i Lewis Sumna Southun Nuclau Vice President Opusting Company. Inc.

Hatch Pmject Supprart 40 innness Parkway Post ( .n.e Box 1295 Birmingham. Alabama 35201 Tel 205 992.7279 Fax 205 992.0341 SOUTHERN h December 3, 1997 COMPANY re h rededd

Docket Nos. 50-321 HL-5530 50-356 U. S. Nucle r Regulatory Commission ATTN: Documer. Control Desk Washington, D. C. .:0555 Edwin I. Hatch Nuclear Plant 10 CFR 50, Appendix E, Section VI. 3. a.

Notification of Changes to Emergency Resnonse Data Systen1 Gentlemen:

In accordance with 10 CFR 50, Appendix E, Section VI. S. a, a description of changes to the Emergency Response Data System (ERDS) data point libraries is being provided in the attachment in the format required by NUREG-1394, Revision 1. The changes indicated for Unit I were implemented on November 16,1997 as a result ofinstalling a new power range neutron monitoring system The changes indicated for Unit 2 are being made in the interest of consistency of data presentation between the two units. Should you have any questions, please adsise.

Sincerely,

/ , C dem D&s&

H. L. Sumner, Jr.

OCV/eb

Enclosure:

Data Point Library Reference File cc: Southern Nuclear Operating Company II!!!0fll0!!Illlill00lll0llIll@

Mr. P. H. Wells, Nuclear Plant General Manager

"~~~"""*""""'"'""'"'

NORMS U. S. Nuclear Regulatory Commission. Washington. D. C.

Mr. L. N. Olshan, Project Manager - Hatch f

U. S. Nuclear Recidatory Commission. Region 11 \

Mr. L. A. Reyes, Regional Administrator g g C.] ?. Mr. B. L. Holbrook, Senior Resident Inspector - Hatch 971209M733 971203 PDR ADOCK 05000321 F PDR

Enclosure Table of Changes to ERDS Data Point Library E. I. Hatch Unit 1 NRC - EMERGENCY RESPONSE D ATA SYSTEM .

DATA POINT LIBRARY A-44047 Rev. 03 l Sensoridentification:

14. Emuent Gas Rad (Main Stack Rad.) IDIl RIS-K600A Narrow 1D11-P007 Wide (Kaman) 1D11 RIS-K600B
15. Emuent Liquid Radiation (Radwaste Emuent Radiation) IDi1-RIS-K604
16. Emuent Liquid Radiation (PSW Emuent Radiation) ID11 RIS-K605
17. Emuent Gas Rad (Rx Building Stack Radiation) 1D11 RIS-K619A Narrow IDIl P007 Wide (Kaman) 1D11-RIS-K619B
18. DrywellRadiation A 1D11 K621 A 19.~ Hydepn Concentrafon (H2) 1P33-P601A 1P33-P601B
20. Drywell Radiation B IDIl-K621B
21. Reactor Pressure IB21-PIS-N690A IB21 PIS-N690D
22. N1 Power Range (APRMS - AVE Pwr) IC51-RIS-K615A

' IC51 RIS-K615B IC51-RIS K615C IC51-RIS-K615D

23. Oxygen Concentration (O2) IP33-P601A IP33 P601B
24. NI Source Range (SRM Average Reading; IC51-RIS-K600A IC51 RIS-K600B IC51-RIS K600C IC51-RIS-K600D 3 ii HL-5530 E-1

Enclosure l - Table of Changes to ERDS Data Point Library i

E. I Hateh Unit 1 22 of 30 NRC - EMERGENCY RESPONSE DATA SYSTEM DATA POINT LIBRARY A-44047 Rev. 03 l Date: 11/16/97 l

Reactor Unit: HTl Data Feeder: N/A NRC ERDS Parameter: NI POWER RNG Point I.D.: APRM Plant-Specific Point

Description:

APRM AVERAGE READING - % POWER Generic / Condition

Description:

NUC INST PWR RNG Analog / Digital: A Engineering Units or Digital States:  %(PERCENT)

Engineering Ihits Conversion: 1% = 1 PERCENT POWER Minimum Instrument Range: 0 Maximum Instrument Range: 125 Zero Re&rence Point: N/A Reference Point Notes: 124 FISS CHMBRS AVERAGED BY 4 APRMS l

Proc or Sens: P Number of Sensors: 4 l

How Processed: NUMERICAL AVERAGE OF AVAILABLE APRMS I Sensor Locations: FISS CHMBR IN 4 CORE QUADS AT 4 HEIGHTS Alarm or Trip Setpoints: SCRAM = FLOW BIAS; CLAMP = 115.5%; 120%; 20% HI NI Detector Power Supply Cut-off Power Level: DOWNSCALE = 3%

NI Detector Power Supply Tum-on Power Level: GREATER THAN 3%

Instrument Failure Mode: LOW = 3%; .LE.16 LPRMS; POWER l

Temperatw Cornpensation For DP Transmitters: N Level Reference Leg: N/A Unique System

Description:

APRM READINGS ARE NUMERICALLY AVERAGED FOR VALUE. QUAL TAGS USED = 0; =2(LESS THAN 3 APRMS AVAIL AND READING NOT AT l TRIP POINT); =3 NO APRMS AVAIL; =6(APRMS AVERAGE POWER.GE.

SET POINT) TRIP SET POINTS ARE BIASED IN THE RUN MODE FOR RECIRC FLOW; CLAMP AT I15.5%, TIME DELAY FOR THIS TRIP.

El POWER TRIP (NO BIAS, NO DELAY) = 120%. UNIT OUT OF RUN MODE SET POINT = 20%. NO QUALITY TAG FOR 120% TRIP.

HL-5530 E-2

Enclosure Table ofChanges to ERDS Data Point Library E.1. Hatch Unit 2 22 of 30 NRC - EMERGENCY RESPONSE DATA SYSTEM DATA POINT LIBRARY A-51672 Rev. 05 l Date: 11/16/97 l

Reactor Unit: HT2 Data Feeder: N/A NRC ERDS Parameter: NI POWER RNG Point I.D.: APRM Plant-Specific Point

Description:

APRM AVERAGE READING - % POWER Generie/ Condition

Description:

NUC INST PWR RNG Analog / Digital: A Engineering Units or Digital States:  %(PERCENT)

Engineering Units Conversion: 1% = 1 PERCENT POWER Minimum Instrument Range: 0 Maximum Instrument Range: 125 Zero Reference Point: N/A Reference Point Notes: 12 + FISS CHMBRS AVERAGED BY 4 APRMS

^

Proc or Sens: P Number of Sensors: 4 How Processed: NUMERICAL AVERAGE OF AVAILABLE APRMS Sensor Locations: FISS CHMBR IN 4 CORE QUADS AT 4 HEIGHTS Alarm or Trip Setpoints:

SCRAM = FLOW PIAS; CLAMP = 115.5%; 120%; 20% HI l N1 Detector Power Supply Cut-off Power Level: DOWNSCALE = 3%

NI Detector Power Supply Turn-on Power Level: GREATER THAN 3%

Instrument Failure Mode: LOW = 3%; .LE.16 LPRMS; POWER Temperature Compensation For DP Transmitters: N Leve! Reference Leg: N/A

- Unique System

Description:

APRM READINGS ARE NUMERICALLY AVERAGED FOR VALUE. QUAL TAGS USED = 0; =2(LESS THAN 3 APRMS AVAIL AND READING NOT AT TRIP POINT); =3 NO APRMS AVAIL; =6(APRMS AVERAGE POWER.GE.

SET POINT). TRIP SET POINTS ARE BIASED IN THE RUN MODE FOR RECIRC FLOW; CLAMP AT I15.5%, TIME DELAY FOR THIS TRIP.

HI POWER TRIP (NO BIAS, NO DELAY) = 120%. UNIT OUT OF RUN MODE SET POINT = 20%. NO QUALITY TAG FOR 120% TRIP.

HL-5530 E-3 k _ _