IR 05000346/2021003

From kanterella
Jump to navigation Jump to search
Integrated Inspection Report 05000346/2021003
ML21313A272
Person / Time
Site: Davis Besse 
(NPF-003)
Issue date: 11/10/2021
From: Billy Dickson
NRC/RGN-III/DRP/B2
To: Tony Brown
Energy Harbor Nuclear Corp
References
IR 2021003
Download: ML21313A272 (18)


Text

SUBJECT:

DAVIS-BESSE NUCLEAR POWER STATION - INTEGRATED INSPECTION REPORT 05000346/2021003

Dear Mr. Brown:

On September 30, 2021, the U.S. Nuclear Regulatory Commission (NRC) completed an inspection at Davis-Besse Nuclear Power Station. On October 26, 2021, the NRC inspectors discussed the results of this inspection with you and other members of your staff. The results of this inspection are documented in the enclosed report.

No findings or violations of more than minor significance were identified during this inspection.

This letter, its enclosure, and your response (if any) will be made available for public inspection and copying at http://www.nrc.gov/reading-rm/adams.html and at the NRC Public Document Room in accordance with Title 10 of the Code of Federal Regulations 2.390, Public Inspections, Exemptions, Requests for Withholding.

Sincerely, Billy C. Dickson, Jr., Chief Branch 2 Division of Reactor Projects Docket No. 05000346 License No. NPF-3

Enclosure:

As stated

Inspection Report

Docket Number:

05000346

License Number:

NPF-3

Report Number:

05000346/2021003

Enterprise Identifier:

I-2021-003-0072

Licensee:

Energy Harbor Nuclear Corp.

Facility:

Davis-Besse Nuclear Power Station

Location:

Oak Harbor, OH

Inspection Dates:

July 01, 2021 to September 30, 2021

Inspectors:

R. Cassara, Resident Inspector

J. Cassidy, Senior Health Physicist

D. Mills, Senior Resident Inspector

J. Nance, Operations Engineer

J. Neurauter, Senior Reactor Inspector

R. Rolph, Senior Resident Inspector

Approved By:

Billy C. Dickson, Jr., Chief

Branch 2

Division of Reactor Projects

SUMMARY

The U.S. Nuclear Regulatory Commission (NRC) continued monitoring the licensees performance by conducting an integrated inspection at Davis-Besse Nuclear Power Station, in accordance with the Reactor Oversight Process. The Reactor Oversight Process is the NRCs program for overseeing the safe operation of commercial nuclear power reactors. Refer to https://www.nrc.gov/reactors/operating/oversight.html for more information.

List of Findings and Violations

No findings or violations of more than minor significance were identified.

Additional Tracking Items

Type Issue Number Title Report Section Status LER 05000346/2019-003-00 LER 2019-003-00 for Davis-Besse, Unit 1,

Anticipatory Reactor Trip System Actuated During Turbine Stop Valve Testing due to the Closure of a Main Turbine Stop Valve.

71153 Closed

PLANT STATUS

Unit 1 began the inspection period at full power. On July 8, 2021, the unit tripped from 100 percent power due to a failure of the generator exciter power supply that caused a turbine trip.

The unit was returned to full power on July 12, 2021 and remained at or near full power for the remainder of the inspection period.

INSPECTION SCOPES

Inspections were conducted using the appropriate portions of the inspection procedures (IPs) in effect at the beginning of the inspection unless otherwise noted. Currently approved IPs with their attached revision histories are located on the public website at http://www.nrc.gov/reading-rm/doc-collections/insp-manual/inspection-procedure/index.html. Samples were declared complete when the IP requirements most appropriate to the inspection activity were met consistent with Inspection Manual Chapter (IMC) 2515, Light-Water Reactor Inspection Program - Operations Phase. The inspectors reviewed selected procedures and records, observed activities, and interviewed personnel to assess licensee performance and compliance with Commission rules and regulations, license conditions, site procedures, and standards.

Starting on March 20, 2020, in response to the National Emergency declared by the President of the United States on the public health risks of the coronavirus (COVID-19), resident and regional inspectors were directed to begin telework and to remotely access licensee information using available technology. During this time, the resident inspectors performed periodic site visits each week, increasing the amount of time on site as local COVID-19 conditions permitted.

As part of their onsite activities, resident inspectors conducted plant status activities as described in IMC 2515, Appendix D; observed risk significant activities; and completed on site portions of IPs. In addition, resident and regional baseline inspections were evaluated to determine if all or a portion of the objectives and requirements stated in the IP could be performed remotely. If the inspections could be performed remotely, they were conducted per the applicable IP. In some cases, portions of an IP were completed remotely and on site. The inspections documented below met the objectives and requirements for completion of the IP.

REACTOR SAFETY

71111.01 - Adverse Weather Protection

Seasonal Extreme Weather Sample (IP Section 03.01) (1 Sample)

(1) The inspectors evaluated readiness for seasonal extreme weather conditions prior to the onset of seasonal warm temperatures and heavy rains for plant systems including the emergency diesel generators, component cooling water system, and service water system.

71111.04 - Equipment Alignment

Partial Walkdown Sample (IP Section 03.01) (4 Samples)

The inspectors evaluated system configurations during partial walkdowns of the following systems/trains:

(1) Emergency diesel generator train 2 during the week ending September 11, 2021
(2) Containment spray train 2 during the week ending September 11, 2021
(3) Motor driven feedwater while auxiliary feedwater train 2 inoperable for scheduled maintenance and broken governor linkage replacement during the week ending September 25, 2021
(4) Auxiliary feedwater train 1 while auxiliary feedwater train 2 inoperable for scheduled maintenance and broken governor linkage replacement during the week ending September 25, 2021

Complete Walkdown Sample (IP Section 03.02) (1 Sample)

(1) Decay heat/low pressure injection full system walkdown during the week ending September 4, 2021

71111.05 - Fire Protection

Fire Area Walkdown and Inspection Sample (IP Section 03.01) (5 Samples)

The inspectors evaluated the implementation of the fire protection program by conducting a walkdown and performing a review to verify program compliance, equipment functionality, material condition, and operational readiness of the following fire areas:

(1) Main steam line rooms 1 and 2, fire area DH, during the week ending July 17, 2021
(2) Auxiliary feed pump 1 room, fire area F, during the week ending July 26, 2021
(3) Emergency core cooling system 2 room and decay heat coolers room, fire area AB-01, during the week ending August 28, 2021
(4) Diesel Generator 1-2 room, fire area J, during the week ending September 11, 2021
(5) Mechanical penetration room 4, fire area A, during the week ending September 11, 2021

71111.06 - Flood Protection Measures

Inspection Activities - Internal Flooding (IP Section 03.01) (1 Sample)

The inspectors evaluated internal flooding mitigation protections in the:

(1) Emergency core cooling system room 2 and mechanical penetration room 4

71111.11Q - Licensed Operator Requalification Program and Licensed Operator Performance

Licensed Operator Performance in the Actual Plant/Main Control Room (IP Section 03.01) (2 Samples)

(1) The inspectors observed and evaluated licensed operator performance in the control room during service water pump 3 testing and shutdown following pump replacement
(2) The inspectors observed and evaluated licensed operator performance in the control room during shutdown operations and restart following the reactor trip on July 8, 2021

Licensed Operator Requalification Training/Examinations (IP Section 03.02) (1 Sample)

(1) Observation of operator performance during simulator training for drill and exercise performance during the week ending September 11, 2021

71111.12 - Maintenance Effectiveness

Maintenance Effectiveness (IP Section 03.01) (3 Samples)

The inspectors evaluated the effectiveness of maintenance to ensure the following structures, systems, and components (SSCs) remain capable of performing their intended function:

(1) Repair of atmospheric vent valve 2 during the week ending July 10, 2021
(2) Decay heat/low pressure injection cooler 1 outlet valve failed closed during the week ending August 21, 2021
(3) Motor-operated valve interlock switch replacements CV2002 during the week ending September 30, 2021

Quality Control (IP Section 03.02) (1 Sample)

The inspectors evaluated the effectiveness of maintenance and quality control activities to ensure the following SSC remains capable of performing its intended function:

(1) Emergency diesel generator 1 voltage regulator reference adjuster replacement during the week ending August 7, 2021

71111.15 - Operability Determinations and Functionality Assessments

Operability Determination or Functionality Assessment (IP Section 03.01) (6 Samples)

The inspectors evaluated the licensee's justifications and actions associated with the following operability determinations and functionality assessments:

(1) Train 2 emergency core cooling systems CR-2021-05793 during the week ending July 31, 2021
(2) Decay heat train 1 due to failed DH14B CR 2021-06239 during the week ending August 21, 2021
(3) DH14B failed closed CR 202-06239 during the week ending August 21, 2021
(4) Motor-operated valve interlock switch replacements CV2002 during the week ending September 4, 2021
(5) CV-2002B motor-operated valve failed to cycle during maintenance during the week ending September 4, 2021
(6) Auxiliary feedwater pump turbine governor linkage broken during maintenance, CR 2021-07124, during the week ending September 25, 2021

71111.19 - Post-Maintenance Testing

Post-Maintenance Test Sample (IP Section 03.01) (5 Samples)

The inspectors evaluated the following post-maintenance test activities to verify system operability and functionality:

(1) Auxiliary feedwater pump 1 following planned maintenance during the week ending August 14, 2021
(2) Emergency diesel generator 1 following planned replacement of speed switch ST6221 during the week ending August 21, 2021
(3) Decay heat/low pressure injection pump quarterly test following DH14B repair during the week ending August 21, 2021
(4) Emergency diesel generator train 1 following speed switch replacement during the week ending August 7, 2021
(5) Auxiliary feedwater train 2 following scheduled maintenance and broken governor linkage replacement during the week ending September 25, 2021

71111.20 - Refueling and Other Outage Activities

Refueling/Other Outage Sample (IP Section 03.01) (1 Sample)

(1) The inspectors evaluated activities related to plant trip on July 8, 2021

71111.22 - Surveillance Testing

The inspectors evaluated the following surveillance tests:

Surveillance Tests (other) (IP Section 03.01)

(1) Reactor protection system manual reactor trip during the week ending July 10, 2021
(2) Auxiliary feedwater pump 1 quarterly surveillance run during the week ending August 14, 2021
(3) Emergency diesel generator 2 monthly test during the week ending September 4, 2021

Inservice Testing (IP Section 03.01) (2 Samples)

(1) Decay heat/low pressure injection pump 1 quarterly test reperformed on August 19, 2021
(2) Emergency diesel generator 1 monthly test during the week ending August 21, 2021

FLEX Testing (IP Section 03.02) (1 Sample)

(1) Emergency feedwater pump quarterly run during the week ending September 4, 2021

71114.06 - Drill Evaluation

Drill/Training Evolution Observation (IP Section 03.02) (1 Sample)

The inspectors evaluated:

(1) Integrated drill on August 24,

RADIATION SAFETY

71124.07 - Radiological Environmental Monitoring Program

Environmental Monitoring Equipment and Sampling (IP Section 03.01) (1 Sample)

(1) The inspectors evaluated environmental monitoring equipment and observed collection of environmental samples.

Radiological Environmental Monitoring Program (IP Section 03.02) (1 Sample)

(1) The inspectors evaluated the implementation of the licensees radiological environmental monitoring program.

GPI Implementation (IP Section 03.03) (1 Sample)

(1) The inspectors evaluated the licensees implementation of the Groundwater Protection Initiative program to identify incomplete or discontinued program elements.

OTHER ACTIVITIES - BASELINE

71152 - Problem Identification and Resolution

Annual Follow-up of Selected Issues (IP Section 02.03) (1 Sample)

The inspectors reviewed the licensees implementation of its corrective action program related to the following issues:

(1) Shield building core bore inspections including the expansion of shoulder 3 work scope due to increased crack size

71153 - Follow Up of Events and Notices of Enforcement Discretion Event Report (IP Section 03.02)

The inspectors evaluated the following licensee event reports (LERs):

(1) LER 2019-003 "Anticipatory Reactor Trip System Actuated Unexpectedly During Turbine Stop Valve Testing due to the Closure of a Main Turbine Stop Valve" (ADAMS Accession No. ML19312A071), (also see EN 54263). During scheduled quarterly turbine valve testing on September 7, 2019, the plant tripped from 95 percent power due to spurious closure of main stop valve Number 4 during main stop valve Number 2 testing. Following the trip maintenance and component replacements were performed to address licensee identified electrohydraulic control system failure modes. On February 28, 2021, during scheduled main stop valve testing, the same issue was noted but did not result in a reactor trip. Following this the licensee began testing the stop valves at 40 percent power (below the ARTS trip setpoint). Subsequently the licensee identified a 1997 General Electric Technical Information Letter that suggested installation of restricting orifices in the EHC system.

Following the reactor trip on July 8, 2021, the licensee installed the restricting orifices and successfully tested the main stop valves at 95 percent power. The inspectors determined that it was not reasonable to foresee or correct the cause discussed in the LER therefore no performance deficiency was identified. The inspectors did not identify a violation of NRC requirements. This LER is closed.

INSPECTION RESULTS

Observation: Expansion of Shoulder 3 Work Scope Due to Increased Crack Size 71152 As indicated in Condition Report (CR) 2021-06142: During ECP 18-0037-006 preparation, the exact extent of the Shield Building shoulder repair in the upper region was not able to be obtained. The inability to obtain the exact extent of repair for this region was due to the station vent platforms/ladders interfering with performing Impulse Response. During the demolition of the upper region, the licensee observed that the laminar crack extended beyond the initial demo limits. The licensee performed subsequent Impulse Response and identified that the demo limits would need to be expanded to completely encapsulate the laminar crack.

The inspectors reviewed the licensee's documentation affected by expanding Shoulder 3 demolition limits. Specifically, the inspector reviewed CR 2021-06142 for issues the licensee needed to resolve related to expanded Shoulder 3 repair, the associated EC 18-0037-006 including 50.59 Screen 18-00648, and related engineering calculations and evaluations:

Calculation C-CSS-099.20-076 that demonstrated shield building structural integrity during the interim concrete demolition condition,

Evaluation EER 601327705 that evaluated and provided details for the temporary modification of the platform brace and installation of scaffold bearing on the second platform, and Evaluation EER 601275302 that evaluated the structural adequacy of the shield building dome and shell with additional loads from the knuckle boom crane during the concrete repair.

The inspectors verified that the licensee had calculations/evaluations that supported expanding Shoulder 3 repair limits, including modifying existing supporting structures.

No findings of significance were identified.

EXIT MEETINGS AND DEBRIEFS

The inspectors verified no proprietary information was retained or documented in this report.

On October 26, 2021, the inspectors presented the integrated inspection results to Mr. T. Brown, Site Vice President, and other members of the licensee staff.

On July 16, 2021, the inspectors presented the radiation protection inspection results to Mr. T. Brown, Site Vice President, and other members of the licensee staff.

DOCUMENTS REVIEWED

Inspection

Procedure

Type

Designation

Description or Title

Revision or

Date

DB-OP-06012

2: DH LOOP 2 Normal Lineup Valve Checklist

DB-OP-06225

Transferring the MDFP from the Main Feedwater Mode to the

Auxiliary Feedwater Mode Valve Lineup

71111.04

Procedures

DB-SS-03090

MDFP Flow Path Valve Checklist

PFP-AB-105

Auxiliary Building

PFP-AB-113

Auxiliary Building

PFP-AB-314

Auxiliary Building

PFP-AB-319

Auxiliary Building

PFP-AB-601E

No. 1 Main Steam Line Area, Room 601E, Fire Area DH

71111.05

Fire Plans

PFP-AB-602

No. 2 Main Steam Line Area, Room 602, Fire Area DH

DB-OP-06013

Containment Spray Train 2 Valve Checklist

DB-OP-06233

Auxiliary Feedwater System Train 1 Lineup Valve Checklist

71111.06

Procedures

DB-OP-06316

EDG 2 Switch and Breaker Checklist

20-02223

IR21: Failed Mechanical Interlock on BE1183

03/14/2020

20-08295

BF1182 Mechanical Interlock Found with Broken Piece and

Mounting Screw Stripped

10/26/2020

20-08328

BF1183 Forward/Reverse Contactor Mechanical Interlock

Found Degraded

10/27/2020

20-08416

CV5076 Sticking Mechanical Interlock

10/29/2020

21-01311

HIC DH14B Demand Signal Continued to Display 20 Percent

Open While Set to 0 Percent Open

2/26/2021

21-06239

DH14B Failed Closed

08/18/2021

Corrective Action

Documents

21-06676

Mechanical Interlock Failure

09/02/2021

FSK-M-GCB-3-1

Decay Heat Pump Recirculation Piping

ISI-SK-050

Decay Heat Coolers 1-1 and 1-2 Outline and Supports

ISID2-033C

Decay Heat Train 2

ISIM2-233F

Low Pressure Injection System

Drawings

ISIM2-234D

Containment Spray System and Spent Fuel Pool Cooling

System

71111.12

Engineering

Changes

60129065B

Engineering Evaluation Request

10/26/2020

Inspection

Procedure

Type

Designation

Description or Title

Revision or

Date

Procedures

DB-SP-03446

Decay Heat Train 1 Pump and Valve Test

200694387

PM 11998 BF1183 Test

11/05/2020

200696633

MV2002B Inspect RPS/SFAS#3

08/31/2021

Work Orders

200790236

PM 12098 BF1181 Test

10/29/2020

2019-10673

SW Pump 3 Abnormal Noise

2/30/2019

20-01303

DH2734 Declutched and Manually Seated

2/19/2020

20-02223

1R21: Failed Mechanical Interlock on BE1183

03/14/2020

20-02817

IST Trending: Adverse Step Change Closed Stroke Time on

DH13A

03/31/2020

20-04130

Service Water Pump 2 Packing Leak Off Excessive

05/09/2020

20-08295

BF1182 Mechanical Interlock Found with Broken Piece and

Mounting Screw Stripped

10/26/2020

20-08328

BF1183 Forward/Reverse Contactor Mechanical Interlock

Found Degraded

10/27/2020

20-08416

CV5076 Sticking Mechanical Interlock

10/29/2020

21-00465

MUP 1 O/B Temperature Element Failed

01/26/2021

21-01311

HIC DH14B Demand Signal Continued to Display 20 Percent

Open While Set to 0 Percent Open

2/26/2021

21-03540

Makeup Pump Room A/C Unit Found Tripped Off

05/01/2021

21-03710

System Monitoring - Makeup Pump Motor 1 Pump

End Bearing Oil Temperature, T747, Erratic Indication

05/06/2021

21-04524

Cycle 22 1/8th Core Location H14 Max Segment Peaking

Deviation Approaching BMAC Limit

06/08/2021

21-05586

Wet Wash Building Wall Settled and Put Stress on Piping

and Conduit for Makeup Pump Room Air Conditioner

07/22/2021

21-05609

MUP Room Temperature Exceeds 115 Degrees Fahrenheit

07/23/2021

21-05626

Makeup Pump 1 Speed Increaser Oil Level Low

07/23/2021

21-05633

SW Pump 3 Full Flow Testing Stopped due to Loss of Pump

Packing Gland Leak Off

07/24/2021

21-05658

Entry into Abnormal Procedure for Loss of Service Water

Secondaries

07/26/2021

21-06239

DH14B Failed Closed

08/18/2021

71111.15

Corrective Action

Documents

21-06676

Mechanical Interlock Failure

09/02/2021

Inspection

Procedure

Type

Designation

Description or Title

Revision or

Date

Corrective Action

Documents

Resulting from

Inspection

21-06146

21 NRC SIT: Switch DST for MUP Time Delay

Relay 2Y1 Isolation Potentially Exposed to Similar

Degradation Mechanisms as EDG FFSS

08/13/2021

FSK-M-GCB-3-1

Decay Heat Pump Recirculation Piping

ISI-SK-050

Decay Heat Coolers 1-1 and 1-2 Outline and Supports

ISIM2-233F

Low Pressure Injection System

Drawings

ISIM2-234D

Containment Spray System and Spent Fuel Pool Cooling

System

Engineering

Changes

60129065B

Engineering Evaluation Request

10/26/2020

601264224

Davis-Besse Nuclear Power Tip Maintenance Notification

03/14/2020

Miscellaneous

Letter from M.

Bezilla L-20-063

Core Operating Limits Report, Cycle 21

DB-SP-03446

Decay Heat Train 1 Pump and Valve Test

Procedures

DB-SP-03446

Decay Heat Train 1 Pump and Valve Test

200694387

PM 11998 BF1183 Test

11/05/2020

200696633

MV2002B Inspect RPS/SFAS#3

08/31/2021

Work Orders

200790236

PM 12098 BF1181 Test

10/29/2020

2017-10465

Recent Hope Creek EDG OD: Failure of New Dynalco

Speed Switch

11/15/2017

2017-10873

CFR Part 21 Notice from Engine Systems Inc. for

EDG Speed Switch

10/30/2017

2019-05707

C30205 SBODG Ground Meter Low mAMPs

07/03/2019

20-01303

DH2734 Declutched and Manually Seated

2/19/2020

20-02817

IST Trending: Adverse Step Change Closed Stroke Time on

DH13A

03/31/2020

21-01311

HIC DH14B Demand Signal Continued to Display 20 Percent

Open While Set to 0 Percent Open

2/26/2021

Corrective Action

Documents

21-06239

DH14B Failed Closed

08/18/2021

FSK-M-GCB-3-1

Decay Heat Pump Recirculation Piping

ISI-SK-050

Decay Heat Coolers 1-1 and 1-2 Outline and Supports

71111.19

Drawings

ISID2-033C

Decay Heat Train 2

Inspection

Procedure

Type

Designation

Description or Title

Revision or

Date

ISIM2-233F

Low Pressure Injection System

ISIM2-234D

Containment Spray System and Spent Fuel Pool Cooling

System

10CFR21-0118

10CFR21 Reporting of Defects and Non-Compliance

24A-ISS6221

String/System Work Package

Miscellaneous

LER-2021-001

Emergency Diesel Generator Speed Switch Failure due to

Direct Current System Ground

DB-MI-04226

String Check of 24A-ISS6221/24A-ISS6221A

Diesel Generator 1-1 Speed Transmitters

DB-SP-03446

Decay Heat Train 1 Pump and Valve Test

Procedures

DB-SP-03446

Decay Heat Train 1 Pump and Valve Test

200798736

AFP 1 Quarterly Test

08/11/2021

200801345

AFP 2 Quarterly Test

09/20/2021

Work Orders

200859701

EDG 1 Speed Switch Should be Replaced

08/12/2021

20-01303

DH2734 Declutched and Manually Seated

2/19/2020

20-02817

IST Trending: Adverse Step Change Closed Stroke Time on

DH13A

03/31/2020

21-01311

HIC DH14B Demand Signal Continued to Display 20 Percent

Open While Set to 0 Percent Open

2/26/2021

Corrective Action

Documents

21-06239

DH14B Failed Closed

08/18/2021

FSK-M-GCB-3-1

Decay Heat Pump Recirculation Piping

ISI-SK-050

Decay Heat Coolers 1-1 and 1-2 Outline and Supports

ISID2-033C

Decay Heat Train 2

ISIM2-233F

Low Pressure Injection System

Drawings

ISIM2-234D

Containment Spray System and Spent Fuel Pool Cooling

System

DB-SC-03070

Emergency Diesel Generator 1 Monthly Test

DB-SP-03446

Decay Heat Train 1 Pump and Valve Test

DB-SP-03446

Decay Heat Train 1 Pump and Valve Test

Procedures

DB-SS-04201

Emergency Feedwater Pump Quarterly Test

200798736

AFP 1 Quarterly Test

08/11/2021

200799536

EDG 1 Monthly Test

08/12/2021

71111.22

Work Orders

200800408

EDG 2 Monthly Test

09/01/2021

Inspection

Procedure

Type

Designation

Description or Title

Revision or

Date

Corrective Action

Documents

CR-2019-01163

REMP Air Monitor Failure Trend

2/10/2019

CR-2021-05395

NRC Identified: Vegetation Growth Around Radiological

Environmental Monitoring Program Air Sampling Stations

07/15/2021

Corrective Action

Documents

Resulting from

Inspection

CR-2021-05419

NRC Identified: DB-HP-01702: Procedure Confusion on

Environmental Air Sampler Calibration

07/15/2021

20 Annual Radiological Environmental Operating Report

Including the Radiological Effluent Release Report

05/01/2021

Miscellaneous

Offsite Dose Calculation Manual

DB-CN-03005

Radiological Monitoring Weekly, Semi-Monthly, and Monthly

Sampling

DB-HP-01452

Air Sampler Calibration

DB-HP-01466

AVS-28A Constant Flow Air Sampler Calibration

DBPM-CHEM-

0004

Groundwater Monitoring Program

Procedures

NOP-OP-2012

Groundwater Monitoring

Self-Assessments

NUPIC Audit

Number:24879

Supplier Audit Report for ATI Environmental, Inc.

Northbrook, IL

2/18/2020

71124.07

Work Orders

200788171

Meteorological Monitoring System Primary Channel

Calibration

05/12/2021

Calculations

C-CSS-099.20-

076

Shield Building Evaluation of Interim Condition with Partial

and Limited Concrete Removal

Corrective Action

Documents

21-06142

Shield Building Shoulder 3 Work Scope

08/13/2021

Corrective Action

Documents

Resulting from

Inspection

21-06134

21 NRC SIT: Incorrect AP-913 Classification for C3621

08/13/2021

Engineering

Changes

18-0037-006

Shield Building Shoulder 3 Removal

Notification

601275302

Shield Building Evaluation Study for Knuckle Boom Crane

Loading Operation

71152

Engineering

Evaluations

Notification

601327705

Shield Building Shoulder 3: Evaluate and Provide Details for

Temporary Modification of Platform and Installation of

08/17/2021

Inspection

Procedure

Type

Designation

Description or Title

Revision or

Date

Scaffold Bearing on Second Platform

Miscellaneous

CFR 50.59

Screen 18-00648

ECP 18-0037

3