ML18052A894

From kanterella
Revision as of 13:17, 3 February 2020 by StriderTol (talk | contribs) (Created page by program invented by StriderTol)
(diff) ← Older revision | Latest revision (diff) | Newer revision → (diff)
Jump to navigation Jump to search
Proposed Tech Spec Changes to Table 3.22.1 Re Fire Detection Instrumentation
ML18052A894
Person / Time
Site: Palisades Entergy icon.png
Issue date: 03/09/1987
From:
CONSUMERS ENERGY CO. (FORMERLY CONSUMERS POWER CO.)
To:
Shared Package
ML18052A893 List:
References
NUDOCS 8703120444
Download: ML18052A894 (3)


Text

e

.* *~

ATTACHMENT*

Consumers Power Company Palisades Plant Docket 50-255 PROPOSED TECHNICAL SPECIFICATIONS PAGE CHANGES March 9, 1987 2 Pages T'SPO 28 7-0 209A-NL04 /NL02

TABLE 3.22.1 NUMBER OF TYPE OF MINIMUM FIRE DETECTION ZONE DETECTORS DETECTORS INSTRUMENTS OPERABLE

1. Diesel Generator Room 1-1, Col J~28 1 Water Flow Sw 1
2. Diesel Generator Room 1-2, Col M-28 1 Water Flow Sw 1
3. Control Room and Room 325 7 Smoke 5
4. Control Room Adjacent Offices, Rooms 324 & 320 2 Smoke 1
5. Cable Spreading Room (224) Area 8 Smoke 6
6. Refueling and Spent Fuel Area, Room 220 4 Smoke 2
7. Switchgear Room 1-D, Room 223 4 Smoke 3
8. North Penetration, Room 332 2 Smoke 1
9. Switchgear Room 1-C, Room 116A 2 Smoke 1
10. Southwest Cable Penetration, Room 250 2 Smoke 1
11. Engineered Safeguards Panel Area 3 Smoke 2
12. Stairwell Outside Engineered Safeguards Panel Area 1 Smoke 1
13. Component Cooling Pump Room 123 2 Smoke 1
14. Safeguard Area Room 4 3 Smoke 2
15. Safeguard Area Room 5 2 Smoke 1
16. Corridor 106 on 590' Elevation 6 Smoke 4
17. Charging Pump Room 104 2 Smoke 1
18. Containment, Interior North Penetration Area 3 Smoke 2 "FIRE DETECTION INSTRUMENTATION - MINIMUM INSTRUMENTS OPERABLE" 3-97 PROPOSED TSP0287-0209A-NL04/NL02

TABLE 3.22.1 (continued)

NUMBER OF TYPE OF MINIMUM FIRE DETECTION ZONE DETECTORS DETECTORS INSTRUMENTS OPERABLE

19. Containment, Interior Southwest Penetration Area 3 Smoke 2
20. Containment Instrument Air Room 3 Smoke 2
21. Auxiliary Feed Pump Room, 570' Level of 1 Smoke 1 Turbine Building
22. Battery Room 225A 1 Smoke 1
23. Battery Room 225B 1 Smoke 1
24. HVAC Equipment Rooms and Chase West Mechanical Equipment Room 1 Smoke 1 East Mechanical Equipment Room 1 Smoke 1 Duct Chase 1 Smoke 1
25. Air Handling Units V-95 and V-96 Inlet Ducts 2 Smoke 2
26. Electrical Equipment Room 4 Smoke .3
27. Technical Support Center 2 Smoke 1
28. Intake Structure, Room 136 11 Ultraviolet 7 "FIRE DETECTION INSTRUMENTATION - MINIMUM INSTRUMENTS OPERABLE" 3-97a PROPOSED TSP0287-0209A-NL04/NL02