05000400/LER-1989-001, :on 890116,w/plant in Mode 1,reduction of Turbine Load Ensued & Turbine Trip Occurred Due to Low Condenser Vacuum Resulting in Automatic Reactor Trip.Caused by Personnel Error.Personnel Counselled
| ML18005A818 | |
| Person / Time | |
|---|---|
| Site: | Harris |
| Issue date: | 03/23/1989 |
| From: | Schwabenbauer, Watson R CAROLINA POWER & LIGHT CO. |
| To: | NRC OFFICE OF INFORMATION RESOURCES MANAGEMENT (IRM) |
| References | |
| HO-890038-(O), LER-89-001, LER-89-1, NUDOCS 8903270363 | |
| Download: ML18005A818 (8) | |
| Event date: | |
|---|---|
| Report date: | |
| Reporting criterion: | 10 CFR 50.73(a)(2) 10 CFR 50.73(a)(2)(iv), System Actuation |
| 4001989001R00 - NRC Website | |
text
REGULATORY INFORMATION DISTRIBUTION SYSTEM (RIDS)
ACCESSION NBR:8903270363 DOC.DATE: 89/03/23 NOTARIZED: NO FACIL:50-400 Shearon Harris Nuclear Power Plant, Unit 1, Carolina AUTH.NAME AUTHOR AFFILIATION SCHWABENBAUER Carolina Power 6 Light Co.
WATSON,R.A.
Carolina Power 6 Light Co.
RECIP.NAME RECIPIENT AFFILIATION DOCKET 05000400
SUBJECT:
LER 89-001-02:on 890116,plant trip due to low condenser vacuum caused by personnel error on valve lineup.
W/8 ltr.
DISTRIBUTION CODE:
IE22D COPIES RECEIVED:LTR ENCL i
SIZE:
7 TITLE: 50.73 Licensee Event Report (LER), Inci ent Rpt, etc.
NOTES:Application for permit renewal filed.
05000400 /
RECIPIENT ID CODE/NAME PD2-1 LA BECKER,D INTERNAL: ACRS MICHELSON ACRS WYLIE AEOD/DSP/TPAB DEDRO
~ NRR/DEST/ADE 8H NRR/DEST/CEB 8H NRR/DEST/ICSB 7
NRR/DEST/MTB 9H NRR/DEST/RSB 8E NRR/DLPQ/HFB 10 NRR/DOEA/EAB 11 NRR/DREP/RPB 10 NUDOCS-ABSTRACT RES/DSIR/EIB RGN2 FILE 01 EXTERNAL: EG&G WILLIAMS,S H ST LOBBY WARD NRC PDR NSIC MURPHY,G.A COPIES LTTR ENCL 1
1 1
1 1
1 1
1 1
1 1
1 1
1 1
1 1
1 1
1 1
1 1
1 1
1 2
2 1
1 1
1 1
1 4=
4 1
1 1
1 1
1 RECIPIENT ID CODE/NAME PD2-1 PD ACRS MOELLER AEOD/DOA AEOD/ROAB/DSP IRM/DCTS/DAB NRR/DEST/ADS'E NRR/DEST/ESB 8D NRR/DEST/MEB 9H NRR/DEST/PSB 8D NRR/DEST/SGB 8D NRR/DLPQ/QAB 10 NRR/DREP/RAB 10 NR~R DR~IS SIB 9A gKEG~IZ2r 02 RES/DSR/PRAB FORD BLDG HOY g A LPDR NSIC MAYS,G COPIES LTTR ENCL 1
1 2
2 1
1 2
2 1
1 1
0 1
1 1
1 1
1 1
1 1
1 1
1 1
1 1
l.
1 1
1 1
1 1
1 1
R I
h NOTE 'IO ALL "RIDS" RECIPIENIS'IZASE HELP US 'IQ REDUCE WASTEl CDNZACr 'IHE DOCUMENT CONTROL DESK ROOM Pl-37 (EXT. 20079)
IO ZLG62VZE YOUR NAME FRY DIPHKBVZIGN LISTS FOR DOCUMEÃI'S YOU DGH'T NEED!
TOTAL NUMBER OF COPIES REQUIRED:
LTTR 45 ENCL 44
NRC Form 366 (0 83)
LICENSEE EVENT REPORT (LER)
U.S. NUCLEAR REGULATORY COMMISSION APPROVED OMB NO. 31604104 EXPIRES: 8/31/88 FACILITYNAME (II SHEARON HARRIS NUCLEAR POWER-PLANT UNIT ONE DOCKET NUMSER (2) 0 5
0 0
0 g
PAGE 3
1 OF TITLE I~ I PLANT TRIP DUE TO LOW CONDENSER VACUUM CAUSED BY PERSONNEL ERROR ON VALVE LINE P EVENT DATE (5)
LFR NUMBER (6)
REPORT'ATE (7)
OTHER FACILITIES INVOLVED(8)
MONTH DAY YEAR YEAR SEQUENTIAL NVMSER
>))r rlsvislorr NUMBER MONTH OAY YEAR FACILITYNAMES DOCKET NUMBER(S) 0 5
0 0
0 0 116 8
9 8
9 0 0 1
0 2 03 238 9
0 5
0 0
0 OPERATING MODE (6)
POWER LEVEL 00) 1 00 h+PcjP/gp
)Eke@. 6'. +AN:
NAME 20A02(b) 20AOS (~ )(I) (I) 20A06(a) (I)(EI 20.405(a) (I)(ill) 20A06 (a) (I) (Iv) 20.405( ~ )(I)(vl 20.405(c) 50.36(c) (I) 50.36(c)(2) 50.73( ~ ) (2) (I) 60.73(a) (2)(ll) 50.73(a)(2)(ill)
LICENSEE CONTACT FOR THIS LER (12) 60.73(a)(2)(lv) 50.73( ~)(2)(v) 50.73(a) (2) (vll) 50.73(a) (2) (vill)IA) 50.73(a)
(2)(vill)
(8) 60.73(a)(2)(x)
THIS REPORT IS SUBMITTED PURSUANT 70 THE REOUIREMENTS OF 10 CFR (): IChech one or more of the follovflnpi (11 73.7$ (6) 73.71(c)
OTHER ISPeclfy in Ahrcrect Oelovv ond In Text, NRC Form 366AI TELFPHONE NUMBER RICHARD SCHWABENBAUER - REGULATORY COMPLIANCE TECHNICIAN AREA CODE 91 936 2-2 66 9
COMPLETE ONE LINE FOR EACI4 COMPONENT FAILURE DESCRIBED IN THIS REPORT (13I
CAUSE
SYSTEM COMPONENT MANUFAC.
TURER REPORTABLE TO NPRDS ops%(g)'))i~j
CAUSE
SYSTEM COMPONENT MANVFAC.
TURE'R REPORTABLE TO NPRDS KP~)%~'
I,@.PC.
X@
P,A ~'.ci SUPPLEMENTAL REPORT EXPECTED (14I EXPECTED SUBMISSION DATE I15)
MONTH DAY YEAR YES Ilfyer, complete EXPECTED svBfyflSSIDH DATEI NO ABSTRACT ILimitto f400 rooter, i.e., approximately lilreen rlnple opere rypevyrirten liner) (16)
The plant was operating in Mode 1,
Power Operation, at 100 percent reactor power on January 16, 1989.
Plant personnel were in the process of removing a clearance on a valve in the Auxiliary Steam Condensate Tank vent line system to the Main Condenser.
During the course of the restoration a direct vent path to the atmosphere from the Main Condenser was established due to a
mispositioned valve and resulted in a
rapid loss of condenser vacuum.
A reduction of turbine load ensued and a turbine trip at 1518 hours0.0176 days <br />0.422 hours <br />0.00251 weeks <br />5.77599e-4 months <br /> due to low condenser vacuum.
The turbine trip was immediately followed by an automatic reactor trip and a plant shutdown.
The Auxiliary Feedwater System actuated on Steam Generator lo-lo level to maintain water levels and the Main Steam Isolation Valves were closed to limit plant cooldown and the plant was stabilized in Mode 3, Hot Standby.
The
cause
of the event was personnel error in not having a shift foreman clearance on a
manual valve which was required to be in an abnormal position, and providing insufficient restoration details for the proper valve lineup.
Corrective Actions include:
the appropriate personnel have been counselled, the event has been discussed stressing the need for good working practices, a shift foreman clearance placed on the manual valve, and repair to the motor operated valve will be completed.
There were no safety consequences as a
result of this event as all plant systems functioned as required with the exception of the Turbine Driven Auxiliary Feedwater Pump which tripped after 15 seconds of operation.
This event is being reported in accordance with 10CFR50.73(a)(2)(iv) as an Engineered Safety System Feature and Reactor Protection System actuation.
NRC Form 366 FS 83) 8903270363 890323 PDR AD( (CK 050064(.')0 PDC
NAC Foim 300A (943)
LICENSEE EVENT REPORT (LER) TEXT CONTINUATION U.S, NUCLEAR REOULATOAYCOMMISSION APPROVED OMS NO. 3(50&100 EXPIRES: 8/31/88 FACILITYNAME (11 DOCKET NUMBER (2)
LER NUMSEA 10)
~AOE (31 SHEARON HARRIS NUCLEAR POWER PLANT UNIT 1
TEXT ///moro F/Moo /F /oqvoo//, Moo /AN/'ooo//YRC FCFm 300A'Fl ((7)
DESCRIPTION
o s
o o o4 00 YEAR 8
9 50ovENT/*L Ioo2 NVMFER 001 REVISION NVM ER 02 02 OF 0 6
The plant was operating in Mode 1,
Power Operation, at 100 percent reactor power on January 16, 1989.
Plant personnel were in the process of removing a
clearance on valve 1AC-346 (EIIS:SA) which was issued to perform preventive maintenance on the operator for the valve.
Personnel were not aware that valve 1AC-346 was not fully shut and proceeded to open valve lAC-345 (EIIS:SA)
(refer to attached sketch) before going to Motor Control Center (MCC)-IE31 (EIIS:ED) to restore power to the valve operator for lAC-346.
Opening valve 1AC-345 allowed atmospheric pressure to enter the Auxiliary Steam Condensate tanks (EIIS:SA) vents through valve 1AC-346 which was approximately one half open.
Valve lAC-349 (EIIS:SA) opened in an attempt to maintain the required back pressure on the Auxiliary Steam Condensate tanks.
This resulted in a
direct path from the atmosphere to the Main Condenser (EIIS:SG).
A rapid loss of condenser vacuum followed and Turbine Generator (EIIS:TA) load decreased and at 1518 hours0.0176 days <br />0.422 hours <br />0.00251 weeks <br />5.77599e-4 months <br /> the turbine tripped on low condenser vacuum.
The turbine trip was immediately followed by an automatic reactor trip and a
plant shutdown.
The following is a sequence of events leading to the trip'.
HOUR EVENT 14:50 15:10 15:14 Removal of clearance authorized.
Approximate time of opening valve 1AC-345.
Initial reports of turbine load decreasing with reactor power remaining nearly constant.
An Auxiliary Operator reported a rapid increase in condenser sight glass level (63" to 68" in a
few moments).
The Load Dispatcher reported a plant load decrease.
15:14:46 High hotwell level alarm.
P 15:15:15 Low Condenser Vacuum Alarm.
15:15:37 High Hotwell Temperature Alarm.
Operators attempted to control turbine load by taking manual control.
Load on the DEH system remained stable.
15:18:15 Turbine trip on low vacuum.
15:18:15 Reactor trip due to turbine trip.
15: 23 Approximate time that condenser level reached 100 inches and condenser pressure reached 14.3 psi.
15:40 Radwaste Control Operator removed the clearance tag from the control switch for 1AC-346 and placed the switch to "SHUT."
NRC FORM 300A 19831 o U S OPO'(980.0.024 530/455
NRC FRIm 3ddA (943)
LICENSEE EVENT REPORT (LER) TEXT CONTINUATION U.S. NUCLEAR REGULATORY COMMISSION APPROVEO OMB NO. 3150-0)OE EXPIRES: 8/3l/88 FACILITYNAME 0)
SHEARON HARRIS NUCLEAR POWER PLANT UNIT ONE TEXT I////RFS FPoco II/odvPRI, VFF FIR/R/ono/ IYRC F(Fm 355A'FI I(T)
==DESCRIPTION==DOCKET NUMBER (21 0
5 0
0 0
YEAR LER NUMBER (5)
SEOVENTIAL NVMSER REV ISION NVM ER PAGE (3) oF 0
All three Auxiliary Feedwater (AFW) Pumps (EIIS:BA) started on Steam Generator (SG)
(EIIS:TB) lo-lo level to maintain SG water levels and the Main Steam Isolation Valves (MSIV)
(EIIS:SB) were shut to prevent excessive plant cooldown.
The plant was then stabilized in Mode 3, Hot Standby.
All plant systems functioned as required with the exception of the Turbine Driven AFW pump which tripped after 15 seconds of operation.
The cause of the Turbine Driven AFW pump trip was excessive moisture in the steam supply line to the pump.
A program to periodically drain the line of moisture was instituted and Operations Surveillance Test (OST)-1111, Auxiliary Feedwater Pump 1X-SAB Operability Test Monthly Interval Modes 1-2-3, was performed and successfully completed to verify the operability of the pump.
A normal plant start up followed and the plant was returned to service at 0601 hours0.00696 days <br />0.167 hours <br />9.937169e-4 weeks <br />2.286805e-4 months <br /> on January 17, 1989.
CAUSE
Valve lAC-346 has a history of problems that must be considered in order to understand this event.
A valve seat leak was reported by Work Request (WR) 87-ALAT1 on May 1,
- 1987, and a torque switch problem documented by WR 86-ABCF2 on January 21, 1986.
These job orders are not complete.
WR 88-AQSYl was issued on July 8,
- 1988, because the valve would not fully shut and gave an intermediate position indication.
Operators found that a slight movement of the manual operator was sufficient to gi've a fully shut indication so the problem was assumed to be related to the limit switches.
A deficiency tag (011882) was placed on the operating switch in the Radwaste Control Room.
On August 30,
- 1988, a
Caution Tag (RW88-086) was placed on the control switch.
This tag instructed operators to shut 1AC-345 since 1AC-346 would not fully shut.
1AC-345 is designated a "Normally Open" valve by Operating Procedure (OP)-130.01, Auxiliary Steam and Condensate System Operating Procedure.
On October 30,
- 1988, valve 1AC-346 was added to the Radwaste Control Room Plant Programs (PLP)-702, Independent Verification, log (entry RW88-071) as requiring independent verification.
PLP-702 does not require independent verification of valve lineups for the Auxiliary Steam and Condensate System.
The use of a
PLP-702 log entry was elective in this case.
This entry was deleted on December 18,
- 1988, when the plant shutdown for repairs and a
subsequent entry was not made when the plant was returned to service.
WR 88-KXY395 was issued in September of 1988 to conduct routine maintenance on the Limitorque valve operator for 1AC-346. This maintenance was scheduled due on September 23,
- 1988, and overdue February 8,
1989.
Clearance RW89-63 was requested and issued on January 16,
- 1989, to accomplish WR 88-KXY395.
The work to be performed was routine lubrication of the valve operator.
NRC FORM ESSA (983)
RU.S GPO.1988 0-82E 538/455
NRC Form 355A I94I3l LICENSEE EVENT REPORT (LERI TEXT CONTINUATION U.S. NUCLEAR REGULATORY COMMISSION APPROVED OMS NO. 3150&104 EXPIRES; 8/31/88 FACILITYNAME 111 SHEARON HARRIS NUCLEAR POWER PLANT UNIT ONE TEXT ///more 4Peee lf/el/rkerL we //o/N/4/ F//IC Frem 3584'4/ IIT)
==CAUSE==DOCKET NUMSER 12l o
s o
o o
4 0
LER NUMSER ISI YEAR
.'re< sEQUENT/AL ++ip REyrsroN NvM TR To.f NUM eR 89 00 1 0 2
~AOE 13) 0 6
0 4 QF When clearance RW89-63 was prepared the placement sequence was clearly specified but the existence of a caution tag on valve lAC-346 was not noted on the clearance and no restoration sequence was specified.
The lubrication maintenance was conducted in a routine manner and should not have affected valve position.
When the clearance was
- removed, the restoration sequence consisted of verbal instructions by the Radwaste Control Room to a
Radwaste operator.
As a
- result, 1AC-345 was opened to place it in the position required by OP-130.01 before any attempt to shut or verify the position of lAC-346.
This caused the loss of condenser vacuum since 1AC-346 was in an undetermined intermediate position.
There are several factors that contributed to this event:
a.
When the Caution Tag was initially prepared for 1AC-346, as a minimum a
Caution Tag should have also been placed on lAC-345.
In retrospect a
shift foreman clearance on 1AC-345 would have been preferable.
b.
Personnel involved with preparing the clearance did not adequately research the clearance.
This research would have revealed the need for 1AC-345 to remain shut.
C ~
The restoration was not correct in that the position'f 1AC-346 was not verified prior to removing the clearance and repositioning 1AC-345.
The plants standard practice for motor operated valves is to restore
- power, confirm correct position or use the control switch to reposition, and then position other manual isolation valves.
ANALYSIS:
There were no safety consequences as a result of this event.
All plant systems with the exception of the Turbine Driven AFW pump responded as required and the plant was stabilized in Mode 3 at normal no load temperature and pressure.
Normal SG water levels were restored with the Auxiliary Feedwater System.
The Turbine Driven AFW pump tripped after 15 seconds of operation due to excessive moisture in the steam supply line to the pump.
A program to periodically drain the line of moisture was instituted and OST-llll performed to verify operability of the pump.
This event is being reported in accordance with 10CFR50.73(a)(2)(iv) as an Engineered Safety System Feature (EIIS:JE) and Reactor Protection System (EIIS:ID) actuation.
NRC FORM 3444 19413 I e U.S GPO,1985 0 824 53S/455
/943 I LICENSEE EVENT REPORT (LER) TEXT CONTINUATION U.S, NUCLEAR REGULATORY COMMISSION APPROVED OMS NO. 3I50M104 EXPIRES: 8/3I/88 FACILITYNAME (II SHEARON HARRIS NUCLEAR POWER PLANT UNIT ONE DOCKET NUMBER Ill YEAR LER NUMSER (8)
IxcE Sf OVS NTIAL Ir>)X NVM SR aX/ RfVISION NVM fFI PAGE IS)
TEXT /// mare u>>ce */II/rkerLIr>>~ H/IC forrrr 355A'F/ Ill/
ANALYSIS:0 5
0 0
0 4
0 0 Q
9 0 0
1 0
2 0. 5o'0 6
Another event reported involving an incorrect valve restoration lineup and resulting in a plant trip, was reported in LER-87-041-00.
CORRECTIVE ACTION/ACTION TO PREVENT RECURRENCE:
1.
The applicable personnel involved were counselled and disciplinary action was taken.
2.
The event was discussed by the Operations Manager in a Shift Foreman meeting.
The.meeting stressed:
a) the necessity for adequately researching clearances, b) the necessity for periodically observing activities being performed outside the control room to insure procedures and good working practices are being implemented
- properly, and c) the necessity of using a shift foreman clearance when manipulation of a
component could result in a challenge to the plant.
3.
A shift foreman clearance was placed on valve 1AC-345 pending the repair of 1AC-346.
4.
The repair of valve 1AC-346 will be completed.
NRC FORM Sddo ISA) e U.S GPO.1085-0824 538/f55
I
~
AuxiliarySteans Candensate System Return Yenting Path Almosphere 1AC-346 6
tI piping I AC-345 PY-0185A 1 ox Hain 8"
Condenser pl ping Connecllon 1hC-3 17 lhC-349 1 AC-350
<<169 3AC-312 Vf.P.O.
huxillar y Sleam Condenselo Tank 1-4h (2000 gal) 3AC-313 W.P.D.
Auxiliary Sleam Condensolo Tank 1-40 (2000 gal) 3AC-316 B.A.B.
Auxiliary Steam Condensale Tank 1-AC (220 goi)
O~ Halnlalns AuxiliaryCondensale Syslem backpreseure al 1 ps'
CRATE Carolina Power & Light Company J
HARRIS NUCLEAR PROJECT P.O.
Box 165 New Hill, NC 27562 NAR 25 1989 File Number.'SHF/10-13510C Letter Number.'O-890038 (0)
U.S. Nuclear Regulatory Commission ATTN:
NRC Document Control Desk Washington, DC 20555 SHEARON HARRIS NUCLEAR POWER PLANT UNIT 1
DOCKET NO. 50-400 LICENSE NO. NPF-63 LICENSEE EVENT REPORT 89-001-02 Gentlemen.'n accordance with Title 10 to the Code of Federal Regulations, the enclosed Licensee Event Report is submitted.
The original report fulfilled the requirement for a written report within thirty (30) days of a reportable occurrence and is in accordance with the format set forth in NUREG-1022, September 1983.
Revision 1 was submitted due to a change in the reported status of valve repair.
Revision 2 is being submitted due to a
page sequence/duplication error.
Very truly yours, Q+P R. A. Watson Vice President Harris Nuclear Project RJS:acm Enclosure cc'.
Mr. R. A. Becker (NRR)
Mr. W. H. Bradford (NRC SHNPP)
Mr. S.
D. Ebneter (NRC RII)
MEM/LER-89-001/1/Osl