ENCLOSURE TENNESSEE VALLEY AUTHORITY BROWNS FERRY NUCLEAR PLANT (BFN)

UNITS 1 g 2g AND 3

RESPONSE

TO REQUEST FOR ADDITIONAL INFORMATION REGARDING BROWNS FERRY NUCLEAR PLANT INDIVIDUAL PLANT EXAMINATION FOR EXTERNAL EVENTS (Report Attached)

Browns Ferry Nuclear Plant - IPEEE TABLEOF CONTENTS SEISMIC UESTIONS

1. - Safe Shutdown E<<luipmcnt List.
2. - Nonseismic Failures And Human Actions.
3. - External Flooding
4. - Quantitative RLE Information.
5. - HCLPF Evaluations
6. - Masonry Walls.
7. - Screening OfThe Reinforced Concrete Chimney.

[Later]

[Later]

[Later]

3 4

4

. [Later]

1. - Consideration OfHot Shorts And Spurious Actuations..
2. - Control Room Evacuation Scenario.
3. - Heat Loss Factor (HLF)..
4. - Electrical Cabinet Heat Release Rate.........
5. - Description ofInitiating Events
6. - Remote Shutdown Capability
7. - Consideration ofTransient Combustibles
8. - NFPA Compliance ofAutomatic Fire Suppression Systems.
9. - Fire Severity Factors.
10. - Fire Propagation Scenariosin ControlBuildingEL593 (Fire Compartment 16-1)
11. - Basis for Single Stuck Open SRV in Control Room Fire Scenario
12. - Fire Propagation From Cable Spreading Rooms to Control Rooms.
13. - Consideration for Fires AffectingBoth Units
14. - Miscellaneous Issues Related to Fire Areas 12 Ec 13.

FIRE UESTION UNI UE TO UNIT3 5

. 6 13 18

[Later]

19 24 26 27 28

[Later]

29

[Later]

32

1. - Fire Propagation in Horizontal Cable Tray HIGH WINDS FLOODS AND OTHER EXTERNALEVENTS UESTIONS ON UNITS 1 2 AND 3
1. - Probable Mmimum Precipitation Criteria.
2. - Severe Accidents.

33

[Later]

[Later]

ATTACHMENT1 - Compartment Temperatures Using MQHMethodology (Question 3)

ATTACHMENT2 - Changesin Damage Threshold Elevations and CriticalRadial Distances Based on 0.7 HLF and 190 Btulsec Heat Release Rate forElectrical Cabinet(Question 3 d'c 4)

ATTACHMENT3-Tiine to Detection, Manual Suppression d<<: Time to damage, Compt 16-1 (Question 10)

ATTACHMENT4-Cable Tray Fire Propagation (Question Specific to Unit 3)

ATTACHMENT5-Cable Spreading Room Fire Propagation Analysis (Question 12)

ATTACHMENT6-Calculation CD-Q0000-940339 RI, Calculation ofBasic Paraineters forA-46 and Individual Plant Examination ofExternal Events (IPEEE) Seismic Program ATTACHMENT7 - HCLPF Bounding Calculations References ATTACHMENT8-Calculation 50147-C-011 RI, HCLPF Calculations for Electrical Equipment on the A-46Safe Shutdown Equipinent List ATTACHMENT9-Calculation 50147-C-012 Rl, HCLPF Calculations forSelected Blochaualls NOTE:

Thc calculations contained in this rcport are current as ofthc submittal date. Future revisions as may bc re<<iuired willbc available for rcvicw on-site.

Page 1 of 34

Browns Ferry Nuclear Plant - IPEEE SEISMIC UESTIONS SEISMIC UESTION 1 - SAFE SHUTDOWN EQUIPMENT LIST System analysis forthe development offhe safe shutdown equipment list (SSEL) is discussed in Section 3 ofthe Seismic IPEEE (Internal Plant Examinafion forExternal EvenfJ Report and Secfion 4 of fhe USI A-46 Seismic Evaluation Report of the submittal. Itis noted that only low pressureinjection systems are selectedin fhe Browns Feny Nuclear plant IPEEE; high pressure injection systems (i.e., reactor coreisolafion cooling (RCIC) and high-pressure coolantinjecfion (HPCI) are notincludedin fhe SSEL.

For success path and system selection, Electric Power Research Institute (ERPI) NP-604$ -SL stafes this:

"In general, fhe selected path forperforming the safety functions to shuf down fhe reactor willbe the one consisting ofthe front line systems (and their necessary support systems) that were provided as a first line ofdefense,'nd designed to respond automatically (at leastin the short time during and after the SME (seismic margin earthquake J to fhe types of transients andlor accidents that might beinduced by a margin earthquake."

Based on this criterion, fhe high pressureinjecfion sysfemsi.e.,

(HPCI and RCIC) seem to provide a hefter choice forcoolant injecfion. However, high pressure injection systems are not includedin the Browns Ferry SSEL, and low pressure systems (i.e., core spray and low pressure coolant injecfion) are used forfhe success paths forinvenfory control. Manual reactor coolant system depressurizafion is therefore required forbofh paths, and consequently, the demands on fhe depressurization system and operator actions are more significant.

a.

Please provide the basis for not including any high pressure injection system in the SSEL (other than the reason given in the submittal that they are only moderately reliable based on industry experience).

Please address the EPRI NP-6041-SL criterion on system selection, quoted above, in your discussion.

b.

Based on plant procedures, please provided a detailed description of expected operator actions following a seismic margin earthquake (SME). Please describe in more detail the operator actions and their failure probabilities under SME conditions for reactor coolant system depressurization and decay heat removal.

c.

Please describe the major equipment included in the Browns Ferry high pressure systems, and describe any known or suspected weal links in the systems under SME conditions.

Res onse to uestion 1

[Later]

Page2of 34

Browns Feny Nuclear Plant - IPEEE SEISMIC UESTION 2-NONSEISMIC FAILURES AND HUMANACTIONS Nonseismic failures and human actions are not specifically addressedin fhe submittal.

The only statemenf made in the submittal relafed to these issuesis this: "The SPLDs (success path logic diagrams J were reviewed and agreed upon by Browns Ferry Operafions personnel." Both nonsesimic failures and human actions are especiallyimportant at Browns I=eny because of the reliance ofthe success path on a single-train system(or a single loop ofa system) and the lack ofautomatic systemsin the success path forcoolantinjection and decay heaf removal.

Regarding nonseismic failures and human actions, NUREG-1407 states that "Success paths are chosen based on a screening crifenon applied to nonseismic failures and needed human actions. Ifisimporfant that the failure modes and human acfions are clearlyidentified and have low enough probabilities fo not affect the seismic margins evaluation."

Please describe how nonseismic failures and human actions were treatedin the analysis and address fhe concerns ofthe above quoted statement from NUREG-1407.

Res onse to Uestion 2

[Later]

SEISMIC UESTION 3 - EXTERNALFLOODING Seismicinduced fireifloods are brieflydiscussedin Section S ofthe Seismic IPEEE Report. For seismic-induced floods, itis simply stated fhat the probability ofplant and equipment flooding associafed with rupture of flire profecfion systems has been previously addressed by Tennessee ValleyAuthorit. No references are providedin the submittal on the source ofthisinformafion.

Furfhermoie, only flooding associated with fhe fire profection systemis mentioned in fhe submittal.

This does not seem to be consistenf with NUREG-1407 which states that fhe effects ofseismicallyinduced external flooding due to a failure ofupstream dams and flooding due fo failure oftanks have nof been addressed.

Please provide a discussion on this issue consistent with the sfatemenf in NUREG-1407.

Res onse to Uestion 3

[Later]

SEISMIC QUESTION 4-QUANTITATIVERLE INFORMATION No quantitafiveinformafionis providedin the submittal pertaining to the development offhe review-level-earthquake (RLE)in-structure response spectra and comparison to the design basis earthquake (DBE) in-structure response spectra.

It appears that fhis defailedinformafion is confainedin Reference 9 to the submittal. Please submit Reference 9, so that our review of fhe seismicinput can be completed.

Page 3 of 34

q b'<,'

Browns Ferry Nuclear Plant - IPEEE Res onse to uestion 4 A copy of calculation CD-Q0000-940339 R1, "Calculation of Basic Parameters forA46 and Individual Plant Examination of External Events (IPEEE) Seismic Program," is provided in.

SEISMIC QUESTION 5 - HCLPF EVALUATIONS Section 6 ofthe submittal discusses 22 bounding calculations forhigh-confidence-of-low-probability-of-failure (HCPLF) evaluations.

Please provide references forthese calculations, and also submit the calculation forthe transformers which have an estimated HCLPF capacity of 0.26g.

Res onse to uestion 5 The bounding calculations for high-confidence-of-low-probability-of-failure (HCLPF) evaluations are contained in calculations 50147-C-003 RO, -004 RO, -005 RO, and -011 R1. The requested calculation references are provided in Attachment 7. The calculations for the transformers which have an estimated HCPLF capacity of 0.26g are documented on calculation 50147-C-011 R1. This calculation is enclosed as Attachment 8. The HCPLF calculation appears on pages 18 and 19 of the calculation.

SEISMIC UESTION 6 - MASONRYWALLS Section 5.9.1 ofthe submittal discusses masonry walls.

Three reinforced walls are identified as having an estimated HCPLF capacity of 0.27g.

Please submit the calculation forthese walls and also provide additional description ofthe assessment oftheir failure mode and potential interaction with SSEL equipment.

Res onse to uestion 6 The calculation for these walls is contained in calculation 50147-C-012 R1, which is enclosed as Attachment 9. The requested information is found on pages 18-20.

The evaluation of the failure mode of the subject block walls and their potential interaction with SSEL equipment appears on pages 18, 19, 20, and 23 of calculation 50147-C-012 R1. The following SSEL equipment is in the vicinityof the subject block walls.

Panel 2-9-9 SSEL No. 9045 Panel 3-9-54 SSEL No. 39133 Panel 3-9-55 SSEL No. 39134 The calculation discloses that this equipment is approximately 5-7 feet from the block walls. The mode of failure of the propped cantilever walls is the result of the formation of plastic hinges in their span which would cause only some spalling of the surface of the walls. Therefore, there is no interaction between the block walls and SSEL equipment.

Page 4 of 34

Brosvns Ferry Nuclear Plant - IPEEE SEISMIC UESTION 7 - SCREENING OF THE REINFORCED CONCRETE CHIMNEY Section 5.5.4 ofthe submittal discusses the reinforced concrete chimney which stands 600 feet high. Please clarify the basis forscreening the chimney forthe 0.3g RLE. Ifthisis based on a calculation ofHCPLF capacity, please submit the calculation.

Res onse to uestion 7

[Later]

FIRE tlUESTIONF FIRE QUESTION 1 - CONSIDERATION OF HOT SHORTS AND SPURIOUS ACTUATIONS IN THE IPEEE ANALYSIS From the submittalsit cannot be determined that the licensee has considered hot shorts and spurious actuations as a failure mode forcontrol orinstrumentation cables.

In particular, considerations shouldinclude fhe treatment ofconductor-to conductor shorts within a given

, cable.

Hot shortsin control cables can simulate the closing ofcontrol switches leading, for example, to the repositioning of valves, spurious operation ofmotors and pumps, or the shutdown ofoperating equipment. These types offaults might, forexample, lead to a loss-of coolant accident (LOCA), diversion offlowwithin various plant systems, deadheading and failure ofimportant pumps, premature or undesirable switching ofpump suction sources, undesirable equipment operations, and unrecoverable damage to motor operated valves. For main control room (MCR) abandonment scenarios, such spurious operations and actions may not be indicated at the remote shutdown panel(s), may not be directly recoverable from remote shutdown locations, or may lead to the loss ofremote shutdown capabi%ty (e.g. through loss of shutdown panel power sources).

In instrumentation circuits, hot shorts may cause misleading plant readings potentially leading toinappropriat control actions or generation ofactuation signals foremergency safeguard features.

Please discuss to what extent these issues have been consideredin the IPEEE. Ofparticular interest are potential vulnerabilities of the automatic depressunzation, HPCI, and RCIC systems to spurious actuation signals. Ifthey have not been considered, please provide an assessment ofhow inclusion ofpotential hot shorts and spurious actuafions wouldimpact the quantificatl'on offire con. damage scenariosin the IPEEE.

Res onse to Question 1

Hot shorts and spurious actuations have not specifically been considered in the analyses.

Fires were assumed to occur at specific locations or compartments resulting in either an engulfing fire (initial screening) causing damage to all power and control cables and components in the area or the fire damage is confined within a zone of influence (detailed screening) based on the fire size. A damage to cables translates to incapacitation of the associated equipment (i.e. core injection pumps, HVAC systems to vital areas, etc.). The plant PSA model is modified accordingly and the core melt frequency is calculated based on specific initiating events likely to Page 5 of 34

BroNns Feny Nuclear Plant - IPEEE have occurred due to the fire. The methodology is focused on the effects of fires on control and power cables and determines the impact of their failure to operate (i.e. functional failure) but not their spurious operation. Also recovery from fire related damage was specifically not considered.

For example, those scenarios that could impact the operability of a 480VAC board for which the plant risk model allows recovery (i.e. top event R480), this top event was set to disallow recovery of the affected board.

In summary the BFN IPEEE-Fire methodology is typical of how fire risk analysis is performed in nuclear plants.

While the potential exists for other than functional failures, in most cases these form of failures would not be detrimental to safe plant shutdown.

Following are some examples:

~

ADS Accumulators (MSRV air supply) - The accumulators are mechanical devices located inside the inert drywell. They would not experience spurious actuations during a fire.

~

ADS/MSRV - Spurious operation of one MSRV can be mitigated by a minimum set of safe shutdown equipment, e.g. one RHR pump, one RHRSW pump, two EECW pumps, etc.

The minimum set is likelyto be available from the diverse set of equipment in the plant..

~

MSIV-The valves are of fail safe design and willthus close when the circuits are subjected to the affects of fire.

~

HPCI - Spurious operation of HPCI is mitigated by operator action in the control room if high water trip does not occur automatically.

~

RCIC/CRD - spurious operation of these system is not a concern because of their relatively low flow. Plant procedures allow adequate time to prevent water intrusion into the main steam lines.

It should be noted that only a fraction of fires that occur will be in the appropriate location and only fraction of these fires will have the appropriate severity to cause damage.

The BFN methodology assumes a fullydeveloped fire with peak heat release rates at the inception of fire for most locations and does not apply the probability factors.

However, when circuit faults are considered (i.e. conductor to conductor shorts within the same cable, cable to cable shorts, etc.), the probabilities of these occurrences have to be considered.

Currently, circuit faults cannot be adequately modeled due to lack of accrued experience and availability of quantitative PRA methods. It is recognized that these circuit faults can occur in a fire situation and cause spurious actuations, their probability of occurring is assumed to be very low.

The ability to recover from fire-related impacts in the Main Control Room was within the design intent of the remote shutdown capability effort. While "hot short" or instrumentation impacts could occur prior to the enablement of the remote shutdown capability, they are considered to the extent as described in response to Question 6.

FIRE UESTION 2 - CONTROL ROOM EVACUATIONSCENARIO Firesin the MCR are potentiallyrisk-significant because they can cause instrumentation and control failures (e.g., loss ofsignals or spurious signals) formultiple redundant divisions, and because they can force control room abandonment. Although data from two experiments concerning the timing ofsmokeinduced, forced control room abandonment are available (2. 1J, the data must be carefullyinterpreted, and the analysis must properiy consider the differences in configuration between the experiments and the actual control room being evaluated fortire risk. In particular, the expenmental configuration included placement ofsmoke detectorsinside the cabinetin which the fire originated. as well as an open cabinet door forthat cabinet. In one Page 6 of 34

Bro>vns Ferry Nuclear Plant - IPEEE case, failure to account forthese configuration differences led to more than an order of magnitude underestimatein the conditional probability offorced control room fire abandonment (2.2). In addition, another study raises questions about control room habitability due to room air temperatun concerns (2.3J. The submittals appear to assume a control room abandonment probability based on the manual non-suppression probabi%'ty of3.4 x 10

. This valueis traceable to NSAC/181, the work reviewedin Reference 2.2.

Please provide the detailed assumptions (including the assumed fin. frequency, any frequency reduction factor, and the probability ofabandonment) usedin analyzing the MCR and justifications for these assumptions.

In particular, ifthe probability ofabandonmentis based on a probability distribution forthe time required to suppress the fire, please justifythe parametric form ofthe distribution and specify the data used to quantify the distribution parameters.

Ref 2.1 J. Chavez, et al., "An Experimental Investigation ofInternally Ignited Fires in Nuclear Power Plant Cabinets, Part II-Room Effects Tests,"

NUREG/CR-452TN2, October 1988.

Ref. 2.2 J. Lambright, et al., "A Review ofFire PRA (Probabilistic Risk AssessmentJ Requantification Studies Reportedin NSAC/181," prepared forthe United States Nuclear Regulatory Commission, April 1994.

Ref. 2.3 J. Usher and J. Boccio, 'Fire Environment Determination in the LaSalle Nuclear Power Plant Control Room," NUREG/CR-5037, prepared forthe United States Nuclear Regulatory Commission, October 1987.

Res onse to uestion 2 Based on additional industry guidance available since the original submittal, the Control Rooms (Fire Compartment 16-3) fire PRA is being re-quantified.

Following is the re-quantification discussion.

Specific response to the question follows the re-quantification analysis.

Re-uantification The following two cases of control room abandonment are evaluated in the current Fire IPEEE submittal:

Case 1 - Unit 2 Control Room abandonment following an unsuppressed fire in the Unit 1 control area.

Case 3 - Unit 2 Control Room abandonment following an unsuppressed fire in the Unit 2 control area.

For Case 1, all Unit 2 equipment remains available, except that disabled by the Control Room Abandonment procedure (2-AOI-100-2 for Unit 2).

Page 7 of 34

Browns Ferxy Nuclear Plant - IPEEE Case 3 shown in the submittal could be evaluated as failing ifthe shift to remote shutdown is unsuccessful, as described in Table M-3 of the EPRI Fire PRA Implementation Guide.

Using a human error rate of 0.064 (NSAC/181, NUREG-1521) for successfully performing the Control Room Abandonment procedure, the frequency for this type of scenario would become:

CDF = Ignition x probability of x

failure of remote Frequency non-suppression shutdown capability

= 0.0118 x 0.0034 x

0.064

= 2.57E-6 Which is above the FIVE screening cutoff of 1E-6. Note that this assumes that any fire in the Unit 2 control area that is not suppressed willresult in Control Room abandonment, even for fires in non-critical panels.

A more detailed evaluation considering critical and non-critical panels is shown below.

Evaluation of Current Scenarios Using EPRI Fire PRA Implementation Guide In Appendix M of the EPRI Fire PRA Implementation Guide (EPRI TR-105928, Final Report),

each of the Control Room scenario core damage frequency equations given in Table M-3 is bounded by the ignition frequency, multiplied by the likelihood of suppression prior to control room abandonment, multiplied by the likelihood of failing to enable the remote shutdown capability. Several of the equations then include a failure term for the hardware operated from the remote shutdown panel.

For Browns Ferry, this term is dominated by RCIC failure, which has a nominal value of 0.0662 (split fraction RCI1 in the BFNU2M plant model).

In essence this acts to double the scenario core damage frequency when one uses an operator failure rate of 0.064 for performing the action to enable the remote shutdown capability.

These values are then multiplied by the panel ignition frequency (0.0118 per control room for the BFN IPEEE submittal, 0.00233 in NUREG-1521, multiplied by 0.02 to account for the panel population) and the suppression factor (0.0034). This generates a scenario frequency of:

0.0118 x 0.02 x 0.0034 x (0.064) for each non-critical cabinet 0.0118 x 0.02 x 0.0034 x (0.064+ 0.0662) for each critical cabinet The other scenario concerns fires that develop in a critical cabinet and self-extinguish or are suppressed.

The equation for this scenario (for successful suppression) becomes:

0.0118 x 0.02 x (1- 0.0034) x CCDFtcasoafromBFNIPEEEj

= 2.35E-4 x 1.88E-4

= 4.42E-8 Page 8 of 34

Browns Ferry Nuclear Plant - IPEEE Graphically, these scenarios can be shown in an event tree format as:

Critical Cabinet 0.0118x0.02 Suppressed CCDF for Case 3 0.0118x0.02x(1-0.0034)x1.88E-04

=

4.42E-08 (RCIC Failure)

Unsuppressed Evacuate Control Room 0.0118x0.02x0.0034x(0.064+0.0662)

1.04E-07 Non-Critical Cabinet 0.0118%0.02 Suppressed N/A Possible Plant Trip Unsuppressed 0.0118x0.02x0.0034x0.064

Evacuate Control Room 5.14E-08 Using the Browns Ferry IPEEE submittal value for Control Room ignition frequency of 0.0118, this generates a fire related core damage frequency of 5.14E-8 for each non-critical cabinet 1.04E-7 for each critical cabinet (unsuppressed) 4.42E-8 for each critical cabinet (suppressed) 1.48E-7 total for each critical cabinet While each individual scenario remains screened, the total core damage frequency for all Control Room scenarios willexceed the FIVE cutoff of 1E-6 (i.e. 2.31E-6 for 45 non-critical panels and 7.40E-7 for 5 critical panels, or 3.05E-6 total).

This evaluation is conservative in that it does not address recovery of the Main Control Room after 60 minutes (see Step 2.5 in Appendix M of the Fire PRA Implementation Guide). Also, this evaluation assumes that any fire that is not suppressed willrequire control room abandonment.

Scenarios!dentified by NUREG-1521 Appendix B of NUREG-1521 (Technical Review of Risk-Informed, Performance-Based Methods for Nuclear Power Plant Fire Protection Analyses Draft report for comment) gives two primary scenarios for control room fires. The first addresses fire in a critical panel, requiring control room evacuation.

The second addresses fire in other cabinets, but still requires control room evacuation.

Each of these scenarios is described quantitatively below (values obtained from Tables B.4 and B.5 of NUREG-1521).

Page 9 of 34

Broivns Ferry Nuclear Plant - IPEEE Term Description a

Frequency of control room fires b

Area ratio of sensitive cabinet to total cabinet area within the control room c

Failure of remote shutdown capability d

Probability that smoke willforce abandonment of control room, given a fire e

Fire induced core damage frequency for Control Room Scenario 1

a x b x c x d =

Value 0.0118 0.020 0.064 0.10 1.51E-06 For the case of a fire in a non-sensitive cabinet, the probability of core damage can be bounded by the MSIV closure case.

As shown in NUREG-1521, core damage can occur as a result of failure to enable the remote shutdown panel, but only ifthe backup automatic systems (in this case HPCI and RCIC) fail to operate.

Term Description a

Frequency of control room fires b

Area ratio of non-sensitive cabinet to total cabinet area within the control room c

Failure of remote shutdown capability d

RCIC failure e

HPCI failure, given RCIC failure f

Probability that smoke willforce abandonment of control room, given a fire g

Fire induced CDF for Control Room Scenario 1

axbxcxdxexf=

Value 0.0118 0.98 0.064 0.0662 0.110 0.10 5.39E-07 Therefore, by this methodology, the total core damage frequency due to control room fires for Browns Ferry would be (1.51E-6+ 5.39E-7 =) 2.05E-6.

This value is slightly above the FIVE screening cutoff of 1E-6. Please note that this evaluation is conservative in that it assumes that one in ten Control Room fires results in Control Room abandonment.

If this were the case, the fire events database, which has 12 Control Room fires listed, should have at least one evacuation, whereas ten of the entries did not even result in a plant trip and none of the fires led to a control room abandonment situation.

Detailed Res onse to uestion 2 (Response to this question is primarily based on Response to Generic RAI on Fire-IPEEE, Question 4)

The question deals with detailed assumptions used in analyzing the MCR and justifications for those assumptions, including:

1.

Fire frequency 2.

Fire reduction factors 3.

Probability of abandonment, including specifically

~

Justification for the parametric form of the distribution

~

Data used for quantification Page10of 34

Browns Ferry Nuclear Plant - IPEEE fq t

h (C

p 1-)

Attachment B of the submittal and is based on the FIVE methodology.

The fire frequency is dominated by the electrical cabinets (approximately 80% of the total). The generic electric cabinet fire frequency is multiplied by a weighting factor of 3 to account for 3 control rooms.

Therefore, the fire frequency for the control room is based on generic data as identified in the FIVE methodology and no other assumptions or factors were used.

Fre uenc Reduction Factors The factors used in the re-quantified analysis include the'area ratio of the critical cabinet to total cabinet area (0.02), probability that operators willfail to recover the plant from the remote shutdown panel (0.064), probability that smoke willforce abandonment of the control room given a fire (0.1) and probability of non-suppression.

(0.0034). These generic factors have been derived from NUREG-1521, NSAC/181 and the EPRI Fire PRA Implementation Guide.

Probabilit of Non-Su ression and Abandonment The RAI specifically questions control room non-suppression probability and the time of fire detection.

The following discussion includes the selection of the detection time and its basis, conservatisms in the timeline, sensitivity of the results to the operating experienced used, the functional form of the suppression curve and its basis, and discusses the BNL report.

Detection Time. To best evaluate the probability of non-suppression, the analysis should consider a timeline of opportunities for detection.

For each opportunity in the timeline, the analysis should consider the associated plant specific factors that might impact the effectiveness of detection at that point. Given an agreed upon probability of non-suppression that is a function of time available to suppress the fire, the control room non-suppression time can then be calculated on a plant specific basis.

The detection time assumed is neither the earliest opportunity for detection, namely when the initiating electrical malfunction occurs, nor the latest opportunity, namely the time when rapid smoke generation occurs.

Photo-Electric smoke detectors are installed inside the electrical/control panels at BFN control rooms.

Human detection willprovide increased capability to detect fire.

Eleven of twelve control room fires in the FEDB are electrical cabinet fires. (There is one kitchen fire listed in the control room area.).

Due to limited amount of transient combustible inventories or other unique sources, it is assumed that electrical cabinet fires are the only significant fires that have the potential to cause control room evacuation.

Control room electrical fires do not involve high-energy electrical circuitry because the control room contains only instrumentation and control circuitry. Fire events experience with low voltage electrical fires indicates that these fires are slowly developing and are most often diagnosed by local personnel, even when such fires occur in areas outside of the constantly manned control room. For this reason, it is assumed that the electrically ignited cabinet fire tests Pest 24 and Test 25 at SNL) are representative of the expected timeline of fire development in a control room electrical cabinet.

Similarly, it is assumed that human detection is the most likely means of fire detection in the control room.

In the case of the control room Page llof 34

Bro~vns Ferry Nuclear Plant - IPEEE fires reported in NSAC-179L, only two of ten applicable fires were detected by smoke detectors.

Even in these cases, the event description lists local personnel in conjunction with automatic detection.

This experience provides strong qualitative evidence that detection of control room fires is a "competition" between human and automatic means that is often "won" by the human.

The following table lays out the time line for a control room fire based on SNL tests 24 and 25.

The table indicates that substantial time is available for detection prior to the time selected in NSAC-181.

It indicates that the number of means by which detection can occur increases substantially over time.

Timeline of Control Room Fire Events Representative Event from SNL Tests Time(s) from SNL Tests 24 25 Scenario Event Available Means of Detection Time ignition source was ene ized 0:00, 0:00 Electrical malfunction occurs Control board indication Ozone smell in CR J

Time smoke became visible Time cable ignition was observed Not addressed by test scenario Rapid growth in measured heat release rate and smoke generation rate 10:30, 9:30 15:20, 15:40 NA 22:20, 20:00 Electrical item (relay, resistor on circuit board or cable) overheats and starts smoking Electrical item (relay, resistor on circuit board or cable) ignites Fire propagates from electrical item to cables or other combustibles (e.g.,

adjacent plastic - relay cover or circuit board Cables fullyinvolved in burning, dense smoke accumulates at the ceiling Control board indication Ozone smell in CR Smoke observed inside the cabinet with direct viewing In-cabinet detector actuates Control board indication Ozone smell in CR Smoke observed inside the cabinet with direct viewing In-cabinet detector actuated Flaming visible with direct viewing Smoke visible outside the cabinet Ceilin detector actuates'7 Same as above Same as above Flame visible outside the cabinet Smoke level begins to descend from ceilin Time control panels are no

'onger visible 27:00, 23:00 30:00, 30:00 1

Smoke begins to obscure full Same as above length of control board panels (1) First set of times is the point of measured obscuration and the second set of times is the point when obscuration was observed.

Page 12 of 34

Browns Ferry Nuclear Plant - IPEEE

~

Starting with the electrical malfunction, the opportunity for detection begins.

As time grows, the amount of ozone will increase and this means of detection will correspondingly grow rapidly. Once visible smoke is produced, a similar condition will occur. That is, the continuous puffs of smoke mentioned in the review willaccumulate and be more likely to be noticed.

From a practical perspective, it is difficultwith the information available to date to predict detection rates for each of these time periods.

In lieu of that, the time selected is consistent with operating experience and SNL test described above.

The SNL tests document how actual observations seemed to indicate that the control board was visible even when measured values indicated that it should not be. The detection time and the "observed" time for forced evacuation, allow about 15 minutes for suppression.

Functional Form of the Distribution. The functional form of the manual suppression distribution selected is lognormal. This distribution form was selected because itwas found by EPRI to be the best fitfor extrapolating human response data collected from simulators.

EPRI considered at one time the Weibull distribution but finallyconcluded that the lognormal was the best selection for post accident human events.

In reviewing the simulator data it collected at a number of different power plants, EPRI found that goodness of fittests generally were comparable or better for the lognormal distribution.

In addition, the lognormal distribution had been selected by a number of other interpreters of simulator data and found acceptable.

Finally, the lognormal distribution tends to give a higher probability at longer times, i.e., on a relative basis it is conservative.

A lognormal distribution with a mean of 3.4E-03 and an error factor of seven was used in the uncertainty analysis for manual suppression within 15 minutes.

.Tt R

i i

ML p

(NURGl'ontrol room temperature effects may even be more limiting than smoke in causing evacuation.

The excerpts of the BNL report contained in the Critique do not seem to be consistent with the SNL cabinet fire tests.

In SNL test 24, the time of assumed evacuation occurs while room temperature is still at its nominal value at the 6-foot elevation (Figure 31, p. 37).

In SNL test 25, the temperature at 6 foot elevation was only slightly above nominal at the assumed time of evacuation and never even reached 40 degrees C (Figure 38, p. 43). Test 25 involved operation of the facilitywith 8 room changes per hour (versus 1 room change per hour in test 24). The SNL report speculates that cooling from the ventilation system probably kept the temperature low. Hence, we would conclude that as long as operators initiated the smoke removal system in the control room, it is unlikely that room temperature would become a significant concern.

FIRE UESTION 3-HEAT LOSS FACTOR HLF The heat loss factoris defined as the fraction ofenergy released by a fire that is transferred to the enclosure boundaries.

This is a key parameterin the prediction ofcomponent damage, asit determines the amount ofheat available to the hot gas layer. A larger heat loss factor means that a larger amount ofheat (due to a more severe fire, a longer burning time, or both) is needed to cause a given temperature ris. It can be seen thatifthe value assumed forthe heat loss factoris unrealistically high, fire scenarios can be improperiy screened out. Figure 3.0 provides a representative example ofhow hot gas layer temperature predictions can change Page 13 of 34

Browns Ferry Nuclear Plant - IPEEE assuming different heat loss factors. Note that: (1) the curves are computed for a 1000 kWfire in a 10m x 5m x 4m compartment with a forced ventilation rate of 1130 cfm; (2) the fireinduced vulnerability evaluation (FIVE)-recommended damage temperature forqualified cableis 700'F forqualified cable and 450'F for unqualified cable; and, (3) the Society forFire Protection Engineers (SFPE) curve in the figure is generated from a correlation providedin the SFPE Handbook (3-11.

Based on evidence provided by a 1982 paper by Cooper, et al. 3.2, the EPRI Fire PRA Implementation Guide recommends a heat loss factor of0.94 forfires with durations greater than five minutes and 0.85 for "exposure fires away from a wall and quickly developing hot gas layers." However, as a general statement, this appears to be a misinterpretation of the results.

Reference 3.2, which documents the results ofmulti-compartment fire experiments, states that the higher heat loss factors are associated with the movement ofthe hot gas layer from the burning compartment to adjacent, cooler compartments. Earlierin the experiments, where the hot gas layeris limited to the burning compartment, Reference 3.2 reports much lower heat loss factors (on the order of 0.51 to 0.74). These lower heat loss factor are more appropriate when analyzing a single compartment fire. In summary, (a) hot gas layer predictions are very sensitive to the assumed value ofthe heat loss factor; and (b) large heat loss factors cannot bejustified forsingle room scenarios based on the information referenced in the EPRI Fire PRA Implementation Guide.

The submittalsindicates that a heat loss factor of0.85 was usedin the Browns Ferry study. In light ofthe preceding discussion, please either. (a)justifythe value used and discussits effect on the identification offire vulnerabilities, or (b) repeat the analysis using a morejustifiable value and provide the resulting change in scenario contribution to core damage frequency.

Figure 3.0- Sensitivity ofthe hot gas layer temperature predictions to the assumed heat loss factor.

3.1 P.J. Dinenna, et al, eds "SFPE Handbook ofFire Protection Engineering,"2nd Edition, National Fire protection Association, p. 3-140, 1995.

3.2 L. Y. Cooper, M. Harklemad, J. Quintiere, W. Rinkinen, "An Experimental Study of Upper Hot Layer Stratificationin Full-Scale Multiroom Fire Scenarios,'ASME (American Society ofMechanical Engineers) Journal ofHeat Transfer, 104,741-749, November 1982.

Res onse to uestion 3 The Heat Loss Factor (HLF) is a parameter used in the FIVE methodology in the prediction of hot gas layer (or the compartment environment) temperatures, ifa fire burns without intervention and consumes all of the available fuel. Ifthe combustible loading of the compartment is found to be sufficient enough to develop damaging temperatures, then all contents of the room are considered damaged and specific source/target evaluations are not necessary.

Therefore, the HLF has no direct relationship in the calculation of plume or ceiling jet temperatures or radiant heat flux to determine target damage.

However, the BFN analyses conservatively adjusts the critical temperature rise based on hot gas layer temperatures, considering all the available fuel in the compartment is consumed.

This method effectively assumes instantaneous consumption of all fuel resulting in higher ambient temperatures and Page14of 34

Browns Ferry Nuclear Plant - IPEEE therefore, higher fire plume/ceiling jet sublayer temperatures (i.e. superimposed fire plume/ceiling jet sublayer).

The calculated damage envelop is thus increased.

Heat loss factors typically range between 70 and 95 percent of the total energy released in enclosure fires (EPRI-TR100443, Section 7.7.2)

. The variables expected to influence the hot gas layer temperatures in a single compartment are the heat release rates; duration of fire; the room size; air flow rate to the fire, reflected in the size of the opening; and the thermal properties of floor, ceiling and walls. The FIVE methodology simplifies the analysis by utilizing the Heat loss Factor (HLF) which accounts for the heat loss to the boundaries.

The FIVE methodology also assumes fires to be fuel controlled. Therefore, it can be seen that HLF willin affect vary from compartment to compartment (i.e. higher values for larger compartments).

HLF will also be higher during early stages of a fire and reduce as the boundaries heat up. Itwill be extremely difficultto justify a single value of HLF for all compartments and for all stages of a fire. For this very reason, the fire protection literature refrains from the use of HLF. However, it can also be reasonably concluded that compartments with large surface areas; large openings to allow for vent flows; and higher thermal conductivity and specific heat are expected to have higher HLF values (i.e. larger compartments have the ability to loose more heat).

Most of the fire scenarios evaluated at BFN are in the Reactor Buildings which are very large open areas with concrete boundaries and large openings.

Therefore, BFNs use of the higher value of 85 percent in its analysis is justified.

Due to the uncertainties involved in the selection of the HLF, an alternate method to determine compartment temperatures is being performed.

Unlike FIVE methodology, this method includes most of the parameters described above in computing compartment temperatures.

These temperatures willthen be compared to the compartment temperatures computed by the FIVE methodology.

Temperatures in compartments are calculated using the method of MQH for naturally ventilated fires (

Reference:

SFPE Handbook 2"'dition, Page 3-139, Equation 12).

As an example, the electrical cabinet 480V RMOV Board 2C located in Unit 2 Reactor Building EL 565 willbe evaluated using the MQH method.

The HRR for the cabinet is taken as 190 Btu/sec (200 kW); the fire duration is approximately 1800 sec based on the combustible loading of 372,000 Btu. The openings and surface areas are conservatively approximated.

The thermal properties of concrete are from SFPE Handbook.

See Attachment 1 for the computations.

The compartment temperatures calculated by this method are very close to the hot gas layer temperature calculated using the FIVE method with 0.7 HLF (Attachment 2). Increase in surface areas and opening size results in lower temperatures corresponding to higher HLF.

Based on the results of the alternate method, all significant fire sources including electrical cabinets are being re-evaluated using a HLF of 0.7 (Attachment 2). Note that the heat release rate (HRR) for electrical cabinets is taken as 190 Btu/sec as suggested in RAI Question 0 4.

The table below depicts the summary of current IPEEE values and the re-calculated values based on 0.7 HLF and 190 Btu/sec for electrical cabinets.

Also provided is the walked down zone of influence used in determining cable damage envelop.

Page15of 34

Browns Ferry Nuclear Plant - IPEEE

,Ij'riitior'i':.'..;,",::'l,'."::..:,":".'::.,".':j;.;:lN'.':'-:.4!%'::,:Curr'ent,':::;:IPEEE!Viliie)'.'.;.:.:,.l':;j"-',

HLF='0':85:;::ERR:=.',.'.;$.09,':,:$$'.

Btii/sec":fo'r!Elect:;~P>"~~)','."':',,::

'":.Re-.',ciIculate'd:;:Bsse'cf:::,",::":,::!'.:,::::

,';HRR=,',$

,90,:Bb'ilsec:,.foi,..:..'-:..'le'ct:;-'.",'Ca6j'r'ie'ts'~$$$:.:-jgi4!':;

Cui'ident
:Zo'rie,:..".of,;,'lnACie'rice'j'j".

!(ZPl):;::Us'e'd'jr't;Date'r'ij)ir'iij:::,::!y

Oamage,
p~r,

~Cnttca~fey

.;;",,:,:~~

':;:Ht;,'::(ft)i;:::-'.;:::,::.;,::';:,::,:':",'Radial.;;.';:.",".;;.::.'".:,':.i'.,':'.,';

Critical':":'-::::4
",.Radial,:;
.'.i;;:-,:

!QTikirice: ft ';

Pa)ii'age;:Ht;.':.:,".:;
(),',;,.;.,;.,.,r.;
,,".Rjd!$tji'.:';;~jqiiil
.5ista'r'ice". ft 480V RMOV BD 2C 480V RB Vent BD 2B 250V RMOV BD 2C 2-PNLA-25-340/341 D

ell Torus Com 480V RMOV BD 2D U2 Pref. AC Trans.

RBCCW Pum 2A/2B 480V RMOV BD 2E MG Sets 2DN &2EA 4KV-480VTrans.

2-LPNL-025-0031 4KV RPT BD 2-1/2-2 6.77 6.77 6.82 6.70 11.85 6.82 9.13 4.01 11.81 7.04 9.29 7.26 6.9 2.60 2.60 2.60 2.52 5.35 2.60 3.78 1.38 2.60 2.67

~

3.78 2.60 2.60 8.7 8.7 8.8 6.9 12.0 8.9 9.2 4.0 15.2 7.3 9.7 10.4 9.1 3.5 3.5 3.5 2.5 5.4 3.5 3.8 1.4 7.0 2.7 3.8 3.5 3.5 8.0 8.0 9.0 7.0 12.0 9.0 4.0 12.0 7.0 10.0 10.0 7.0 3.0 40 4.0 3.0 6.0 4.0 4.0 2.0 2.0 3.0 3.0 4.0 3.0 MG Sets 2DA and 2EN 6.99 2.67 7.2 2.7 7.0 3.0 LPNL-25-23/24 240V Li htin BD 2B SLC Pum s A and B 7.13 6.74 12.19 2.60 2.60 5.35 9.8 8.6 12.6 3.5 3.5 5.4 10.0 7.0 13.0 4.0 2.0 6.0 Comparison of the re-calculated damage threshold elevations and the critical radial distances with the walked-down zone of influence (ZOI) indicates that the increase in distances were within the margin available for most of the non-electrical cabinet ignition sources; for some electrical cabinets the increase in damage height and radial distance was minimal and did not involve additional components; 480V RMOV BD 2E depicted the most significant increase in damage height and critical radial distance due to its location in the comer (location factor 4).

This electrical board was again walked down to determine the impact of a larger damage envelop.

No additional electrical cables were identified within the expanded ZOI. 4KVRPT BD 2-1/2-2 and 240V Lighting BD 2B also depicted slightly larger ZOI, however, no additional components were identified.

The above evaluation was done for unit 2. Unit 3 results are expected to be similar.

Therefore, the above analysis shows that the changes in ZOI due to higher HLF and cabinet HRR are not significant to cause appreciable changes to the calculated core damage frequencies (CDF).

Page 16 of 34

0

Browns Ferry Nuclear Plant - IPEEE FIRE UESTION 4-ELECTRICALCABINETHEAT RELEASE RATE The analysis of the maximum rate ofburning in a closed but ventilated electrica panel under oxygen-limited burning conditions (Submiftal Affachmenf A: Heat Release Rafes) appears opfimisficin comparison to experimental data. The cited air flowcorrelation from Drysdale (Submittal Reference 21) only applies fo one-direction (out) flowthrough a single opening in a large room under post-flashover condifions. These conditions are not consistent with the postulated panel fire conditions because:

(1) fhe postulafed fireis assumed to bein fhe pre-flashover stage, (2) fhe electrical panels apparently have openings near both the top and bottom offhe panels allowing forboth inlef and outlet flowand the development ofa significant "chimney effecf"due fo buoyancy driven air flow, and (3) warping ofthe panel doors during the fire willlikelyallow for the area available forair flowto increase in size as compared to fhe assumed she ofthe venfilafion grills based on the testing experiences ofbofh Sandia National Laborafories (SNL) (ref 4. 1) and, more recently, fhe Technical Research Center (VTT) of Finland (refs. 4.2 and 4.3). Further, fhe cited maximum heat release rate (HRR) of53 BTUls Is opfimisticin comparison fo the measured heat release rates forclosed panels as tested both by SNL and VIT. In the SNL tesfs closedlvenfilafed panel HRR values up to 265 BTUIs were measured (i.e., Considering SNL Scoping Test 10) andin the VTTFinland fests, maximum HRR values of up to 380 BTUls were measured (i.e., considering VTTpanel test ¹1).

Please assess fhe changesin the /PEEE fire analysis results andinsightsif fhe maximum HRR ofa closed but ventilated electrical panel is increased fo 190 BTUls, fhe midrange ofthe available test data.

4.1 Chavez, J. M., "An Experimental Investigation ofInternally Ignited Firesin Nuclear Power Plant Confro/ Cabinets. Part I: Cabinet Effect Tests,"

NUREGICR4527, April 1987.

4.2.

Mangs, Johan and Keski-Rahkonen, Olavi, "Full Scale Fire Experiment on Electronic Cabinets," Technical Research Center ofFinland (Valtion Teknillinen Tutkimuskeskus, V/77, VTTpublicafion 186, Espoo, Finland, 1994 (ISBN 951-384924-5; ISSN 1235-0621; UDC 614.84:699.81:621.3.05).

4.3 Mangs, Johan and Keski-Rahkonen, Olavi, "Full Scale Fire Experiments on Electronic Cabinets II,"Technical Research Center ofFinland (Valfion Teknillinen Tufkimuskeskus, VTT), VTTpublicafion 269, Espoo, Finland, 1996 (ISBN 951-384927-9; ISSN 12350621; UDC 614.842:621.3.04:53.083).

Res onse to uestion 4 The air flowcorrelation cited in Attachment A of the submittal is valid for stoichiometric burning utilizing all available air ifthe vent flow rate is fullychoked (Equation 1). Using 3 MJ/kg as the heat released per unit mass of air consumed, this yields a stoichiometric rate of heat release as depicted in Equation 2 and is similar to the correlation used in the BFN submittal.

Using a compartment energy balance and a simple energy loss model, Babrauskas, V ("Estimating Room Flashover Potential", Fire Technology, 16(2), 1980) developed a relationship between the ventilation parameter and the rate of heat release required to cause flashover.

Based on the database of 33 compartment fire tests, he found that the rate of heat release required to Page 17 of 34

Browns Ferry Nuclear Plant - IPEEE cause flashover, is described by Equation 3. This corresponds to half the heat release rate which would occur for stoichiometric rate of heat release (Equation 2). Therefore, the methodology used in the submittal is conservative, as it uses the stoichiometric burning and is consistent with HRR calculation correlation's found in the fire protection literature.

Since the ratio of the heat of complete combustion to the air mass is nearly constant (3 MJ/kg) for most fuels; by specifying the opening size, one can obtain the HRR instantaneously.

m, =0 SA,JH,[kgls]....Eq.u.ation 1

Q

~ y 15002 JH [W]

Eqttation 2

Q~, = 750M,v%[k8'J.....

..It.quation 3

Most electrical cabinets have no ventilation o enin s as described in Attachment C of the submittal. 480V RMOV BD 2E does have small openings at the top and bottom.

However, since the calculated HRR is based on choked air flowconditions as discussed above, maximum HRR is calculated for the opening size specified.

The HRR calculation method as described above is valid and conservative.

However, we agree that during actual fire scenarios, warping of the panel doors is likely. This willincrease the area available for air flowand thus increase the HRR. Therefore, all electrical cabinets have been re-evaluated using the HRR of 190 Btu/sec as suggested by the reviewer. The resulting changes in the damage threshold elevations/distances and corresponding CDF impacts are addressed in response to question number 3 and Attachment 2.

FIRE UESTION 5-DESCRIPTION OF INITIATINGEVENTS The initiating events and systemic or functional sequences identified foreach fire source locationin a compartment are crucial to the evaluation ofconditional core damage probability.

The selection influence both the complement ofequipment and the human actions that are assumed to be required to prevent con. damage.

The human error probabilities (HEPs) used in the analysis must properly reflect the potential effects offin. (e.g., smoke, heat, loss oflighting),

evenif these effects do not directly cause equipment damagein the scenarios being analyzed.

A review ofthe reasonableness ofthe quantitative screening calculationsin the Browns Feny fire IPEEE cannot be made because the accident sequences, analytical assumptions, functional or systemic event trees associated with fire-initiated sequences, and human actions have not been provided in accordance with NUREG-1407 (page C-4, Items 9, 10, and 11).

Quantr'frcatr'on ofthe fire core damage frequency (CDF) and screening relied on a limitedset of initiating events whose selection was notjustifiedin the submittals (Table 5-1in the Unit 2 submittal, and Table 5-4in the Unit 3 submittal). Several boiling water reactor-typicalinitiating events are notincluded among the table entries, e.g., loss ofheating, ventilation, and air condition, loss ofservice or component cooling water, orinadvertent safety relief valve actuation.

Page 18 of 34

I a

J

Browns Ferry Nuclear Plant - IPEEE Please provide the following foreach unscreened compartment: (1) the initiating events

analyzed, (2) the accident sequences and a word description ofthe accident sequences that does not rely upon knowledge ofthe top eventidentifiers in the event tr..s,, (3) a list ofkey analytical assumptions usedin the development ofthe conditional probability ofcore damage, (4) the functional or systemic event trees usedin fhe fire analysis with a description ofthe top events, (5) the key human actions ofeach sequence and the HEPs (descriptions and numerical values) foreach. For the HEPs, describe how the effects ofthe postulated fires were treated.

Res onse to uestion 5

[Later]

FIRE UESTION 6 - REMOTE SHUTDOWN CAPABILITY NUREG-1407, Section 4.2 and Appendix C, and Generic Letter (GL) 86-20, Supplement 4, request that documentation be submitted with the IPEEE submittal with regard to the Fire Risk Scoping Study (FRSS) issues, including the basis and assumptions used to address these issues, and a discussion ofthe findings and conclusions. NUREG-1407 also requests that evaluation results and potentialimprovements be specifically highlighted. Control system interactionsinvolving a combination offire-induced failures and high probabi%ty random equipment failures were identifiedin fhe FRSS as potential contributors to firerisk.

The issue ofcontrol systemsinteractionsis associated primarily with the potential that a firein the plant (e.g., the MCR) might lead to potential control systems vulnerabi%ty. Given a fin.in the plant, the likelysources ofcontrol systemsinteractions are between the control room, the remote shutdown panel, and shutdown systems. Specific areas that have beenidentified as requiring attentionin the resolution offhisissue include:

Electricalindependence ofthe remote shutdown control systems:

The primary concern of control systemsinteractions occurs at plants that do not provide independent remote shutdown control systems.

The electncalindependence ofthe remote shutdown panel and the evaluation ofthe level ofindication and control ofremote shutdown control and monitoring circuits need fo be assessed.

Loss ofcontrol equipment orpower before transfer. The potential forloss ofcontrol power forcertain control circuits as a result ofhot shorts andlor blown fuses before transfemng control from fhe MCR to remote shutdown locations needs to be assessed.

Spurious actuation ofcomponents leading to component damage, LOCA, or intedacing systems LOCA: The spurious actuation ofone or more safety-related to safe-shutdown-related components as a result offire-induced cable faults, hot shorts, or component failures leading to component damage, LOCA, orinterfacing systems LOCA, prior to taking control from fhe remote shutdown panel, needs to be assessed.

This assessment also needs to include fhe spurious starting and running ofpumps as well as the spurious repositioning of valves.

Page 19of 34

Browns Ferry Nuclear Plant - IPEEE Total loss ofsystem function: The potential fortotal loss ofsystem function as a result offire-induced redundant component failures or electrical distribution system (power source) failure needs to be addressed.

Please describe your remote shutdown capability, including the natun. and location ofthe shutdown station(s), as well as the types ofcontrol actions which can be taken from the remote panel(s). Oescnbe how your procedures provide fortransfer ofcontrol to the remote station(s).

Provide an evaluation ofwhether loss ofcontrol power due to hot shorts andlor blown fuses could occur prior to transfemng control to the remote shutdown location and identifythe risk contribution ofthese types offailures (ifthese failures are screened, please provide the basis forthe screening). Finally, provide an evaluation ofwhether spurious actuation ofcomponents as a result offire-induced cable faults, hot shorts, or component failures could lead to component damage, a LOCA, oraninterfacing systems LOCA pnor to taking control from the remote shutdown panel (considering both spurious starting and running ofpumps as well as the spurious repositioning of valves).

Res onse to uestion 6 The Backup Control System (BCS) provides backup control features for the systems needed to fulfillthe shutdown function from outside the main control room (MCR) and bring the reactor to a cold shutdown condition in an orderly fashion irrespective of shorts, opens, and/or grounds in the MCR circuits. The BCS also provides the overriding controls for (1) those items not needed for actual shutdown operation but which have the potential through operation to cause a loss of coolant and possible damage to the reactor system and core, and (2) those items which could jeopardize the reliability of the 4160 volt shutdown board system by overloads due to spurious load and transfer breaker operation. The BCS also meets the 10CFR50 Appendix R requirements for Alternate Shutdown capability for a fire in the Control Bay (including compartments 16-1, 16-2, 16-3, 17, 18 8 19).

The system provides alternative shutdown capability for equipment which may be damaged in the control bay (CB). The backup system is physically and electrically separated from the damaging influence from any affected areas in the CB. The system provides the ability to achieve cold shutdown with equipment which is redundant or diverse to that which is in the MCR (or the affected area in the CB). It is in this sense that the Backup Control equipment is associated with the single-failure criteria, not that all features of Backup Control are, in themselves, single-failure proof.

The Backup Control Panel (Panel 25-32) is physically located in the Shutdown Board Room (within the Reactor Building) for each unit and is thus physically separated from the control bay.

Transfer switches of the maintained contact type are located on the backup control panel and are used to transfer control from the MCR to the backup control panel. Other BCS functions take place at the 4KV Shutdown Boards, 480V Reactor MOV Boards and 250V DC Reactor MOV Boards via transfer switches. An example would be the manual controls for the Diesel Generators which are located on the respective "4160 volt shutdown boards (and locally at the diesel generators) as backup for automatic or manual initiation from the control room.

Page 20 of 34

C

Browns Ferry Nuclear Plant - IPEEE Procedures are in place to effect an orderly transfer of control from the MCR to the backup control locations. Abnormal Operating Instructions (AOI) are provided for evacuation from the control room for all but an Appendix R event. Safe Shutdown Instructions (SSI) are provided for evacuation resulting from an Appendix R event.

Only essential systems are provided at the BCS and include the following:

Main Steam S stem The controls and appropriate instrumentation for monitoring the following functions/components of the main steam system are provided on the 480V Reactor MOV Board or the 250V DC Reactor MOV Board or the backup control panel:

a.

Main Steam Safety Relief Valves (MSRV) b.

Main Steam Line Isolation Valves (control for closure only) c.

Main Steam Line Drain Valves The evaluations of associated circuits, including the evaluation of high-low pressure interfaces concluded that the MSRV is the limiting component whose spurious operation could adversely affect plant shut down. Therefore, analyses were performed to demonstrate that spurious operation of one MSRV could be mitigated by the minimum safe shutdown systems.

Feedwater S stem Reactor pressure and water level indication is provided on the appropriate board(s) or the backup control panel for monitoring the reactor condition regardless of the condition of the control room or spreading room circuits.

RHR Service Water S stem The service water supply to the EECW System and to the two RHR heat exchangers that serve the appropriate RHR backup control loop on each unit have controls for the service water pumps and associated valves, and appropriate instrumentation for monitoring operation of the system are provided on the backup control panel and/or the appropriate boards. Transfer switches and control switches for the pumps and valves are located on the appropriate 4160 volt AC boards and 480 volt MOV boards.

250 volt DC Power S stem The plant dc power system is protected by its physical location and circuit design such that essential circuits for emergency shutdown are available irrespective of the main control room condition. The battery and board rooms are dispersed along the length of the Control Bay at elevation 593.0 level which is below the Cable Spreading Rooms.

Penetrations into the Cable Spreading Rooms are designed to prevent fire propagation across them. The circuits necessary for shutdown do not traverse the Cable Spreading Rooms but cross the wall into the reactor building via conduits. Such circuits are provided for backup systems and equipment and are obtained from the 250 volt DC reactor MOV boards which have direct feeds from the unit battery boards.

Page 21 of 34

Broivns Ferry Nuclear Plant - IPEEE Emer enc E ui mentCoolin WaterS stem EEC The emergency equipment cooling water system needed for cooling the diesels, RHR pump seal, and RHR room coolers and ventilation/air-conditioning have pump and valve control switches at the backup control panels as backup for the normal manual or automatic initiation from the control room. Pump control switches are required as part of the RHRSW system. Transfer switches for the EECW valves are located on the appropriate 480 volt AC boards or 250 volt DC boards. Spurious closure of the EECW sectionalizing valves is prevented by maintaining the valve breakers open during normal power operation.

Reactor Core In'ection Coolin RCIC The valve, pump and turbine controls necessary to operate the RCIC system and the appropriate instrumentation for monitoring its operation are provided on a backup control panel (s),or the appropriate 250 volt DC or 480 volt AC boards. Spurious operation of the RCIC system is not a concern based on the flow rate (600 GPM). Plant procedures and training allow adequate time for manual actions to prevent water intrusion into the main steam lines due to the spurious initiation of RCIC.

Hi h Pressure Coolant In'ection HPCI The control of the steam supply valve for the HPCI system is provided on the appropriate 250 volt DC reactor MOV board to ensure that uncontrolled fillingof the reactor vessel is not caused if HPCI is brought on by circuit malfunction or reactor low level. Analysis of the spurious operation of the HPCI system shows that the operator can terminate HPCI flow within 10 minutes to prevent water intrusion into the main steam lines.

Residual Heat Removal RHR Valve, pump and motor controls and the appropriate instrumentation are provided for monitoring the operation of one RHR loop per unit. The modes of RHR operation provided from the backup control panel (and/or the appropriate boards) include:

a.

Suppression Pool Cooling b.

Low Pressure Coolant Injection (LPCI) c.

Shutdown Cooling Transfer switches and control switches for all the RHR pumps and valves for one loop per unit are located on the appropriate 4160 volt AC or 480 volt AC or 250 volt DC boards.

Page22of 34

Broxvns Ferry Nuclear Plant - IPEEE Core S ra CS A control circuit is provided at the 4KV shutdown boards to trip and lock-out all core spray pumps independent of the condition of the control room or spreading room circuits (to prevent potential overload on the 4KV busses and associated diesels).

Diesel Generator S stem Diesel Generator manual controls for diesel startup are located on the respective 4160 volt shutdown boards and locally at the diesel generator(s) as backup for the automatic or manual initiation from the diesel information panel for Unit 1/2 and from the 4KV shutdown boards for Unit 3. Operation of the loads on the diesels is performed at the 4KV shutdown boards. Undesired loads (which might occur from circuit malfunctions and thus cause diesel/4KV overload conditions) are prevented by using control circuits which are independent of the control room and/or cable spreading rooms.

Control Rod Drive CRD The backup control (transfer and control switches) for CRD Hydraulic Pumps 1B and 3B (and the required valves) are provided on the appropriate 480 volt AC reactor MOV board and 4160 volt AC board for supporting the reactor water level associated with the operation of the RHR (LPCI) and RCIC systems. The scram discharge volume test pilot solenoid valve is provided with a transfer switch and a control switch on the backup control panel. Spurious operation of the CRD system is not a concern based on the flow rate for CRD (200 GPM). Plant procedures and training allow adequate time for manual actions to prevent water intrusion into the main steam lines due to the spurious operation of the CRD system.

Analyses were performed to determine the effects of spurious operations on the shutdown capability of the minimum Safe Shutdown Systems (SSDS). This analysis was performed for four categories of plant equipment at BFN:

a.

Minimum SSDS (RHR, RHRSW, EECW, etc.)

b.

MSRVs c.

High-low Pressure Interface d.

Other Plant Equipment (Core Spray, HPCI, RCIC, etc.)

The process of identifying the significant spurious operation for a fire within the nuclear steam supply system and balance-of-plant system was performed by locating the following:

a.

Allhigh-low pressure interfaces b.

Allpotential paths for coolant inventory loss c.

Allpotential paths for flowdiversion d.

AIIpotential flow blockages Page 23 of 34

Browns Ferry Nuclear Plant - IPEEE Each of these potential adverse spurious operations was evaluated for its potential consequence in accordance with the assumptions described below:

a.

Spurious operation occurs simultaneously with other fire effects.

b.

Spurious operation for any equipment is considered plausible unless the equipment is protected in the fire area.

c.

The number of spurious operations considered in this analysis is limited by the design requirements for associated circuits which is:

1.

For non-high-low pressure interface components circuit failures/spurious operations are analyzed one at a time.

2.

For high-low pressure interface components two or more circuit failures/spurious operations are assumed to occur at the same time.

d.

Spurious operation which could defeat the RPS or MSIVs is not considered to be plausible (The RPS and MSIVs are redundant and fail-safe on loss of power. This redundancy provides for a system which is single-failure proof such that a failure will fail the system in the safe direction).

e.

Spurious operation of three-phase electrically powered equipment due to hot shorts of the power cables is considered to be incredible (with the exception of high-low-pressure interfaces).

As described above, all significant plant damage states; i.e. all high-low pressure interface spurious actuations, all potential paths for coolant inventory loss, all potential paths for flow diversion, all potential flowblockages; were taken into consideration.

Note that spurious actuations are considered one at a time unless at high low pressure interfaces, where multiple spurious are assumed in any single line. Therefore, spurious operation analysis was performed for the minimum SSDS for the time frame before the manual transfer occurs. This evaluation shows that the system design capability ensures the availability of the minimum SSDS in spite of their own spurious operation.

Cables and components are considered to be incapacitated (unavailable) when subjected to a fire environment; spurious actuations and circuit failures due to fires are not specifically modeled as described in response to Question 1. As stated in the response; "currently circuit faults cannot be adequately modeled due to lack of accrued experience and availability of quantitative PRA methods".

FIRE UESTION 7-CONSIDERATION OF TRANSIENT COMBUSTIBLES In general, the firerisk associated with a given compartmentis composed ofcontributions from fixed and transientignition souitces. Neglect ofeither contribution can load to an underestimate of the compartment's risk and, in some cases, to improper screening offire scenarios. Ifsuch compartments contain the cables forall redundant trains ofimportant plant safety systems, a

major vulnerability may be overiooked, without sufficient analysis ofpotential accident sequences and needed recovery actions.

In the Browns Ferry submittals, transient combustibles appear to have been considered onlyin the reactor buildings. No basis forexcluding other fire zones was given. Also, in calculating the area ratio (the u-termin FIVE) forfires from transient combustibles leading to damage by radiant exposure, the appropriate floorarea to be usedis defined by a perimeter drawn around the target a damage distance away. As such, the u-factor varies from room to room depending Page 24 of 34

Browns Ferry Nuclear Plant - IPEEE on the number and dimensions oftargets. (As an example, for a trash bag with a 5-foot damage radius, and a target with a square footprint 4 feet on a side, the damage footprint would have an area ofabout 158 square feet, i.e., all of the floorarea within 5 feet ofthe target) itis not clear that such considerations were used to determine the 1500 square feet area usedin Section 6.1.1 ofthe submittals.

In compartments where all fixedignitions sources have been screened out, has the possibility of transient combustible fires been considered? For each compartment where transient fires have not been considered, please provide thejustification forthis conclusion and provide a discussion on compartmentinventoryin terms ofsystem trains and associated components (i.e, cables and other equipment). Please explain whether or not the conditional core damage probabi%ties, given damage to all cables and equipmentin these compartments, are significant (i.e., cables from redundant trains are present). Ifthe conditional core damage probability fora compartmentis considered significant, please providejustification forassigning a very low likelihood ofoccurrence to transient fuel fires forthe compartment. Finally, please confirm or correct the estimated contribution from transient combustible firesin the reactor buildings to the plants'ire risks.

Res onse to uestion 7 The initial screening phase of the analysis (Section 5 of submittal) considers engulfing fire in all compartments and components located within the compartment are assumed to be damaged.

Therefore, fixed or transient combustible analysis is not necessary at this stage.

The compartments which were not screened out initiallywere then evaluated as part of detailed screening process (Section 6). The detailed phase of the analysis considers specific fire scenarios involving fixed and transient combustibles.

Fixed and transient ignition sources were specifically addressed for the Unit 2 and Unit 3 Reactor Buildings. Other fire areas/compartments (e.g. 4,5,8,9,16-1,16-2,16-3,18,25-1,25-2 and 25-3 in Unit 2) are mostly electrical/switchgear rooms with the exception of turbine building and some areas in the control building.

In the electrical rooms, the source and targets willgenerally be electrical cabinets and cables associated with the same cabinet.

Therefore, a source/target evaluation involving fixed or transient combustibles is not practical. These areas were evaluated based on an "event tree" approach.

In the use of an event tree approach to the analysis of fires, the fire frequency for the areas is segmented into a range of cases.

These cases are selected to cover the range between "high frequency/low consequence" such as fires that result in a turbine trip only, to "lowfrequency/high consequence" events, such as control room evacuation.

Note that the total ignition frequency used in the event tree analysis includes contribution of transient combustibles.

The target damage foot print area calculations for radiant exposure (from transient combustibles) were not necessarily based on all of the floor area within 5 feet of the target.

For example, ifthe 5 feet distance from the target included the walkways, access areas, space behind electrical cabinets, etc. then those spaces were not considered in the area calculations.

However, due to the uncertainties involved in the area calculations, a sensitivity analysis has been performed to assess the impact on CDF estimates.

Page 25 of 34

Broivns Ferry Nuclear Plant - IPEEE Units 2 and 3 reactor building have also been provided with NFPA code complying automatic sprinkler systems.

However, for fire scenarios in the reactor buildings, no credit is taken for the automatic operation of the sprinkler systems.

Smoke detector response and/or sprinkler activation response calculations were performed for information purposes only.

FIRE uestion 9 - FIRE SEVERITY FACTORS Fire severity factors were usedin the analysis ofmany fire compartmentsin the fire assessment.

No source is cited, and values were not typicallyspecified fora given scenario.

The severity factors were usedin scenarios where fire suppression was credited.

Since the potential fora large fi8 Is dependent upon fire suppression, there appears to be a significant possibility that the use ofa fire severity factor, when fire suppiessionis explicitlymodeled, fakes double credit forsuppression efforts.

For the scenarios where manual and/or automatic fire suppression and severity factors were credited, please explain why crediting both does not constitute redundant credit for suppression.

Also, provide the bases forall the fire severity factors usedin the study.

Res onse to uestion 9 Fire severity factors have been used in the analysis of compartments where the "event tree"

,approach is used as described in response to question number 7. The factors have been used to define probabilities of:

a. minor and severe fires
b. success and failure of automatic suppression
c. success and failure of manual suppression Minor and severe fires:

A fire in any compartment usually starts by ignition of a single material or component.

The frequency of this occurrence is addressed as the ignition frequency for that specific compartment.

The fire can remain as a "minor" fire which does not require any manual or automatic means of suppression, or the fire can develop into a "severe" fire which does require manual or automatic means of suppression.

Section 6.2.1 of the submittals describe the development of the fire severity factors. The purpose of the severity factors was to segment the ignition frequencies into "minor" and "severe" cases.

In the development of fire severity factors, the adaptation of information from the EPRI fire events database (FEDB) specifically considered that any fire that was suppressed with hose streams or automatic suppression systems be addressed as a severe fire. In other words, the evaluations did not "double count" for those fires in the FEDB where manual suppression was provided by the fire brigade or actuation of the installed systems.

Success and failure of automatic su ression:

As described above, only severe fires are likely to become fullydeveloped fires. There is a chain of ignitions which could lead to fully developed conditions, and depending upon the fire resistance of the compartment boundaries, the fire could spread beyond the compartment.

There is however, a chance (probability) that this chain could break at some stage due to automatic suppression or manual fire fighting before involving the entire compartment.

The automatic suppression, ifavailable in the compartment has a reliability of 95% or a non-suppression probability of 0.05 (

References:

EPRI TR-100370, Reference Table 3 for preaction systems; NSAC-179L). Note that Page 27 of 34

Broxvns Feny Nuclear Plant - IPEEE automatic suppression systems, where taken credit for, are installed to meet NFPA codes and industry standards.

The systems are regularly tested for operability and performance at pre-defined intervals.

Success and failure of manual su ression:

BFN has a dedicated on-site fire brigade.

The fire brigade response time is within five to ten minutes of smoke/fire detection (based on observed fire drill response time). A central fire alarm panel and color graphics monitor is located at the permanently manned fire brigade station. Therefore, there is no time delay due to notification from the control room. The prompt response time of the fire brigade ensures that electrical cabinet fires remain confined to the cabinet (15 minutes - EPRI TR-105928); cable tray fires remain confined to the initial tray (12 minutes - NUREG /CR5384); and exposure fires are extinguished before damagingthe targets in most cases.

Based on demonstrated manual response time and effectiveness, the probability of manual suppression not controlling the fire is conservatively assigned a value of 0.1 (EPRI TR-100370, Section 6.3.6.2).

Factors for non-suppression in the control room are discussed in response to question 2.

FIRE UESTION 10- FIRE PROAGATION SCENARIO IN CONTROL BUILDINGEL 593 FIRE COMPARTMENT 16-1 In the treatment offires in fire compartment 16-1, the effect of CO2 fire suppression systems on the fire scenario frequency did not takeinto account the competition between the time required forsuppression and the time required fordamage or the time required forcontrol room evacuation (see Section 6.2.6in the Unit 2 submittal and Section 6.2.4 in the Unit 3 submittal).

Delaysin suppression may be significant andimportant to determining the scenario outcome.

Please re-examine the fire propagation scenanosin compartment 16-1. Include time-to-damage and time-to-suppress estimates in the evaluation ofthe CDF contribution from this compartment.

Res onse to uestion 10 Manually actuated CO2 systems are installed in each of the three AuxiliaryInstrument Rooms and the two Computer Rooms in fire compartment 16-1 (control building EL 593). These areas primarily house low voltage electrical cabinets.

Automatic addressable smoke detectors (photo-electric) are installed in these rooms and meet the location and placement requirements of NFPA 72. These rooms have a relatively low ceiling height (12'); ceiling is beamed construction type (willtrap smoke and heat); and detectors are located within beam pockets.

Allthese features help early fire detection.

Fire events experience with low voltage (250V or less) electrical fires indicates that these fires are slowly developing.

Electrical cabinets are separated from each other by double walls and have some air gap.

Fire is not expected to spread to an adjacent cabinet for at least 15 minutes (EPRI TR-105928, Appendix H). See Attachment 3 for smoke detector response time for the AuxiliaryInstrument Room. Computer room response time will be similar.

Electrical cabinet peak heat release rate is assumed to be 190 Btu/sec (as suggested in Q-4). However, calculations were also done at lower HRR to conservatively determine the smoke detector response time and also make sure that there will be no smoke stratification.

Page 28 of 34

Broivns Ferry Nuclear Plant - IPEEE The following table depicts the results of the calculation in Attachment 3. Note that in most cases the fire brigade will be at the location well before fire spread to an adjacent cabinet (based on review of fire drills).

Heat Rclcase Rate Btu/sec 50

'100 190 Smoke Detector Activation Time Sec 24 Fire Spread to Adjacent Cabinet Min 15 15 15 Fire Brigade Manual Resyonsc Min 5-10 5-10 5-10 The above analysis shows that the time to detection and the time taken for manual response willlimitthe fire damage to the cabinet of origin. Therefore, the non-suppression probability of 0.1 in the analysis is justified. Control room evacuation is conservatively assumed for all severe fires that are not suppressed by either the manual actuation of the installed CO2 system or by the fire brigade.

This evaluation results in no change in the CDF contribution from this compartment.

FIRE UESTION 11 - BASIS FOR SINGLE STUCK OPEN SRV IN CONTROL ROOM FIRE SCENARIO In the control room fire scenario, two cases were evaluated, each involving a single stuck-open safetylielief valve (SRY). Please provide the basis forselecting the number ofstuck-open SRVs in fire scenarios.

Res onse To uestion 11

[Later]

FIRE UESTION 12 - FIRE PROPAGATION FROM CABLE SPREADING ROOMS TO CONTROL ROOMS In the control building, fires were consideredindividuallyin each ofthree zones. Also, propagationinto the middle zone (16-2) was considered, but not out ofthe middle zone to the overlying and underlying zones. Ofparticularinterestis the scenanoinvolving a fire which originatesin the middle zone, containing the cable spreading room, and propagates to the overiying control room (16-3).

Please evaluate the contribution to the fire CDF from this scenario.

Res onse to uestion 12 Fire compartment 16-2, Cable Spreading Room (CSR) is located in the control building. It interfaces with the control rooms (16-3) above and below with series of rooms including auxiliary instrument rooms, computer rooms, etc. (16-1) and fire areas 17, 18 and 19. CSR is not separated from control rooms by fire rated barriers.

However, as described in the submittal, Page 29 of 34

Browns Ferry Nuclear Plant - IPEEE the CSR ceiling construction provides substantial protection against spread of fire and smoke.

Note that appropriate pressure seals are provided to maintain control room habitability. Cable spreading room presents a deep seated fire hazard scenario and therefore, a quick response and high density sprinkler system was designed for the area (refer to details in response to question 8). The CSR ceiling is of obstructed construction, i.e. construction where beams, trusses, or other members impede heat flowor water distribution in a manner that materially affects the ability of sprinklers to control or suppress a fire. Beams are approximately 30" deep and spaced approximately 8 ft. apart and therefore treated as separate spaces.

Cross members provide additional obstruction forming deep pockets.

The detection and suppression design considered all of these aspects.

Smoke detectors and sprinkler are placed within the beam pockets to provide prompt detection capability and adequate spray pattern.

Additionally, intermediate level sprinklers are installed in the flue space between stacks of cable trays (similar to protection of rack storage occupancies).

Due to congestion of cable trays, two smoke detectors are placed within each beam pocket (37' 8'). Sprinkler are spaced approximately 10'part.

Sprinkler and smoke detectors design meets the NFPA Code requirements.

Based on the above described ceiling construction and detector/sprinkler placement; smoke detector response and sprinkler activation time is calculated in Attachment 5. The HRR is assumed to be a slow growth fire.

The evaluation shows that for slow growing fires, time to reach 300 Btu/sec fire size (design objective to limitthe fire to one or two trays) is 219 seconds, whereas time to detect and activate sprinklers is no more that 50 seconds.

Therefore, it can be concluded that fires in the CSR can be detected and suppressed well before critical conditions are reached.

Even for medium and fast developing fires the time to reach 300 Btu/sec is 164 seconds and 82 seconds respectively and the sprinkler system is expected to control such fires and prevent fires from propagating to the control rooms located above.

FIRE UESTION 13-CONSIDERATION OF FIRES AFFECTING BOTH UNITS Fires that could affect both Units 2 and 3 were not considered.

The submittalindicates that some fire areas contain elements ofboth units. For multi-unitsites, there are threeissues of potentialinterest. Hence, please answer the following:

A firein a shared area might cause a simultaneous trip demand formore than one unit. This may considerably complicate the response ofoperators to the fire event, and may create conflicting demands on plant systems which are shared between units. Please provide the followinginformation regarding thisissue: (1) identify all fire areas that are shared between units and the potentiallyrisk important systemslcomponents foreach unit that are housedin each such area, (2) foreach area identifiedin (1) above, provide an assessment ofthe associated multi-unitfirerisk, (3) forthe special case ofcontrol rooms, assess the likelihood ofa fire or smoke-induced evacuation with subsequent shutdown ofboth units from remote shutdown panels, and (4) provide an assessment ofthe COF contribution ofany such multi-unitscenario.

Page30of 34

Browns Ferry Nuclear Plant - IPEEE Atsome sites, fhe safe shutdown path fora given unif may call fbrcross-connecfs to a sisfer unitin fhe event ofcerfain fin s. Hence, the fire analysis shouldinclude the unavailability offhe cnoss-connected equipment due to oufages at the sister unit (e.g., routine in-service maintenance oufages andlor fhe pofenfial that normally available equipment may be unavailable during extended or refueling outages af fhe sister unit). Please provide the following relevant information regarding thisissue:

(1) indicate whether any fin response safe shutdown procedures call forunit cross-connects, and (2)ifany such cross-connecfs are required, defermine the impact on the fire CDFifthe total unavailability offhe sister unit equipmenf is included in fhe assessment.

Propagation offire, smoke, and suppressants between fin zones containing equipment forone unit to fire zones containing equipment forthe other unit also can result in multi-unitscenarios, Hence, fhe fire assessmenf foreach unit should include analyses ofscenanos addressing propagation ofsmoke, fire and suppressants to and from fire zones containing equipment forthe other unit.

From the information in the submittal, itis nof clearif these types ofscenarios are possible. Please provide an assessment ofthe contnbufion to fhe core damage frequency ofany such mulfi-unitscenarios.

Res onse to Uestion 13

[Later]

FIRE UESTION 14-MISCELLANEOUS ISSUES RELATED TO FIRE AREAS 12 8 13 On page 76 ofbofh submittals, fire areas 12 and 13 (shutdown board rooms F and E) were described as containing Division 1 and 2 essential swifchgear separated by a three to four-foot wide walkway. The Unit 2 submittal describes these as 4 kVshutdown board rooms.

Neifher essential swifchgear nor any 4 kVequipment were notedin the discussion ofthese areas in Sections 5 and 6 ofthe submittals. In fhe Unit 2 submittal, these areas were screened based on fire fiequency alone.

In the Unit 3 submittal, screening ofarea 12 assumed an all-engulfing fire to determine a P2-value of3.07x 10 (Table 5-5). The detailed analysis ofthis same area in Section 6 also assumed an all-engulfing fire scenario. However, the P2-value noted was 2.86 x 10 (Table 6-6). No reason forthis difference was given.

Question 4 above (electrica cabinet heat release rafe assumption) questions the assumptions that heaf release rates willbe small and fhat cabinets willprevent propagation ofthe fire and damage to surrounding equipment. Crediting electrical cabinets with the ability fo contain damage can also be an optimistic assumpfion forhigh-volfage cabinets (480V and higher) since an explosive breakdown ofthe electrical conductors may breach the cabinet and allow fire and damage to spread. For example, swifchgear fires at Yankee-Rowein 1984 and Oconee Unif 1 in 1969 both n.suited in fire damage outside the cubicles.

In fire areas 12 and 13, the adequacy ofseparation ofDivisions 1 and 2 essenfial swifchgear by a three fo four-foot wide walkwayis also questioned.

Page31 of 34

I-

Broivns Ferry Nuclear Plant - IPEEE For fire areas 12 and 13 ofboth units, please review the eguipmentinventory assumedin the fire study forequipment ofthe types discussed above. Please describe any corrections to the equipment list and fire frequency forthese

areas, (i.e., updates ofthe appropriate discussionsin Section 5 ofthe submittals).

For any fire areas 12 or 13 left unscreened, please describe and develop any new scenarios (through to the contribution to the CDF) and update any scenarios already describedin the submittals that result from Section 5 updates.

For any fire areas 12 or 13 left unscreened and containing multiple divisions ofessential switchgear, please demonstrate the importance ofthe assumed confinement by the cabinet offire and damage by dropping the assumption and estimating the effects ofpropagating fire and/or damage on the CDF estimates.

Res onse to uestion 14:

No reference could be found in the Unit 2 submittal indicating fire areas 12 and 13 to be 4kV shutdown board rooms. As shown in the equipment listing for Fire Area 12 on Page 5-14 of the Unit 2 submittal and Page 5-28 of the Unit 3 submittal, shutdown board rooms E and F contain 250VDC and 480VAC switchgear, but do not contain 4kV switchgear.

As noted in the discussion, however, the 250VDC panel in this room supplies control power for 4kV shutdown boards 3EA and 3EC. These switchgears supply loads that are primarily dedicated to Unit 3 loads, such that the impact on Unit 2 operation is less significant than a fire related impact on one of the Unit 2 boards, which are located in shutdown board rooms A, B, C and D, respectively.

In Unit 3 submittal for fire area 12, the difference in P2 value of 3.07E-03 (Table 5-5) and P2 value of 2.86E-04 (Table 6-6) is due to the treatment of 120VAC l&C Bus 3B failure rate. The initial screening failed 120VAC l&C Bus 3B (Top Event DO), whereas, the detailed review considered this as a degraded failure (i.e. used Split Fraction DO3). The Unit 3 submittal (Page 6-49, above Table 6-6) states that "This case is similar to the initial screening evaluation, except that I&C bus 3B is not assumed to fail, only to lose power from sources that are located in this area."

Further discussion of the basis for this change is provided under item (3) on Page 6-47 of the Unit 3 submittal.

Note that 120VAC I&C Bus 3B is not located in this area, only one of its power sources.

For the Unit 2 submittal, these fire areas were screened at the initial level of quantification. This assumes that all equipment in the area is damaged by any fire in the area, which is similar to the "explosive breakdown of the electrical conductors" resulting in damage outside the cubicles case discussed above.

In other words, the "assumed confinement" for this type of fire was not used.

In the case of the Unit 3 evaluation, since the equipment in these rooms are primarily devoted to Unit 3 operation, neither of these areas were screened at the initial level of quantification.

The detailed evaluation of each of these areas is then described in Section 6.2.2 (Fire Area 12) and 6.2.3 (Fire Area 13). Several cases were developed in each of these sections.

The intent Page 32 of 34

Browns Ferry Nuclear Plant - IPEEE was that the worst case would be similar to that shown in Section 5 (i.e. an "engulfing" fire, similar to the "explosive breakdown" case described by the reviewer).

The fraction of fires assigned to this case was 7.3% (i.e. 0.073) of the total fire ignition frequency for the affected area.

The derivation of this factor is described in Section 6.2.1 of the Unit 3 report, which identified 18 of 245 fires for this type of area that were suppressed with hose streams or installed systems (i.e. a non-minor fire).

It should be noted that this evaluation only considers the fire severity factor for this type of area and does not address suppression.

Ifall fires are considered as engulfing, the evaluation of fire areas 12 and 13 for Unit 3 would simplify to:

Fire Area 12: 6.97E-3 x 2.86E-4 = 1.99E-6 Fire Area 13: 6.87E-3 x 2.12E-4 = 1.46E-6 Though neither of these values is below the screening cutoff of 1E-6, both are within a factor of two of the cutoff and neither yet addresses suppression or fire severity. This treatment is judged to be overly conservative.

FIRE UESTION UNI UE TO THE UNIT3 SUBMITTAL In computing the extent offire propagation and equipment damage for a given scenario, itis impoitant that expenmental results not be used out ofcontext, Inappropriate use of experimental results (e.g. employing propagation times or assuming a fire spread geometry specific to a particular cable tray separation to firesinvolving cable trays with different separation) can lead to improper assessments ofscenario importance. The Browns Ferry Unit 3 submittal assumes a fixed fire spread geometry (35 ) forat least one cable tray fire scenario, based on a single test.

The submittal does not provide a basis forexpecting the single experimental observation to be reproduced In the plant fire scenario.

For each fire scenarioin which experimental data were used to estimate the rate and extent of fire propagation, please:

(a) indicateif FIVE(or similar) calculations were performed forthe scenario and provide the results (equipment damaged) ofthese calculations; (b) indicate which experimental results were used and how they were uti%'zed in the analysis; and, (c)justifythe applicability ofthese expenmental results to the scenario being analyzed. The discussion of results applicability should compare the geometries, ignition sources, fuel type and loadings, ventilation characteristics, and compartment characteristics ofthe experimental setup(s) with those ofthe scenario ofinterest.

Res onse To The Fire uestion Uni ue To Unit 3 This scenario will be re-examined neglecting the time delay in fire propagation and limited use of experimental information.

This fire scenario involves a dry type transformer as a fire source, and stack of cable trays as target located approximately 14" above the transformer.

As noted in the submittal, plastic associated with the transformer windings is the only combustible source.

There is no oil in the transformer.

However, it is conservatively assumed that the cable trays willget involved in the transformer fire. The extent of vertical and horizontal fire propagation in cable tray is then Page 33 of 34

Browns Ferry Nuclear Plant - IPEEE determined to calculate the heat release rates.

The FIVE methodology generally assumes that the width of the fire plume is the foot print of the fire source.

Any component within the zone of the fire plume is considered damaged, or in this case ignited. Due to the uncertainty in the timing of fire propagation, it is conservatively assumed that the trays are involved almost immediately and therefore, no timing study is necessary.

It is observed by review of some tests (NUREG/CR 5384) that the area of horizontal propagation spreads outwards at an angle of 35.

This observation was considered in determining the extent of the damage rather than just the foot print of the fire source.

Therefore, the only experimental information used in this scenario is to determine the extent of outward spread of fire. This is conservative based on limited fire potential of the transformer and instantaneous involvement of all four cable trays.

The heat release rate (HRR) calculation remains unchanged.

As shown in the submittal, the HRR calculation is based on guidance provided in the SFPE Handbook.

A simple "zone" fire model (Fastlite 1.1.2 by NIST) was used to run this case.

Fastlite uses a two-zone method to calculate fire growth. Each zone is assumed to have uniform properties such as temperature, heat flux, gas concentration, etc. See Attachment 4 for the results of this calculation. A much smaller floor area was considered in the analysis; the fire was considered unconstrained and the peak HRR of 475 Btu/sec was assumed to occur within 100 seconds.

Note that FIVE methodology cannot be used to predict fire propagation and COMPBRN does not adequately model fire propagation in cable trays.

The results of the calculation show that the upper layer (hot gas) temperatures of 320'F are well below the damage threshold of the cables.

HIGHWINDS FLOODS ANDOTHER EXTERNALEVENTS UESTIONS ON UNITS 1 2 AND3

[Later]

Page34of 34

Browns Ferry Nuclear Plant - IPEEE ATTACHMENTS

A'14LvtENT 1 QUESTION NO. 3 Browns Ferry Plant - IPEEE Alternate Method to Calculate Compartment Temperatures P

OF 2 Compartment Fires

( Pre-flashover Temperatures

)

Pre-flashover temperatures in compartments can be calculated using the method of MQH for naturally ventilated fires:

(SFPE Handbook 2nd Edition, page 3-139, Equation 12) 2

= 6.85 A,~H,h,A, I/3 Where:

Q=

Ao=

Ho=

hk=

AT=

g a heat release rate, kW area of opening, sq. m opening height, m

effective heat transfer coefficient, kW/m.K total area of interior compartment surfaces, sq. m upper gas layer temperature rise above ambient, K Effective Heat Transfer:

Thermal Penetration Time:

k hR for(t > t )

kpc

"'=for(t < t )

t pc x

2 Where:

p = density(kg I m c = SpecificHeat(kS' m *K) 8 = Thickness(m) t = ExposureTime(s) k = ThermalConductivity(kW I m ~ c)

A I

QUESTION NO. 3 Browns Ferxy Plant - IPEEE Alternate Method to Calculate Compartment Temperatures P

OF 2 is;g;,:f,4 lk~(esSig:. iiigjggiiigitgir'gcigi ssi ~zgzi&g'j%Amigi$ yg<%~ n'jiiÃ~sr.'"";h>>for(t> f )

','
,'oncrete(12")

0.305 1800 1.40E-03 2000 0.88 29236 0.005 0.037 1

100 200 300 400 500 600 700 800 900 1000 1100 1200 1300 1400 1500 1600 1700 1800 1.570 0.157 0.111 0.091 0.078 0.070 0.064 0.059 0.055 0.052 0.050 0.047 0.045 0.044 0.042 0.041 0.039 0.038 0.037 j4'jib)!Tlm'epyrzii <$@Concret&pgg 313 317 318 319 319 319 320 320 320 320 320 321 321 321 321 321 321 321 322 105 111 113 114 115 115 116 116 117 117 117 118 118 118 119 119 119 119 119 Compt;"',,'.fern jg.;';.:;;:::,;Cornjt;-'ITemj~!",'!

DATA:

Heat Release Rate (Q), kW AreaofOpening (Ao), m =

Opening Height (Ho), m =

'Total area of surfaces, (A>) m =

Compartment temperature 120 115 5 110

u. 105 E

+

1OO P,058'580N8 Time (sec) 200 25 5

4000

  • Note: Total area of surfaces includes the floor area.

Iffloor area is ignored, the compartment temperature willbe 123 F.

ATTACHMENT2 Drowns Feny Nuclear Plant - IPEEE QUESTION NO. 3 AND 4 FIVEMethod - Impact ofLower HLF and Higher HRR PAGE 1OF 17 Location:

E ui ment Reactor Buildin, Unit 2, EL 565 480V RMOV Board 2C Floor Area 16500

<-User In ut Maximum Ambient Tem erature a

Critical Radial Flux to Target Radiant Fraction of Heat Release Btu/s/ft 100 0.5 0.4

<-User In ut

<-User In ut

<-User In ut Critical Damage Tem erature c

Hei ht from Fire Source to Ceilin, H Fire heat release rate Q

Location factor L

Effective heat release rate (Q,tt)

Critical temperature rise (dT),

Damage Threshold Elevation (Zit)

Radiant Heat Release rate Critical Radial Flux to Distance Btu/sec Btu/sec Btu/s 425 22 190 190 307 8.7 76.0 3.6

<-Userln ut

<-User In ut

<-User In ut

<-User In ut Q*LF Tc Ta T incr Equation 1 8 2 Q,Radiant Frac.

(Equation 5)

Total Heat Qtot to HGL Btu 372000

<-Userln ut Estimated Heat Loss Fraction Calculated Qnet Calculated Enclosure Volume, V Calculated QnetN HGL Temperature Increase Hot Gas Layer Temp. (T>>,)

HL (T t.t~)

Btu Btu/ft 0.70 111600 363000 0.31 18 1'i 8

<-User In ut Qtct (" HLF)

Equation 3 and 4 Ta+HGL Temp incr.

ATTACHMENT2 Browns Ferry Nuclear Plant - IPEEE QUESTION NO. 3 AND 4 FIVE Method - Impact ofLower HLF and Higher HRR PAGE 2OF 17 Location:

E ui ment Reactor Building, Unit 2, EL 565 480V RB Vent Board 2B Floor Area 16500

<<-User In ut Maximum Ambient Tem erature a

100

<<-User In ut Critical Radial Flux to Ta et Radiant Fraction of Heat Release Critical Dama e Tem erature c

Height from Fire Source to Ceilin, H Btu/s/ft 0.5 0.4 425 22

<<-User In ut

<<-User In ut

<<-Userln ut

<<-Userln ut Fire heat release rate Q

Location factor LF Effective heat release rate (Q,<)

Btu/sec Btu/sec 190

<<-User In ut

<<-User In ut 190 Q*LF Critical temperature rise (bT)~

Damage Threshold Elevation (Z;,)

305 8.7 Tc Ta T wncr Equation 1 & 2 Radiant Heat Release rate Critical Radial Flux to Distance Total Heat Qtot to HGL Btu/s Btu 76.0 Q,~Radiant Frac.

3.5 (Equation 5) 408000

<<-User ln ut Estimated Heat Loss Fraction HL 0.70

<<-User In ut Calculated Qnet Calculated Enclosure Volume, V Calculated QnetN Btu Btu/ft 122400 Q)oi (1-HLF) 363000 0.34 HGL Temperature Increase Hot Gas Layer Temp. (T>>i) 20 120 Equation 3 and 4 Ta+HGL Temp incr.

~

ATTACHMENT2 QUESTION NO. 3 AND 4 Browns Ferry Nuclear Plant - IPEEE FIVEMethod - Impact ofLower HLF and Higher HRR PAGE 3 OF 17 Location:

E ui ment Reactor Building, Unit 2, EL 565 250V RMOV Board 2C Floor Area 16500

<-User In ut Maximum Ambient Tem erature a

100

<-User In ut Critical Radial Flux to Ta et Radiant Fraction of Heat Release Critical Dama e Tem erature c

Height from Fire Source to Ceilin, H Fire heat release rate Q

Location factor L

Effective heat release rate (Q,g Critical temperature rise (bT)~

Damage Threshold Elevation (Z,;t)

Radiant Heat Release rate Critical Radial Flux to Distance Btu/s/ft Btu/sec Btu/sec Btu/s 0.5 0.4 425 22 190 190 298 8.8 76.0 3.5

<-Userln ut

<-Userln ut

<-Userln ut

<-User In ut

<-User In ut

<-User In ut Q*LF Tc Ta T incr Equation 1 &2 Q,>Radiant Frac.

(Equation 5)

Total Heat Qtot to HGL Estimated Heat Loss Fraction Calculated Qnet HL Btu Btu 544000 0.70 163200

<-User In ut

<-User In ut Qtot (1-HLF)

Calculated Enclosure Volume, V 363000 Calculated QnetN HGL Temperature Increase Hot Gas Layer Temp.

(T>,l)

(T w~)

Btu/ft 0.45 27 127 Equation 3 and 4 Ta+HGL Temp incr.

ATTACHMENT2 Browns Ferry Nuclear Plant - IPEEE QUESTION NO. 3 AND4 FIVEMethod - Impact ofLower HLF and Higher HRR PAGE 4OF 17 Location:

E ui ment Reactor Building, Unit 2, EL 565 D

ell Torus Com ressor Floor Area 16500

<-User In ut Maximum Ambient Tem erature a

100

<-User In ut Critical Radial Flux to Target Radiant Fraction of Heat Release Btu/s/ft 0.5 0.4

<-User In ut

<-User In ut Critical Damage Tem erature c

425

<-Userln ut Hei ht from Fire Source to Ceilin, H Fire heat release rate Q

Btu/sec 22 450

<-User In ut

<-User In ut Location factor L

Effective heat release rate (Q,~)

Critical temperature rise (bT),~

Damage Threshold Elevation (Zi,)

Radiant Heat Release rate Btu/sec Btu/s 450 318 12.0 180.0

<-User In ut Q*LF Tc Ta-T incr Equation 1 8 2 Q~Radiant Frac.

Total Heat Qtot to HGL Estimated Heat Loss Fraction HL Calculated Qnet Critical Radial Flux to Distance Btu Btu 5.4 145000 0.70 43500 (Equation 5)

<-User In ut

<-User In ut Q(g (1-HLF)

Calculated Enclosure Volume, V Calculated QnetN HGL Temperature Increase Hot Gas Layer Temp. (T)

(Th incr)

Btu/ft F

363000 0.12 107 Equation 3 and 4 Ta+HGL Temp incr.

A%I'ACHMENT2 Browns Ferry Nuclear Plant - IPEEE QUESTION NO. 3 AND 4 FIVE Method - Impact ofLower HLF and Higher HRR PAGE 5 OF 17 Location:

E ui ment Reactor Building, Unit 2, EL 593 480V RMOV Board 2D Floor Area 12800

<-User In ut Maximum Ambient Tem erature a

100

<-User In ut Critical Radial Flux to Ta et Radiant Fraction of Heat Release Critical Dama e Tem erature c

Btu/s/lt 0.5 0.4 425

<-Userln ut

<-Userln ut

<-Userln ut Hei ht from Fire Source to Ceiling, H Fire heat release rate Q

Location factor LF Effective heat release rate (Q,tr)

Critical temperature rise (d T),

Damage Threshold Elevation (Zi,)

Radiant Heat Release rate Critical Radial Flux to Distance Btu/sec Btu/sec Btu/s 22 190 190 295 8.9 76.0 3.5

<-User In ut

<-User In ut

<-User In ut Q*LF Tc Ta T wncr Equation 1 8 2 Q,tt-Radiant Frac.

(Equation 5)

Total Heat Qtot to HGL Estimated Heat Loss Fraction Calculated Qnet HL Btu Btu 462000 0.70 138600

<-User In ut

<-User In ut Qtct (" HLF)

Calculated Enclosure Volume, V 281600 Calculated QnetN HGL Temperature Increase Hot Gas Layer Temp. (T>>i)

(T w~)

Btu/ft 0.49 30 130 Equation 3 and 4 Ta+HGL Temp incr.

t

~

ATI'ACHMENT2 Browns Ferry Nuclear Plant - IPEEE QUESTION NO. 3 AND 4 FIVE Method - Impact ofLower HLF and Higher HRR PAGE 6OF 17 Location:

E ui ment Reactor Buildin, Unit 2, EL 593 Unit 2 Preferred AC Transformer Floor Area Maximum Ambient Tem erature a

Critical Radial Flux to Ta et Btu/s/ft 100 0.5

<-User In ut

<-User In ut 12800

<-User In ut Radiant Fraction of Heat Release 0.4

<-User In ut Critical Dama e Tem erature c

Hei ht from Fire Source to Ceilin, H 425 22

<-User In ut

<-User In ut Fire heat release rate Q

Location factor L

Effective heat release rate (Q,fi)

Critical temperature rise (bT),

Damage Threshold Elevation (Z;t)

Radiant Heat Release rate Btu/sec Btu/sec Btu/s 224

<-User In ut

<-User ln ut 224 Q*LF 307 9.2 Tc Ta-T incr Equation 1 & 2 89.6 Q,>Radiant Frac.

Critical Radial Flux to Distance 3.8 (Equation 5)

Total Heat Qtot to HGL Estimated Heat Loss Fraction Calculated Qnet HL Btu Btu 0.70

<-User In ut 84000 Q(,i (1-HLF) 280000

<-Userln ut Calculated Enclosure Volume, V Calculated QnetN HGL Temperature Increase (T i')

Btu/ft 281600 0.30 18 118 Equation 3 and 4 Ta+HGL Temp incr.

1

~,

ATTACHMENT2 Browns Ferry Nuclear Plant - IPEEE QUESTION NO. 3 AND 4 FIVEMethod - Impact ofLower HLF and Higher HRR PAGE 7OF 17 Location:

E ui ment Reactor Building, Unit 2, EL 593 RBCCW Pum 2A/2B Floor Area 12800

<-User In ut Maximum Ambient Tem erature a

100

<-User In ut Critical Radial Flux to Ta et Radiant Fraction of Heat Release CriticalDama e Tem erature c

Btu/s/ft 0.5 0.4 425

<-User In ut

<-User In ut

<-User In ut Hei ht from Fire Source to Ceiling, H Fire heat release rate Q

Location factor L

Effective heat release rate (Q,<)

Btu/sec Btu/sec 22 30 30

<-Userln ut

<-Userln ut

<-Userln ut Q*LF Critical temperature rise (d,T),<

Damage Threshold Elevation (ZIt)

Radiant Heat Release rate Critical Radial Flux to Distance Btu/s 320 4.0 Tc Ta Th incr Equation 1 8 2 12.0 Q,tr Radiant Frac.

1.4 (Equation 5)

Total Heat Qtot to HGL Estimated Heat Loss Fraction Calculated Qnet HL Btu Btu 0.70

<-Userln ut 22500 Qt(g (1-HLF) 75000

<-Userln ut Calculated Enclosure Volume, V Calculated QnetN HGL Temperature Increase Hot Gas Layer Temp.

(Tg,)

(Th I.Incr)

Btu/ft F

281600 0.08 105 Equation 3 and 4 Ta+HGL Temp Incr.

ATTACHMENI' Browns Ferry Nuclear Plant - IPEEE QUESTION NO. 3 AND4 FIVEMethod - Impact ofLower HLF and Higher HRR PAGE SOF17 Location:

E ui ment Floor Area 9640

<-User In ut Reactor Buildin, Unit 2, EL 621 480V RMOV Board 2E Maximum Ambient Tem erature a

Critical Radial Flux to Ta et Btu/s/ft 100 0.5

<-User In ut

<-Userln ut Radiant Fraction of Heat Release 0.4

<-Userln ut Critical Damage Tem erature c

Hei ht from Fire Source to Ceilin, H Fire heat release rate Q

Location factor L

Effective heat release rate (Q,tr)

Critical temperature rise (bT)~

Damage Threshold Elevation (Zit)

Radiant Heat Release rate Btu/sec Btu/sec Btu/s 425 13 190 760 302 15.2 304.0

<-User In ut

<-User In ut

<-User In ut

<-User In ut Q*LF Tc Ta Th wncr Equation 1 8 2 Q,II.Radiant Frac.

Estimated Heat Loss Fraction HL Calculated Qnet Critical Radial Flux to Distance Total Heat Qtot to HGL Btu Btu 7.0 163000 0.70 48900 (Equation 5)

<-User In ut

<-User In ut Qtot (" HLF)

Calculated Enclosure Volume, V Calculated QnetN HGL Temperature Increase Hot Gas Layer Temp. (T)

(T I-Irw:r)

Btu/ft F

125320 0.39 23

'i23 Equation 3 and 4 Ta+HGL Temp incr.

ATTACHMENT2 Browns Ferry Nuclear Plant - IPEEE QUESTION NO. 3 AND4 FIVEMethod - Impact ofLower HLF and Higher HRR PAGE 9 OF 17 The above fire source willcreate a ceiling jet sublayer extending (damage threshold elevation exceeds the ceiling height) from the source.

Location:

E ui ment Reactor Buildin, Unit 2, EL 621 MG Sets 2DN and 2EA Floor Area 9640

<-User In ut Maximum Ambient Tem erature a

Critical Radial Flux to Ta et Btu/s/ft 100 0.5

<-User In ut

<-User In ut Radiant Fraction of Heat Release 0.4

<-Userln ut Critical Dama e Tem erature c

Height from Fire Source to Ceilin, H Fire heat release rate Q

Radiant Heat Release rate Critical Radial Flux to Distance Total Heat Qtot to HGL Estimated Heat Loss Fraction HL Location factor L

Effective heat release rate (Q~)

Critical temperature rise (dT),

Damage Threshold Elevation (Zlt)

Btu/sec Btu/sec Btu/s Btu 425 13 112 112 284 7.3 44.8 2.7 280000 0.70

<-User In ut

<-Userln ut

<-Userln ut

<-User In ut Q"LF Tc Ta T wncr Equation 1 & 2 Q~Radiant Frac.

(Equation 5)

<-User In ut

<-Userln ut Calculated Qnet Btu 84000 Qig (1-HLF)

Calculated Enclosure Volume, V Calculated QnetN HGL Temperature Increase Hot Gas LaJer Temp (Thgi)

(T I.incr)

Btu/ft F

125320 0.67 41 141 Equation 3 and 4 TatHGL Temp Incr.

ATTACHMENT2 Browns Ferry Nuclear Plant - IPEEE QUESTION NO. 3 AND 4 FIVEMethod - Impact ofLower HLF and Higher HRR PAGE 10 OF 17 Location:

E ui ment Floor Area 4KVPSOV Transformer 9640

<-User In ut Reactor Buildin, Unit 2, EL 621 Maximum Ambient Tem erature a

100

<-Userln ut Critical Radial Flux to Ta et Radiant Fraction of Heat Release CriticalDama e Tem erature c

Btu/s/ft 0.5 0.4 425

<-User In ut

<-User In ut

<-User In ut Height from Fire Source to Ceilin, H 13

<-User In ut Fire heat release rate Q

Location factor L

Effective heat release rate (Q,II)

Critical temperature rise (bT)~

Damage Threshold Elevation (Z;t)

Radiant Heat Release rate Critical Radial Flux to Distance Btu/sec Btu/sec Btu/s 112 224 284 9.7 89.6 3.8

<-User In ut

<-User In ut Q*LF T;T;Th gcr Equation 1 8 2 Q,II Radiant Frac.

(Equation 5)

Total Heat Qtot to HGL Estimated Heat Loss Fraction Calculated Qnet HLF Btu Btu 280000 0.70 84000

<-User In ut

<-User In ut Qtot (" HLF)

Calculated Enclosure Volume, V 125320 Calculated QnetN HGL Temperature Increase Hot Gas Layer Temp. (T>>i)

(Th I.Incr)

Btu/ft 0.67 41 Equation 3 and 4 Ta+HGL Temp Incr.

ATTACHMENT2 Browns Ferry Nuclear Plant - IPEEE QUESTION NO. 3 AND 4 FIVE Method - Impact ofLower HLF and Higher HRR PAGE 11OF 17 Location:

Reactor Buildin, Unit 2, EL 621 E ui ment Floor Area 9640

<-User In ut 2-LPNL-025-0031 Maximum Ambient Tem erature a

Critical Radial Flux to Ta et Btu/s/ft 100 0.5

<-Userln ut

<-User In ut Radiant Fraction of Heat Release 0.4

<-User In ut Critical Dama e Tem erature c

Height from Fire Source to Ceilin, H Fire heat release rate Q

Btu/sec 425 13 190

<-User In ut

<-User In ut

<-User In ut Location factor L

Effective heat release rate (Q,ll)

Critical temperature rise (bT)~

Damage Threshold Elevation (Zit)

Radiant Heat Release rate Critical Radial Flux to Distance Total Heat Qtot to HGL Btu/sec Btu/s Btu 190 225 10.4 76.0 3.5 653000

<-User In ut Q*LF Tc Ta Thgwncr Equation 1 8 2 Q,ll Radiant Frac.

(Equation 5)

<-User In ut Estimated Heat Loss Fraction Calculated Qnet Calculated Enclosure Volume, V Calculated QnetN HGL Temperature Increase Hot Gas Layer Temp. (Th,i)

HL (T

I.incr)

Btu Btu/ft 0.70 195900 125320 1.56 100 200

<-User In ut Qtot (1-HLF)

Equation 3 and 4 Ta+HGL Temp incr.

ATTACHMENT2 Browns Ferry Nuclear Plant - IPEEE QUESTION NO. 3 AND4 FIVEMethod - Impact ofLouver HLF and Higher HRR PAGE 12 OF 17 Location:

E ui ment Floor Area 9640

<-User In ut Reactor Building, Unit 2, EL 621 4KV RPT Boards 2-1 / 2-2 Maximum Ambient Tem erature a

100

<-Userln ut Critical Radial Flux to Target Radiant Fraction of Heat Release Btu/s/It 0.5 0.4

<-User In ut

<-User In ut Critical Dama e Tem erature c

Hei ht from Fire Source to Ceilin, H Fire heat release rate Q

Btu/sec 425 13 190

<<-User In ut

<-User In ut

<-User In ut Location factor L

Effective heat release rate (Q<<)

Critical temperature rise (hT)~

Damage Threshold Elevation (Zlt)

Radiant Heat Release rate Critical Radial Flux to Distance Total Heat Qtot to HGL Btu/sec Btu/s Btu 190 284 9.1 76.0 3.5 280000

<-User In ut Q*LF Tc Ta T wncr Equation 1 &2 Q<<Radiant Frac.

(Equation 5)

<-User In ut Estimated Heat Loss Fraction Calculated Qnet Calculated Enclosure Volume, V Calculated QnetN HGL Temperature Increase Hot Gas Layer Temp.

(Thg~)

HL Btu Btu/ft 0.70 84000 125320 0.67 41 141

<-User In ut Q,c, (1-Hl F)

Equation 3 and 4 Ta+HGL Temp Incr.

ATTACHMENT2 Browns Feny Nuclear Plant - IPEEE QUESTION NO. 3 AND 4 FIVEMethod - Impact ofLower HLF and Higher HRR PAGE 13 OF 17 Location:

E ui ment Floor Area 8600

<-User In ut Reactor Building, Unit 2, EL 639 MG Sets 2DA and 2EN Maximum Ambient Tem erature a

100

<-Userln ut Critical Radial Flux to Ta et Btu/s/ft 0.5

<-User In ut Radiant Fraction of Heat Release CriticalDama e Tem erature c

Hei ht from Fire Source to Ceilin, H Fire heat release rate Q

Location factor L

Btu/sec 0.4 425 18 112

<-Userln ut

<-User In ut

<-User In ut

<-User In ut

<-User In ut Effective heat release rate (Q,<)

Critical temperature rise (dT),

Btu/sec 292 Tc Ta T wncr 112 Q*LF Damage Threshold Elevation (Zi,)

7.2 Equation 1 8 2 Radiant Heat Release rate Critical Radial Flux to Distance Total Heat Qtot to HGL Btu/s Btu 44.8 Q,>Radiant Frac.

2.7 (Equation 5) 280000

<-Userln ut Estimated Heat Loss Fraction HL 0.70

<-User In ut Calculated Qnet Calculated Enclosure Volume, V Calculated QnetN Btu Btu/ft 84000 Qtot (1-HLF) 154800 0.54 HGL Temperature Increase (T w~)

33 133 Equation 3 and 4 Ta+HGL Temp incr.

~ 4

ATTACHMENT2 Browns Feay Nuclear Plant - IPEEE QUESTION NO. 3 AND 4 FIVE Method - Impact ofLower HLF and Higher HRR PAGE 14 OF 17 Location:

E ui ment Reactor Buildin, Unit 2, EL 639 LPNL-25-23 and 24 Floor Area 8600

<-User In ut Maximum Ambient Tem erature a

100

<-User In ut Critical Radial Flux to Ta et Btu/s/ft 0.5

<-User In ut Radiant Fraction of Heat Release 0.4

<-Userln ut CriticalDama e Tem erature c

425

<-Userln ut Hei ht from Fire Source to Ceilin, H Fire heat release rate Q

Location factor L

Effective heat release rate (Q,II)

Critical temperature rise (hT),

Damage Threshold Elevation (Zi,)

Radiant Heat Release rate Btu/sec Btu/sec Btu/s 18 190 190 249 9.8 76.0

<-User In ut

<-User In ut

<-User In ut Q*LF Tc Ta T incr Equation 1 &2 Q~Radiant Frac.

Critical Radial Flux to Distance 3.5 (Equation 5)

Total Heat Qtot to HGL Estimated Heat Loss Fraction Calculated Qnet HL Btu Btu 630000 0.70 189000

<-User In ut

<-User In ut QI~ (1-HLF)

Calculated Enclosure Volume, V 154800 Calculated QnetN HGL Temperature Increase Hot Gas Layer Temp. (T>,i)

(Th I.incr)

Btu/ft 1.22 76 176 Equation 3 and 4 Ta+HGL Temp incr.

ATTACHMENT2 Browns Ferry Nuclear Plant - IPEEE QUESTION NO. 3 AND 4 FIVE Method - Impact ofLoNer HLF and Higher HRR PAGE 15 OF 17 Location:

E ui ment Reactor Building, Unit 2, Ei 639 240V Li hting Board 2B Floor Area 8600

<-User In ut Maximum Ambient Tem erature a

100

<-User In ut Critical Radial Flux to Ta et Btu/s/ft 0.5

<-User In ut Radiant Fraction of Heat Release Critical Dama e Tem erature c

Hei ht from Fire Source to Ceiling, H Fire heat release rate Q

Btu/sec 0.4 425 18 190

<-User In ut

<-User In ut

<-User In ut

<-User In ut Location factor LF Effective heat release rate (Q,<)

Critical temperature rise (ET),nt Damage Threshold Elevation (Z)

Radiant Heat Release rate Critical Radial Flux to Distance Total Heat Qtot to HGL Btu/sec Btu/s Btu 190 312 8.6 76.0 3.5 112000

<-User In ut Q*LF Tc Ta T wncr Equation 1 8 2 Q,>Radiant Frac.

(Equation 5)

<-User In ut Estimated Heat Loss Fraction Calculated Qnet Calculated Enclosure Volume, V Calculated QnetN HGL Temperature Increase Hot Gas Layer Temp.

(Th,~)

HL (T w~)

Btu Btu/ft F

0.70 33600 154800 0.22 13 113

<-User In ut Q)g (1-HLF)

Equation 3 and 4 Ta+HGL Temp fncr.

ATTACHMENT2 Browns Feny Nuclear Plant - IPEEE QUESTION NO. 3 AND4 FIVEMethod - Impact ofLower HLF and Higher HRR PAGE 16 OF 17 Location:

E ui ment Reactor Buildin, Unit 2, EL 639 SLC Pum s A and B oil Floor Area Maximum Ambient Tem erature a

Critical Radial Flux to Ta et Btu/s/ft 8600 100 0.5

<-User In ut

<-User In ut

<-User In ut Radiant Fraction of Heat Release 0.4

<-Userln ut CriticalDama e Tem erature c

Hei ht from Fire Source to Ceiling, H Fire heat release rate Q

Btu/sec 425 450

<-User In ut

<-User In ut

<-User In ut Location factor L

Critical Radial Flux to Distance Total Heat Qtot to HGL Estimated Heat Loss Fraction HL Calculated Qnet Effective heat release rate (Q,)

Critical temperature rise (d,T)~

Damage Threshold Elevation (Zit)

Radiant Heat Release rate Btu/sec Btu/s Btu Btu 1

<-Userln ut 450 Q*LF 292 Tc Ta T

'fgllcr 0.70

<-User In ut 84000 Qig (1-HLF) 12.6 Equation 1 & 2 180.0 Q,>Radiant Frac.

5.4 (Equation 5) 280000

<-User In ut Calculated Enclosure Volume, V Calculated QnetN HGL Temperature Increase Hot Gas Layer Temp. (Th,i)

Btu/ft 154800 0.54 33 133 Equation 3 and 4 Ta+HGL Temp incr.

ATTACHMENT2 Browns Feay Nuclear Plant - IPEEE QUESTION NO. 3 AND4 FIVEMethod - Impact ofLower HLF and Higher HRR PAGE 17 OF 17 REFERENCED E UATIONS g

(btu I sec) 6T( F) 340 t argel Zcrit = 33 crit Q=pTgp'=Q071"'Q24*560*v=99K...................(4)

ATTACHMENT3 QUESTION NO. 10 PAGE 1 OF 1 Browns Ferry Nuclear Plant - IPEEE Time to Detection Manual Suppression, Time to Damage SMOKE DETECTOR ACTIVATIONAND SMOKE STRATIFICATION The upward movement of the smoke in the plume is dependent on the smoke being buoyant relative to the surroundings.

Given the physical configuration (fire sources and detector location), following correlations can be used to determine the time to detector actuation and smoke stratification possibility.

References:

1. NFPA 72, Fire Alarm and Detection System.
2. NFPA 92 B, Smoke Management Systems.
3. Fire technology, Aug 1990, Smoke management of Covered MaIls and Atria.
4. Fire technology, May 1991, Letters to editor Ceilin Mounted Smoke Detector Res onse For radius-to-ceiling height ratios less than approximately 0.6, the temperature rise of the smoke can be estimated as function of time based on theoretical generalizations of the limited amount of experimental data.

For X < 100:

X=

where:

X=

Y=

4.6*10 Y

+ 2.7*10'M tQ1/3 / H4/3 DTH

/Q and where:

t = time from ignition (sec)

Q = heat release rate (steady fire) (Btu/sec)

H = ceiling height above fire surface (ft)

DT = Temperature rise of gasses within ceiling jet ( F)

Stratification of Smoke Assuming the ambient temperature increases linearly with increasing elevation, the maximum rise of of the plume is dependent on the convective portion of the heat release rate of the fire and temperature change from floorto ceiling.

Hrnax = 74Qc DTo where:

Q, = Convective portion of the heat release rate (Btu/sec) (approximately 70% of total heat release rate)

DTii = difference between ambient temp. at ceiling and ambient temp. at the level of fire surface ('F)

~Descri tion:

Height (H):

Temperature rise within ceiling jet (DT) (Temp. rise required for smoke detector activation):

Heat release rate (Q):

Difference between ambient temp. at ceiling and ambient temp. at the level of fire surface (DTo):

Convective heat release rate (Qg (Q*0.7):

Data 12 18 50 30 35 Y=

83.42 X=

3.20 Activation time for smoke detector (t) =

24 Seconds Maximum Smoke Height (H,) =

40 Feet (Activation time IQ=100 Btu/s is 8 sec; 1190 Btu/s is 3 sec)

Fire Brigade manual Response

=

5 to 10 Minutes (Based on Fire Drills)

Fire Damage to Adjacent Cabinet =

15 Minutes (Based on Industry Tests)

P

ATTACHMENT4 QUESTION SPECIFIC TO UNIT3.

Brosvns Ferry Nuclear Plant - IPEEE Stacked Cable Tray Fire Scenario (Fastlite 1.1.2)

Reactor Building, Unit 3, 2/621 4KV-480V Transformer 0-FXA-266-OTHB PAGE 1 OF 1

<I'<>.>>>'~:i'>><'k '.>'

>>N>>.'>>1>'> <:h'~.'<>

lw'<'><.'>>'.<.">..>1>:P;>'. ><.'>"."1>":wr>~'"<>,

',:'., @%>':>k>a'>.:>'~" ~5."'>"<,>'.".:.>":>.">>>:>":>'.>1;.'>>: R@>'."a..<:: '">>~%kS>>>Ni >:<>>r%

@48>I<'>'X(MB~~(>";>'>'PK~~N>i>i>~'.o'.'g'N'>b~HRR4~gNNÃ<@43>i<~ wV,Nf>4A er>T<,err(

!><><>!>%<Pa?',it>:;<N Floor Area 625 ft

!I.~!.'5%((seetl%~":4"~ '::i~~ ':iY"k%~85'Vs':N(%'kCÃNiV i@4i8<4Ãb%k".p.:,':."~kkN@NÃ4~~$$<i~<."'"""4<:

Height Horiz. 0 enin s Vert. 0 enin s Peak HRR 15 ft 5'Wx5'H None 475 Btu/s Heat of Combustion 20000 Btu/Ib Unconstrained Fire 0

100 200 300 400 500 600 700 800 900 1000 1700 0

475 475 475 475 475 475 475 475 475 475 475 100 216 285 294 298 300 302 304 306 308 310 320 Upper Layer Temperature NJ45'N>>'<.",<

8 >.gc I '<zwi< >;I(<;Fi>.",>

250 I

200

~~ 150 0

g<!54 $5<."".8

'j(pp>i@ pi+i'j i;,)io'j>'!','@gag

)t>j~>.'i!~ Ir>N>,',',j t$

@:IR>)

>~+8..,<.',"<ter..'. 1

.;.'<~$5'/ PS(qN

,"sxq0

(<<zgi~ 'gR@

s>4$ PPkNI:!is(k i<ZgYt':: rgj'j.:,i0 '.!!N!jw

.4%'A. 'tie%<:P>:Sk' 100 200 300 400 500 600 700 800 900 1000 1100 1200 1300 1400 1500 1600 1700 Time (Sec)

Heat Release Rate 200

<,:ggQ MNj;.'<'i $p';.

Y,

)gp>IP<:&~gzrx.';>;.'j(>',

igyyz;x;<>.rp:g.<yy:

<kj',;:::, Fg>(im 0~x"';~i;INN'ji>ig g@gg tr;j;,'<g: PA>+

~mg i)>jj~j: ~j,:"j$ji!

g<',pN):.'<,:g)/~i g//<'Yj><r,'P t.;

0 100 200 300 4$

500 600 700 800 900 1000 1100 1200 1300 1400 1500 1600 1700 Time (sec)

PAGE I OF2 A%I'ACHMENT5 Browns Ferry Nuclear Plant - IPEEE QUESTION NO. 12 Assessment of CSR Fire Protection Features in Meeting Design Objectives CABLE SPREADING ROOM FIRE PROPAGATION ANALYSIS A fire in the CSR is expected to be s/ow growing at least initially, and ifnot controlled may become medium or fast growing fire. It is intended to detect and suppress the fire while still in the slow growth phase.

A slow growth fire is defined as a fire which takes 400 or more seconds from the time established burning takes place until the fire reaches a HRR of 1000 Btu/sec.

Ifthe fire has to be limited to a maximum of 300 Btu/s (design objective); i.e the fire may have caused limited damage to one or two cable trays, the time to detection and suppression can be evaluated.

The following calculation evaluates ifthe design objective is met by the installed fire suppression and detection systems:

In ut Parameters metric units Ceiling Hei ht m AmbientTem

. C Growth Time s HRR K Power Law" "

HRR K Radial distance to Detector r

m Radial distance to S rinkler r m

Hei ht of Ceilin Above Fire H m

3.1 20 400 1055 315 3.4 1.54 2.47 10.0 ft (slow fire)

(1 000 Btu/sec reached in 400 sec)

(Design objective to limitfire size to 300 Btu/sec) 11.0 ft 5.0 ft 8.0 ft Slow Fire Intensit Coefficient Q(kF) = o/(k8'I s )t~(s)........ Equation 1 0.0066 kW/s Time to Reach 315 kW 300 Btu/sec t(sec) =

......E...q..u.a..t.ion2

~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~

~

G t(sec) =

219 Sec La Time Associated with Fire Detection The total lag time (Lagpi

+ Lag~(('

I t) can be calculated as follows:

(Mowrer, F.W.,"Lag times associated with suppression and detection", Fire Technology, Vol 26, No 3, 1990)

(1.4r + 0.2H)

(0.028aH)'"

t(sec)

=

24 Sec

ATTACHMENT5 QUESTION NO. 12 Browns Ferry Nuclear Plant - IPEEE Assessment ofCSR Fire Protection Features in Meeting Design Objectives PAGE 2OF2 Time to Detection (English Units)

(See Attachment 4 for References and associated information)

~Descri tion:

Height (H):

Temperature rise within ceiling jet (DT) (Temp. rise required for smoke detector activation):

Meat release rate (Q):

Convective heat release rate (Qg (Q*0.7):

Data 10 18 300 210 Y=

18.64 X=

0.16 Activation time for smoke detector (t) =

1 Seconds Time for S rinkler Activation Length (radial distance) of sprinkler from fire source centerline (L) ft.

Width (Distance between beams) (W) ft.

Distance from fire source to ceiling (H) ft Detector (sprinkler) actuation temperature (Td) ( F)

Time Constant (TC) seconds (Ref: Table A-6E, EPRI FIVE Document for Quick Response)

Heat release rate (Q) Btu/sec (design Objective) t Plume temperature rise ('F)

(Equation 2)

Ceiling Jet temperature rise factor at sprinkler (Ref: Table 6A/6B EPRI FIVE Document)

Ambient Temperature

( F)

Temperature rise at target ('F)

Temperature at target ( F)

Data 5

8 8

165 30 300 476 0.4 100 190 290 t~= ln Z

1 (Td Ta)

(Tg Ta)

.............. Equationl g (btu/sec) b T('F) =340>>

Equa..t.i.o..>>..2...

.(/i)

(dimensionless actuation time, Equation 1) 0.42 Estimated time for sprinkler actuation (td)

(seconds) 13 Conclusion The above evaluation shows that for slow growing fires, time to reach 300 Btu/sec fire size is 219 seconds, whereas t

time to detect and activate sprinklers is no more that 50 seconds.

Therefore, it can be concluded that fires in the CSR can be detected and suppressed well before critical conditions are reached.

Even for medium (300 sec) and fast (150 sec) developing fires the time to reach 300 Btu/sec is 164 seconds and 82 seconds.

The sprinkler system is expected to control such fires.