Letter Sequence Response to RAI |
|---|
|
Initiation
- Request, Request, Request, Request, Request, Request, Request, Request, Request, Request, Request, Request, Request, Request, Request, Request, Request, Request, Request
- Acceptance...
- Supplement, Supplement, Supplement, Supplement, Supplement, Supplement, Supplement, Supplement, Supplement, Supplement, Supplement, Supplement, Supplement, Supplement, Supplement, Supplement, Supplement, Supplement, Supplement, Supplement, Supplement, Supplement
Results
Other: ML110620203, ML11140A163, ML11172A096, ML11224A265, ML11230A003, ML11305A075, ML11318A121, ML11318A122, ML11318A123, ML11318A124, ML11318A125, ML11318A126, ML11318A127, ML11318A128, ML11318A129, ML11318A130, ML11318A131, ML11318A132, ML11318A133, ML11318A135, ML11318A136, ML11318A138, ML11318A139, ML11318A140, ML11318A141, ML11318A142, ML11318A143, ML11318A144, ML11318A145, ML11318A146, ML11318A147, ML11318A148, ML11318A149, ML11318A150, ML11318A151, ML11318A152, ML11318A153, ML11318A154, ML11318A155, ML11318A156, ML11318A157, ML11318A158, ML11318A159, ML11318A160, ML11318A161, ML11318A162, ML11318A163, ML11318A164, ML11318A165, ML11318A166... further results
|
MONTHYEARML1106202032011-03-17017 March 2011 License Renewal Application Online Reference Portal Project stage: Other ML1108309782011-04-14014 April 2011 Request for Additional Information for the Review of the South Texas Project, License Renewal Application, Fire Protection and Component Integrity (TAC Nos. ME4536 ME4637 Project stage: RAI ML1108907642011-04-14014 April 2011 Request for Additional Information for the Review of the South Texas Project, License Renewal Application-Electrical Branch Scoping Project stage: RAI ML1108205792011-04-14014 April 2011 Request for Additional Information for the Review of the South Texas Project, License Renewal Application -Section 2.4 Structural Project stage: RAI ML1112501472011-05-0505 May 2011 Notice of Withdrawal of Megan Wright in the Matter of South Texas Project, Units 1 and 2 Project stage: Request ML11130A0262011-05-0505 May 2011 Response to Request for Additional Information for License Renewal Application Project stage: Response to RAI ML11145A0902011-05-12012 May 2011 Response to Request for Additional Information for Licence Renewal Application Project stage: Response to RAI ML11137A0922011-05-24024 May 2011 Request for Additional Information for the Review of the South Texas Project, Units 1 and 2, License Renewal Application Future Consideration of Operating Experience Project stage: RAI ML11140A1632011-06-0606 June 2011 Plan for the Aging Management Program Regulatory Audit Regarding the South Texas Project, Units 1 and 2 License Renewal Application Review Project stage: Other ML11172A0962011-06-16016 June 2011 Amendment 2 to the License Renewal Application Project stage: Other NOC-AE-11002681, Amendment 2 to the License Renewal Application2011-06-16016 June 2011 Amendment 2 to the License Renewal Application Project stage: Other ML11181A0372011-06-23023 June 2011 Response to Request for Additional Information for License Renewal Application Project stage: Response to RAI NOC-AE-11002683, Response to Request for Additional Information for License Renewal Application (TAC Nos. ME4936 and ME4937)2011-06-23023 June 2011 Response to Request for Additional Information for License Renewal Application (TAC Nos. ME4936 and ME4937) Project stage: Response to RAI ML11154A0132011-07-0606 July 2011 Summary of Telephone Conference Call Held on May 23, 2011, Between the NRC and STPNOC, Concerning Requests for Additional Information Pertaining to the South Texas Project, LRA-Future Consideration of Operating Experience Project stage: RAI ML11166A2392011-07-12012 July 2011 Letter Request for Additional Information for South Texas Project Electric Generating Station, Units 1 and 2 License Renewal Application - Scoping and Screening Balance of Plant Project stage: RAI ML11201A0552011-07-28028 July 2011 Requests for Additional Information for the Review of the South Texas Project, License Renewal Application - Scoping and Screening Audit Project stage: RAI NOC-AE-11002702, Response to Request for Additional Information for the Review of the South Texas Project License Renewal Application2011-08-0909 August 2011 Response to Request for Additional Information for the Review of the South Texas Project License Renewal Application Project stage: Response to RAI ML11234A0452011-08-0909 August 2011 Response to Request for Additional Information for the South Texas Project License Renewal Application Project stage: Response to RAI ML11245A1012011-08-0909 August 2011 Response to Request for Additional Information for the Review of the South Texas Project License Renewal Application Project stage: Response to RAI ML11214A0052011-08-15015 August 2011 Requests for Additional Information for the Review of the South Texas Project, Units 1 and 2 License Renewal Application - Aging Management Programs Audit, Structures/Electrical Project stage: RAI ML11214A0272011-08-15015 August 2011 Requests for Additional Information for the Review of the South Texas Project, Units 1 and 2 License Renewal Application - Aging Management Programs Audit, Reactor Systems Project stage: RAI ML11214A0882011-08-15015 August 2011 Request for Additional Information for the Review of the South Texas Project, Units 1 and 2 License Renewal Application - Aging Management Programs Audit, Plant Systems Project stage: RAI ML11238A0712011-08-18018 August 2011 Response to Request for Additional Information for the South Texas Project License Renewal Application Project stage: Response to RAI ML1123000162011-08-18018 August 2011 License Renewal - Errata in AMP RAI Package Project stage: RAI NOC-AE-11002716, Response to Request for Additional Information for the South Texas Project License Renewal Application (TAC ME4936 and ME4937)2011-08-18018 August 2011 Response to Request for Additional Information for the South Texas Project License Renewal Application (TAC ME4936 and ME4937) Project stage: Response to RAI ML11238A0722011-08-23023 August 2011 Response to Request for Additional Information for the South Texas Project License Renewal Application Project stage: Response to RAI NOC-AE-11002714, Response to Request for Additional Information for the South Texas Project License Renewal Application (TAC ME4936 and ME4937)2011-08-23023 August 2011 Response to Request for Additional Information for the South Texas Project License Renewal Application (TAC ME4936 and ME4937) Project stage: Response to RAI ML11230A0032011-09-0606 September 2011 Scoping and Screening Audit Report Regarding the South Texas Project, Units 1 and 2 Project stage: Other ML11266A0192011-09-15015 September 2011 Response to Request for Additional Information for License Renewal Application Project stage: Response to RAI ML11266A0202011-09-15015 September 2011 Response to Requests for Additional Information for License Renewal Application Project stage: Response to RAI NOC-AE-11002731, Response to Requests for Additional Information for License Renewal Application (TAC Nos. ME4936 and ME4937)2011-09-15015 September 2011 Response to Requests for Additional Information for License Renewal Application (TAC Nos. ME4936 and ME4937) Project stage: Response to RAI NOC-AE-11002730, Response to Request for Additional Information for License Renewal Application (TAC Nos. ME4936 and ME4937)2011-09-15015 September 2011 Response to Request for Additional Information for License Renewal Application (TAC Nos. ME4936 and ME4937) Project stage: Response to RAI ML1124402012011-09-21021 September 2011 Request for Additional Information for the Review of the South Texas Project, Units 1 and 2 License Renewal Application - Aging Management Review, Set 2 Project stage: RAI ML11250A0432011-09-22022 September 2011 Requests for Additional Information for the Review of the South Texas Project, Units 1 and 2 License Renewal Application - Aging Management Review, Set 1 Project stage: RAI ML11224A2652011-09-22022 September 2011 Aging Management Programs Audit Report Regarding the South Texas Project, Units 1 and 2, Station License Renewal Application Project stage: Other ML11258A1612011-09-22022 September 2011 Request for Additional Information for the Review of the South Texas Project, Units 1 and 2 License Renewal Application - Aging Management Review, Set 3 Project stage: RAI ML11272A1652011-10-0404 October 2011 Summary of Telephone Conference Call Held on September 28, 2011, Between the NRC and STP Nuclear Operating Company, Concerning Request for Additional Information Pertaining to the South Texas Project, LRA Project stage: RAI ML11291A1522011-10-10010 October 2011 Response to Requests for Additional Information for the License Renewal Application Project stage: Response to RAI NOC-AE-11002732, Response to Requests for Additional Information for the License Renewal Application2011-10-10010 October 2011 Response to Requests for Additional Information for the License Renewal Application Project stage: Response to RAI ML11291A1202011-10-10010 October 2011 10CFR50.59 Summary Report Project stage: Request ML11273A0172011-10-11011 October 2011 Requests for Additional Information for the Review of the South Texas Project, Units 1 and 2, License Renewal Application - Aging Management Review, Set 5 Project stage: RAI ML11273A0082011-10-11011 October 2011 Requests for Additional Information for the Review of the South Texas Project, Units 1 and 2, License Renewal Application - Aging Management Review, Set 4 Project stage: RAI ML11277A0472011-10-18018 October 2011 Requests for Additional Information for the Review of the South Texas Project, Units 1 and 2, License Renewal Application - Aging Management Program, Set 6 Project stage: RAI NOC-AE-11002737, Supplement to License Renewal Application (TAC Nos. ME4936 and ME4937)2011-10-18018 October 2011 Supplement to License Renewal Application (TAC Nos. ME4936 and ME4937) Project stage: Supplement ML11298A0822011-10-18018 October 2011 Supplement to License Renewal Application Project stage: Supplement ML11305A0762011-10-25025 October 2011 Response to Requests for Additional Information for License Renewal Application Project stage: Response to RAI NOC-AE-11002756, Contact Information Change, License Renewal Application (TAC ME4936 and ME4937)2011-10-26026 October 2011 Contact Information Change, License Renewal Application (TAC ME4936 and ME4937) Project stage: Other ML11305A0752011-10-26026 October 2011 Contact Information Change, License Renewal Application Project stage: Other ML11318A1772011-11-0303 November 2011 Drawing No. LR-STP-WL-7R309F90001 1, Rev. 1, Piping and Instrumentation Diagram Liquid Waste Processing System Project stage: Other ML11318A1722011-11-0303 November 2011 Drawing No. LR-STP-WL-5R309F05022 2, Rev. 1, Piping and Instrumentation Diagram Liquid Waste Processing System Project stage: Other 2011-06-16
[Table View] |
Text
JLM11"m Nuclear Operating Company South Texas Pro/cd Electric GeneratinS Station P0 Box 289 Wdswvorth Texas 77483
-Wv-/---
May 05, 2011 NOC-AE-1 1002670 10CFR54 STI: 32862176 File: G25 U. S. Nuclear Regulatory Commission Attention: Document Control Desk One White Flint North 11555 Rockville Pike Rockville, MD 20852-2746 South Texas Project Units 1 and 2 Docket Nos. STN 50-498, STN 50-499 Response to Request for Additional Information for the South Texas Proiect License Renewal Application
Reference:
- 1. STPNOC Letter dated October 25, 2010, from G. T. Powell to NRC Document Control Desk, "License Renewal Application", (NOC-AE-10002607) (ML103010257)
- 2. NRC letter dated April 14, 2011, "Requests for Additional Information for the Review of the South Texas Project, License Renewal Application -
Electrical Branch Scoping", (ML110890764)
By Reference 1, STP Nuclear Operating Company (STPNOC) submitted the License Renewal Application (LRA) for South Texas Project (STP) Units 1 and 2. By Reference 2, the NRC staff requested additional information for the review of the STP LRA. STPNOC's response to the request for additional information is included in the Enclosure to this letter.
There are no regulatory commitments in this letter.
Should you have any questions regarding this letter, please contact either Arden Aldridge, STP License Renewal Project Lead, at (361) 972-8243 or Ken Taplett, STP License Renewal Project Regulatory point-of-contact, at (361) 972-8416.
I declare under penalty of perjury that the foregoing is true and correct.
Executed on Mooszod
'Date G. T. Powell Vice President, Technical Support & Oversight KJT
Enclosure:
STPNOC Response to Request for Additional Information
cc:
(paper copy without enclosures)
Regional Administrator, Region IV U. S. Nuclear Regulatory Commission 612 East Lamar Blvd, Suite 400 Arlington, Texas 76011-4125 Balwant K. Singal Senior Project Manager U.S. Nuclear Regulatory Commission One White Flint North (MS 8B1) 11555 Rockville Pike Rockville, MD 20852 Senior Resident Inspector U. S. Nuclear Regulatory Commission P. 0. Box 289, Mail Code: MN116 Wadsworth, TX 77483 C. M. Canady City of Austin Electric Utility Department 721 Barton Springs Road Austin, TX 78704 John W. Daily License Renewal Project Manager (Safety)
U.S. Nuclear Regulatory Commission One White Flint North (MS O11-F1) 11555 Rockville Pike Rockville, MD 20852 Tam Tran License Renewal Project Manager (Environmental)
U. S. Nuclear Regulatory Commission One White Flint North (MS 011 F01) 11555 Rockville Pike Rockville, MD 20852 NOC-AE-1 1002670 Page 2 (electronic copy without enclosures)
A. H. Gutterman, Esquire Kathryn M. Sutton, Esquire Morgan, Lewis & Bockius, LLP John Ragan Catherine Callaway Jim von Suskil NRG South Texas LP Ed Alarcon Kevin Polio Richard Pena City Public Service Peter Nemeth Crain Caton & James, P.C.
C. Mele City of Austin Richard A. Ratliff Alice Rogers Texas Department of State Health Services Balwant K. Singal John W. Daily Tam Tran U. S. Nuclear Regulatory Commission
Enclosure NOC-AE-1 102670 Page 1 STPNOC Response to Request for Additional Information RAI 2.5-1, Temperature sensors/transducers subject to aging management review.
Background:
NEI 95-10, "Industry Guideline for Implementing the Requirements of 10 CFR Part 54 - The License Renewal Rule," Appendix B indicates that elements, resistance temperature detectors (RTDs), sensors, thermocouples and transducers should be included in the list of components/commodity groups subject to Aging Management Review if a pressure boundary is applicable.
Issue:
The staff cannot find these components/groups in the applicant's LRA.
Request:
Please justify why these components are not included in Section 2.5 of the License Renewal Application.
STPNOC Response The commodity group associated with elements, Resistance Temperature Detectors (RTDs),
sensors, thermocouples and transducers designated as "thermowell" are found in Sections 2.3.3 and 2.3.4 of the LRA. The following mechanical systems have component type "thermowell" with an intended function of "pressure boundary". These "thermowells" are within the scope of license renewal and are subject to an aging management review.
Spent Fuel Pool Cooling & Cleanup (LRA Table 2.3.3-2)
Essential Cooling Water & ECW Screen Wash (LRA Table 2.3.3-4)
Chilled Water HVAC (LRA Table 2.3.3-9)
Chemical & Volume Control (LRA Table 2.3.3-19)
Standby Diesel Generator (LRA Table 2.3.3-20)
Liquid Waste Processing (LRA Table 2.3.3-22)
Main Steam (LRA Table 2.3.4-1)
Auxiliary Feedwater (LRA Table 2.3.4-6)
RAI 2.5-2, Control circuits and structures associated with Station Blackout (SBO) recovery.
Background:
In accordance with 10 CFR 54.4(a)(3) and SRP-LR section 2.5.2.1.1, the control circuits and structures associated with the switchyard circuit breakers used to supply the SBO recovery paths should be within the scope of license renewal.
Issue:
The applicant has not included these components/groups within the scope of license renewal.
Request:
Please confirm whether these components are within the scope of license renewal. If not within scope, then justify why they are not included.
STPNOC Response Switchyard circuit breakers within the scope of license renewal remain in position when offsite power is interrupted. Each of the breakers contains stored energy such that the breakers may be operated without use of control circuits during a loss of offsite power event. Therefore control circuits are not required for station blackout recovery and are not within the scope of license renewal.
Enclosure NOC-AE-1 102670 Page 2 The structures associated with the switchyard station blackout recovery path are within the scope of license renewal. See LRA Section 2.4.7 "Electrical Foundations and Structures".