MONTHYEARML13317A5071983-02-10010 February 1983 Notifies That Resources Necessary to Reply to Generic Ltrs 82-28 & 82-33,requesting Identification of Design for Reactor Coolant Inventory Sys & Schedule for Completion of Requirements for Emergency Response Capability,Unavailable Project stage: Other ML13333B8821983-04-18018 April 1983 Summary of 830413 Meeting W/Utils in Bethesda,Md Re Licensee Plans for Managing Plant Retrofit Items & Early Return to Power.List of Attendees & Handouts Encl Project stage: Meeting ML13317A5811983-04-21021 April 1983 Forwards Rept on Current Status of Emergency Response Capability Implementation,Per Suppl 1 to NUREG-0737 (Generic Ltr 82-33) Project stage: Other ML20023C1051983-05-0303 May 1983 Safety Evaluation Supporting Amend 91 to License DPR-49 Project stage: Approval ML20023C1061983-05-0303 May 1983 Notice of Issuance & Availability of Amend 91 to License DPR-49 Project stage: Other ML20023C1021983-05-0303 May 1983 Amend 91 to License DPR-49,revising Plan for Integrated Scheduling of Mods Project stage: Other ML13333B9021983-06-0101 June 1983 Plan for Managing Plant Retrofit Project stage: Other ML13333B9001983-06-0303 June 1983 Summary of 830601 Meeting W/Util Re Plan for Managing Retrofit Items.License Amend Schedule,W/Proposed safety- Based Integrated Schedule,Will Be Submitted on or About 831115.List of Attendees & Handouts Encl Project stage: Meeting ML13310A8011983-06-10010 June 1983 Submits Description & Basic Premise for Plan for Early Return to Power & Plan for Managing Plant Retrofit & Discusses Implementation of Each Plan Project stage: Other ML13310A8031983-06-13013 June 1983 Delineates Activities Associated W/Continuation of Work to Resolve Differences Resulting from Sep.Proposed Corrective Actions to Resolve Open Items Will Be Provided in Last Quarter of 1983 Project stage: Other ML13310A8041983-06-16016 June 1983 Forwards Replacement Page 2 for R Dietch Re Util Plans for Continuation of Work at Facility.Replacement Page Supplied to Clarify Possible Problems of Interpretation Due to Typographical Errors Project stage: Other ML13310A8051983-06-17017 June 1983 Forwards Plan for Managing Plant Retrofit to Assist in Reducing Capital Expenditures & to Improve Capacity Factor. NRR Concurrence Requested Project stage: Other ML13310A8751983-08-0101 August 1983 Comments on Util Approach to Continuation of Work at Facility.General Approach to Establish Integrated Schedule for Implementing Mods Acceptable.Plan for Early Return to Power,Per ,Not Received Project stage: Other ML13310A9371983-09-0101 September 1983 Application for Withholding Proprietary Westinghouse Analytical Ranking Process Project stage: Request ML13308A2891983-09-0202 September 1983 Notification of 830908 Meeting W/Util in San Diego,Ca to Discuss Unit 3 Readiness for Full Power Operation Project stage: Request ML13310A9341983-09-0202 September 1983 Submits Methodology to Be Used in Developing Integrated Living Schedule.Final Result Will Be long-term Schedule for Implementing Backfits Based on 18-month Operating Cycles. Proprietary Version Withheld (Ref 10CFR2.790) Project stage: Other ML13333B9511983-10-20020 October 1983 Summary of 831005 Meeting W/Util & Westinghouse Re Methodology Being Used to Prioritize Backfit Projects. Viewgraphs Encl Project stage: Meeting ML13310B0331983-10-24024 October 1983 Forwards Proprietary Viewgraphs Provided at 831005 Meeting W/Util & Westinghouse.Viewgraphs Withheld Per NRC Manual Chapter 9.5(4) Since Matl Intended for General Info & Will Not Be Used as Basis for NRC Actions Project stage: Meeting ML13310B0581983-11-0101 November 1983 Forwards Proprietary Affidavit of Jd Mcadoo,Identifying Info Sought to Be Withheld in 830901 Submittal.Affidavit Withheld (Ref 10CFR2.790) Project stage: Other ML13310B0731983-11-16016 November 1983 Advises That 830902 Proposed Methodology to Be Used to Develop Integrated Living Schedule for Implementation of Capital Mod Projects,Acceptable W/Two Exceptions Re Integrated Retrofit Schedule & Facility Restart Project stage: Other ML13310B0751983-11-21021 November 1983 Forwards Schedules for All Capital Backfit Projects Based on Westinghouse Analytical Ranking Process Methodology. Submittal Provided for Early Review & Comment.Upon Resolution,License Amend Will Be Submitted Project stage: Other ML13310B1081983-12-0606 December 1983 Forwards Summaries of All Regulatory Projects Included in Integrated Living Schedule & Edited Schedule of Backfits, in Response to NRC Request at 831122 Meeting Project stage: Meeting ML13333B9911983-12-15015 December 1983 Summary of 831122 Meeting W/Util & Westinghouse Re Results of Util Prioritization of Capital Backfit Projects & Integrated Living Schedule Project stage: Meeting ML13310B1591984-01-20020 January 1984 Advises That Revised Schedule for Capital Projects to Implement Proposed Integrated Living Schedule Unacceptable. Proposed Schedule Indicates Delays in Implementing Mods Prescribed in Commission Regulations Project stage: Other ML13310B2611984-02-27027 February 1984 Forwards Revised Integrated Living Schedule Based on Removing Any SEP & Fire Protection Safe Shutdown Backfits. Outage Schedules for Three Cycles of Operation Encl Project stage: Other ML13333C0191984-03-20020 March 1984 Summary of 840308 Meeting W/Utils in Bethesda,Md Re Licensee Revised Proposal for Integrated Living Schedule Submitted by .List of Attendees & Agenda Encl Project stage: Meeting ML13333C0201984-03-30030 March 1984 Summary of 840328 Meeting W/Util & Bechtel in Bethesda,Md Re Licensing Activities at Facility & Licensee Proposal for Integrated Living Schedule Project stage: Meeting ML13310B4171984-05-23023 May 1984 Application for Amend 119 to License DPR-13,consisting of Proposed Change 134.Change Revises Section 3, Contents & Conditions, to Include New Condition 3.J, Integrated Living Schedule of Backfits Project stage: Request ML13310B4131984-05-23023 May 1984 Forwards Application for Amend 119 to License DRP-13, Consisting of Proposed Change 134.Change Revises Section 3, Contents & Conditions to Include New Condition 3.J, Integrated Living Schedule of Backfits. Fee Encl Project stage: Request ML13324A7031985-08-29029 August 1985 Forwards Revised Integrated Living Schedule & Revised Proposed License Condition & Plan to Support Issuance of License Condition 3.J, Integrated Living Schedule of Backfits Project stage: Other ML13324A8261986-03-26026 March 1986 Provides Written Notification of Changes to Integrated Living Schedule Section V.B & Justification for Deferral of Implementation to Cycle 10.Waste Gas Decay Tank Instrumentation Being Upgraded Project stage: Other ML13330B1231986-10-14014 October 1986 Forwards Third Edition of Integrated Living Schedule,Per 840523 Application for Amend to License DPR-13.Encl Includes Summary of Progress Since Last Submittal.Next Refueling/ Backfit Outage Scheduled for First Quarter 1988 Project stage: Request ML13330B1781987-03-23023 March 1987 Forwards Fourth Edition of Integrated Living Schedule,Per Project stage: Other ML13316A9661987-04-20020 April 1987 Forwards Amend 98 to License DPR-13 & Safety Evaluation. Amend Implements License Condition Establishing Integrated Implementation Schedule Program Plan.Evaluation of Plan & Plan Encl Project stage: Approval ML13316A9701987-04-20020 April 1987 Safety Evaluation Supporting Amend 98 to License DPR-13 Project stage: Approval ML13316A9691987-04-20020 April 1987 Amend 98 to License DPR-13,implementing License Condition Which Establishes Integrated Implementation Schedule Program Plan.Plan Requires Util to Follow Plan & Terms for Establishing & Revising Schedules for Specific Plant Mods Project stage: Other 1983-06-16
[Table View] |
Text
I STRIBUTION RC POR Local PDR October 20, 1983 ORB #5 Reading DCrutch.field WPaulson OELD EdOedan Docket No. 50-206 ATaylor ACRD (10)0 NRC Participants NSIC LICENSEE:
Southern California Edison Company FACILITY:
San Onofre Generating Station, Unit No. 1 SUbJECT:
SUMMiARY OF OCTOBER 5, 1983 NEETING On October 5, 1983, members of the NRC staff met with representatives of Southern California Edison Company (SCE) and their contractor, Westinghouse Electric Corporation.
The purpose of the neeting was to discuss the methodology being used to prioritize backfit projects for San Onofre Unit No. 1. is a list of attendees.
SCE is developing an "Integrated Living Schedule" to be used in scheduling all capital backfit projects. The licensee's representatives and their contractors discussed the details of the methodology and provided results and sensitivity studies for a subset of about 10 backfit items. Copies of the non-proprietary viewgraphs used by the licensee are provided in enclosure 2.
The NRC staff indicated that it would like to review the total list of m11odi fications that SCE is prioritizing.
The NRC staff also indicated that the Duane Arnold approach for formalizing schedules is the approach that the staff would like to take.
Original signed by Walter A. Paulson, Project Manager Operating Reactors Branch #5 Division of Licensing
Enclosures:
- 1.
List of attendees
- 2.
Viewyraphs cc w/enclosures:
See next page 8310250254 831020 PDR ADOCK 05000206 P
PDR
)L 5
D OFFCEk.L.....
SURNAME L4 Pa son j P C t ff
.1d DATEb
NRC FORM 318 (10-80) NRCM 0240 OFFICIAL RECORD COPY USGPO: 1981-335-960
Mr. R. Dietch cc Charles R. Kocher, Assistant General Counsel James Beoletto, Esquire Southern California Edison Company Post Office Box 800 Rosemead, California 91770 David R. Pigott Orrick, Herrington & Sutcliffe 600 Montgomery Street San Francisco, California 94111 Harry B. Stoehr San Diego Gas & Electric Company P. 0. Box 1831 San Diego, California 92112 Resident Inspector/San Onofre NPS c/o U. S. NRC P. 0. Box 4329 San Clemente, California 92672 Mayor City of San Clemente San Clemente, California 92672 Chairman Board of Supervisors County of San Diego San Diego, California 92101 California Department of Health ATTN: Joseph 0. Ward, Chief Radiation Control Unit Radiological Health Section 714 P Street, Room 498 Sacramento, California 95814 U. S. Environmental Protection Agency Region IX Office ATTN:
Regional Radiation Representative 215 Freemont Street San Francisco, California 94111 John B. Martin, Regional Administrator Nuclear Regulatory Commission, Region V 1450 Maria Lane Walnut Creek, California 94596
ATTENDANCE LIST OCTOBER 5, 1983 MEETING NRC STAFF, SOUTHERN CALIFORNIA EDISON, WESTINGHOUSE NAME AFFILIATION C. Grimes NRC H. Vander-Molen NRC J. Hannon 1NRC E. McKenna NRC S. Miner NRC W. Paulson NRC T. Philips.
SCE J. Rainsberry SCE G. Hammond SCE D. Dominicis Westinghouse R. Steitter Westinghouse C. Hirst Westinghouse ENCLOSURE I
0 THE BACKFIT LOG AT SAN ONOFRE UNIT 1 MUST BE IMPLEMENTED IN A STABLE, CONTROLLABLE MANNER.
IMPLEMENTATION OF AN INTEGRATED LIVING SCHEDULE WILL ASSURE THAT MODIFICATIONS ARE IMPLEMENTED IN ORDER OF POTENTIAL FOR ENHANCEMENT OF SAFE PLANT OPERATION O
LLL CAPITAL PROJECTS TO BE INCLUDED.
AMOUNT OF BACKFIT BASED ON CONSTRAINTS OF 18 MONTH CYCLE, 3 MONTH OUTAGE.
NEW PROJECTS WILL BE INCORPORATED AS THEY ARISE.
ENCLOSURE 2
PROCESS 0
IDENTIFY PROJECTS ALL PROJECTS OF REGULATORY ORIGIN --
NRR AND I&E.
ALL CAPITAL PROJECTS OF BETTERMENT ORIGIN.
PROCESS 0
RANKED LIST SCHEDULED USING STANDARD TECHNIQUES 0
SCHEDULES CODIFIED WITH NRC 0
NEW PROJECTS SUBJECT TO INTEGRATION
CONCLUSIONS INTEGRATED LIVING3 SCHEDULE FOR SAN ONoFRE UNIT 1:
PROVIDES STABILITY AND PREDICTABILITY c
PROVIDES FOR IMPLEMENTATION OF PROJECTS BASED ON ENHANCEElT OF SAFE PLART OPERATION PROVIDES METHOD OF SCHEDULING IMPLEfENTATION DATES o ASSISTS IN CONTROLLING CAPITAL EXPENDITURES