Special Rept:On 990407,radiation Monitor RM-14A Was Declared Inoperable.Caused by Failed Communication Link from TSC to Plant Process Computer Sys.Communication Link Was re-established & RM-14A Was Declaed Operable on 990521
ML17265A713
Person / Time
Site: Ginna Constellation icon.png
Issue date: 07/22/1999
From: Mecredy R
ROCHESTER GAS & ELECTRIC CORP.
To: Vissing G
NRC (Affiliation Not Assigned), NRC OFFICE OF INFORMATION RESOURCES MANAGEMENT (IRM)
References
NUDOCS 9907300068
Download: ML17265A713 (5)


Text

~~ a M~MZt.L J.

e ~

REGULATORY INFORMATION DISTRIBUTION SYSTEM (RIDS)

ACCESSION NBR:9907300068 DOC.DATE: 99/07/22 NOTARIZED: NO DOCKET FACIL:50'->244 Robert Emmet Ginna Nuclear Plant, Unit 1, Rochester G 05000244 AUTH.NAME AUTHOR AFFILIATION MECREDY,R.C. Rochester Gas &. Electric Corp.

RECIP.NAME RECIPIENT AFFILIATION VISSING,G.S.

SUBJECT:

Special rept:on 990407,radiation monitor RM-14A was declared inoperable. Caused by failed communication link from TSC to plant process computer sys.Communication link was re-established & RM-14A was declared operable on 990521.

DISTRIBUTION CODE: IE22D COPIES RECEIVED:LTR ENCL SIZE-TITLE: 50.73/50.9 Licensee Event Report (LER), Incident Rpt, etc.

NOTES:License Exp date in accordance with 10CFR2,2.109(9/19/72). 05000244 RECIPIENT COPIES RECIPIENT COPIES ID CODE/NAME LTTR ENCL ID CODE/NAME LTTR ENCL LPDl-1 PD VISSING,G.

INTERNAL:~FILE CENTE NRR/DIPM/IOLB 1 NRR/DRIP/REXB NRR/DSSA/SPLB 1 1 RES/DET/ERAB RES/DRAA/OERAB 1 1 RGN" FILE 01 EXTERNAL: L ST LOBBY WARD LMITCO MAPSHALL NOAC POORE,W. NOAC QUEENER,DS NRC PDR NUDOCS FULL TXT WASTETH NOTE TO ALL NRZDSN RECIPIENTS:

PLEASE HELP US TO REDUCE TO HAVE YOUR NAME OR ORGANIZATION REMOVED FROM DISTRIBUTION LIS OR REDUCE THE NUMBER OF COPIES RECEIVED BY YOU OR YOUR ORGANIZATION, CONTACT THE DOCUMENT CONTR DESK (DCD) ON EXTENSION 43.5-2083 TOTAL NUMBER OF COPIES REQUIRED: LTTR 15 ENCL

"'Q AND ROCHESTER GAS AND ElECTRIC CORPORATION ~ B9 EASTAVfNUE, ROCHESTER, N.Y. Id6d9-0001 AREA CODE 716 5'-2700 ROBERT C. MECREDY Vice President Nucteor Operotions July 22, 1999 U. S. Nuclear Regulatory Commission Document Control Desk Attn: Guy S. Vissing Project Directorate I-1 Washington, D AC. 20555

Subject:

Special Report Inoperable Radiation Monitor R.E. Ginna Nuclear Power Plant Docket No. 50-244

Dear Mr. Vissing:

Since radiation monitor RM-14A was inoperable for more than 30 days, this Special Report is submitted in accordance with the Ginna Station Offsite Dose Calculation Manual (ODCM) Procedure CHA-RETS-ODCM,Section III.A.2.a.iii and Table III-2, outlining the action taken, the cause of the inoperability, and the return to service date.

Radiation monitor RM-14A is the high range plant vent effluent monitor, and monitors particulate, Iodine-131, and noble gas in the ventilation air exhausted from the auxiliary and intermediate buildings. On April 7, 1999, at 0622 EDST, the RM-14A skid was declared inoperable because of the data not being available in the Control Room. Control Room indication is via a computer link between the Eberline RCT-1 terminal in the Technical Support Center (TSC) and the Plant Process Computer System (PPCS).

The detectors associated with radiation monitor RM-14A were functional and the data was displayed on the field unit, located in the intermediate building (north) intermediate level.

However, RM-14A was declared inoperable because the communication link from the TSC and the PPCS failed to transmit the data to the Control Room reliably. The concern was that as long as the data was not being transmitted reliably to the Control Room, data r acquisition may not be readily available in an emergency situation.

Between April 7, 1999 and May 21, 19'99, the station was involved in the 1999 refueling outage. RM-14A data was field unit approximately 90% of the time during available at the the interval in question. The restoration of the RM-14A communication link was placed at a lower priority due to other maintenance scheduled for the 1999 outage.

'tt907300068 990722 PDR ADQCK 05000244 S PDR

N On May 21, 1999, Instrument and Control technicians were successful in re-establishing the communication link from the field unit to the RCT-1 terminal in the TSC and to the PPCS in the Control Room. RM-14A was declared operable on May 21, 1999.

At that time, it was observed that the ODCM required an NRC notification. This was documented in the Ginna Station Corrective Action system as ACTION Report No. 99-0925.

The root cause for RM-14A being declared inoperable was attributed to a loose connector in the RCT-1 terminal, which resulted in poor reliability in the communication link between the field unit, the RCT-1 terminal and the PPCS. Since being returned to operable status on May 21, RM-14A data has been displayed reliably in the Control Room.

Very truly yours, Robert C. Me redy xc: Mr. Guy S. Vissing (Mail Stop 8C2)

Project Directorate I Division of Licensing Project Management Office of Nuclear Reactor Regulation U.S. Nuclear Regulatory Commission Washington, D.C: 20555 Regional Administrator, Region I U.S. Nuclear Regulatory Commission 475 Allendale Road King of Prussia, PA 19406 U.S. NRC Ginna Senior Resident Inspector