MONTHYEARML24032A0202024-01-31031 January 2024 NPDES Biocide/Corrosion Treatment Plan Annual Report, Cy 2023 ML23319A2452024-01-29029 January 2024 Issuance of Amendment Nos. 366 and 360; 164 and 71 Regarding the Adoption of TSTF-567, Revision 1, Add Containment Sump TS to Address GSI-191 Issues CNL-24-017, Tennessee Valley Authority - Central Emergency Control Center Emergency Plan Implementing Procedure and Emergency Preparedness Department Procedure Revisions2024-01-17017 January 2024 Tennessee Valley Authority - Central Emergency Control Center Emergency Plan Implementing Procedure and Emergency Preparedness Department Procedure Revisions ML24018A0142024-01-17017 January 2024 Engine Systems, Inc., Report No. 10CFR21-0137, Rev. 1, 56913-EN 56913 ML24011A3182024-01-11011 January 2024 Submittal of Discharge Monitoring Report (Dmr), October 2023 ML24011A3172024-01-11011 January 2024 Submittal of Discharge Monitoring Report (Dmr), September 2023 ML24011A3202024-01-11011 January 2024 Submittal of Discharge Monitoring Report (Dmr), December 2023 ML24011A3162024-01-11011 January 2024 Submittal of Discharge Monitoring Report (Dmr), August 2023 ML24011A3192024-01-11011 January 2024 Submittal of Discharge Monitoring Report (Dmr), November 2023 IR 05000327/20234422024-01-11011 January 2024 95001 Supplemental Inspection Report 05000327/2023442 and 05000328/2023442 and Follow-Up Assessment Letter ML24010A2132024-01-10010 January 2024 CFR 21.21 Final Report Regarding Siemens Medium Voltage Circuit Breakers ML24018A0952024-01-0404 January 2024 Engine Systems, Inc., 10CFR21 Reporting of Defects and Non-Compliance Report No. 10CFR21-0137, Rev. 0 ML24004A0332024-01-0303 January 2024 Interim Report of a Deviation or Failure to Comply Crompton Instruments Type 077 Ammeter ML24004A0402024-01-0303 January 2024 Response to NRCs November 8, 2023, Request for Additional Information - Related to Independent Spent Fuel Storage Installation CNL-23-068, Request for Exemption from Enhanced Weapons, Firearms Background Checks, and Security Event Notifications Implementation2023-12-21021 December 2023 Request for Exemption from Enhanced Weapons, Firearms Background Checks, and Security Event Notifications Implementation CNL-23-036, Application to Revise Function 5 of Technical Specification Table 3.3.2-1, Engineered Safety Feature Actuation System Instrumentation, for the Sequoyah Nuclear Plant and Watts Bar Nuclear Plant (SQN-TS-23-02 and WBN-TS-23-08)2023-12-18018 December 2023 Application to Revise Function 5 of Technical Specification Table 3.3.2-1, Engineered Safety Feature Actuation System Instrumentation, for the Sequoyah Nuclear Plant and Watts Bar Nuclear Plant (SQN-TS-23-02 and WBN-TS-23-08) ML23346A1222023-12-12012 December 2023 Annual Non-Radiological Environmental Operating Report - 2023 IR 05000327/20234202023-11-28028 November 2023 Security Baseline Inspection Report 05000327/2023420 and 05000328/2023420 CNL-23-067, Central Emergency Control Center Emergency Plan Implementing Procedure Revisions2023-11-27027 November 2023 Central Emergency Control Center Emergency Plan Implementing Procedure Revisions ML23324A4362023-11-0909 November 2023 Exam Corporate Notification Letter Aka 210-day Letter ML23307A0822023-11-0808 November 2023 Request for Additional Information August 4, 2022, Exemption Request for Deviating from the Conditions of Certificate of Compliance No. 1032, Amendment No. 3, Related to Sequoyah Nuclear Plant Independent Spent Fuel Storage Installation IR 05000327/20230032023-11-0303 November 2023 Integrated Inspection Report 05000327/2023003 and 05000328/2023003 ML23306A1592023-11-0202 November 2023 Enforcement Action EA-22-129 Inspection Readiness Notification ML23292A0792023-10-19019 October 2023 Tennessee Valley Authority - Emergency Plan Implementing Procedure Revision, Includes EPIP-5, Revision 58, General Emergency IR 05000327/20230112023-10-16016 October 2023 Triennial Fire Protection Inspection Report 05000327/2023011 and 05000328/2023011 ML23285A0882023-10-12012 October 2023 Submittal of Sequoyah Nuclear Plant, Units 1 and 2, Submittal of Updated Final Safety Analysis Report Amendment 31 ML23284A4252023-10-11011 October 2023 10 CFR 50.59 and 10 CFR 72.48 Changes, Tests, and Experiments Summary Report; Commitment Summary Report; and Update to the Fire Protection Report ML23283A2792023-10-10010 October 2023 Revisions to the Sequoyah Nuclear Plant Units 1 and 2 Technical Requirements Manual ML23279A0612023-10-0505 October 2023 Paragon Energy Solutions LLC, Part 21 Final Report Re Potential Defect with Eaton Jd and Hjd Series Molded Case Circuit Breakers (Mccbs) ML23277A0462023-10-0404 October 2023 Revisions to the Sequoyah Nuclear Plant Units 1 and 2 Technical Specification Bases ML23275A0272023-09-29029 September 2023 Submittal of Discharge Monitoring Report (DMR) Quality Assurance Study 43 Final Report 2023 ML23271A1662023-09-28028 September 2023 Registration of Spent Fuel Storage Cask Pursuant to 10 CFR 72.212(b)(2) CNL-23-059, Supplement to Sequoyah Nuclear Plant, Units 1 and 2, and Watts Bar Nuclear Plant, Units 1 and 2, Application to Revise Technical Specifications to Adopt TSTF-567-A, Revision 1, Add Containment Sump TS to Address GSI-191 Issues (SQN-TS-23-2023-09-20020 September 2023 Supplement to Sequoyah Nuclear Plant, Units 1 and 2, and Watts Bar Nuclear Plant, Units 1 and 2, Application to Revise Technical Specifications to Adopt TSTF-567-A, Revision 1, Add Containment Sump TS to Address GSI-191 Issues (SQN-TS-23-03 CNL-23-061, Tennessee Valley Authority - Central Emergency Control Center Emergency Plan Implementing Procedure Revision2023-09-20020 September 2023 Tennessee Valley Authority - Central Emergency Control Center Emergency Plan Implementing Procedure Revision IR 05000327/20234032023-09-14014 September 2023 Cyber Security Inspection Report 05000327/2023403 and 05000328/2023403 (Cover Letter) ML23257A0062023-09-14014 September 2023 Enforcement Action EA-22-129 Inspection Postponement Request ML23254A2192023-09-11011 September 2023 Emergency Plan Implementing Procedure Revisions ML23254A0652023-09-0707 September 2023 Registration of Spent Fuel Storage Cask Pursuant to 10 CFR 72.212(b)(2) CNL-23-057, Central Emergency Control Center Emergency Plan Implementing Procedure Revisions. Includes CECC-EPIP-1, Revision 76 and CECC-EPIP-9, Revision 642023-09-0505 September 2023 Central Emergency Control Center Emergency Plan Implementing Procedure Revisions. Includes CECC-EPIP-1, Revision 76 and CECC-EPIP-9, Revision 64 IR 05000327/20230052023-08-29029 August 2023 Updated Inspection Plan for Sequoyah Nuclear Plant, Units 1 and 2 - Report 05000327/2023005 and 05000328/2023005 ML23233A0122023-08-17017 August 2023 Unit 1 Cycle 25 Refueling Outage - 90-Day Inservice Inspection Summary Report - Supplement ML23233A0142023-08-15015 August 2023 Discharge Monitoring Report (Dmr), July 2023 ML23215A1212023-08-0303 August 2023 301 Exam Administrative Items (2B) Normal Release ML23215A1572023-08-0303 August 2023 Enforcement Action EA-22-129 Inspection Readiness Notification CNL-23-028, Application to Revise Technical Specifications to Adopt TSTF-567-A, Revision 1, Add Containment Sump TS to Address GSI-191 Issues (SQN-TS-23-03 and WBN-TS-23-06)2023-08-0202 August 2023 Application to Revise Technical Specifications to Adopt TSTF-567-A, Revision 1, Add Containment Sump TS to Address GSI-191 Issues (SQN-TS-23-03 and WBN-TS-23-06) ML23192A4472023-07-31031 July 2023 Staff Assessment of Updated Seismic Hazards at TVA Sites Following the NRC Process for the Ongoing Assessment of Natural Hazards Information 2024-01-04
[Table view] |
Text
UNITED STATES NUCLEAR REGULATORY COMMISSION WASHINGTON, D.C. 20555-0001 JUly 27, 2010 Mr. Rodney M. Krich Vice President, Nuclear Licensing Tennessee Valley Authority 3R Lookout Place 1101 Market Street Chattanooga, TN 37402-2801
SUBJECT:
SEOUOYAH NUCLEAR PLANT, UNITS 1 AND 2 - EMERGENCY DIESEL GENERATOR FUEL OIL - ALTERNATE SAMPLING PROCEDURE OF STORAGE TANKS (TAC NOS. ME3439 AND ME3440)
Dear Mr. Krich:
By letter dated February 24, 2010, as supplemented by letter dated May 13, 2010, Tennessee Valley Authority (TVA or the licensee) submitted a request to use an alternative sampling procedure for the emergency diesel generator (EDG) fuel oil storage tanks for Sequoyah Nuclear Plant (SON), Units 1 and 2.
The requirement to sample the diesel fuel oil storage tanks comes from Technical Specification (TS) Surveillance Requirement 4.8.1.1.2.c, which states that, "At a frequency in accordance with the Diesel Fuel Oil Testing Program, verify fuel oil properties of new and stored fuel oil are tested in accordance with, and maintained within the limits specified in the Diesel Fuel Oil Testing Program." TS Section 6.16, "Diesel Fuel Oil Testing Program," requires that sampling and testing of new and stored fuel be performed in accordance with applicable American Society for Testing Materials (ASTM) standards. Historically, TVA has performed a manual "all-levels" sample in accordance with Section 8 of ASTM D4057-1988, "Standard Practice for Manual Sampling of Petroleum and Petroleum Products." However, Section 8.1 of ASTM D4057-1988 specifies that alternate sampling methods may be used with agreement of the parties involved.
TVA determined that U. S. Nuclear Regulatory Commission (NRC) staff approval of the alternative sampling methods was necessary to satisfy the criteria of ASTM D4057-1988; there is no change to the TSs or its bases.
The "all-levels" sample from ASTM D4057-1988 draws a sample that is representative of the entire tank, by opening an empty specialized container near the bottom of the fuel oil storage tanks and drawing the container upward to the top of the tank as it fills. Instead of this process, TVA proposed to take samples from the fuel oil transfer pump discharge lines of each fuel oil storage tank. The transfer pumps take suction near the bottom of their respective tanks through a 4-inch diameter line. There is a 1-inch diameter line and valve off each discharge line that will be used as the sample point. To obtain a fuel oil sample, TVA proposed that the fuel oil transfer pump for the tank to be sampled will be placed in the recirculation mode for a period of time necessary to ensure a one-volume recirculation of the contents, based on the volume of diesel fuel in the tank. After the tank has been recirculated for the appropriate time, TVA proposed that the sample line will be flushed and a sample obtained. The fuel oil sample will be analyzed in accordance with existing TS requirements.
R. Krich -2 To show that the new sampling procedure would provide results that were representative of the fuel oil contained in the tanks and equivalent to the existing procedure, the licensee collected samples using the existing "all-levels" method, and the new proposed method, from Fuel Oil Storage Tanks 1 and 2 for a period of 3 months. The sampies were then tested with the same procedures and the results were provided in the enclosure of TVA letter dated February 24, 2010. The NRC staff reviewed the proposed sampling process and the test results comparison provided in the enclosure of TVA letter dated February 24, 2010. Based on the comparison of the sampling methods and test results, the NRC staff finds that the proposed sampling method provides an equivalent sample of the fuel oil storage tank contents as the "all-levels" sampling method in ASTM 04057-1988.
Based on the NRC staff review of the TVA request, the NRC staff finds the alternative sampling technique for SON, Units 1 and 2 EDG fuel oil storage tanks acceptable. Pursuant to ASTM 04057-1988, Section 8.1, TVA is authorized to obtain samples from the fuel oil transfer pump discharge lines of each EDG storage tank by the described process in lieu of specific methods described in applicable ASTM standards.
If you have any questions regarding this matter, please contact Siva P. Lingam at 301-415-1564.
~k1/~r~
Douglas A. Broaddus. Chief Plant Licensing Branch 11-2 Division of Operating Reactor Licensing Office of Nuclear Reactor Regulation Docket No. 50-327 and 50-328 cc: Distribution via Listserv
R. Krich -2 To show that the new sampling procedure would provide results that were representative of the fuel oil contained in the tanks and equivalent to the existing procedure, the licensee collected samples using the existing "all-levels" method, and the new proposed method, from Fuel Oil Storage Tanks 1 and 2 for a period of 3 months. The samples were then tested with the same procedures and the results were provided in the enclosure of TVA letter dated February 24, 2010. The NRC staff reviewed the proposed sampling process and the test results comparison provided in the enclosure of TVA letter dated February 24, 2010. Based on the comparison of the sampling methods and test results, the NRC staff finds that the proposed sampling method provides an equivalent sample of the fuel oil storage tank contents as the "all-levels" sampling method in ASTM D4057-1988.
Based on the NRC staff review of the TVA request, the NRC staff finds the alternative sampling technique for SON, Units 1 and 2 EDG fuel oil storage tanks acceptable. Pursuant to ASTM D4057-1988, Section 8.1, TVA is authorized to obtain samples from the fuel oil transfer pump discharge lines of each EDG storage tank by the described process in lieu of specific methods described in applicable ASTM standards.
If you have any questions regarding this matter, please contact Siva P. Lingam at 301-415-1564.
Sincerely, IRA BMozafari forI Douglas A. Broaddus, Chief Plant Licensing Branch 11-2 Division of Operating Reactor Licensing Office of Nuclear Reactor Regulation Docket No. 50-327 and 50-328 cc: Distribution via Listserv DISTRIBUTION:
PUBLIC LPL2-2 RlF RidsNrrDorlLpl2-2 RidsNrrPMSequoyah RidsNrrLACSola RidsOgcMailCenter RidsNrrDorlDpr RidsAcrsAcnw_MailCTR RidsNrrDciCsgb RidsRgn2MailCenter A. Johnson, NRR RidsN rrLABClayton ADAMS Accession N0: ML101680207 . db)y memo dae
- transmltte t d OFFICE LPL2-2/PM LPL2-2/LA NRRlDCI/CSGB/BC LPL2-2/BC NAME SLingam CSoia by RTaylor DBroaddus by (BClayton) (BMozafari)
DATE 7/26/10 7/27/10 06/16/10* 7/27/10 OFFICIAL RECORD COpy