IE Insp Repts 50-324/79-13 & 50-325/79-13 on 790327-30.No Noncompliance Noted.Major Areas Inspected:Fire Protection & Safe Shutdown Sys Mods
ML19263E847
Person / Time
Site: Brunswick  
Issue date: 04/20/1979
From: Dance H, Ouzts J, Riley B
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
To:
Shared Package
ML19263E844 List:
References
50-324-79-13, 50-325-79-13, NUDOCS 7906250365
Download: ML19263E847 (3)


Text

.

UNITED STATES

$

tka stou p

NUCLEAR REGULATORY COMMISSION g

g o

REGION il

)

o E

101 M ARIETTA STREET.N.W.

.

ATLANTA. GEORGI A 30303 i

o,,,...../

Report Nos. 50-325/79-13 and 50-324/79-13 Licensee: Carolina Power and light Company 411 Fayetteville Street Raleigh, North Carolina 27602 Facility Name:

Brunswick 1 and 2 Docket Nos. 50-325 and 50-324 License Nos. DPR-71 and DPR-62 C.

Inspection at g hport,

,

(

k 20 19 Inspectors:

.

-

B. W. R' ley 4{

Date Signed

'

C n /L Shc./n

/

Ddte Signel J. E. O zts ( 20/~/f Approved by:

(b w t

_

Date Signed H. C. Dance, Section Chief, RONS Branch SUMMARY Inspection on March 27-30, 1979 Areas Inspected This routine unannounced inspection involved 46 inspector-hours onsite in the areas of fire protection and safe shutdown systems modifications.

Results Of the two areas inspected, no apparent items of noncompliance or deviations were identified.

2215 103

7906250 366i

,

... _

.

i DETAILS 1.

Persons Contacted Licensee Employees A. C. Tollison, Plant Manager

  • J. M. Brown, Superintendent - Operation
  • K. E. Enzor, Administrative Supervisor R. Groover, Construction Manager
  • D. E. Novotny, Plant Security Specialist
  • J.

T. Parlier, Project Engineer R. Porterfield, Fire Marshall

  • W. L. Tripplett, Engineering Super isor
  • W.M. Tucker, Superintendent-TechnicalandAdmi$strative
  • R. M. Poulk, NRC Coordinator Other Organizations
  • J. D. Powell, Burns Security Four UEC engineers were also contacted.

UShTC

  • D.

E. Moore, Inspector

  • Attended exit interview 2.

Exit Interview The inspection scope and findings were summarized on March 30, 1979, with those persons indicated in Paragraph 1 above.

3.

Licensee Action on Previous Inspection Findings Not inspected.

4.

Unresolved Items Unresolved items were not identified during this inspection.

\\

/

5.

Fire Protection aad Safe Shutdown Systems Features

'/

The inspectors reviewed selective records and visually verified the completion status of commitments made to NRR for startup of Unit 1.

The reviewandinspectionineJbdedasamplingofworkandrecordscoveredin about seventeen modificatf 6n work packages.

I 2215 104

..

..

.

.

2-The inspectors determined that approved written procedures were utilized as appropriate in the areas of installation checks, flush and hydro of systems and acceptance testing.

The inspectors also determined that the licensee was in the process of revising operating and surveillance test procedures as appropriate to accomodate new or modified systems and Technical Specifications.

Installation and construction work is more than 90 percent completed.

Work remaining included the installation of some piping and deluge valves for sprinkler systems. Functional testing of some systems and a majority of the completed work packages have not been reviewed by the operations department.

The licensee expects all committed modifications to be completed prior to the startup of Unit 1 on approximately April 7,1979. Completion of these modifications will be verified later by NRC. The review of completed work package records will be reviewed by NRC inspectors at subsequent inspections.

Within the areas inspected no items of noncompliance or deviations were identified.

6.

General I

The inspectors determined that the following items relating to Unit startup were in process or close to completion.

a.

Torus to reactor building vacuum breakers modification Reference LER 1-78-82 b.

Feedwater pipe whip restraint modification in drywell. Reference LER 2-79-007 Miscellaneous pipe support modifications. Reference LER 1-78-92 c.

7.

Previous Unresolved Item Inspection Report 50-324/79-7 identified at unresolved item (324/79-07-02)

concerning apparent missing record of performance of PT 6.1 for April 1978.

The licensee had since found the record and the inspector reviewed as satisfactory PT 6.1 for April 1978. This item is closed.

2215 105

___

.

3