Telecopy Ro:On 740806,torus Water Level Exceeded Tech Spec Limits.Caused by Failure of Level Instrumentation.Proper Level Restored
ML20084L655
Person / Time
Site: Dresden Constellation icon.png
Issue date: 08/07/1974
From: Stephenson B
COMMONWEALTH EDISON CO.
To: James Keppler
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION III)
Shared Package
ML20084L651 List:
References
NUDOCS 8305230595
Download: ML20084L655 (2)


Text

- - . _ . _ - _ . - _ . - _. . . - - - . - _ - - - - _ - _ - , - - - _ - . . . - _ .

i

.I i

l l

i 1

(- L I k EJJ RJ ' '

4

w Western union ele ram -

R l ! D * '. . ...

TELEGRAMS (OTHER THAU MOSET ORDERSJ:': i f

Ts PHYSICAL DELIVE~sY rcc eted" 3U~['C '

VEA118(1124)(1-Of5Ff2W219fFD 08/07/74 11ET ~ ghbla d 105 IPMVEIJ MVN . Sold l Ey_,$ E .

I K .

$ ~Ik@ES 10055 IDVE MORRIS IL> 15a 03-07; 850A CDI ".,eMD!, o r I,l ,i -. 1 i

PM5 JnMES KEPPLER REff0NAFDIVEdioWATE"0f 5E61RITORY -

~

I3fOPEdATIONREGION4USATOMIC~ENEh6Y'C0MM'ISSIONWUX 799 800SEVELI RD l}bg GLEN ELLYN IL 60157

$g SUBJECT DPR-19 DRESDEN NUCLEAR POWin SIATION UNIT 2 8 IHIS WILL CONFIRM A CONVEhSATION WIIH F MAURA 0F YOUR OFFICE AT

,1615 HOUh8 THIS DATE CONCERNING TORUS WATER LEVEL IN EXCESS OF

(

mhIECHINCALSPECIFICATIONoLIMITSDUETOFAILUAEOFLEVELINSTRUMEN-TATION. AT 1557 6 AUGUST 1974 A T0RUS LEVEL ALARM RECEIVED A A 'IIME ,

, OF NORMAL INDICATED TORUS LEVEL GENERATED-A REQUEST TO CALLIBRATE THE i

nr.mdQfeUS LEVEL TRANSMITTER. THE CALLIBRATION WAS IN ERROR AND AS A f*

4 l

l l

i 1

4 l

!, < 4

  • Tele ram '

V Eftern Unionau uL  :

e IEStA.T THE SPERATOR THOUGHT WATER LEVEL VAS T00 HIGH AND PLMPED DeWN -

TORUS LEVEL AT 2400 HOURS 10 A LEVEL BELOW THE MINIMUM REQUIRED.

THE POSSIBILITY OF ERROER BECAME APPARENT ABOUT 1515 6 AUGUST AND 1

,' WAS CONFIRMED ni 1600 TO BE A APPROXIMATELY -7. INCHES OR 2 INCHES i i BELOW MINIMUM LEVEL OF -5 INCHES On APPRonIMATELY 2 PERCENT LESS THAN REQUIRED VOLUME. IMMEDIATELY TOOK MEASURES TO RESTORE LEVEL:

FROM'SIORA0E TANK. LEVEL RESTORED AI 2000. I f'

bb STEPHEN 60N SUPERINTENDENT DRESDEN NUCLEAR POWER STATION i >

i COMMONVEALTH EDISON CO RT 1 MORRib IL 60450 Q h  !