ML18052A894

From kanterella
Jump to navigation Jump to search
Proposed Tech Spec Changes to Table 3.22.1 Re Fire Detection Instrumentation
ML18052A894
Person / Time
Site: Palisades 
Issue date: 03/09/1987
From:
CONSUMERS ENERGY CO. (FORMERLY CONSUMERS POWER CO.)
To:
Shared Package
ML18052A893 List:
References
NUDOCS 8703120444
Download: ML18052A894 (3)


Text

  • ~

ATTACHMENT*

Consumers Power Company Palisades Plant Docket 50-255

' e PROPOSED TECHNICAL SPECIFICATIONS PAGE CHANGES March 9, 1987 2 Pages T'SPO 28 7-0 209A-NL04 /NL02

FIRE DETECTION ZONE

1. Diesel Generator Room 1-1, Col J~28
2.

Diesel Generator Room 1-2, Col M-28

3.

Control Room and Room 325 TABLE 3.22.1 NUMBER OF DETECTORS

4.

Control Room Adjacent Offices, Rooms 324 & 320

5.

Cable Spreading Room (224) Area

6.

Refueling and Spent Fuel Area, Room 220

7.

Switchgear Room 1-D, Room 223

8.

North Penetration, Room 332

9.

Switchgear Room 1-C, Room 116A

10. Southwest Cable Penetration, Room 250
11. Engineered Safeguards Panel Area
12. Stairwell Outside Engineered Safeguards Panel Area 1

1 7

2 8

4 4

2 2

2 3

1 2

3 2

6 2

3

13. Component Cooling Pump Room 123
14. Safeguard Area Room 4
15. Safeguard Area Room 5
16. Corridor 106 on 590' Elevation
17. Charging Pump Room 104
18. Containment, Interior North Penetration Area TYPE OF DETECTORS Water Flow Sw Water Flow Sw Smoke Smoke Smoke Smoke Smoke Smoke Smoke Smoke Smoke Smoke Smoke Smoke Smoke Smoke Smoke Smoke MINIMUM INSTRUMENTS OPERABLE 1

1 5

1 6

2 3

1 1

1 2

1 1

2 1

4 1

2 "FIRE DETECTION INSTRUMENTATION - MINIMUM INSTRUMENTS OPERABLE" 3-97 PROPOSED TSP0287-0209A-NL04/NL02

TABLE 3.22.1 (continued)

FIRE DETECTION ZONE

19. Containment, Interior Southwest Penetration Area
20. Containment Instrument Air Room
21. Auxiliary Feed Pump Room, 570' Level of Turbine Building
22. Battery Room 225A
23. Battery Room 225B
24. HVAC Equipment Rooms and Chase West Mechanical Equipment Room East Mechanical Equipment Room Duct Chase
25. Air Handling Units V-95 and V-96 Inlet Ducts
26. Electrical Equipment Room
27. Technical Support Center
28. Intake Structure, Room 136 NUMBER OF TYPE OF DETECTORS DETECTORS 3

Smoke 3

Smoke 1

Smoke 1

Smoke 1

Smoke 1

Smoke 1

Smoke 1

Smoke 2

Smoke 4

Smoke 2

Smoke 11 Ultraviolet "FIRE DETECTION INSTRUMENTATION - MINIMUM INSTRUMENTS OPERABLE" 3-97a TSP0287-0209A-NL04/NL02 MINIMUM INSTRUMENTS OPERABLE 2

2 1

1 1

1 1

1 2

.3 1

7 PROPOSED

..