Finding | |
|---|---|
| Title | Untimely Conective Actions for Repeated Control Room Fan Failures |
| Description | The inspectors identified an NCV of 10 CFR 50, Appendix B, Criterion XVl, Corrective Action, because Entergy personnel did not promptly correct an adverse condition related to the safety-related control room ventilation fan. Specifically, between September 1, 2O1O and September 27 ,2011, inspectors identified that Entergy personnel did not promptly implement corrective actions to revise maintenance procedures to include post maintenance belt tensioning after a break-in period which resulted in additional failures of the 21 central control room fan (CCRF) while in service. Entergy staff revised scheduled work orders to perform post-maintenance break-in checks. Entergy personnel entered this issue into the CAP as CR- |
| Site: | Indian Point |
|---|---|
| Report | IR 05000247/2011005 Section 1R04 |
| Date counted | Dec 31, 2011 (2011Q4) |
| Type: | NCV: Green |
| cornerstone | Barrier Integrity |
| Identified by: | NRC identified |
| Inspection Procedure: | IP 71111.04 |
| Inspectors (proximate) | B Bickett J Furia J Noggle M Catts M Gray O Ayegbiso S Mccarver T Fish |
| CCA | P.3, Resolution |
| INPO aspect | PI.3 |
| ' | |