LER 78-009/01T-0 on 781226:during Surveillance of Repair on Halon Sys for Relay Room & Computer Room,Noted That Fire Watch Was Adjacent To,But Not In,Unprotected Area.Caused by Failure to Communicate Proper Assignment to Personnel
ML17261A099
Person / Time
Site: Ginna Constellation icon.png
Issue date: 01/09/1979
From: Larizza G
ROCHESTER GAS & ELECTRIC CORP.
To:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION I)
Shared Package
ML17244A311 List:
References
LER-78-009-01T, LER-78-9-1T, NUDOCS 7901150123
Download: ML17261A099 (4)


Text

NRC FORM 366 U. S JCLEAR REGULATORY COMMISSION f7.77)

ICENSEE EVENT REPORT CONTROL BLOCK: Q! (PLEASE PRINT OR TYPE ALL REQUIRED INFORMATIONI I 6

~01 N Y R E G 1 Qs 0 0 0 0 0 0 0 - 0 0 Qs 4 1 1 1 1 Q4~Qs 7 8 9 LICENSEE CODE 14 'IB LICENSE NUMBER 25 26 LICENSE TYPE 30 57 CAT 58 CON'T

~o!

7 8

~LQB 0 5 0 0 0 2 4 4Q71 68 69 2 2 EVENT DATE 6 8 74 Qs 75 0 1 0 REPORT DATE 9 7 9 80 Qs 60 61 DOCKET NUMBER EVENT DESCRIPTION AND PROBABLE CONSEQUENCES Q10 Durin C surveillance of a re air on the Halon s stem for the Rela Room and Com-

~D3 puter Room, it was noticed that the fire watch, located in the area of repa ir work, was adjacent to hut not in the unprotected area as required. (T.8.3.14.4.1). The Pire t

~D6 Detection S stem Alarm for this area was o erable at all times and observable to

~os Control Room Personnel.

~DB 7 8 9 80 SYSTEM CAUSE CAUSE COMP. VALVE CODE CODE SUBCODE COMPONENT CODE SUBCODE SUBCODE

[OD9) 8 Q" A Q>> ~CQ>> P I P E X X Q4 ~AQIs ~ZQIs 7 8 9 10 11 12 13 18 19 20 SEQUENTIAl OCCURRENCE REPORT REVISION Q>>

LER(RO ssr<<r ACTION FUTURE EVENT YEAR

~78 21 22 EFFECT

+

23 SHUTDOWN

~00 24 REPORT NO.

9 26

+a 27

~01 28 ATTACHhIENT CODE 29 NPRDQ TYPE QT 30 PRIME COMP.

31 NO.

[Jo 32 COMPONENT TAKEN ACTION ON PLANT METHOD HOURS Q22 SUBMITTED FORM SUB. SUPPLIER MANUFACTURER

~NQIs~ZQIo ~ZQoo ~ZQ>> . O O O O ~YQso ~NQs4 ~LQss A 4 9 O Qs 33 34 35 36 37 40 41 42 43 44 47 CAUSE DESCRIPTION AND CORRECTIVE ACTIONS Q27 o Lack of communicating proper assignment to fire watch in terms of Limitin Conditions for Operation. Fire watch was immediately relocated to area affected b s stem impairment. Test personnel and maintenance personnel were reinstructed on procedure reference to Tech . Specs . Changes to procedures PT- 1 3 1 . 9 and M-6 7 5 were

~

3 ~ ~

4 initiated to clearly indicate required fire watch assignment, to be in effect by 1/16/79.

0 7 8 9 80 FACILITY METHOD OF STATUS 99POWER OTHER STATUS DISCOVERY DISCOVERY DESCRIPTION Q32

~ls ME Ql! Qm NA QC surveillance 7 8 9 10 12 13 44 4S 46 80 ACTIVITY CONTENT

~16 RELEASED OF RELEASE

~ZQ33 Z AhlOUNT OF ACTIVITY NA Q LOCATION OF RELEASE NA Q

Q34 7 8 9 ,

10 11 44 45 80 PERSONNEL EXPOSURES NUMBER TYPE'ESCRIPTION Q39

~l7 ~00 0 Qs! ~ZQss NA 7 8 9 11 12 13 80 PER BONNE IL INJ IJ RIES 7 8 9 11 12 80 LOSS OF OR OAAIAGE TO FACILITY TYPE DESCRIPTION Q43

~z NA "o>>50 iaS 7 8 9 10 80 O

ISSUED

~NQ44 PUBLICITY DESCRIPTION ~ NA NRC USE ONLY 7 8 9 10 68 69 80 o NAME QF PREPARER G. F. Larizza PHDNE.716/546-2700, ext. 29 1-245

Attachment to LER 78-009/1T-0 Rochester Gas and Electric Corporation R. E. Ginna Nuclear Power Plant, Unit No. 1 Docket No. 50-244 On December 26, 1978 a continuous fire watch with portable equip-ment was stationed for testing and repair of the Halon system for the Com-puter Room and Relay Room at 1000 hours0.0116 days <br />0.278 hours <br />0.00165 weeks <br />3.805e-4 months <br />. At approximately 1500 hours0.0174 days <br />0.417 hours <br />0.00248 weeks <br />5.7075e-4 months <br /> QC personnel performing surveillance discovered that contrary to Technical Specification 3. 14.4.1 the assigned fire watch was found to be not within the area affected by system impairment, but was located in an adjacent area in the Turbine Building, where repairs on the Halon system were in progress.

The fire watch was immediately'elocated to the proper area. At all times the fire detection system alarm for Relay Room and Computer Room was operable and observable to Control Room personnel.

Fire watch personnel customarily are assigned to monitor maintenance activities for fire hazards connected with them, and their familiarity with Technical Specification assignment requirements for areas of fire protection system impairment are limited. The proper assignment for the fire watch in this case was not adequately communicated as the procedures used by the test personnel and the repair personnel gave only general reference to the Technical Specifications. These personnel have been reinstructed on the specific requirements of the Technical Specifications. Changes to test procedure PT-13.1.9 Halon System Testing (Resetting) Computer Room and Relay Room and the maintenance procedure M-67.5 Halon System Maintenance, Computer Room and Relay Room have been initiated to clearly indicate the fire watch assignment, and are expected to be in effect by January 16, 1979.