Category:License-Monthly Operating Report
MONTHYEARRNP-RA/05-0035, March 2005 Monthly Operating Reports for H. B. Robinson Steam Electric Plant (Hbrsep), Unit No. 22005-04-11011 April 2005 March 2005 Monthly Operating Reports for H. B. Robinson Steam Electric Plant (Hbrsep), Unit No. 2 RNP-RA/05-0025, February 2005 Monthly Operating Report for H. B. Robinson Steam Electric Plant, Unit No. 22005-03-10010 March 2005 February 2005 Monthly Operating Report for H. B. Robinson Steam Electric Plant, Unit No. 2 RNP-RA/05-0002, December 2004 Monthly Operating Report for H. B. Robinson Steam Electric Plant, Unit No. 22005-01-0707 January 2005 December 2004 Monthly Operating Report for H. B. Robinson Steam Electric Plant, Unit No. 2 RNP-RA/04-0149, November 2004 Monthly Operating Report for the H. B. Robinson, Unit 22004-12-0707 December 2004 November 2004 Monthly Operating Report for the H. B. Robinson, Unit 2 RNP-RA/04-0132, September 2004 Monthly Operating Report for H.B. Robinson, Unit 22004-10-11011 October 2004 September 2004 Monthly Operating Report for H.B. Robinson, Unit 2 RNP-RA/04-0117, August 2004 Monthly Operating Report for H B Robinson Steam Electric Plant Unit 22004-09-0303 September 2004 August 2004 Monthly Operating Report for H B Robinson Steam Electric Plant Unit 2 RNP-RA/04-0103, July 2004 Monthly Operating Report for H. B. Robinson Steam Electric Plant, Unit 22004-08-0404 August 2004 July 2004 Monthly Operating Report for H. B. Robinson Steam Electric Plant, Unit 2 RNP-RA/04-0087, June 2004 Monthly Operating Report for H. B. Robinson, Unit 22004-07-0808 July 2004 June 2004 Monthly Operating Report for H. B. Robinson, Unit 2 RNP-RA/04-0052, April 2004 Monthly Operating Report for H. B. Robinson Steam Electric Plant, Unit No. 22004-05-11011 May 2004 April 2004 Monthly Operating Report for H. B. Robinson Steam Electric Plant, Unit No. 2 RNP-RA/04-0041, March 2004 Monthly Operating Report for H.B. Robinson, Unit 22004-04-0505 April 2004 March 2004 Monthly Operating Report for H.B. Robinson, Unit 2 RNP-RA/04-0030, February 2004 Monthly Operating Report for H.B. Robinson, Unit 22004-03-0505 March 2004 February 2004 Monthly Operating Report for H.B. Robinson, Unit 2 RNP-RA/04-0020, January 2004 Monthly Operating Report for H.B. Robinson, Unit 22004-02-0505 February 2004 January 2004 Monthly Operating Report for H.B. Robinson, Unit 2 RNP-RA/04-0004, December 2003 Monthly Operating Report for H.B. Robinson, Unit 22004-01-0606 January 2004 December 2003 Monthly Operating Report for H.B. Robinson, Unit 2 RNP-RA/03-0155, November 2003 Monthly Operating Report for H.B. Robinson, Unit 22003-12-0909 December 2003 November 2003 Monthly Operating Report for H.B. Robinson, Unit 2 RNP-RA/03-0140, October 2003 Monthly Operating Report for H B Robinson Steam Electric Plant Unit 22003-11-0606 November 2003 October 2003 Monthly Operating Report for H B Robinson Steam Electric Plant Unit 2 RNP-RA/03-0132, September 2003 Monthly Operating Report for H. B. Robinson, Unit 22003-10-10010 October 2003 September 2003 Monthly Operating Report for H. B. Robinson, Unit 2 RNP-RA/03-0115, August 2003 Monthly Operating Report for H. B. Robinson, Unit 22003-09-0909 September 2003 August 2003 Monthly Operating Report for H. B. Robinson, Unit 2 RNP-RA/03-0105, July 2003 Monthly Operating Report for H.B. Robinson, Unit 22003-08-12012 August 2003 July 2003 Monthly Operating Report for H.B. Robinson, Unit 2 RNP-RA/03-0085, June 2003 Monthly Operating Report for H. B. Robinson, Unit 22003-07-10010 July 2003 June 2003 Monthly Operating Report for H. B. Robinson, Unit 2 RNP-RA/03-0079, May 2003 Monthly Operating Report for H.B. Robinson, Unit 22003-06-10010 June 2003 May 2003 Monthly Operating Report for H.B. Robinson, Unit 2 RNP-RA/03-0062, April 2003 Monthly Operating Report for H.B. Robinson Steam Electric Plant, Unit No.22003-05-0606 May 2003 April 2003 Monthly Operating Report for H.B. Robinson Steam Electric Plant, Unit No.2 RNP-RA/03-0042, March 2003 Monthly Operating Report for H.B. Robinson Steam Electric Plant, Unit No. 22003-04-0404 April 2003 March 2003 Monthly Operating Report for H.B. Robinson Steam Electric Plant, Unit No. 2 RNP-RA/03-0033, February 2003 Monthly Operating Report for H.B. Robinson Steam Electric Plant, Unit 22003-03-0707 March 2003 February 2003 Monthly Operating Report for H.B. Robinson Steam Electric Plant, Unit 2 RNP-RA/03-0021, January 2003 Monthly Operating Report for H.B. Robinson Steam Electric Plant, Unit No. 22003-02-10010 February 2003 January 2003 Monthly Operating Report for H.B. Robinson Steam Electric Plant, Unit No. 2 RNP-RA/03-0004, December 2002 Monthly Operating Report for H.B. Robinson Steam Electric Plant, Unit 22003-01-10010 January 2003 December 2002 Monthly Operating Report for H.B. Robinson Steam Electric Plant, Unit 2 RNP-RA/02-0185, November 2002 Monthly Operating Report for H. B. Robinson, Unit 22002-12-13013 December 2002 November 2002 Monthly Operating Report for H. B. Robinson, Unit 2 RNP-RA/02-0174, October 2002 Monthly Operating Report for H B Robinson Unit 22002-11-14014 November 2002 October 2002 Monthly Operating Report for H B Robinson Unit 2 RNP-RA/02-0153, September 2002 Monthly Operating Report for Robinson Unit 22002-10-0707 October 2002 September 2002 Monthly Operating Report for Robinson Unit 2 RNP-RA/02-0142, August 2002 Monthly Operating Report for H. B. Robinson Unit 22002-09-12012 September 2002 August 2002 Monthly Operating Report for H. B. Robinson Unit 2 RNP-RA/02-0119, July 2002 Monthly Operating Report for H. B. Robinson Unit 22002-08-13013 August 2002 July 2002 Monthly Operating Report for H. B. Robinson Unit 2 RNP-RA/02-0102, June 2002 Monthly Operating Report for H.B. Robinson Steam Electric Co., Unit 22002-07-10010 July 2002 June 2002 Monthly Operating Report for H.B. Robinson Steam Electric Co., Unit 2 RNP-RA/02-0088, May 2002 Monthly Operating Report for H.B. Robinson Steam Electric Plant, Unit 22002-06-0505 June 2002 May 2002 Monthly Operating Report for H.B. Robinson Steam Electric Plant, Unit 2 RNP-RA/02-0075, April 2002 Monthly Operating Report for H. B. Robinson Unit 22002-05-14014 May 2002 April 2002 Monthly Operating Report for H. B. Robinson Unit 2 RNP-RA/02-0050, March 2002 Monthly Operating Report for H.B. Robinson Steam Electric Plant, Unit 22002-04-11011 April 2002 March 2002 Monthly Operating Report for H.B. Robinson Steam Electric Plant, Unit 2 RNP-RA/02-0035, February 2002 Monthly Operating Report for H.B. Robinson Steam Electric Plant, Unit 22002-03-11011 March 2002 February 2002 Monthly Operating Report for H.B. Robinson Steam Electric Plant, Unit 2 RNP-RA/02-0019, January 2002 Monthly Operating Report for H. B. Robinson Steam Electric Plant, Unit 22002-02-12012 February 2002 January 2002 Monthly Operating Report for H. B. Robinson Steam Electric Plant, Unit 2 RNP-RA/02-0001, December 2001 Monthly Operating Report for H. B. Robinson, Unit 22002-01-0707 January 2002 December 2001 Monthly Operating Report for H. B. Robinson, Unit 2 2005-04-11
[Table view] |
Text
TS 5.6.4 by ProgressEnergy TRM 6.2 Serial: RNP-RA/03-0079 JUN 10 2003 United States Nuclear Regulatory Commission Attn: Document Control Desk Washington, DC 20555 H. B. ROBINSON STEAM ELECTRIC PLANT, UNIT NO. 2 DOCKET NO. 50-261/LICENSE NO. DPR-23 MONTHLY OPERATING REPORT Ladies and Gentlemen:
In accordance with the H. B. Robinson Steam Electric Plant (HBRSEP), Unit No. 2, Technical Specifications Section 5.6.4, Monthly Operating Reports, and HBRSEP, Unit No. 2, Technical Requirements Manual Selction 6.2, Monthly Operating Report, Progress Energy Carolinas, Inc., also known as Carolina Power & Light Company, submits the attached report of operating statistics and shutdown experience for the month of May 2003.
If you have any questions concerning this matter, please contact me.
Sincerely, C. T. Baucom Supervisor - Licensing/Regulatory Programs CTB/jwv Attachment c: NRC Resident Inspector, HBRSEP L. A. Reyes, NRC, Region II C. P. Patel, NRC, NRR Progress Energy Carolinas, Inc.
Roblnson Nuclear Plant 3581 West Entrance Road HartswIle SC 29550
Attachment to Serial: RNP-RA/03-0079 Page 1 of 2 MONTHLY OPERATING REPORT DOCKET NO. 050-0261 UNIT H. B. ROBINSON STEAM ELECTRIC PLANT (HBRSEP), UNIT NO. 2 DATE 6/2/03 COMPLETED BY TIM SURMA TELEPHONE (843) 857-1086 REPORTING PERIOD: MAY 2003
- 1. DESIGN ELECTRICAL RATING (NET MWE): 765
- 2. MAX DEPENDABLE CAPACITY (NET MWE): 710 THIS YR TO MONTH DATE CUMULATIVE
- 3. NUMBER OF HOURS REACTOR CRITICAL 744.00 3623.0 215420.99
- 4. HOURS GENERATOR ON LINE 744.00 3623.0 212101.26
- 5. UNIT RESERVE SHUTDOWN HOURS 0.00 0.00 23.20
- 6. NET ELEC. ENERGY GENERATED (MWH) 541560.00 2691709.00 138629167.00
Attachment to Serial: RNP-RA/03-0079 Page 2 of 2 DOCKET NO. 050-0261 UNIT NAME HBRSEP, UNIT NO. 2 DATE 6/2/03 COMPLETED BY TIM SURMA TELEPHONE (843) 857-1086 REPORTING PERIOD: MAY 2003 No. Date Type Duration Reason1 Method of Shutting Down Cause / Corrective Actions / Comments F: Forced (Hours) the Reactor or Reducing Power 2 S: Scheduled 1 2 Reason: Method:
A-Equipment Failure (Explain) 1-Manual B-Maintenance or Test 2-Manual Scram C-Refueling 3-Automatic Scram D-Regulatory Restriction 4-Continuation E-Operator Training & License Examination 5-Other (Explain)
F-Administrative G-Operational Error (Explain)
H-Other (Explain)
SUMMARY
- The unit operated at approximately full power for the entire month. Power was reduced for approximately ten (10) hours to perform turbine valve testing.
There were no challenges to the pressurizer safety valves during the month.