ML17300A618
| ML17300A618 | |
| Person / Time | |
|---|---|
| Site: | Palo Verde |
| Issue date: | 10/31/1986 |
| From: | ARIZONA PUBLIC SERVICE CO. (FORMERLY ARIZONA NUCLEAR |
| To: | |
| Shared Package | |
| ML17300A617 | List: |
| References | |
| TAC-60773, NUDOCS 8611050421 | |
| Download: ML17300A618 (42) | |
Text
DESCRIPTION OF PROPOSED ENHANCEMENTS TO THE PVNGS CONTROL BUILDING ELEVATION 74'-0" MASONRY WALLS FOR THE ARIZONA NUCLEAR POWER PROJECT PALO VERDE NUCLEAR GENERATING STATION UNITS 1, 2
AND 3 OCTOBER 1986 I
8611050421 861031 PDR
- DOCK 05000528 P
PDR'
r
TABLE OF CONTENTS l.
INTRODUCTION 2.
SUMMARY
AND CONCLUSIONS 3.
DESCRIPTION OF ENHANCEMENTS 4.
DESIGN AND ANALYSIS A.
Methodology and Assumptions B.
Summary of Results 5.
REFERENCES TABIES 1.
Parameters Used in the Design and Analysis of Masonry Wall Enhancements 2.
Lower Bound First Mode Frequencies of Modified Masonry Walls 3.
Stress Summary for Modified Masonry Walls FIGURES 1.
Masonry Wall Modification's Control Building Plan Elev. 74'-0" 2.
Masonry Wall Modifications Typical Elevation and Details 3.
North Panel Finite Element Model 4.
Center Panel Finite Element Model 5.
South Panel Finite Element Model 6.
Control Building Response
- Spectrum, O.lg OBE 7.
Control Building Response
- Spectrum, 0.2g SSE 1060K/0037K
P l'I
DESCRIPTION OF PROPOSED ENHANCEMENTS TO THE PVNGS CONTROL BUILDING ELEVATION 74'-0" MASONRY WALLS l.
INTRODUCTION In response to an NRC requirement.
'o strengthen the PVNGS Control
. (1)
Building masonry walls at Elevation 74'-0",
a wall upgrade has been designed using conservative analysis techniques and assumptions.
I'he modifications consist of a
series of vertical steel
'plates that sandwich the wall and are bolted together to form a composite section.
The modifications assure that wall
- masonry, reinforcement, and bond stresses will remain within conservative allowable limits under both OBE and SSE conditions.
The analysis and design basis for the modification, as well as the resulting
- stresses, are described in the following sections.
2 ~
SUMMARY
AND CONCLUSIONS The modification of the Control Building Elevation 74'-0" masonry walls consists of the addition of a series of steel plate assemblies that both strengthen and stiffen each of the three wall segments.
Each plate assembly consists of a pair of vertical steel plates, one on each side of the wall, connected by pretensioned through bolts (see Figures 1 and 2).
Plate length and spacing considers the location of existing penetrations, attachments and location of maximum out-of-plane bending.
Torquing of the through bolts provides a friction connection between the plate and masonry surfaces that permits the transfer of shear forces resulting from out-of-plane bending.
In developing the, design, anticipated methods of implementation and otential impact to existing safety related components and equipment were P
~I taken into account.
These considerations resulted in the sandwich plate" design which provides for ease of installation.
The modification design was based on finite element model analysis to determine the response of the walls.
The steel plates increase the stiffness of the walls thus increasing the wall frequency to a
range outside the peak spectral acceleration.
This results in all stresses remaining below NRC established allowables.
These enhancements will serve to strengthen the walls and increase the existing design margins.
~
5 gR g
III F
v Ih e
~
II E
~
~
3.
DESCRIPTION OF MODIFICATIONS The purpose of the modifications of the masonry walls at Elevation 74'-0" of the Control Building is to strengthen the wall and increase wall design margin for seismic loading conditions.
This has been achieved by developing a
modification that stiffens the
- walls, thereby reducing seismic response and limiting deflection and cracking.
The subject walls are located at Elevation 74'-0" of the Control Building, oriented along the north-south center line and separate the two essential air handling rooms (see Figure 1).
The walls are non-shear, non-load bearing partitions subject to vertical and lateral seismic inertial loads due to their own weight and the weight of light attachments (instrumentation tubing, conduit, junction boxes, etc.).
The wall modification consists of a
series of vertical steel plate assemblies connected to the wall by through bolts (see Figures 1 and 2).
Each assembly consists of two plates located on opposing sides of the wall and connected by pretensioned threaded rods (through bolts) that clamp the plates together.
The plate assemblies become an integral part of the wall, permitting composite
- action, when the through bolts are torqued allowing the transfer of shear stresses resulting from out-of-plane bending.
The plates vary in length from approximately 8 to 17 feet long, are centered at approximately the midheight of the wall, and are spaced approximately 3 to 6 feet apart horizontally.
The spacing and length of the plate assemblies are varied in order to avoid existing penetrations and minimize the relocation of existing wall attachments.
To preclude inadvertent cutting of main vertical reinforcement, the through bolts are installed only through the center webs of the masonry units.
In order to minimize potential impacts on the plant and to assure the safe implementation of these modifications, the design and construction of the modifications has been optimized to include the following considerations:
Manageable size pieces of steel plates for easier installation.
20 Flexibility in placement of the steel plates to accommodate physical restrictions caused by existing components and, therefore, minimizing relocations.
Q Bolted construction utilizing the least amount of bolts required, thereby minimizing drilling operations, and minimizing in~lant welding.
b t
(
4.
DESIGN AND ANALYSIS A.
Methodolo and Assum tions The masonry wall modification is designed as a
composite section consisting of reinforced masonry and steel plates.
The plate assemblies are located to stiffen and strengthen the critical sections of each wall to reduce stresses under seismic conditions.
The plate assemblies and wall were analyzed by use of a finite element model of each of the three walls, using response spectra techniques.
The design spectra used were developed from the published floor response spectra by scaling to O.lg for OBE and 0.2g for SSE and enveloping the response at elevations 74'-0" and 100'-0".
A two-dimensional finite element model was utilized in order to accurately represent the stiffening plates in their actual locations and thus take into account variations in plate length and spacing.
The 22 foot high by 27 foot long wall segments were modeled using plate elements 12 inches thick, 16 inches wide, and 8
or 16 inches high.
The models include all ma)or penetrations and door openings (see Pigures 3,
4, and 5).
The steel plate assemblies were modeled by calculating the stiffness of the transformed steel/masonry section and appropriately increasing element stiffness in the areas corresponding to the plate assembly locations.'he boundary conditions of the wall models were chosen to reflect the as-built connection details.
Wall mass includes the dead weight of the wall, plate assemblies, and attachments.
The plate element properties used in the response spectrum analysis represented either fully cracked or uncracked
- sections, depending on the level of applied moment.
Each analysis was initiated by assuming all masonry elements were uncracked and had the stiffness of the gross section.
When resulting moments were determined to cause cracking in a masonry element, the properties of that element were changed to represent a fully cracked section (i.e.,
masonry cracked to neutral axis, tension carried by reinforcement and where applicable steel plate).
This iterative process was repeated until an equilibrium condition was reached.
The moment required to crack an element was calculated based on the 1985 Uniform Building Code (UBC) modulus of rupture value for masonry (fr) of 97 psi.
In addition to simplyfing the analysis, the use of only uncracked and fully cracked elements yielded conservative
- results, since the increased tensile capacity of the grout and the stiffness of partially cracked sections were not considered (i.e.,
no 3-stage behavior was assumed).
Because dowel placement was confirmed by documented inspection during construction, as-designed "d" values were used for doweled elements.
Por all remaining elements the cracked stiffness was
~
I U
1 E
'au
- e "1
determined using the average as-built "d" distance values obtained from PVNGS Non-Conformance Report CJ-5343.
The minimum expected PVNGS masonry compressive
- stress, (f'm), is 2000 psi.
However, for stress calculationsy the conservative value of f'm 1500 psi was used per UBC-79.
For modulus of elasticity, the American Concrete Institute (ACI) 531-79 Code and UBC-79 specify a
value of 1000 f'm.
Utilizing the expected masonry compressive
- strength, the modulus of elasticity value, E,
would be 2.0 x
106 psi.
However, it is known that the code equation may be unconservative and therefore to address NRC concerns<
)
an E
value of 1.5 x
10 was
- used, 6
which is 750 x f'm considering the expected f'm value.
See Table 1 for ma)or design and analysis parameters.
The methodology and assumptions used conform to the requirements of the PVNGS Final Safety Analysis Report (FSAR),
Section 3.7 and Bechtel Topical Report BC-TOP-4A, "Seismic Analysis of Structures and Equipment for Nuclear Power Plants" (referenced in FSAR Sections 1.6, 3.7 and 3.8).
The seismic response for each wall segment was calculated for O.lg
- OBE, 4X damping, and 0.2g
- SSE, 7X damping conditions.
Utilizing the maximum moment obtained from the response spectra
- analysis, stresses in each of the wall components (e.g.,
- masonry, reinforcement and.steel plates) were calculated following working stress design methods.
Summa of Results The seismic response of each wall is primarily dependent on the first mode (fundamental) frequency.
The calculated first mode frequency for each wall segment, for both OBE and SSE conditions, is listed in Table 2.
The amplified regions for the horizontal OBE and SSE wall specific (east~est direction, envelope of elevation 74'-0" and 100'-0") response spectra occur at frequencies less than about 6 Hz.
By comparison of this value to the modified wall first mode frequencies contained in Table 2, it can be seen that the wall frequencies are higher than the frequency at which the amplified region begins.
The calculated frequencies, as given in Table 2,
are shown on Figures 6
and 7 together with the wall specific spectra and the spectra used in the modification design.
Since conservative assumptions are made regarding the parameters which determine the frequencies (moment of inertia, modulus of rupture, and modulus of elasticity),
the calculated frequencies are considered to be lower bound estimates.
Variations that could be expected in these parameters will increase the wall frequencies, away from the
k'I
(
W
~
~
1 h
amplified region of the
- spectra, thus resulting in further reduction of wall accelerations.
The conservatisms associated with wall frequencies and the margin between the wall specific spectra and design spectra provide assurance'hat upper bound loads have been utilized to design the wall modifications.
Therefore, these modifications would significantly increase the existing seismic design margin of the walls.
The maximum calculated
- masonry, reinforcement,
- bond, and steel plate stresses for all walls are summari'zed in Table 3 for both OBE and SSE conditions.
For comparison
- purposes, the corresponding allowable stresses are also listed.
The allowable stresses are based on f'm 1500 psi.'llowable masonry and reinforcement stresses are in accordance with ACI 531-79 and the provisions of Appendix A to SRP 3.8.4 (NUREG 0800, July 1981).
To compensate for possible variations due to the absence of full in-process inspection, applicable allowable stresses have been reduced per ACI 531-79 guidelines.
Allowable bond stresses conform to ACI 531-79 requirements and the recommendations of the NRC (1.5 increase factor for SSE conditions).
The American Institute of Steel Construction (AISC) Steel Construction
- Manual, 8th Edition and the provisions of PVNGS
- FSAR, Section 3.8 are the sources for the allowable stress values for the steel reinforcing plates.
In determining plate allowable compression
- stresses, the slenderness effects are taken into account.
As can be seen from Table 3, all calculated stresses are within the prescribed allowable
Therefore, it is concluded that the Control Building masonry walls at elevation 74'-0",
modified as described herein, will provide additional margin and meet NRC acceptance criteria and will perform their intended function under postulated seismic conditions.
5.
REFERENCES (1)
Letter from E.
A. Licitra,
- NRC, to E.
E.
Van Brunt, Jr.,
- ANPP, Dated October 6, 1986.
Subject:
Palo Verde Masonry Walls
l Cl C 4
TABLE 1 Major Parameters Used in the Design and Analysis of Masonry Wall Enhancements Parameter Element size Element stiffness 16" x 16" x 12" (some 16" x 8" x 12")
Uncracked (gross) section or fully cracked section Boundary conditions Reflect as-built connection configuration Masonry compressive
- strength, f'm Masonry modulus of elasticity, Em 2000 psi, expected 1500 psi, for stress calculations 1.5 x 106 psi Masonry modulus of rupture, f'm Rebar yield strength Rebar location 97 psi 60,000 psi Main reinforcement:
as-built "d" Dowel reinforcement:
as-designed "d"
Steel plates Through bolts
Response
spectra 1/2" and 3/4" thick, ASTM A36 5/8" and 7/8" diameter, ASTM A36 or A307 Published floor response spectra (scaled to O.lg OBE and 0.2g SSE,)
enveloped for elevation 74'nd 100'asonry stress allowables Steel plate allowables Per AC1 531-79 and SRP 3.8.4 (NUREG-0800)
Per AISC, 8th Edition
Jg (
I
TABLE 1 Ma)or Parameters Used in the Design and Analysis of Masonry Wall Enhancements Parameter Descri tion Element size Element stiffnes 16" x 16" x 12" (some 16" x 8" x 12")
Uncracked (gross) section or fully cracked section Boundary conditions Reflect as-built connection configuration Masonry compressive
- strength, f'm Masonry modulus of elasticity, Em 2000 psi, expected 1500 psi, for stress calculations 1.5 x 106 psi Masonry modulus of rupture, f'm Rebar yield strength Rebar location 97 psi 60,000 psi Main reinforcement:
as-built "d" Dowel reinforcement:
as-designed "d"
Steel plates Through bolts
Response
spectra 1/2" and 3/4" thick, ASTM A36 5/8" and 7/8" diameter, ASTM A36 or A307 Published floor response spectra (scaled to O.lg OBE and 0.2g SSE,)
enveloped for elevation 74'nd 100'asonry stress allowables Steel plate allowables Per ACl 531-79 and SRP 3.8.4 (NUREG-0800)
Per AISC, 8th Edition
TABLE 2 LOWER BOUND FIRST MODE FREQUENCIES OF MODIFIED MASONRY WALLS WALL LOCATION FREQUENCY (Hz)
SSE OBE North Center South 8.4 9.8 9.2 7.3 8.6 8.9
I
. ~
H I
)
y/~
I I
H T
h II W
f 4
Il II
'j I
t
TABLE 3 STRESS
SUMMARY
FOR MODIFIED MASONRY WALLS 0.1 OBE STRESS
( si) 0.2 SSE COMPONENT Masonry Com ression Reinforcement Tension Reinforcement.
Bond IPlate I Com ression I
ITension MAXIMUM CALCULATED 330 119200 95 1,850 2 630 1
120 I
165 2
10,000 I
2 870 2
22 000 I
3 850 MAXIMUM ALLOWABLE CALCULATED 1) 333 I
660 (1
24,000 I
21,100 I
ALLOWABLE1I 833 I
1I 48,ooo I
I 3
I 180 I
2 I
16,OOO fl 2
I 35 000 I
(1)
(2)
(3)
Allowable stresses based on ACI 531-79 and Appendix A to SRP 3.8.4.
Allowable stresses based on AISC Steel Construction
- Manual, 8th Edition.
Allowable stress increased using NRC recommended value of 1.5.
\\
I O
'C 0
I 4
I I
J 1I
'~
~PLATE w/DOLT
~ uAsoeez tvWsc Clod ru) 5TEEL COLUMN MA5'OH'VALf (CEAI7ER)
REINFORCED CQWRETE
)/PI L MA5DPlRYPVj4J.L
- (~ours)
FIGURE 1:
MASONRY PALL MODIFICATIONS CONTROL BUILDINC PLAN ELEV. 74'-0"
I ri RIICC r
rr e
~ ~
0 r
J rr
~! Ql~~
~~I I~~
M% &M
==:Qi~~
WR HW WMl le WQ %W
~~iH)~~
rr
~
g
~
~ l I
I
~
~
go CS'/,'r-a~a tJ g+r 26'g go(/)
v'/~
Q9)//
w el/
55 5
gW t
tgo7 t/9'27 l~
~if
ZSZ g(5//
'/97 ltd Wo C/O t0 5/5 o
(ao u~/,
IXX'l
/ss
/.
.2/$
ZtS 5&
'2'/)/
Ci.
'ZJC xX' t7/t.
O'S 7''z
/19 izci /e/,
or/t/
2/7
/dP.
'g/7 Zo/
Z/9 cl~
ZttZj
'2(/4 t/j.
Zt5J Ol
)f
'27/
2(7 tp
/93.
~/!
//SP Cr/
Cef
'gJ 7
/do ggyJ VC2
/dS
/d9.
/7O
/7/
/)/o /~
/g/
y $/7 rc t/t/7, ye/
Q ///
cg Azg) tp
/SO
/S/
/J2 t7
//
vip
//~ ot g/
//1
//o
/t//
/tt i/Og
/g%
/
o' V>C
/07/
~ (pi) 7 tdP t~t
.7O.
7/
!fe t/~
72 rc j ft/
'73
'P7 C't
/ttZ t//C
//7
,(/2
~z~:
5/
tAq t/"/ ~
)
~'C
~
,z+e, t/9 l 2/
i' AC I=I5URE 3: NORTH PANEL I=DVITE ELEMENT MODEL
~P Z99 'cco pt3/t
'I v.
r P/3
- 3/9/
ZCt/
ZoZ 297 277 3'op 3ctF
- 3/o sg 2ee C
tsc
<9l gp/
P2 rt 26o 2eo 229 29o
'2)P
~p~,'c$
2zc'~~
II tti.
r 7/
272 ZCP l 2C$
'c'3 255/
2r4 267 gr) !
I 273 27>
2+tt3 a<<4>>.
Ct'e JOO JOI IW Wc
'ag cr tfo c
acr ZZ7 KP I
l/O>>
t~i
/
V 2JJ ZJf p
Zzc 2Jo 237 PZC Zc 5
<<J Q
,ZZ$
Co<<
</
'l
~>> 2//
~
'2/J ttt~
~~
rtS Z/7 2/r 2/9
'5-.
zoo 2//
>/t/
2/or sp.
2C<<
'Cj
<< ~
r
~
Cro 3/3'OC<<
2O/
gb V~
I
/5= /f/
car VV
//C'/
og o
Ca Vf
/75~
ft~ ~
P-a
/7Cl
/7/7 tnt Qa Pe, jsj giC
/P/l,I@st )
/P7 a~
i'35,. /go /o/
C.a rt
/QC tW (o..
a/CX
't~
y
<<g
/)r /
l/o.
ISZ /
Iat v'
ICC/I a'I
/J/
. - 2
/-"..
~\\
(a.
!tr ~
/Jp
/t,
/ro 1I 5
/<<>>t
~j.
R
//3
.I/O/
I/3 Jrt Jrv tt s't
/. l ~'/)
4
~
Jtr I V 57 5P 97
/<<rQ
/CC/! /Or
/Ct
'o a
p=
p(
Z) eS a Pr) 7t
>7 7P
/5 7Ca PT t;
o ey'!
tt
<<a
~
6..'6 C
P n('o 65 1
a/$
tVt'f
<<I
~
137) JP J5 I
~
'=o I
~
~
k.
Pg 3Co
. 3/
2P 3Z 5 -! /r:
lt'I
/r
/C 5
<<o 7
I g
t V
C lt
!r lt IO It 0
I 293 29/r tt')f 2)cr 2'~/
2S'~
1 235 ta to~
I'.r r>> 7 I/7.
CC Fgg 7':
3~3-! Jc.
//
!1
~
t 1
PC lf/7
>> 7/>>
/<<+o/
>>4
+/+~ 4/
<<7>>
P7 arv
/!
!Jg C.'~
i Xr
~r r i /
'A4< J JC'r
<~.-
PJ7 CJC+
/de
./c 7
/7.
/7/
/7>>,
v4.
/C ~
~!/>>
r/4
~ rd>>
/55
/r7 irk'c Vr<<+C I !4 WV
~ iver (r 7 C
- C/
(C/"
'74 iN
'74 C
-Ch Ca 5
vA
<< ~
'FIGURE 5: SQL/TH PAMFL FlIMITEE.LEIAFMT Af'OOEL
l 4
t f
II
CONTROL BUILDING RESPONSE SPECTRUM 0.1 G OBE HORIZONTAL ENVELOPE OF EL. 74'c EL. 100' 1.4 USED IN DESIGN V/ALL SPECIFIC 1.2 M
0
. 0 o.s I-CL 0.6 LJO (3
0.~
0.2
.0.01 r
So&le l.OA'Gt.
ptge7 hfPOE-pEEJUENcl66 PERIOD (SEC)
FIGURE
.0
0 I
I l
CONTROL BUILDING RESPONSE.
SPECTRUM 0.2G SSE HORIZONTAL ENVELOPE OF'L. 74'c EL. 100' g t 1.4 1.2 USED IN DESIGN
~
WALL SPECIFIC V)
~+
1.O 0
0.8 I
CL 0.6 0O o.4 0.2
<oeee t3oAJn pigO1 gPOE FP'Fqu~NeiEe 0.0.Ot
~ ~ o pcRioD (sec)
FIGURE 7
.0
I ll I
t
DOCKET NO(S).
50-528 Mr. E. E. Van Brunt, Jr.
Executive Vice President Arizona Nuclear Pcr/er Pxoject P. 0. Box 52034 Phoenix, Arizona 85072-2034 October 20, 1986 DISTRIBUTION Docket File LPDR PRC System PDR PD7 Reading JLee (2)
SUBJECT:
ARIZCem PUBLIC SERVICE amore, ET AL PAM VERDE NUCEZRR CDMRRPIKQ SZAXIQNi UNIT NO. 1 The following documents concerning our review of the subject facility are transmitted for your information.
D Notice of Receipt of Application, dated D Draft/Final Environmental Statment, dated D Notice of Availabilityof Draft/Final Environmental Statement, dated D Safety Evaluation Report, or Supplement No.
, dated D Notice of Hearing on Application for Construction Permit, dated D Notice of Considera'tion of Issuance of Facility Operating License, dated GP iIII Notice; Applications and Amendments to Operating Licenses Involving no Significant Hazards Considerations, dated 9 24 86 (See e 33961).
D Application and Safety Analysis Report, Volume D Amendment No.
to Application/SAR dated D Construction Permit No. CPPR-
, Amendment No.
dated D Facility Operating License No.
, Amendment No.
, dated D Order Extending Construction Completion Date, dated D Other (Specify)
Enclosures:
As stated Office of Nuclear Reactor Regulation See next page OF F1Caa P
~ ~
~ ~
~ I ~ ~ ~
~ ~
SURNAME%
p
~ ~ ~ ~
~
fe ~ ~ ~ ~ ~ ~ ~ ~ ~ ~
oATa+ ] 0 0/86 NAC FORM 318 t1/84) NACM 0240
I 7(
gw
~
~ I V
\\ J r
4 I
'C
~ w
~,w<
P ~
sC a,
Hr. E.
E.
Van Brunt, Jr.
Arizona Nuclear Power Project Palo Verde CC:
Arthur C. Gehr, Esq.
Snell 5 Wilmer 3100 Valley Center Phoenix, Arizona 85073 Mr. James M. Flenner, Chief Counsel Arizona Corporation Commission 1200 West Washington Phoenix, Arizona 85007 Charles R. Kocher, Esq. Assistant Council James A. Boeletto, Esq.
Southern California Edison Company P. 0.
Box 800
- Rosemead, Cal ifor nia 917?0 Hr. Hark Ginsberg Energy Director Office of Economic Planning and Development 1700 West Washington - 5th Floor Phoenix, Arizona 85007 Kenneth Berlin, Esq.
Winston 8 Strawn Suite 500 2550 H Street, NW Washington, DC 20037 Hs. Lynne Bernabei Government Accountability Project of the Institute for Policy Studies 1901 gue Street, NW Washington, DC 20009 Ms. Jill Morrison 522 E. Colgate Tempi, Arizona 85238 Hr. Charles B. Brinkman, Manager Washington Nuclear Operations Combustion Engineering, Inc.
7910 Woodmont Avenue Suite 1310
- Bethesda, Maryland 20814 Mr. Wayne Shirley Assistant Attorney General Bataan Memorial Building Santa Fe, New Mexico 87503 Mr. Roy Zimmerman U.S. Nuclear Regulatory Commission P. 0.
Box 239 Arlington, Arizona 85322 Ms. Patricia Lee Hourihan 6413 S. 26th Street Phoenix, Arizona 85040 Mr. Ron Rayner P. 0.
Box 1509
- Goodyear, AZ 85338 Regional Administrator, Region V
U. S. Nuclear Regulatory Cooeission 1450 Maria Lane Suite 210 Walnut Creek, California 94596
)
I
Chairman Arizona Corporation Commission Post Office Box 6019
- Phoenix, Arizona 85003 Arizona Radiation Regulatory Agency ATTN:
Ms. Clara Palovic, Librarian 4814 South 40 Street
- Phoenix, Arizona 85040 Mr. Charles Tedford, Director Arizona Radiation Regulatory Agency 4814 South 40 Street
- Phoenix, Arizona 85040 Chairman Maricopa County Board of Supervisors ill South Third Avenue
- Phoenix, Arizona 85003
0 14