IR 05000424/2012002
| ML12121A498 | |
| Person / Time | |
|---|---|
| Site: | Vogtle (NPF-068, NPF-081) |
| Issue date: | 04/30/2012 |
| From: | Frank Ehrhardt NRC/RGN-II/DRP/RPB2 |
| To: | Tynan T Southern Nuclear Operating Co |
| References | |
| IR-12-002 | |
| Download: ML12121A498 (27) | |
Text
April 30, 2012
SUBJECT:
VOGTLE ELECTRIC GENERATING PLANT - NRC INTEGRATED INSPECTION REPORT 05000424/2012002 AND 05000425/2012002
Dear Mr. Tynan:
On March 31, 2012, the U.S. Nuclear Regulatory Commission (NRC) completed an inspection at your Vogtle Electric Generating Plant, Units 1 and 2. The enclosed integrated inspection report documents the inspection results which were discussed on April 23, with S. Bargeron and other members of your staff.
The inspection(s) examined activities conducted under your license as they relate to safety and compliance with the Commissions rules and regulations and with the conditions of your license.
The inspectors reviewed selected procedures and records, observed activities, and interviewed personnel.
One self-revealing finding of very low safety significance (Green) was identified during this inspection.
This finding was determined to involve a violation of NRC requirements. The NRC is treating this violation as a non-cited violation (NCV) consistent with Section 2.3.2 of the Enforcement Policy.
If you contest this non-cited violation (NCV), you should provide a response within 30 days of the date of this inspection report, with the basis for your denial, to the Nuclear Regulatory Commission, ATTN: Document Control Desk, Washington DC 20555-0001; with copies to the Regional Administrator, Region II; the Director, Office of Enforcement, United States Nuclear Regulatory Commission, Washington, DC 20555-0001; and the NRC Resident Inspector at the Vogtle Electric Generating Plant.
If you disagree with the cross-cutting aspect assigned in this report, you should provide a response within 30 days of the date of this inspection report, with the basis for your disagreement, to the Regional Administrator, Region II; and the NRC Resident Inspector at the Vogtle Electric Generating Plant. The information you provide will be considered in accordance with Inspection Manual Chapter 0305.
In accordance with the 10 CFR 2.390 of the NRCs Rules of Practice, a copy of this letter, its enclosures, and your response (if any) will be available electronically for public inspection in the NRC Public Document Room or from the Publicly Available Records (PARS) component of the NRCs Agencywide Document Access and Management System (ADAMS). ADAMS is accessible from the NRC Web site at http://www.nrc.gov/reading-rm/adams.html (the Public Electronic Reading Room).
Sincerely,
/RA/
Frank Ehrhardt, Chief Reactor Projects Branch 2 Division of Reactor Projects
Docket Nos.: 05000424, 05000425 License Nos.: NPF-68 and NPF-81
Enclosures:
Inspection Report 05000424/2012002 and 05000425/2012002 w/Attachment: Supplemental Information
REGION II==
Docket Nos.:
50-424, 50-425
License Nos.:
Report Nos.:
05000424/2012002 and 05000425/2012002
Licensee:
Southern Nuclear Operating Company, Inc. (SNC)
Facility:
Vogtle Electric Generating Plant, Units 1 and 2
Location:
Waynesboro, GA 30830
Dates:
January 1, 2012 through March 31, 2012
Inspectors:
M. Cain, Senior Resident Inspector
T. Chandler, Resident Inspector
Approved by:
Frank Ehrhardt, Chief Reactor Projects Branch 2 Division of Reactor Projects
Enclosure
SUMMARY OF FINDINGS
IR 05000424/2012002, 05000425/2012002; January 1, 2012 - March 31, 2012; Vogtle
Electric Generating Plant, Units 1 and 2; Integrated Report
The report covered a three-month period of inspection by two resident inspectors. One non-cited violation (NCV) with very low safety significance (Green) was identified. The significance of most findings is indicated by their color (Green, White, Yellow, or Red)using Inspection Manual Chapter (IMC) 0609, Significance Determination Process (SDP). Findings for which the SDP does not apply may be Green or assigned a severity level after NRC management review. The cross-cutting aspect was determined using IMC 0310, Components Within The Cross-Cutting Areas. The NRC's program for overseeing the safe operation of commercial nuclear power reactors is described in NUREG-1649, Reactor Oversight Process, Rev 4 dated December 2006.
Cornerstone: Mitigating Systems
Green: A self-revealing NCV of technical specification (TS) 5.4.1 was identified for failure to properly implement approved maintenance procedures. Specifically, maintenance technicians failed to properly re-land control wires, as required by procedure, on the Unit 2 turbine-driven auxiliary feedwater (TDAFW) pump following preventive maintenance activities. Once the loose wire connections inside junction box 2CWJB2729 were identified, the licensee immediately tightened the connections per procedure. The licensee entered this issue into their corrective action program (CR 404401 and CR 407192).
The finding was considered more than minor because it impacted the Reactor Safety Mitigating Systems Cornerstone objective to ensure the availability, reliability, and capability of systems that respond to initiating events to prevent undesirable consequences and affected the cornerstone attribute of equipment performance.
Specifically, loose wires in the control circuit for the TDAFW pump prevented the trip and throttle valve from operating correctly and caused the TDAFW pump to be declared inoperable for several hours. The inspectors used the Phase 1 Initial Screening and Characterization of Findings (IMC 0609.04 Exhibit 1) to characterize the finding. Since the inspectors answered No to all of the Table 4a Mitigating Systems Cornerstone questions, the inspectors concluded that the finding was of very low safety significance (Green). The inspectors determined that the cause of this finding was related to the Work Practices component of the Human Performance cross-cutting area due to failure to follow procedures. H.4(b) (Section 1R22)
REPORT DETAILS
Summary of Plant Status
Unit 1 operated at essentially full rated thermal power (RTP) for the entire inspection period.
Unit 2 operated at essentially full RTP for the entire inspection period.
REACTOR SAFETY
Cornerstones: Initiating Events, Mitigating Systems, Barrier Integrity
==1R01 Adverse Weather Protection
a. Inspection Scope
Impending Adverse Weather Condition Review.==
On January 4, the inspectors reviewed licensee procedure 11877-1 and 11877-2, Cold Weather Checklist, to verify the licensee had implemented actions to prepare the plant site for predicted severe weather conditions of sub-freezing temperatures. The inspectors walked down various safety-significant areas of the plant to verify the licensees ability to respond to the predicted adverse weather conditions.
b. Findings
No findings were identified.
==1R04 Equipment Alignment
a. Inspection Scope
Partial System Walkdown.==
The inspectors performed partial walkdowns of the following three systems to verify correct system alignment for the existing plant conditions. The inspectors checked for correct valve and electrical power alignments by comparing positions of valves, switches, and breakers in the plant to positions listed in the system operating procedure. Additionally, the inspectors reviewed the condition report database to verify that equipment alignment problems were being identified and appropriately resolved. Documents reviewed are listed in the attachment.
- Unit 2 train A engineered safety features (ESF) chiller system during the Unit 2 train B ESF chiller maintenance outage
- Unit 1 train A nuclear service cooling water (NSCW) system while the train B NSCW system was out of service due to a maintenance outage (AOT) on the 1B emergency diesel generator (EDG)
- Unit 2 train A, B & D 125V DC 1E electrical distribution system while the train C battery charger 2CD1CA was out of service due to a planned maintenance outage Complete System Walkdown. The inspectors performed a complete walkdown of the Unit 1 train B emergency diesel generator (EDG) and fuel oil transfer system during the train A EDG allowed outage time (AOT). The inspectors performed a detailed check of valve positions, electrical breaker positions, and operating switch positions to evaluate the operability of the redundant trains or components by comparing the required position in the system operating procedure to the actual position. The inspectors also reviewed control room logs, condition reports, and system health reports to verify that alignment and equipment discrepancies were being identified and appropriately resolved. The documents reviewed are listed in the Attachment.
b. Findings
No findings were identified.
==1R05 Fire Protection
a. Inspection Scope
Fire Drill Observation.==
On February 2, inspectors observed a fire drill from the control room, the primary fire brigade locker, and the fire scene. The fire was simulated to be in the Unit 2 Turbine Plant Component Cooling Water (TPCCW) air compressor #2 located on the A level in the Turbine Building. The inspectors assessed the adequacy of the fire drill and fire brigade response using licensee procedures 92000-C, Fire Protection Program, 92005-C, Fire Response Procedure, NMP-TR-425, Fire Drill Program, and 17103A-C, Annunciator Response Procedures for the Fire Alarm Computer. The inspectors evaluated the fire brigade performance to verify that they responded to the fire in a timely manner, donned proper protective clothing, used self-contained breathing apparatus, and had the equipment necessary to control and extinguish the fire. The inspectors assessed the adequacy of the fire brigades fire fighting strategy including entry into the fire area, communications, search and rescue, and equipment usage.
Fire Area Tours. The inspectors walked down the following five plant areas to verify the licensee was controlling combustible materials and ignition sources as required by procedures 92015-C, Use, Control, and Storage of Flammable/Combustible Materials, and 92020-C, Control of Ignition Sources. The inspectors assessed the condition of fire detection, suppression, and protection systems and reviewed the licensees fire protection limiting condition for operation log and condition report (CR) database to verify that the corrective actions for degraded equipment were identified and appropriately prioritized. The inspectors also reviewed the licensees fire protection program to verify the requirements of Updated Final Safety Analysis Report Section 9.5.1, Fire Protection Program, and Appendix 9A, Fire Hazards Analysis, were met. Documents reviewed are listed in the Attachment.
- Unit 2 auxiliary component cooling water (ACCW) heat exchanger rooms
- Unit 2 train B emergency diesel generator (EDG) building
- Unit 1 and Unit 2 fuel handling building level A spent fuel pool heat exchanger and piping penetration rooms
- Unit 2 4.16 kV switchgear and remote shutdown rooms
- Unit 2 containment spray (CS) and residual heat removal (RHR) pump rooms
b. Findings
No findings were identified.
==1R07 Heat Sink Performance
a. Inspection Scope
Annual Review.==
The inspectors reviewed the licensees records of the performance tests conducted on the Unit 2 B train EDG Jacket Water (JW) heat exchanger. The inspectors reviewed EPRI NP-7552, Heat Exchanger Performance Monitoring Guidelines to ensure that the licensees testing procedures were appropriate. Additionally, the inspectors reviewed the licensees corrective action program (CAP) for heat exchanger performance issues to ensure that discrepancies were being identified and appropriately resolved. Documents reviewed are listed in the Attachment.
b. Findings
No findings were identified.
==1R11 Licensed Operator Requalification
a. Inspection Scope
==
Resident Quarterly Observation of Operator Requalification Activities. The inspectors observed license requalification training conducted in the classroom. The inspectors observed the following lessons taught on March 20:
- V-RQ-PP-39000-011, introduction to PRA, enhanced (a)4, and risk managed technical specifications
- V-RQ-PP-29102-003, containment HVAC systems review
Documents reviewed are listed in the Attachment. The inspectors specifically assessed the following areas:
- Proper implementation of systematic approach to training
- Clarity and formality of communications
- Proper use of training aids
- Proper questing techniques used by the evaluators
Resident Quarterly Observation of Operator Performance In-Plant. The inspectors observed operator performance in the main control room on January 25, during startup and testing of the 1A EDG following a 13-day outage. Documents reviewed are listed in the Attachment. The inspectors specifically assessed the following areas:
- Operator compliance and use of plant procedures, including procedure entry and exit, performing procedure steps in the proper sequence, procedure place keeping, and technical specification entry and exit
- Control board component manipulations
- Communications between crew members
- Use and interpretation of plant instruments, indications and alarms
- Use of human error prevention techniques, such as pre-job briefs and peer checking
- Documentation of activities, including initials and sign-offs in procedures, control room logs, and technical specification entry and exit
- Management and supervision of activities, including risk management and reactivity management
b. Findings
No findings were identified.
==1R12 Maintenance Effectiveness
a. Inspection Scope
==
The inspectors evaluated the equipment issues described in the CRs listed below to verify the licensees effectiveness in performing corresponding preventive or corrective maintenance associated with structures, systems, and components (SSCs), to evaluate the effectiveness of the licensees treatment of equipment performance problems, and to verify the licensees maintenance practices met the requirements of 10 CFR 50.65 (the Maintenance Rule) and licensee procedure 50028-C, Engineering Maintenance Rule Implementation. The reviews included adequacy of the licensees failure characterization, establishment of performance criteria or 50.65(a)(1) performance goals, and adequacy of corrective actions. Other documents reviewed during these inspections included control room logs, system health reports, the maintenance rule database, and maintenance work orders. The inspectors also interviewed system engineers and the maintenance rule coordinator to assess the accuracy of identified performance deficiencies and extent of condition.
- 2007108257, safety features sequencer system functional failures
- 2006103407, pressure boundary leakage identified from bypass line
b. Findings
No findings were identified.
==1R13 Maintenance Risk Assessments and Emergent Work Evaluation
a. Inspection Scope
==
The inspectors reviewed the following five work activities to verify plant risk was properly assessed by the licensee prior to conducting the activities. The inspectors reviewed risk assessments and risk management controls implemented for these activities to verify they were completed in accordance with procedure 00354-C, Maintenance Scheduling, and 10 CFR 50.65(a)(4). The inspectors also reviewed the CR database to verify that maintenance risk assessment problems were being identified at the appropriate level, entered into the corrective action program, and appropriately resolved.
- Week of 1/9: operability testing on the 2B EDG concurrent with the maintenance outage on Unit 2 NSCW pump #5
- Week of 2/6: failure and subsequent troubleshooting of the Unit 2 turbine-driven auxiliary feedwater pump concurrent with testing of the solid state protection system
- Week of 2/13: corrective maintenance being performed on the Unit 1 loop 1 main feed regulation valve concurrent with high-risk work being performed in the high voltage switchyard
- Week of 2/27: preventive maintenance outage (AOT) on the Unit 1B emergency diesel generator (EDG) concurrent with failure of the #3 NSCW pump
- Week of 3/12: operability testing on the 1A EDG concurrent with high-risk work being performed in the low voltage switchyard
b. Findings
No findings were identified.
==1R15 Operability Evaluations
a. Inspection Scope
==
The inspectors reviewed the following six evaluations to verify they met the requirements of procedure NMP-GM-002, Corrective Action Program, and NMP-GM-002-001, Corrective Action Program Instructions. The scope of this inspection included a review of the technical adequacy of the evaluations, the adequacy of compensatory measures, and the impact of the equipment condition on continued plant operation.
- CR 385878 and TE 309973, packing gland hold down stud/nut missing on one side of unit 1 auxiliary spray to pressurizer isolation valve (1-1208-U4-A11)
- CR 400312 and TE 316317, bending radius violation on new replacement cable for 1RE0006
- CR 405658, accumulator sample isolation valves leaking by
- CR 411376 and TE 321825, TDAFW drain valve ALB16 D05 in solid - valve 2HV5178 is remaining open due to failure of 2LSH5178
- CR 414015, unit 2 unexpected alarm on B SSMP and 2ND3B trouble
- CR 404401, unit 2 TDAFW trip and throttle valve failure
b. Findings
No findings were identified.
==1R18 Plant Modifications
a. Inspection Scope
The inspectors reviewed temporary modification SNC357635 and associated 10CFR50.59 screening criteria against the system design bases documentation and procedure NMP-ES-054-001, Temporary Modification Processing This modification was installed because one packing gland stud on the pressurizer auxiliary spray line isolation valve 11208U4A11 is missing and the other gland stud is bent. This temporary modification installs an all threaded rod that takes the place of the missing stud and is designed to ensure the packing ring and follower remain in position.
The inspectors reviewed the implementation, engineering justification, and operator awareness of this temporary modification.
The inspectors reviewed temporary modification SNC345028 and associated 10CFR50.59 screening criteria against the system design bases documentation and procedure NMP-ES-054-001. This temporary modification installed a temporary pressure gauge and M&TE on several drain valves in the chemical and volume control system (CVCS) letdown system to determine the source of high back pressure on CVCS mixed bed demineralizer #2. The inspectors reviewed the implementation, engineering justification, and operator awareness for this temporary modification.
b. Findings
No findings were identified.
==1R19 Post-Maintenance Testing
a. Inspection Scope
==
The inspectors either observed post-maintenance testing or reviewed the test results for the following six maintenance activities to verify that the testing met the requirements of procedure 29401-C, Work Order Functional Tests, for restoring equipment operability and functional capability. The inspectors also reviewed the test procedures to verify the acceptance criteria were sufficient to meet the Technical Specifications operability requirements.
- Maintenance outage work orders: SNC125468 - temperature switch calibration, SNC125854 - clean/inspect/megger motor, lube bearings, SNC128307 - replace Train B ESF Chiller TDC sensor, and SNC125852 - B ESF chiller 002 channel calibration T-4193
- MWO SNC359763 - correct dual indication on Unit 2 loop 1 atmospheric relief valve 2PV-3000
- MWO SNC337135 - change upper motor bearing oil on 2B1205P6002
- Maintenance outage for 1B diesel generator major inspection 2012
- MWO SNC367372 - Unit 2 TDAFW trip and throttle valve will not open
b. Findings
No findings were identified.
==1R22 Surveillance Testing
a. Inspection Scope
==
The inspectors reviewed the following six test procedures and also either observed the testing or reviewed test results to verify that testing was conducted in accordance with the procedures and that the acceptance criteria adequately demonstrated that the equipment was operable. Additionally, the inspectors reviewed the CR database to verify that the licensee had adequately identified and implemented appropriate corrective actions for surveillance test problems.
Surveillance Tests
- 14421-2 Rev. 40, solid state protection system train B operability test
- 14980B-1 Rev. 23.5, diesel generator 1B operability test
- 24797-1 Rev. 20.1, steam pressure loop 4 (Protection I) 1P-544 channel operational test and channel calibration
- 14980B-2 Rev. 22.5, diesel generator 2B operability test
In-Service Tests (IST)
- 14805B-2 Rev. 3, train B residual heat removal pump IST and response time test
- 14810-2 Rev. 41, TDAFW pump operability, response time and check valve IST
b. Findings
Introduction.
A Green self-revealing non-cited violation (NCV) of technical specification 5.4.1 was identified for failure to properly implement approved maintenance procedures.
Specifically, maintenance mechanics failed to properly re-land control wires, as required by procedure, on the Unit 2 turbine-driven auxiliary feedwater (TDAFW) pump following preventive maintenance activities. As a result, the Unit 2 TDAFW pump was rendered inoperable for 26 hours3.009259e-4 days <br />0.00722 hours <br />4.298942e-5 weeks <br />9.893e-6 months <br />.
Description.
On February 9, 2012, during restoration of the Unit 2 TDAFW pump from a surveillance test, the trip and throttle valve (2PV15129) failed to automatically open after being reset using the hand switch in the control room. Subsequent inspection and troubleshooting identified eight loose wire connections inside junction box 2CWJB2729, which is mounted on the side of the TDAFW pump. Two of these eight loose connections were in the circuit that prevented the trip and throttle valve from opening once it was reset. Further investigation revealed that several connections inside junction box 2CWJB2729 had been lifted and re-landed during the 10-year preventive maintenance outage that had been performed in September 2011. A review of the completed preventive maintenance procedures indicate that even though the manipulated wires were re-landed to their proper terminal locations, they were not tightened as required by maintenance procedure 25717-C, Torquing Electrical Type Connections. This fact was not identified at that time. However, the TDAFW pump operated normally and successfully passed all surveillance testing for approximately five months. The licensee has theorized that friction between the wire lugs and the terminal board was adequate to allow proper operation of the TDAFW pump during that time period. This theory is supported by the fact that when the wire bundle in the terminal box was moved during troubleshooting on February 9, 2012, the trip and throttle valve began to operate properly. Once the loose wire connections inside junction box 2CWJB2729 were identified, the licensee immediately tightened the connections per procedure. To check extent of condition, the licensee also verified that all connections in the corresponding junction box on the Unit 1 TDAFW pump were properly tightened. While the event investigation was taking place, the licensee issued a standing order to instruct the operators to locally declutch and open the trip and throttle valve if operation of the TDAFW pump was required.
The safety function of the auxiliary feedwater (AFW) system is to supply water to the steam generators to remove decay heat and other residual heat by delivering at least the minimum required flow rate to the steam generators at pressures corresponding to the lowest steam generator safety valve set point plus 3%. In addition, the AFW system must supply enough makeup water to replace steam generator secondary inventory lost as the unit cools to Mode 4 conditions. The licensee concluded that because the trip and throttle valve is normally full open, and the loose wires only prevented the trip and throttle valve from being re-opened following a turbine trip, no loss of safety function occurred. In addition, the operators always had the ability to open the trip and throttle valve locally.
Analysis.
The failure to properly re-land wires in junction box 2CWJB2729 following preventive maintenance activities on the TDAFW pump is a performance deficiency because the licensee failed to meet a standard (procedure 25717-C, Torquing Electrical Type Connections) and the cause was reasonably within the licensees ability to foresee and correct. The finding was considered more than minor because it impacted the Reactor Safety Mitigating Systems Cornerstone objective to ensure the availability, reliability, and capability of systems that respond to initiating events to prevent undesirable consequences and affected the cornerstone attribute of equipment performance. Specifically, loose wires in the control circuit for the TDAFW pump prevented the trip and throttle valve from operating correctly and caused the TDAFW pump to be declared inoperable for 26 hours3.009259e-4 days <br />0.00722 hours <br />4.298942e-5 weeks <br />9.893e-6 months <br /> while troubleshooting was being performed.
The inspectors evaluated the finding using IMC 0609, Appendix A, Determining the Significance of Reactor Inspection Findings for At-Power Situations and used 0609.04, Phase 1 Initial Screening and Characterization of Findings, to characterize the finding. Using Exhibit 1 Table 2, the inspectors determined that the finding affected the Mitigation Systems Cornerstone. Specifically, the finding degraded the short term heat removal systems. Since the inspectors answered No to all of the Exhibit 1, Table 4a Mitigating Systems Cornerstone screening questions, the inspectors concluded that the finding was of very low safety significance (Green).
The primary cause of the performance deficiency, as determined by the inspectors, was less than adequate procedure use and self-checking. The inspectors determined that the cause of this finding was related to the Work Practices component of the Human Performance cross-cutting area due to failure to follow procedures. H.4(b) Specifically, the maintenance technician failed to tighten the lugs after re-landing the wires as required by procedure.
Enforcement.
The inspectors determined that the finding represents a violation of regulatory requirements because it involved improper implementation of procedures associated with safety-related plant equipment. TS 5.4.1 requires that written procedures, specified in Regulatory Guide 1.33, Revision 2, Appendix A, February 1978, shall be established, implemented, and maintained. Regulatory Guide 1.33 states that maintenance activities that can affect the performance of safety-related equipment should be performed in accordance with written procedures, documented instructions, or drawings appropriate to the circumstances. Contrary to the above, maintenance personnel failed to follow the approved maintenance procedures, and as a result, failed to properly re-land wires in the control circuitry of the Unit 2 TDAFW pump following preventive maintenance activities in September 2011. As a result of the violation, the Unit 2 TDAFW pump was rendered inoperable for 26 hours3.009259e-4 days <br />0.00722 hours <br />4.298942e-5 weeks <br />9.893e-6 months <br /> on February 9, 2012. Once the loose wire connections were identified, the licensee immediately tightened the connections per procedure. Because this violation was of very low safety significance and it was entered into the licensees corrective action program (ref. CR 404401 and CR 407192), this violation is being treated as an NCV, consistent with the Enforcement Policy. This finding will be tracked as NCV 05000425/2012002-01, Work Practice Error Renders Unit 2 TDAFW Pump Inoperable.
1EP6 Drill Evaluation
a. Inspection Scope
The inspectors reviewed the facility activation exercise guide and observed the following emergency response activity to verify the licensee was properly classifying emergency events, making the required notifications, and making appropriate protective action recommendations in accordance with procedures 91001-C, Emergency Classifications, and 91305-C, Protective Action Guidelines.
C On February 15, 2012, the licensee conducted an emergency preparedness drill which involved actuation of the TSC, the OSC, and the EOF. The drill scenario began with pressurizer pressure instrument 1PI-458 failing high with an anticipated transient without scram (ATWS). After operators successfully manually tripped the reactor, a large break loss of coolant accident (LBLOCA) and subsequent failure of the 1B safety injection pump discharge piping failure occurred.
b. Findings
No findings were identified.
OTHER ACTIVITIES
4OA1 Performance Indicator (PI) Verification
a. Inspection Scope
The inspectors sampled licensee submittals for the listed PIs during the period from January 1, 2011 through December 31, 2011, for Unit 1 and Unit 2. The inspectors verified the licensees basis in reporting each data element using the PI definitions and guidance contained in procedure 00163-C, NRC Performance Indicator and Monthly Operating Report Preparation and Submittal, and Nuclear Energy Institute document NEI 99-02, Regulatory Assessment Indicator Guideline.
The inspectors reviewed Unit 1 and Unit 2 operator log entries, the Vogtle Electric Generating Plant Unit 1 and Unit 2 NRC Mitigating System Performance Index Basis Document, the monthly operating reports and monthly PI summary reports to verify that the licensee had accurately submitted the PI data.
Mitigating Systems Cornerstone
- Unplanned Scrams per 7,000 Critical Hours
- Unplanned Scrams with Complications
- Unplanned Power Changes per 7,000 Critical Hours
b. Findings
No findings were identified.
4OA2 Identification and Resolution of Problems
.1 Daily Condition Report Review.
As required by inspection procedure 71152, Identification and Resolution of Problems, and in order to help identify repetitive equipment failures or specific human performance issues for follow-up, the inspectors performed a daily screening of items entered into the licensees corrective action program. This review was accomplished by either attending daily screening meetings that briefly discussed major CRs, or accessing the licensees computerized corrective action database and reviewing each CR.
.2 Focused Review
a. Inspection Scope
The inspectors performed a detailed review of the following CRs which address various issues identified during the extended maintenance outage (AOT) of the 1A EDG. The goal of the review was to verify that the full extent of the issues were identified, appropriate evaluations were performed, and appropriate corrective actions were specified and prioritized. The inspectors evaluated the CRs against the licensees corrective action program as delineated in procedure NMP-GM-002, Corrective Action Program, and 10 CFR 50, Appendix B. Documents reviewed are listed in the
.
- 395186 - energized heater at 1A diesel generator
- 395873 - debris discovered in area of #7 cylinder
- 396442 - 1A EDG came out of maintenance mode
- 396593 - 1A diesel generator TD4 failure
- 396599 - failure of 3-way valve discovered during 1A EDG functional test
- 396606 - during testing on 1A EDG lube oil annunciator in solid
- 396744 - no clear direction for setting of power driven potentiometer limit switches
- 396812 - meggering procedure 25736-C needs enhancing
- 396866 - issues identified with procedure GEN 95 Chapter 46
- 397023 - 1A EDG #7 rod bearing scoring
- 397070 - 1A EDG paint chips found in oil system
- 400096 - excessive leak by into 1A EDG jacket water stand pipe
The inspectors performed a detailed review of the following CR which addressed an increasing trend in the Unit 2 containment building radioactivity. The goal of the review was to verify that the full extent of the issue was identified, an appropriate evaluation was performed, and appropriate corrective actions were specified and prioritized. The inspectors evaluated the CR against the licensees corrective action program as delineated in procedure NMP-GM-002 and 10 CFR 50, Appendix B, Criterion XVI, Corrective Action. Documents reviewed are listed in the Attachment.
C CR 393818 Unit 2 containment radioactivity indicates an increasing trend
b. Findings and Observations
No findings were identified.
4OA3 Event Follow-up
.1 (Closed) Licensee Event Report 05000424/2010-001-01:
Breaker Failure Results in 1B Train Containment Cooling System Being Declared Inoperable
On October 24, 2010, the licensee attempted to manually start Containment Cooling Unit
- 8 in low speed during the performance of a Containment Cooling System Operability and Response Time Test and the cooling unit did not start. Work Order (WO)1102198301 investigation identified that the circuit breaker had two breaker cover mounting holes that were cracked. This allowed the top right hand side screw to come in contact with the breakers closing mechanism, thus preventing the breaker from closing.
The inspectors reviewed the LER, the associated condition report and apparent cause determination, and subsequent action items. The enforcement aspects associated with this event were documented in NRC integrated inspection report 05000424,425/2010005 Section 4OA2. No other findings were identified. This LER is closed.
.2 (Closed) Licensee Event Report 05000425/2011-001:
Inoperable Core Exit Thermocouple Indicator on the B Train Remote Shutdown Panel
October 27, 2011, the licensee discovered that mode changes had been made contrary to TS LCO 3.0.4. TS 3.3.4, Remote Shutdown System, limiting condition for operation (LCO) requires two channels of Core Exit Thermocouples (CETC) to be operable.
During startup from the refueling outage 2R15, one of the CETC channels credited for satisfying this requirement was inoperable but was not recognized as being inoperable until the unit was in mode 1. Since mode changes were made with only one of the two required CETC channels operable, the unit was operated in a condition contrary to TS LCO 3.0.4. The inspectors reviewed the LER, the associated condition report and apparent cause determination, and subsequent action items. The enforcement aspects associated with this event were documented in NRC integrated inspection report 05000424,425/2011005 Section 4OA7. No other findings were identified. This LER is closed.
.3 (Closed) Licensee Event Report 05000424/2011-003:
Control Room Air Damper Found Closed Results in Technical Specification Non-Compliance
On September 22, 2011 at approximately 0155 hours0.00179 days <br />0.0431 hours <br />2.562831e-4 weeks <br />5.89775e-5 months <br />, the licensee discovered that the Control Room Normal Heating, Ventilation, and Air Conditioning (HVAC) damper AHV-12153 was closed. This stops all air flow through the control room radioactive gas monitors, rendering them inoperable. A subsequent review of the plant computer system showed the valve was closed on September 19, 2011 at 2029 hours0.0235 days <br />0.564 hours <br />0.00335 weeks <br />7.720345e-4 months <br />. Because the TS require the control room emergency filtration system (CREFS) to be placed in the emergency mode if the control room air intake radioactive gas monitors are inoperable for more than one hour, and this was not done, the units operated in a condition prohibited by the TS. The inspectors reviewed the LER, the associated condition report and apparent cause determination, and subsequent action items. The enforcement aspects associated with this event were documented in NRC integrated inspection report 05000424,425/2011004 Section 4OA7. No other findings were identified. This LER is closed.
4OA5 Other Activities
.1 Quarterly Resident Inspector Observations of Security Personnel and Activities
a. Inspection Scope
During the inspection period, the inspectors conducted observations of security force personnel and activities to ensure that the activities were consistent with licensee security procedures and regulatory requirements relating to nuclear plant security. These observations took place during both normal and off-normal plant working hours.
These quarterly resident inspector observations of security force personnel and activities did not constitute any additional inspection samples. Rather, they were considered an integral part of the inspectors' normal plant status reviews and inspection activities.
b. Findings and Observations
No findings were identified.
.2 Institute of Nuclear Power Operations (INPO) Report Review
During this inspection period the final INPO Evaluation Report dated February 2012 was reviewed. The report contained no safety issues which were not already known by the NRC.
4OA6 Meetings, Including Exit
.1 Exit Meeting
On April 23, the resident inspectors presented the inspection results to Mr. S. Bargeron and other members of your staff, who acknowledged the findings. The inspectors confirmed that proprietary information was not provided or examined during the inspection.
ATTACHMENT:
SUPPLEMENTAL INFORMATION
KEY POINTS OF CONTACT
Licensee personnel
- S. Bargeron, Plant Manager
- R. Brown, Training Manager
- R. Collins, Chemistry Manager
- D. Puckett, Performance Analysis Supervisor
- R. Dedrickson, Plant Manager
- K. Dyar, Security Manager
- I. Kochery, Health Physics Manager
- T. Tynan, Site Vice-President
- D. McCary, Operations Manager
- S. Swanson, Site Support Manager
- S. Waldrup, Site Engineering Director
NRC personnel
- F. Ehrhardt, Chief, Region II Reactor Projects Branch 2
LIST OF ITEMS
OPENED AND CLOSED
OPEN AND CLOSED
Work Practice Error Renders Unit 2 TDAFW Pump Inoperable (Section 1R22)
CLOSED
- 05000424/2010-001-01 LER
Breaker Failure Results in 1B Train Containment Cooling System Being Declared Inoperable (Section 4OA3.1)
Inoperable Core Exit Thermocouple Indicator on the B Train Remote Shutdown Panel (Section 4OA3.2)
Control Room Air Damper Found
Closed
Results in Technical Specification Non-
Compliance (Section 4OA3.3)