed Integrated Leak Test Methodologies to Perform Containment Leakage Rate Testing ML20206G8811999-05-0303 May 1999 Proposed Tech Specs,Increasing Allowable Leakage from ECCS Components,Establishing Consistent Licensing Basis for Accidents Requiring Dose Analysis & Clarifying Requirements of CREVS ML20205P2511999-05-0101 May 1999 Rev 0 to Vepc North Anna Power Station Unit 1 ISI Program Plan for Third Insp Interval:Components & Component Supports ML20205P2341999-05-0101 May 1999 Rev 0 to Vepc North Anna Unit 1 ISI Program for Third Insp Interval Vol 1:ISI Program for Components & Component Supports for Interval 3 990501-090430 ML20203C8251999-02-0505 February 1999 Proposed Tech Specs Re Allowed Outage Time for PORV Nitrogen Accumulators & Separate Actions for PORV Operability ML20205P2651999-02-0404 February 1999 Rev 0 to Vepc North Anna Power Station Unit 1 ISI Plan for Third Interval for Sys Pressure Tests ML20198J0971998-12-22022 December 1998 Proposed Tech Specs Bases Changes Re EDG Steady State Frequency to Be Incorporated Into TS During Implementation of Amends 216 & 197 ML20196K1971998-12-22022 December 1998 Rev 0 to NE-1176, North Anna Unit 1,Cycle 14 Startup Physics Tests Rept, Dec 1998 ML20206N8851998-12-14014 December 1998 Rev 0 to ASME Section XI Sys Pressure Test Program,Second Insp Interval ML20206N8711998-11-30030 November 1998 Rev 11,Vol I to ISI Plan for Second Insp Interval for Components & Component Supports ML20195J4431998-11-18018 November 1998 Proposed Tech Specs Re Revs to Allowable Groundwater Elevations & Removal of Piezometer Device Numbers Associated with Svc Water Reservoir ML20195C9461998-11-10010 November 1998 Proposed Tech Specs,Clarifying Operability Requirements for Pressurizer Heaters & Emergency Power Source for Pressurizer Heaters ML20154P2831998-10-16016 October 1998 Marked-up & Typed Tech Spec Pages to Revise EDG Section to Be Consistent with Station Procedures Associated with Steady State Conditions & W NSAL 93-022,for 980728 Application for Amends to Licenses NPF-4 & NPF-7 ML20153H5341998-09-24024 September 1998 Proposed Tech Specs 3/4.5.1 Re Safety Injection Accumulator Boron Concentration Verification ML20236U8411998-07-28028 July 1998 Proposed Tech Specs 4.6.2.2.1 & 4.6.2.2.2,revising Testing Acceptance Criteria to Demonstrate Operability of Casing Cooling & Outside Recirculation Spray Pumps ML20236U8711998-07-28028 July 1998 Proposed Tech Specs,Revising EDG Section to Be Consistent W/ Station Procedures Associated W/Steady State Conditions & W Nuclear Safety Advisory Ltr NSAL 93-022 ML20236U8651998-07-28028 July 1998 Proposed Tech Specs 3/4.1.2 & 3/4.5.5,re RWST & Boron Concentration Ph Range Bases Change to Address Discrepancies Between Previous NRC Issued Ser,Ts Bases & Applicable Sections of SRP ML20236H5311998-07-0101 July 1998 Draft Nuclear Control Room Operator Development Program NAPS Module NCRODP-78 Spent Fuel Dry Storage Cask System. Draft Lesson Plans & Job Performance Measures Included ML20236U8891998-06-25025 June 1998 Rev 0 to NE-1163, North Anna Unit 2 Cycle 13 Startup Physics Tests Rept ML20249C7211998-06-19019 June 1998 Proposed Improved Tech Specs for North Anna ISFSI ML20236H5541998-06-0404 June 1998 Rev 5 to Procedure VPAP-0810, Crane & Hoist Program ML20236H5391998-06-0404 June 1998 Rev 1 to Procedure VPAP-0809, NUREG-0612 Heavy Load Program ML20206N8581998-04-30030 April 1998 Rev 5,Vol 1 to ISI Program for Second Insp Interval & Components & Component Supports,For 901214-010430 ML20236H5701998-04-0202 April 1998 Rev 8 to Procedure VPAP-1901, Industrial Safety & Health ML18152A3651998-03-25025 March 1998 Proposed Tech Specs Revising Station Mgt Titles to Reflect New Positions Approved by Vepc Board of Directors on 980220 ML20217E9011998-03-25025 March 1998 Proposed Tech Specs Re Configuration Risk Mgt Program for risk-informed Allowed Outage Times & Insp Frequency of EDGs ML20236H5631998-02-10010 February 1998 Rev 11 to Procedure VPAP-0105, Fitness for Duty Program ML20202E1551998-02-0909 February 1998 Proposed Tech Specs Re EDG Allowed Outage Time ML20202C5871998-02-0303 February 1998 Proposed Tech Specs Re Reactor Coolant Pump Flywheel Insps & Loop Flow Straightener Insps ML20202C3381998-02-0303 February 1998 Proposed Tech Specs Modifying Testing Requirements for Reactor Trip Bypass Breaker ML20210Q2051997-12-31031 December 1997 1997 Severe Accident Management Tabletop (Scenario 1) Drill Manual ML20203G5191997-12-29029 December 1997 Ultrasonic Exam Technique for Detection of Microbilogically Induced Corrosion in North Anna Stainless Steel Service Water Piping ML20199G4161997-11-18018 November 1997 Revised Proposed TS Pages,Establishing 14 Day AOT Applicable Whenever EDG Is Inoperable ML20199H4001997-11-18018 November 1997 Proposed Tech Specs Permitting Quarterly Testing of Turbine Governor & Throttle Valves ML20199A1481997-11-0505 November 1997 Proposed Tech Specs Pages,Providing Administrative Controls in TS 3/4.9.7,to Permit Spent Fuel Pit Gate Movement Over Irradiated Fuel ML20198G5401997-08-31031 August 1997 Rev 0 to NE-1133, North Anna Unit 1,Cycle 13 Startup Physics Tests Rept, Aug 1997 ML20199G5681997-06-30030 June 1997 Rev 5 to VPAP-2001, Station Planning & Scheduling. Even Numbered Pages of Incoming Submittal Not Included ML20210Q1991997-06-10010 June 1997 Rev 0 to VPAP-2604, Severe Accident Mgt Guideline (SAMG) Program Administration ML20141F3741997-05-14014 May 1997 Proposed Tech Specs Revising Wording in Surveillance Requirement 4.7.1.7.2.a to Clarify Testing & Insp Methodology of Turbine Governor Control Valves.Clarification Also Provided for TS 3/4.7.1.7 ML20137C8581997-03-18018 March 1997 Proposed Tech Specs Re Containment Gaseous & Particulate Radiation Monitors ML20134J4141997-02-0404 February 1997 Revised Pp of Proposed TS Changes Re Intermediate Range Trip Setpoints & Allowable Values for Units 1 & 2 ML20134F1231997-02-0303 February 1997 Proposed Tech Specs Re Use of Lead Test Assemblies in Plant,Units 1 & 2 1999-08-04
[Table view] Category:TEST/INSPECTION/OPERATING PROCEDURES
MONTHYEARML20211D9201999-08-20020 August 1999 Revised Pages to Third Ten Year ISI Program & Relief Requests ML20195B5881999-05-14014 May 1999 Rev 8,Change 2 to Vepc North Anna Unit 2 IST Program Plan for Pumps & Valves Second Insp Interval,901214-001214 ML20195B5691999-05-14014 May 1999 Rev 8,Change 2 to Vepc North Anna,Unit 1 IST Program Plan for Pumps & Valves Second Insp Interval 901214-001214 ML20205P2341999-05-0101 May 1999 Rev 0 to Vepc North Anna Unit 1 ISI Program for Third Insp Interval Vol 1:ISI Program for Components & Component Supports for Interval 3 990501-090430 ML20205P2511999-05-0101 May 1999 Rev 0 to Vepc North Anna Power Station Unit 1 ISI Program Plan for Third Insp Interval:Components & Component Supports ML20205P2651999-02-0404 February 1999 Rev 0 to Vepc North Anna Power Station Unit 1 ISI Plan for Third Interval for Sys Pressure Tests ML20206N8851998-12-14014 December 1998 Rev 0 to ASME Section XI Sys Pressure Test Program,Second Insp Interval ML20206N8711998-11-30030 November 1998 Rev 11,Vol I to ISI Plan for Second Insp Interval for Components & Component Supports ML20236H5311998-07-0101 July 1998 Draft Nuclear Control Room Operator Development Program NAPS Module NCRODP-78 Spent Fuel Dry Storage Cask System. Draft Lesson Plans & Job Performance Measures Included ML20236H5541998-06-0404 June 1998 Rev 5 to Procedure VPAP-0810, Crane & Hoist Program ML20236H5391998-06-0404 June 1998 Rev 1 to Procedure VPAP-0809, NUREG-0612 Heavy Load Program ML20206N8581998-04-30030 April 1998 Rev 5,Vol 1 to ISI Program for Second Insp Interval & Components & Component Supports,For 901214-010430 ML20236H5701998-04-0202 April 1998 Rev 8 to Procedure VPAP-1901, Industrial Safety & Health ML20236H5631998-02-10010 February 1998 Rev 11 to Procedure VPAP-0105, Fitness for Duty Program ML20210Q2051997-12-31031 December 1997 1997 Severe Accident Management Tabletop (Scenario 1) Drill Manual ML20199G5681997-06-30030 June 1997 Rev 5 to VPAP-2001, Station Planning & Scheduling. Even Numbered Pages of Incoming Submittal Not Included ML20210Q1991997-06-10010 June 1997 Rev 0 to VPAP-2604, Severe Accident Mgt Guideline (SAMG) Program Administration ML20199G4461996-08-29029 August 1996 Rev 28 to 1-MOP-6.90, Emergency Diesel Generator 1-EE-EG-1H. Page 35 of 72 in Attachment 4 of Incoming Submittal Was Not Included ML20236H5561996-08-0202 August 1996 Rev 3 to Procedure TRCP-0009, Instructional Staff Training & Qualifications ML20134J9601996-05-31031 May 1996 /Unit 2 Fuel Assembly Insp Program ML20138B5421996-05-16016 May 1996 Rev 7 to VPAP-2103, Odcm ML20217K4481995-10-31031 October 1995 Seismic Design & Evaluation Guidelines for DOE HLW Storage Tanks & Appurtenances ML20084U1811995-04-30030 April 1995 Rev 5 to Second 10-yr Interval ISI Program Plan ML20069A7971994-03-29029 March 1994 Second Interval ISI Plan, Rev 5 ISI Program,Rev 3 ML20065H9221993-11-30030 November 1993 ISI Program General Second Insp Interval ML20058N4911993-11-0505 November 1993 Rev 7 to North Anna Units 1 & 2 IST Program Plan Second Insp Interval 901214-001214 ML20092M9061991-09-0101 September 1991 Rev 2 to VPAP-2103, Odcm ML20081F3501991-05-28028 May 1991 Rev 1 to North Anna Unit 1 Inservice Insp Plan for Components & Component Supports,Second Insp Interval ML20082K8211991-05-0303 May 1991 Rev 1 to Station Administrative Procedure VPAP-2104, Radwaste Process Control Program ML18151A6551990-11-14014 November 1990 Revised Corporate Emergency Plan Implementing Procedures, Including Rev 0 to CPIP-1.0,CPIP-2.0,CPIP-2.1,CPIP-2.2, CPIP-2.3,CPIP-2.4,CPIP-2.5,CPIP-2.6,CPIP-3.0,CPIP-3.1 & CPIP-3.2 ML20058C1151990-10-17017 October 1990 Inservice Testing Program Plan for North Anna Unit 1 ML20065P2741990-09-30030 September 1990 Rev 1 to Vol 1 of VEPCO North Anna Power Station Unit 2 Inservice Insp Plan for Second Insp Interval:For Components & Component Supports 901214-001214 ML20065P2711990-09-30030 September 1990 Vol 1,Rev 0 to VEPCO North Anna Power Station Unit 1 Inservice Insp Plan for Second Insp Interval:For Components & Component Supports Dec 1988 - Dec 1998 ML20058G0551990-08-31031 August 1990 Inservice Insp Program for Second Insp Interval,Vol 1,Inservice Insp Program for Components & Component Supports ML20055D4931990-06-14014 June 1990 Rev 6 to VEPCO North Anna Power Station Unit 1 Inservice Testing Program Plan for Pumps & Valves Second Insp Interval 901214-001214 ML20055D4941990-06-14014 June 1990 Rev 6 to VEPCO North Anna Power Station Unit 2 Inservice Testing Program Plan for Pumps & Valves Second Insp Interval 901214-001214 ML20043B1091990-04-27027 April 1990 Rev 0 to Station Administrative Procedure VPAP-2103, Odcm. ML20043B1111990-04-27027 April 1990 Rev 0 to Station Administrative Procedure VPAP-2104, Radwaste Process Control Program. ML20248E9201989-10-0303 October 1989 Inservice Testing Program Plan for Pumps & Valves First Insp Interval 780606 - 901214, Rev 5 ML20248E9231989-10-0303 October 1989 Inservice Testing Program Plan for Pumps & Valves First Insp Interval 801214 - 901214, Rev 5 ML20197F1261988-03-31031 March 1988 Rev 0 to Inservice Insp Program Plan for Second Insp Interval,Vol 1,Inservice Insp Program Plan for Components & Component Supports,880606-980606. W/92 Oversize Drawings ML20235U3391987-06-12012 June 1987 Revised Emergency Plan Implementing Procedures,Including Rev 1.00 to 1-ES-3.1, Post-STGR Cooldown Using Backfill (W/No Attachments) & Rev 1.00 to 1-EP-0, Reactor Trip or Safety Injection (W/No Attachments). Related Info Encl ML20215K2681985-12-19019 December 1985 Offsite Dose Calculation Manual,North Anna Power Station Units 1 & 2 ML20215K2731985-11-27027 November 1985 Process Control Program,North Anna Power Station Units 1 & 2 ML20108A1041985-03-0404 March 1985 Proposed Methodology for Implementing Mechanical Cleaning of Svc Water Piping & Repair of Svc Water Isolation Valves ML20108B5801985-02-28028 February 1985 VEPCO Proposed Program,Mechanical Cleaning & Valve Repair Svc Water Sys,North Anna Power Station,Feb 1985. W/One Oversize Drawing.Aperture Card Available in PDR ML20112G3771984-11-15015 November 1984 Emergency Exercise 841115,Exercise Manual ML18141A5301984-03-0101 March 1984 Control Room Design Review Program Plan for North Anna & Surry Power Stations, in Response to Suppl 1 to NUREG-0737 ML20079L5361983-12-21021 December 1983 Public Version of Rev 5 to Emergency Plan Implementing Procedure EPIP-3.04, Activation of Emergency Operation Facility ML18142A1371983-09-15015 September 1983 Procedure 1-OP-4.19, Receipt & Storage of Spent Fuel TN-8L Shipping Cask,Unloading & Handling Procedures. 1999-08-20
[Table view] |
Text
_
. % s 4
~~~
2-EP-1
~3 Page 1 of 5 (d 12-t5-19 VIRGINIA ELECTRIC AND POWER COMPAW NORTH ANNA POWER STATION UNIT NO. 2 REACTOR TRIP
REFERENCES:
- 1. Westinghouse Logics 5655D33 series.
- 2. 12050-LSK-1.4
- 3. FSAR, Section 15 REV. NO. 1 PAGE: E*1 TIRE DATE: 12-15-79 APPROVAL: Y\
RIV. NO. 2 PAGE: 3 DATE: 03-13-80 APPRCVAL: MU j' N REV. NO. 3 PAGE:3-5,ATT.1, DATE: 05-22-80 APPROVAL: M ATT. 2 U
... e
- T T T P C C P F. O ,r ,,a e
- -. -)
r .. .
, s
_.. . . - : ., , u *..'" F P. .. . . .~ '
? :e . : .-
,,--.=,...e
- s. .-
...n
-l
.m: ;
f I '- '
, [
~
'I N0;? 04- g33,.
' '] ...-
.,,7.._
- - ' _ , _ _ ... 8 ATEST REV!SJCN RECOMMEND APPROVAL: /.. w%'d LI_,
APPROVED BY: \.D ".is CHAIRMAN ST.3 TION NUCLEAR SAFETY AND OPERATING COMMITTEE SAFETY RELATED 80 0605 0 33d
2-EP-1 Page 2 of 5 12-15-79 1.0 Indications 1.1 The annunciation of any alarm light on the reactor trip first-out portion of panels D or E.
1.2 The individual rod position indication system show all full length rods on the bottom.
1.3 Reactor trip breakers (Train A & B) indi' ate open.
2.0 Automatic Actions 2.1 Train "A" and "B" reactor trip breakers are opened simul-taneously.
2.2 Turbine trip by reactor trip (P-4).
2.3 The steam generator feedwater regulating valves will control level, until T,yg decreases below 554 and then will trip closed (P-4).
l t
4 J
2-EP-1 Page 3 of 5 05-22-80 3.0 Immediate Operator Actions 3.1 Manually trip the reactor, verify all full length rods are fully inserted and that power level has decreased to 2 zero.
NOTE: If any required automatic action has not occurred, it shall be manually initiated.
NOTE: If the reactor has not tripped following the opening of the Reactor Trip Breakers, manually initiate safety injection.
3.2 Manually trip the turbine.
3.3 Verify proper operation of the Steam Dump Control Valyes or the Steam Generator Power Operated Relief Valves and that' rave is decreasing and/or stabilizing at 547 F.
NOTE: If it is determined that an uncontrolled RCS cooldown is in progress, simultaneously close all three MSTV's.
3.4 Verify Main or Auxiliary Feedwater Flow and that Steam Generator levels are recovering. (33% narrow range level) 3.5 Verify that pressurizer level is recovering. (21%)
3.6 Verify that Pressurizer pressure is recovering. (2235 PSIG) 3.7 Announce on Gaitronics Reactor Trip Unit #2.
3.8 If any of the above parameters are deteriorating (step 3.3 thru l 3.6) and/or a Safety Injection is imminent, proceed to the appropriate EP and request that SR0/STA evaluate the accident i
l utilizing the attached diagnostic checklist. If all parameter:
are returning to normal, proceed to Section 4.0, Long Term d
Operator Action.
CAUTION: Do not make operational decisions based solely on a l single plant parameter when one or more confirming l indications are available.
i 1) EP-2 Loss of Reactor Coolant (high Cont. radiation level)
- 2) EP-3 Loss of Secondary Coolant (rapid increase or decrease in Tave)
- 3) EP-4 Steam Generator Tube Rupture (high air ejector rad. level)
- 4) EP-5 Safety Injection I
2-EP-1 Page 4 of 5 05-22-80 Initials 4.0 Long Term Operator Actions 4.1 Verify all full length rods are fully inserted.
NOTE: Emergency borate 7 minutes for each full length rod not fully inserted.
4.2 Verify all turbine throttle, governor, reheat stops and inter-cepts valves closed.
4.3 Close the " Reheater" inlet valves by pushing the " Reset" push-button on the reheater control panel.
4.4 Verify all turbine drains open.
4.5 Verify the auto transfer of power from station service to reserve station service transformers and transformers are not overloaded. (Tiem delay of 30 seconds except upon thrust bearing or generator trips.)
4.6 Verify generator breakers G2T-575 and G-202 open.
4.7 Isolate auxiliary steam loads and shift auxiliary steam supply from the affected unit as necessary.
4.7 Close and lock 2-CH-140.
4.8 Stop or verify stopped one main feed pump, the LP heater drain pumps and the HP Heater drain pumps.
4.9 Control Steam generator level at "N0 LOAD" level (33%) on feedwater bypass FCV's or on auxiliary feedwater system. If a main feed pump is running, place *he aux feed pumps in "AUT0".
4.10 Verify steam dump steam pressure control setpoint at 1005 psig (the pot setting should be 71.78%) and shift steam dumps to pressure mode.
4.11 Verify the Vital busses, Semi Vital Busses, and DC busses are energized as per Attachment 2.
2-EP-1 Page 5 of 5 05-22-80 4.0 Long Term Operator Actions (cont.)
4.13 Determine the cause of the trip, from first-out indication, compiter post-trip review, and/or sequence of evnets recorder, and refer to the appropriate emergency or abnormal procedures.
4.14 Verify source range unblock when below P-6 reset at 5 x 10 -11 amps.
NOTE: Manual reset of source ranges may be required on a malfunction of an Intermediate Range Channel.
4.15 Initiate reactor shutdown and trip report form.
4.16 Return the emergency borate system to normal as per 2-0P-8.7, if necessary.
4.17 If the unit is to be shutdown for an extended period of time, re-establish a ring bus lineup in the switchyard in accordance with system operators instructions.
4.18 Inform chemistry to perform 2-PT-53.5 (reactor coolant system specific activity and isotopic analysis for iodine) following a trip from above 15% rated thermal react- power.
4.1? Establish proper load shedding as per 1-0P-26.7.
I 4.20 Proceed to 2-0P-1.5 or 2-OP-3.2 and re-establish initial condi-tions as appropriate. If a fast recovery is desired proceed to
( 2-OP-1.6.
Completed By:
Date:
l i
I
2-EP-1 Attachment 1 Page 1 of 1 05-22-80 p DOMINANT PAR E TIR h -
H e f- ASSOCIATED PARAMETER ff ~e{gg Z# n
~~
,fj /4- 7 j High Cont. Radiation Levels Low Steamline Pressure (one Generator)
High Air Ejector Radiation Level High Cont. Press.
High Cont. Recire. Sump Level High Cont. Temp.
High Steam F' low Steam Flow / Feed Flow Mismatch High Steam Generator Blowdown Radiation Level Incident Diagnosed as:
By:
SR0/STA
/
2-EP-1 Attachment 2 Page 1 of 2 05-22-80 ELECTRICAL BUS VERIFICATION Initial 120 VOLT VITAL BUSSES Verify vital Bus 2-I energized Indication: Voltmeter for Bus 2-1 on backboard.
Verify vital Bus 2-II energized Indication: Voltmeter for Bus 2-2 on9backbsard.
Verify vital Bus 2-III energized Indication: Voltmeter for Bus 2-3 on backboard.
Verify vital Bus 2-IV energized Indication: Voltmeter for Bus 2-4 on backboard.
125 VOLT DC BUSSES NOTE: Associated DC bus voltage indication will be lost if its associated 120V vital bus is lost. The Control board voltage indication for the DC buses comes from a transducer powered from the associated 120V vital bus.
Verify 125 VDC distribution cabinet 2-I energized Indication: Primary, voltmeter for Batt. 2-1 on backboard back-up, light indication on BKR 25C1 (control PWR l
available).
, Verify 125 VDC distribution cabinet 2-II energized Indication- Primary, voltmeter for Batt. 2-II on backboard back-up, :.2ght indication on BDR 25B1 (Control PWR availabl .) or power available for emergency turnine oil pump.
Verify 125VDC distribution cabinet 2-III energized Indication: Primary, voltmeter for Batt. 2-III on backboard back-up, ligh indication on BKR 25A2 (control PWR available),
j Verify 125VDC distribution cabinet 2-IV energized l
l Indication: primary voltmeter for Batt. 2-IV on backboard l back-up power available for air sife seal oil back-up l pump.
/
1 2-EP-1 Attachment 2 Page 2 of 2 05-22-80 Initial SEMI-VITAL BUSSES Verify semi-vital bus 1A energized Indication: Subcooling monitoring syste.a (Panel A) energized.
Verify semi-vital bus 1B energized Indication: Subcooling monitoring system (Panel B) energized.
If the power is lost to any of the above buses refer to 2-AP-10.1.
3 1
/