05000275/FIN-2010006-04
From kanterella
Jump to navigation
Jump to search
Finding | |
---|---|
Title | Untimely and Inadequate Corrective Actions for the Emergency Diesel Generators |
Description | The team identified a noncited violation of 10 CFR Part 50, Appendix B, Criterion XVI, Corrective Action, with two examples for the failure of the licensee to promptly identify and correct nonconforming conditions related to the emergency diesel generators meeting the design basis. The first example resulted from the failure to identify that instrument inaccuracies were not accounted for in the bounding calculations. The second example involved the failure to identify that the worst case loading calculations exceeded the emergency diesel generator operating load limit. The failure to promptly identify and correct the design deficiencies associated with the emergency diesel generators was a performance deficiency. This finding is greater than minor because it was associated with the design control attribute of the Mitigating Systems Cornerstone and affected the cornerstones objective to ensure the availability, reliability, and capability of systems that respond to initiating events to prevent undesirable consequences. In accordance with Inspection Manual Chapter 0609, Significant Determination Process, the team performed a Phase 1 analysis to analyze the significance of this finding and determined the finding is of very low safety significance because the condition was a design or qualification deficiency confirmed not to result in loss of operability or functionality, did not represent an actual loss of safety function of the system or train, did not result in the loss of one or more trains of nontechnical specification equipment, and did not screen as potentially risk significant due to a seismic, flooding, or severe weather initiating event. The finding had a crosscutting aspect in the area of human performance, decision making, because the licensee did not use conservative assumptions in the decision making process or conduct an adequate effectiveness review to verify the validity of the underlying assumptions for a safety-significant decision |
Site: | Diablo Canyon |
---|---|
Report | IR 05000275/2010006 Section 4OA2 |
Date counted | Sep 30, 2010 (2010Q3) |
Type: | NCV: Green |
cornerstone | Mitigating Systems |
Identified by: | NRC identified |
Inspection Procedure: | IP 71152 |
Inspectors (proximate) | R Taylor T Brown M Hay A Fairbanks S Hedger |
CCA | H.14, Conservative Bias |
INPO aspect | DM.2 |
' | |
Finding - Diablo Canyon - IR 05000275/2010006 | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Finding List (Diablo Canyon) @ 2010Q3
Self-Identified List (Diablo Canyon)
| |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||