Redacted - Waterford Steam Electric Station, Unit 3, Revision 309 to Final Safety Analysis Report, Chapter 7, Instrumentation and Controls, Section 7.5
ML16356A567
Person / Time
Site: Waterford 
Issue date: 08/25/2016
From:
Entergy Operations
To:
Office of Nuclear Reactor Regulation
Shared Package
ML16256A115 List: ... further results
References
W3F1-2016-0053
Download: ML16356A567 (84)


Text

WSES-FSAR-UNIT-3 7.5-1 Revision 8 (5/96) 7.5 SAFETY RELATED DISPLAY INSTRUMENTATION 7.

5.1 DESCRIPTION

This section describes those display instrumentation systems which provide timely information to the operator and allows him to adequately monitor conditions in the reactor, Reactor Coolant System (RCS),

containment, and safety related process systems throughout all operating conditions of the plant so that he may perform adequately all required manual actions important to plant safety.

Display Instrumentation is identified in Tables 7.5-1 and 7.5-3. Table 7.5-1 identifies the instrumentation which is provided for the monitoring of anticipated operational occurrences and of accident conditions.

Table 7.5-3 identifies the instrumentation which is provided for the monitoring of accident conditions as defined by NRC Regulatory Guide 1.97, Rev. 3.

The display instrumentation in Table 7.5-1 is tabulated in the following categories:

a)

Plant Process Display Instrumentation Information available to the operator for monitoring conditions in the reactor and related systems.

b)

Reactor Protective System (RPS) Monitoring Information available to the operator for monitoring the status of the Reactor Protective System (RPS) -

c)

Engineered Safety Features (ESF) System Monitoring Information available to the operator for monitoring the status of each ESF system.

d)

ESF Support Systems Instrumentation Information available to the operator for monitoring support systems required to function for the operation of ESF systems.

e)

Auxiliary Control Panel Instrumentation, see Section 7.4 f)

Control Element Assembly (CEA) Position Indication Information available to the operator for monitoring position of the control element assemblies.





WSES-FSAR-UNIT-3 7.5-2 Revision 8 (5/96) 7.5.1.1 Plant Process Display Instrumentation Table 7.5-1 lists the significant process instrumentation that is provided to inform the operator of the status of the reactor plant. This information, which is used for the start up, operation, and shutdown of the plant, is provided on the Reactor Turbine Generator Board (RTGB) and other Control Panels in the main control room. The information is provided in a form that is useful to the operator and may be indicated, recorded, or monitored. Alternate indication and control instrumentation is provided at local panels and the auxiliary control panel outside of the main control room to allow reactor shutdown and maintenance of the reactor in a safe condition during either hot shutdown or cold shutdown, should the main control room become inaccessible.

In addition to the hardwired display instrumentation listed in Table 7.5-1, there are 14 computer-driven CRT displays and two plasma displays on the Main Control Board. The plasma displays are driven by the Qualified Safety Parameter Display System (QSPDS) computers; one of the CRTs on the same panel is driven by the Radiation Monitor computers, while the remaining 13 CRTs are driven by the Plant Monitoring Computer (PMC). These displays can provide the main control room operators, at their request, with a continuous indication of the status of a specified set of parameters which can be used to define the safety status of the plant.



The plant monitoring computer is used for the Plant Safety Parameter Display System (SPDS) function (NUREG 0737 Supplement 1). Additional CRTs will be located in the Onsite Technical Support Center and the Emergency Offsite Facility. The Waterford 3 SPDS function is described in Appendix 7A.



7.5.1.2 Reactor Protective System Monitoring Although the RPS is automatic and does not require operator action, sufficient information is provided in the main control room to confirm that a Limiting Safety System Settings have been reached and a reactor trip has taken place. This information indicates process parameters that initiate reactor trip, pretrip, and bypass lights located in the PPS remote operators modules on the main control boards; audible alarms; CEA position information (Subsection 7.5.1.6); and trip switchgear circuit breaker position indication.

Operating bypass indication as described in Subsection 7.2.1.1.5 is provided on the remote modules, which are located on the main control board. Individual trip channel bypass indication is provided locally at the PPS cabinets, as well as on the remote modules on the main control board.

7.5.1.3 Engineered Safety Features Monitoring The Engineered Safety Features Actuation System (ESFAS) continuously monitors the system input parameters, and. performs actuation logic to initiate safeguards should these inputs reach their trip setpoints.

After the automatic actuation of the ESF systems, they continue to function properly without operator action. For example when the transfer of safety injection pump suction from the refueling water storage pool (RWSP) to the SIS sump is required, the recirculation actuation

WSES-FSAR-UNIT-3 7.5-3 signal automatically actuates this transfer. When the transfer is completed, the operator manually isolates the RWSP. (Subsection 7.3.1.1.2)

Even though the actuation of the ESF systems is automatic and does not require operator action, sufficient information is provided in the control room to allow monitoring of the operation of the ESF and related systems during normal operating and post accident conditions and to take any anticipatory action that may be desirable. This information consists of valve position indication, pump operating status, tank level indication, flow indication, RCS temperature and pressure, and indication of the process parameters that actuate ESF systems. In addition, four control modules, each associated with one channel of the PPS, are located on the control board to provide indication of the pretrip, trip, bypass, and operating bypass condition of each of the ESFAS input signals. Individual trip channel bypass indication is provided locally at the PPS, as well as on the remote modules on the RTGB.

7.5.1.4 ESF Support Systems Monitoring ESF Support Systems are those systems which are required to function for the operation of the ESF system. The instrumentation provided enables the operator to monitor important process variables and take appropriate action.

The Support Systems are as follows:

a)

Component Cooling Water System (CCWS) b)

Vital electrical distribution systems c)

Diesel Fuel Oil Storage and Transfer System d)

Heating, Ventilating and Air Conditioning (HVAC) for areas containing ESF Systems.

The CCWS, and HVAC Systems are operating during normal operation. On emergency signal those systems switch to an emergency mode of operation, and effectively support the operation of the ESF System. Proper environmental conditions are maintained in the main control room by the HVAC System in order to keep personnel safe and electronic equipment operational.

ESF Support System Instrumentation is located on various RTGB panels. Redundant safety channels are provided and identified as SA, SB and SAB. The operator observes selected parameters such as flow, pressure, temperature, level, and takes appropriate action to keep the systems in operating condition.

The power to ESF Support System Instrumentation is supplied by 120V uninterruptible AC system and 125V DC system. Safety related instrumentation for the systems outlined above is shown in Table 7.5-1.

7.5.1.5 Auxiliary Control Panel Instrumentation See Section 7.4.

WSES-FSAR-UNIT-3 7.5-4 Revision 12 (10/02) 7.5.1.6 Monitoring of CEA Position Indication Two diverse, independent CEA position indication systems provide CEA position information to the operator.

The systems are the Pulse Counting CEA Position Indication System and the Reed Switch CEA Position Indication System. These systems are described below. CEA position displays are located on the main control boards. These displays are described in Subsection 7.2.1.1.2.2. CEA position system block diagram is shown in Figure 7.2-4.

7.5.1.6.1 Pulse Counting CEA Position Indication System

¨(DRN 02-386)

The Pulse Counting CEA Position Indication System infers each CEA position by maintaining a record of the "raise" and "lower" control pulses sent to each magnetic jack control element drive mechanism (CEDM).

The pulse counting CEA position signal associated with each CEA is reset to a fixed value whenever the rod drop contact (located within the reed switch position transmitter housing) is closed (zero for a regular CEA).

This permits the pulse counting system to automatically reset the position to zero, whenever a reactor trip occurs or whenever a CEA is dropped into the core. This system is incorporated in the plant monitoring computer which feeds control board digital displays. One digital display provides individual CEA group information. A second digital display provides individual CEA position information. The position of each CEA is periodically printed out for a permanent record.

(DRN 02-386)

The Pulse Counting CEA Position Indication System provides position information to CEA related alarm programs and the Core Operating Limit Supervisory System (COLSS) contained in the plant computer.

Alarms are included in the system design to provide information to the operator required to maintain proper CEA control and to aid in the monitoring of CEA limits. The following alarms are provided by the pulse counting CEA Position Indication System:

a)

Power Dependent Insertion Limits Alarms An alarm is provided in the event CEA insertion exceeds predetermined limits required to maintain adequate shutdown margin and to insure CEA insertion consistent with the CEA ejection analysis. Further definition of the PDEL function is provided in Section 7.7.

b)

Pre-Power Dependent Insertion Limits Alarm This alarm is provided to advise the operator of an impending approach to PDILs.

c)

Out of Sequence Alarm An alarm is provided to alert the operator in the event the CEA groups are inserted or withdrawn in a sequence other than the predetermined acceptable sequence.

WSES-FSAR-UNIT-3 7.5-5 Revision 12 (10/02) d)

CEA Deviation Alarm An alarm is provided to alert the operator in the event the deviation in position between the highest and lowest CEA in any group exceeds a predetermined allowable deviation.

e)

Core Operating Limit Supervisory System (COLSS) Alarms The pulse counting CEA Position Indication System provides input data to COLSS. These data are used in the COLSS power distribution calculations, and alarms are initiated in the, event the affected COLSS limits are reached. The basis for the COLSS alarms and the use of the pulse count CEA position information is discussed in Section 7.7.

7.5.1.6.2 Reed Switch CEA Position Indication System The Reed Switch CEA Position Indication System utilizes a series of magnetically actuated reed switches (Reed Switch Position Transmitters (RSPT)) to provide signals representing CEA position. Two independent reed switch position transmitters are provided for each CEA. The RSPT provides an analog position indication signal and three physically separate discrate reed switch position signals. The analog position indication system utilizes a series of magnetically actuated reed switches spaced at 1-1/2 in. intervals along the RSPT assembly and arranged with precision resistors in a voltage divider network. The RSPT am mounted adjacent to the CEDM pressure housing, which contains the CEA extension shaft and actuating magnet. The analog output signal is proportional to the CEA position within the reactor core. The three discrete reed switch position signals are contact closure signals from three separately located reed switches. These signals are an upper electrical limit, a lower electrical limit and a rod drop contact.

¨(DRN 02-386; 02-1478)

CEA position information is provided to the core protection calculators (CPCS) directly and also to the CEA calculators. The CEA calculators display the position of each regulating and shutdown CEA to the operator in a bar chart format on a dedicated CRT on the RTGB. The operator has the capability to select either CEA calculator for display. In addition, a backup readout is provided that can be utilized to read the output of any CEA analog reed switch position signal. The backup readout is a digital meter on the CPCs operator's module, from which the operator can address any analog position signal for display on the digital meter. In addition to the displays, CEA deviation information is provided by the CEA calculators to the CPCs and a CEA deviation alarm. The CEA deviation alarm is provided to the plant annunciator system in the event a CEA calculator indicates that the difference between the highest and lowest CEA positions in a group exceeds a predetermined allowable deviation. The CEA deviation information is used in the CPCs determination of power distribution. The power distribution is then factored into the low DNBR and high local power density trip function. Pretrip alarms are initiated if the DNBR or local power density trip limits are approached. A pretrip alarm light is provided on the Plant Protection System control panel. Also, a pretrip alarm is provided to the plant annunciator system.

(DRN 02-386; 02-1478)

The three discrete CEA position switches provide signals (contact closure signals) to the Control Element Drive Mechanism Control System (CEDMCS) as shown in Figure 7.2-2. The signals are utilized to provide CEA limit indication on the RTGB and also to provide input

WSES-FSAR-UNIT-3 7.5-6 Revision 11-A (02/02) to the CEA control interlocks. Each of the three discrete reed switch contacts actuates an interface relay located within the CEDMCS. These relays provide contact signals for indication and control and, in the case of the rod drop switch, an additional contact signal is provided to the plant monitoring computer to reset the pulse counting system. The upper and lower electrical limits indication appears as two separate lights on the CEDMCS control panel mounted on the RTGB. The CEA drop indication appears on the core mimic display mounted on the main control board.

7.5.1.6.3 CEA Limit Lights Indication A light display is provided on the RTGB to indicate the fully withdrawn and fully inserted position of each CEA and provides indication of a dropped CEA.

7.5.1.7 Accident Monitoring Instrumentation The accident monitoring system is designed to monitor plant variables during and following an accident.

¨(DRN 01-28)

Indications of plant variables are required by the control room operating personnel during accident situations to (1) provide information required to permit the operator to take preplanned manual actions to accomplish safe plant shutdown; (2) determine whether the reactor trip, safety-feature systems, and manually initiated safety systems and other systems important to safety are performing their intended functions. (i.e.,

reactivity control, core cooling, maintaining reactor coolant system integrity, and maintaining containment integrity); and (3) provide information to the operators that will enable them to determine the potential for causing a gross breach of the barriers to radioactivity release (i.e., fuel cladding, reactor coolant pressure boundary, and containment) and to determine if a gross breach of a barrier has occurred. In addition to the above, indications of plant variables that provide information on operation of plant safety systems and other systems important to safety are required by the control room operating personnel during an accident to (1) furnish data regarding the operation of plant systems in order that the operator can make appropriate decisions as to their use and (2) provide information regarding the release of radioactive materials to allow for early indications of the need to initiate action necessary to protect the public and for an estimate of the magnitude of any impending threat. Instrumentation systems provided for the remote monitoring of accident conditions were qualified for operation in environmental and seismic conditions specified in Sections 3.10 and 3.11. Safety related instrumentation should continue to perform its safety function(s) and read within the required accuracy following, but not necessarily during, a safe shutdown earthquake. Table 7.5-3 shows that the instrumentation systems furnished in the design provide redundancy and appropriately wide range information of accident conditions.

The wide range of information furnished to the operator by the extensive instrumentation and control systems described in the table provide the long-term monitoring and surveillance capabilities of accident conditions.

(DRN 01-28)

¨ (DRN 00-25) 7.5.1.8 Bypassed and Inoperable Status Indication Waterford 3 does not have a Bypassed and Inoperable Status Indication System (BISIS), but has established other measures for indicating the bypassed or inoperable status of the protective system, systems actuated or controlled by the protection system, and auxiliary or supporting systems that must be operable for the protection system and the systems it actuates to perform their safety related functions.

Alternate means are available to comply with regulations implemented by Regulatory Guide 1.47.

(DRN 00-25)

WSES-FSAR-UNIT-3 7.5-7 Revision 11 (05/01)

 (DRN 00-25) 7.5.1.8.1 Reactor Protection System The reactor protection system monitors neutron power, hot and cold leg temperatures, pressurizer pressure, control element assembly position, reactor coolant pump speed, containment pressure, and steam generator level and pressure to detect conditions requiring a reactor trip and generate the reactor trip signal. The Reactor protection system energizes a reactor trip signal to de-energize the control element assemblies to drop into the core. The provisions for monitoring the reactor protection system are described in section 7.2.1.1.5, 7.5.1.2 and 7.5.2.2. These provisions include automatic indication in the control room to alert the operator when required protective actions have been bypassed or rendered inoperable. All bypasses are annunciated visually and audibly in the control room.

7.5.1.8.2 Engineered Safety Features Actuation System The engineered safety features actuation system monitors pressurizer pressure, containment pressure, containment area radiation, fuel handling building radiation, steam generator level and pressure, refueling water storage pool level, and emergency bus voltage to detect conditions requiring an actuation of the engineered safety features (ESF) and generate the required engineered safety feature actuation signal (ESFAS). Seven electrical signals (SIAS, CIAS, CSAS, MSIS, EFAS, RAS and FHA) are provided to actuate the appropriate ESF system, when required. The ESF system actuated by the ESFAS include:

safety injection, containment isolation, containment cooling, containment spray, main steam isolation, emergency feedwater, recirculating actuation, and ESF ventilation systems. The provisions for monitoring the engineered safety features actuation system are described in sections 7.2.1.1 5, 7.3.1.1, 7.5.1.3 and 7.5.2.3. These provisions include automatic indication in the control room to alert operators when required protective actions have been bypassed or rendered inoperable-Individual trip channel bypass indication is provided locally at the PPS, as well as on the remote modules on the RTGB control panel.

7.5.1.8.3 Systems and Support Systems Actuated by the Plant Protection System The systems and support systems actuated by the Plant Protection System and provisions to monitor bypassed or inoperable conditions of these systems are described in sections 7.3.1, and 7.3.2.

Additionally, safety related display instrumentation is provided as described in section 7.5.1.4, and Table 7.5-1 to monitor the status of each system and support system actuated by the Plant Protection System.

Improved regulatory guidance, design enhancements, and additional administrative controls have been implemented following issuance of Regulatory Guide 1.47 which assure the Operator has sufficient information to monitor the status of systems and support systems actuated by the Plant Protection System. NUREG-0700, NUREG-0737 and Regulatory Guide 1.97 were issued after Regulatory Guide 1.47. These documents address system operator configurations for human factors and the information needed by the operator to safely shutdown the facility. Enhancements were made in response to these documents.

A detailed review of the Control Room and Remote Shutdown Panel human factors was performed in response to NUREG-0700 and NUREG-0737. The enhancements recommended by this review were documented and implemented, as required, and the response to Regulatory Guide 1.97 was revised.

Design enhancements have been completed to improve the ability of the Operator to monitor the status of each system and support system actuated by the Plant Protection System. The control panels have been color coded by system and indicator scales have been human factored to allow the operator quick assessment of system status and process conditions. The non-safety related Plant Monitoring Computer provides the operator with real time information of system status on dedicated screens in the control room.

The Plant Monitoring computer functionality and capabilities are discussed in section 7.5a. The information provided by the Qualified Safety Parameters Display System, Safety Parameters Display

 (DRN 00-25)

WSES-FSAR-UNIT-3 7.5-8 Revision 11 (05/01)

 (DRN 00-25)

System, and Plant Monitoring Computer supplements the Plant Annunciator system, which provides system and major component alarms. Design changes to eliminate nuisance alarms from the control room have been implemented to assure Operator attention for alarms during plant operations.

Operational guidance has been enhanced to improve the ability of the Operator to monitor the status of each system and support system actuated by the Plant Protection System. Design changes have reduced the frequency of nuisance alarms, thereby minimizing the number of distractions and improving operator response. Administrative controls have been enhanced including measures to identify systems that are bypassed or inoperable, including: Equipment Out Of Service, Clearance Requests, Temporary Alteration Control, Independent Verification Program, Work Authorization Program, Condition Report Process, Control of Valves and Breakers, Alarm and Control Room Instrumentation Control. Conditions that render systems or support systems actuated by the Plant Protection System inoperable are subject to Technical Specifications action statements. Administrative controls to track entry into Technical Specifications action statements have been enhanced and are used to track the operability status of the systems and support systems actuated by the Plant Protection System.

The procedures for operating the facility coupled with human factoring of the instrumentation and controls in the control room and the design of the safety-related systems discussed in Section 7.5.1.8 comply with Criterion XIV, Inspection, Test and Operating Status of 10CFR5O Appendix B, Section 50.55a Codes and Standards of 10CFR50, and Section 4.13 of IEEE Standard 379-1971 Criteria for Nuclear Power Plant Protections Systems. A separate Bypassed and Inoperable Status Indication System (BISIS) is not required.

 (DRN 00-25) 7.5.1.9 Control Panels and Annunciators 7.5.1.9.1 Control Panels The RTGB is of the free standing benchboard type board with control switches primarily arranged on the lower bench portion, indicating and recording display instrumentation primarily on the lower vertical section, and annunciator windows primarily on the upper vertical section. The RTGB consists of six separate control panels and three plant monitoring computer CRT display panels and one Radiation Monitoring and Qualified Safety Parameter Display Panel located in the main control room and mounted adjacent to one another in a "U-shaped" arrangement. The panels are identified as follows:

CP1 Turbine Generator Control Plant CP2 Reactor Control Panel CP3 Plant Monitoring Computer CRT Panel 2 (Non-safety)

CP4 Chemical and Volume Control System Control Panel CP6 Radiation Monitoring and Qualified Safety Parameter Display Panel CP7 Plant Protection System Remote Control Panel CP8 Engineered Safety Features Panel CP18 HVAC Control Panel CP35 Plant Monitoring Computer CRT Panel 1 (Non-safety)

WSES-FSAR-UNIT-3 7.5-9 Revision 11 (05/01)

CP36 Plant Monitoring Computer CRT Panel 3 (Non-safety)

In addition there is another safety related control panel in the main control room which is not a part of the U-shaped arrangement and is identified as CP33, hydrogen and cooling tower control panel.

In front of the main control board there is operators console CP9, which is not safety-related. The equipment located on operators console CP9 and on the main control board sections CP3, CP35, CP36 and the Shift Supervisors office is related to the Plant Monitoring Computer and although is helpful to the operator, is not safety-related.

Control switches and display instrumentation on the safety portion of the control panels are arranged functionally. Lights indicate valve positions or equipment status. Important system process parameters are displayed on indicators or recorders.

Safety-related display instrumentation which is a part of the PPS is divided into four redundant channels.

These redundant channels consist of mechanical and electrical devices and the circuitry involved in analog measurements to generate signals for the protective trips of the reactor. They are identified with the suffix SMA, SMB, SMC, and SMD.

All other safety-related instrumentation is either a part of ESF or support systems, and is divided into two redundant channels. These are identified with the suffix SA or SB. There is an additional safety-related channel which is identified with the suffix SAB. Equipment which belongs to this channel is used as a backup or a replacement for channel SA or SB.

All RTGB panels are classified seismic Category 1. The compliance of the instrumentation and control to the requirements of Regulatory Guide 1.75 is discussed in Section 8.3.

Figures 7.5-1 through 7.5-7 demonstrate the physical and electrical separation and identification of safety-related redundant channels.

7.5.1.9.2 Annunciators Waterford 3 has a total of 12 non-safety annunciator display units, each with 120 windows. and two safety-related annunciator display units, each with 45 windows in the main control room. Non-safety alarm contacts are wired separately to the non-safety annunciator logic and lamp cabinet. All alarm window displays are arranged functionally. Safety-related annunciators have two safety-related channels; one annunciator unit is a part of the SA channel and the other is a part of the SB channel. All safety-related redundant alarms are part of these units. The balance of the annunciator windows are utilized for other annunciation purposes. Alarm contacts for the safety-related annunciators are wired separately within each channel.

Audible alarms and visual annunciators alert the plant operator to the occurrence of malfunctions in equipment or systems, and signal changes in plant equipment status and operating modes. Alarms and status displays inform the operator of any deviations from normal operating conditions, such as the impending occurrence of automatic trips of the RPS and the status, malfunction, bypass or override condition of safety systems.

The arrangement of all annunciator windows is shown on figures listed in Table 1.7-1.

WSES-FSAR-UNIT-3 7.5-10 Revision 11 (05/01) 7.5.2 ANALYSIS 7.5.2.1 Plant Process Display Instrumentation Plant process display instrumentation gives the operator information to monitor conditions in the plant and to perform operations important to plant safety. In addition, the information allows the operator to crosscheck plant protection system measurement channels to ensure operational availability of these channels as discussed in Sections 7.2 and 7.3. The following design criteria were used in the selection of plant instrumentation:

a)

Provide continuous monitoring of process parameters required by the operator.

b)

Provide display information to the operator that is reliable, comprehensible, and timely.

c)

Provide instrumentation display that adequately monitors the parameter over the range required for various conditions.

d)

Provide a permanent record of those parameters for which trend information is useful.

e)

Provide four channels of indication for RPS and ESFAS process parameters to allow cross-checking of channels.

f)

Failure of a single indicator or one channel shall not adversely affect operators action.

Sufficient information is provided for the operator to accurately assess the conditions within the plant systems, to perform those appropriate actions in a timely manner, and to maintain the reactor systems within the conditions assumed by the safety analysis in Chapter 15.

7.5.2.2 Reactor Protective System Monitoring Sufficient information is provided for the operator to confirm that a trip has occurred and to determine which process parameter caused the trip. CEA insertion information after a trip can be determined by the operator from the CRT bar chart display information and CEA limit light indication. Indication of neutron flux levels in the reactor core, as well as other reactor and RCS information, is provided for the operator.

The following design criteria were used in the selection of information that is provided to the operator:

a)

System conditions requiring operator attention during routine plant operations and at the time of reactor trip are displayed on the RTGB.

b)

Annunciation at the control board of all operations performed at the PPS cabinet affecting the function of the system.

c)

Indication of all selected plant variables that are manually bypassed.

d)

Automatic or manual removal of a bypass shall be indicated.

7.5.2.3 Engineered Safety Features Monitoring

WSES-FSAR-UNIT-3 7.5-11 Revision 11 (05/01)

Information is provided so the operator can monitor the status of the ESF systems. The following design criteria were used in the selection of information that is provided to the operator:

a)

System conditions requiring operator attention or action during routine plant operations are displayed and/or controlled at the RTGB.

b)

All operations performed at the ESFAS cabinets that affect the functioning of the system are annunciated at the main control room.

c)

Indication is provided for all selected plant variables that are manually blocked or bypassed.

d)

Automatic or manual removal of block or bypasses shall be indicated.

e)

Information is provided to aid the operator in determining when manual actuation of an ESF system is required and to aid in confirming proper system operation after automatic initiation.

Input parameters that initiate actuation are indicated on the RTGB along with positive indications that pumps and valves have actuated and that flows have been established.

f)

Testing of ESFAS components can be accomplished on a scheduled basis during plant operation without adversely affecting the system operation.

Consistent with the above criteria the information which is provided for the operators use is shown in Table 7.5-1.

7.5.2.4 ESF Support System Monitoring Instrumentation for the ESF Support Systems is located on the RTGB and grouped functionally. Channels are identified the same way as the ESF System. Description of ESF Support System is discussed in Section 7.3. The following design criteria were used in selecting the process information for the operators use:

a)

Provide continuous monitoring of various process parameters that are essential for the proper operation of a particular system in a normal and an emergency mode of operation.

b)

Provide system conditions requiring an operators attention or actions.

c)

Provide redundancy of channels of instrumentation and control for reliable display and operation.

d)

Provide the capability for periodic testing of the equipment during normal operation.

e)

Provide display information which is accurate and timely.

Using these criteria the operator has sufficient instrumentation for his use to properly assess the situation during various modes of operation and take corrective action. The instrumentation is shown in Table 7.5-1.

7.5.2.5 Auxiliary Control Panel Instrumentation See Section 7.4.

WSES-FSAR-UNIT-3 7.5-12 Revision 14-B (06/06) 7.5.2.6 CEA Position Indication CEA position indication allows the operator to easily determine the position of all of the CEAs within the reactor core. The information is presented in a form that can be assessed by the operator to determine that the CEAs are in the required position, that a CEA has dropped into the core, or that the CEA positions are as required after a reactor trip.

The following design criteria were used in selection of the CEA position indication:

a)

Position readouts of all CEAs may be obtained.

b)

Continuous position indication of all CEAs is available.

c)

A means is provided to alert the operator to deviation of CEAs within a group.

d)

A permanent record may be made of the position of any or all CEAS.

e)

Separate "full-in" and "full-out" indications are provided for each CEA.

f)

Redundant and diverse means of indicating CEA position is provided.

7.5.2.7 Accident Monitoring Instrumentation Table 7.5-3 lists the variables committed to by Waterford 3 and recommended by Regulatory Guide 1.97, Revision 3. The table includes the Waterford 3 assigned category, range, environmental and seismic qualification, number of channels, power supply, type of control room display, availability on the Safety Parameter Display System (SPDS), quality assurance, and comments.

Those items which are not in complete compliance with Regulatory Guide 1.97 are discussed in the notes to Table 7.5-3.

7.5.2.7.1 Design Bases 7.5.2.7.1.1 Variable Type Definitions The variables identified in Table 7.5-3 are divided into five types in accordance with Regulatory Guide 1.97. The definition for each type of variable is as follows:

(DRN 04-1967, R14)



Type A - Those variables to be monitored that provide the primary information required to permit the Control Room operator to take specific manually controlled actions for which no automatic control is provided and that are required for safety systems to accomplish their safety functions for design basis accident events. Type A variables are plant specific and were selected based on a review of Emergency Operating Procedures to identify information essential for the direct accomplishment of specified safety functions. As a result of the review of Waterford 3 Emergency Operating Procedures and FSAR Chapter 15, the following variables were identified as Type A:

RCS Pressure RCS Hot Leg Temperature RCS Cold Leg Temperature Containment Pressure

(DRN 05-1382, R14-B)

(DRN 05-1382, R14-B)

(DRN 04-991, R13-A)

Condensate Storage Pool Water Level Control Room Air Intake Radiation Levels

(DRN 04-991, R13-A; 04-1967, R14)

WSES-FSAR-UNIT-3 7.5-13 Revision 11 (05/01)

Primary information is information that is essential for the direct accomplishment of the specified safety functions; it does not include those variables that are associated with contingency actions that may also be identified in written procedures.

Type B - Those variables that provide information to indicate whether plant safety functions are being accomplished. Plant safety functions are (1) reactivity control, (2) core cooling, (3) maintaining reactor coolant system integrity, and (4) maintaining containment integrity (including radioactive effluent control).

Type C - Those variables that provide information to indicate the potential for breaching or the actual breach of the barriers to fission product releases. The barriers are (1) fuel cladding, (2) primary coolant pressure boundary, and (3) containment.

Type D - Those variables that provide information to indicate the operation of individual safety systems and other systems important to safety. These variables are to help the operator make appropriate decisions in using the individual systems important to safety in mitigating the consequences of an accident.

Type E - Those variables to be monitored as required for use in determining the magnitude of the release of radioactive materials and continually assessing such releases.

7.5.2.7.1.2 Evaluation Criteria As recommended by Regulatory Guide 1.97 each variable type was evaluated based on the importance to safety of the measurement of the specific variable.

Category 1:

provides the most stringent requirements and is intended for key variables. All Type A and some Type B, C, D and E variables are Category 1.

Category 2:

provides less stringent requirements and applies to instrumentation intended for indicating system operating status.

Category 3:

provides requirements that will ensure high quality off-the

-shelf instrumentation is obtained and applies to back up and diagnostic instrumentation. This category is also used when the state-of-the-art will not support requirements for higher qualified instrumentation.

The specific design and qualification criteria used to evaluate each variable, based on the category classification, are presented below:

Category I Environmental Qualification Currently the Environmental Qualification Program at Waterford 3 is in compliance with 10CFR50.49.

Regulatory Guide 1.97 Revision 3 Category 1 and Category 2 components located

WSES-FSAR-UNIT-3 7.5-14 Revision 11 (05/01) in harsh environments have been evaluated and are qualified within the scope of this program. The determination of qualification was based on having either actual environmental qualification documentation available or documentation on similar equipment available.

Seismic Qualification Currently installed instrumentation meets the requirements contained in Subsection 3.10. In general, original equipment was qualified with IEEE-344-1971, although in some cases, it was qualified to IEEE-344-1975. Instrumentation added as a result of the Regulatory Guide 1.97 Rev 3 guidelines for Category I equipment has been qualified to IEEE-344-1975.

Redundancy The location of the sensors and the points at which the sensing lines are connected to the process loop have been selected to provide physical separation of the channels to the maximum extent practicable, thereby precluding a situation in which a single event could cause failure of both channels, unless mentioned otherwise. Refer to Section 8.3 for further details for exception taken to the requirements for physical separation of redundant channels as defined in Regulatory Guide 1.75.

Power Supply Category I instruments are supplied with power from a Class 1E power supply. The Waterford 3 Class 1E power system is designed to meet the requirements of IEEE 279-1971, IEEE 308-1971, Regulatory Guides 1.6 and 1.32.

Quality Assurance The quality assurance program is described in the Quality Assurance Program Manual. These measures include appropriate requirements for design review, procurement, inspection, and testing which ensures that components are of a quality consistent with minimum maintenance requirements and low failure rates.

Display and Recording Continuous real-time display of at least one channel is provided in the Control Room. Recording of the instrument is provided for at least one of the redundant channels. Where it has been determined that direct and immediate trend or transient information is essential for operator information or action (Type A variable), a continuous dedicated recorder is provided with redundant backup recording and trending available on QSPDS and redundant dedicated indicators in the Control Room that can be utilized for trend information if necessary (one of the redundant dedicated indicators may be the continuous dedicated recorder listed above).

Service, Testing and Calibration Either channel may be tested, calibrated and/or repaired without detrimental effects on the other channel.

WSES-FSAR-UNIT-3 7.5-15 Revision 11 (05/01))

Performance of the surveillance instrumentation will be verified during reactor operation subject to the following:

1)

Testing will not adversely affect the safety or operability of the plant.

2)

Normal channel operation is considered an acceptable method of verifying surveillance instrumentation performance if channel operating parameters are similar to those anticipated following a LOCA.

3)

Where surveillance instrumentation performance cannot be verified under the conditions of one and two above, periodic testing is performed.

The loops can be checked from the sensor signal through the readout located in the main control room. Many of these sensors specified are also used in the PPS and, therefore, will be tested during PPS testing. For those sensors that are not part of the PPS, testing will be performed on a periodic basis.

Identification The channels are identified uniquely as indicated in Table 7.5-3. The channels are identified to distinguish between redundant channels of the same variable.

Category 2 Environmental Qualification - Same as Category I Seismic Qualification - No specific provision Redundancy - No specific provision Power Supply - Energized from highly reliable source (e.g., The non-Class 1E Vital).

Quality Assurance - Same as Category I Display and Recording - "On-demand" or continuous display is provided in the control room. No direct or immediate trend or transient information was determined to be essential for operator information or action.

Service, Testing and Calibration - Same as Category I Identification - No specific provision 7.5.2.9 Main Control Room Panels and Annunciators The main control room panels with annunciators provide the operator sufficient information concerning the plant condition. With the help of display instrumentation, equipment status indication, bypass and inoperable status indication, and annunciation, the operator can properly assess the situation during various modes of plant operation and take corrective or anticipatory action in order to maintain the plant in a safe condition.

WSES-FSAR-UNIT-3 7.5-16 Revision 11 (05/01) 7.5.2.10 System Drawings All applicable safety related display instrumentation system schematics, functional block diagrams, wiring diagrams and layouts have been provided. See Section 1.7 for a listing of all drawings.

7.5.2.11 Quality Assurance Quality Assurance procedures for handling, packaging, and shipping are consistent with the recommendations of Regulatory Guide 1.38 as discussed in the QA Program Manual.

7.5.2.12 Seismic and Environmental Qualification Applicable seismic and environmental qualification criteria, testing, and results are discussed in Sections 3.10 and 3.11, respectively.

WSES-FSAR-UNIT-3 Table 7.5-1 (Sheet 1 of 27)

SAFETY-RELATED PANEL MOUNTED DISPLAY INSTRUMENTATION PANEL: CP TURBINE GENERATOR CONTROL PANEL INDICATORS Tag No Service Channel Scale - Units RPS ESF PPDI ESSI DG A VOLTAGE SA 0-5250 VAC X

4KV BUS 3A3-S VOLTAGE SA 0-5250 VAC X

DG A SYNCHROSCOPE SA N/A X

DG A FREQUENCY SA 55-65 HZ X

DG A CURRENT (PHASE C)

SA 0-1000 AC AMP X

DG A MW SA 0-7 MW X

DG A MVAR SA

(-)-0-5 MVAR X

DG B VOLTAGE SB 0-52509 VAC X

4KV BUS 3B3-S VOLTAGE SB 0-5250 VAC X

DG B SYNCHROSCOPE SB N/A X

DG B FREQUENCY SB 55-65 HZ X

DG B CURRENT (PHASE C)

SB 0-1000 AC AMP X

DG A OIL DAY TANK LEVEL SA 0-6 FT X

All abbreviations used in this Table are in the Legend which follows on Sheet 27.

Security-Related Information Withheld Under 10 CFR 2.390

WSES-FSAR-UNIT-3 Table 7.5-1 (Sheet 2 of 27)

Revision 306 (05/12)

PANEL: CP TURBINE GENERATOR CONTROL PANEL INDICATORS Tag No Service Channel Scale - Units RPS ESF PPDI ESSI BATTERY SA VOLTAGE SA 0-150 VDC X

X X

X DG A RUNNING VOLTS SA 0-5250 VAC DG A INCOMING VOLTS SA 0-5250 VAC DG B OIL DAY TANK LEVEL SB 0-6 FT X

BATTERY SB VOLTAGE SB 0-150 VDC X

X X

X DG B RUNNING VOLTS SB 0-5250 VAC DG A INCOMING VOLTS SB 0-5250 VAC DG B MW SB 0-7 MW X

DG B MVAR SB

(-)5-0-5 MVAR X

125 VDC AB SYSTEM SAB 0-150 VDC X

PANEL: CP REACTOR CONTROL PANEL INDICATORS Tag No Service Channel

  • Scale - Units RPS ESF PPDI ESSI RED TRACE - LOOP 1 HOT LEG TEMP GREEN TRACE - LOOP 2 HOT LEG TEMP SMA SMA 525-675F 525-675F X

X SUBCOOLED MARGIN MONITOR 200F (SUBCOOLED0 50F (SUPERHEAT)

X SUBCOOLED MARGIN MARGIN 200F (SUBCOOLED) 50F (SUPERHEAT)

X

  • Scales linear unless otherwise stated.

Security-Related Information Withheld Under 10 CFR 2.390

WSES-FSAR-UNIT-3 Table 7.5-1 (Sheet 3 of 27) Revision 10 (10/99)

PANEL: CP PLANT PROTECTION SYSTEM REMOTE CONTROL PANEL INDICATORS Tag No Service Channel

  • Scale - Units RPS ESF PPDI ESSI REFUELING WATER STORAGE POOL LEVEL SMA 0-100 %

X X

PZR PRESS AND SETPOINT SMA 0-3000 PSIA X

X PZR PRESSURE SMA 1500-2500 PSIA X

NEUTRON FLUX AND DATE OF CHANGE OF POWER sma 2x10-8-200%(LOG)

-1 to +7 DPM (LINEAR) x 120 AC POWER SUPPLY CHANN. SMA VOLTAGE SMA 0-150 VAC X

X LOOPS 1 & 2 HOT LEG TEMP SMA 525-675°F X

X LOOPS 1 & 2 COLD LEG TEMP SMA 465-615°F X

X LOCAL POWER DENSITY AND DNBR MARGIN SMA 0-25 kw/ft 0-10 X

X CONTAINMENT PRESSURE (NARROW RANGE)

SMA 0-30 PSIA X

X CONTAINMENT PRESSURE (WIDE RANGE)

SMA 0-30 PSIA X

REFUELING WATER STORAGE POOL LEVEL SMB 0-100 %

X PZR PRESS AND SETPOINT SMB 0-3000 PSIA X

X X

PZR PRESSURE SMB 1500-2500 PSIA X

NEUTRON FLUX AND RATE OF CHANGE OF POWER SMB 2x10-8-200%(LOG)

-1 to +7 DPM(LINEAR)

X

  • Scales linear unless otherwise stated.
    • These are two system instruments in common housing.

Security-Related Information Withheld Under 10 CFR 2.390

WSES-FSAR-UNIT-3 Table 7.5-1 (Sheet 4 of 27) Revision (12/97)

PANEL: CP PLANT PROTECTION SYSTEM REMOTE CONTROL PANEL INDICATORS Tag No Service Channel

  • Scale - Units RPS ESF PPDI ESSI 120 V AC POWER SUPPLY CHANN. SMB VOLTAGE SMB 0-150 VAC X

X LOOPS 1 & 2 HOT LEG TEMP SMB 525-675 F X

LOOPS 1 & 2 COLD LEG TEMP SMB 465-615 F X

X X

LOCAL POWER DENSITY AND DNBR MARGIN SMB 0-25 kw/ft 0-10 X

CONTAINMENT PRESSURE (NARROW RANGE)

SMB 0-30 PSIA X

X CONTAINMENT PRESSURE (WIDE RANGE)

SMB 0-30 PSIA X

REFUELING WATER STORAGE POOL LEVEL SMC 0-100 %

X PZR PRESS AND SETPOINT SMC 0-3000 PSIA X

X PZR PRESSURE SMC 1500-2500 PSIA X

NEUTRON FLUX AND RATE OF CHANGE OF POWER SMC 2x10(-8) -200%(LOG)

-1 TO +7 DPM(LINEAR)

X 120 V AC POWER SUPPLY CHANN. SMC VOLTAGE SMC 0-150 VAC X

X LOOPS 1 & 2 HOT LEG TEMP SMC 525-675°F X

X LOOPS 1 & 2 COLD LEG TEMP SMC 465-615°F X

X LOCAL POWER DENSITY AND DNBR MARGIN SMC 0-25 kw/ft 0-10 kw/ft X

REFUELING WATER STORAGE POOL LEVEL SMD 0-100 %

X PZR PRESS AND SETPOINT SMD 0-3000 PSIA X

X PZR PRESURE SMD 1500-2500 PSIA X

  • Scales linear unless otherwise stated.
    • These are two system instruments in common housing.

Security-Related Information Withheld Under 10 CFR 2.390

WSES-FSAR-UNIT-3 Table 7.5-1 (Sheet 5 of 27) Revision 11 (05/01)

PANEL: CP PLANT PROTECTION SYSTEM REMOTE CONTROL PANEL INDICATORS Tag No Service Channel

  • Scale - Units RPS ESF PPDI ESSI NEUTRON FLUX AND RATE OF CHANGE OF POWER SMD 2x10-8-200%(LOG)

-1 to +7 DPM(LINEAR)

X 120 V AC POWER SUPPLY CHANN. SMD VOLTAGE SMD 0-150 VAC X

LOOPS 1 & 2 HOT LEG TEMP SMD 525-675°F X

LOOPS 1 & 2 COLD LEG TEMP SMD 454-615°F X

X LOCAL POWER DENSITY AND DNBR MARGIN SMD 0-25 kw/ft 0-10 X

CONTAINMENT PRESSURE (NARROW RANGE)

SMD 0-30 PSIA X

X CONTAINMENT PRESSURE (WIDE RANGE)

SMD 0-30 PSIA X

CONTAINMENT PRESSURE (NARROW RANGE)

SMC 0-30 PSIA X

X CONTAINMENT PRESSURE (WIDE RANGE)

SMC 0-30 PSIA X

REACTOR COOLANT SG-1 DIFF PRESS (RCP SHEARED SHAFT DETECTION)

SMA 0-50 PSID X

  • Scales linear unless otherwise stated.
    • These are two system instruments in common housing.

Security-Related Information Withheld Under 10 CFR 2.390

WSES-FSAR-UNIT-3 Table 7.5-1 (Sheet 6 of 27) Revision 11 (05/01)

PANEL: CP PLANT PROTECTION SYSTEM REMOTE CONTROL PANEL INDICATORS Tag No Service Channel

  • Scale - Units RPS ESF PPDI ESSI NEUTRON FLUX AND RATE OF CHANGE OF POWER SMD 2x10-8-200%(LOG)

-1 to +7 DPM(LINEAR)

X 120 V AC POWER SUPPLY CHANN. SMD VOLTAGE SMD 0-150 VAC X

LOOPS 1 & 2 HOT LEG TEMP SMD 525-675° F X

LOOPS 1 & 2 COLD LEG TEMP SMD 465-615° F X

X LOCAL POWER DENSITY AND DNBR MARGIN SMD 0-25 kw/ft 0-10 X

CONTAINMENT PRESSURE (NARROW RANGE)

SMD 0-30 PSIA X

X CONTAINMENT PRESSURE (WIDE RANGE)

SMD 0-30 PSIA X

CONTAINMENT PRESSURE (NARROW RANGE)

SMC 0-30 PSIA X

X CONTAINMENT PRESSURE (WIDE RANGE)

SMC 0-30 PSIA X

REACTOR COOLANT SG-1 DIFF PRESS (RCP SHEARED SHAFT DETECTION)

SMA 0-50 PSID X

  • Scales linear unless otherwise stated.
    • These are two system instruments in common housing.

Security-Related Information Withheld Under 10 CFR 2.390

WSES-FSAR-UNIT-3 Table 7.5-1 (Sheet 7 of 27)

Revision 306 (05/12)

PANEL: CP PLANT PROTECTION SYSTEM REMOTE CONTROL PANEL INDICATORS Tag No Service Channel

SMA 0-50 PSID X

REACTOR COOLANT SG-1 DIFF PRESS (RCP SHEARED SHAFT DETECTION)

SMB 0-50 PSID X

REACTOR COOLANT SG-2 DIFF PRESS (RCP SHEARED SHAFT DETECTION)

SMB 0-50 PSID X

REACTOR COOLANT SG-1 DIFF PRESS (RCP SHEARED SHAFT DETECTION)

SMC 0-50 PSID X

REACTOR COOLANT SG-2 DIFF PRESS (RCP SHEARED SHAFT DETECTION)

SMC 0-50 PSID X

REACTOR COOLANT SG-1 DIFF PRESS (RCP SHEARED SHAFT DETECTION)

SMD 0-50 PSID X

REACTOR COOLANT SG-2 DIFF PRESS (RCP SHEARED SHAFT DETECTION)

SMD 0-50 PSID X

PRESSURIZER PRESSURE SMA 0-3000 PSIA X

RED TRACE - LOOP 1A COLD LEG TEMP GREEN TRACE - LOOP 2A COLD LEG TEMP SMA SMA 465-615 F 465-615 F X

X REFUELING WATER POOL LEVEL SMB 0-100 %

X

  • Scales linear unless otherwise stated.
    • These are two system instruments in common housing.

Security-Related Information Withheld Under 10 CFR 2.390

WSES-FSAR-UNIT-3 Table 7.5-1 (Sheet 8 of 27)

PANEL: CP PLANT PROTECTION SYSTEM REMOTE CONTROL PANEL INDICATORS Tag No Service Channel

  • Scale - Units RPS ESF PPDI ESSI CORE PROTECTION CALCULATOR OPERATORS MODULE SMA NA X

PLANT PROTECTION SYSTEM REMOTE CONTROL MODULE SMA NA X

CORE PROTECTION CALCULATOR OPERATORS MODULE SMB NA X

PLANT PROTECTION SYSTEM REMOTE CONTROL MODULE SMB NA X

CORE PROTECTION CALCULATOR OPERATORS MODULE SMC NA X

PLANT PROTECTION SYSTEM REMOTE CONTROL MODULE SMC NA X

CORE PROTECTION CALCULATOR OPERATORS MODULE SMD NA X

PLANT PROTECTION SYSTEM REMOTE CONTROL MODULE SMD NA X

  • Scales linear unless otherwise stated.

Security-Related Information Withheld Under 10 CFR 2.390

WSES-FSAR-UNIT-3 Table 7.5-1 (Sheet 9 of 27) Revision 10 (10/99)

PANEL: CP ENGINEERED SAFETY FEATURES PANEL INDICATORS Tag No Service Channel Scale - Units RPS ESF PPDI ESSI STM GEN NO. 1 PRES SMB 0-1200 PSIA X

X X

STM GEN NO. 1 PRES PRESS SET POINT SMB 0-1200 PSIA X

X X

STM GENERATOR 1 DOWNCOMER LEVEL SMB 0-100 %

X X

X STM GENERATOR 2 DOWNCOMER LEVEL SMB 0-100 %

X X

X STM GEN NO. 2 PRES SMB 0-1200 PSIA X

X X

STM GEN NO. 2 PRES PRESS SET POINT SMB 0-1200 PSIA X

X X

STM GEN NO. 1 PRES SMA 0-1200 PSIA X

X X

STM GEN NO. 1 PRES PRESS SET POINT SMA 0-1200 PSIA X

X X

STM GENERATOR 1 DOWNCOMER LEVEL SMA 0-100 %

X X

X STM GENERATOR 2 DOWNCOMER LEVEL SMA 0-100 %

X X

X STM GEN NO. 2 PRES SMA 0-1200 PSIA X

X X

STM GEN NO. 2 PRES PRESS SET POINT SMA 0-1200 PSIA X

X X

Security-Related Information Withheld Under 10 CFR 2.390

WSES-FSAR-UNIT-3 Table 7.5-1 (Sheet 10 of 27) Revision 10 (10/99)

PANEL: CP ENGINEERED SAFETY FEATURES PANEL INDICATORS Tag No Service Channel Scale - Units RPS ESF PPDI ESSI CONT SUMP LEVEL SA 0-30(a) FT X

STM GENERATOR 1 PRESS SMD 0-1200 PSIA X

X X

STM GEN NO. 1 PRES PRESS SET POINT SMD 0-1200 PSIA X

X X

STM GENERATOR 1 DOWNCOMER LEVEL SMD 0-100 %

X X

X STM GENERATOR 2 DOWNCOMER LEVEL SMD 0-100 %

X X

X STM GEN NO. 2 PRES SMD 0-1200 PSIA X

X X

STM GEN NO. 2 PRES PRESS SET POINT SMD 0-1200 PSIA X

X X

STM GEN NO. 1 PRES SMC 0-1200 PSIA X

X X

STM GEN NO. 1 PRES PRESS SET POINT SMC 0-1200 PSIA X

X X

STM GENERATOR 1 DOWNCOMER LEVEL SMC 0-100 %

X X

X STM GENERATOR 2 DOWNCOMER LEVEL SMC 0-100 %

X X

X STM GEN NO. 2 PRES SMC 0-1200 %

X X

X STM GEN NO. 2 PRES PRESS SET POINT SMC 0-1200 %

X X

X SHDN HX A CCW FLOW SA 0-7000 GPM X

X CCW HDR A TEMP SA 50-130 F X

X Security-Related Information Withheld Under 10 CFR 2.390

WSES-FSAR-UNIT-3 Table 7.5-1 (Sheet 11 of 27) Revision 10 (10/99)

PANEL: CP ENGINEERED SAFETY FEATURES PANEL INDICATORS Tag No Service Channel Scale - Units RPS ESF PPDI ESSI CCW HDR A FLOW SA 0-10,000 GPM X

X CCW HDR A PRES SA 0-150 PSIG X

X COND STORAGE POOL LEVEL SA 0-100 %

X X

SHUTDOWN COOLING HX INLET PRESS SA 0-550 PSIG X

X SHDWN HX OUTLET TEMP SA 0-400°F X

LPSI PUMP A OUTLET WATER TO SHUTDOWN HX A SA 0-400°F X

LPSI HEADER A TEMP SA 0-400°F X

CONTAINMENT SPRAY PUMP A DISCH PRESS SA 0-350 PSIG X

CONTAINMENT SPRAY HDR A FLOW SA 0-2500 GPM X

EFP A DISCH PRESS SA 0-1500 PSIG X

EMERG FW TO SG 1 FLOW SA 0-800 GPM X

CCW SURGE TANK LVL SA 0-100%

X X

CCW SURGE TANK LVL SB 0-100%

X X

SHDN HX CCW FLOW SB 0-7000 GPM X

X CCW HDR B TEMP SB 50-130 F X

X Security-Related Information Withheld Under 10 CFR 2.390

WSES-FSAR-UNIT-3 Table 7.5-1 (Sheet 12 of 27) Revision 10 (10/99)

PANEL: CP ENGINEERED SAFETY FEATURES PANEL INDICATORS Tag No Service Channel Scale - Units RPS ESF PPDI ESSI CCW HDR B FLOW SB 0-10000 GPM X

X CCW HDR B PRES SB 0-150 PSIG X

X CONDENSATE STORAGE POOL LEVEL SB 0-100 %

X X

SHUTOWN COOLING HX B INLET PRESS SB 0-550 PSIG X

SHDWN HX B OUTLET TEMP SB 0-400 F X

SHDWN HX B TEMP SB 0-400 F X

LPSI HDR B TEMP SB 0-400 F X

CONTAINMENT SPRAY PUMP B DISCH PRESS SB 0-350 PSIG X

CONTAINMENT SPRAY FLOW SB 0-2500 GPM X

EFP B DISCH PRESS SB 0-1500 PSIG X

EMERG FW TO SG 2 FLOW SB 0-800 GPM X

EFP A/B DISCH PRESS SAB 0-1500 PSIG X

MN STM TO EFPT PRESS SAB 0-1300 PSIG X

EMERG FW PMP SPEED TURB DRIVEN SAB 0-6000 RPM X

WET CLG TWR A BASN SA 0-100 %

X Security-Related Information Withheld Under 10 CFR 2.390

WSES-FSAR-UNIT-3 Table 7.5-1 (Sheet 13 of 27) Revision 10 (10/99)

PANEL: CP ENGINEERED SAFETY FEATURES PANEL INDICATORS Tag No Service Channel Scale - Units RPS ESF PPDI ESSI WET CLG TWR B BASN SB 0-100 %

X LPSI PUMP A MOTOR AMPS SA 0-100A X

LPSI PUMP B MOTOR AMPS SB 0-100A X

RCS COLD LEG 2A TEMPERATURE SA 50-750°F X

RCS COLD LEG 1B TEMPERATURE SB 50-750°F X

RCS HOT LEG 1 TEMPERATURE SB 50-750°F X

RCS HOT LEG 1 PRESSURE SB 0-3000 PSIA X

SATURATION MARGIN TEMPERATURE SB 200-50°F (SUBC) - (SUPH)

X SHUTDOWN HX B INLET PRESSURE SB 0-600 PSIG X

STEAM GEN. NO. 1 LEVEL (WIDE RANGE)

SA 0-100 %

X STEAM GEN. NO. 1 LEVEL (WIDE RANGE)

SA 0-100 %

X RCS LOOP 2 SHUTDOWN FLOW SA 0-5500 GPM X

RCS HOT LEG 2 TEMPERATURE SA 50-750°F X

Security-Related Information Withheld Under 10 CFR 2.390

WSES-FSAR-UNIT-3 Table 7.5-1 (Sheet 14 of 27) Revision 11 (05/01)

PANEL: CP ENGINEERED SAFETY FEATURES PANEL INDICATORS Tag No Service Channel Scale - Units RPS ESF PPDI ESSI STEAM GEN. NO. 2 PRESSURE SB 0-1200 PSIA X

STEAM GEN. NO. 1 LEVEL (WIDE RANGE)

SB 0-100 %

X STEAM GEN. NO. 2 LEVEL (WIDE RANGE)

SB 0-100 %

X PRESSURIZER LEVEL SA 0-100 %

X SATURATION MARGIN TEMPERATURE SA 200-50 F (SUBC) - (SUPH)

X RCS LOOP 1 SHUTDOWN FLOW SB 0-5500 GPM X

SI HOT LEG 1 LEAKAGE PRESS SA 0-3000 PSIG X

SI HOT LEG 2 LEAKAGE PRESS SB 0-3000 PSIG X

RWS POOL LEVEL (A)

SA 0-100 %

X RWS POOL LEVEL (B)

SB 0-100 %

X Security-Related Information Withheld Under 10 CFR 2.390

WSES-FSAR-UNIT-3 Table 7.5-1 (Sheet 15 of 27) Revision 9 (12/97)

PANEL: CP ENGINEERED SAFETY FEATURES PANEL INDICATORS Tag No Service Channel Scale - Units RPS ESF PPDI ESSI

LPSI FLOW CONT VA 2SI-V1541A2 (SI-635)-POS. IND SA 0-100 % OPEN X

X HPSI FLOW CONT VA 2SI-V1542A3 (SI-637)-POS. IND SA 0-100 % OPEN X

X LPSI FLOW CONT VA 2SI-V1549A1 (SI-615)-POS. IND SB 0-100 % OPEN X

X HPSI FLOW CONT VA 2SI-V1550A1 (SI-617)-POS. IND SA 0-100 % OPEN X

X HPSI FLOW CONT VA 2SI-V1548A4 (SI-627)-POS. IND SA 0-100 % OPEN X

X HPSI FLOW CONT VA 2SI-V1548A4 (SI-647)-POS. IND SA 0-100 % OPEN X

X LPSI FLOW CONT VA 2SI-V1539B1 (SI-625)-POS. IND SB 0-100 % OPEN X

X HPSI FLOW CONT VA 2SI-V1540B2 (SI-626)-POS. IND SB 0-100 % OPEN X

X LPSI FLOW CONT VA 2SI-V1544B4 (SI-645)-POS. IND SA 0-100 % OPEN X

X HPSI FLOW CONT VA 2SI-V1544B4 (SI-646)-POS. IND SB 0-100 % OPEN X

X HPSI FLOW CONT VA 2SI-V1545B1 (SI-636)-POS. IND SB 0-100 % OPEN X

X HPSI FLOW CONT VA 2SI-V1545B1 (SI-616)-POS. IND SB 0-100 % OPEN X

X SHUTDOWN COOLING FLOW CONTROL VALVE 2SI-FM318A (SI-657)

SA 0-100 % OPEN X

SHUTDOWN COOLING FLOW CONTROL VALVE 2SI-FM349B (SI-656)

SB 0-100 % OPEN X

Security-Related Information Withheld Under 10 CFR 2.390

WSES-FSAR-UNIT-3 Table 7.5-1 (Sheet 16 of 27)

Revision 306 (05/12)

PANEL: CP ENGINEERED SAFETY FEATURES PANEL RECORDERS Tag No Service Channel Scale - Units RPS ESF PPDI ESSI RED TRACE - SG #1 PRESS GREEN TRACE - SG #2 PRES SMA SMA 0-1200 PSIA 0-1200 PSIA X

X X

X RED TRACE - SG #1 LEVEL GREEN TRACE - SG #2 LEVEL SMA SMA 0-100 %

0-100 %

X X

X X

RED TRACE - SHTDN HX A INLET PRESS GREEN TRACE - SPARE SA 0-550 PSIG X

RED TRACE - SHTDN HX A OUTLET TEMP GREEN TRACE - SPARE SA 0-400F X

RED TRACE - LPSI PUM 'A' OUTLET WATER TO SHTDN HX A GREEN TRACE - LPSI HDR A SA SA 0-400F 0-400F X

X RED TRACE - LPSI PUMP B OUTLET WATER TO SHTDN HX A GREEN TRACE - LPSI HDR B SB SB 0-400F 0-400F X

X RED TRACE - CONTAINMENT PRESS GREEN TRACE SB 0-70 PSIA X

GREEN TRACE - SIS SUMP WATER LEVEL SB 0-16 FT X

Security-Related Information Withheld Under 10 CFR 2.390

WSES-FSAR-UNIT-3 Table 7.5-1 (Sheet 17 of 27)

PANEL: CP ENGINEERED SAFETY FEATURES PANEL MISCELLANEOUS EQUIPMENT Tag No Service Channel Scale - Units RPS ESF PPDI ESSI ELECTRONIC MANUAL LOADER SA NA X

SERVICE - EMERGENCY FEEDWATER TO STEAM GEN NO. 1 VALVE 2FW-V852A ELECTRONIC MANUAL LOADER SA NA X

SERVICE - EMERGENCY FEEDWATER TO STEAM GEN NO. 1 VALVE 2FW-V853A ELECTRONIC MANUAL LOADER SB NA X

SERVICE - EMERGENCY FEEDWATER TO STEAM GEN NO. 2 VALVE 2FW-V851B MAIN STEAM ATMOSPHERIC DUMP VALVE 2 MS-PM 629A SA NA X

MAIN STEAM ATMOSPHERIC DUMP VALVE 2 MS-PM 630B SB NA X

Security-Related Information Withheld Under 10 CFR 2.390

WSES-FSAR-UNIT-3 Table 7.5-1 (Sheet 18 of 27) Revision 10 (10/99)

PANEL: CP HVAC CONTROL PANEL INDICATORS Tag No Service Channel Scale - Units RPS ESF PPDI ESSI WTR CHILLER WC-1 (3A-SA) CHILLED WTR INLET TEMP SA 0-110°F X

X WTR CHILLER WC-1 (3A-SA) CHILLED WTR OUTLET TEMP SA 0-110°F X

X WTR CHILLER WC-1 (3A-SA) CCW INLET TEMP SA 40-150°F X

X WTR CHILLER WC-1 (3A-SA) CCW OUTLET TEMP SA 40-150°F X

X WTR CHILLER WC-1 (3B-SB) CHILLED WTR INLET TEMP SB 0-110°F X

X WTR CHILLER WC-1 (3B-SB) CHILLED WTR OUTLET TEMP SB 0-110°F X

X WTR CHILLER WC-1 (3B-SB) CCW INLET TEMP SB 40-150°F X

X WTR CHILLER WC-1 (3B-SB) CCW OUTLET TEMP SB 40-150°F X

X WTR CHILLER WC-1 (3C-SA/B) CHILLED WTR INLET TEMP SAB 0-110°F X

X WTR CHILLER WC-1 (3C-SA/B) CHILLED WTR OUTLET TEMP SAB 0-110°F X

X WTR CHILLER WC-1 (3C-SA/B) CCW INLET TEMP SAB 40-150°F X

X WTR CHILLER WC-1 (3C-SA/B) CCW OUTLET TEMP SAB 40-150°F X

X AH-1 (3C-SA) CCW INLET TEMP SA 40-150°F X

X AH-1 (3C-SA) CCW OUTLET TEMP SA 40-240°F X

X AH-1 (3A-SA) CCW INLET TEMP SA 40-150°F X

X Security-Related Information Withheld Under 10 CFR 2.390

WSES-FSAR-UNIT-3 Table 7.5-1 (Sheet 19 of 27)

Revision 11-A (02/02)

PANEL: CP HVAC CONTROL PANEL INDICATORS Tag No Service Channel Scale - Units RPS ESF PPDI ESSI AH-1 (3A-SA) CCW OUTLET TEMP SA 40-240°F X

X AH-1 (3D-SB) CCW INLET TEMP SB 40-150°F X

X AH-1 (3D-SB) CCW OUTLET TEMP SB 40-240F X

X AH-1 (3B-SB) CCW INLET TEMP SB 40-150°F X

X AH-1 (3B-SB) CCW OUTLET TEMP SB 40-240°F X

X CONTROL ROOM AMBIENT DIFF PRESSURE SA

(-)0.5-0-(+)0.5 in H20 X

X CONTROL ROOM AMBIENT DIFF PRESSURE SB

(-)0.5-0-(+)0.5 in H20 X

X DG "A" ROOM TEMP SA 40-140°F X

DG "B" ROOM TEMP SB 40-140°F X

WTR CHILLER WC-1 (3A-SA) CCW INLET PRESS SA 0-125 PSIG X

X WTR CHILLER WC-1 (3A-SA) CCW OUTLET PRESS SA 0-125 PSIG X

X WTR CHILLER WC-1 (3A-SA) CHILLED WTR INLET PRESS SA 0-100 PSIG X

X WTR CHILLER WC-1 (3A-SA) CHILLED WTR OUTLET PRESS SA 0-100 PSIG X

X Security-Related Information Withheld Under 10 CFR 2.390

WSES-FSAR-UNIT-3 Table 7.5-1 (Sheet 20 of 27)

Revision 11-A (02/02)

PANEL: CP HVAC CONTROL PANEL INDICATORS Tag No Service Channel Scale - Units RPS ESF PPDI ESSI WTR CHILLER WC-1 (3B-SB) CCW INLET PRESS SB 0-125 PSIG X

X WTR CHILLER WC-1 (3B-SB) CCW OUTLET PRESS SB 0-125 PSIG X

X WTR CHILLER WC-1 (3B-SB) CHILLED WTR INLET PRESS SB 0-100 PSIG X

X WTR CHILLER WC-1 (3B-SB) CHILLED WTR OUTLET PRESS SB 0-100 PSIG X

X WTR CHILLER WC-1 (3C-SA/B) CCW INLET PRESS SAB 0-125 PSIG X

X WTR CHILLER WC-1 (3C-SA/B) CCW OUTLET PRESS SAB 0-125 PSIG X

X WTR CHILLER WC-1 (3C-SA/B) CHILLED WTR INLET PRESS SAB 0-100 PSIG X

X WTR CHILLER WC-1 (3C-SA/B) CHILLED WTR OUTLET PRESS SAB 0-100 PSIG X

X WTR CHILLER WC-1 (3A-SA) CCW FLOW SA 0-1000 GPM X

X WTR CHILLER WC-1 (3A-SA) CHILLED WTR FLOW SA 0-600 GPM X

X WTR CHILLER WC-1 (3B-SB) CCW FLOW SB 0-1000 GPM X

X WTR CHILLER WC-1 (3B-SB) CHILLED WTR FLOW SB 0-600 GPM X

X WTR CHILLER WC-1 (3C-SA/B) CCW FLOW SAB 0-1000 GPM X

X WTR CHILLER WC-1 (3C-SA/B) CHILLED WTR FLOW SAB 0-600 GPM X

X CONTROL ROOM NORTH EMERG AIR INTAKE FLOW SA 0-250 CFM X

Security-Related Information Withheld Under 10 CFR 2.390

WSES-FSAR-UNIT-3 Table 7.5-1 (Sheet 21 of 27)

PANEL: CP HVAC CONTROL PANEL INDICATORS Tag No Service Channel Scale - Units RPS ESF PPDI ESSI CONTROL ROOM SOUTH EMERG AIR INTAKE FLOW SA 0-250 CFM X

CONTROL ROOM NORTH EMERG AIR INTAKE FLOW SB 0-250 CFM X

CONTROL ROOM SOUTH EMERG AIR INTAKE FLOW SB 0-250 CFM X

CF CLR 1A CCW FLOW SA 0-1500 GPM X

X CF CLR 2A CCW FLOW SA 0-1500 GPM X

X CF CLR 1B CCW FLOW SB 0-1500 GPM X

X CF CLR 2B CCW FLOW SB 0-1500 GPM X

X Security-Related Information Withheld Under 10 CFR 2.390

WSES-FSAR-UNIT-3 Table 7.5-1 (Sheet 22 of 27)

Revision 306 (05/12)

PANEL: CP HVAC CONTROL PANEL RECORDERS Tag No Service Channel Scale - Units RPS ESF PPDI ESSI RED TRACE - CONTMT FAN COOLER AH-1 (3A-SA) INLET TEMP SA 0-450F X

X GREEN TRACE - CONTMT FAN COOLER AH-1 (3A-SA) EXH TEMP SA X

X RED TRACE - CONTMT FAN COOLER AH-1 (3C-SA) INLET TEMP SA 0-450F X

GREEN TRACE - CONTMT FAN COOLER AH-1 (3C-SA) EXH TEMP SA X

RED TRACE - CONTMT FAN COOLER AH-1 (3B-SB) INLET TEMP SB 0-450F X

GREEN TRACE - CONTMT FAN COOLER AH-1 (3B-SB) EXH TEMP SB X

RED TRACE - CONTMT FAN COOLER AH-1 (3D-SB) EXH TEMP SB 0-450F X

GREEN TRACE - CONTMT FAN COOLER AH-1 (3D-SB) EXH TEMP SB X

RED TRACE - CONTMT FAN COOLER AH-1 (3A-SA) UNIT DIFF PRESS SA 0-10 in. H2O x

GREEN TRACE - CONTMT FAN COOLER AH-1 (3C-SA) UNIT DIFF PRESS SA X

RED TRACE - CONTMT FAN COOLER AH-1 (3B-SB) UNIT DIFF PRESS SB 0-10 in. H2O X

GREEN TRACE - CONTMT FAN COOLER AH-1 (3D-SB) UNIT DIFF PRESS SB X

RED TRACE - SBVS FILTER TRAIN A DIFF PRESS SA 0.15 in. H2O X

X GREEN TRACE - FHB EMERG FILTER TRAIN A DIFF PRESS Security-Related Information Withheld Under 10 CFR 2.390

WSES-FSAR-UNIT-3 Table 7.5-1 (Sheet 23 of 27)

Revision 306 (05/12)

PANEL: CP HVAC CONTROL PANEL RECORDERS Tag No Service Channel Scale - Units RPS ESF PPDI ESSI RED TRACE - CONTR ROOM EMERG FILTER TRAIN A DIFF PRESS SA 0-15 in. H2O X

X GREEN TRACE - CVAS FILTER TRAIN A DIFF PRESS RED TRACE - SBVS FILTER TRAIN B DIFF PRESS SB 0-15 in. H2O X

X GREEN TRACE - FHB EMERG FILTER TRAIN B DIFF PRESS RED TRACE - CONTR ROOM EMERG FILTER TRAIN B DIFF PRESSS SB 0-15 in. H2O X

X GREEN TRACE - CVAS FILTER TRAIN B DIFF PRESS MISCELLANEOUS EQUIPMENT CONTR ROM EMERG INTAKE NO. 1 AIR FLOW SA NA X

X CONTR ROOM EMERG INTAKE NO. 2 AIR FLOW SB NA X

X CONTR ROOM EMERG FILTER UNIT INLET DAMPER D-17 (SA)

SA NA X

X CONTR ROOM EMERG FILTER UNIT INLET DAMPER D-17 (SB)

SB NA X

X FHB FILTER UNIT INLET DAMPER D-29 (SA)

SA NA X

X FHB FILTER UNIT INLET DAMPER D-29 (SB)

SB NA X

X Security-Related Information Withheld Under 10 CFR 2.390

WSES-FSAR-UNIT-3 Table 7.5-1 (Sheet 24 of 27)

Revision 11-A (02/02)

PANEL: CP HYDROGEN AND COOLING TOWER CONTROL PANEL INDICATORS Tag No Service Channel Scale - Units RPS ESF PPDI ESSI H2 RECOMBINER A TEMP SA 0-2000°F X

H2 RECOMBINER A ELECTRIC POWER LOAD SA 0-100 KW X

X COMPONENT COOLING WTR SYS A TEMP SA 50-130°F X

X AUXILIARY COMPONENT COOLING WTR SYS A FLOW SA 0-7500 GPM X

X H2 RECOMBINER B TEMP SB 0-2000°F X

H2 RECOMBINER B ELECTRIC POWER LOAD SB SB 0-100 KW X

COMPONENT COOLING WTR SYS B TEMP SB 50-130°F X

X AUXILIARY COMPONENT COOLING WTR SYS B FLOW SB 0-7500 GPM X

X WET TOWER "A" BASIN TEMP SA 30-110°F X

WET TOWER "B" BASIN TEMP SB 30-110°F X

Security-Related Information Withheld Under 10 CFR 2.390

WSES-FSAR-UNIT-3 Table 7.5-1 (Sheet 25 of 27)

PANEL: CP HYDROGEN AND COOLING TOWER CONTROL PANEL RECORDERS Tag No Service Channel Scale - Units RPS ESF PPDI ESSI H2 ANALYZER A RECORDER SA 0-10%

X H2 ANALYZER B RECORDER SB 0-10%

X Security-Related Information Withheld Under 10 CFR 2.390

WSES-FSAR-UNIT-3 Table 7.5-1 (Sheet 26 of 27)

PANEL: CP HYDROGEN AND COOLING TOWER CONTROL PANEL MISCELLANEOUS Tag No Service Channel Scale - Units RPS ESF PPDI ESSI ESFAS TEST MODULE A SA NA X

AUXILIARY COMPONENT COOLING WTR SYS A TEMP CNTRL VA 3CC-TM290A CONTROL STATION SA 50-130°F X

ESFAS TEST MODULE B SB NA X

AUXILIARY COMPONENT COOLING WTR SYS B TEMP CONTRL VA 3CCTM291B CONTROL STATION SB 50-130°F X

NOTE:

(a) The transmitter for this indicator or recorder has not been tested for a submerged environment, and the equipment is therefore not considered qualified beyond the point of submergence (approximately 17 feet).

Security-Related Information Withheld Under 10 CFR 2.390

WSES-FSAR-UNIT-3 Table 7.5-1 (Sheet 27 of 27) Revision 10 (10/99)

LEGEND PPS

- Plant Protection System



ESF

- Engineered Safeguard Features



ESSI

- ESF Support System Instrumentation PPDI

- Plant Process Display Instrumentation CCW HDR

- Component Cooling Water Header EFW

- Emergency Feedwater LPSI

- Low Pressure Safety Injection HPSI

- High Pressure Safety Injection SG

- Steam Generator HVAC

- Heating, Ventilating and Air Conditioning DG

- Diesel Generator PZR

- Pressurizer STM

- Steam SHDN HX

- Shutdown Heat Exchanger CF CLR

- Containment Fan Cooler CLG TWR

- Cooling Tower RCS

- Reactor Cooling System SBVS

- Shield Building Ventilation System FHB

- Fuel Handling Building CVAS

- Controlled Ventilation Area System RAB

- Reactor Auxiliary Building

WSES-FSAR-UNIT-3 Revision 8 (5/96)



TABLE 7.5-2 WAS DELETED.



WSES-FSAR-UNIT-3 TABLE 7.5-3 (Sheet 1 of 40)

Revision 308 (11/14)

ACCIDENT MONITORING INSTRUMENTATION SERIAL NUMBER VARIABLE RG197 CAT/

TYPE LOOP COMPONENT COMP TYPE LOCATION ENV SEIS QA POWER SUPPLY CLASS RANGE/UNITS NUMBER OF CHANNEL SPDS I/O COMMENTS NEUTRON FLUX B1 ENIINFD0001C2 S

CP-7 A

A A

1E VITAL 2

C26236 REFER TO NOTE 14.

ENIIJI0001C I

2.00E 200%

RC IUR0102A2 R

CP-7 2.00E 200%

RC IUR0102A2 R

CP-7 2.00E 200%

NEUTRON FLUX B1 ENIINFD0003D2 S

RCB A

A A

1E VITAL 2

C26330 REFER TO NOTE 14.

ENIIJI0001D I

CP-7 2.00E 200%

RC IUR0102B2 R

CP-7 2.00E 200%

CTRL ROD POSI B3 CEDIREEDXXXX-1 CEDIREEDXXXX-2 S

S RCB RCB N/A A

A 1E VITAL FULL IN-NOT FULL IN N/A N/A XXXX=0001 TO 0091, DISP ON CP2(CRT, & MIMIC DISP PANEL)

REFER TO NOTE 14.

RCS COLD LEG WATER TEMPERATURE A1 B1 B3 RC ITE0112CA2 RC ITR0115 S

R RCB CP-2 A

A A

1E VITAL 50-750 DEGF 1 FOR COLD LEG 1A C26239 IND ON QSPDS RCS COLD LEG WATER TEMPERATURE A1 B1 B3 RC ITE0112CB2 RC ITI0112CB S

I RCB CP-8 A

A A

1E VITAL 50-750 DEGF 1 FOR COLD LEG 1B C26333 IND ON QSPDS RCS COLD LEG WATER TEMPERATURE A1 B1 B1 RC ITE0122CA2 RC ITI0122CA RC ITR0125 S

I R

RCB CP-8 CP-2 A

A A

1E VITAL 50-750 DEGF 50-750 DEGF 1 FOR COLD LEG 2A C26240 IND ON QSPDS RCS COLD LEG WATER TEMPERATURE A1 B1 B3 RC ITE0122CB2 S

RCB A

A A

1E VITAL 1 FOR COLD LEG 2B C26332 IND ON QSPDS RCS COLD LEG TEMPERATURE B1 REFER TO SERIAL NO. 4.

RCS HOT LEG WATER TEMPERATURE A1 B1 RC ITE0112HB2 RC ITI0112HB S

I RCB CP-8 A

A A

1E VITAL 50-750 DEGF 1 PER HOT LEG 1 & 2 N/A RCS HOT LEG WATER TEMPERATURE A1 B1 RC ITE0122HA2 RC ITI0122HA RC ITR0112-2 S

I R

RCB CP-8 CP-2 A

A A

1E VITAL 50-750 DEGF 50-750 DEGF 1 PER HOT LEG 1 & 2 N/A IND ON QSPDS.

RCS HOT LEG WATER TEMPERATURE A1 B1 RC ITE0122HA1 RC ITR0102HA S

R RCB CP-2 A

A A

1E VITAL 525-675 DEGF 1 PER HOT LEG 1 & 2 C26426 C26331 REFER TO NOTE 14 FOR THE RECORDER ONLY.

Security-Related Information Withheld Under 10 CFR 2.390

WSES-FSAR-UNIT-3 TABLE 7.5-3 (Sheet 2 of 40) Revision 11-A (02/02)

ACCIDENT MONITORING INSTRUMENTATION SERIAL NUMBER VARIABLE RG197 CAT/

TYPE LOOP COMPONENT COMP TYPE LOCATION ENV SEIS QA POWER SUPPLY CLASS RANGE/UNITS NUMBER OF CHANNEL SPDS I/O COMMENTS RCS HOT LEG WATER TEMPERATURE A1 B1 RC ITE0112HA1 RC ITR0102HA S

R RCB CP-2 A

A A

1E VITAL 525-675 DEGF 1 PER HOT LEG 1 & 2 C26238 REFER TO NOTE 14 FOR THE RECORDER ONLY.

RCS HOT LEG WATER TEMPERATURE A1 B1 RC ITE0112HA2 RC ITR0112-1 S

R RCB CP-2 A

A A

1E VITAL 50-750 DEGF 1 PER HOT LEG 1 & 2 N/A IND ON QSPDS.

RCS HOT LEG WATER TEMPERATURE A1 B1 RC ITE0122HB2 S

RCB A

A A

1E VITAL 1 PER HOT LEG 1 & 2 N/A IND ON QSPDS.

RCS PRESSURE A1 B1 C1 RC IPT0102A RC IPI0102A RC IPR0102A S

I R

RCB CP-7 CP-7 A

A A

1E VITAL 0-3000 PSIA 0-3000 PSIA 0-3000 PSIA 6

N/A RCS PRESSURE A1 B1 C1 RC IPT0102B RC IPI0102B S

I RCB CP-7 A

A A

1E VITAL 0-3000 PSIA 0-3000 PSIA 6

N/A RCS PRESSURE A1 B1 C1 RC IPT0102C RC IPI0102C S

I RCB CP-7 A

A A

1E VITAL 0-3000 PSIA 0-3000 PSIA 6

N/A RCS PRESSURE A1 B1 C1 RC IPT0102D RC IPI0102D S

I RCB CP-7 A

A A

1E VITAL 0-3000 PSIA 0-3000 PSIA 6

N/A RCS PRESSURE A1 B1 C1 RC IPT9120A S

RCB A

A A

1E VITAL 0-4000 PSIG 6

N/A IND ON QSPDS. REFER TO NOTE 2.

RCS PRESSURE A1 B1 C1 RC IPT9120B S

RCB A

A A

1E VITAL 0-4000 PSIG 6

N/A IND ON QSPDS. REFER TO NOTE 2.

RCS PRESSURE B1 REFER TO SERIAL #7.

RCS PRESSURE C1 REFER TO SERIAL #7.

RCS PRESSURE C1 REFER TO SERIAL #7.

CORE EXIT TEMPERATURE B3 C1 RC IUR0102A1 RC ITE0093-L16 R

S CP-7 RCB A

A A

1E VITAL 200-2300 DEGF 2

C26417 C26510 IND ON QSPDS. REFER TO FSAR SECTIONS 1.9A.3.3 AND Security-Related Information Withheld Under 10 CFR 2.390

WSES-FSAR-UNIT-3 TABLE 7.5-3 (Sheet 3 of 40)

Revision 304 (06/10)

ACCIDENT MONITORING INSTRUMENTATION SERIAL NUMBER VARIABLE RG197 CAT/

TYPE LOOP COMPONENT COMP TYPE LOCATION ENV SEIS QA POWER SUPPLY CLASS RANGE/UNITS NUMBER OF CHANNEL SPDS I/O COMMENTS RC ITE0093-G18 RC ITE0093-E20 RC ITE0094-G13 RC-ITE0095-A14 RC ITE0095-C9 RC ITE0095-E6 RC ITE0096-G2 RC-ITE0096-C4 RC ITE0098-T2 RC ITE0098-L9 RC ITE0098-R4 RC ITE0100-T16 RC ITE0101-W18 RC ITE0092-G20 RC ITE0093 G16 RC ITE0093-L13 RC ITE0094-G9 RC ITE0094-C16 RC ITE0095-E9 RC ITE0096-E4 RC ITE0096-A8 RC ITE0097-L2 RC ITE0098-R6 RC ITE0099-W6 RC ITE0100-W13 RC ITE0100-T13 RC ITE0101-T18 S

S S

S S

S S

S S

S S

S S

S S

S S

S S

S S

S S

S S

S S

RCB RCB RCB RCB RCB RCB RCB RCB RCB RCB RCB RCB RCB RCB RCB RCB RCB RCB RCB RCB RCB RCB RCB RCB RCB RCB RCB 1.9A.4.1 AND FIGURE 1.9A-9 FOR CORE EXIT THERMOCUPLES CONFIGURATIONS. REFER TO NOTE 14 FOR THE RECORDER ONLY.

CORE EXIT TEMPERATURE B3 C1 RC IUR0102B1 RC ITE0092-L18 RC ITE0092-R16 RC ITE0093-E18 R

S S

S CP-7 RCB RCB RCB A

A A

1E VITAL 200-2300 DEGF 2

N/A IND ON QSPDS. REFER TO FSAR SECTIONS 1.9A.3.3 AND 1.9A.4.1 AND FIGURE 1.9A-9 FOR CORE EXIT THERMOCOUPLES CONFIGURATION. REFER TO NOTE 14 FOR THE RECORDER ONLY.

RC ITE0094-E13 RC ITE0095-C13 RC ITE0096-C6 S

S S

RCB RCB RCB REFER TO NOTE 20 Security-Related Information Withheld Under 10 CFR 2.390

WSES-FSAR-UNIT-3 TABLE 7.5-3 (Sheet 4 of 40)

Revision 13 (04/04)

ACCIDENT MONITORING INSTRUMENTATION SERIAL NUMBER VARIABLE RG197 CAT/

TYPE LOOP COMPONENT COMP TYPE LOCATION ENV SEIS QA POWER SUPPLY CLASS RANGE/UNITS NUMBER OF CHANNEL SPDS I/O COMMENTS RC ITE0097-L4 RC ITE0098-T4 RC ITE0098-L6 RC ITE0099-R9 RC ITE0100-W9 RC ITE0101-Y14 RC ITE0101-W16 RC ITE0101-R20 RC ITE0092-R18 RC ITE0092-L20 RC ITE0094-E16 RC ITE0094-C18 RC ITE0096-E2 RC ITE0097-G6 RC ITE0097-R2 RC ITE0097-G4 RC ITE0099-W4 RC ITE0099-T9 RC ITE0099-R13 RC ITE0099-T6 RC ITE0100-Y8 RC ITE0101-T20 S

S S

S S

S S

S S

S S

S S

S S

S S

S S

S S

S RCB RCB RCB RCB RCB RCB RCB RCB RCB RCB RCB RCB RCB RCB RCB RCB RCB RCB RCB RCB RCB RCB Refer to Note 20 Refer to Note 20 CORE EXIT TEMPERATURE C1 REFER TO SERIAL #11.

COOLANT LEVEL IN B1 RC ILR2103A1 RC ILR2103A2 R

R CP-7 CP-7 A

A A

1E VITAL 0-100%

0-100%

2 N/A IND ON QSPDS. RECORDERS PROVIDE INDICATION OF LEVEL REACTOR RC IHTE0111A RC IHTE0121A RC IHTE0131A RC IHTE0141A RC IHTE0211A RC IHTE0221A RC IHTE0231A RC IHTE0241A RC IUTE0111A RC IUTE0121A RC IUTE0131A RC IUTE0141A RC IUTE0211A RC IUTE0221A RC IUTE0231A RC IUTE0241A S

S S

S S

S S

S S

S S

S S

S S

S RCB RCB RCB RCB RCB RCB RCB RCB RCB RCB RCB RCB RCB RCB RCB RCB FROM BOTTOM OF HOT LEG TO TOP OF VESSEL. REFER TO NOTE 14 FOR THE RECORDERS ONLY.

Security-Related Information Withheld Under 10 CFR 2.390

WSES-FSAR-UNIT-3 TABLE 7.5-3 (Sheet 5 of 40) Revision 11-A (02/02)

ACCIDENT MONITORING INSTRUMENTATION SERIAL NUMBER VARIABLE RG197 CAT/

TYPE LOOP COMPONENT COMP TYPE LOCATION ENV SEIS QA POWER SUPPLY CLASS RANGE/UNITS NUMBER OF CHANNEL SPDS I/O COMMENTS COOLANT LEVEL IN REACTOR B1 RC ILR2103B1 RC ILR2103B2 RC IHTE0111B RC IHTE0121B RC IHTE0131B RC IHTE0141B RC IHTE0211B RC IHTE0221B RC IHTEO231B RC IHTE0241B RC IUTE0111B RC IUTE0121B RC IUTE0131B RC IUTE0141B R

R S

S S

S S

S S

S S

S S

S CP-7 CP-7 RCB RCB RCB RCB RCB RCB RCB RCB RCB RCB RCB RCB A

A A

1E VITAL 0-100%

0-100%

2 N/A IND ON QSPDS. RECORDERS PROVIDE INDICATION OF LEVEL FROM BOTTOM OFHOT LEG TO TOP OF VESSEL.

REFER TO NOTE 14 FOR THE RECORDERS ONLY.

RC IUTE0211B RC IUTE0221B RC IUTE0231B RC IUTE0241B S

S S

S RCB RCB RCB RCB DEGREE OF SUBCOOLING B2 RC ITI2200A1 RC ITI2200A2 RC IUR0101A1 RC IUR0101A2 RC ITE0112HA2 RC IPT0106A I

I R

R S

S CP-2 CP-8 CP-7 CP-7 RCB RCB A

A A

1E VITAL 200 SC-50SH DEGF 200 SC-50SH DEGF 200 SC-800SH DEGF 200 SC-800SH DEGF 0-3000 PSIA 2

C26506 C26413 C26508 C26415 INPUTS FROM TEMP SENSORS OFRCS HOT & COLD LEG ARE ALSO USED IN CALCULATING DEG. OFSUBCOOLING. IND ON QSPDS. REFER TO NOTE 14 FOR THE RECORDERS ONLY.

DEGREE OF SUBCOOLING B2 RC ITI2200B1 RC ITI2200B2 RC IUR0101B1 RC IUR0101B2 RC ITE0122HB2 RC IPT0106B I

I R

R S

S CP-2 CP-8 CP-7 CP-7 RCB RCB A

A A

1E VITAL 200 SC-50SH DEGF 200 SC-50SH DEGF 200 SC-800SH DEGF 200 SC-800SH DEGF 0-3000 PSIA 2

N/A INPUTS FROM TEMP SENSORS OFRCS HOT & COLD LEG ARE ALSO USED IN CALCULATING DEG. OF SUBCOOLING. IND ON QSPDS. REFER TO NOTE 14 FOR THE RECORDERS ONLY.

RCS PRESSURE B1 REFER TO SERIAL #7.

CONTAINMENT SUMP LEVEL WIDE RANGE B1 C1 SI ILT7145A SI ILI7145A S

I RCB CP-8 A

A A

1E VITAL 0-16 FTW 0-16 FTW 2

N/A IND ON QSPDS. REFER TO NOTE 14.

CONTAINMENT SUMP LEVEL WIDE RANGE B1 C1 SI ILT7145B SI ILR7145B S

R RCB CP-8 A

A A

1E VITAL 0-16 FTW 0-16 FTW 2

N/A REFER TO NOTE 14 FOR THE RECORDER ONLY.

Security-Related Information Withheld Under 10 CFR 2.390

WSES-FSAR-UNIT-3 TABLE 7.5-3 (Sheet 6 of 40) Revision 11-A (02/02)

ACCIDENT MONITORING INSTRUMENTATION SERIAL NUMBER VARIABLE RG197 CAT/

TYPE LOOP COMPONENT COMP TYPE LOCATION ENV SEIS QA POWER SUPPLY CLASS RANGE/UNITS NUMBER OF CHANNEL SPDS I/O COMMENTS CONTAINMENT SUMP LEVEL NARROW RANGE B2 C2 SP ILT6705A SP ILI6705A S

I RCB CP-8 A

A A

1E VITAL 0-15 FTW 0-15 FTW 2

C26235 IND ON QSPDS CONTAINMENT SUMP LEVEL NARROW RANGE B2 C2 SP ILT6705B SP ILR6705B S

R RCB CP-8 A

A A

1E VITAL 0-15 FTW 0-15 FTW 2

N/A CNTMT SUMP WATER LEVEL C1 C2 REFER TO SERIAL #16.

CONTAINMENT PRESSURE A1 B1 C1 ESFIPT6750A ESFIP16750A S

I RCB CP-8 A

A A

1E VITAL 0-70 PSIA 0-70 PSIA 2

N/A CONTAINMENT DESIGN PRESSURE IS 44 PSIG.

REFER TO NOTE 14.

CONTAINMENT PRESSURE A1 B1 C1 ESFIPT6750B ESFIPR6750B S

R RCB CP-8 A

A A

1E VITAL 0-70 PSIA 0-70 PSIA 2

N/A CONTAINMENT DESIGN PRESSURE IS 44 PSIG.

REFER TO NOTE 14 FOR THE RECORDER ONLY.

CNTMNT PRESS.

B1 REFER TO SERIAL #18.

CNTMNT PRESS.

C1 REFER TO SERIAL #18.

CNTMNT ISOL VLV POSITION B1 MS IZS0120A NOT AVAILABLE S

I RB CP-8 B

A A

1E EMERG.

CLOSED NOT CLOSED CLOSED / OPEN 1/VALVE D55002 MS MVAAA120A MAIN STEAM DRAIN. NOTE 3 CNTMNT ISOL VLV POSITION B1 MS IZS0119A NOT AVAILABLE S

I RB CP-8 B

A A

1E EMERG.

CLOSED NOT CLOSED CLOSED / OPEN 1/VALVE D55003 MS MVAAA119A MAIN STEAM DRAIN. NOTE 3 CNTMNT ISOL VLV POSITION B1 MS IZS0120B NOT AVAILABLE S

I RB CP-8 B

A A

1E EMERG.

CLOSED NOT CLOSED CLOSED / OPEN 1/VALVE D55007 MS MVAAA120B MAIN STEAM DRAIN. NOTE 3 CNTMNT ISOL VLV POSITION B1 MS IZS0119B NOT AVAILABLE S

I RB CP-8 B

A A

1E EMERG.

CLOSED NOT CLOSED CLOSED / OPEN 1/VALVE D55008 MS MVAAA119B MAIN STEAM DRAIN. NOTE 3 CNTMNT ISOL VLV POSITION B1 BD IZS0102A2 NOT AVAILABLE S

I RCB CP-8 A

A A

1E EMERG.

CLOSED NOT CLOSED CLOSED / OPEN 1/VALVE D11405 BD MVAAA102A STEAM GENERATOR BLOWDOWN.

NOTE 4 CNTMNT ISOL VLV POSITION B1 BD IZS0103A2 NOT AVAILABLE S

I RB CP-8 A

A A

1E EMERG.

CLOSED NOT CLOSED CLOSED / OPEN 1/VALVE D11406 BD MVAAA103A STEAM GENERATOR BLOWDOWN.

NOTE 4 CNTMNT ISOL VLV POSITION B1 BD IZS0102B2 NOT AVAILABLE S

I RCB CP-8 A

A A

1E EMERG.

CLOSED NOT CLOSED CLOSED / OPEN 1/VALVE D11407 BD MVAAA102B STEAM GENERATOR BLOWDOWN.

NOTE 4 CNTMNT ISOL VLV POSITION B1 BD IZS0103B2 NOT AVAILABLE S

I RB CP-8 A

A A

1E EMERG.

CLOSED NOT CLOSED CLOSED / OPEN 1/VALVE D11408 BD MVAAA103B STEAM GENERATOR BLOWDOWN.

NOTE 4 Security-Related Information Withheld Under 10 CFR 2.390

WSES-FSAR-UNIT-3 TABLE 7.5-3 (Sheet 7 of 40)

Revision 15 (03/07)

ACCIDENT MONITORING INSTRUMENTATION SERIAL NUMBER VARIABLE RG197 CAT/

TYPE LOOP COMPONENT COMP TYPE LOCATION ENV SEIS QA POWER SUPPLY CLASS RANGE/UNITS NUMBER OF CHANNEL SPDS I/O COMMENTS CNTMNT ISOL VLV POSITION B1 IA IZS0909/2 NOT AVAILABLE S

I RB CP-8 A

A A

1E VITAL CLOSED NOT CLOSED CLOSED / OPEN 1/VALVE D61120 IA MVAAA909 INSTRUMENT AIR. NOTE 5. REFER TO NOTE

14.

CNTMNT ISOL VLV POSITION B1 NG IZS0157/2 NOT AVAILABLE S

I RB CP-8 A

A A

1E VITAL CLOSED NOT CLOSED CLOSED / OPEN 1/VALVE D61002 NG MVAAA157 NITROGEN SUPPLY. NOTE 5. REFER TO NOTE 14.

CNTMNT ISOL VLV POSITION B1 CVCIZS0109/2 NOT AVAILABLE S

I RCB CP-4 A

A A

1E VITAL CLOSED NOT CLOSED CLOSED / OPEN 1/VALVE D39108 CVCMVAAA109 CVCS LETDOWN. NOTE 4. REFER TO NOTE 14.

CNTMNT ISOL VLV POSITION B1 CVCIZS0103/2 NOT AVAILABLE S

I RCB CP-4 A

A A

1E VITAL CLOSED NOT CLOSED CLOSED / OPEN 1/VALVE D39104 CVCMVAAA103 CVCS LETDOWN. NOTE 4. REFER TO NOTE 14.

CNTMNT ISOL VLV POSITION B1 PSLIZS0107/2 S

I RB CP-8 A

A A

1E EMERG.

CLOSED NOT CLOSED CLOSED / OPEN 1/VALVE N/A PSLMVAAA107 RCS SAMPLE.

NOTE 4 CNTMNT ISOL VLV POSITION B1 PSLIZ0105/2 NOT AVAILABLE S

I RCB CP-8 A

A A

1E EMERG.

CLOSED NOT CLOSED CLOSED / OPEN 1/VALVE N/A PSLMVAAA105 RCS SAMPLE.

NOTE 4 CNTMNT ISOL VLV POSITION B1 PSLIZS0204/2 NOT AVAILABLE S

I RB CP-8 A

A A

1E EMERG.

CLOSED NOT CLOSED CLOSED / OPEN 1/VALVE N/A PSLMVAAA204 PRESSURIZER SURGE LINE SAMPLE. NOTE 4 CNTMNT ISOL VLV POSITION B1 PSLIZS0203/2 NOT AVAILABLE S

I RCB CP-8 A

A A

1E EMERG.

CLOSED NOT CLOSED CLOSED / OPEN 1/VALVE N/A PSLMVAAA203 PRESSURE SURGE LINE SAMPLE. NOTE 4 CNTMNT ISOL VLV POSITION B1 PSLIZS0304/2 NOT AVAILABLE S

I RB CP-8 A

A A

1E EMERG.

CLOSED NOT CLOSED CLOSED / OPEN 1/VALVE N/A PSLMVAAA304 PRESSURIZER SAMPLE. NOTE 4 CNTMNT ISOL VLV POSITION B1 PSLIZS0303/2 NOT AVAILABLE S

I RCB CP-8 A

A A

1E EMERG.

CLOSED NOT CLOSED CLOSED / OPEN 1/VALVE N/A PSLMVAAA303 PRESSURIZER SAMPLE. NOTE 4 CNTMNT ISOL VLV POSITION B1 GWMIZS0105/2 NOT AVAILABLE S

I RB CP-4 A

A A

1E EMERG.

CLOSED NOT CLOSED CLOSED / OPEN 1/VALVE D41307 GWMMVAAA105 WASTE GAS VENT HEADER. NOTE 4 CNTMNT ISOL VLV POSITION B1 GWMIZS0104/2 NOT AVAILABLE S

I RCB CP-4 A

A A

1E EMERG.

CLOSED NOT CLOSED CLOSED / OPEN 1/VALVE D41306 GWMMVAAA104 WASTE GAS VENT HEADER. NOTE 4 CNTMNT ISOL VLV POSITION B1 SP IZS0106/2 NOT AVAILABLE S

I RB CP-8 A

A A

1E EMERG.

CLOSED NOT CLOSED CLOSED / OPEN 1/VALVE N/A SP MVAAA1O6 CONTAINMENT SUMP PUMP DISCHARGE.

NOTE 4 Security-Related Information Withheld Under 10 CFR 2.390

WSES-FSAR-UNIT-3 TABLE 7.5-3 (Sheet 8 of 40)

Revision 15 (03/07)

ACCIDENT MONITORING INSTRUMENTATION SERIAL NUMBER VARIABLE RG197 CAT/

TYPE LOOP COMPONENT COMP TYPE LOCATION ENV SEIS QA POWER SUPPLY CLASS RANGE/UNITS NUMBER OF CHANNEL SPDS I/O COMMENTS

)

CNTMNT ISOL VLV POSITION B1 SP IZS0105/2 NOT AVAILABLE S

I RCB CP-8 A

A A

1E EMERG.

CLOSED NOT CLOSED CLOSED / OPEN 1/VALVE N/A SP MVAAA105 CONTAINMENT SUMP PUMP DISCHARGE.

NOTE 4 CNTMNT ISOL VLV POSITION B1 BM IZS0110/2 NOT AVAILABLE S

I RB CP-4 A

A A

1E EMERG.

CLOSED NOT CLOSED CLOSED / OPEN 1/VALVE D40119 BM MVAAA110 REACTOR DRAIN TANK OUTLET. NOTE 4 CNTMNT ISOL VLV POSITION B1 BM IZS0109/2 NOT AVAILABLE S

I RCB CP-4 A

A A

1E EMERG.

CLOSED NOT CLOSED CLOSED / OPEN 1/VALVE D40118 BM MVAAA109 REACTOR DRAIN TANK OUTLET. NOTE 4 CNTMNT ISOL VLV POSITION B1 CVCIZS0401/2 NOT AVAILABLE S

I RB CP-4 A

A A

1E EMERG.

CLOSED NOT CLOSED CLOSED / OPEN 1/VALVE D39410 CVCMVAAA401 RCP BLEEDOFF. NOTE 4 CNTMNT ISOL VLV POSITION B1 RC IZS0606/2 NOT AVAILABLE S

I RCB CP-4 A

A A

1E EMERG.

CLOSED NOT CLOSED CLOSED / OPEN 1/VALVE D39411 RC MVAAA606 RCP BLEEDOFF. NOTE 4 CNTMNT ISOL; VLV POSITION B1 CARIZS0201B NOT AVAILABLE S

I RCB CP-18 A

A A

1E EMERG.

CLOSED NOT CLOSED CLOSED / OPEN 1/VALVE D51512 CARMVAAA201B CARS EXHAUST. NOTE 6 CNTMNT ISOL VLV POSITION B1 CARIZS0200B2 NOT AVAILABLE S

I RCB CP-18 A

A A

1E VITAL CLOSED NOT CLOSED CLOSED / OPEN 1/VALVE N/A CARMVAAA200B CARS EXHAUST. NOTE 6. REFER TO NOTE 14.

CNTMNT ISOL VLV POSITION B1 CARIZS0202B2 NOT AVAILABLE S

I RB CP-18 A

A A

1E VITAL CLOSED NOT CLOSED CLOSED / OPEN 1/VALVE N/A CARMVAAA202B CARS EXHAUST. NOTE 6. REFER TO NOTE 14.

CNTMNT ISOL VLV POSITION B1 CARIZS0201A NOT AVAILABLE S

I RCB CP-18 A

A A

1E EMERG.

CLOSED NOT CLOSED CLOSED / OPEN 1/VALVE D51511 CARMVAAA201A CARS EXHAUST. NOTE 5 CNTMNT ISOL VLV POSITION B1 ARMISV0110 NOT AVAILABLE S

I RB CP-14 A

A A

1E VITAL CLOSED NOT CLOSED CLOSED / OPEN 1/VALVE N/A ARMISV0110 CONTAINMENT ATMOSPHERIC MONITOR.

NOTE 4. REFER TO NOTE 14.

CNTMNT ISOL VLV POSITION B1 ARMISV0109 NOT AVAILABLE S

I RCB CP-14 A

A A

1E VITAL CLOSED NOT CLOSED CLOSED / OPEN 1/VALVE N/A ARMISV0109 CONTAINMENT ATMOSPHERIC MONITOR.

NOTE 4. REFER TO NOTE 14.

CNTMNT ISOL VLV POSITION B1 ARMISV0103 NOT AVAILABLE S

I RB CP-14 A

A A

1E VITAL CLOSED NOT CLOSED CLOSED / OPEN 1/VALVE N/A ARMISV0103 CONTAINMENT ATMOSPHERIC MONITOR.

NOTE 5. REFER TO NOTE 14.

CNTMNT ISOL VLV POSITION B1 SSLIZS8006A2 NOT AVAILABLE S

I RB CP-8 A

A A

1E VITAL CLOSED NOT CLOSED CLOSED / OPEN 1/VALVE N/A SSLMVAAA8006A STEAM GENERATOR BLOWDOWN SAMPLE. NOTE 4. REFER TO NOTE 14.

Security-Related Information Withheld Under 10 CFR 2.390

WSES-FSAR-UNIT-3 TABLE 7.5-3 (Sheet 9 of 40) Revision 11-A (02/02)

ACCIDENT MONITORING INSTRUMENTATION SERIAL NUMBER VARIABLE RG197 CAT/

TYPE LOOP COMPONENT COMP TYPE LOCATION ENV SEIS QA POWER SUPPLY CLASS RANGE/UNITS NUMBER OF CHANNEL SPDS I/O COMMENTS CNTMNT ISOL VLV POSITION B1 SSLIZS8004A2 NOT AVAILABLE S

I RCB CP-8 A

A A

1E VITAL CLOSED NOT CLOSED CLOSED / OPEN 1/VALVE N/A SSLMVAAA8004A STEAM GENERATOR BLOWDOWN SAMPLE. NOTE 4. REFER TO NOTE 14.

CNTMNT ISOL VLV POSITION B1 CVRISV0401 NOT AVAILABLE S

I RB CP-18 A

A A

1E EMERG.

CLOSED NOT CLOSED CLOSED / OPEN 1/VALVE D51411 CVRISV0401 CNTMNT VAC RELIEF INSTRUMENT LINE NOTE 3. ALSO REFER TO FSAR SEC. 6.2.4.2.2. REFER TO NOTE 14.

CNTMNT ISOL VLV POSITION B1 SI IZS0343/2 NOT AVAILABLE S

I RCB CP-8 A

A A

1E EMERG.

CLOSED NOT CLOSED CLOSED / OPEN 1/VALVE D44010 SI MVAAA343 SIT DRAIN TO RWSP NOTE 5 CNTMNT ISOL VLV POSITION B1 FP IZS0601A2 NOT AVAILABLE S

I RB CP-8 A

A A

1E EMERG.

CLOSED NOT CLOSED CLOSED / OPEN 1/VALVE D49820 FP MVAAA601A CONTAINMENT FIRE WATER HEADER. NOTE 5

CNTMNT ISOL VLV POSITION B1 FP IZS0601B2 NOT AVAILABLE S

I RB CP-8 A

A A

1E EMERG.

CLOSED NOT CLOSED CLOSED / OPEN 1/VALVE D49821 FP MVAAA601B CONTAINMENT FIRE WATER HEADER. NOTE 5

CNTMNT ISOL VLV POSITION B1 CVRISV0400 NOT AVAILABLE S

I RB CP-18 A

A A

1E EMERG.

CLOSED NOT CLOSED CLOSED / OPEN 1/VALVE D51413 CVRISV0400 CNTMNT VAC RELIEF INSTRUMENT LINE NOTE 3. ALSO REFER TO FSAR SEC. 6.2.4.2.2. REFER TO NOTE 14.

CNTMNT ISOL VLV POSITION B1 HRAISV0110A HRAISV0109A HRAISV0126A NOT AVAILABLE S

S S

I RB RCB RB CP-33 A

A A

1E EMERG.

CLOSED NOT CLOSED CLOSED NOT CLOSED CLOSED NOT CLOSED CLOSED / OPEN 1/VALVE N/A HRAISV0110A, HRAISV0109A AND HRAISV0126A HYDROGEN ANALYZER NOTE 7.

CNTMNT ISOL VLV POSITION B1 HRAISV0110B HRAISV0109B HRAISV0126B NOT AVAILABLE S

S S

I RB RCB RB CP-33 A

A A

1E EMERG.

CLOSED NOT CLOSED CLOSED NOT CLOSED CLOSED NOT CLOSED CLOSED / OPEN 1/VALVE N/A HRAISV0110B, HRAISV0109B AND HRAISV0126B HYDROGEN ANALYZER NOTE 7

CNTMNT ISOL VLV POSITION B1 CAPIZS0103/2 NOT AVAILABLE S

I RCB CP-18 A

A A

1E EMERG.

CLOSED NOT CLOSED CLOSED / OPEN 1/VALVE D51005 CAPMVAAA103 CONTAINMENT PURGE INLET. NOTE 4 CNTMNT ISOL VLV POSITION B1 CAPIZS0104/2 NOT AVAILABLE S

I RCB CP-18 A

A A

1E EMERG.

CLOSED NOT CLOSED CLOSED / OPEN 1/VALVE D51007 CAPMVAAA104 CONTAINMENT PURGE INLET. NOTE 4 COMPONENT DELETED FROM TABLE CNTMNT ISOL VLV POSITION B1 SI IZS0602A NOT AVAILABLE S

I RB CP-8 A

A A

1E EMERG.

CLOSED NOT CLOSED CLOSED / OPEN 1/VALVE D44501 SI MVAAA602A SI FROM SIS SUMP NOTE 3 Security-Related Information Withheld Under 10 CFR 2.390

WSES-FSAR-UNIT-3 TABLE 7.5-3 (Sheet 10 of 40) Revision 11-A (02/02)

ACCIDENT MONITORING INSTRUMENTATION SERIAL NUMBER VARIABLE RG197 CAT/

TYPE LOOP COMPONENT COMP TYPE LOCATION ENV SEIS QA POWER SUPPLY CLASS RANGE/UNITS NUMBER OF CHANNEL SPDS I/O COMMENTS

)

CNTMNT ISOL VLV POSITION B1 SI IZS0602B NOT AVAILABLE S

I RB CP-8 A

A A

1E EMERG.

CLOSED NOT CLOSED CLOSED / OPEN 1/VALVE D44503 SI MVAAA602B SI FROM SIS SUMP NOTE 3 CNTMNT ISOL VLV POSITION B1 MS IZS0124AA3 NOT AVAILABLE S

I RB CP-8 B

A A

1E EMERG.

CLOSED NOT CLOSED CLOSED / OPEN 2/VALVE N/A MS MVAAA124A MAIN STEAM.

NOTE 3 CNTMNT ISOL VLV POSITION B1 MS IZS0124AB3 S

RB B

A A

1E EMERG.

CLOSED NOT CLOSED 2/VALVE N/A MS MVAAA124A MAIN STEAM.

IND IS ON THE PLANT COMPUTER SYSTEM PT ID D55014. NOTE 3 CNTMNT ISOL VLV POSITION B1 SSLIZS0301A2 NOT AVAILABLE S

I RB CP-8 B

A A

1E VITAL CLOSED NOT CLOSED CLOSED / OPEN 1/VALVE N/A SSLMVAA301A MAIN STEAM SAMPLE NOTE 3. REFER TO NOTE 14.

CNTMNT ISOL VLV POSITION B1 MS IZS0124BA3 S

RB B

A A

1E EMERG.

CLOSED NOT CLOSED 2/VALVE N/A MS MVAAA124B MAIN STEAM.

IND IS ON THE PLANT COMPUTER SYSTEM PT ID D55016. NOTE 3 CNTMNT ISOL VLV POSITION B1 MS IZS0124BB3 NOT AVAILABLE S

I RB CP-8 B

A A

1E EMERG.

CLOSED NOT CLOSED CLOSED / OPEN 2/VALVE N/A MS MVAAA124B MAIN STEAM.

NOTE 3 CNTMNT ISOL VLV POSITION B1 SSLIZS0301B2 NOT AVAILABLE S

I RB CP-8 B

A A

1E VITAL CLOSED NOT CLOSED CLOSED / OPEN 1/VALVE N/A SSLMVAAA301B MAIN STEAM SAMPLE. NOTE 3. REFER TO NOTE 14.

CNTMNT ISOL VLV POSITION B1 EFWIZS0229A2 NOT AVAILABLE S

I RB CP-8 B

A A

1E EMERG.

CLOSED NOT CLOSED CLOSED / OPEN 1/VALVE N/A EFWMVAAA229A EMERGENCY FEEDWATER. NOTE 4. REFER TO NOTE 14.

CNTMNT ISOL VLV POSITION B1 EFWIZS0228A2 NOT AVAILABLE S

I RB CP-8 B

A A

1E EMERG.

CLOSED NOT CLOSED CLOSED / OPEN 1/VALVE N/A EFWMVAAA228A EMEREGENCY FEEDWATER.

NOTE 4 CNTMNT ISOL VLV POSITION B1 EFWIZS0229B2 NOT AVAILABLE S

I RB CP-8 B

A A

1E EMERG.

CLOSED NOT CLOSED CLOSED / OPEN 1/VALVE N/A EFWMVAAA229B EMERGENCY FEEDWATER. NOTE 4 CNTMNT ISOL VLV POSITION B1 EFWIZS0228B2 NOT AVAILABLE S

I RB CP-8 B

A A

1E EMERG.

CLOSED NOT CLOSED CLOSED / OPEN 1/VALVE N/A EFWMVAAA228B EMERGENCYT FEEDWATER. NOTE 4. REFER TO NOTE 14.

CNTMNT ISOL VLV POSITION B1 SSLIZS8006B2 NOT AVAILABLE S

I RB CP-8 A

A A

1E VITAL CLOSED NOT CLOSED CLOSED / OPEN 1/VALVE N/A SSLMVAAA8006B STEAM GENERATOR BLOWDOWN SAMPLE. NOTE 4. REFER TO NOTE 14.

Security-Related Information Withheld Under 10 CFR 2.390

WSES-FSAR-UNIT-3 TABLE 7.5-3 (Sheet 11 of 40) Revision 11-A (02/02)

ACCIDENT MONITORING INSTRUMENTATION SERIAL NUMBER VARIABLE RG197 CAT/

TYPE LOOP COMPONENT COMP TYPE LOCATION ENV SEIS QA POWER SUPPLY CLASS RANGE/UNITS NUMBER OF CHANNEL SPDS I/O COMMENTS CNTMNT ISOL VLV POSITION B1 SSLIZS8004B2 NOT AVAILABLE S

I RCB CP-8 A

A A

1E VITAL CLOSED NOT CLOSED CLOSED / OPEN 1/VALVE N/A SSLMVAAA8004B STEAM GENERATOR BLOWDOWN SAMPLE. NOTE 4. REFER TO NOTE 14.

CNTMNT ISOL VLV POSITION B1 CAPIZS0204/2 NOT AVAILABLE S

I ANN CP-18 A

A A

1E EMERG.

CLOSED NOT CLOSED CLOSED / OPEN 1/VALVE D51011 CAPMVAAA204 CONTAINMENT PURGE OUTLET. NOTE 4 CNTMNT ISOL VLV POSITION B1 CAPIZS0203/2 NOT AVAILABLE S

I RCB CP-18 A

A A

1E EMERG.

CLOSED NOT CLOSED CLOSED / OPEN 1/VALVE D51009 CAPMVAAA203 CONTAINMENT PURGE OUTLET. NOTE 4 COMPONENT DELETED FROM TABLE CNTMNT ISOL VLV POSITION B1 CC IZS0641/2 NOT AVAILABLE S

I RB CP-8 A

A A

1E EMERG.

CLOSED NOT CLOSED CLOSED / OPEN 1/VALVE N/A CC MVAAA641 CCW TO RCPS AND CEDM COOLER. NOTE 5 CNTMNT ISOL VLV POSITION B1 CC IZSO713/2 NOT AVAILABLE S

I RB CP-8 A

A A

1E EMERG.

CLOSED NOT CLOSED CLOSED / OPEN 1/VALVE N/A CC MVAAA713 CCW TO RCPS AND CEDM COOLER. NOTE 4 CNTMNT ISOL VLV POSITION B1 CC IZS0710/2 NOT AVAILABLE S

I RCB CP-8 A

A A

1E EMERG.

CLOSED NOT CLOSED CLOSED / OPEN 1/VALVE N/A CC MVAAA710 CCW TO RCPS AND CEDM COOLER. NOTE 4 CNTMNT ISOL VLV POSITION B1 FW IZS0184AA2 NOT AVAILABLE S

I RB CP-8 B

A A

1E EMERG.

CLOSED NOT CLOSED CLOSED / OPEN 2/VALVE N/A FW MVAAA184A MAIN FEEDWATER NOTE 3 CNTMNT ISOL VLV POSITION B1 FW IZS0184AB2 S

RB B

A A

1E EMERG.

CLOSED NOT CLOSED 2/VALVE N/A FW MVAAA184A MAIN FEEDWATER IND IS ON THE PLANT COMPUTER SYS. (PT ID D09000). NOTE 3 CNTMNT ISOL VLV POSITION B1 FW IZSO184BB2 NOT AVAILABLE S

I RB CP-8 B

A A

1E EMERG.

CLOSED NOT CLOSED CLOSED / OPEN 2/VALVE N/A FW MVAAA184B MAIN FEEDWATER NOTE 3 CNTMNT ISOL VLV POSITION B1 FW IZS0184BA2 S

RB B

A A

1E EMERG.

CLOSED NOT CLOSED 2/VALVE N/A FW MVAAA184B MAIN FEEDWATER IND IS ON THE PLANT COMPUTER SYS. (PT ID D09001). NOTE 3 CNTMNT ISOL VLV POSITION B1 SA ISV9082 NOT AVAILABLE S

I RB CP-8 A

A A

1E EMERG.

CLOSED NOT CLOSED CLOSED / OPEN 1/VALVE N/A SA ISV9082 ESSENTIAL IA TO CC-710. NOTE 5 CNTMT ISOL ITION B1 MS IZS0401A NOT AVAILABLE S

I RB CP-8 B

A A

1E EMERG CLOSED NOT CLOSED CLOSED / OPEN 1/VALVE N/A MS MVAAA401A EMERGENCY SG FEED PUMP TURBINES.

NOTE 3, 15.

Security-Related Information Withheld Under 10 CFR 2.390

WSES-FSAR-UNIT-3 TABLE 7.5-3 (Sheet 12 of 40) Revision 11-A (02/02)

ACCIDENT MONITORING INSTRUMENTATION SERIAL NUMBER VARIABLE RG197 CAT/

TYPE LOOP COMPONENT COMP TYPE LOCATION ENV SEIS QA POWER SUPPLY CLASS RANGE/UNITS NUMBER OF CHANNEL SPDS I/O COMMENTS CNTMT ISOL VLV POSITION B1 MS IZS0401B NOT AVAILABLE S

I RB CP-8 B

A A

1E EMERG CLOSED NOT CLOSED CLOSED / OPEN 1/VALVE N/A MS MVAAA401B EMERGENCY SG FEED PUMP TURBINES.

NOTE 3, 15.

CNTMT ISOL VLV POSITION B1 MS IZS0116A2 ANNUN. M0701 S

I RB CP-19 B*

B A

N1E VITAL CLOSED NOT CLOSED SG1 ATMOSPHERIC DUMP VLV OPEN 1/VALVE N/A MS MVAAA116A ATMOSPHERIC STEAM DUMP. NOTE 3, 15, 16..

CNTMT ISOL VLV POSITION B1 MS IZS0116B2 ANNUN. N0701 S

I RB CP-19 B*

B A

N1E VITAL CLOSED NOT CLOSED SG2 ATMOSPHERIC DUMP VLV OPEN 1/VALVE N/A MS MVAAA116B ATMOSPHERIC STEAM DUMP. NOTE 3, 15, 16.

CNTMT ISOL VLV POSITION B1 CVRIZS0101 1/2 NOT AVAILABLE S

I ANN CP-18 A

A A

1E VITAL CLOSED NOT CLOSED OPEN / CLOSED 1/VALVE N/A CVRMVAAA101 CONTAINMENT VACUUM RELIEF. NOTE 15.

CNTMT ISOL VLV POSITION B1 CVRIZS0201 1/2 NOT AVAILABLE S

I ANN CP-18 A

A A

1E VITAL CLOSED NOT CLOSED CLOSED / OPEN 1/VALVE N/A CVRMVAAA201 CONTAINMENT VACUUM RELIEF. NOTE 15.

CNTMT ISOL VLV POSITION B1 CC IZS0807A1/2 NOT AVAILABLE S

I RB CP-18 A

A A

1E EMERG CLOSED NOT CLOSED GREEN / RED 1/VALVE N/A CC MVAAA807A COMPONENT COOLING WATER INLET TO CNTMNT FAN COOLER UNITS.

NOTE 3, 15.

CNTMT ISOL VLV POSITION B1 CC IZS0807B1/2 NOT AVAILABLE S

I RB CP-18 A

A A

1E EMERG CLOSED NOT CLOSED GREEN / RED 1/VALVE N/A CC MVAAA807B COMPONENT COOLING WATER INLET TO CNTMNT FAN COOLER UNITS.

NOTE 3, 15.

CNTMT ISOL VLV POSITION B1 CC IZS0808A1/2 NOT AVAILABLE S

I RB CP-18 A

A A

1E EMERG CLOSED NOT CLOSED GREEN / RED 1/VALVE N/A CC MVAAA808A COMPONENT COOLING WATER INLET TO CNTMNT FAN COOLER UNITS.

NOTE 3, 15.

CNTMT ISOL VLV POSITION B1 CC IZS0808B1/2 NOT AVAILABLE S

I RB CP-18 A

A A

1E EMERG CLOSED NOT CLOSED GREEN / RED 1/VALVE N/A CC MVAAA808B COMPONENT COOLING WATER INLET TO CNTMNT FAN COOLER UNITS.

NOTE 3, 15.

CNTMT ISOL VLV POSITION B1 CC IZS0822A1/2 NOT AVAILABLE S

I RB CP-18 A

A A

1E EMERG CLOSED NOT CLOSED GREEN / RED 1/VALVE N/A CC MVAAA822A COMPONENT COOLING WATER OUTLET FROM CNTMNT FAN COOLER UNITS. NOTE 3, 15.

CNTMT ISOL VLV POSITION B1 CC IZS0822B1/2 NOT AVAILABLE S

I RB CP-18 A

A A

1E EMERG CLOSED NOT CLOSED GREEN / RED 1/VALVE N/A CC MVAAA822B COMPONENT COOLING WATER OUTLET FROM CNTMNT FAN COOLER UNITS. NOTE 3, 15.

Security-Related Information Withheld Under 10 CFR 2.390

WSES-FSAR-UNIT-3 TABLE 7.5-3 (Sheet 13 of 40)

Revision 305 (11/11)

ACCIDENT MONITORING INSTRUMENTATION SERIAL NUMBER VARIABLE RG197 CAT/

TYPE LOOP COMPONENT COMP TYPE LOCATION ENV SEIS QA POWER SUPPLY CLASS RANGE/UNITS NUMBER OF CHANNEL SPDS I/O COMMENTS CNTMT ISOL VLV POSITION B1 CC IZS0823A1/2 NOT AVAILABLE S

I RB CP-18 A

A A

1E EMERG CLOSED NOT CLOSED GREEN / RED 1/VALVE N/A CC MVAAA823A COMPONENT COOLING WATER OUTLET FROM CNTMNT FAN COOLER UNITS. NOTE 3, 15.

CNTMT ISOL VLV POSITION B1 CC IZS0823B1/2 NOT AVAILABLE S

I RB CP-18 A

A A

1E EMERG CLOSED NOT CLOSED GREEN / RED 1/VALVE N/A CC MVAAA823B COMPONENT COOLING WATER OUTLET FROM CNTMNT FAN COOLER UNITS. NOTE 3, 15.

CNTMT ISOL VLV POSITION B1 CS IZS0125A1/2 NOT AVAILABLE S

I RB CP-8 A

A A

1E EMERG CLOSED NOT CLOSED CLOSED / OPEN 1/VALVE N/A CS MVAAA125A CONTAINMENT SPRAY. NOTE

15.

CNTMT ISOL VLV POSITION B1 CS IZS0125B1/2 NOT AVAILABLE S

I RB CP-8 A

A A

1E EMERG CLOSED NOT CLOSED CLOSED / OPEN 1/VALVE N/A CS MVAAA125B CONTAINMENT SPRAY. NOTE

15.

CNTMT ISOL VLV POSITION B1 SI IZS0138A NOT AVAILABLE S

I RB CP-8 A

A A

1E EMERG CLOSED NOT CLOSED MORE / LESS 1/VALVE N/A SI MVAAA138A SAFETY INJECTION FROM LPSI PUMPS.

NOTE 5, 15.

CNTMT ISOL VLV POSITION B1 SI IZS0138B NOT AVAILABLE S

I RB CP-8 A

A A

1E EMERG CLOSED NOT CLOSED MORE / LESS 1/VALVE N/A SI MVAAA138B SAFETY INJECTION FROM LPSI PUMPS.

NOTE 5, 15.

CNTMT ISOL VLV POSITION B1 SI IZS0139A NOT AVAILABLE S

I RB CP-8 A

A A

1E EMERG CLOSED NOT CLOSED MORE / LESS 1/VALVE N/A SI MVAAA139A SAFETY INJECTION FROM LPSI PUMPS.

NOTE 5, 15.

CNTMT ISOL VLV POSITION B1 SI IZS0139B NOT AVAILABLE S

I RB CP-8 A

A A

1E EMERG CLOSED NOT CLOSED MORE / LESS 1/VALVE N/A SI MVAAA139B SAFETY INJECTION FROM LPSI PUMPS.

NOTE 5, 15.

CNTMT ISOL VLV POSITION B1 SI IZS0405A1/2 NOT AVAILABLE S

I RCB CP-8 A

A A

1E EMERG CLOSED NOT CLOSED CLOSED / OPEN 1/VALVE N/A SI MVAAA405A SAFETY INJECTION SHUTDOWN COOLING. NOTE 15.

CNTMT ISOL VLV POSITION B1 SI IZS0405B1/2 NOT AVAILABLE S

I RCB CP-8 A

A A

1E EMERG CLOSED NOT CLOSED CLOSED / OPEN 1/VALVE N/A SI MVAAA405B SAFETY INJECTION SHUTDOWN COOLING. NOTE 15.

CNTMT ISOL VLV POSITION B1 SI IZS0407A NOT AVAILABLE S

I RB CP-8 A

A A

1E EMERG CLOSED NOT CLOSED CLOSED / OPEN 1/VALVE N/A SI MVAAA407A SAFETY INJECTION SHUTDOWN COOLING. NOTE 15.

CNTMT ISOL VLV POSITION B1 SI IZS0407B NOT AVAILABLE S

I RB CP-8 A

A A

1E EMERG CLOSED NOT CLOSED CLOSED / OPEN 1/VALVE N/A SI MVAAA407B SAFETY INJECTION SHUTDOWN COOLING. NOTE 15.

CNTMT ISOL VLV POSITION B1 SI ISV4052A NOT AVAILABLE S

I RCB CP-8 A

A A

1E EMERG CLOSED NOT CLOSED CLOSED / OPEN 1/VALVE N/A SI ISV4052A SAFETY INJECTION SHUTDOWN COOLING. NOTE 15.

CNTMT ISOL VLV POSITION B1 SI ISV4052B NOT AVAILABLE S

I RCB CP-8 A

A A

1E EMERG CLOSED NOT CLOSED CLOSED / OPEN 1/VALVE N/A SI ISV4052B SAFETY INJECTION SHUTDOWN COOLING. NOTE 15.

Security-Related Information Withheld Under 10 CFR 2.390

WSES-FSAR-UNIT-3 TABLE 7.5-3 (Sheet 14 of 40) Revision 11-A (02/02)

ACCIDENT MONITORING INSTRUMENTATION SERIAL NUMBER VARIABLE RG197 CAT/

TYPE LOOP COMPONENT COMP TYPE LOCATION ENV SEIS QA POWER SUPPLY CLASS RANGE/UNITS NUMBER OF CHANNEL SPDS I/O COMMENTS CNTMT ISOL VLV POSITION B1 SI IZS0225A NOT AVAILABLE S

I RB CP-8 A

A A

1E EMERG CLOSED NOT CLOSED MORE / LESS 1/VALVE N/A SI MVAAA225A SAFETY INJECTION SYSTEM FROM HPSI LOOP 1A. NOTE 5, 15.

CNTMT ISOL VLV POSITION B1 SI IZS0225B NOT AVAILABLE S

I RB CP-8 A

A A

1E EMERG CLOSED NOT CLOSED MORE / LESS 1/VALVE N/A SI MVAAA225B SAFETY INJECTION SYSTEM FROM HPSI LOOP 1A. NOTE 5, 15.

CNTMT ISOL VLV POSITION B1 SI IZS0226A NOT AVAILABLE S

I RB CP-8 A

A A

1E EMERG CLOSED NOT CLOSED MORE / LESS 1/VALVE N/A SI MVAAA226A SAFETY INJECTION SYSTEM FROM HPSI LOOP 1B. NOTE 5, 15.

CNTMT ISOL VLV POSITION B1 SI IZS0226B NOT AVAILABLE S

I RB CP-8 A

A A

1E EMERG CLOSED NOT CLOSED MORE / LESS 1/VALVE N/A SI MVAAA226B SAFETY INJECTION SYSTEM FROM HPSI LOOP 1B. NOTE 5, 15.

CNTMT ISOL VLV POSITION B1 SI IZS0227A NOT AVAILABLE S

I RB CP-8 A

A A

1E EMERG CLOSED NOT CLOSED MORE / LESS 1/VALVE N/A SI MVAAA227A SAFETY INJECTION SYSTEM FROM HPSI LOOP 2A. NOTE 5, 15.

CNTMT ISOL VLV POSITION B1 SI IZS0227B NOT AVAILABLE S

I RB CP-8 A

A A

1E EMERG CLOSED NOT CLOSED MORE / LESS 1/VALVE N/A SI MVAAA227B SAFETY INJECTION SYSTEM FROM HPSI LOOP 2A. NOTE 5, 15.

CNTMT ISOL VLV POSITION B1 SI IZS0228A NOT AVAILABLE S

I RB CP-8 A

A A

1E EMERG CLOSED NOT CLOSED MORE / LESS 1/VALVE N/A SI MVAAA228A SAFETY INJECTION SYSTEM FROM HPSI LOOP 2B. NOTE 5, 15.

CNTMT ISOL VLV POSITION B1 SI IZS0228B NOT AVAILABLE S

I RB CP-8 A

A A

1E EMERG CLOSED NOT CLOSED MORE / LESS 1/VALVE N/A SI MVAAA228B SAFETY INJECTION SYSTEM FROM HPSI LOOP 2B. NOTE 5, 15.

CNTMT ISOL VLV POSITION B1 SI IZS0506A NOT AVAILABLE S

I RB CP-8 A

A A

1E EMERG CLOSED NOT CLOSED MORE / LESS 1/VALVE N/A SI MVAAA506A SAFETY INJECTION HOT LEG INJECTION. NOTE 5, 15.

CNTMT ISOL VLV POSITION B1 SI IZS0506B NOT AVAILABLE S

I RB CP-8 A

A A

1E EMERG CLOSED NOT CLOSED MORE / LESS 1/VALVE N/A SI MVAAA506B SAFETY INJECTION HOT LEG INJECTION. NOTE 5, 15.

CNTMT ISOL VLV POSITION B1 CVCIZS0209 1/2 NOT AVAILABLE S

I RB CP-4 A

A A

1E VITAL CLOSED NOT CLOSED RED / GREEN 1/VALVE N/A CVCMVAAA209 CHEMICAL AND VOLUME CONTROL CHARGING LINE. NOTE 15.

CNTMT ISOL VLV POSITION B1 CVCISV0216A NOT AVAILABLE S

I RCB CP-4 A

A A

1E VITAL CLOSED NOT CLOSED RED / GREEN 1/VALVE N/A CVCMVAAA216A CHEMICAL AND VOLUME CONTROL CHARGING LINE. NOTE 15.

Security-Related Information Withheld Under 10 CFR 2.390

WSES-FSAR-UNIT-3 TABLE 7.5-3 (Sheet 15 of 40)

Revision 12-B (04/03)

ACCIDENT MONITORING INSTRUMENTATION SERIAL NUMBER VARIABLE RG197 CAT/

TYPE LOOP COMPONENT COMP TYPE LOCATION ENV SEIS QA POWER SUPPLY CLASS RANGE/UNITS NUMBER OF CHANNEL SPDS I/O COMMENTS

)

CNTMT ISOL VLV POSITION B1 CVCISV0216B NOT AVAILABLE S

I RCB CP-4 A

A A

1E VITAL CLOSED NOT CLOSED RED / GREEN 1/VALVE N/A CVCMVAAA216B CHEMICAL AND VOLUME CONTROL CHARGING LINE. NOTE 15.

CNTMT ISOL VLV POSITION B1 CVCISV0218A NOT AVAILABLE S

I RCB CP-4 A

A A

1E VITAL CLOSED NOT CLOSED RED / GREEN 1/VALVE N/A CVCMVAAA218A CHEMICAL AND VOLUME CONTROL CHARGING LINE. NOTE 15.

CNTMT ISOL VLV POSITION B1 CVCISV0218B NOT AVAILABLE S

I RCB CP-4 A

A A

1E VITAL CLOSED NOT CLOSED GREEN / RED 1/VALVE N/A CVCMVAAA218B CHEMICAL AND VOLUME CONTROL CHARGING LINE. NOTE 15.

CNTMT ISOL VLV POSITION B1 SI-ISV-14023A NOT AVAILABLE S

I RB CP-8 A

A A

1E VITAL CLOSED NOT CLOSED RED / GREEN 1/VALVE D10844 SI-ISV-14023A LPSI VENT ISOLATION NOTE 14.

COMPONENTS DELETED FROM TABLE COMPONENTS DELETED FROM TABLE COMPONENTS DELETED FROM TABLE COMPONENTS DELETED FROM TABLE CORE EXIT TEMPERATURE C1 REFER TO SERIAL #011.

RADIOACTIVITY CONCENTRATION C1 SEE SERIAL #88. MONITORED VIA GRAB SMPL FROM PASS.

REFER TO FSAR SUBSECTION 9.3.8.

ANA OF PRIM COOLANT C3 SEE SERIAL #88. MONITORED VIA GRAB SMPL FROM PASS.

REFER TO FSAR SUBSECTION 9.3.8.

RCS PRESSURE C1 REFER TO SERIAL #007.

CNTMNT PRESS.

C1 REFER TO SERIAL #018.

CNTMNT WATER LEVEL C1 REFER TO SERIAL #016.

CNTMNT AREA RADIATION C3 REFER TO SERIAL #070.

RCS PRESSURE C1 REFER TO SERIAL #007.

EFFLUENT RADIOACTIVITY C3 REFER TO SERIAL #75. NOBLE GAS EFFLUENT FROM COND AIR REMOVAL SYSTEM EXHAUST.

Security-Related Information Withheld Under 10 CFR 2.390

WSES-FSAR-UNIT-3 TABLE 7.5-3 (Sheet 16 of 40)

Revision 15 (03/07)

ACCIDENT MONITORING INSTRUMENTATION SERIAL NUMBER VARIABLE RG197 CAT/

TYPE LOOP COMPONENT COMP TYPE LOCATION ENV SEIS QA POWER SUPPLY CLASS RANGE/UNITS NUMBER OF CHANNEL SPDS I/O COMMENTS CONTAINMENT HYDROGEN CONCENTRATION D3 D3 HRAMANN0001A HRAIAR8001A S

R RAB CP-33 A

A A

1E VITAL 0-10%

0-10%

2 N/A INST. IS SELF COMPENSATED FOR A PRESSURE RANGE OF -

5 PSIG TO CONTAINMENT DESIGN PRESSURE.

CONTAINMENT HYDROGEN CONCENTRATION D3 D3 HRAMANN0001B HRAIAR8001B S

R RAB CP-33 A

A A

1E VITAL 0-10%

0-10%

2 C26339 INST. IS SELF COMPENSATED FOR A PRESSURE RANGE OF -

5 PSIG TO CONTAINMENT DESIGN PRESSURE.

CONTAINMENT PRESSURE C1 ESFIPT6755A ESFIPR6755A S

R RB CP-8 A

A A

1E VITAL

(-)5-195 PSIG

(-)5-195 PSIG 2

A42208 CONT DESIGN PRESSURE IS 44 PSIG. REFER TO NOTE 14.

CONTAINMENT PRESSURE C1 ESFIPT6755B ESFIPR6755B S

R RB CP-8 A

A A

1E VITAL

(-)5-195 PSIG

(-)5-195 PSIG 2

A42209 CONT DESIGN PRESSURE IS 44 PSIG. REFER TO NOTE 14.

CNTMNT EFFL.

RADIOACTIVITY C2 REFER TO SERIAL #076.

EFFLUENT RADIOACTIVITY C2 REFER TO SERIAL #076.

SDCS COOLING WATER FLOW D2 CC IFT5570A CC IFE5570A CC IFI5570A S

S I

RAB RAB CP-8 A

A A

1E VITAL 0-7000 GMP 0-7000 GPM 0-7000 GPM 2

N/A COOLING WATER DESIGN FLOW IS 0-3000 GPM. REFER TO SERIAL #42 FOR SYSTEM FLOW.

SDCS COOLING WATER FLOW D2 CC IFT5570B CC IFE5570B CC IFI5570B S

S I

RAB RAB CP-8 A

A A

1E VITAL 0-7000 GPM 0-7000 GPM 0-7000 GPM 2

N/A COOLING WATER DESIGN FLOW IS 0-3000 GPM.

SDCS HX OUTLET TEMPERATURE D2 CS ITE0303X CS ITR0303X CS ITI0303X S

R I

RAB CP-8 CP-8 A

A A

1E VITAL 0-400 DEGF 0-400 DEGF 2

N/A REFER TO NOTE 14.

SDCS HX OUTLET TEMPERATURE D2 CS ITE0303Y CS ITI0303Y S

I RAB CP-8 A

A A

1E VITAL 0-400 DEGF 2

N/A SAFETY INJECTION TANK-LEVEL D2 SI ILT0313 SI ILI0313 S

I RCB CP-8 A

A A

N1E VITAL 121.9-2131.2 CU FT 0-100%

5-95% VOL.

1/TANK N/A SAFETY INJECTION TANK-LEVEL D2 SI ILT0323 SI ILI0323 S

I RCB CP-8 A

A A

N1E VITAL 121.9-2131.2 CU FT 0-100%

5-95% VOL.

1/TANK N/A SAFETY INJECTION TANK-LEVEL D2 SI ILT0333 SI ILI0333 S

I RCB CP-8 A

A A

N1E VITAL 121.9-2131.2 CU FT 0-100%

5-95%

1/TANK N/A Security-Related Information Withheld Under 10 CFR 2.390

WSES-FSAR-UNIT-3 TABLE 7.5-3 (Sheet 17 of 40) Revision 11-A (02/02)

ACCIDENT MONITORING INSTRUMENTATION SERIAL NUMBER VARIABLE RG197 CAT/

TYPE LOOP COMPONENT COMP TYPE LOCATION ENV SEIS QA POWER SUPPLY CLASS RANGE/UNITS NUMBER OF CHANNEL SPDS I/O COMMENTS SAFETY NJECTION TANK-LEVEL D2 SI ILT0343 SI ILI0343 S

I RCB CP-8 A

A A

N1E VITAL 121.9-2131.2 CU FT 0-100%

5-95% VOL.

1/TANK N/A SAFETY NJECTION TANK PRESS.

D2 SI IPT0311 SI IPI0311 S

I RCB CP-8 A

A A

N1E VITAL 0-750 PSIG 0-750 PSIG 1/TANK N/A SAFETY NJECTION TANK PRESS.

D2 SI IPT0321 SI IPI0321 S

I RCB CP-8 A

A A

N1E VITAL 0-750 PSIG 0-750 PSIG 1/TANK N/A SAFETY NJECTION TANK PRESS.

D2 SI IPT0331 SI IPI0331 S

I RCB CP-8 A

A A

N1E VITAL 0-750 PSIG 0-750 PSIG 1/TANK N/A SAFETY NJECTION TANK PRESS.

D2 SI IPT0341 SI IPI0341 S

I RCB CP-8 A

A A

N1E VITAL 0-750 PSIG 0-750 PSIG 1/TANK N/A SAFETY INJ.

TANK ISOL.

VLV POSI.

D2 SI IZS0331A NOT AVAILABLE S

I RCB CP-8 A

A A

1E EMERG.

OPEN-CLOSED RED / GREEN 1/VALVE N/A FOR VALVE SI MVAAA331A SAFETY INJ.

TANK ISOL.

VLV POSI.

D2 SI IZS0331B NOT AVAILABLE S

I RCB CP-8 A

A A

1E EMERG.

OPEN-CLOSED RED / GREEN 1/VALVE N/A FOR VALVE SI MVAAA331B REFER TO NOTE. 14.

SAFETY INJ.

TANK ISOL.

VLV POSI.

D2 SI IZS0332A NOT AVAILABLE S

I RCB CP-8 A

A A

1E EMERG.

OPEN-CLOSED RED / GREEN 1/VALVE N/A FOR VALVE SI MVAAA332A SAFETY INJ.

TANK ISOL.

VLV POSI.

D2 SI IZS0332B NOT AVAILABLE S

I RCP CP-8 A

A A

1E EMERG.

OPEN-CLOSED RED / GREEN 1/VALVE N/A FOR VALVE SI MVAAA332B BORIC ACID CHARGIN FLOW D2 REFER TO SERIAL #061 DESIGN FLOW IS 132 GPM FLOW IN HPSI SYSTEM TO COLD LEG OOP 1A D2 SI IFE0311 SI IFT0311 SI IFI0311 S

S I

RAB RAB CP-8 A

A A

N1E VITAL 0-500 GPM 0-500 GPM 0-500 GPM 1/LEG D43400 D43600 DESIGN FLOW IS 380 GPM FLOW IN HPSI SYSTEM TO COLD LEG OOP 1B D2 SI IFE0321 SI IFT0321 SI IFI0321 S

S I

RAB RAB CP-8 A

A A

N1E VITAL 0-500 GPM 0-500 GPM 0-500 GPM 1/LEG D43500 DESIGN FLOW IS 380 GPM Security-Related Information Withheld Under 10 CFR 2.390

WSES-FSAR-UNIT-3 TABLE 7.5-3 (Sheet 18 of 40) Revision 11-A (02/02)

ACCIDENT MONITORING INSTRUMENTATION SERIAL NUMBER VARIABLE RG197 CAT/

TYPE LOOP COMPONENT COMP TYPE LOCATION ENV SEIS QA POWER SUPPLY CLASS RANGE/UNITS NUMBER OF CHANNEL SPDS I/O COMMENTS FLOW IN HPSI SYSTEM TO COLD LEG D2 SI IFE0331 SI IFT0331 SI IFI0331 S

S I

RAB RAB CP-8 A

A A

N1E VITAL 0-500 GPM 0-500 GPM 0-500 GPM 1/LEG N/A DESIGN FLOW IS 380 GPM FLOW IN HPSI SYSTEM TO COLD LEG D2 SI IFE0341 SI IFT0341 SI IFI0341 S

S I

RAB RAB CP-8 A

A A

N1E VITAL 0-500 GPM 0-500 GPM 0-500 GPM 1/LEG N/A DESIGN FLOW IS 380 GPM FLOW IN HPSI SYSTEM TO HOT LEG PUMP A D2 SI IFE0390A SI IFT0390A SI IFI0390A S

S I

RAB RAB CP-8 A

A A

N1E VITAL 0-500 GPM 0-500 GPM 0-500 GPM 1/LEG N/A DESIGN FLOW IS 190 GPM FLOW IN HPSI SYSTEM TO HOT LEG D2 SI IFE0390B SI IFT0390B SI IFI0390B S

S I

RAB RAB CP-8 A

A A

N1E VITAL 0-500 GPM 0-500 GPM 0-500 GPM 1/LEG N/A DESIGN FLOW IS 190 GPM FLOW IN LPSI SYSTEM D2 SI IFE1307A SI IFT1307A SI IFI1307A1 S

S I

RAB RAB CP-8 A

A A

1E VITAL 0-5500 GPM 0-5500 GPM 0-5500 GPM 1/LEG S43101 DESIGN FLOW IS 4050 GPM FLOW IN LPSI SYSTEM D2 SI IFE1306B SI IFT1306B1 SI IFI1306B1 S

S I

RAB RAB CP-8 A

A A

1E VITAL 0-5500 GPM 0-5500 GPM 0-5500 GPM 1/LEG S43201 DESIGN FLOW IS 4050 GPM REFUELING WATER STORAGE POOL LEVEL D2 SI ILT0305A SI ILI0305A S

I RAB CP-7 A

A A

1E VITAL 0-20 FT.

0-100%

4 N/A MAX. HEIGHT OF POOL UP TO TOP OF LINER IS 20.92 FT.

REFUELING WATER STORAGE POOL LEVEL D2 SI ILT0305B SI ILI0305B S

I RAB CP-7 A

A A

1E VITAL 0-20 FT.

0-100%

4 N/A MAX. HEIGHT OF POL UP TO TOP OF LINER IS 20.92 FT.

REFUELING WATER STORAGE POOL LEVEL D2 SI ILT0305C SI ILI0305C S

I RAB CP-7 A

A A

1E VITAL 0-20 FT.

0-100%

4 N/A MAX. HEIGHT OF POOL UP TO TOP OF LINER IS 20.92 FT.

REFER TO NOTE 14.

REFUELING WATER STORAGE POOL LEVEL D2 SI ILT0305D SI ILI0305D S

I RAB CP-7 A

A A

1E VITAL 0-20 FT.

0-100%

4 N/A MAX. HEIGHT OF POOL UP TO TOP OF LINER IS 20.92 FT.

RCP STATUS RCP 1A D3 RC EM1A-7C RC ECT1A-7-1A RC ECT1A-7-1B RC ECT1A-7-1C I

S S

S CP-2 TGB TGB TGB C

N/A A

N1E 0-1200A 1 PER PUMP N/A RCP STATUS RCP 1B D3 RC EM1B-7C RC ECT1B-7-1A RC ECT1B-7-1B RC ECT1B-7-1C I

S S

S CP-2 TGB TGB TGB C

N/A A

N1E 0-1200A 1 PER PUMP N/A Security-Related Information Withheld Under 10 CFR 2.390

WSES-FSAR-UNIT-3 TABLE 7.5-3 (Sheet 19 of 40) Revision 11-A (02/02)

ACCIDENT MONITORING INSTRUMENTATION SERIAL NUMBER VARIABLE RG197 CAT/

TYPE LOOP COMPONENT COMP TYPE LOCATION ENV SEIS QA POWER SUPPLY CLASS RANGE/UNITS NUMBER OF CHANNEL SPDS I/O COMMENTS

)

RCP STATUS RCP 2A D3 RC EM1A-8C RC ECT1A-8-1A RC ECT1A-8-1B RC ECT1A-8-1C I

S S

S CP-2 TGB TGB TGB C

N/A A

N1E 0-1200A 1 PER PUMP N/A RCP STATUS RCP 2B D3 RC EM1B-8C RC ECT1B-8-1A RC ECT1B-8-1B RC ECT1B-8-1C I

S S

S CP-2 TGB TGB TGB C

N/A A

N1E 0-1200A 1 PER PUMP N/A PRESS SAFETY VLV POSITION D2 VLPIZE0317A1 VLPIZT0317A1 NOT AVAILABLE S

S I

RCB RAB CP-2 A

A B

N1E VITAL CLOSED NOT CLOSED CLOSED NOT CLOSED GREEN / RED 2/VALVE N/A IND ON QSPDS REFER TO NOTE 19 PRESS SAFETY VLV POSITION D2 VLPIZE0317A2 VLPIZT0317A2 S

S RCB CP-19 A

N/A B

N1E VITAL CLOSED NOT CLOSED 2/VALVE N/A IND ON PLANT COMPUTER (PT ID A12207)

REFER TO NOTE 19 PRESS SAFETY VLV POSITION D2 VLPIZE0317B1 VLPIZT0317B1 NOT AVAILABLE S

S I

RCB RAB CP-2 A

A B

N1E VITAL CLOSED NOT CLOSED CLOSED NOT CLOSED GREEN / RED 2/VALVE N/A IND ON QSPDS REFER TO NOTE 19 PRESS SAFETY VLV POSITION D2 VLPIZE0317B2 VLPIZT0317B2 S

S RCB CP-19 A

N/A B

N1E VITAL CLOSED NOT CLOSED 2/VALVE N/A IND ON PLANT COMPUTER (PT ID A12208)

REFER TO NOTE 19 PRESSURIZER LEVEL D1 RC ILT0110X RC ILI0110X RC ILR0110XY S

I R

RCB CP-2 CP-2 A

A A

1E VITAL 28.8-10959.9 G 0-100%

0-100%

2 A12200 A12201 PRESSURIZER LEVEL D1 RC ILT0110Y RC ILI0110Y RC ILR0110XY S

I R

RCB CP-2 CP-2 A

A A

1E VITAL 28.8-10959.9 G 0-100%

0-100%

2 A12202 PRESSURIZER PROPORTIONAL HEATER STATUS D2 RC EM0100-3A RC ECT32A-5C-A RC ECT32A-5C-B RC ECT32A-5C-C I

S S

S CP-2 RAB RAB RAB C

N/A A

N1E 0-300A 1 PER HEATER N/A PRESSURIZER PROPORTIONAL HEATER STATUS D2 RC EM0100-3B RC ECT32B-5C-A RC ECT32B-5C-B RC ECT32B-5C-C I

S S

S CP-2 RAB RAB RAB C

N/A A

N1E 0-300A 1 PER HEATER N/A QUENCH TANK LEVEL D3 RC ILT0116 RC ILI0116 S

I RCB C P-2 N/A N/A N/A N1E VITAL 83.7-2367.3 G 0-100%

1 N/A Security-Related Information Withheld Under 10 CFR 2.390

WSES-FSAR-UNIT-3 TABLE 7.5-3 (Sheet 20 of 40)

Revision 12-C (07/03)

ACCIDENT MONITORING INSTRUMENTATION SERIAL NUMBER VARIABLE RG197 CAT/

TYPE LOOP COMPONENT COMP TYPE LOCATION ENV SEIS QA POWER SUPPLY CLASS RANGE/UNITS NUMBER OF CHANNEL SPDS I/O COMMENTS QUENCH TANK TEMPERATURE D3 RC ITE0116 RC ITI0116 S

I RCB CP-2 N/A N/A N/A N1E VITAL 50-750 DEGF 1

N/A QUENCH TANK PRESSURE D3 RC IPT0116 RC IPI0116 S

I RCB CP-2 N/A N/A N/A N1E VITAL 0-150 PSIG 0-150 PSIG 1

N/A DESIGN PRESSURE IS 130 PSIG.

STEAM GEN.

LEVEL NARROW RANGE D1 SG ILT1113A SG ILI1113A SG ILR1113A S

I R

RCB CP-8 CP-8 A

A A

1E VITAL 0-100%

0-100%

4/SG N/A REFER TO NOTE 14 FOR THE RECORDER ONLY.

STM GEN LEVEL NARROW RANGE D1 SG ILT1113B SG ILI1113B S

I RCB CP-8 A

A A

1E VITAL 0-100%

4/SG N/A STM GEN LEVEL NARROW RANGE D1 SG ILT1113C SG ILI1113C S

I RCB CP-8 A

A A

1E VITAL 0-100%

4/SG N/A REFER TO NOTE 14.

STM GEN LEVEL NARROW RANGE D1 SG ILT1113D SG ILI1113D S

I RCB CP-8 A

A A

1E VITAL 0-100%

4/SG N/A STM GEN LEVEL NARROW RANGE D1 SG ILT1123A SG ILI1123A SG ILR1123A S

I R

RCB CP-8 CP-8 A

A A

1E VITAL 0-100%

0-100%

4/SG N/A REFER TO NOTE 14 FOR THE RECORDER ONLY.

STM GEN LEVEL NARROW RANGE D1 SG ILT1123B SG ILI1123B S

I RCB CP-8 A

A A

1E VITAL 0-100%

4/SG N/A STM GEN LEVEL NARROW RANGE D1 SG ILT1123C SG ILI1123C S

I RCB CP-8 A

A A

1E VITAL 0-100%

4/SG N/A REFER TO NOTE 14.

STM GEN LEVEL NARROW RANGE D1 SG ILT1123D SG ILI1123D S

I RCB CP-8 A

A A

1E VITAL 0-100%

4/SG N/A STM GEN LEVEL WIDE RANGE D1 SG ILT1115A SG ILI1115A2 S

I RCB CP-8 A

A A

1E VITAL 0-40 FT 0-100%

2/SG N/A REFER TO NOTE 9.

STM GEN LEVEL WIDE RANGE D1 SG ILT1115B SG ILI1115B2 SG ILR1115B S

I R

RCB CP-8 CP-8 A

A A

1E VITAL 0-40 FT 0-100%

0-100%

2/SG N/A REFER TO NOTE 9.

STM GEN LEVEL WIDE RANGE D1 SG ILT1125A SG ILI1125A2 S

I RCB CP-8 A

A A

1E VITAL 0-40 FT 0-100%

2/SG N/A REFER TO NOTE 9.

STM GEN LEVEL WIDE RANGE D1 SG ILT1125B SG ILI1125B2 SG ILR1125B S

I R

RCB CP-8 CP-8 A

A A

1E VITAL 0-40 FT 0-100%

0-100%

2/SG N/A REFER TO NOTE 9.

Security-Related Information Withheld Under 10 CFR 2.390

WSES-FSAR-UNIT-3 TABLE 7.5-3 (Sheet 21 of 40)

Revision 14 (12/05)

ACCIDENT MONITORING INSTRUMENTATION SERIAL NUMBER VARIABLE RG197 CAT/

TYPE LOOP COMPONENT COMP TYPE LOCATION ENV SEIS QA POWER SUPPLY CLASS RANGE/UNITS NUMBER OF CHANNEL SPDS I/O COMMENTS STEAM GEN.

PRESSURE D2 MS IPT0301A MS IPR0301A S

R RB CP-1 A

A A

N1E VITAL 0-1300 PSIG 0-1300 PSIG 1/SG N/A REFER TO NOTE 14.

STEAM GEN.

PRESSURE D2 MS IPT0301B MS IPR0301B S

R RB CP-1 A

A A

N1E VITAL 0-1300 PSIG 0-1300 PSIG 1/SG N/A REFER TO NOTE 14.

MAIN STEAM FLOW IND.

D2 MS IFE0300A MS IFT0300A MS IFI0300A S

S I

RCB RCB CP-1 A

A A

N1E VITAL 0-9 MPPH 0-9 MPPH 0-9 MPPH 1/SG N/A REFER TO NOTE 14.

MAIN STEAM FLOW IND.

D2 MS IFE0300B MS IFT0300B MS IFI0300B S

S I

RCB RCB CP-1 A

A A

N1E VITAL 0-9 MPPH 0-9 MPPH 0-9 MPPH 1/SG N/A REFER TO NOTE 14.

MAIN FW FLOW D3 FW IFE1111 FW IFT2000A FW IFI2000A S

S I

RAB RAB CP-1 C

A A

N1E VITAL 0-9 MPPH 0-9 MPPH 0-9 MPPH 2/SG N/A REFER TO NOTE 10 & 14.

MAIN FW FLOW D3 FW IFE1121 FW IFT2000B FW IFI2000B S

S I

RAB RAB CP-1 C

A A

N1E VITAL 0-9 MPPH 0-9 MPPH 0-9 MPPH 2/SG N/A REFER TO NOTE 10 & 14.

MAIN FW FLOW D3 FW IFE1111 FW IFT1111 FW IFR1111 S

S R

RAB RAB CP-1 C

A A

N1E VITAL 0-9 MPPH 0-9 MPPH 0-9 MPPH 2/SG N/A REFER TO NOTE 10 & 14.

MAIN FW FLOW D3 FW IFE1121 FW IFT1121 FW IFR1121 S

S R

RAB RAB CP-1 C

A A

N1E VITAL 0-9 MPPH 0-9 MPPH 0-9 MPPH 2/SG N/A REFER TO NOTE 10 & 14.

EFW FLOW D2 EFWIFE8330A EFWIFT8330A EFWIFI8330A2 S

S I

RAB RAB CP-8 A

A A

1E VITAL 0-800 GPM 0-150 INW 0-800 GPM 1/SG S10101 PROVIDED RANGE IS 0-114%

OF DESIGN FLOW.

EFW FLOW D2 EFWIFE8330B EFWIFT8330B EFWIFI8330B2 S

S I

RAB RAB CP-8 A

A A

1E VITAL 0-800 GPM 0-150 INW 0-800 GPM 1/SG S10201 PROVIDED RANGE IS 0-114%

OF DESIGN FLOW.

CONDENSATE STORAGE POOL WATER LEVEL A1 D1 EFWILT9013A EFWILI9013A EFWILR9013A S

I R

RAB CP-8 CP-8 A

A A

1E VITAL 0-21 FT 0-100%

0-100%

2 N/A CONDENSATE STORAGE POOL WATER LEVEL A1 D1 EFWILT9013B EFWILI9013B S

I RAB CP-8 A

A A

1E VITAL 0-21 FT 0-100%

2 N/A Security-Related Information Withheld Under 10 CFR 2.390

WSES-FSAR-UNIT-3 TABLE 7.5-3 (Sheet 22 of 40)

Revision 12-C (07/03)

ACCIDENT MONITORING INSTRUMENTATION SERIAL NUMBER VARIABLE RG197 CAT/

TYPE LOOP COMPONENT COMP TYPE LOCATION ENV SEIS QA POWER SUPPLY CLASS RANGE/UNITS NUMBER OF CHANNEL SPDS I/O COMMENTS CONTAINMENT SPRAY FLOW D2 CS IFE7122A CS IFT7122A CS IFI7122A S

S I

RAB RAB CP-8 B

A A

1E VITAL 0-2500 GPM 0-2500 GPM 0-2500 GPM 2

A42404 DESIGN FLOW IS 1750 GPM REFER TO NOTE 14.

CONTAINMENT SPRAY FLOW D2 CS IFE7122B CS IFT7122B CS IFI7122B S

S I

RAB RAB CP-8 B

A A

1E VITAL 0-2500 GPM 0-2500 GPM 0-2500 GPM 2

A42504 DESIGN FLOW IS 1750 GPM.

CCW FLOW CONTAINMENT FAN COOLERS D2 CC IFE7570A1 CC IFT7570A1 CC IFI7570A1 S

S I

RB RB CP-18 A

A A

1E VITAL 0-1500 GPM 0-1500 GPM 0-1500 GPM 1/COOLER N/A EMERGENCY DESIGN FLOW IS 1350 GPM. REFER TO NOTE 14.

CCW FLOW CONTAINMENT FAN COOLER D2 CC IFE7570A2 CC IFT7570A2 CC IFI7570A2 S

S I

RB RB CP-18 A

A A

1E VITAL 0-1500 GPM 0-1500 GPM 0-1500 GPM 1/COOLER N/A EMERGENCY DESIGN FLOW IS 1350 GPM. REFER TO NOTE 14.

CCW FLOW CONTAINMENT FAN COOLERS D2 CC IFE7570B1 CC IFT7570B1 CC IFI7570B1 S

S I

RB RB CP-18 A

A A

1E VITAL 0-1500 GPM 0-1500 GPM 0-1500 GPM 1/COOLER N/A EMERGENCY DESIGN FLOW IS 1350 GPM.

CCW FLOW CONTAINMENT FAN COOLERS D2 CC IFE7570B2 CC IFT7570B2 CC IFI7570B2 S

S I

RB RB CP-18 A

A A

1E VITAL 0-1500 GPM 0-1500 GPM 0-1500 GPM 1/COOLER N/A EMERGENCY DESIGN FLOW IS 1350 GPM.

CONT. ATMOS.

TEMPERATURE FAN COOLER INLET D2 CCSITE5150-1A CCSITE5150-2A CCSITR5155A S

S R

RCB RCB CP-18 A

A A

1E VITAL 0-450 DEGF 0-450 DEGF 0-450 DEGF 1/COOLER A51123 REFER TO NOTE 14.

CONT. ATMOS.

TEMPERATURE FAN COOLER OUTLET D2 CCSITE5152A CCSITR5155A S

R RCB CP-18 A

A A

1E VITAL 0-450 DEGF 0-450 DEGF 1/COOLER N/A REFER TO NOTE 14.

CONT. ATMOS.

TEMPERATURE FAN COOLER INLET D2 CCSITE5155-1A CCSITE5155-2A CCSITR5150A S

S R

RCB RCB CP-18 A

A A

1E VITAL 0-450 DEGF.

0-450 DEGF.

0-450 DEGF.

1/COOLER A51115 REFER TO NOTE 14.

CONT. ATMOS.

TEMPERATURE FAN COOLER OUTLET D2 CCSITE5157A CCSITR5150A S

R RCB CP-18 A

A A

1E VITAL 0-450 DEGF 0-450 DEGF 1/COOLER N/A REFER TO NOTE 14.

Security-Related Information Withheld Under 10 CFR 2.390

WSES-FSAR-UNIT-3 TABLE 7.5-3 (Sheet 23 of 40)

Revision 12-C (07/03)

ACCIDENT MONITORING INSTRUMENTATION SERIAL NUMBER VARIABLE RG197 CAT/

TYPE LOOP COMPONENT COMP TYPE LOCATION ENV SEIS QA POWER SUPPLY CLASS RANGE/UNITS NUMBER OF CHANNEL SPDS I/O COMMENTS CONT. ATMOS.

TEMPERATURE FAN COOLER INLET D2 CCSITE5150-1B CCSITE5150-2B CCSITR5155B S

S R

RCB RCB CP-18 A

A A

1E VITAL 0-450 DEGF 0-450 DEGF 0-450 DEGF 1/COOLER A51127 REFER TO NOTE 14 FOR THE RECORDER ONLY.

CONT. ATMOS.

TEMPERATURE FAN COOLER OUTLET D2 CCSITE5152B CCSITR5155B S

R RCB CP-18 A

A A

1E VITAL 0-45O DEGF 0-450 DEGF 1/COOLER N/A REFER TO NOTE 14 FOR TIME RECORDER ONLY.

CONT. ATMOS.

TEMPERATURE FAN COOLER INLET D2 CCSITE5155-1B CCSITE5155-2B CCSITR5150B S

S R

RCB RCB CP-18 A

A A

1E VITAL 0-450 DEGF 0-450 DEGF 0-450 DEGF 1/COOLER A51119 REFER TO NOTE 14 FOR TIME RECORDER ONLY.

CONT. ATMOS.

TEMPERATURE FAN COOLER OUTLET D2 CCSITE5157B CCSITR5150B S

R RCB CP-18 A

A A

1E VITAL 0-450 DEGF 0-450 DEGF 1/COOLER N/A REFER TO NOTE 14 FOR THE RECORDER ONLY.

CONTAINMENT SUMP WATER TEMPERATURE D2 SI ITE7116A SI ITI7116A S

I RB CP-8 A

A A

1E VITAL 32-240 DEGF 32-240 DEGF 2

N/A REFER TO NOTE 11.

REFER TO NOTE 14.

CONTAINMENT SUMP WATER TEMPERATURE D2 SI ITE7116B SI ITI7116B S

I RB CP-8 A

A A

1E VITAL 32-240 DEGF 32-240 DEGF 2

N/A REFER TO NOTE 11.

REFER TO NOTE 14 FOR THE RECORDER ONLY.

CVCS CHARGING FLOW D2 CVCIFT0212 CVCIFE0212 CVCIFI0212 S

S I

RB RB CP-4 A

A A

N1E VITAL 0-150 GPM 0-150 GPM 0-150 GPM 1

N/A DESIGN FLOW IS 132 GPM IND ON QSPDS.

CVCS CHARGING FLOW-OUT D2 CVCIFT0202 CVCIFE0202 CVCIFI0202 S

S I

RAB RAB CP-4 A

A A

N1E VITAL 0-150 GPM 0-150 GPM 0-150 GPM 1

N/A DESIGN FLOW IS 126 GPM IND ON QSPDS.

VOLUME CTRL TANK LEVEL D2 CVCILT0226 CVCILI0226 S

I RAB CP-4 A

A A

N1E VITAL 469.8-4410.7 G 0-100%

1 N/A CCW TEMP. TO ESF SYSTEM D2 CC ITI7070A CC ITE7070A I

S CP-8 RAB B

A A

1E VITAL 50-130 DEGF 50-130 DEGF 1/HEADER N/A REFER TO NOTE 12.

CCW TEMP. TO ESF SYSTEM D2 CCC ITI7070B CC ITE7070B I

S CP-8 RAB B

A A

1E VITAL 50-130 DEGF 50-130 DEGF 1/HEADER N/A REFER TO NOTE 12. REFER TO NOTE 14.

CCS FLOW TO ESF SYSTEM D2 CC IFT7070A CC IFE7070A CC IFI7070A1 S

S I

RAB RAB CP-8 B

A A

1E VITAL 0-1000 GPM 0-10000 GPM 0-10000 GPM 1/HEADER N/A DESIGN FLOW IS 6800 GPM.

REFER TO NOTE 14.

Security-Related Information Withheld Under 10 CFR 2.390

WSES-FSAR-UNIT-3 TABLE 7.5-3 (Sheet 24 of 40)

Revision 12-C (07/03)

ACCIDENT MONITORING INSTRUMENTATION SERIAL NUMBER VARIABLE RG197 CAT/

TYPE LOOP COMPONENT COMP TYPE LOCATION ENV SEIS QA POWER SUPPLY CLASS RANGE/UNITS NUMBER OF CHANNEL SPDS I/O COMMENTS CCW FLOW TO ESF SYSTEM D2 CC IFT7070B CC IFE7070B CC IFI7070B1 S

S I

RAB RAB CP-8 B

A A

1E VITAL 0-1000 GPM 0-10000 GPM 0-10000 GPM 1/HEADER N/A DESIGN FLOW IS 6800 GPM.

REFER TO NOTE 14.

HIGH LEVEL RAD LIQUID HOLD UP TANK LEVEL D3 BM ILT0607A BM ILI0607A S

I RAB CP-4 C

A A

N1E VITAL 1565.5-46576.8 G 0-100%

1/TANK N/A HIGH LEVEL RAD LIQUID HOLD UP TANK LEVEL D3 BM ILT0608 BM ILI0608 S

I RAB CP-4 C

A A

N1E VITAL 1565.5-46576.8 G 0-100%

1/TANK N/A HIGH LEVEL RAD LIQUID HOLD UP TANK LEVEL D3 BM ILT0609 BM ILI0609 S

I RAB CP-4 C

A A

N1E VITAL 1565.5-46576.8 G 0-100%

1/TANK N/A HIGH LEVEL RAD LIQUID HOLD UP TANK LEVEL D3 BM ILT0610 BM ILI0610 S

I RAB CP-4 C

A A

N1E VITAL 1565.5-46576.8 G 0-100%

1/TANK N/A RAD GAS DECAY TANK PRESSURE D3 GWMIPT6709 S

RAB C

N/A N/A N1E VITAL 0-600 PSIG 1/TANK N/A IND ON PLANT COMPUTER.

(PT ID A41301) PROVIDED RANGE IS 0-158% OF DESIGN PRESSURE.

RAD GAS DECAY TANK PRESSURE D3 GWMIPT6710 S

RAB C

N/A N/A N1E VITAL 0-600 PSIG 1/TANK N/A IND ON PLANT COMPUTER.

(PT ID A41302) PROVIDED RANGE IS 0-158% OF DESIGN PRESSURE.

RAD GAS DECAY TANK PRESSURE D3 GWMIPT6711 S

RAB C

N/A N/A N1E VITAL 0-600 PSIG 1/TANK N/A IND ON PLANT COMPUTER.

(PT ID A41303) PROVIDED RANGE IS 0-158% OF DESIGN PRESSURE.

EMER. VENT.

DAMPER POSI D2 HVCIZS0304A2 HVCIZS0304A1 S

S RAB RAB B

A B

1E EMERG.

OPEN-CLOSED 1

N/A IND ON PLANT COMPUTER.

(PT ID D052626, D052627).

REFER TO NOTE 19.

EMER. VENT.

DAMPER POSI D2 HVCIZS0304B1 HVCIZS0304B2 S

S RAB RAB B

A B

1E EMERG.

OPEN-CLOSED 1

N/A IND ON PLANT COMPUTER.

(PT ID D052628, D052629).

REFER TO NOTE 19.

EMER. VENT.

DAMPER POSI D2 HVCIZS0312A1 HVCIZS0312A2 S

S RAB RAB B

A B

1E EMERG.

OPEN-CLOSED OPEN-CLOSED 1

N/A CNTRL RM KITCHEN & CONF RM EXHAUST FAN BYPASS DAMPER. REFER TO NOTE 19.

Security-Related Information Withheld Under 10 CFR 2.390

WSES-FSAR-UNIT-3 TABLE 7.5-3 (Sheet 25 of 40)

Revision 12-C (07/03)

ACCIDENT MONITORING INSTRUMENTATION SERIAL NUMBER VARIABLE RG197 CAT/

TYPE LOOP COMPONENT COMP TYPE LOCATION ENV SEIS QA POWER SUPPLY CLASS RANGE/UNITS NUMBER OF CHANNEL SPDS I/O COMMENTS EMER. VENT.

DAMPER POSI D2 HVCIZS0312B1 HVCIZS0312B2 S

S RAB RAB B

A B

1E EMERG.

OPEN-CLOSED OPEN-CLOSED 1

N/A IND ON PLANT COMPUTER.

(PT ID D52635, D52634).

REFER TO NOTE 19.

EMER. VENT.

DAMPER POSI D2 HVCIZS0205A1 HVCIZS0205A2 NOT AVAILABLE S

S I

RAB RAB CP-18 B

A A

1E VITAL OPEN-CLOSED OPEN-CLOSED RED / GREEN 1

N/A CNTROL RM EMERGENCY FILTRATION SYSTEM FAN INTAKE DAMPER. REFER TO NOTES 14 AND 19.

EMER. VENT.

DAMPER POSI D2 HVCIZS0213A1 HVCIZS0213A2 S

S RAB RAB B

A A

1E VITAL OPEN-CLOSED OPEN-CLOSED 1

N/A CNTROL RM EMER FILT SYS RETURN AIR DAMPER. IND ON PLANT COMP (PT ID D52733, D52732). REFER TO NOTES 14 AND 19.

EMER. VENT.

DAMPER POSI D2 HVCIZS0205B1 HVCIZS0205B2 NOT AVAILABLE S

S I

RAB RAB CP-18 B

A A

1E VITAL OPEN-CLOSED OPEN-CLOSED RED / GREEN 1

N/A CNTROL RM EMER FILT SYS FAN INLET DAMPER. REFER TO NOTE 19.

EMER. VENT.

DAMPER POSI D2 HVCIZS0213B1 HVCIZS0213B2 S

S RAB RAB B

A A

1E VITAL OPEN-CLOSED OPEN-CLOSED 1

N/A CNTROL RM EMER FILT SYS FAN RETURN AIR DAMPER.

IND IS ON PLANT COMPUTER (PT ID D52734, D52735).

REFER TO NOTE 19.

EMER. VENT.

DAMPER POSI D2 HVCIZS0103A1 HVCIZS0103A2 S

S RAB RAB B

A A

1E EMERG.

OPEN-CLOSED OPEN-CLOSED 1

N/A CNTROL RM SUPPLY FAN INTAKE DAMPER IND ON PLANT COMPUTER (PT ID D52640, D52641). REFER TO NOTE 19.

EMER. VENT.

DAMPER POSI D2 HVCIZS0103B1 HVCIZS0103B2 S

S RAB RAB B

A A

1E EMERG.

OPEN-CLOSED OPEN-CLOSED 1

N/A CNTROL RM SUPPLY FAN INTAKE DAMPER. IND ON PLANT COMPUTER (PT ID D52642, D52643). REFER TO NOTE 19.

EMER. VENT.

DAMPER POSI D2 SVSIZS0105A1 SVSIZS0105A2 S

S RAB RAB B

A A

1E EMERG.

OPEN-CLOSED OPEN-CLOSED 1

N/A RECIRC DAMPER, IND ON PLANT COMP (PT ID D52636, D52637). REFER TO NOTE 19.

EMER. VENT.

DAMPER POSI D2 SVSIZS0105B1 SVSIZS0105B2 S

S RAB RAB B

A A

1E EMERG.

OPEN-CLOSED OPEN-CLOSED 1

N/A RECIRC DAMPER, IND ON PLANT COMP (PT ID D52638, D52639). REFER TO NOTE 19.

EMER. VENT.

DAMPER POSI D2 SVSIZS0106A1 SVSIZS0106A2 S

S RAB RAB B

A A

1E EMERG.

OPEN-CLOSED OPEN-CLOSED 1

N/A RECIRC DAMPER, IND ON PLANT COMP (PT ID D53163, D53164). REFER TO NOTE 19.

Security-Related Information Withheld Under 10 CFR 2.390

WSES-FSAR-UNIT-3 TABLE 7.5-3 (Sheet 26 of 40)

Revision 13 (04/04)

ACCIDENT MONITORING INSTRUMENTATION SERIAL NUMBER VARIABLE RG197 CAT/

TYPE LOOP COMPONENT COMP TYPE LOCATION ENV SEIS QA POWER SUPPLY CLASS RANGE/UNITS NUMBER OF CHANNEL SPDS I/O COMMENTS EMER. VENT.

DAMPER POSI D2 SVSIZS0106B1 SVSIZS0106B2 S

S RAB RAB B

A A

1E EMERG.

OPEN-CLOSED OPEN-CLOSED 1

N/A RECIRC DAMPER, IND ON PLANT COMP (PT ID D53188, D53187). REFER TO NOTE 19.

EMER. VENT.

DAMPER POSI D2 HVRIZS0121A1 HVRIZS0121A2 S

S RAB RAB C

N/A N/A N1E EMERG.

OPEN-CLOSED OPEN-CLOSED 1

N/A RAB NORMAL VENT SYSTEM EXHAUST FAN INLET DAMPER IND ON PLANT COMPUTER (PT ID D52021, D52022). REFER TO NOTE 19.

EMER. VENT.

DAMPER POSI D2 HVRIZS0122A1 HVRIZS0122A2 S

S RAB RAB C

N/A N/A N1E EMERG.

OPEN-CLOSED OPEN-CLOSED 1

N/A RAB NORMAL VENT SYSTEM EXHAUST FAN OUTLET DAMPER IND ON PLANT COMPUTER (PT ID D52025, D52026). REFER TO NOTE 19.

EMER. VENT.

DAMPER POSI D2 HVRIZS0121B1 HVRIZS0121B2 S

S RAB RAB C

N/A N/A 1E EMERG.

OPEN-CLOSED OPEN-CLOSED 1

N/A RAB NORMAL VENT SYSTEM EXHAUST FAN INLET DAMPER IND ON PLANT COMPUTER (PT ID D52023, D52024). REFER TO NOTE 19.

EMER. VENT.

DAMPER POSI D2 HVRIZS0122B1 HVRIZS0122B2 S

S RAB RAB C

N/A N/A N1E EMERG.

OPEN-CLOSED OPEN-CLOSED 1

N/A RAB NORMAL VENT SYSTEM EXHAUST FAN INLET DAMPER IND ON PLANT COMPUTER (PT ID D52027, D52028). REFER TO NOTE 19.

EMER. VENT.

DAMPER POSI D2 SVSIZ0101/1 SVSIZS0101/2 NOT AVAILABLE S

S I

RAB RAB CP-18 B

A A

1E EMERG.

OPEN-CLOSED OPEN-CLOSED RED / GREEN 1

N/A SWGR AREA AIR HANDLING UNIT OUTSIDE DAMPER.

REFER TO NOTE 19.

EMER. VENT.

DAMPER POSI D2 SVSIZS0102/1 SVSIZS0102/2 NOT AVAILABLE S

S I

RAB RAB CP-18 B

A A

1E EMERG.

OPEN-CLOSED OPEN-CLOSED RED / GREEN 1

N/A SWGR AREA AIR HANDLING UNIT OUTSIDE DAMPER.

REFER TO NOTE 19.

EMER. VENT.

DAMPER POSI D2 SVSIZS0103A1 SVSIZS0103A2 S

S RAB RAB B

A A

1E EMERG.

OPEN-CLOSED OPEN-CLOSED 1

N/A SWGR AREA AIR HANDLING UNIT RETURN AIR DAMPER.

IN ON PLANT COMPUTER (PT ID D53151, D53152). REFER TO NOTE 19.

EMER. VENT.

DAMPER POSI D2 SVSIZS0103B1 SVSIZS0103B2 S

S RAB RAB B

A A

1E EMERG.

OPEN-CLOSED OPEN-CLOSED 1

N/A SWGR AREA AIR HANDLING UNIT RETURN AIR DAMPER.

IN ON PLANT COMPUTER (PT ID D53153, D53154). REFER TO NOTE 19.

EMER. VENT.

DAMPER POSI D2 ANPIZS0103/1 ANPIZS0103/2 S

S RAB RAB C

N/A N/A N1E VITAL OPEN-CLOSED OPEN-CLOSED 1

N/A ANNULUS NEG. PRESS. SYS.

INLET DAMPER. IND ON PLANT COMP (PT ID D51603, D51612). REFER TO NOTE 19.

Security-Related Information Withheld Under 10 CFR 2.390

WSES-FSAR-UNIT-3 TABLE 7.5-3 (Sheet 27 of 40)

Revision 13 (04/04)

ACCIDENT MONITORING INSTRUMENTATION SERIAL NUMBER VARIABLE RG197 CAT/

TYPE LOOP COMPONENT COMP TYPE LOCATION ENV SEIS QA POWER SUPPLY CLASS RANGE/UNITS NUMBER OF CHANNEL SPDS I/O COMMENTS EMER. VENT.

DAMPER POSI D2 ANPIZS0106/1 ANPIZSO106/2 S

S RAB RAB C

N/A N/A N1E VITAL OPEN-CLOSED OPEN-CLOSED 1

N/A ANNULUS NEG. PRESS. SYS.

EXHAUST DAMPER. IND ON PLANT COMP (PT ID D51604, D51605). REFER TO NOTE 19.

EMER. VENT.

DAMPER POSI D2 CCSIZS0102A1 CCSIZS0102A2 S

S RCB RCB A

A A

1E EMERG.

OPEN-CLOSED OPEN-CLOSED 1

N/A CONTAINMENT FAN COOLER SAFETY DISCHARGE DAMPER.

IND ON PLANT COMPUTER.

(PT ID D51152, D51153).

REFER TO NOTE 19.

EMER. VENT.

DAMPER POSI D2 CCSIZS0102B1 CCSIZS0102B2 S

S RCB RCB A

A A

1E EMERG.

OPEN-CLOSED OPEN-CLOSED 1

N/A CONTAINMENT FAN COOLER SAFETY DISCHARGE DAMPER.

IND ON PLANT COMPUTER.

(PT ID D51154, D51155).

REFER TO NOTE 19.

EMER. VENT.

DAMPER POSI D2 ANPIZS0102/1 ANPIZS0102/2 NOT AVAILABLE S

S I

RB RB CP-18 A

A A

1E EMERG.

OPEN-CLOSED OPEN-CLOSED RED / GREEN 1

N/A ANNULUS NEGATIVE PRESSURE SYSTEM ISOLATION VALVE. REFER TO NOTE 19.

EMER. VENT.

DAMPER POSI D2 HVRIZS0313B NOT AVAILABLE S

I RAB CP-18 A

A A

1E EMERG.

OPEN-CLOSED RED / GREEN 1

N/A CVAS FILTER TR-B OUTLET VALVE. REFER TO NOTE 19.

EMER. VENT.

DAMPER POSI D2 HVRIZSO304B NOT AVAILABLE S

I RAB CP-18 A

A A

1E EMERG.

OPEN-CLOSED LESS / MORE 1

N/A CVAS FILTER TR-B INLET VALVE. REFER TO NOTE 19.

EMER. VENT.

DAMPER POSI D2 ANPIZS0101/1 ANPIZS0101/2 NOT AVAILABLE S

S I

RB RB CP-18 A

A A

1E EMERG.

OPEN-CLOSED OPEN-CLOSED RED / GREEN 1

N/A ANNULUS NEGATIVE PRESSURE SYS ISOLATION VALVE. REFER TO NOTE 19.

EMER. VENT.

DAMPER POSI D2 HVRIZS0301/1 HVRIZS0301/2 NOT AVAILABLE S

S I

RAB RAB CP-18 A

A A

1E EMERG.

OPEN-CLOSED OPEN-CLOSED RED / GREEN 1

N/A RAB VENT. SYS FAN TRANSFER VALVE. REFER TO NOTE 19.

EMER. VENT.

DAMPER POSI D2 SBVIZS0101A NOT AVAILABLE S

I RB CP-18 A

A A

1E EMERG.

OPEN-CLOSED LESS / MORE 1

N/A SHIELD BLDG VENT FAN (SBV-MFAN-0001A) TR. A INLET VALVE. REFER TO NOTE 19.

EMER. VENT.

DAMPER POSI D2 SBVIZS0110A NOT AVAILABLE S

I RAB CP-18 A

A A

1E EMERG.

OPEN-CLOSED RED / GREEN 1

N/A SHIELD BLDG VENT FAN (SBV-MFAN-0001A) TR. A OUTLET VALVE. REFER TO NOTE 19.

EMER. VENT.

DAMPER POSI D2 SBVIZS0114A NOT AVAILABLE S

I RAB CP-18 A

A A

1E EMERG.

OPEN-CLOSED RED / GREEN 1

N/A SHIELD BLDG VENT FAN (SBV-MFAN-0001A) DISCHARGE STACK VALVE. REFER TO NOTE 19.

EMER. VENT.

DAMPER POSI D2 HVCIZS0307/1 HVCIZS0307/2 NOT AVAILABLE S

S I

RAB RAB CP-18 B

A A

1E EMERG.

OPEN-CLOSED OPEN-CLOSED RED / GREEN 1

N/A CONTROL ROOM TOILET EXHAUST FAN E-34 ISOLATION DISCHARGE VALVE. REFER TO NOTE 19.

Security-Related Information Withheld Under 10 CFR 2.390

WSES-FSAR-UNIT-3 TABLE 7.5-3 (Sheet 28 of 40)

Revision 13 (04/04)

ACCIDENT MONITORING INSTRUMENTATION SERIAL NUMBER VARIABLE RG197 CAT/

TYPE LOOP COMPONENT COMP TYPE LOCATION ENV SEIS QA POWER SUPPLY CLASS RANGE/UNITS NUMBER OF CHANNEL SPDS I/O COMMENTS EMER. VENT.

DAMPER POSI D2 SBVIZS0113A NOT AVAILABLE S

I RB CP-18 A

A A

1E EMERG.

OPEN-CLOSED RED / GREEN 1

N/A SHIELD BLDG VENT FAN (SBV-MFAN-0001A) RECIRCULATION VALVE TO ANNULUS. REFER TO NOTE 19.

EMER. VENT.

DAMPER POSI D2 SBVIZS0101B NOT AVAILABLE S

I RB CP-18 A

A A

1E EMERG.

OPEN-CLOSED LESS / MORE 1

N/A SHIELD BLDG VENT FAN (SBV-MFAN-0001B) TR. B INLET VALVE.

REFER TO NOTE 19.

EMER. VENT.

DAMPER POSI D2 HVRIZS0109/1 HVRIZS0109/2 NOT AVAILABLE S

S I

RB RB CP-18 A

A A

1E EMERG.

OPEN-CLOSED OPEN-CLOSED RED / GREEN 1

N/A RAB NORMAL VENT SYS ISOLATION VALVE. REFER TO NOTE 19.

EMER. VENT.

DAMPER POSI D2 HVRIZS0111/1 HVRIZS0111/2 NOT AVAIABLE S

S I

RB RB CP-18 A

A A

1E EMERG.

OPEN-CLOSED OPEN-CLOSED RED / GREEN 1

N/A RAB NORMAL VENT SYS SUPPLY TO PIPE PENETRATION AREA VLV. REFER TO NOTE 19.

EMER. VENT.

DAMPER POSI D2 HVRIZS0313A NOT AVAILABLE S

I RAB CP-18 A

A A

1E EMERG.

OPEN-CLOSED RED / GREEN 1

N/A CVAS FILTER TR. A OUTLET VLV.

REFER TO NOTE 19.

EMER. VENT.

DAMPER POSI D2 HVRIZS0104/1 HVRIZS0104/2 NOT AVAILABLE S

S I

RAB RAB CP-18 A

A A

1E EMERG.

OPEN-CLOSED OPEN-CLOSED RED / GREEN 1

N/A RAB NORMAL VENT SYS TO PIPE PENETRATION AREA VALVE.

REFER TO NOTE 19.

EMER. VENT.

DAMPER POSI D2 HVRIZS0304A NOT AVAILABLE S

I RAB CP-18 A

A A

1E EMERG.

OPEN-CLOSED RED / GREEN 1

N/A CVAS FILTER TR. A INLET VLV.

REFER TO NOTE 19.

EMER. VENT.

DAMPER POSI D2 HVRIZS0105/1 HVRIZS0105/2 NOT AVAILABLE S

S I

RB RB CP-18 A

A A

1E EMERG.

OPEN-CLOSED OPEN-CLOSED RED / GREEN 1

N/A RAB NORMAL VENT SYS SUPPLY TO PIPE PENETRATION AREA VALVE. REFER TO NOTE 19.

EMER. VENT.

DAMPER POSI D2 HVCIZS0306/1 HVCIZS0306/2 NOT AVAILABLE S

S I

RAB RAB CP-18 B

A A

1E EMERG.

OPEN-CLOSED OPEN-CLOSED RED / GREEN 1

N/A CONTROL ROOM TOILET EXHAUST FAN E-34 ISOLATION DISCHARGE VALVE. REFER TO NOTE 19.

EMER. VENT.

DAMPER POSI D2 SBVIZS0110B NOT AVAILABLE S

I RAB CP-18 A

A A

1E EMERG.

OPEN-CLOSED RED / GREEN 1

N/A SHIELD BLDG VENT FAN (SBV-MFAN-0001B) TR. B OUTLET VALVE. REFER TO NOTE 19.

EMER. VENT.

DAMPER POSI D2 SBVIZS0114B NOT AVAILABLE S

I RAB CP-18 A

A A

1E EMERG.

OPEN-CLOSED RED / GREEN 1

N/A SHIELD BLDG VENT FAN (SBV-MFAN-0001B) MAIN DISCH. TO STACK VALVE. REFER TO NOTE 19.

EMER. VENT.

DAMPER POSI D2 HVCIZS0314/1 HVCIZS0314/2 NOT AVAILABLE S

S I

RAB RAB CP-18 B

A A

1E EMERG.

OPEN-CLOSED OPEN-CLOSED RED / GREEN 1

N/A C NTRL ROM KITCHEN &

CONFERENCE RM EXH FAN E-42 ISO DISCHARGE VALVE. REFER TO NOTE 19.

EMER. VENT.

DAMPER POSI D2 HVCIZS0101/1 HVCIZS0101/2 NOT AVAILABLE S

S I

RAB RAB CP-18 B

A A

1E EMERG.

OPEN-CLOSED OPEN-CLOSED RED / GREEN 1

N/A CONTROL ROOM SUPPLY FAN OUTSIDE INTAKE AIR VALVE.

REFER TO NOTE 19.

Security-Related Information Withheld Under 10 CFR 2.390

WSES-FSAR-UNIT-3 TABLE 7.5-3 (Sheet 29 of 40)

Revision 13 (04/04)

ACCIDENT MONITORING INSTRUMENTATION SERIAL NUMBER VARIABLE RG197 CAT/

TYPE LOOP COMPONENT COMP TYPE LOCATION ENV SEIS QA POWER SUPPLY CLASS RANGE/UNITS NUMBER OF CHANNEL SPDS I/O COMMENTS EMER. VENT.

DAMPER POSI D2 HVRIZS0110/1 HVRIZS0110/2 NOT AVAILABLE S

S I

RB RB CP-18 A

A A

1E EMERG.

OPEN-CLOSED OPEN-CLOSED RED / GREEN 1

N/A RAB NORMAL VENT SYS EXHAUST ROOM PIPE CHASE AREA VALVE. REFER TO NOTE 19.

EMER. VENT DAMPER POSI D2 HVRIZS0106/1 HVRIZS0106/2 NOT AVAILABLE S

S I

RAB RAB CP-18 A

A A

1E EMERG.

OPEN-CLOSED OPEN-CLOSED RED / GREEN 1

N/A RAB NORMAL VENT SYS ISO VLV. REFER TO NOTE 19.

EMER. VENT DAMPER POSI D2 HVRIZS0108/1 HVRIZS0108/2 NOT AVAILABLE`

S S

I RB RB CP-18 A

A A

1E EMERG.

OPEN-CLOSED OPEN-CLOSED RED / GREEN 1

N/A RAB NORMAL VENT SYS ISO VLV. REFER TO NOTE 19.

EMER. VENT DAMPER POSI D2 HVRIZS0302/1 HVRIZS0302/2 NOT AVAILABLE S

S I

RB RB CP-18 A

A A

1E EMERG.

OPEN-CLOSED OPEN-CLOSED RED / GREEN 1

N/A CVAS FAN E-23 TRANSFER VALVE. REFER TO NOTE 19.

EMER. VENT DAMPER POSI D2 HVCIZS0313/1 HVCIZS0313/2 NOT AVAILABLE S

S I

RAB RAB CP-18 B

A A

1E EMERG.

OPEN-CLOSED OPEN-CLOSED RED / GREEN 1

N/A CNTROL RM KITCHEN &

CONFERENCE RM EXN FAN E-42 ISO DISCHARGE VALVE.

REFER TO NOTE 19.

EMER. VENT DAMPER POSI D2 HVCIZS0102/1 HVCIZS0102/2 NOT AVAILABLE S

S I

RAB RAB CP-18 B

A A

1E EMERG.

OPEN-CLOSED OPEN-CLOSED RED / GREEN 1

N/A CNTROL RM S FAN OUTSIDE INTAKE AIR VALVE. REFER TO NOTE 19.

EMER. VENT DAMPER POSI D2 SBVIZS0113B NOT AVAILABLE S

I RB CP-18 A

A A

1E EMERG.

OPEN-CLOSED RED / GREEN 1

N/A SHIELD BLDG VENT FAN (SBV-MFAN-0001B) RECIRCULATION VLV TO ANNULUS. REFER TO NOTE 19.

EMER. VENT DAMPER POSI D2 HVCIZS0107/1 HVCIZS0107/2 NOT AVAILABLE S

S I

RAB RAB CP-18 A

A A

1E EMERG.

OPEN-CLOSED OPEN-CLOSED RED / GREEN 1

N/A RAB NORMAL VENT SYS ISO VLV. REFER TO NOTE 19.

STATUS OF STANDBY POWER BATTERY AB VOLTAGE D2 DC EXCTR4403AB DC IEI4613 S

I RAB CP-1 B

A A

1E EMERG.

0-150 VDC 1

N/A STATUS OF STANDBY POWER DG 1 WATTS D2 EG IEI6907A EG ECT2316-2A EG ECT2316-2B EG ECT2316-2C EG EPT2316A I

S S

S S

CP-1 RAB RAB RAB RAB B

A A

1E VITAL 0-7 MW 1

N/A REFER TO NOTE 14.

Security-Related Information Withheld Under 10 CFR 2.390

WSES-FSAR-UNIT-3 TABLE 7.5-3 (Sheet 30 of 40)

Revision 15 (03/07)

ACCIDENT MONITORING INSTRUMENTATION SERIAL NUMBER VARIABLE RG197 CAT/

TYPE LOOP COMPONENT COMP TYPE LOCATION ENV SEIS QA POWER SUPPLY CLASS RANGE/UNITS NUMBER OF CHANNEL SPDS I/O COMMENTS STATUS OF STANDBY POWER DG 2 WATTS D2 EG IEI6907B EG ECT2366-2A EG ECT2366-2B EG ECT2366-2C EG EPT2366A I

S S

S S

CP-1 RAB RAB RAB RAB B

A A

1E VITAL 0-7 MW 1

N/A STATUS OF STANDBY POWER DG 1 VARS D2 EG IEI6908A EG ECT2316-2A EG ECT2316-2B EG ECT2316-2C EG EPT2316A I

S S

S S

CP-1 RAB RAB RAB RAB B

A A

1E VITAL

(-)5 TO +5 MVAR 1

N/A REFER TO NOTE 14.

STATUS OF STANDBY POWER DG 2 VARS EG IEI6908B EG ECT2366-2A EG ECT2366-2B EG ECT2366-2C EG EPT2366A I

S S

S S

CP-1 RAB RAB RAB RAB B

A A

1E VITAL

(-)5 TO +5 MVAR 1

N/A STATUS OF STANDBY POWER DG 1 LOAD CURRENT D2 EG IEI6909A EG ECT2316-2A EG ECT2316-2B EG ECT2316-2C EG EPT2316A I

S S

S S

CP-1 RAB RAB RAB RAB B

A A

1E VITAL 0-1000 A 1

N/A REFER TO NOTE 14.

STATUS OF STANDBY POWER DG 2 LOAD CURRENT D2 EG IEI6909B EG ECT2366-2B EG ECT2366-2C EG ECT2366A I

S S

S CP-1 RAB RAB RAB B

A A

1E VITAL 0-1000 A 1

N/A STATUS OF STANDBY POWER DG 1 FREQUENCY D2 EG EXMTR2328A EG IEI6911A S

I RAB CP-1 B

A A

1E VITAL 55-65 HZ 1

N/A REFER TO NOTE 14.

STATUS OF STANDBY POWER DG 2 FREQUENCY D2 EG EXMTR2378A EG IEI6911B S

I RAB CP-1 B

A A

1E VITAL 55-65 HZ 1

N/A STATUS OF STANDBY POWER BATTERY A VOLTAGE D2 DC EXMTR4403A DC IEI7010A1 S

I RAB CP-1 B

A A

1E VITAL 0-150 VDC 1

N/A REFER TO NOTE 14.

STATUS OF STANDBY POWER BATTERY B VOLTAGE D2 DC EXMTR4403B DC IEI7010B1 S

I RAB CP-1 B

A A

1E VITAL 0-150 VDC 1

N/A REFER TO NOTE 14.

STATUS OF STANDBY POWER DG 1 VOLTAGE D2 EG EM 2317A EG EPT 2316A I

S CP-1 RAB B

A A

1E VITAL 0-5250 VAC 1

N/A REFER TO NOTE 14.

Security-Related Information Withheld Under 10 CFR 2.390

WSES-FSAR-UNIT-3 TABLE 7.5-3 (Sheet 31 of 40) Revision 10 (10/99)

ACCIDENT MONITORING INSTRUMENTATION

SERIAL NUMBER VARIABLE RG197 CAT/

TYPE LOOP COMPONENT COMP TYPE LOCATION ENV SEIS QA POWER SUPPLY CLASS RANGE/UNITS NUMBER OF CHANNEL SPDS I/O COMMENTS



STATUS OF STANDBY POWER DG 2 VOLTAGE D2 EG EM 2376A EG EPT 2366A I

S CP-1 RAB B

A A

1E VITAL 0-5250 VAC 1

N/A STATUS OF STANDBY POWER INST AIR SPLY PRESSURE D2 IA IPT9700 IA IPI9700 S

I TGB CP-1 C

N/A N/A N1E VITAL 0-125 PSIG 1

N/A REFER TO NOTE 14.

STATUS OF STANDBY POWER STATION AIR PRESSURE D2 SA ITP9800 SA IPI9800 S

I TGB CP-1 C

N/A N/A N1E VITAL 0-125 PSIG 1

N/A REFER TO NOTE 14.

STATUS OF STANDBY POWER DG 1 AND 2 TROUBLE (ALARM)

D2 D0201 D0203 I

I CP-1 CP-1 B

A A

1E VITAL 1/DG N/A ANNUNCIATION STATUS OF STANDBY POWER DG 1, 2 NOT AVAIL (ALARM)

D2 D0101 EGFILS6906A EGAIPS3008A1 EGAIPS3008A2 D0103 EGFILS6906B EGAIPS3008B1 EGAIPS3008B2 I

S S

S I

S S

S CP-1 RAB RAB RAB CP-1 RAB RAB RAB B

A A

1E VITAL 1/DG N/A ANNUNCIATION REFER TO NOTE 14.

STATUS OF STANDBY POWER BATTERY A, B AND AB TROUBLE D2 DC ERELA1 DC ERELA2 DC EFDSA C1208 DC ERLB1 DC ERELB2 DC EFDSB C1210 DC ERELAB1 DC ERELAB2 DC EFDSAB C1209 S

S S

I S

S S

I S

S S

I RAB RAB RAB CP-35 RAB RAB RAB CP-35 RAB RAB RAB CP-35 B

A A

1E VITAL 1/BUS N/A ANNUNCIATION ANNUNCIATION ANNUNCIATION REFER TO NOTE 14.

STATUS OF STANDBY POWER NITROGEN SYSTEM TROUBLE D2 D0608 NG ECP214A-1BR I

S CP-1 CHILL C

N/A N/A N1E VITAL 1

N/A ANNUNCIATION Security-Related Information Withheld Under 10 CFR 2.390

WSES-FSAR-UNIT-3 TABLE 7.5-3 (Sheet 32 of 40)

Revision 13 (04/04)

ACCIDENT MONITORING INSTRUMENTATION SERIAL NUMBER VARIABLE RG197 CAT/

TYPE LOOP COMPONENT COMP TYPE LOCATION ENV SEIS QA POWER SUPPLY CLASS RANGE/UNITS NUMBER OF CHANNEL SPDS I/O COMMENTS STATUS OF STANDBY POWER EMERGENCY BUS VOLTAGE (3A3-S)

D2 4KVEPT3A-12A 4KVEPT3A-12B 4KVEPT3A-12C EG EM2317B S

S S

I RAB RAB RAB CP-1 B

A A

1E EMERG.

0-5250 VAC 1

N/A STATUS OF STANDBY POWER EMERGENCY BUS VOLTAGE (3B3-S)

D2 4KVEPT3B-12A 4KVEPT3B-12B 4KVEPT3B-12C EG EM2367B S

S S

I RAB RAB RAB CP-1 B

A A

1E EMERG.

0-5250 VAC 1

N/A CNTMNT ARE HIGH RANGE RADIATION E1 C3 ARMIRD5400A ARMIRE5400A ARMIR15400A S

S I

RCB RCB CP-14 A

A A

1E VITAL 1.00E+00-1.00E+08 R/hr 1.00E+00-1.00E+08 R/hr 2

C48234 CNTMNT AREA HIGH RANGE RADIATION E1 ARMIRD5400B ARMIRE5400B ARMIRI5400B S

S I

RCB RCB CP-14 A

A A

1E VITAL 1.00E+00-1.00E+08 R/hr 1.00E+00-1.00E+08 R/hr 2

C48235 RADIATION EXPOSURE RATE E2 ARMIRD5204 ARMIRE5204 S

S RB RAB C

N/A N/A N1E EMERG.

1.00E+02-1.00E+07 mR/hr 1.00E+02-1.00E+07 mR/hr 1

C48222 IND & RECORDING PROVIDED BY RAD COMPUTER ON CP-6 RADIATION EXPOSURE RATE E2 ARMIRD5205 ARMIRE5205 S

S RAB RAB C

N/A N/A N1E EMERG.

1.00E+02-1.00E+07 mR/hr 1.00E+02-1.00E+07 mR/hr 1

C48229 IND & RECORDING PROVIDED BY RAD COMPUTER ON CP-6 RADIATION EXPOSURE RATE E2 ARMIRD5206 ARMIRE5206 S

S RAB RAB C

N/A N/A N1E EMERG.

1.00E+02-1.00E+07 mR/hr 1.00E+02-1.00E+07 mR/hr 1

C48227 IND & RECORDING PROVIDED BY RAD COMPUTER ON CP-6 RADIATION EXPOSURE RATE E2 ARMIRD5207 ARMIRE5207 S

S RAB RAB C

N/A N/A N1E EMERG.

1.00E+02-1.00E+07 mR/hr 1.00E+02-1.00E+07 mR/hr 1

C48223 IND & RECORDING PROVIDED BY RAD COMPUTER ON CP-6 RADIATION EXPOSURE RATE E2 ARMIRD5208 ARMIRE5208 S

S RAB RAB A

N/A B

N1E EMERG.

1.00E+02-1.00E+07 mR/hr 1.00E+02-1.00E+07 mR/hr 1

C48224 IND & RECORDING PROVIDED BY RAD COMPUTER ON CP-6 RADIATION EXPOSURE RATE E2 ARMIRD5209 ARMIRE5209 S

S RAB RAB A

N/A B

N1E EMERG.

1.00E+02-1.00E+07 mR/hr 1.00E+02-1.00E+07 mR/hr 1

C48231 IND & RECORDING PROVIDED BY RAD COMPUTER ON CP-6 RADIATION EXPOSURE RATE E2 ARMIRD5210 ARMIRE5210 S

S RAB RAB A

N/A B

N1E EMERG.

1.00E+02-1.00E+07 mR/hr 1.00E+02-1.00E+07 mR/hr 1

C48225 IND & RECORDING PROVIDED BY RAD COMPUTER ON CP-6 CNTMNT OR PURGE EFFL.

E2 REFER TO SERIAL #076.

Security-Related Information Withheld Under 10 CFR 2.390

WSES-FSAR-UNIT-3 TABLE 7.5-3 (Sheet 33 of 40)

Revision 303 (06/09)

ACCIDENT MONITORING INSTRUMENTATION SERIAL NUMBER VARIABLE RG197 CAT/

TYPE LOOP COMPONENT COMP TYPE LOCATION ENV SEIS QA POWER SUPPLY CLASS RANGE/UNITS NUMBER OF CHANNEL SPDS I/O COMMENTS RCB SHIELD BLDG ANNULUS E2 REFER TO SERIAL #076.

AUX BLDG NOBLE GASES

& VENT FLOW RATE E2 REFER TO SERIAL #076.

CONDENSER AIR REMOVAL SYS EXHAUST C3 E2 PRMIRD0002 PRMIRE0002 RMSIUR0052-1 RMSIUR0052-2 PRMIFT0002 S

S R

R S

TGB TGB CP-52 CP-52 TGB C

N/A N/A N1E EMERG.

1.00E-07 to 1.00E+05Ci/cc 1.00E-07 to 1.00E+05Ci/cc 1.00E-03 to 1.00E+09Ci/sec 1.00E-07 to 1.00E+05Ci/cc 0-100 SCFM 1

C48209 C48212 C48215 C48218 REFER TO NOTE 13.

PLANT STACK MONITOR E2 C2 C3 PRMIRD0110 RMSIUR0052-1 PRMIRE0110 PRMIFT0110A1 S

R S

S RAB CP-52 RAB RAB A

N/A B

N1E EMERG.

1.00E-07 to 1.00E+05Ci/cc 1.00E+01 to 1.00E+13Ci/sec 1.00E-07 to 1.00E+05Ci/cc 0-153938 SCFM 1

C48194 C48188 C48185 PLANT STACK DESIGN FLOW IS 108,500 SCFM PLANT STACK MONITOR E2 C2 PRMIRD0110 RMSIUR0052-2 PRMIRE0110 PRMIFT0110A1 S

R S

S RAB CP-52 RAB RAB A

N/A B

N1E EMERG.

1.00E-07 to 1.00E+05Ci/cc 1.00E-07 to 1.00E+05Ci/cc 1.00E-07 to 1.00E+05Ci/cc 0-153938 SCFM 1

C48191 VENTS FROM ATMOS DUMP VA NOBLE GASES RADIATION E2 ARMIRD5500A ARMIRE5500A RMSIUR0052-2 S

S R

RB RAB CP-52 A

N/A B

N1E EMERG.

1.00E-01 to 1.00E+05mR/HR 1.00E-01 to 1.00E+05mR/HR 1.00E-01 to 1.00E+05mR/HR 1/MS LINE C48232 CALCULATION METHODOLOGY IS DESCRIBED IN FSAR SUBSEC 1.9.29.4. REFER TO NOTE 14.

VENTS FROM ATMOS DUMP VA NOBLE GASES RADIATION E2 ARMIRD5500B ARMIRE5500B RMSIUR0052-2 S

S R

RB RAB CP-52 A

N/A B

N1E EMERG.

1.00E-01 to 1.00E+05mR/HR 1.00E-01 to 1.00E+05mR/HR 1.00E-01 to 1.00E+05mR/HR 1/MS LINE C48233 CALCULATION METHODOLOGY IS DESCRIBED IN FSAR SUBSEC 1.9.29.4. REFER TO NOTE 14.

VENTS FROM ATMOS DUMP VA STM GEN PRES.

& FLOW E2 REFER TO SERIAL #052 & 053.

CONTROL ROOM A1 ARM-IRD-0200.1 S

RAB B

A A

1E VITAL 10 10

-2 2

N/A NONE AIR INTAKE RAD ARM-IRD-0200.2 S

RAB Ci/cc MON.

ARM-IRE-0200.1 R

CP-14 ARM-IRE-0200.2 R

CP-14 ARM-IRI-0200.1 I

CP-14 ARM-IRI-0200.2 I

CP-14 CONTROL ROOM A1 ARM-IRD-0200.5 S

RAB B

A A

1E VITAL 10 10

-2 2

N/A NONE AIR INTAKE RAD ARM-IRD-0200.6 S

RAB Ci/cc MON.

ARM-IRE-0200.5 R

CP-14 ARM-IRE-0200.6 R

CP-14 ARM-IRI-0200.5 I

CP-14 ARM-IRI-0200.6 I

CP-14 Security-Related Information Withheld Under 10 CFR 2.390

WSES-FSAR-UNIT-3 TABLE 7.5-3 (Sheet 34 of 40)

Revision 303 (06/09)

ACCIDENT MONITORING INSTRUMENTATION SERIAL NUMBER VARIABLE RG197 CAT/

TYPE LOOP COMPONENT COMP TYPE LOCATION ENV SEIS QA POWER SUPPLY CLASS RANGE/UNITS NUMBER OF CHANNEL SPDS I/O COMMENTS AIRBORNE RAD MAT. REL FROM FUEL HANDLING BLDG E2 PRMIRD3032 PRMIRE3032 RMSIUR0052-1 PRMIFT3032-B1 S

S R

S FHB FHB CP-52 FHB N/A N/A N/A N1E 1.00E-07 to 1.00E+05Ci/cc 1.00E-07 to 1.00E+05Ci/cc 1.00E-01 to 1.00E+11Ci/sec 0-8000 SCFM 1

C48206 C48200 C48197 DESIGN FLOW IS 3472 SCFM.

AIRBORNE RAD MAT. REL FROM FUEL HANDLING BLDG E2 PRMIRD3032 PRMIRE3032 RMSIUR0052-2 PRMIFT3032-B2 S

S R

S FHB FHB CP-52 FHB N/A N/A N/A N1E 1.00E-07 to 1.00E+05Ci/cc 1.00E-07 to 1.00E+05Ci/cc 1.00E-07 to 1.00E+05Ci/cc 0-8000 SCFM 1

C48203 DESIGN FLOW IS 3472 SCFM.

ALL INDENT.

PLANT RELEASE POINTS (PART. &

HAL.) COND. VAC PP, FUEL HAND.

BLDG EMGR EXH PLNT VENT STACK E3 GRAB SAMPLING AS REQ. IN NUREG 0737.II.F.1 AT ALL REL. POINTS (CONDENSER VACUUM PUMP, FHB EMERG.

EXH., PLANT VENT STACK)

N/A REFER TO FSAR 1.9-29.

RAD. EXP.

METERS E3 N/A N/A N/A N/A N/A N/A DELETED IN RG 1.97 R/3 AIRBORNE RADIOHALOGENS

& PARTICULATE E3 N/A N/A N/A N/A 1.00E-08 1.00E+02 CI/CC N/A N/A PORTABLE INSTRUMENT PLANT & ENV RAD. PHOTONS E3 N/A N/A N/A N/A P 2.00E-04 R/HR B 1.00E-02 to 1.00E+05 RADS/HR N/A N/A PORTABLE INSTRUMENT PLANT AND ENV RADIO-ACT.

PORTABLE INST E3 N/A N/A C

N1E N/A N/A STATIONARY MULTI CHANNEL ANALYZER IS USED TO ANALYZE GRAB SAMPLE MET-WIND DIR 199' PRI TOW E3 EM ISE0100 B EM ISTRGMOD0001 S

R LOCAL LOCAL N/A N/A N/A N1E 0-360 DEG 0-360 DEG 1

N/A IND IS ON THE PLANT COMPUTER (PT ID C485311)

MET-WIND DIR 33' PRI TOW E3 EM ISE 0103B EM ISTRGMOD0001 S

R LOCAL LOCAL N/A N/A N/A N1E 0-360 DEG 0-360 DEG 1

N/A IND IS ON THE PLANT COMPUTER (PT ID C48530)

MET-WIND DIR 33' BK-UP TOW E3 EM ISE 0113B EM ISTRGMOD0001 S

R LOCAL LOCAL N/A N/A N/A N1E 0-360 DEG 0-360 DEG 1

N/A IND IS ON THE PLANT COMPUTER (PT ID C48616)

MET-WIND SPD 199' PRI TOW E3 EM ISE 0100A EM ISTRGMOD0001 S

R LOCAL LOCAL N/A N/A N/A N1E 0-55 MPS 0-55 MPS 1

N/A IND IS ON THE PLANT COMPUTER (PT ID C48527)

MET-WIND SPD 33' PRI TOW E3 EM ISTE 0103A EM ISTRGMOD0001 S

R LOCAL LOCAL N/A N/A N/A N1E 0-55 MPS 0-55 MPS 1

N/A IND IS ON THE PLANT COMPUTER (PT ID C48526)

Security-Related Information Withheld Under 10 CFR 2.390

WSES-FSAR-UNIT-3 TABLE 7.5-3 (Sheet 35 of 40)

Revision 14 (12/05)

ACCIDENT MONITORING INSTRUMENTATION SERIAL NUMBER VARIABLE RG197 CAT/

TYPE LOOP COMPONENT COMP TYPE LOCATION ENV SEIS QA POWER SUPPLY CLASS RANGE/UNITS NUMBER OF CHANNEL SPDS I/O COMMENTS MET-WIND SPD 33' BK-UP TOW E3 EM ISE 0113A EM ISTRGMOD0001 S

R LOCAL LOCAL N/A N/A N/A N1E 0-55 MPS 0-55 MPS 1

N/A IND IS ON THE PLANT COMPUTER (PT ID C48614)

EST OF ATMOS.

STAB. SPLIT DELTA-TEMP.

DIFF.PRI TOW A E3 EM ITE 0101A/B EM ISTRGMOD0001 S

R LOCAL LOCAL N/A N/A N/A N1E

-5 TO +10 DEGC

-5 TO +10 DEGC 1

N/A IND IS ON THE PLANT COMPUTER. (PT ID C48528)

EST OF ATMOS.

STAB SPLIT DELTA-TEMP.

DIFF. PRI TOW B E3 EM ITE 0102A/B EM ISTRGMOD0001 S

R LOCAL LOCAL N/A N/A N/A N1E

-5 TO +10 DEGC

-5 TO +10 DEGC 1

N/A IND IS ON THE PLANT COMPUTER. (PT ID C48529)

EST OF ATMOS STAB SPLIT DELTA-TEMP.

DIFF. BK UP TOW E3 EM ITE 0111A/B EM ISTRGMOD0001 S

R LOCAL LOCAL N/A N/A N/A N1E

-5 TO +10 DEGC

-5 TO +10 DEGC 1

N/A IND IS ON THE PLANT COMPUTER. (PT ID C48615)

EST OF ATMOS.

STAB SPLIT SIGMA-THETA 199 PRI TOW E3 EM ISE 0100B EM ISTRGMOD0001 S

R LOCAL LOCAL N/A N/A N/A N1E 0-100 DEG 0-100 DEG 1

N/A IND IS ON THE PLANT COMPUTER. (PT ID C48533)

EST OF ATMOS.

STAB SPLIT SIGMA-THETA 33 PRI TOW E3 EM ISE 103B EM ISTRGMOD0001 S

R LOCAL LOCAL N/A N/A N/A N1E 0-100 DEG 0-100 DEG 1

N/A IND IS ON THE PLANT COMPUTER. (PT ID C48532)

EST OF ATMOS.

STAB SPLIT SIGMA-THETA E3 EM ISE 0113B EM ISTRGMOD0001 S

R LOCAL LOCAL N/A N/A N/A N1E 0-100 DEG 0-100 DEG 1

N/A IND IS ON THE PLANT COMPUTER. (PT ID C48617)

GROSS ACTIVITY E3 C

N/A N/A N1E EMERG.

10 CI/ML-10 CI/ML N/A N/A FSAR SUBSEC 9.3.8 PROVIDES DESCRIPTION OF POST ACCIDENT SAMPLING SYSTEM (PASS)

GAMMA SPECTRUM E3 C3 C3 C

N/A N/A N1E EMERG.

ISOTOPIC ANALYSIS N/A N/A FSAR SUBSEC 9.3.8 PROVIDES DESCRIPTION OF POST ACCIDENT SAMPLING SYSTEM (PASS) (NOTE 18)

BORON CONTENT E3 C

N/A N/A 1E EMERG.

0-6000 PPM N/A N/A FSAR SUBSEC 9.3.8 PROVIDES DESCRIPTION OF POST ACCIDENT SAMPLING SYSTEM (PASS)

CHLORIDE CONTENT E3 C

N/A N/A N1E EMERG.

0-20 PPM N/A N/A FSAR SUBSEC 9.3.8 PROVIDES DESCRIPTION OF POST ACCIDENT SAMPLING SYSTEM (PASS)

Security-Related Information Withheld Under 10 CFR 2.390

WSES-FSAR-UNIT-3 TABLE 7.5-3 (Sheet 36 of 40)

Revision 14 (12/05)

ACCIDENT MONITORING INSTRUMENTATION SERIAL NUMBER VARIABLE RG197 CAT/

TYPE LOOP COMPONENT COMP TYPE LOCATION ENV SEIS QA POWER SUPPLY CLASS RANGE/UNITS NUMBER OF CHANNEL SPDS I/O COMMENTS DISSOLVED HYDROGEN E3 C

N/A N/A N1E EMERG.

0-2000CC(STP)/KG N/A N/A FSAR SUBSEC 9.3.8 PROVIDES DESCRIPTION OF POST ACCIDENT SAMPLING SYSTEM (PASS)

DISSOLVED OXYGEN E3 C

N/A N/A N1E EMERG.

0-20 PPM N/A N/A FSAR SUBSEC 9.3.8 PROVIDES DESCRIPTION OF POST ACCIDENT SAMPLING SYSTEM (PASS)

PH E3 C

N/A N/A N1E EMERG.

1-13 N/A N/A FSAR SUBSEC 9.3.8 PROVIDES DESCRIPTION OF POST ACCIDENT SAMPLING SYSTEM (PASS)

HYDROGEN CONTENT E3 N/A N/A N/A N1E EMERG.

0-10% (0-100%

INST. SCALE) 1 N/A FSAR SUBSEC 9.3.8 PROVIDES DESCRIPTION OF POST ACCIDENT SAMPLING SYSTEM (PASS)

OXYGEN CONTENT E3 N/A N/A N/A N1E EMERG.

0-30% (0-100%

INST. SCALE) 1 N/A FSAR SUBSEC 9.3.8 PROVIDES DESCRIPTION OF POST ACCIDENT SAMPLING SYSTEM.

GAMMA SPECTRUM E3 N/A N/A N/A N1E EMERG.

SUFF. FOR ISOT.

ANALYSIS 1

N/A FSAR SUBSEC 9.3.8 PROVIDES DESCRIPTION OF POST ACCIDENT SAMPLING SYSTEM (PASS)

Security-Related Information Withheld Under 10 CFR 2.390

WSES-FSAR-UNIT-3 TABLE 7.5-3 (Sheet 37 of 40)

Revision 307 (07/13)

Following notes are referred to in comment section of Table 7.5.3 (DRN 04-991, R13-A)

NOTE 1:

Deleted.

(DRN 04-991, R13-A)

NOTE 2:

For RCS pressure, Reg. Guide 1.97, Rev. 3 recommends a range of 0-4000 psig. Recorder and indicator have a range of 0-3000 psig. However, a range of 0-4000 psig is provided on the QSPDS which records on a 30 minute rolling buffer with the highest pressure value.

NOTE 3:

One containment isolation valve outside the containment is provided for certain lines penetrating the containment through Class C or Class D penetrations. (FSAR subsection 6.2.4.1.2 provides further details.) Dedicated indication for this valve is provided in the control room.

NOTE 4:

Two automatic valves are in series. Each valve operator is actuated from a separate and redundant ESFAS channel, with power supplied to each valve from a separate Train (bus) (except for valves CAP-103 and CAP-104 and valves CAP-203 and CAP-204) and each valve has a dedicated indication in the control (FSAR Section 6.2.4).

NOTE 5:

Redundant valve provided for subject line is either a check valve or locked closed valve. Only power operated (pneumatic, electric or solenoid) valve on subject line is provided with a dedicated indication in the control room (Refer to FSAR Subsection 6.2.4).

NOTE 6:

CARS line through penetration #47 has valve CARMVAAA202B outside the containment and its actuator is powered from Train B. Line inside the containment branches into two, with isolation valves CARMVAAA201B and CARMVAAA200B on each branch. Actuators of valve CARMVAAA201B is powered from Train B and of valve CARMVAAA200B is powered from Train A. CARS is a back up to Hydrogen Recombiner System. CARS manually operated from main control room only during post accident, and after manually opening the locked closed valve CARMVAAA203B installed downstream of CARMVAAA202B. Valve CARMVAAA202B is also designed to close upon loss of power to operators. Hence, present configuration satisfies the intent of Reg. Guide 1.97, Rev. 3 to provide adequate indication of containment isolation.

NOTE 7:

Two valves on supply lines are installed, one on each side of penetration. Third valve on return line has a redundant check valve inside the containment. Valves located outside the containment are locked closed during Normal and Shutdown condition and are controlled administratively. Sensors of three automatic valves are wired in parallel to a common set of indication. The valves actuated through a common hand switch. This design and administrative controls provided adequate conservatisms to existing configuration to meet the intent of Reg. Guide 1.97, Rev. 3.

NOTE 8:

Deleted NOTE 9:

For Steam Generator Level, Reg. Guide 1.97, Rev. 3 identifies Steam Generator Level as a Type D Category 1 variable. It specifies a range of "From tube sheet to separators." Furthermore, within Table 1, Item 2 of Reg.

Guide 1.97, Rev. 3 it states the following with regard to redundancy, "Within each redundant division of a safety system, redundant monitoring channels are not needed except for steam generator level in two loop plants."

Waterford 3 meets the intent of these requirements using the following independent and diverse channels of instrumentation:

(EC-8460, R307)

1.

Two qualified channels of wide range steam generator level are utilized for each steam generator. Their range is 0-42.4 (509) feet which encompasses the distance from approximately 1 foot above the tube sheet and the separator.

2.

Four qualified channels of narrow range steam generator level are utilized for each steam generator. Their range encompasses just over 17.1 feet (205) encompassing the normal operating range of the steam generator.

(EC-8460, R307)

3.

One qualified channel of Emergency Feedwater (EFW) flow per steam generator. Its range is 0-800 gpm which encompasses 0 to 114% of the EFW design flow.

WSES-FSAR-UNIT-3 TABLE 7.5-3 (Sheet 38 of 40)

Revision 307 (07/13)

4.

One qualified channel of main steam flow indication per steam generator.

5.

One qualified channel of steam generator pressure indication per steam generator.

6.

One qualified channel of RCS hot leg and cold leg temperature indication per hot/cold leg.

(EC-8460, R307)

The Plant Protection System provides protection against loss of primary heat sink by the Low Steam Generator Water Level Trip (LSGLT). Four narrow range instruments per SG are used for this trip signal initiation (Ins. Loops LT-1113A, B, C, D; LT-1123A, B, C, D for SG1 and 2 respectively). LSGLT set point corresponds to 5% of distance between the two narrow range liquid level pressure taps and is referenced from the lower tap. This set point corresponds to a water level of 31.3ft. above the tube sheet. The above mentioned instrument loops were also used for actuation of Emergency Feedwater Actuation System (EFAS). (Ref.

to W3-DBD-012 for further details) and High Steam Generator Level Trip (HSGLT). Whenever the level drops below or exceeds the narrow range level instruments, it will be monitored by either of the qualified independent channels of wide range SG level. In the extremely unlikely event that at least one wide range SG level indication was not available, the operator could determine level using diverse channels of indication. Using EFW flow coming into the SG, MS Flow going out of the SG and SG Pressure the operator can determine if SG level is increasing, decreasing or stabilized under/above the narrow range SG level.

Similarly, the operator could utilize SG Pressure, RCS Hot Leg temperature and RCS Cold Leg Temperature to determine SG level relative to the narrow range level indications. Such indications would be adequate until the SG level had returned to the range of the narrow range SG level instruments as directed by the EOPs.

(EC-8460, R307)

(DRN 04-744, R14)

NOTE 10: For Main Feedwater Flow, Reg. Guide 1.97, Rev. 3 recommends to measure up to 110% of design flow. Provided instruments at Waterford 3 can measure up to 108% of design flow. Design flow is 8.34 MPPH.

(DRN 04-744, R14)

NOTE 11: For Containment Sump Water Temperature, Reg. Guide 1.97, Rev. 3 recommends a range of 50-250 DEGF. Provided range is32-240 DEGF which is based on plant specific analysis.

NOTE 12: For Component Cooling Water Temperature to ESF system, Reg. Guide 1.97, Rev. 3 recommends a range of 32-200 DEGF. Provided range is 50-130 DEGF which is based on plant specific analysis. Refer to FSAR Table 9.2-9.

NOTE 13: For Condenser Air Removal Exhaust, Reg. Guide 1.97, Rev. 3 recommends a range of 0-100% of design flow from the flow transmitters. Provided flow value is fixed at a value of 218 SCFM. However during accident conditions the exhaust is routed via the plant stack.

NOTE 14: During a station blackout, these items are load-shedded to preserve the station batteries for a 4 hour4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br /> coping strategy. Ref. OP-902-005 and letter W3F192-0079.

For a loss of offsite power and failure of one diesel, the devices on the failed division only, are de-energized to conserve the battery in that division. This action extends battery power and provides additional time for trouble-shooting and restarting the failed diesel.

NOTE 15: This valve does not receive an automatic closure signal.

NOTE 16: Deviation from the qualification requirements of RG 1.97 for MS-116 A&B position indication was approved by the NRC via Safety Evaluation dated 6/5/97. (Also ref. letter W3F1-97-0120). TS 3.3.3.6 does not apply to this non-safety indication.

NOTE 18: Reg. Guide 1.97, Rev. 3, requires Category 1 for Radioactivity Concentration (Type C). A system which could meet Category 1 is not commercially available. The PASS meets Category 3 requirements.

NOTE 19; Operating status of the variable is indicated on the plant monitoring computer. Power supply class listed in table indicates power class for the monitored component. Power for plant monitoring computer is provided from highly reliable N1E Vital power supply which complies with Reg. Guide 1.97 requirements.

(DRN 03-1873, R13)

NOTE 20: Instrumentation not active. Simulated (Dummy) ICI assembly installed.

(DRN 03-1873, R13)

WSES-FSAR-UNIT-3 TABLE 7.5-3 (Sheet 39 of 40) Revision 10 (10/99)

Guide for Columns/Fields for Table 7.5-3 Column Heading Serial Number:

Sequential no. for each variable in Reg. Guide 1.97 Variable:

Name of the variable as defined in Reg. Guide 1.97 RG 1.97 Type/Category:

Type and Category of variable as defined in Reg. Guide 1.97 Loop Component:

UNID nos. of sensing, indicating and recording devices that are part of the instrumentation loop.

Component Type:

Defines the function of the component as follows.

S:

Sensing Device I:

Indicating Device R:

Recording Device Location:

Provides the building location for sensing device or the Control Panel no. for indicating or recording device. Following symbols are used.

RB:

Reactor Building (Wing Area)

RCB:

Reactor Containment Building RAB:

Reactor Auxiliary Building ANN:

Annulus Shield Building CP:

Control Panel in Control Room TGB:

Turbine Generator Building FHB:

Fuel Handling Building CHILL:

Chiller Building ENV:

Defines Environmental Qualification status of the loop.

A:

All or part of the instrument loop components fall within the scope of 10CFR 50.49 and NUREG 0588. Loop components located in a harsh environment are qualified for the environment in which they are located.

B:

This instrument loop is Class 1e, is located in a mild environment and is designed to function in such an environment. Limit switches for MS-116 A&B are Class 1E, power supply for indication is non 1E Vital.

C:

This instrument is non-Class 1E and is designed to withstand its specific service environment.

N/A:

Not Applicable SEIS:

Defines Seismic Qualification status of the loop. Following notations are used.

A:

Applicable components of this loop are seismically qualified in accordance with the criteria of FSAR Section 3.10.

B:

Portions of this indication loop are not seismically qualified.

N/A:

Not Applicable

WSES-FSAR-UNIT-3 TABLE 7.5-3 (Sheet 40 of 40) Revision 10 (10/99)

QA:

Defines Quality Assurance level of loop. Following notations are used.

A:

Either all or part of the components of this instrument loop are Class 1E or installed on safety class 1, 2, 3 lines or have an LP&L safety class designation of "SR." (Ref: Q-List). As such it is subject to quality assurance program requirements in accordance with 10CFR50 Appendix B.

B:

This loop is Non-Class 1E but it requires Quality Assurance requirements to support EQ and/or SQ requirements as specified by Reg.

Guide 1.97 Rev. 3.

N/A:

Not Applicable Power Supply Class:

Classified the power supply of loop components. NOTE: Vital receives power from uninterruptible power source. Emergency is backed up by Diesel Generator and/or Batteries.

Range/Units:

Define the range and the units for the instrument.

Following units have been used.

ppm:

Parts per Million DEGF Degrees in Fahrenheit DEGC:

Degrees in Celsius PSIA:

Pounds per square inch - absolute PSIG:

Pounds per square inch - gage Ft:

Feet FTW:

Feet of Water INW:

Inch of Water GPM:

Gallons per Minute Cu Ft:

Cubic Feet A:

Ampere G:

Gallons MPPH:

Million Pound Per Hour V:

Volts MW:

Mega Watts MVAR:

Mega Volt AMp Reactive Hz:

Hertz Ci/cc:

Micro Curies per Cubic Centimeter SCFM:

Cubic Feet per Minute (Standard)

DEG:

Degrees for Angular Direction MPS:

Meters per Second KG:

Kilo Gram R/HR:

Roentgen per hour No. of Channels:

Identifies Total number of channels provided for this variable. This number is indicated on each line item for that variable.

SPDS I/O:

Point Identification for Safety Parameter Display System.

Comment:

Special comments applicable to this loop, e.g. QSPDS stands for Qualified Safety Parameter Display System. PASS stands for Post Accident Sampling System.